Western Airconditioning FUSIO W 5, FUSIO W 8, FUSIO W 11, FUSIO W 6, FUSIO W 14 Technical Manual

...
Page 1
Technical Manual
Western Airconditioning B.V. Tel +31 (0) 332477800 www.western.nl
FUSIO W
Water/water
Heatpump
Page 2
climate
cold heat
Table of contents
Basic concepts 16
Basic concept 01.00.10 16 Basic concept 01/01/2010 17 Basic concept 01.20.10 18 Basic concept 01.21.10 19 Basic concept 02.00.10 20 Basic concept 02.20.10 21 Basic concept 02.30.10 22 Basic concept 02.40.10 23
Extensions 24
Extension 1: Heating circuit 1 mixed and consumer unmixed 24 Extension 2: 2 heating circuits mixed 25 Extension 3: Hot water storage tank with solar circuit 26 Extension 4: Swimming pool heater 27
Extension 5: Free cooling for GK 01. ... or GK 04. ... 28
Extension 6: Free cooling for GK 02. ... or GK 05. ... 29
Extension 7: Cascade 30 Extension 7: Cascade with DHW 31 Extension 20: Heating circuit mixed 32 Extension 21: Heating circuit mixed and consumer unmixed 33 Extension 22: Heating circuit mixed and DHW heating 34 Extension 23: Heating circuit mixed and DHW heating 35
Terminal diagrams 36
Terminal diagram for basic concept 01.00.10 36 Terminal diagram for basic concept 01/01/2010 37 Terminal diagram for basic concept 01.20.10 38 Terminal diagram for basic concept 01.21.10 39 Terminal diagram for basic concept 02.00.10 40 Terminal diagram for basic concept 02.20.10 41 Terminal diagram for basic concept 02.30.10 42 Terminal diagram for basic concept 02.40.10 43
Technical data 4
FUSIO W 5 - FUSIO W 8, brine/water with Optiplus controller 4
Dimension drawings 8
FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller 6
FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller 9
FUSIO W 5 - FUSIO W 8, brine/water Optiplus controller 8
Power curves 10
FUSIO W 5 10 FUSIO W 6 11
FUSIO W 11 13 FUSIO W 14 14 FUSIO W 18 15
FUSIO W 8 12
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 3
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 4
climate
cold heat
Standard performance data (as per EN 14511) W 35 W 50 W 35 W 50 W 35 W 50
Heat output at B0 kW 5.0 4.6 5.9 5.5 7.7 7.3
COP at B0 - 4.5 3.0 4.5 3.0 4.5 3.0
El. power consumption at B0 kW 1.1 1.6 1.3 1.8 1.7 2.4
Cooling output at B0 kW 3.9 3.0 4.5 3.6 6.0 4.9
Sound
Sound power level Lwa dB(A) 39 39 43
Sound pressure level in 1 m
1)
Lpa dB(A) 24 24 28
Field of application
Heat source temperature min/max °C -6 to +20
Heat flow temperature at > B0 min/max °C +20 to +65
Heat flow temperature at B-6 min/max °C +25 to +60
Vaporiser, brine side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 0.88/1.01/1.17 1.04/1.19/1.39 1.36/1.55/1.81
Pressure drop via heat pump kPa 4/5/7 6/7/9 7/9/11
Free compression 2) kPa 57/55/53 54/52/48 50/47/43
Medium water/ethylene glycol % 75/25 75/25 75/25
Built-in brine pump A 14-1 KW A 14-1 KW A 14-1 KW
Condenser, heater side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 0.43/0.61/0.86 0.51/0.72/1.01 0.66/0.95/1.33
Pressure drop via heat pump kPa 2/4/7 3/5/9 3/5/10
Free compression 2) kPa 51/48/43 49/46/40 48/44/36
Medium water % 100 100 100
Built-in heating pump A 13-1 A 13-1 A 13-1
Dimensions/connections/miscellaneous
Dimensions D x W x H mm 700 x 530 x 1260
Total weight kg 140 140 150
Heating circuit connection AG Inch 5/4" 5/4" 5/4"
Brine circuit connection AG Inch 5/4" 5/4" 5/4"
Cooling agent/filling quantity -- / kg R-410A/1.8 R-410A/1.8 R-410A/1.9
Refrigeration oil filling quantity 0.7 0.7 1.2
Expansion vessel heater
3)
V SD 25.3 SD 25.3 SD 35.3
set upstream pressure, heating circuit p 1.0 1.0 1.0
Expansion vessel, brine circuit V SD 12.3 SD 12.3 SD 18.3
set upstream pressure, brine circuit p 0.5 0.5 0.5
Safety valve (brine/heating) p 3.0 3.0 3.0
Switching point, brine pressure controller p 0.4 0.4 0.4
Heat pump type FUSIO W 5 FUSIO W 6 FUSIO W 8
Model All in One All in One All in One
Controller Optiplus integrated integrated integrated
WPZ-test number SW-311-12-10
FUSIO W 5 - FUSIO W 8 brine/water with Optiplus controller
1) Free field value
2) Free compression is specified for highest level
3) Expansion vessel heater is enclosed from fusio w 11
4) fusio w 5 and fusio w 6 without soft starter
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Technical data FUSIO W 1/2
Page 5
Electrical data
Operating voltage power 3/ N / PE / 400 V / 50 Hz
External Abs. with el. heating insert AT 16 16 20
External Abs. without el. heating insert AT 13 13 13
Output electrical heating insert 400 V kW 2/4/6 2/4/6 2/4/6
max. machine current with el. heating insert A 14.9 15.5 16.5
max. machine current without el. heating insert A 6.3 6.8 7.8
Starting current direct/with soft starter
4)
A 28/-- 28/-- 43/21
Protection class IP 20 20 20
max. power consumption, circulation pumps kW 0.4 0.4 0.5
max. power consumption total kW 8.6 9.1 9.9
Observe local conditions and regulations
Built-in components
Heat pump type FUSIO W 5 FUSIO W 6 FUSIO W 8
One All in One All in One
Controller Optiplus integrated integrated integrated
WPZ-test number ... ... ...
