Westermo TD-36, TD-36 485 User Manual

Page 1
TD-36
DIN-rail Tele and Leased Line modem
TD-36 485
DIN-rail Tele and Leased Line modem
with I/O and RS-485
www.westermo.com
Westermo Teleindustri AB
User Guide
6618-2202
TD-36
Page 2
Page 3
3
6618-2202
Legal information
The contents of this document are provided “as is”. Except as required by applicable  law, no warranties of any kind, either express or implied, including, but not limited to,  the implied warranties of merchantability and fitness for a particular purpose, are made  in relation to the accuracy and reliability or contents of this document. Westermo  reserves the right to revise this document or withdraw it at any time without prior  notice.
Under no circumstances shall Westermo be responsible for any loss of data or income  or any special, incidental, and consequential or indirect damages howsoever caused.
More information about Westermo can be found at the following Internet address:
http://www.westermo.com
Page 4
4
6618-2202
Safety
Before installation: This modem is for restricted access area use only. 
Read this manual completely and gather all information on the unit. Make sure  that you understand it fully. Check that your application does not exceed the safe  operating specifications for this unit. 
This unit should only be installed by qualified personnel. This unit should be built-in to an apparatus cabinet, or similar, where access is 
restricted to service personnel only. The power supply wiring must be sufficiently fused, and if necessary it must be 
possible to disconnect manually from the power supply. Ensure compliance to  national installation regulations.
Maximum 20 A branch circuit protection required. The product is intended to work with IT power system. This unit uses convection cooling. To avoid obstructing the airflow around the unit, 
follow the spacing recommendations (see Cooling section).
Before mounting, using or removing this unit:
Prevent access to hazardous voltage by disconnecting the unit from power supply. Warning! Do not open connected unit. Hazardous voltage may occur within this 
unit when connected to power supply or TNV circuits.
Care recommendations
Follow the care recommendations below to maintain full operation of unit and to fulfil  the warranty obligations. This unit must not be operating with removed covers or lids. Do not attempt to disassemble the unit. There are no user serviceable parts inside. Do not drop, knock or shake the unit, rough handling above the specification may cause  damage to internal circuit boards. Do not use harsh chemicals, cleaning solvents or strong detergents to clean the unit. Do not paint the unit. Paint can clog the unit and prevent proper operation. Do not expose the unit to any kind of liquids (rain, beverages, etc). The unit is not water­proof. Keep the unit within the specified humidity levels. Do not use or store the unit in dusty, dirty areas, connectors as well as other mechanical  part may be damaged. If the unit is not working properly, contact the place of purchase, nearest Westermo   distributor office or Westermo Tech support.
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified  conditions.
Page 5
5
6618-2202
According to:   TIA-968-A and CS-03 Part 1, issue 9
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA.   On the left side of this equipment is a label that contains, among other information, a product  identifier in the format US:AAAEQ##TXXXX.  If requested, this number must be provided to the  telephone company.  
A plug and jack used to connect this equipment to the premises wiring and telephone network must  comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA.  A compliant  telephone cord and modular plug is provided with this product.  It is designed to be connected to a  compatible modular jack that is also compliant.  See installation instructions for details.
Caution-to reduce the risk of fire, use only No.26 AWG or lager telecommunication cable.  The USOC jack required RJ11-C, and the REN is used to determine the number of devices that 
may be connected to a telephone line.  Excessive RENs on a telephone line may result in the  devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs  should not exceed five (5.0).  To be certain of the number of devices that may be connected to a  line, as determined by the total RENs, contact the local telephone company.  For products approved  after July 23, 2001, the REN for this product is part of the product identifier that has the format  US:AAAEQ##TXXXX.  The digits represented by ## are the REN without a decimal point   (e.g., 03 is a REN of 0.3).  For earlier products, the REN is separately shown on the label.
If this equipment TD-36/485 causes harm to the telephone network, the telephone company will  notify you in advance that temporary discontinuance of service may be required.  But if advance  notice isn't practical, the telephone company will notify the customer as soon as possible.  Also, you 
will be advised of your right to file a complaint with the FCC if you believe it is necessary. The telephone company may make changes in its facilities, equipment, operations or procedures that 
could affect the operation of the equipment. If this happens the telephone company will provide  advance notice in order for you to make necessary modifications to maintain uninterrupted service.
Agency approvals and standards compliance
Type Approval / Compliance
EMC EN 61000-6-2, Immunity industrial environm
EN 55024, Immunity IT equipment
EN 61000-6-3, Emission residential environments
FCC part 15 Class B
EN 50121-4, Railway signalling and telecommunications apparatus
IEC 62236-4, Railway signalling and telecommunications apparatus
Safety EN 60950-1 and UL 60950-1, IT equipment
PSTN CS 03 Part 1, issue 9
FCC part 68, TIA-968-A ETSI TS103 021-1, ETSI TS103 021-2, ETSI TS103 021-3 AS/ACIF S002, AS/ACIF S006
Page 6
6
6618-2202
If trouble is experienced with this equipment TD-36/485, for repair or warranty information, please  contact Westermo Data Communication,Inc. 11200 Westheimer,Suit 900. Houston,TX,,77042.   Phone number: 713-240-0367.  If the equipment is causing harm to the telephone network, the   telephone company may request that you disconnect the equipment until the problem is resolved.
There are no repairs the customer/user can perform inside the modem. In the event of equipment malfunction, all repairs should be performed by our Company or an 
authorized agent.  It is the responsibility of users requiring service to report the need for service to  our Company or to one of our authorized agents.  Service can be facilitated through our office at:
Westermo Data Communication Inc
11200 Westheimer Suit 900 Houston,TX, 77042 TEL:713-240-0367 
Connection to party line service is subject to state tariffs.  Contact the state public utility commission,  public service commission or corporation commission for information.
If your home has specially wired alarm equipment connected to the telephone line, ensure the instal­lation of this TD-36/485 does not disable your alarm equipment. If you have questions about what will  disable alarm equipment, consult your telephone company or a qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory notice  in their customer information suggesting the customer use a surge arrestor.  Telephone companies  report that electrical surges, typically lightning transients, are very destructive to customer terminal  equipment connected to AC power sources. This has been identified as a major nationwide problem.
Page 7
7
6618-2202
Declaration of Conformity
Westermo Teleindustri AB
Declaration of conformity
Org.nr/
Postadress/Postal addr ess
Tel.
Telefax
Postgiro
Bankgiro
Corp. identity number Registered office
S-640 40 Stora Sundby 016-428000 016-428001 52 72 79-4 5671-5550 556361-2604 Eskilstuna
Sweden Int+46 16428000 Int+46 16428001
The manufacturer
Westermo Teleindustri AB SE-640 40 Stora Sundby, Sweden
Herewith declares that the product(s)
Type of product Model Art no Installation manual
DIN-rail Tele and Leased Line modem
TD-36
3618-0101
6618-2201
DIN-rail Tele and Leased Line modem with I/O and RS-485
TD-36 485
3618-0001
6618-2201
is in conformity with the following EC directive(s).
No Short name
89/336/EEG Electromagnetic Compatibility (EMC) 73/23/EEG Low Voltage Directive - LVD
References of standards applied for this EC declaration of conformity.
