Westermo TD-29P User Manual

Multidropp 2-tråd
Multidrop 2-wire
Multidrop 2-Draht
Multipoints 2-fils
INSTALLATIONSANVISNING
INSTALLATION MANUAL
INSTALLATIONS ANLEITUNG
6611-2022
www.westermo.com
TD-29P
FSK-modem
©
Westermo Teleindustri AB • 2004 • REV. A
Galvanic Isolation
Transient
Protection
Balanced
Transmission
CE
Approved
GB.16 6611-2022
Contents
1. Safety .............................................................................................................................................................................. 17
2. Approvals
................................................................................................................................................................... 17
2.1 Declaration of Conformity ........................................................................................................................ 18
3. Introduction
........................................................................................................................................................... 19
4. Specifications
............................................................................................................................................. 20–21
4.1 Interfaces ................................................................................................................................................................. 20
4.2 Isolation between interfaces .................................................................................................................... 21
4.3 Environmental ..................................................................................................................................................... 21
4.4 Mechanical .............................................................................................................................................................. 21
5. Maintenance
.......................................................................................................................................................... 22
6. Installation
..................................................................................................................................................... 22–26
6.1 Mounting / Removal ........................................................................................................................................ 22
6.2 Connections .......................................................................................................................................................... 23
6.3 LED Status Indicators ................................................................................................................................... 23
6.4 RS-485 Interface ................................................................................................................................................ 24
6.5 Line Interface ....................................................................................................................................................... 24
6.6 Power Interface .................................................................................................................................................. 24
6.7 Configuration ....................................................................................................................................................... 25
6.7.1 DIP switch settings .................................................................................................................... 25–26
7. Functional description
................................................................................................................... 27–28
7.1 Block diagram ...................................................................................................................................................... 27
7.2 RS-485 connection ........................................................................................................................................... 27
7.3 Line connection .................................................................................................................................................. 28
GB.176611-2022
2. Approvals
Conformity with the Directive 89/336/EEC Electromagnetic Compatibility (EMC) has been assessed by application of standards EN 61000-6-2 (industrial immunity) EN 61000-6-4 (industrial emission).
1. Safety
General:
Before using this unit, read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this unit.
Before installation, maintenance or modification work:
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap). Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains supply and all other electrical connections.
Installation:
This unit should only be installed by qualified personnel. This unit should only be installed in a “restricted access area”, for example a lockable cabinet where access is restricted to service personnel only.
This unit is intended for permanent connection to the AC/DC mains supply. The power supply wiring must be sufficiently fused, and if necessary it must be
possible to disconnect manually from the AC/DC mains supply. Ensure compliance to national installation regulations.
Units with the rated voltage exceeding 42.4 V peak or 60 VDC, are defined as class I equipment with a protective earthing conductor terminal.
Units with the rated voltage up to 42.4 V peak or 60 VDC, are defined as class III equipment and shall be separated from hazardous voltage by double or reinforced insulation.
This unit uses convection cooling.To avoid obstructing the air flow around the unit, follow the spacing recommendations (see Installation section).
!
!
!
GB.18 6611-2022
2.1 Declaration of Conformity
GB.196611-2022
3. Introduction
The TD-29P is designed for communication on 2-wire copper cable (twisted pair). Multidrop or point to point half duplex communication is possible at baud rates, 9600 bit/s and 19.2 kbit/s.
The TD-29P is easy to configure for different operating conditions with DIP-switches. Character format, baud rate, transmission level and DCD detection level can be selected. DTE-equipment can be connected through an RS-485 interface.There are two baud rate settings.The maximum bus length in multidrop configuration is dependent on the number of units connected.
The TD-29P is designed to be used on dedicated lines and is not approved to European standard CTR-15 (2-wire leased line).
Transmission Range
speed point to point Signal loss Loss per unit (bit/s) (km) (dB/km) (multidropp) (dB)
9 600 11 2.1 0,3
19 200 9 2,5 0,4
Measured with Cat.5 cable UTP 4x2x24 AWG. Signal level >-24 dBm.The bus length depends on th line quality.
PROFIBUS DP PROFIBUS DP
Dedicated Line
PROFIBUS DP
GB.20 6611-2022
4. Specifications
4.1 Interfaces
Power
TD-29P DC
Rated voltage 24 VDC Operating voltage 12–36 VDC Rated current 200 mA Rated frequency DC (Reverse polarity protected) Connection 2-pos. screw terminal Connector size 0.2–2.5 mm2 (AWG 24-12)
RS-485
Electrical specification RS-485 Data rate 9 600 bit/s–19.2 kbit/s Connection Screw terminal Connector size 0.2–2.5 mm
2
(AWG 24-12)
Circuit type TNV-1
FSK-Line
Electrical specification – Data rate 9 600 bit/s–19.2 kbit/s Connection Screw terminal Connector size 0.2–2.5 mm
2
(AWG 24-12)
Circuit type TNV-3
GB.216611-2022
4.2 Isolation between interfaces
Power to all other 1.5 kV RMS @ 50Hz and 60 s duration FSK-Line to all other 1.5 kV RMS @ 50Hz and 60 s duration
4.3 Environmental
Temperature, operating 5–50°C Temperature,
storage and transportation –40 to +85°C Relative humidity, operating 0 to 95% (non-condensing) Relative humidity, 0 to 95%
storage and transportation (condensation allowed outside packaging)
4.4 Mechanical
Dimension (W x H x D) 55 x 100 x 128 mm Weight 0.5 kg Mounting 35 mm DIN-rail Degree of protection IP 20 (IEC 529)
GB.22 6611-2022
5. Maintenance
No maintenance is required, as long as the unit is used as intended within the specified conditions.