FUSIO W 5 - FUSIO W 8 with Optiplus controller
– Circulation pumps energy class A – Safety valve 3.0 bar – Pressure gauge 0–4 bar – flexible connection-hoses – Heat pump controller Optiplus – Temperature sensor – Expansion vessels (heating vessel enclosed from fusio w 11
– Pressure controller
– Flow sensor
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Technical data FUSIO W 2/2
Page 6
climate
cold heat
Sound
Sound power level Lwa dB(A) 43 47 50
Sound pressure level in 1 m
1)
Lpa dB(A) 28 32 35
Field of application
Heat source temperature min/max °C -6 to +20
Heat flow temperature at > B0 min/max °C +25 to +65
Heat flow temperature at B-6 min/max °C +25 to +60
Vaporiser, brine side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 1.88/2.15/2.51 2.45/2.80/3.27 3.13/3.58/4.18
Pressure drop via heat pump kPa 8/11/14 12/15/20 17/21/29
Free compression
2)
kPa 100/95/91 92/86/80 81/72/59
Medium water/ethylene glycol % 75/25 75/25 75/25
Built-in brine pump A 16-1 KW A 16-1 KW A 16-1 KW
Condenser, heater side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 0.91/1.30/1.81 1.18/1.69/2.36 1.53/2.18/3.06
Pressure drop via heat pump kPa 4/7/13 5/10/18 7/14/27
Free compression
2)
kPa 77/73/61 75/66/52 70/57/36
Medium water % 100 100 100
Built-in heating pump A 15-1 A 15-1 A 15-1
Dimensions/connections/miscellaneous
Dimensions D x W x H mm 700 x 530 x 1260
Total weight kg 170 170 190
Heating circuit connection AG Inch 5/4" 5/4" 5/4"
Brine circuit connection AG Inch 5/4" 5/4" 5/4"
Cooling agent/filling quantity -- / kg R-410A/2.1 R-410A/2.8 R-410A/3.1
Refrigeration oil filling quantity l 1.2 1.2 1.0
Expansion vessel heater
3)
V l SD 50.3 SD 50.3 SD 80.3
set upstream pressure, heating circuit p bar 1.0 1.0 1.0
Expansion vessel, brine circuit V l SD 25.3 SD 25.3 SD 35.3
set upstream pressure, brine circuit p bar 0.5 0.5 0.5
Safety valve (brine/heating) p bar 3.0 3.0 3.0
Switching point, brine pressure controller p bar 0.4 0.4 0.4
Heat pump type FUSIO W 11 FUSIO W 14 FUSIO W 18
Model All in One All in One All in One
Controller Optiplus integrated integrated integrated
WPZ-test number SW-307-12-06
FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller
Standard performance data (as per EN 14511) W 35 W 50 W 35 W 50 W 35 W 50
Heat output at B0 kW 10.6 9.9 13.8 12.9 17.8 16.7
COP at B0 - 4.7 3.1 4.7 3.1 4.5 3.1
El. power consumption at B0 kW 2.2 3.2 2.9 4.1 3.9 5.4
Cooling output at B0 kW 8.3 6.7 10.9 8.8 13.9 11.3
1) Free field value
2) Free compression is specified for highest level
3) Expansion vessel heater is enclosed from fusio w 11
4) FUSIO W 5 and FUSIO W 6 without soft starter
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Technical data FUSIO W 1/2
Page 7
Electrical data
Operating voltage power 3/ N / PE / 400 V / 50 Hz
External Abs. with el. heating insert 20 25 25
External Abs. without el. heating insert 13 16 16
Output electrical heating insert 400 V 2/4/6 2/4/6 2/4/6
max. machine current with el. heating insert 19.1 21.4 24.5
max. machine current without el. heating insert 10.4 12.7 15.8
Starting current direct/with soft starter
4)
52/25 62/30 75/36
Protection class 20 20 20
max. power consumption, circulation pumps 0.5 0.7 0.7
max. power consumption total 10.9 12.6 14.6
Observe local conditions and regulations
Built-in components
Heat pump type FUSIO W 11 FUSIO W 14 FUSIO W 18
Model All in One All in One All in One
Controller Optiplus integrated integrated integrated
WPZ-test number ... ... ...
FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller
– Circulation pumps energy class A – Safety valve 3.0 bar – Pressure gauge 0–4 bar – flexible connection-hoses – Heat pump controller Optiplus – Temperature sensor – Expansion vessels (heating vessel enclosed from FUSIO W 11 – Pressure controller – Flow sensor
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Technical data FUSIO W 2/2
Page 8
700
1175
1260
530
240
250
200
1175
485
690
90 290 150
530
700
90
150
150
140
450
450
450
300
1
2
3
4
55
5
5
Tableau
100
7
6
Layout
Electric
Connections
Hot water
Inlet-outlet
Outlet
Heat source
Inlet
Heat source
Inlet-outlet
Hot water inlet
Hot water outlet
Sensor
cable
Feeder
cable
Legend
1 Hot water outlet 2 Hot water inlet 3 Heat source outlet 4 Heat source inlet 5 Minimum distances 6 Outlet of safety valve from heat source and heater 7 Ball valves
All dimensions are in mm
The external sensor (QAC 34/101) and the documents are enclosed in the electric panel.
Front view Lateral view Connection side
OH FUSIO W 5- FUSIO W 11, brine/water optiplus controller
Dimension drawing
FUSIO W
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 9
700
1175
1260
530
240
250
200
1175
485
690
90 290 150
530
700
90
150
150
140
450
450
450
300
1
2
3
4
55
5
5
Tableau
100
6
8
7
8
8
Layout
Electric
Connections
Hot water
Inlet-outlet
Outlet
Heat source
Inlet
Heat source
Inlet-outlet
Hot water inlet
Hot water outlet
Sensor
cable
Feeder
cable
Legend
1 Hot water outlet 2 Hot water inlet 3 Heat source outlet 4 Heat source inlet 5 Minimum distances 6 Outlet of safety valve from heat source and heater 7 Ball valves 8 Connection expansion vessel heater 1500 mm hose length from the outlet
All dimensions are in mm
The external sensor (QAC 34/101) and the documents are enclosed in the electric panel.