No Title Issue
EN 61000-6-2 Immunity for industrial environments 2 (2001) EN 55024 Information technology equipment – Immunity 1 (1998) EN 61000-6-3 Emission standard for industrial environments 1 (2001) EN 60950 Safety of information technology equipment 6 (2000) EN 50121-4 Railway signalling and telecommunications apparatus IEC 62236-4 Railway signalling and telecommunications apparatus UL 60950-1 Safety – Part 1: General Requirements 1 (2007-07-07) CSA C22.2 60950-1-03 Safety – Part 1: General Requirements 1 (2006-07) FCC Part 68 Terminal Equipment to Telephone Network according
to TIA-968-A and CS-03 Part 1, Issue 9
(2006-11-03)
The last two digits of the year in which the CE marking was affixed: 06
Herewith declares that product(s) listed above is in conformity with
No Title Issue
FCC part 15 Radio frequency devices
Pierre Öberg Technical Manager 26 of May 2008
Page 8
8
6618-2202
Type tests and environmental conditions
Electromagnetic Compatibility
Phenomena Test Description Test levels
ESD EN 61000-4-2 Enclosure contact  ± 6 kV
Enclosure air ± 8 kV
RF field AM   modulated 
IEC 61000-4-3 Enclosure 10 V/m 80% AM (1 kHz), 80 – 1000 MHz
20 V/m 80% AM (1 kHz), 80 – 2000 MHz
RF field 900 MHz ENV 50204 Enclosure 20 V/m pulse modulated 200 Hz, 900 ± 5 MHz
Fast transient EN 61000-4-4 Signal ports ± 2 kV
Power ports ± 2 kV
Surge EN 61000-4-5 Signal ports unbalanced ± 2 kV line to earth, ± 2 kV line to line 
Signal ports balanced ± 2 kV line to earth, ± 1 kV line to line
Power ports ± 2 kV line to earth, ± 2 kV line to line
RF conducted EN 61000-4-6 Signal ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Voltage dips and inter­ruption
EN 61000-4-11 AC power ports 10 & 5 000 ms, interruption
10 & 500 ms, 30% reduction 100 & 1 000 ms, 60% reduction
Mains freq. 50 Hz EN 61000-4-16 Signal ports 100 V 50 Hz line to earth
Voltage dips and   interruption
EN 61000-4-29 DC power ports 10 & 100 ms, interruption
10 ms, 30% reduction 10 ms, 60% reduction +20% above & –20% below rated voltage
Radiated emission  EN 55022 Enclosure Class A
FCC part 15 Class A
Conducted emission EN 55022 AC power ports Class B
FCC part 15 AC power ports Class B
EN 55022 DC power ports Class B
Dielectric strength EN 60950 Signal port to other 
isolated ports
2 kVrms 50 Hz 1 min
Power port to other  isolated ports
3 kVrms 50 Hz 1 min 2 kVrms 50 Hz 1 min (@ rated power <60 V)
Environmental
Temperature Operating –25 to +70°C
Storage & Transport –40 to +70°C
Humidity Operating 5 to 95% relative humidity non condensing
Storage & Transport 5 to 95% relative humidity non condensing
Altitude Operating 2 000 m / 70 kPa
Reliability prediction  (MTBF)
MIL-HDBK-  217F
Operating
Service life Operating 10 year
Vibration IEC 60068-2-6 Operating 7.5 mm, 5 – 8 Hz 
2 g, 8 – 500 Hz
Shock IEC 60068-2-27 Operating 15 g, 11 ms
Packaging
Enclosure UL 94 PC / ABS Flammability class V-1
Dimension W x H x D 55 x 100 x 132 mm
Weight 0.36 kg
Degree of protection IEC 529 Enclosure IP 20
Cooling Convection
Mounting Horizontal on 35 mm DIN-rail
Page 9
9
6618-2202
Description
The TD-36 (485) is designed to function reliably within industrial environments and in  areas of high level interference. 
The TD-36 (485) is a V.34 modem meaning that it can support bidirectional data rates of  up to 33.6 kbit/s on the PSTN or leased line side. Fast connect ensures that leased lines  can re-establish connections in the range of 5 seconds.
The modem is equipped with transient protection on the line side and a “watchdog”  that monitors and automatically resets the modem in the event of a fault. These func­tions together with remote configuration make the modem perfect for installation at  unmanned sites and prevent the need of costly service trips.
The modem also has password protection, dial-back security and caller ID answering to  ensure that only authorised users can communicate with the modem and any connected  equipment.
The TD-36 (485) also has a single digital input and output relay. The input and output can  be used to trigger, or be triggered by a number of different user defined events. Both the  digital input and output are galvanically isolated from the rest of the modem.
For ease of setup the modem is supported by the Westermo TD-tool configuration soft­ware but also has DIP switches to assist configuration. Drivers for Windows setup are  also supplied.
…  Extended temperature range –25°C to +70°C …  Data rate up to 33.6 kbit/s with Fast Connect … Terminal rate up to 115.2 kbit/s …  2-wire Leased Line (also 4-wire Leased Line on TD-36 485) … V23 HDX with multidrop (also FDX on TD-36 485) …  DTR and incoming data dialling …  DIP-switch configuration … Watchdog …  Secure call back and access …  Industrial environment transient protection on all interfaces …  Up to 11 bits … Tri-Galvanic isolation (interface/line/supply)  …  Caller ID presentation and answering …   Remote configuration …   RS-422 / RS-485 interface (only in TD-36 485) …  Digital I/O (only in TD-36 485) …  Dial backup for PSTN and Leased Line (only in TD-36 485)
Page 10
10
6618-2202
Generic I/O
The generic I/O gives the following functionality:
1. Establishing a data connection to a predefined target number
When the input is pulsed, the modem establishes a data connection to the stored   predefined number. After a time (specified in the modem) without data exchange,   the connection is released by an inactivity timer.
2. Sending an SMS Message to a predefined targetnumber
When the input is pulsed, the modem will send an SMS to a predefined number.   The SMS Messages can handle at least 160 characters. TAP and UCP protocols are   supported.
3. Sending a Text Message to a predefined targetnumber
When the input is triggered, the modem will establish a connection to the stored  modem number and transfer a predefined text message. This is not an SMS message.
4. Using the remote digital output
When the input is triggered, the modem will establish a connection to the stored   number of a remote TD-36 and send out a command, that pulses the remote output  according to a predefined sequence. 
5. Executing an AT-Command string 
Pre-programmed AT command strings stored in the modem can be executed.   These can (for example) be used for switching DTE communication parameters for  online and offline modes by using two entries.
6. Transparent I/O 
When the input is triggered, the modem will establish a connection to the stored   number of a remote TD-36 and send out a command, and after a connection is  
established, the I/O is bi-directional.
Page 11
11
6618-2202
Digital Output
The digital output gives the following functionality:
1. Output Contact
The modem has a change over relay output (SPDT-contact). This output can be   controlled by a remote modem through Transparent I/O and Output service in the  Generic I/O function. The output can also be programmed to follow the local DCD   or DTR signals.
2. Remotely controlled
The output can be programmed to follow a remote modem data input. A remote unit  can also set/reset the output as well as transferring a sequence of “set- and resets” of  the output. 
3. Follow DCD/Network
The output can be programmable to follow the local DCD or DTR signal.
Digital Input
The digital input gives the following functionality:
1. Static input
A static digital level trigged input high or low  triggers the Generic I/O. With a level  trigged input only the first entry in the Generic I/O list can be trigged by the I/O input.
The input is trigged when the selected level has been stable for ta ms. A new trig will not  occur until the input has return to the opposite state an back again.
t
a
High level trigged input timing
t
a
Trig
Trig
t
a
Low level trigged input timing
t
a
Trig
No trig due to low level shorter than t
a
t
a
<t
a
Page 12
12
6618-2202
2. Pulsed Input
When input is set to edge trigged pulsed the number of pulses counted selects the entry  to be trigged.
For the pulsing of an input, some timings must be kept.  The input is filtered and pulses shorter than ta is discriminated. The time between pulses 
must also be kept shorter than Tp. One other restriction on Tp is that Tp  2ta.    When time between pulses exceeds Tp the number of pulses are accumulated and an  entry selected by number of pulses counted.