6. Installation
6.1 Mounting / Removal
Before mounting or removing the unit:
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap).
Prevent access to hazardous voltages by disconnecting the unit from AC/DC power supply and all other electrical connections.
Mounting
This unit should be mounted on 35 mm DIN-rail which is horizontally mounted on a wall or cabinet backplate.
This unit uses convection cooling.To avoid obstructions to the airflow around the unit, use the following spacing rules. Recommended spacing 25 mm (1.0 inch) above/below and 10 mm (0.4 inches) left/right the unit.
Snap on mounting, see figure
Removal
Press down the black support at the back of the unit using a screwdriver, see figure.
Min
10 mm
(0.4 inches)
CLICK!
GB.236611-2022
6.3 LED Status Indicators
PWR LED on Power on
LED off Power off
TD LED on Transmit line data active
LED off Transmit line data inactive
RD LED on Receive line data active
LED off Receive line data inactive
DCD LED on Data Carrier Detect active
LED off Data Carrier Detect inactve
6.2 Connections
Line connection
Power supply
RS-485 Interface
LED indicators
GB.24 6611-2022
2-position
Screw terminal Direction Description
1 In/Out 2 In/Out
9-position ITU-T V.11
Screw terminal Direrction Description Description
7 In/Out A (T+) Transmitter/Receiver 6 In/Out B (T–) Transmitter/Receiver
Connection Description Description
1 0 VDC 2 + 12–36 VDC
6.4 RS-485 Interface
5678943
2
1
The definition of R+/R–,T+T– can vary between different manufacturers.
6.5 Line Interface
Transmitter/Receiver Transmitter/Receiver
6.6 Power Interface
1
2
1
2
GB.256611-2022
6.7 Configuration
6.7.1 DIP switch settings
DIP-switches are accessable under the lid on top of the unit. DIP-switches are used to configure the modem.
Warning!
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap), before the lid on top of the modem is removed.
Warning! Do not open connected equipment.
Prevent access to hazardous voltages by disconnecting the unit from AC/DC power supply and all others electrical connections.
NOTE
When configuring via DIP-switches, the settings of DIP-switches configure the unit only after a power reset.A setting configured by any other method during normal operation, overrides the DIP-switch setting. However, at power up, the DIP-switch settings have precedence over the setting configured by any other method.
123 456789
S1:1–8
S2:1–4
!
!
GB.26 6611-2022
Factory setting
Termination of RS-485*
Character format
S1
10 bits
ON
12345678
S1
11 bits
ON
12345678
Selection of Baud rate
S1
9 600 bit/s
ON
12345678
S1
19.2 kbit/s
ON
12345678
Termination of the line*
S1
No termination
ON
12345678
S1
Termination
ON
12345678
Selection of transmission level*
S1
–9 dBm
ON
12345678
S1
5 dBm
ON
12345678
Selection of
minimum detection level
S1
–30 dBm
ON
12345678
S1
–20 dBm
ON
12345678
S1: 5 and 8 not used
* Load 600
S2
No termination
ON
1234
S2
Termination
ON
1234
S1
ON
12345678
S2
ON
1234
* The line should be terminated at the end points.
* The line should be terminated at the end points. S2: 1 and 2not used
Switch block 1 – S1
Switch block 2 – S2
GB.276611-2022
7. Functional description
7.1 Block diagram
7.2 RS-485 connection
Amplifier S1:6
S1:7
RD
LED
DCD
LED
BA
Screw terminal
12345 678
0V
F1
0V
+5V
–5V
0V S2:4
S2:3
5V 0V
9
TD
LED
MCU
1–5, 7–9 not used
FSK
Demodulator
Isolated
Power Supply
S1:4 0V
0V
PWR
LED
Line
switch
Line
Power Supply
2-wire
7 6
A/A’ B/B’ B/B’
A/A’
Twisted pair
TD-29P
RS-485 equipment
Transmitter/ Receiver
Transmitter/ Receiver
GB.28 6611-2022
POWER
LINE CONNECTION
PWR
TD
RD
RTS
CTS
DCD
+
–
POWER
LINE CONNECTION
PWR
TD
RD
RTS
CTS
DCD
+
–
POWER
LINE CONNECTION
PWR
TD
RD
RTS
CTS
DCD
+
–
POWER
LINE CONNECTION
DCD
+
–
7.3 Line connection
Multidrop half duplex with TD-29P
2-position detachable screw terminal
Termination to be set with DIP-switches
GB.296611-2022
OWN COMMENTS
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
.....................................................................................................................................................................................................................
T04-0340 • 6611-2022 04.11 Mälartryck AB, Eskilstuna, Sweden
Westermo Teleindustri AB • SE-640 40 Stora Sundby, Sweden
Phone +46 16 42 80 00 Fax +46 16 42 80 01
E-mail: info@westermo.se
Westermo Web site: www.westermo.com
Westermo Teleindustri AB have distributors in several countries, contact us for further information.
Westermo Data Communications Ltd Talisman Business Centre • Duncan Road Park Gate, Southampton • SO31 7GA Phone: +44(0)1489 580 585 • Fax.:+44(0)1489 580586 E-Mail: sales@westermo.co.uk
Westermo Data Communications GmbH Goethestraße 67, 68753 Waghäusel Tel.: +49(0)7254-95400-0 • Fax.:+49(0)7254-95400-9 E-Mail: info@westermo.de
Westermo Data Communications S.A.R.L. 9 Chemin de Chilly 91160 CHAMPLAN Tél : +33 1 69 10 21 00 • Fax : +33 1 69 10 21 01 E-mail : infos@westermo.fr
Subsidiaries