Front view Lateral view Connection side
Dimension drawing
FUSIO W
FUSIO W 1 - FUSIO W 18, brine/water with Optiplus controller
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 10
Volume flow source minimum / nominal / standard 0.88/1.01/1.17 m3/h Volume flow heater minimum / nominal / standard 0.43/0.61/0.86 m3/h
3
4
5
6
7
8
9
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11°C13°C15°C
0.0
0.5
1.0
1.5
2.0
2.5
3.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves FUSIO W 1- FUSIO W 5
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 11
Volume flow source minimum / nominal / standard 1.04/1.19/1.39 m3/h Volume flow heater minimum / nominal / standard 0.51/0.72/1.01 m3/h
3
4
5
6
7
8
9
10
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11° C13°C15°C
0.0
0.5
1.0
1.5
2.0
2.5
3.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves
FUSIO W 6
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 12
climate
cold heat
Volume flow source minimum / nominal / standard 1.36/1.55/1.81 m3/h Volume flow heater minimum / nominal / standard 0.66/0.95/1.33 m3/h
4
5
6
7
8
9
10
11
12
13
14
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11°C13°C15°C
1.0
1.5
2.0
2.5
3.0
3.5
4.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves
FUSIO W 8
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 13
Volume flow source minimum / nominal / standard 1.98/2.15/2.51 m3/h Volume flow heater minimum / nominal / standard 0.91/1.30/1.91 m3/h
8
10
12
14
16
18
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11°C13°C15°C
1.0
2.0
3.0
4.0
5.0
6.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves
FUSIO W 11
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 14
climate
cold heat
Volume flow source minimum / nominal / standard 2.45/2.80/3.27 m3/h Volume flow heater minimum / nominal / standard 1.19/1.69/2.36 m3/h
10
12
14
16
18
20
22
24
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11°C13°C15°C
1.0
2.0
3.0
4.0
5.0
6.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves
FUSIO W 14
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 15
Volume flow source minimum / nominal / standard 3.13/3.58/4.18 m3/h Volume flow heater minimum / nominal / standard 1.53/2.18/3.06 m3/h
12
14
16
18
20
22
24
26
28
30
-5°C -3°C -1°C 1°C3°C 5°C7°C 9°C11°C13°C15°C
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
-5°C 0°C5°C 10°C 15°C
1
2
3
4
5
6
7
8
9
-5°C 0°C5°C 10°C 15°C
Heat output in kW
Heat source temperature
Heat source temperature
Heat source temperature
Electric output in kW Performance data COP
tv = 30° tv = 35° tv = 45° tv = 50° tv = 63°
Performance data as per EN 14511
Power curves
FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 16
climate
cold heat
Heat pumps without buffer storage, suitable only for floor heating
Legend B21 Flow temperature sensor, heat pump B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q8 Built-in brine pump Q9 Condenser pump built-in U1 Overflow valve
Function description
Start the heat pump via the external temperature sensor (B9). This works directly in the heating circulation. Depending upon the ambient temperature, the heat pump is switched on and off via the return flow temperature (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The condenser pump (Q9) is in operation during the entire heating period.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump Consumer
U1
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Basic concept 01.00.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 17
U1
EG
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Heat pumps with buffer storage in return flow, suitable only for floor heating
Legend B21 Flow temperature sensor, heat pump B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q9 Condenser pump built-in Q8 Built-in brine pump U1 Overflow valve
Function description
Start the heat pump via the external temperature sensor (B9). This works directly in the heating circulation. A buffer storage is integrated in the return flow. Depending upon the ambient temperature, the heat pump is switched on and off via the return flow temperature (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The condenser pump (Q9) is in operation during the entire heating period. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content must be supplemented with an external vessel.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerBuffer storage
System-specific
Basic concept 01/01/2010
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 18
climate
cold heat
KW
TWW
Q3
B3
U1
K6
1)
SV
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Legend B21 Flow temperature sensor heat pump B3 Domestic water temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor CW Cold water K6 Electric heating insert DHW 1) K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q3 Deflector valve DHW Q8 Built-in brine pump Q9 Condenser pump built-in BV Balancing valve SV Safety valve DHW Domestic hot water U1 Overflow valve
1) Power contactor+fuse in on-site tableau
Function description
Start the heat pump via the external temperature sensor (B9). This works directly in the heating circulation. Depending upon the ambient temperature, the heat pump is switched on and off via the return flow temperature (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The condenser pump (Q9) is in operation during the entire heating period. DHW is charged according to the time program via the temperature sensor (B3), the deflector valve (Q3) is thus switched. The electrical insert (K6) in the DHW storage is controlled by the heat pump controller.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerDomestic water storage tankCharging circuit DHW
Basic concept 01.20.10
FUSIO W 5 - FUSIO W 18
Heat pumps without buffer storage, suitable only for floor heating DHW heating with hydraulic switchover
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 19
KW
TWW
Q3
K6
1)
U1
SV
B3
EG
SRV
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Heat pumps with buffer storage in return flow, suitable only for floor heating DHW heating with hydraulic switchover
Legend
B21 Flow temperature sensor heat pump B3 Domestic water temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor CW Cold water K6 Electric heating insert DHW 1) K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q3 Deflector valve DHW Q8 Built-in brine pump Q9 Condenser pump built-in BV Balancing valve SV Safety valve DHW Domestic hot water U1 Overflow valve
1) Power contactor+fuse in on-site tableau
Function description
Start the heat pump via the external temperature sensor (B9). This works directly in the heating circulation. A buffer storage is integrated in the return flow. Depending upon the ambient temperature, the heat pump is switched on and off via the return flow temperature (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The condenser pump (Q9) is in operation during the entire heating period. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content must be supplemented with an external vessel. DHW is charged according to the time program via the temperature sensor (B3), the deflector valve (Q3) is thus switched. The electrical insert (K6) in the DHW storage is controlled by the heat pump controller.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerBuffer storageDomestic water
storage tank
Charging circuit DHW
System-specific
Basic concept 01.21.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 20
climate
cold heat
Q2
B4
Y1
B1
ST
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
SRV
EG
SRV
Heat pump with buffer storage Charging initiated as per the ambient temperature
Legend B1 Flow temperature sensor heating circuit B21 Flow temperature sensor heat pump B4 Buffer storage temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q2 Heating circuit pump on-site Q8 Built-in brine pump Q9 Condenser pump built-in BV Balancing valve ST Safety thermostat Y1 Heating circuit mixer
Function description