The parameter ta is also used when output pulsing is selected. The parameters ta and Tp are programmable from 10 ms to 2550 ms.
t
a
T
p
>Tp
t
a
T
p
>Tp
Positive edge trigged input timing
Negativ edge trigged input timing
Number of pulses counted accumulated here
Page 13
13
6618-2202
Interface specifications
Power AV
Rated voltage 20 to 250 VDC
24 to 240 VAC
Operating voltage 18 to 300 VDC
22 to 264 VAC
Rated current
125 mA @ 18 VDC    15 mA @ 110 VDC     8 mA @ 250 VDC 120 mA @ 22 VAC   35 mA @ 95 VAC   28 mA @ 240 VAC
Rated frequency DC:  – 
AC: 48 – 62 Hz
Inrush current I
2
t  0.45 A2s
Startup current* 0.25 A
peak
Polarity Polarity independent
Isolation to All other ports 3 kV
rms 50 Hz 1 min
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm
2
 (AWG 24-12)
Shielded cable Not required
Power LV 
Rated voltage 12 to 48 VDC
12 to 27 VAC
Operating voltage 10 to 60 VDC
10 to 30 VAC  48 – 62 Hz
Rated current 150 mA @ 12 VDC 
  70 mA @ 24 VDC    40 mA @ 48 VDC  150 mA @ 12 VAC   70 mA @ 24 VAC
Rated frequency DC: –
AC: 48 – 62 Hz
Inrush current I
2
t  0.25 A2s
Startup current* 0.30 A
peak
Polarity Polarity independent
Isolation to All other ports 3 kV
rms 50 Hz 1 min
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm
2
 (AWG 24-12)
Shielded cable Not required
*  External supply current capability for proper startup
Page 14
14
6618-2202
Public Switched Telephone Network (PSTN)
Electrical specification Public Switched Telephone Network
Data rate 300 bit/s – 33.6 kbit/s
Protocol B103, B212, V21, V22, V22B, V23C, V23 HDX, V32, V32B, V34
Protection Installation Fault Tolerant (up to ±60 V) 
Isolation to Power port   3 kV
rms 50 Hz 1 min
Leased Line   2 kV
rms 50 Hz 1 min
RS-232   2 kV
rms 50 Hz 1 min
RS-485   2 kV
rms 50 Hz 1 min
I/O   2 kV
rms 50 Hz 1 min
Connection RJ-11C and Detachable screw terminal 
Connector size Detachable screw terminal 0.2 – 2.5 mm
2
 (AWG 24 – 12)
Shielded cable Not required
Leased Line (LL)
Electrical specification 2- or 4-wire Leased Line 
Data rate 300 bit/s – 33.6 kbit/s 
Protocol B103, B212, V21, V22, V22B, V23C, V23 HDX, V32, V32B, V34
Transmission range PSTN 30 dB
Budget Leased Line max 40 dB
Protection Installation Fault Tolerant (up to ± 60 V) 
Isolation to Power port   3 kV
rms 50 Hz 1 min
Leased Line   2 kV
rms 50 Hz 1 min
RS-232   2 kV
rms 50 Hz 1 min
RS-485   2 kV
rms 50 Hz 1 min
I/O   2 kV
rms 50 Hz 1 min
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm
2
 (AWG 24 – 12)
Shielded cable Not required
Page 15
15
6618-2202
*   Railway installation close to the rails. 
For a cable located within 3 m and connected to this port, the use of shielded cable is recommended, this is  to minimise the risk of interference. The cable shield should be properly connected (360°) to an earthing point  within 1 m of this port. This earthing point should have a low impedance connection to the conductive enclo­sure of the apparatus cabinet, or similar, where the unit is built-in. This conductive enclosure should be con­nected to the earthing system of an installation and may be directly connected to the protective earth.
RS-422/485 
Electrical specification EIA/TIA-485 ITU V.11
2-wire or 4-wire twisted pair
Data rate 300 bit/s – 115.2 kbit/s 
Data format 7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits.
9-12 bit words 
Protocol Transparent 
Retiming Yes 
Turn around time <10 µs (half duplex)
Transmission range  1200 m, depending on data rate and cable type (EIA RS-485)
Settings 120 W termination and failsafe biasing 680 W
Protection Installation Fault Tolerant (up to ±60 V) 
Isolation to Power port   3 kV
rms 50 Hz 1 min
PSTN Line   2 kV
rms 50 Hz 1 min
Leased Line   2 kV
rms 50 Hz 1 min
I/O   1.5 kV
rms 50 Hz 1 min
Galvanic connection to RS-232
Connection Detachable screw terminal 
Connector size 0.2 – 2.5 mm
2
 (AWG 24 – 12)
Shielded cable Not required* 
Miscellaneous Do not connect RS-232 and RS-422/485 simultaneously
RS-232  
Electrical specification EIA/TIA-232
Data rate 300 bit/s – 115.2 kbit/s
Data format 7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits.
9-12 bit words
Protocol Transparent
Retiming Yes
Transmission range Cable length  15 m
Isolation to Power port   3 kV
rms 50 Hz 1 min
PSTN Line   2 kV
rms 50 Hz 1 min
Leased Line   2 kV
rms 50 Hz 1 min
I/O   1.5 kV
rms 50 Hz 1 min
Galvanic connection to RS-485
Connection 9-pin D-sub female (DCE)  
and Detachable screw terminal (DCE )
Connector size Detachable screw terminal 0.2 – 2.5 mm
2
 (AWG 24 – 12) 
Shielded cable Not required* 
Miscellaneous Do not connect RS-232 and RS-422/485 simultaneously
Page 16
16
6618-2202
Generic I/O interface Input 
Electrical specification Opto isolated input
Input voltage range 0 – 60 VDC
Input current 5 mA @ 60 VDC
Input inactive Uin < 2.5 V
Input active Uin >5.0 V
Transmission range Cable length  15 m
Connection Detachable screw terminal (DCE )
Connector size 0.2 – 2.5 mm
2
 (AWG 24 – 12)
Isolation to Power port  3 kV
rms 50 Hz 1 min
PSTN line  2 kV
rms 50 Hz 1 min
Leased Line  2 kV
rms 50 Hz 1 min
RS-232  2 kV
rms 50 Hz 1 min
RS-485  2 kV
rms 50 Hz 1 min
I/O output  2 kV
rms 50 Hz 1 min
Shielded cable Not required*
Page 17
17
6618-2202
*   Railway installation close to the rails. 
For a cable located within 3 m and connected to this port, the use of shielded cable is recommended, this is  to minimise the risk of interference. The cable shield should be properly connected (360°) to an earthing point  within 1 m of this port. This earthing point should have a low impedance connection to the conductive enclo­sure of the apparatus cabinet, or similar, where the unit is built-in. This conductive enclosure should be con­nected to the earthing system of an installation and may be directly connected to the protective earth.
Generic I/O interface Relay Output 
Electrical specification One change over contact
Switching voltage Max 40 V  AC/DC
Switching current Max 500 mA  AC/DC
Electrical endurancee 5 x 10
5
 operations at 20 W / 20 VA Resistive load
Transmission range Cable length  15 m
Connection Detachable screw terminal (DCE )
Connector size 0.2 – 2.5 mm
2
 (AWG 24 – 12)
Isolation to Power port  3 kV
rms 50 Hz 1 min
PSTN line  2 kV
rms 50 Hz 1 min
Leased Line  2 kV
rms 50 Hz 1 min
RS-232  1.5 kV
rms 50 Hz 1 min
RS-485  1.5 kV
rms 50 Hz 1 min
I/O input  2 kV
rms 50 Hz 1 min
Shielded cable Not required*
Page 18
18
6618-2202
*  Direction relative to this unit. 
