Ethernet switch and router
approved for railway usage
www.westermo.com
Software tools
Related software tools are available in the folder software tools under
technical support on the Westermo website.
License Information
This device contains public available software which is under the GPL lincense.
For more information see legal.pdf included with all firmware releases.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit, http://www.openssl.org
Legal information
The contents of this document are provided “as is”. Except as required by applicable
law, no warranties of any kind, either express or implied, including, but not limited to,
the implied warranties of merchantability and fitness for a particular purpose, are made
in relation to the accuracy and reliability or contents of this document. Westermo
reserves the right to revise this document or withdraw it at any time without prior
notice.
Under no circumstances shall Westermo be responsible for any loss of data or income
or any special, incidental, and consequential or indirect damages howsoever caused.
More information about Westermo can be found at the following Internet address:
http://www.westermo.com
2
6641-2222
Safety
!
!
Before installation:
Read this manual completely and gather all information on the unit. Make sure
that you understand it fully. Check that your application does not exceed the safe
operating specifications for this unit.
This unit should only be installed by qualified personnel.
This unit should be built-in to an apparatus cabinet, or similar, where access is
restricted to service personnel only. The power supply wiring must be sufficiently
fused, and if necessary it must be possible to disconnect manually from all power
supply. Ensure compliance to national installation regulations. This unit relies on
convection heating. Make sure that it is installed so that the ambient temperature
is within the specified temperature range, e.g. by avoiding obstruction of the
airflow around the unit. Also check chapter CEN/TS 45545-2 mounting notes.
Before mounting, using or removing this unit:
Prevent access to hazardous voltage by disconnecting the unit from all power supply.
WARNING
Do not open connected unit. Hazardous voltage may occur within this unit when
connected to power supply.
Before powering-up, a protective earthing conductor must be connected to the
protective earthing terminal and have a cross-sectional area of at least 1.5 mm².
Note that this unit can be connected to two different power sources.
When this unit is operated at an ambient temperature above +60°C (+140°F), the
External Surface of Equipment may exceed Touch Temperature Limit according to
EN/IEC/UL 60950-1. To reduce the risk of fire, use only No. 26 AWG or larger
telecommunication line cord.
6641-2222
3
Care recommendations
Follow the care recommendations below to maintain full operation of unit and to fulfill
the warranty obligations:
…Do not attempt to dissassemble the unit. There are not any user serviceable
parts inside.
…Do not drop, knock or shake the unit. Rough handling above the specification
may cause damage to internal circuit boards.
…Do not use harsh chemicals, cleaning solvents or strong detergents to clean the
unit.
…Do not expose the unit to any kind of liquid (water, beverages, paint etc),
unless all connectors are connected or fitted with protective caps (delivered
with the unit), tightened to the specified torque. Connected cables must have
the appropriate ingress protection code.
…Do not use or store the unit in dusty or dirty areas, unless all connectors and
the ventilation membrane are sufficiently protected.
…Do not cover or bring mechanical force to the ventilation membrane on the
back of the unit.
If the unit is not working properly, contact the place of purchase, nearest Westermo
distributor office or Westermo Tech support.
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified
conditions.
4
6641-2222
Agency approvals and standards compliance
TypeApproval / Compliance
EMCEN 50121-3-2, Railway applications – EMC: Rolling stock – Apparatus
Railway applications, Approval/Compliance – EN 50155
Railway applications – Electronic equipment used on rolling stock
SafetyEN 60950-1, IT equipment
6641-2222
5
Declaration of Conformity
Org.nr/
Westermo Teleindustri AB
Declaration of conformity
The manufacturer
Herewith declares that the product(s)
Type of product Model Art no
EN 50155 Backbone Routing Switch RFR-12-FB 3641-1630
is in conformity with the following EC directive(s).
No Short name
2004/108/EC Electromagnetic Compatibility (EMC)
2006/95/EC Low voltage (LVD)
2011/65/EU Restriction of the use of certain hazardous substances in electrical and
References of standards applied for this EC declaration of conformity.