Start the heat pump via the external temperature sensor (B9). This works on the buffer storage. Depending upon the ambient temperature, the heat pump is switched on and off via the temperature sensor (B4) or (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The pump (Q2) is in operation during the entire heating period. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content must be supplemented with an external vessel. The discharge circuit control is controlled with the optional heating circuit mixer (Y1) via the flow temperature sensor (B1) depending upon the outside temperature. The buffer storage can be charged at reduced rate.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerBuffer storageCharging circuit
heater
System-specific
Basic concept 02.00.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 21
KW
TWW
1)
K6
Q3
B4
SV
SRV
SRV
Q2
Y1
B1
ST
B3
EG
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Heat pump with buffer storage DHW heating with hydraulic switchover
Legend B1 Flow temperature sensor heating circuit B21 Flow temperature sensor, heat pump B3 Domestic hot water temperature sensor B4 Buffer storage temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller
FT Flow sensor
CW Cold water K6 Electric heating insert DHW 1) K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q2 Heating circuit pump on-site Q3 Deflector valve DHW Q8 Built-in brine pump Q9 Condenser pump built-in BV Balancing valve ST Safety thermostat SV Safety valve DHW Domestic hot water Y1 Heating circuit mixer
1) Power contactor and fuse in on-site tableau
Function description
Start the heat pump via the external temperature sensor (B9). This works on the buffer storage. Depending upon the ambient temperature, the heat pump is switched on and off via the temperature sensor (B4) or (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The pump (Q2) is in operation during the entire heating period. DHW is charged according to the time program via the temperature sensor (B3), the deflector valve (Q3) is thus switched. The electrical insert (K6) in the DHW storage is controlled by the heat pump controller. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content must be supplemented with an external vessel. Depending upon the ambient temperature, the discharge circuit control is controlled with the optional heating circuit mixer (Y1) via the flow temperature sensor (B1). The buffer storage can be charged at reduced rate.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerBuffer storageDomestic water
storage tank
Charging circuit
DHW/heater
System-specific
Basic concept 02.20.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 22
climate
cold heat
KW
TWW
1)
K6
Y1
B3
Q2
B1
ST
SV
B4
EG
SRV
SRV
RSV
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Heat pump with combination storage, DHW heating at reduced rate Zonal charging initiated as per the ambient temperature
Legend B1 Flow temperature sensor heating circuit B21 Flow temperature sensor, heat pump B3 Domestic hot water temperature sensor B4 Buffer storage temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor CW Cold water K6 Electric heating insert DHW 1) K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q2 Heating circuit pump on-site Q8 Built-in brine pump Q9 Condenser pump built-in NRV Non-return valve ST Safety thermostat SV Safety valve DHW Domestic hot water Y1 Heating circuit mixer
1) Power contactor+fuse in on-site tableau
Function description
Start the heat pump via the external temperature sensor (B9). This works in the lower zone of the combination storage. Depending upon the ambient temperature, the heat pump is switched on and off via the temperature sensor (B4) or (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The discharge circuit control integrated in the heat pump controller is initiated as per the ambient temperature and is controlled via the flow temperature (B1). The pump (Q2) is in operation during the entire heating period. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content must be supplemented with an external vessel. The combination storage can be charged at reduced rate. DHW is charged as per the time program via the temperature sensor (B3). The electrical insert (K6) in the combination storage is controlled by the heat pump controller.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerCombination storageCharging circuit
Combination storage
System-specific
Basic concept 02.30.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 23
KW
TWW
K6
1)
2)
Y1
2)
B3
B4
Q2
B1
ST
SV
SRV
SRV
RSV
EG
B9
Q9
EG
N1
Q8
PI
B71
K25
E15
B92
E9, E10
B91
EG
B21
B81
B83
PI
FT
Heat pump monovalent with solar combination storage, DHW heating at reduced rate Zonal charging initiated as per the ambient temperature
Legend B1 Flow temperature sensor heating circuit B21 Flow temperature sensor, heat pump B3 Domestic water temperature sensor B4 Buffer storage temperature sensor B71 Return flow temperature sensor, heat pump B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel E15 Brine pressure controller FT Flow sensor CW Cold water K6 Electric heating insert DHW 1) K25 Electric heating insert in flow 6 kW N1 Heat pump controller Optiplus built-in PI Pressure gauge Q2 Heating circuit pump on-site Q8 Brine pump Q9 Condenser pump NRV Non-return valve ST Safety thermostat BV Balancing valve SV Safety valve DHW Domestic hot water Y1 Heating circuit mixer
1) Power contactor+fuse in on-site tableau
2) Solar system on-site, independent of control
by heat pump.
Function description
Start the heat pump via the external temperature sensor (B9). This works in the lower zone of the combination storage. Depending upon the ambient temperature, the heat pump is switched on and off via the temperature sensor (B4) or (B71). The machine has a starting delay in order to prevent wobbling. The integrated electric heating insert (K25) can be used as emergency heating. The discharge circuit control integrated in the heat pump controller is initiated as per the ambient temperature and is controlled via the flow temperature (B1). The pump (Q2) is in operation during the entire heating period. The size of the built-in expansion vessel (EV) must be controlled and depending upon the water content of the heating system, the same must be supplemented with an external vessel. The combination storage can be charged at reduced rate. DHW is charged as per the time program via the temperature sensor (B3). The electrical insert (K6) in the combination storage is controlled by the heat pump controller. The lower part of the combination storage is managed by the solar system, which is independent of the heat pump.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Soil sensor system Heat pump ConsumerSolar systemCombination
storage
Charging circuit
Combination storage
System-specific
Basic concept 02.40.10
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 24
climate
cold heat
Y1
Q2
B1
ST
QX2
Zu
Auf
PE
N
M
1~
L
PE
N
M
1~
L
PE
N
QX4
PE
N
QX2
QX1
Q9
Q8
W
V
U
QX3
Y2
Y1
T
Q2
S
Q3
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
u
t
s
r
q
p
n
k
X
Y
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
Regler Optiplus (RVS 61/3)
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
BX3
BX2
B92
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX1
SRV SRV
UX2
Legend B1 Flow temperature sensor
Heating circuit 1 Q2 Circulation pump heating circuit 1 (mixed)
BV Balancing valve Y1 Mixer heating circuit 1,230 V QX2 Circulation pump, pump circuit
230 V / 400 V
ST Safety thermostat
Heat pump with buffer storage or combination storage No extension module required!
Note: This additional sheet contains additional connection instructions for the electrical installation.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Buffer storage (or combination storage)
Heating circuit 1 with mixer
Consumer without mixer
for controller
QX2 Circulation pump,
pump circuit 230 V, max. 2.0 A (or 400 V via ext. power contactor)
Y1 Mixer heating circuit 1 230 V
Q2 Circulation pump heating
circuit 1 230 V, max.