Leased Line
Position
D-sub
Screw  
terminal
Direction* Description
D-sub  
description
No. 1 No. 4 Outd Data Carrier Direct (DCD)
No. 2 No. 7 Out Received Data (RD)
No. 3 No. 8 In Transmitted Data (TD)
No. 4 No. 3 In Data Terminal Ready (DTR)
No. 5 No. 1 Not Connected Signal Ground (SG) 
No. 6 No. 2 Out Data Set Ready (DSR)
No. 7 No. 6 In Request To Send (RTS)
No. 8 No. 5 Out Clear To Send (CTS)
No. 9 No. 9 Out Ring Indicator (RI)
RS-232 (DCE)
1 2 3 4 5
6 7 8 9
Position Product marking
RJ-11C
Screw 
terminal**
Direction* Description RJ-11C Screw terminal
a Not Connected
b In/Out PSTN Transmit/ Receive 
Disconnects from “pin c”  when the modem goes  Off-Hook
c No. 2 In/Out PSTN Transmit/ Receive
d No. 1 In/Out PSTN Transmit/ Receive
e In/Out PSTN Transmit/ Receive 
Disconnects from “pin c”   when the modem goes  Off-Hook
f Not Connected
*  Direction relative to this unit.  ** The PSTN screw terminals are shared with 2-wire Leased Line. 
PSTN
LL2
LL1
Position Direction Description Product marking
No. 1 In/Out 2-wire Receive/ Transmit LL1
No. 2 In/Out 2-wire Receive/ Transmit LL2
Page 19
19
6618-2202
Power 
LED Indicators  
(for details see page 22)
*  Direction relative to this unit. 
Position Direction* Description Product marking
No. 1 In AC: Neutral 
DC: –Voltage
No. 2 In AC: Line 
DC: +Voltage
Page 20
20
6618-2202
Leased Line
*  Direction relative to this unit. 
Position
D-sub
Screw  
terminal
Direction* Description
D-sub  
description
No. 1 No. 4 Outd Data Carrier Direct (DCD)
No. 2 No. 7 Out Received Data (RD)
No. 3 No. 8 In Transmitted Data (TD)
No. 4 No. 3 In Data Terminal Ready (DTR)
No. 5 No. 1 Not Connected Signal Ground (SG) 
No. 6 No. 2 Out Data Set Ready (DSR)
No. 7 No. 6 In Request To Send (RTS)
No. 8 No. 5 Out Clear To Send (CTS)
No. 9 No. 9 Out Ring Indicator (RI)
RS-232 (DCE)
1 2 3 4 5
6 7 8 9
Position Product marking
RJ-11C
Screw 
terminal**
Direction* Description RJ-11C Screw terminal
a Not Connected
b In/Out PSTN Transmit/ Receive 
Disconnects from “pin c”  when the modem goes  Off-Hook
c No. 2 In/Out PSTN Transmit/ Receive
d No. 1 In/Out PSTN Transmit/ Receive
e In/Out PSTN Transmit/ Receive 
Disconnects from “pin c”   when the modem goes  Off-Hook
f Not Connected
*  Direction relative to this unit.  ** The PSTN screw terminals are shared with 2-wire Leased Line. 
PSTN
LL2
LL1
Position Direction* Description Product marking
No. 1 Out 4-wire Transmit LL1
In/Out 2-wire Receive/ Transmit
No. 2 Out 4-wireTransmit LL2
In/Out 2-wire Receive/ Transmit
No. 3 In 4-wire Receive LL3
In/Out 2-wire Receive/ Transmit at 
Leased Line PSTN backup
No. 4 In 4-wire Receive  LL4
In/Out 2-wire Receive/ Transmit at 
Leased Line PSTN backup
Page 21
21
6618-2202
RS-422/485 
Power 
I/O Input/Relay Output
LED Indicators  
(for details see page 22)
*  Direction relative to this unit. 
*  Direction relative to this unit
Position Direction* Description Product marking
No. 1 In AC: Neutral
DC: –Voltage
No. 2 In AC: Line
DC: +Voltage
Position Direction* Description Product marking
No. 1 In R+ ( A’) Receive RS-422/485 4-wire R+
No. 2 In R– (B’) Receive RS-422/485 4-wire R–
No. 3 Out T+ (A) Transmit RS-422/485 4-wire T/R+
In/Out T+ (A/A’) Transmit/Receive RS-485 2-wire
No. 4 Out T– (B) Transmit RS-422/485 4-wire T/R–
In/Out T+ (A/A’) Transmit/Receive RS-485 2-wire
Position Direction* Description Product marking
No. 1 In Input + +
No. 2 In Input –
No. 1 In/Out Normal 
closed contact
NC
No. 2 In/Out Common 
contact
C
No. 3 In/Out Normal  
open contact
NO
Page 22
22
6618-2202
LED Indicators
LED Status Description
TD
Transmit data
OFF No data 
ON / FLASH The modem receiving data on the DTE interface
RD
Receive data
OFF No data
ON / FLASH The modem transmitting data on the DTE interface
RTS 
Request   to send
OFF RTS signal is inactive
ON RTS signal is active
DCD
Data carrier   detect
OFF DCD signal is inactive
ON DCD signal is active, modem has detected a carrier or the signal is 
set to always ON
DTR
Data terminal  ready
OFF DTR signal is inactive
ON DTR signal is active
REL
Reliable mode
OFF Reliable mode is OFF, direct or normal mode
ON Reliable mode is ON
FLASH Reliable mode with error correction and compression
LINE OFF The modem is on-hook
ON The modem is off-hook with an established connection
FLASH Line backup interface in use
PWR
Power
OFF The modem has no power 
ON The modem is up and running
Only for TD-36 485
I/O IN OFF The I/O input is inactive 
ON The I/O input is active
I/O OUT OFF The I/O output is inactive, C and NC connected
ON The I/O output is active, C and NO connected
Page 23
23
6618-2202
DIP-switch settings
Before DIP-switch settings:
Prevent damage to internal electronics from electrostatic discharges (ESD)   by discharging your body to a grounding point (e.g. use of wrist strap).
NOTE  DIP-switch alterations are only effective after a power on. 
