Western Telematic PTS-9CM20-2, PTS-8NE15-1 User Manual

Page 1
PTS Series
Automatic Power Transfer Switch
Models Covered:
PTS-8NE15-1
PTS-9CM20-2
WTI Part No.: 14124
Rev.: A
Page 2
Warnings and Cautions:
Installation Instructions
Secure Racking
If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require further
evaluation by Certication Agencies. The following items must be considered.
1. The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air ow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 55°C. Consideration should be given to the maximum rated ambient.
2. Installation should be such that a hazardous stability condition is not achieved due to uneven loading.
Input Supply
Check nameplate ratings to assure there is no overloading of supply circuits that could have an effect on overcurrent protection and supply wiring.
Grounding
Reliable earthing of this equipment must be maintained. Particular attention should be given to supply connections when connecting to power strips, rather than direct connections to the branch circuit.
No Serviceable Parts Inside; Authorized Service Personnel Only
Do not attempt to repair or service this device yourself. Internal components must be serviced by authorized personnel only.
• ShockHazard-DoNotEnter
Disconnect Power
If any of the following events are noted, immediately disconnect the unit from the outlet and contact qualied service personnel:
1. If the power cord becomes frayed or damaged.
2. If liquid has been spilled into the device or if the device has been exposed to rain or water.
Two Power Supply Cables
Note that PTS Series units feature two separate power circuits, and a separate power supply cable for each power circuit. Make certain to disconnect both power supply cables before attempting to service or remove the unit.
15-Amp "Starter" Cable
Depending on your specic model, PTS Series units may be shipped with either one or two 125 VAC, 15 Amp "Starter" Cables. These Starter Cables will allow you to connect the PTS to power for bench testing and initial start up and are adequate for applications that only require 15 Amps. For 20-Amp power switching applications, please refer to the WTI Power Cable guide supplied with the unit, or use appropriate 20-Amp cables.
Units with Attached Power Supply Cable(s)
For units with xed Power Cords the socket-outlet shall be installed near the equipment and shall be easily accessible.
Page 3
1. Introduction
This Quick Start Guide describes the installation procedure for the PTS series hardware. The PTS is essentially a power fallback switch, that automatically switches power from a primary input to a secondary input when power to the primary input is lost or interrupted.
2. Hardware Installation
Apply Power to the MPC
Refer to the warnings and cautions at the beginning of this guide and the power rating nameplate on the PTS back panel, and then connect the unit to two appropriate power sources. For units with detachable power input cables, connect the power input cables to the power inlets, install the cable keepers, and then connect the primary power input cable to your primary power supply and the secondary power input cable to your secondary power supply. Refer to the table below for information concerning power requirements and maximum loads.
Model No.
PTS-8NE15-1 15 Amps 100 to 120 VAC 12 Amps 8 ea. NEMA 5-15R 12 Amps*
PTS-9CM20-2 20 Amps 200 to 240 VAC 10/16 Amps 8 ea. IEC-60320-C13
Input
Feeds (x2)
Input
Voltage
Max. Load per Outlet
Outlets
1 ea. IEC-60320-C19
Max. Load
per Unit
16 Amps*
* In accordance with UL requirements, this value has been de-rated to 80%.
Power Input Feeds:
PTS-8NE15-1: Two (2) IEC-60320-C14 Inlets.
PTS-9CM20-2: Two (2) IEC-60320-C20 Inlets.
Notes:
• After connecting your power cables to the PTS unit, make certain to secure the cables in order to prevent accidental disconnection.
• PTS-1 series units are designed for switching power input lines that are typically 120 VAC. If a power input lower than 120 VAC is connected to a PTS-1 unit, then power switching features will not function correctly.
• PTS-2 series units are designed for switching power input lines that are typically 240 VAC. If a power input lower than 240 VAC is connected to a PTS-2 unit, then power switching features will not function correctly.
Page 3
Page 4
3. Operation
When properly installed, the PTS will automatically switch power from the primary input to the secondary input when the power to the primary input is interrupted. After switching from primary to secondary, the PTS will also switch power back to the primary input when power to the primary input is restored. Note that the "Input Power" LEDs on the PTS front panel will light to indicate which power input is active. If the "Primary" LED is lit, this indicates that the Primary Power source is active; if the "Secondary" LED is lit, this indicates that the Secondary power source is active.
FCC Part 15 Regulation
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Plug the equipment into an outlet on a circuit that is different from the one used by the receiver.
• Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation of this device is subject to the following conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference that may cause undesired operation.
WARNING:Changesormodicationstothisunitnotexpresslyapprovedbythe partyresponsibleforcompliancecouldvoidtheuser’sauthoritytooperatethe equipment
Industry Canada - EMI Information
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
5 Sterling • Irvine • California 92618 (949) 586-9950 • Toll Free: 1-800-854-7226 Fax: (949) 583-9514 • http://www.wti.com