1.0 A (or 400 V via ext.
power contactor) Opt: Safety thermo­ stat (ST) in series with Q2
B1 Flow Temperature sensor HK1
Controller Optiplus (RVS 61/3)
Extension 1: Heating circuit 1 mixed and consumer unmixed FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 25
Y1
Q2
B1
ST
QX21
QX23
BX21
QX22
T
QX23
QX21
N
PE
L
n
M
H2
M
BX22
M
BX21
n
n
S
PE
N
PE
N
N
PE
L
Erweiterungsmodul
AVS75.390
2
T
4
3
3
2
S
N
PE
L
n
2
n
2
n
2
X50
Zu
Auf
PE
N
M
1~
L
PE
N
SRV SRV
ST
Legend B1 Flow temperature sensor heating
circuit 1
Q2 Circulation pump heating circuit 1 Connection as per base sheet for basic concept and HP type
BV Balancing valve Y1 Mixer heating circuit 1,230 V
BX21 Flow temperature sensor heating
circuit 2
BX22 Slot empty QX23 Circulation pump heating circuit 2
230 V, max 2 Amp.
QX21 Mixer heating circuit 2, 230 V ST Safety thermostat H2 Digital input X50 Flat plug for connection
Connection cable for controller-basic module
Note:
Parameterisation in the heating circuit 2 is done in the parameter points 1010-1151, which appear for the connection of the extension module. No additional software required!
Heat pump with buffer storage or combination storage Required additionally: Extension module AVS 75.390
Note: This additional sheet contains additional connection instructions for the electrical installation.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Buffer storage (or combination storage)
Heating circuit 1
Heating circuit 2
for controller
QX23 Circulation pump heating
circuit 2 230 V, max. 2.0 A Opt: Safety thermostat (ST) in series with Q23
QX21 Mixer heating circuit 2
Connection control voltage
Extension module
ABS75.390
Extension 2: 2 heating circuits mixed FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 26
climate
cold heat
Q3
B3
K6
SV
TS
DHW heating with hydraulic switchover
Additional: Solar charging with independent solar system
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Charging circuit DHW Domestic hot water
storage tank
Solar system (control independent of heat pump)
Connection diagram for heat pump and hydraulic integration as well as legends: as per basic concept
Terminal assignment: as per basic concept
DHW heating with electric heating
insert
DHW heating solar (additional) TS Solar sensor
DHW
CW
Extension 3: Hot water storage tank with solar circuit FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 27
QX4
PE
N
QX2
QX1
Q9
Q8
W
V
U
QX3
Y2
Y1
T
Q2
S
Q3
R
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
u
t
s
r
q
p
n
k
h
f
X
Y
K1
Q
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
Wärmepumpenregler (RVS 61/3)
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
BX3
BX2
B92
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
M
1~
L
PE
N
SWP
Q15
B13
RSV
Y1
Q2
B1
ST
SRV
Heat pump with swimming pool charging
Note: This additional sheet contains additional connection instructions for the electrical installation.
Legend B13 Swimming pool sensor
(Limit Tmax.) Q15 Swimming pool circulation pump/ Deflector valve
H1 enabled externally NRV Non-return valve SWP Swimming pool pump
(controlled externally)
Function description
As soon as the swimming pool pump is put into operation, the heat pump for the swimming pool charging is switched-on from outside by the swimming pool controller via input H1. The swimming pool pump is controlled by the swimming pool controller. The swimming pool temperature (control temperature) is monitored with the swimming pool sensor (B13).
Attention:
The heat pump must not be enabled unless there is a flow through the heat exchanger.
When operating the swimming pool charging with/without buffer storage, the total heat pump output (B0/W35 or W10/W35) must be accepted by the swimming pool heat exchanger.
The swimming pool must be taken into consideration when designing the soil sensor.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Buffer storage (or combination storage)
Heating circuit 1 Swimming pool charging
for controller
Swimming pool
Swimming pool controller
Enabled on H1 contact
H1 enabled externally
Swimming pool charging
(floating (gold-)contact)
BX2 Swimming pool sensor B13
QX6 Swimming pool -
circulation pump (Q15)
230 V, max. 2.0 A
Heat pump controller (RVS 61/3)
with controller OptiplusExtension 4:
FUSIO W Swimming pool heater
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 28
climate
cold heat
QX4
PE
N
QX2
QX
Q9
Q8
W
V
U
QX3
Y2
T
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
u
t
s
r
q
p
X
Y
PE
N
PE
N
PE
N
PE
N
PE
N
Regler Optiplus (RVS 61/3)
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
BX3
BX2
B92
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
Y1
L
L
L
PE
N
Y 21
Zu
Auf
PE
N
Y1 / Y2
N1
B9
Y1/Y2
B1
Y21
PWT
Free cooling, heating circuit/cooling circuit directly without buffer storage
Note: This additional sheet contains additional connection instructions for the electrical installation.
Function description
For passive cooling (free cooling), cooling is done without operating the cryogenic unit. Heat is directly returned to the connected source (soil sensor or ground water). The heat pump controller runs a cooling curve via the ambient temperature (B9), this is controlled with the connected mixer (Y1/Y2) and the flow temperature (B1). For cooling requirement, the source circuit is controlled by means of a deflector valve (Y21) via the plate heat exchanger (PHE). For heating requirement, the deflector valve is reset and the mixer is shut.
For available room thermostat valves, these must be adaptable for the cooling as well as the heating operation.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Heat pump with basic concept
GK 01. ... (brine/water)
GK 04 ...(water/water)
Consumer
Heating circuit/ cooling circuit
Circulation via Condenser pump
Source circuit
Connection for heat pump
Source connection
Soil sensor or ground water
Y1/Y2 Mixing valve for free cooling
230 V, max. 2.0 A
B1 Flow temperature sensor
additionally allocated terminals Connection
Enabled Free cooling
Y21 Deflector valve free cooling
230 V, max. 2.0 A
Legend B1 Flow temperature sensor
Cooling circuit
B9 External temperature sensor N1 Heat pump controller
Optiplus (built-in) PHE Plate heat exchanger
(for cooling)
Q8/Q9 Integrated circulation pump Y1/Y2 Mixer for cooling circuit 230 V Y21 Deflector valve 230 V
Extension 5: Free cooling for GK 01. ... or GK 04. ...