S4 S3
S5S2S1
S1 DIP-switch  Selection of DTE speed
S1 DIP-switch  Stored values / Auto detect
ON 
 1 2  3 4 5  6 7 8
Use stored values
ON 
 1 2  3 4 5  6 7 8
9600 bit/s
ON 
 1 2  3 4 5  6 7 8
Auto detect*
ON 
 1 2  3 4 5  6 7 8
1200 bit/s
ON 
 1 2  3 4 5  6 7 8
300 bit/s
ON 
 1 2  3 4 5  6 7 8
600 bit/s
ON 
 1 2  3 4 5  6 7 8
2400 bit/s
ON 
 1 2  3 4 5  6 7 8
19.2 kbit/s
ON 
 1 2  3 4 5  6 7 8
38.4 kbit/s
ON 
 1 2  3 4 5  6 7 8
57.6 kbit/s
ON 
 1 2  3 4 5  6 7 8
115.2 kbit/s
ON 
 1 2  3 4 5  6 7 8
4800 bit/s
* 300 and 600 baud not supported
Page 24
24
6618-2202
S1 DIP-switch  Selection of DTE format
ON 
 1 2  3 4 5  6 7 8
7E 1S
ON 
 1 2  3 4 5  6 7 8
7E 2S
ON 
 1 2  3 4 5  6 7 8
7O 1S
ON 
 1 2  3 4 5  6 7 8
7O 2S
ON 
 1 2  3 4 5  6 7 8
8N 1S
ON 
 1 2  3 4 5  6 7 8
8N 2S
ON 
 1 2  3 4 5  6 7 8
8E 1S
ON 
 1 2  3 4 5  6 7 8
8E 2S
ON 
 1 2  3 4 5  6 7 8
8O 1S
ON 
 1 2  3 4 5  6 7 8
8O 2S
ON 
 1 2  3 4 5  6 7 8
Direct mode 8E1 or 8O1. 8O1   in command mode
ON 
 1 2  3 4 5  6 7 8
Direct mode 8E2 or 8O2. 8N2   in command mode
ON 
 1 2  3 4 5  6 7 8
Direct mode 7E1 or 7O1. 8N1   in command mode
ON 
 1 2  3 4 5  6 7 8
Direct mode 7E2 or 7O2.8N2   in command mode
ON 
 1 2  3 4 5  6 7 8
7N 2S
S2 DIP-switch  Leased Line Mode selection
ON 
 1 2  3 4 5  6 7 8
Leased Line disable, PSTN enable
ON 
 1 2  3 4 5  6 7 8
Leased Line answering
ON 
 1 2  3 4 5  6 7 8
Leased Line calling
S2 DIP-switch  DTE interface selection
ON 
 1 2  3 4 5  6 7 8
RS-422/485 disabled,   RS-232 enabled
ON 
 1 2  3 4 5  6 7 8
RS-422/485 enabled,   RS-232 disabled
S2 DIP-switch  RS-422/485
ON 
 1 2  3 4 5  6 7 8
RS-422/485, 2-wire
ON 
 1 2  3 4 5  6 7 8
RS-422/485, 4-wire
Page 25
25
6618-2202
S2 DIP-switch  Selection PSTN backup of Leased Line
ON 
 1 2  3 4 5  6 7 8
Backup of Leased Line disabled
ON 
 1 2  3 4 5  6 7 8
Backup of Leased Line enabled
S2 DIP-switch  Remote configuration control
ON 
 1 2  3 4 5  6 7 8
Use stored values
ON 
 1 2  3 4 5  6 7 8
Remote configuration disabled
S2 DIP-switch  Leased Line 2/4 wire selection
ON 
 1 2  3 4 5  6 7 8
Leased Line 2-wire
ON 
 1 2  3 4 5  6 7 8
Leased Line 4-wire
S2 DIP-switch  Selection of answering/calling mode for PSTN backed up Leased Line
ON 
 1 2  3 4 5  6 7 8
Answering
ON 
 1 2  3 4 5  6 7 8
Calling
S3 DIP-switch  Line mode setting 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
Reliable mode enabled (AT\N2) 
ON 
 1 2  3 4 5  6 7 8
Buffer mode enabled (AT\N0)
S3 DIP-switch  Blind dialing 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
Enable blind dialing (ATX3)
S3 DIP-switch  Dial abort 
ON 
 1 2  3 4 5  6 7 8
Use stored values
ON 
 1 2  3 4 5  6 7 8
Dial abort disabled (AT&A1)
ON 
 1 2  3 4 5  6 7 8
Direct Mode enabled (AT\N1)
Page 26
26
6618-2202
S4 DIP-switch  Auto retrain control 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
Auto retrain disabled (AT%E0)
S4 DIP-switch  Data compression control 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
Data compression disabled  (AT%C0)
S4 DIP-switch  DCD, DTR and DSR control 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
DCD and DSR  always on, DTR  ignored (AT&C0&D0&S0)
S4 DIP-switch  Set modem to factory default
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
Restore factory default setting*
* Don’t leave S4:1 in ON position if not intending to restore factory setting at every power on.
S3 DIP-switch  Flow control DTE interface 
ON 
 1 2  3 4 5  6 7 8
Use stored value for AT&Kn
ON 
 1 2  3 4 5  6 7 8
RTS/CTS flow control enable  (AT&K3)
S3 DIP-switch  PLC parameter setting 
ON 
 1 2  3 4 5  6 7 8
Use stored values 
ON 
 1 2  3 4 5  6 7 8
PLC settings  (ATQ1E0&C1&K0&A1)
S3 DIP-switch  Leased Line termination 
ON 
 1 2  3 4 5  6 7 8
Termination disabled
ON 
 1 2  3 4 5  6 7 8
Termination of Receiver    in 4-wire mode
ON 
 1 2  3 4 5  6 7 8
Termination of Transmitter / Receiver   in 2-wire mode and Transmitter in   4-wire mode
ON 
 1 2  3 4 5  6 7 8
Termination of both Transmitter  and Receiver in 4-wire mode
Page 27
27
6618-2202
S4 DIP-switch  Selection of line speed and modulation
ON 
 1 2  3 4 5  6 7 8
Use saved parameters defined by  AT+MS
ON 
 1 2  3 4 5  6 7 8
V.34, 9600
ON 
 1 2  3 4 5  6 7 8
V.21 300
ON 
 1 2  3 4 5  6 7 8
V.32bis 14400
ON 
 1 2  3 4 5  6 7 8
V.23 1200 hdx
ON 
 1 2  3 4 5  6 7 8
V.34 19200
ON
 1 2  3 4 5  6 7 8
V.22 1200
ON 
 1 2  3 4 5  6 7 8
V.34 24000
ON
 1 2  3 4 5  6 7 8
V.22bis 2400
ON 
 1 2  3 4 5  6 7 8
V.34 28 800
ON
 1 2  3 4 5  6 7 8
V.32bis 4800
ON 
 1 2  3 4 5  6 7 8
V.34 33600
ON
 1 2  3 4 5  6 7 8
V.32bis auto
ON 
 1 2  3 4 5  6 7 8
Automatic line speed
ON 
 1 2  3 4 5  6 7 8
V.32bis 9600
S5 DIP-switch  RS-422/485 termination
No termination
ON 
 1 2  3 4
Factory default
ON 
 1 2  3 4 5  6 7 8
S4
ON 
 1 2  3 4 5  6 7 8
S3
ON 
 1 2  3 4 5  6 7 8
S2
ON 
 1 2  3 4 5  6 7 8
S1
S5
ON 
 1 2  3 4
Termination of R in 4-wire connection
ON 
 1 2  3 4
Termination of both T and R in 2-wire  connection
ON 
 1 2  3 4
Termination of both T and R in 4-wire  connection
ON 
 1 2  3 4
Page 28
28
6618-2202
S1 DIP-switch  Selection of DTE speed 
ON 
 1 2  3 4 5  6 7 8
1200 bit/s
S2 DIP-switch  Leased line mode selection 
ON 
 1 2  3 4 5  6 7 8
1200 bit/s leased line /mulidrop
S4 DIP-switch  V.23 line modulation 
ON 
 1 2  3 4 5  6 7 8
V.23 1200 HDX/FDX
S1 DIP-switch  Selection of DTE-format 
ON 
 1 2  3 4 5  6 7 8
8E1, 8O1, 8O1   in command mode
ON 
 1 2  3 4 5  6 7 8
8E2, 8O2, 8N2   in command mode
ON 
 1 2  3 4 5  6 7 8
7E1, 7O1, 8N1, 8N1   in command mode
ON 
 1 2  3 4 5  6 7 8
7E2, 7O2, 8N2, 8N2   in command mode
S2 DIP-switch  Leased line 2/4-wire selection 
ON 
 1 2  3 4 5  6 7 8
2-wire leased line
ON 
 1 2  3 4 5  6 7 8
4-wire leased line
S3 DIP-switch  Carrier active using RTS or incoming data 
ON 
 1 2  3 4 5  6 7 8
Incoming data
ON 
 1 2  3 4 5  6 7 8
RTS controlled
S4 DIP-switch  Permanent carrier control 
ON 
 1 2  3 4 5  6 7 8
Disabled
ON 
 1 2  3 4 5  6 7 8
Enabled
V.23 2- / 4-wire HDX- / FDX-leased line settings for TD-36 485
Page 29
29
6618-2202
S3 DIP-switch  V.23 leased line termination*
ON 
 1 2  3 4 5  6 7 8
Termination disabled
ON 
 1 2  3 4 5  6 7 8
Termination of transmitter /  receiver in 2-wire mode and  Transmitter in 4-wire mode
ON 
 1 2  3 4 5  6 7 8
Termination of receiver   in 4-wire mode
ON 
 1 2  3 4 5  6 7 8
Termination of both transmitter /  receiver in 4-wire mode
* The leased line should be terminated at the end points.