Optiheat OH es with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 29
N1
B9
Y21
Q2
Y1/Y2
B1
Y21
PWT
QX4
PE
N
QX2
QX
Q9
Q8
W
V
U
QX3
Y2
T
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
u
t
s
r
q
p
X
Y
PE
N
PE
N
PE
N
PE
N
PE
N
Regler Optiplus (RVS 61/3)
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
BX3
BX2
B92
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
Y1
L
L
L
PE
N
Y 21
Zu
Auf
PE
N
Y1 / Y2
Free cooling, heating circuit/cooling circuit indirectly with buffer storage or combination storage
Note: This additional sheet contains additional connection instructions for the electrical installation.
Function description
For passive cooling (free cooling), cooling is done without operating the cryogenic unit. Heat is directly returned to the connected source (soil sensor or ground water). The heat pump controller runs a cooling curve via the ambient temperature (B9), this is controlled with the connected mixer (Y1/Y2) and the flow temperature (B1). For cooling requirement, the source circuit is controlled by means of a deflector valve (Y21) on both sides via the plate heat exchanger (PHE). For heating requirement, the deflector valve is set back to the heating position. For a set discharge circuit control, the mixing valve Y1/Y2 is integrated in the controller. For available room thermostat valves, these must be adaptable for the cooling as well as the heating operation.
Legend B1 Flow temperature sensor
cooling circuit
B9 External temperature sensor N1 Heat pump controller Opti
plus (built-in)
PHE Plate heat exchanger
(for cooling)
Q2 Heating circuit pump Y1/Y2 Mixer for cooling circuit 230 V Y21 Deflector valve 230 V
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Heat pump with basic concept
GK 02. ... (brine/water)
GK 05 ...(water/water)
Consumer
Buffer- or
Combination storage
Source circuit
Connection for heat pump
Source connection
Soil sensor or ground water
additionally allocated terminals
Connection Enabled Free cooling
Y1/Y2 Mixing valve for free cooling
230 V, max. 2.0 A
B1 Flow temperature sensor
Y21 Deflector valve free cooling
230 V, max. 2.0 A
Extension 6: Free cooling for GK 02. ... or GK 05. ...
FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 30
climate
cold heat
B9
B4
B41
B10
PI
SV
EG
B92
B71
B91
N1
B21
Q9
SRV
M
Opt.
B92
B71
B91
N1
B21
Q9
SRV
M
Opt.
B92
B71
B91
N1
B21
Q9
SRV
M
Opt.
Legend B10 Common flow sensor B21 Flow temperature sensor, heat pump B4 Buffer storage temperature sensor top B41 Buffers storage temperature sensor bottom B71 Return flow temperature sensor, heat
pump
B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel N1 Heat pump controller Optiplus built-in PI Pressure gauge Q9 Condenser pump BV Balancing valve Opt. el. butterfly valve (optional)
Requirement bus cable:
Cu cable 1.5 mm2. 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
Function description
The heat pumps are operated via the external sensor B9. This works on the buffer storage. Depending upon the ambient temperature, the heat pumps are switched on and off via the temperature sensor B4 or B41. The machine has a starting delay in order to prevent wobbling. If the common flow temperature B10 is not attained, based on release limit, another heat producer is switched on additionally. If the currently switched on heat producer exceeds the requested power requirement, the producer switches off with the highest priority.
System-specific testing/adaptation:
- Primary side (brine, water intake), discharge circuit control
- Storage size depending upon the performance of the heat producer
- Hydraulic integration
- Shut-off devices, control valves, check valves as per requirement
- Design of expansion system
- Fit adequate dipping sleeves for sensors, thermostats
and thermometer
- Observe structural conditions (insertion, installation, ...)
Cascade operation with several heat pumps with buffer storage
Heat pump 1
Master
Heat pump 2
Slave
Heat pump 3
Slave
Buffer storage
Detail description of Primary circuit as per basic concept
Extension 7: Cascade FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 31
B9
B4
B41
B10
B92
B71
B91
N1
B21
Q9
SRV
B92
B71
B91
N1
B21
Q9
SRV
PI
SV
EG
SV
Q33
B36
TWW
B3
B31
K6
KW
Q3
M
Opt.
M
Opt.
SRV
SRV
Legend B10 Common flow sensor B21 Flow temperature sensor, heat pump B3 Domestic water sensor top B31 Domestic water sensor bottom B36 Domestic water charging sensor B4 Buffer storage temperature sensor top B41 Buffers storage temperature sensor
bottom
B71 Return flow temperature sensor, heat
pump
B9 External temperature sensor B91 Brine inlet temperature sensor B92 Brine outlet temperature sensor EV Expansion vessel K6 Electric heating insert N1 Heat pump controller Optiplus built-in PI Pressure gauge Q3 Domestic water - deflector valve Q33 Domestic water - intermediate circuit
pump
Q9 Condenser pump BV Balancing valve Opt. el. butterfly valve (optional)
Requirement bus cable:
Cu cable 1.5 mm2, 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
Function description
The first slave machine is used for warm water charging, wherein, even the appropriate components are connected. At active charging, the heat pump is isolated hydraulically from the system and is not available for the heating operation. After complete charging, the heat pump is again available for the heating operation. The control regulates the domestic water temperature as per time schedule program at the desired setpoint. Boiler charging is started via drinking water sensor (B3). Once the sensor (B31) attains the desired temperature, charging is stopped.
System-specific testing/adaptation:
- Primary side (brine, water intake), discharge circuit control
- Storage size depending upon the performance of the heat producer
- Hydraulic integration
- Shut-off devices, control valves, check valves as per requirement
- Design of expansion system
- Fit adequate dipping sleeves for sensors, thermostats
and thermometer
- Observe structural conditions (insertion, installation, ...)
Cascade operation with several heat pumps with buffer storage and DHW charging with hydraulic switchover
Detail description of Primary circuit as per basic concept
Heat pump 1
Slave 1
Heat pump 2
Master
Hot water
storage tank
Buffer storageCharging circuit
DHW
Extension 7: Cascade with DHW FUSIO W with controller Optiplus
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 32
climate
cold heat
Y1
Q2
B1
ST
B9
Y2
Y1
N
Q2
N
N
L
060706A
000020RVS46.530/109
1PRVS46.530/109
S060706000020
SRV
1 consumer circuit controlled
Note: This additional sheet contains additional connection instructions for the electrical installation.