Termination recommandations of Leased lines   and Dial-up connections
In some connections the communication line (Leased Line or PSTN) must be  terminated. The table below shows the right way to activate the termination  for different usages. As a standard, the receiver in multidrop systems at the end  points shall be terminated.
S3 DIP-switch  Termination recomendations for TD-36 485
ON 
 1 2  3 4 5  6 7 8
PSTN
ON 
 1 2  3 4 5  6 7 8
Multidrop
V23 2-wire – endunit
ON 
 1 2  3 4 5  6 7 8
PSTN
Backup
ON 
 1 2  3 4 5  6 7 8
Multidrop
V23 2-wire – dropunit
ON 
 1 2  3 4 5  6 7 8
2-wire 
Leased Line
ON 
 1 2  3 4 5  6 7 8
Multidrop
V23 4-wire – endunit
ON 
 1 2  3 4 5  6 7 8
4-wire 
Leased Line
ON 
 1 2  3 4 5  6 7 8
Multidrop
V23 4-wire – dropunit
Page 30
30
6618-2202
=Termination
T
D-36 485 
Slave unit Slave unit Slave unit
T
D-36 485
Slave unit Slave unit Slave unit
Max 0.3 metre
=Termination
T+
T–
T+T- T+T- AB
R+
R–
T+
T–
R– R+ R+T– T– B’ A’ BAT+T+ R–
2-wire termination
4-wire termination
RS-422/485 general advice
Termination recommendations
The RS-422/485 line must be terminated. In the TD-36 485, the termination is combined  with fail-safe functionality. The termination is used to prevent undefined states when the  bus is in tri-state condition.
…  Using 2-wire RS-485 both ends should be terminated.  …  Using 4-wire RS-485 both pairs shall be terminated at both ends.   …  Using 4-wire RS-422 it’s only necessary to terminate the receivers.  
RS-422/485 connection pins can be differently named. For some equipment brands   the T+ corresponds to A, but other brands might use some other naming convention.  If a unit does not work it can help to swap A and B.
Page 31
31
6618-2202
CLICK!
10 mm * 
(0.4 inches)
25 mm
25 mm
*  Spacing (left/right) recommended for 
full operating temperature range
Cooling
This unit uses convection cooling. To avoid  obstructing the airflow around the unit, use the  following spacing rules. Minimum spacing 25 mm  (1.0 inch) above /below and 10 mm (0.4 inches)  left /right the unit. Spacing is recommended for  the use of unit in full operating temperature  range and service life.
Removal
Press down the black support at the back of the unit  using a screwdriver,  see figure.
Mounting
This unit should be mounted on 35 mm DIN-rail, which is   horizontally mounted inside an apparatus cabinet, or similar. 
Snap on mounting, see figure.
Page 32
32
6618-2202
Windows configuration tool TD-Tool
The TD-Tool is a PC – application program with a graphical interface for easy configura­tion of the complex functions found on the encolsed CD or at the Westermo website.
Please refer to TD-Tool for a complete description of the functionality of the Windows  program.
AT-Commands
Please refer to the AT Commands Interface Guide found on the enclosed CD or at  the Westermo website for a complete list of all available AT-commands and a detailed  description of the serial AT-command interface.
Configuration
The TD-36 (485) can be configured both from the local DTE interface and remotely over  the PSTN network. Whether  the local or remote interface is used the configuration can  be made  with AT-commands or  with a PC-based application configuration tool. Basic  configurations can also be made with DIP switches locally.Remote configuration
The TD-36 (485) can be configured from a remote modem. To configure a TD-36 (485)  any GSM, ISDN or PSTN modem can be used.
The modem used  to configure is referred as the “local modem”.  Please make sure that the remote TD-36 (485) is connected to the PSTN network and is  powered up.
…  Connect the local modem to it's media (ISDN, PSTN or GSM) …  Connect the PC's com-port to the DTE interface of the local modem. …  Connect the power supply. …  Start a terminal emulation program (i.e. Windows Hyper-Terminal). …  Configure the local modem data rate and word format. …  Set up a connection to the remote TD-36 (485) to be configured by using the 
normal dial command: ATD<No><CR>. When connected send the remote escape  sequence <++++>. The called remote TD-36 (485) will acknowledges by request­ing the remote password. Enter the correct password (default: no password, just  return). Next; configure the remote TD-36 (485) using AT-commands. The pass­word for remote configuration is defined with AT*WRCP – Remote configuration  password.
…  Configure the parameter on the remote TD-36 (485) from your terminal program 
and save the settings with AT&W.
…  Hang up the connection using the ATH command.
Page 33
33
6618-2202
Application examples
…   TD-36 connected to TD-36 with DTR signal call
Configure the units
Set up the connection – The dialling modem
ATA Enter the answer command when RING comes from the network or set up 
ATS0=1 to auto answer on 1 RING signal (or more than 1)
Set up the connection – The answering modem
PSTN 
Network
NOTE:  If no valid DTR signal can be provided by external application, the modems DSR signal can 
be used to trig the transmission. Connect the DSR signal via a relay, or other potential  free contact, to the DTR signal. A 10 kohm pull down resistor should also be connected  between the DTR and a signal that is always low e.g. the DCD.
DTR
DSR
DCD
Relay
External application
10 kohm May be required in harsh environments.
AT&F Set the unit to factory default
AT&W Store default settings
AT&Z0=nnn Store the number of the remote modem in the dialling TD-36
AT&S0 Set DSR signal always high (if this signal is used to trig the DTR)
AT&B1 Activates automatic DTR dialling if DTR switches from low (OFF)  
to high (ON)
AT&W Save settings
Switch DTR from  OFF to ON
The modem will now dial the phone number stored in the first location of  the telephone number table (AT&Z0=<nnn>)
Page 34
34
6618-2202
 …   Frequently used settings for PLC-systems 
Most PLC-systems and other industrial applications where modems are used require the  same changes to the standard settings.
The most commonly encountered problems concern speed, parity and control signals  from the connected equipment.
Speed and parity are changed with the switches under the cover in block S1. If this action  does not solve the problem the modem’s answering codes and possible echoing of com­mands might be the source of the difficulty.
Below follows a list of commands that might resolve the problems. The commands may  of course be placed on one single command line if desired.
Configure the TD-36 connected to the PLC
PSTN 
Network
Note: S3:5 may be used for this purpose.
AT&F Set the unit to factory default.
ATV0 Gives the answering codes in short format. (digits)
ATQ1 No result codes are sent on the RS-232/V.24 connection.
ATE0 Commands that are sent from the terminal/computer etc.  
are not echoed back to the RS-232/V.24 connection.
AT&C1 DCD will follow the carrier on the line.
AT&K0  No handshaking.
AT&A1 Character abort option OFF.
AT&W Store default settings.
Page 35
…   Leased Line connection using 2- or 4-wire
Leased Line connections can be set up using 2-wire (or 4-wire in TD-36 485). When renting a 4-wire line from a telephone company one pair of cables for  
transmission and one pair for reception are usually provided. The maximum transmission distance depends on the attenuation of the line.  
The maximum value is theoretically 30 dBm. To have a good error rate it is   recommended to keep the attenuation under 25 dB. When renting lines from a telephone  company a longer transmission distance is normally possible as the signals are probably  transmitted over PCM-lines, i.e.  fibre optic or other media with low attenuation.
To set the modem for leased line applications use the dip switches.
Configure the units
35
6618-2202
Leased Line
To make switch setting active the power must be cycled OFF  ON.
S2:1, 2 ON
S2:2 ON
Leased line calling
Leased line answering
S2:5 OFF Leased line 2-wire
S1 Sets speed and parity for the RS-232 port.
S4 Decides line-speed. Must be set in direct mode applications.
Resistance, attunation and distance for different wires
Tele Cable Area Resistance for
double cable
Attunation Recommended 
Max distance  (25 dB)
Max Distance (30 dB)
Ø 0,5 mm*  0,2 mm
2
175 W/km 1,1 dB/km 23 km 27 km
Ø 0,6 mm*  0,3 mm
2
123 W/km 0,9 dB/km 28 km 33 km
Ø 0,7 mm*  0,4 mm
2
93 W/km 0,8 dB/km 31 km 38 km
Ø 0,8 mm  0,5 mm
2
73 W/km 0,7 dB/km 36 km 43 km
Ø 0,9 mm  0,64 mm259 W/km 0,6 dB/km 42 km 50 km
* Frequently used in the local network 
Page 36
36
6618-2202
…   TD-36 – Secure Call-back
The TD-36 is connected to a PLC which one want to restrict access to. The TD-36 can  support access control through the Secure Callback function. In this example password  and callback to a predefined number is chosen. The modem in the calling end is here   chosen to be a PSTN modem, but can be any of the PSTN, ISDN or GSM modem from  the Westermo product range.
The DTE serial speed between the PLC – TD-36 and TDW-33 – PC is assumed to be  9600 8N1 but can be chosen to fit the actual system requirement.
Configure the TD-36
PSTN 
Network
AT&F Set the unit to factory default
AT+IPR=9600 DTE baudrate 9600
AT+ICF=3,4 Character framing 8 data, 1 stop, parity none
ATS0=1 Auto answer after first ring
ATQ1E0&C1&K0&A1 Suitable for PLC communication
AT&W Store default settings
AT*WCB=4  Callback enabled, Password and callback number stored  
in one or more positions of wcbtab
AT*WCBTAB=1,”+4670428000”,  ”n3Y9kA6otYZu8”
Define callback number 1 
 When password 1 is entered number +4670428000 will   be called
AT*WCBTIME=10 Define delay time between hangup an callback 
The TD-36 will wait 10s after hangup to callback   to allow the analogue modem to hangup
Page 37
37
6618-2202
Configure the TDW-33 
Set up the connection 
AT&F Set the unit to factory default
AT+IPR=9600 DTE baudrate 9600
AT+ICF=3,4 Character framing 8 data, 1 stop, parity none
ATS0=1 Auto answer after first ring
AT&W Store default settings
The dialling modem  TDW-33
The answering modem TD-36 Comment 
ATD0705123456  TD-36 answers the call and requests 
to TDW-33
Dial the number to TD-36
CONNECT 9600 TD-36 verifies the password to the 
passwords stored and if true com­pare dissconnects. 
Operator/system at   TDW-33 enters   Password: n3Y9kA6otYZu8
NO CARRIER Wait 10 s  The connection is broken and TD-
36 waits the programmed 10s for  TDW-33 to disconnect
TD-36 dials +4670428000  The number programmed cor-
responding to the password is  dialled, preferable it’s the number  to the TDW-33
CONNECT 9600 CONNECT 9600  Connection is established 
between the PC at TDW-33   and the PLC at TD-36
Page 38
38
6618-2202
…   TD-36 – Silent answering on predefined number
The TD-36 is connected to a power meter which is remotely monitored. The TD-36  shares the PSTN line with normal telephones which is preferred not to give a ring signal  when the meter is read.
The TD-36 is configured to answer calls on the Caller ID received, the valid numbers to  answer is programmed into the TD-36. There exists a number of standards for sending  Caller ID check which standard is used by your operator. The TD-36 supports the major  implementations of Caller ID. In this example the DTMF Caller ID version is used.   Note that some implementations doesn’t give the possibility to make a silent answer  since the Caller ID is sent between first and second ring signal. 
The modem in the calling end is here chosen to be a PSTN modem, but can be any of  the PSTN, ISDN or GSM modem from Westermo product range.
Configure the TD-36 connected to the power meter
PSTN 
Network
AT&F Set the unit to factory default
AT+IPR=9600 DTE baudrate 9600
AT+ICF=3,4 Character framing 8 data, 1 stop, parity none
ATS0=0 No auto answer on Ring signals
ATQ1E0&C1&K0&A1 Suitable for PLC communication
AT&W Save settings
AT*WACCTAB=1,”016428000”  AT*WACCTAB=2,”016480250”
Set the valid A-numbers for automatic answering
AT*WCID=3,3 Set Caller ID to A-number answer with DTMF coded numbers
Page 39
39
6618-2202
…   TD-36 485 2-wire half duplex
In this application the TD-36 485 is set to communicate with a number of units with   RS-485 interface.
The communication is 2 wire half duplex at 38.4 kbit/s, 8 data, parity even and 1 stop bit.
To make switch setting active the power must be cycled OFF -> ON.
Te rmination
TD-36 485
1
2
T/R+
T/R-
3
4
PSTN 
Network
Configure the TD-36 485
AT&F Set the unit to factory default
AT&W Store default settings
S2:3 ON RS-422/485 enable RS-232 disable
S2:4 OFF Select 2-wire RS-485
S1:4 ON 38.4 kbit/s
S1:7 ON 8 data bits even parity 1 stop bit
S3:8 ON Termination / Failsafe active
Page 40
40
6618-2202
…   Remote output and transparent mode In this application the TD-36 485 I/O is used to send a SMS and then make an transpar-
ent I/O connection. The transparent I/O is in this example set up to an IDW-90 ISDN  modem, but can be any of the Westermo remote product supporting Generic I/O   (IDW-90, TD-36 485 and GDW-12).
The TD-36 485 has a alarm signal connected to it’s I/O input, when this input is activated  by the external alarm contact an SMS defined by Entry 1 in the entry list is sent. When  the SMS is transferred Entry 2 is programmed to be trigged. Entry 2 is programmed to  set up an Transparent I/O connection to an ISDN-modem IDW-90. The status of the  alarm signal will be transferred to the remote IDW-90 and activate an Alarm bell.   At this time the SMS should be available on the operators mobile showing the reason   for the alarm. The operator can acknowledge the alarm, the acknowledge signal will   now be transferred back to the originating TD-36 485 and alarm system. The alarm   system will deactivate the alarm output causing the remote alarm bell to stop sounding.  The Transparent I/O connection will be terminated by a programmed timeout.
Alarm output
SMS Sending
Connection
Alarm Bell
Timeout
Timeout retrigger
Timeout retrigger
Timeout
Alarm
system
Alarm
output
I/O Input
5 − 48 V
Acknowlidge
output
TD-36 485
5
6
7
8
9
IDW-90
Acknowlidge Button
Alarm Bell
5 − 48 V
I/O
Input
5
6
7
8
9
PSTN 
Network
GSM 
Network
ISDN 
Network
Page 41
41
6618-2202
Configure the TD-36 485
Configure the IDW-90
Testing by simulating the event
Activate events – The sending modem
To make switch setting active the power must be cycled OFF -> ON.