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Buffer storage (or combination storage)
Heating circuit 1 with mixer
Flow HK1
Input H1
External sensor
Opt. Illumination
RG1
LPB
HK1 pump
HK1mixer
Supply
for controller
Legend B1 Flow temperature sensor heating circuit 1 B9 External sensor (optional) Q2 Circulation pump heating circuit 1 BV Balancing valve ST Safety thermostat Y1 Mixer heating circuit 230 V LPB Connection to main controller
Requirement bus cable:
Cu cable 1.5 mm
2
, 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
Extension 20: Heating circuit mixed FUSIO W... with slave controller RVS 46.530
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 33
Y1
Q2
B1
ST
QX1
B9
SRV
SRV
060404A
000020RVS46.543/109
1PRVS46.543/109
S060404000020
b
2 consumer circuits, controls a group
Note: This additional sheet contains additional connection instructions for the electrical installation.
Legend B1 Flow temperature sensor heating
circuit 1
B9 External sensor (optional) Q2 Circulation pump heating circuit 1
(mixed)
QX1 Circulation pump HKP BV Balancing valve ST Safety thermostat Y1 Heating circuit mixer 230V LPB Connection to main controller
Requirement bus cable:
Cu cable 1.5 mm2. 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Cooling agent fluid B83
Hot gas sensor 2 B82
Flow HK1
Input H1
External sensor
Domestic hot water top
HKP - pump
HK1- mixer
HK1- pump
DHW valve
Opt. Illumination
RG1 / RG2
RG1 / RG2
LPB
Supply
Buffer storage (or combination storage)
Heating circuit 1 with mixer
Consumer without mixer
Extension 21: Heating circuit mixed and consumer unmixed FUSIO W... with slave controller RVS 46.543
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 34
climate
cold heat
060404A
000020RVS46.543/109
1PRVS46.543/109
S060404000020
b
.
.
Y1
Q2
B1
ST
Q3
KW
TWW
B3
K6
SV
B9
SRV
SRV
M
Opt.
Consumer circuit mixed and DHW heating with charging pump No speed control of the charging pump Q3 possible with slave controller
Note: This additional sheet contains additional connection instructions for the electrical installation.
Legend B1 Flow temperature sensor heating
circuit 1
B3 Domestic hot water top B9 External sensor (optional) K6 Electrical heating insert DHW Q2 Circulation pump heating circuit 1 Q3 DHW - charging pump BV Balancing valve ST Safety thermostat Y1 Heating circuit mixer 230V LPB Connection to main controller Opt. el. butterfly valve (optional)
Requirement bus cable:
Cu cable 1.5 mm
2
, 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
Buffer storage (or combination storage)
Heating circuit 1 with mixer
for controller
DHW charging
Flow HK1
Input H1
External sensor
Domestic hot water top
Electrical insert K6
HK1- mixer
HK1- pump
DHW valve Q3
Opt. Illumination
RG1 / RG2
RG1 / RG2
LPB
Supply
Extension 22: Heating circuit mixed and DHW heating FUSIO W... with slave controller RVS 46.543
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 35
060404A
000020RVS46.543/109
1PRVS46.543/109
S060404000020
b
Y1
Q2
B1
ST
Q3
B9
B3
SV
Q33
KW
TWW
K6
SRV
SRV
M
Opt.
Consumer circuit mixed and DHW heating with charging pump and external heat exchanger No speed control of the charging pump Q3 possible with slave controller
Note: This additional sheet contains additional connection instructions for the electrical installation.
Legend B1 Flow temperature sensor heating
circuit 1
B3 Domestic hot water top B9 External sensor (optional) K6 Electrical heating insert DHW Q2 Circulation pump heating
circuit 1
Q3 DHW charging pump Q33 DHW- intermediate circuit pump BV Balancing valve ST Safety thermostat Y1 Heating circuit mixer 230 V LPB Connection to main controller Opt. el. butterfly valve (optional)
Requirement bus cable:
Cu cable 1.5 mm
2
, 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3
• Subjecttotechnicalchanges.
• Installationofadditionalcomponents
as per local regulations and conditions.
• Thispresentationisusedasplanningaidforthe
fitter.
for controller
Flow HK1
Input H1
External sensor
Domestic water
top
Electrical insert K6
HK1- mixer
HK1- pump
DHW pumps (Q3
and Q33)
Opt. Illumination
RG1 / RG2
RG1 / RG2
LPB
Supply
Buffer storage (or combination storage)
Heating circuit 1 with mixer
DHW charging
Extension 23: Heating circuit mixed and DHW heating FUSIO W... with slave controller RVS 46.543
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 36
climate
cold heat
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3 2 1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7 EX6 EX5 EX4 EX3 EX2 EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+ CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3
BSB Connection for external control units
BSB Connection for external control units
LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock Contact is closed
when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
Main
switch
installed
for HP
Terminal diagram for basic concept 01.00.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 37
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3 2 1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7 EX6 EX5 EX4 EX3 EX2 EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+ CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3
BSB Connection for external control units
BSB Connection for external control units
LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
Main
switch
installed
for HP
Terminal diagram for basic concept 01/01/2010
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 38
climate
cold heat
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3 2 1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7 EX6 EX5 EX4 EX3 EX2 EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+ CL­CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL­CL+ CL­CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
L
L
PE
N
L1
L2
L3
L1 L2 L3 N PE
only up to 10 kW additional protection for 12 and 15 kW
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3 BSB Connection for external control units BSB Connection for external control units LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
Main
switch
installed
for HP
K6 Electric heating insert DHW
Enable contactor
manual/auto/off
e.g. Hager ET321 (507403200)
EW Boiler release (RSE)
Terminal diagram for basic concept 01.20.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 39
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3
2
1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7
EX6
EX5
EX4
EX3
EX2
EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+
CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
L
L
PE
N
L1
L2
L3
L1 L2 L3 N PE