AT&F Set the unit to factory default
AT&W Store default settings
AT*WIOP=10,50,2,3,0  Set I/O params  
Min pulse time = 100 ms (10)   Pulse repetition = 500 ms (150) 
Trig type = Pulsed trigged (2)   Pulse trig type = POS, pos edge (3)   Output type  = No output (0)
AT*WIOL=1,2,5,0,0,070428000,   Temp. high server room,  +4670500899,1
Define SMS message on entry 1 
 Entry = 1 (1)   Service = SMS (2)   Retry = NEXT_ALLWAYS (5)   Timeout = 0   Priority = 0 Data 1 = SMS receiver number (070428000)   Data 2 = SMS text (Temp. high server room)   Data 3 = Service center Adress (+4670500899)   Data 4 = SMS protocol UDP (1)
AT*WIOL=2,7,2,60,0,+4616480250 Define Transparent I/O on entry 2 
Entry = 2 (2)   Service = TRANS (7)   Retry = RETRY_3 (2)   Timeout = 600s (60)   Priority = 0   Data 1 = Phone number of the remote IDW-90  (+4616480250)
S3:1,3,4 OFF S3:2 ON V.110 configured for GSM
I/O input pulsed  with one puls SMS message transferred  
and transparent I/O established
AT*WIOT=1 Force sending of SMS-message at entry 1
AT*WIOT=2 Force the transparent I/O connection to be established
Page 42
42
6618-2202
…   TD-36 485 sending text message with SMS by usage of Generic I/O Configure a TD-36 485 to send different SMS depending  
on the I/O input pulse train.
AT&F Set the unit to factory default
AT&W Store default settings
AT*WIOP=5,10,2,3,0 Set I/O params 
Min pulse time = 50 ms (5)  Max pulse time = 100 ms (10)  Trig type = Pulsed trigged (2)  Pulse trig type = POS, pos edge (3)  Output type = No output (0)
AT*WIOL=2,2,0,0,0,”num1”,”text1”,” providernum1”,1,”password1”
Entry = 2 (2)  Service = SMS (2)  Retry = NO (0)  Timeout = 0  Priority = 0  Data 1 = SMS receiver number (num1)  Data 2 = SMS text (text1)  Data 3 = SMS provider number (providernum1)  Data 4 = SMS protocol type UDP (1)  Data 5 = Password if required by provider (password1)
AT*WIOL=3,2,0,0,0,”num2”,”text2”,” providernum2”,1,”password2”
Entry = 3 (3)  Service = SMS (2)  Retry = NO (0)  Timeout = 0  Priority = 0  Data 1 = SMS receiver number (num2)  Data 2 = SMS text (text2)  Data 3 = SMS provider number (providernum2)  Data 4 = SMS protocol UDP (1)  Data 5 = Password if required by provider (password2)
Configure the TD-36 485
5 – 48 V
Trigging SMS no 2
Trigging SMS no 3
GSM 
Network
PSTN 
Network
Page 43
Testing by simulating the event
Send message
I/O input pulsed with two pulses
SMS message text1 transferred to receiver num1
I/O input pulsed  with three  pulses
SMS message text2 transferred to receiver num2
AT*WIOT=2 Force sending of SMS-message at entry 2
AT*WIOT=3 Force sending of SMS-message at entry 3
Page 44
44
6618-2202
Alarm
system
Alarm
output
I/O Input
5 − 48 V
Acknowlidge
output
TD-36 485
5
6
7
8
9
IDW-90
Acknowledge Button
Alarm Bell
5 − 48 V
I/O
Input
5
6
7
8
9
…   Remote output and transparent mode In this application the TD-36 485 I/O is used to send a SMS and then make a transpar-
ent I/O connection. The transparent I/O is in this example set up to an IDW-90 ISDN  modem, but can be any of the Westermo remote products supporting Generic I/O (IDW­90 or TD-36 485).
The TD-36 485 has a alarm signal connected to it’s I/O-input, when this input is activated  by the external alarm contact an SMS defined by Entry 1 in the entry list is sent. When  the SMS is transferred Entry 2 is programmed to be trigged. Entry 2 is programmed to  set up a Transparent I/O connection to an ISDN-modem IDW-90. The status of the alarm  signal will be transferred to the remote IDW-90 and activate an Alarm bell. At this time  the SMS should be available on the operators mobile showing the reason for the alarm.  The operator can acknowledge the alarm, the acknowledge signal will now be transferred  back to the originating TD-36 485 and alarm system. The alarm system will deactivate the  alarm output causing the remote alarm bell to stop sounding. The Transparent I/O con­nection will be terminated by a programmed timeout.
GSM 
Network
PSTN 
Network
ISDN 
Network
Alarm output
SMS Sending
Connection
Alarm Bell
Timeout
Timeout retrigger
Timeout
retrigger
Timeout
Page 45
45
6618-2202
Configure the TD-36 485
AT&F Set the unit to factory default
AT&W Store default settings
AT*WIOP=10,50,2,3,1 Set I/O params 
Min pulse time = 100 ms (10)  Pulse repetition  = 500 ms (150)  Trig type = Pulsed trigged (2)  Pulse trig type = POS, pos edge (3)  Output type  =  output enabled (1)
AT*WIOL=1,2,5,0,0,”0704 28000”, “Temp. high server  room”,”+4670500899”,1, “password”
Define SMS message on entry 1 
Entry = 1 (1)  Service = SMS (2)Retry = NEXT_ALLWAYS(5)  Timeout = 0  Priority = 0  Data 1 = SMS receiver number (070428000)  Data 2 = SMS text (Temp. high server room)  Data 3 = Service center Adress (+4670500899)  Data 4 = SMS protocol UDP (1)
AT*WIOL=2,7,2,60,0,+4616480250 Define Transparent I/O on entry 2 
Entry = 2 (2)  Service = TRANS (7)  Retry =RETRY_3 (2) ;Do 3 connection attempts  Timeout = 600s  (60)  Priority = 0  Data 1 = Phone number of the remote IDW-90  (+4616480250)
Configure the IDW-90
S3:1,3,4 OFF S3:2 ON V.110 configured for GSM
To make switch setting active the power must be cycled OFF -> ON.
Activate events – The sending modem
IO input pulsed  with one puls SMS message transferred and transparent IO established
Testing by simulating the event
AT*WIOT=1 Force sending of SMS-message at entry 1
AT*WIOT=2 Force the transparent I/O connection to be established.
Page 46
Page 47
Page 48
REV.D  6618-2202    2010.07  Westermo Teleindustri AB, Sweden
Westermo Teleindustri AB • SE-640 40 Stora Sundby, Sweden
Phone +46 16 42 80 00  Fax +46 16 42 80 01 
E-mail: info@westermo.se 
Westermo Web site: www.westermo.com
Westermo Teleindustri AB have distributors in several countries, contact us for further information.
Westermo Data Communications AB  Svalgången 1  SE-724 81 Västerås  Phone: +46 (0)21 548 08 00 • Fax: +46 (0)21 35 18 50  info.sverige@westermo.se
Westermo Data Communications Ltd  Talisman Business Centre • Duncan Road  Park Gate, Southampton • SO31 7GA  Phone: +44(0)1489 580-585 • Fax.:+44(0)1489 580586  E-Mail: sales@westermo.co.uk
Westermo Data Communications GmbH  Goethestraße 67, 68753 Waghäusel  Tel.: +49(0)7254-95400-0 • Fax.:+49(0)7254-95400-9  E-Mail: info@westermo.de  
Westermo Data Communications S.A.R.L.  9 Chemin de Chilly 91160 CHAMPLAN  Tél : +33 1 69 10 21 00 • Fax : +33 1 69 10 21 01  E-mail : infos@westermo.fr 
Westermo Data Communications Pte Ltd  2 Soon Wing Road #08-05  Soon Wing Industrial Building  Singapore 347893  Phone +65 6743 9801 • Fax +65 6745 0670  E-Mail: sales@westermo.com.sg 
Subsidiaries
Loading...