only up to 10 kW additional protection for 12 and 15 kW
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3 BSB Connection for external control units BSB Connection for external control units LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A (max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
K6 Electric heating insert DHW
Enable contactor
manual/auto/off
e.g. Hager ET321 (507403200)
EW Storage release (RSE)
Main
switch
installed
for HP
Terminal diagram for basic concept 01.21.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 40
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3 2 1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7 EX6 EX5 EX4 EX3 EX2 EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+
CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
M
1~
L
PE
N
Zu
Auf
PE
N
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional)
QAA55 Phase 1 + 2 QAA75 Phase 1 - 3
BSB Connection for external control units
BSB Connection for external control units
LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Opt. Safety thermostat (ST) in series with Q2
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
Main
switch
installed
for HP
Terminal diagram for basic concept 02.00.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 41
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3 2 1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7 EX6 EX5 EX4 EX3 EX2 EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+ CL­CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL­CL+ CL­CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
M
1~
L
PE
N
L
L
PE
N
L1
L2
L3
L1 L2 L3 N PE
Zu
Auf
PE
N
only up to 10 kW additional protection for 12 and 15 kW
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3 BSB Connection for external control units BSB Connection for external control units LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61/3)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Opt. Safety thermostat (ST) in series with Q2
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
K6 Electric heating insert DHW
Enable contactor
manual/auto/off
e.g. Hager ET321 (507403200)
EW Boiler release (RSE)
Main
switch
installed
for HP
Terminal diagram for basic concept 02.20.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 42
climate
cold heat
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3
2
1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7
EX6
EX5
EX4
EX3
EX2
EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+
CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
M
1~
L
PE
N
L1
L2
L3
L1 L2 L3 N PE
PE
N
only up to 10 kW additional protection for 12 and 15 kW
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3 BSB Connection for external control units BSB Connection for external control units LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61)
Fuse as per heat pump type: See separate sheet Technical data
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Opt. Safety thermostat (ST) in series with Q2
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
K6 Electric heating insert DHW
Enable contactor
manual/auto/off
e.g. Hager ET321 (507403200)
EW Storage release (RSE)
Main
switch
installed
for HP
Terminal diagram for basic concept 02.30.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 43
6 kW 3 kW
32241
6
110K6
2 4 6
14
3 2 1
L1 L2 L3 N PE
QX4
PE
N
QX2
QX1
Q9
Q8
L3
N
N
L
L
EM
W
V
U
3
2
1
QX3
Y2
Y1
T
Q2
S
Q3
R
Ex7
EX6
EX5
EX4
EX3
EX2
EX1
N
PE
L
w
M
M
M
BX1
M
M
B91
M
B71
M
B1
M
B21
M
B9
M
B3
M
B81
G+
CL-
CL+
u
t
s
r
q
p
n
k
h
b
b
f
b
X
Y
K1
E11
Q
P
E10
E9
K
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
PE
N
CL-
CL+
CL-
CL+
N
PE
L
PE
L1
L2
X60
X30
BSB
3
2
U
3
2
V
2
W
4
3
3
3
2
X
2
Y
2
T
4
3
2
Z
4
3
3
2
S
3
2
R
2
Q
7
6
5
4
3
2
2
P
K
N
PE
L
w
2
u
2
t
2
z
2
y
2
x
2
s
2
r
2
q
2
p
2
n
2
k
2
h
2
f
2
3
e
2
3
b
2
b
2
b
2
BX3
BX2
B92
14
a
MB
DB
a
2
PE
QX6
QX5
N
Z
x
y
z
M
BX4
M
M
UX2
UX1
H3
M
H1
e
M
1~
L
PE
N
L1
L2
L3
L1 L2 L3 N PE
PE
N
only up to 10 kW additional protection for 12 and 15 kW
UX1 Output 0 - 10 V diverse functions UX2 Output 0 - 10 V diverse functions BX4 Buffer storage temperature sensor (B4) BX3 DHW Temperature sensor (B31) BX2 Cooling agent temperature sensor fluid (B83)
BX1 Hot gas temperature sensor (B82) B92 Source outlet temperature sensor B91 Source inlet temperature sensor B71 Return flow temperature sensor Heat pump B1 Flow temperature sensor Heating circuit 1 B21 Flow temperature sensor Heat pump B9 External temperature sensor
B3 Domestic water temperature sensor
B81 Hot gas temperature sensor Compressor 1
H3 Digital 0..10 V input H1 Digital 0..10 V input
BSB Room unit illumination
(optional) QAA55 Phase 1 + 2 QAA75 Phase 1 - 3 BSB Connection for external control units BSB Connection for external control units LPB Connection (cascade, bivalence)
Heat pump controller Optiplus (RVS 61)
Attention:
The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes.
Attention: Max. total reference current of all 230 V connections6 A
(max. 2 A per connection)
QX6 Alarm output (K10)
optional
QX5 Deflector valve free cooling (Y21)
QX4 Relay output 230 V
diverse functions (modulated up to max. 1.4A)
QX3 Electric heating insert DHW (K6)
QX2 Pump (Q20)
QX1 Electric heating insert (K25)
(built-in)
Q9 Condenser pump
(built-in)
Q8 Brine pump (built-in)
(directly or via an internal power contactor)
Y1 Heating circuit mixer 230 V
/Y2 (Y1 = open / Y2 = closed)
Q2 Heating circuit pump 230 V
Opt. Safety thermostat (ST) in series with Q2
Q3 Deflector valve DHW 230 V
K1 Compressor 1
E11 Overload compressor 1
Ex7 Three phase current T
Ex6 Three phase current S
Ex5 Three phase current R
Ex4 Thermal relay source pump
Ex3 Pressure / flow source (E15)
Ex2 EW lock (E6)
Ex1 Reduced rate (E5)
E10 High pressure HP
E9 Low pressure BP
Internal wiring not illustrated!!
on-site tableau
EW lock
EW lock: Contact is closed when heat pump is enabled
Circuit breaker all-pole
Supply heat pump
Standard
K6 Electric heating insert DHW
Enable contactor
manual/auto/off
e.g. Hager ET321 (507403200)
EW Storage release (RSE)
Main
switch
installed
for HP
Fuse as per heat pump type: See separate sheet Technical data
Terminal diagram for basic concept 02.40.10
FUSIO W 5 - FUSIO W 18
Connection electric heating insert K25 (internal)
FUSIO W 5 - FUSIO W 18
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Page 44
FUSIOW23062016
Western Airconditioning B.V. De Wel 10, 3871 MV HOEVELAKEN Tel. +31 (0) 33 247 7800
www.western.nl
_______________________________________________________________________________
Western Airconditioning B.V. reserves the right to alter specifications
Loading...