No Title Issue
EN 50121-3-2 Railway applications - Electromagnetic compatibility -- Rolling
EN 60950-1 Information technology equipment - Safety -- General
The last two digits of the year in which the CE marking was affixed: 12
Westermo Teleindustri AB
SE-640 40 Stora Sundby, Sweden
RF field AM modulatedEN 61000-4-3Enclosure RF immunity20 V/m
Fast transientsEN 61000-4-4Signal port immunity±2 kV
SurgesEN 61000-4-5Power port immunity±2 kV (L-E)
EN 50155:2001Power port immunity±8.4 kV (L-E)
Conducted RF emisionEN 61000-4-6Signal port immunity10 V/m
Power frequency magnetic field EN 61000-4-8Enclosure immunity300 A/m
Pulsed magnetic fieldEN 61000-4-9Enclosure immunity300 A/m
Voltage interruptionEN 50155Residual voltage 0%10 ms
Supply overvoltage and
undervoltage
Radiated emissionEN 55011
Conducted emissionEN 55011
Environmental
TemperatureOperating–40 to +70°C* (–40 to +158°F)
HumidityOperating5 to 95% relative humidity
AltitudeOperating2 000 m / 70 kPa
Reliability prediction (MTBF)MIL-HDBK- 217FOperating306 115 h
ShockIEC 60068-2-27Operating10 g, 30 ms Half sine ±3 shocks
Packaging
Dimension W x H x D175 x 100 x 144 mm
Weight2295 g
Degree of protectionIEC 529EnclosureIP65**
CoolingConvection
MountingRear panel wall mounting
* Refer to “Safety” section
** Provided all connectors are connected with IP65 cabling or fitted with protective caps (delivered with the unit),
tightened to the specified torque
Residual voltage 60%
Enclosure measurement40 dBµV/m QP
Power port measurement 99 dBµV QP
Signal port measurement 99 dBµV QP
Storage & Transport–40 to +70°C (–40 to +158°F)
Storage & Transport5 to 95% relative humidity
Non operating11.4 m/s²
±6 kV
±8 kV
80 – 2700 MHz
±1 kV (L-L)
±8.4 kV (L-L)
0.15 – 80 MHz
0.15 – 80 MHz
0, 16.7, 50 Hz
100 ms & 1000 ms
100 ms
30 – 230 MHz
47 dBµV/m QP
230 – 1000 MHz
0.15 – 5 MHz
93 dBµV QP
5 – 30 MHz
0.15 – 5 MHz
93 dBµV QP
5 – 30 MHz
2.0 m/s² Longit. 2.0 m/s²
6641-2222
7
Description
Functional description
RFR-12-FB is switch developed for rail on board and industrial applications approved
according to EN 50155. To meet the environmental requirements from rail and harsh
industrial applications the switch has rugged M12 Ethernet connectors and full metal
housing. The switch fulfill IP 65 degree of protection. Our unique FRNT (Fast Recovery
of Network Topology) technology is the fastest protocol on the market to re-configure
a network in the event of any failure of a link or hardware. Real-time properties are
implemented in the RFR-12-FB in order to achieve determinism for real time critical
applications. The switch also supports QoS (Quality of Service) with four priority queues
and strict priority scheduling as well as HoL (Head of Line Blocking Prevention). All to
assure that the data network is deter ministic. RFR-12-FB also has a by-pass relay that
by-pass the unit in case of power loss to the switch.
8
6641-2222
Interface specifications
Power
Rated voltage24 to 110 VDC
Operating voltage16.8 to 143 VDC
(14.4 to 154 VDC for 100 ms)
Rated current580 mA @ 24 VDC
140 mA @ 110 VDC
Inrush current5 mA²s @ 24 VDC
22 mA²s @ 110 VDC
Startup current
(Power source capability)
PolarityReverse polarity protected
Redundant power inputNo
Isolation toAll interfaces and chassis
Galvanic connection toNone
ConnectionM12 A-coded male
Connector size0.2 – 2.5 mm² (AWG 24 – 13)
Shielded cableNot required
Shielded cableNot required
Miscellaneous–
600 mA @ 24 VDC
275 mA @ 110 VDC
21
M12 A-Coded Power Connector
34
PositionDirection Description
1U+Positive supply voltage
2––
30 V0 V
4––
HousingShieldChassis of product (ground)
6641-2222
9
Ethernet TX (both switch, router and coupler ports)
The agency approvals and standards compliance of the RFR-12 are valid with the
WESTERMO USB configuration plug 3641-0190 attached. Only WESTERMO USB
plugs are allowed for use together with this product.
6641-2222
11
Location of Interface ports, LED's
USB / Configuration
LED indicators
Earth connect
LED indicators
Ethernet
LED indicators
Power
12
6641-2222
LED indicators
LEDStatusDescription
ONOFFUnit has no power.
GREENAll OK, no alarm condition.
REDAlarm condition, or until unit has started up.
BLINKLocation indicator ("Here I am!"). Activated when connected to IPConfig Tool,
FRNTOFFFRNT disabled.
GREENFRNT OK.
REDFRNT Error.
BLINKUnit configured as FRNT Focal Point.
RSTPOFFRSTP disabled.
GREENRSTP enabled.
BLINKUnit selected as RSTP root switch.
USR 1OFF(Configurable) VPN disabled.
GREEN(Configurable) Default: At least one VPN tunnel up and OK.
RED(Configurable) Default: All VPN tunnels down.
X1 to X12 OFFNo Link.
GREENLink established.
GREEN FLASH Data traffic indication.
YELLOWPort alarm and no link. Or if FRNT, RSTP or Link Aggregation mode,
(Alarm conditions are configurable, see ''WeOS Management Guide'').
or upon request from Web or CLI.
port is blocked.
6641-2222
13
By-Pass functionality
The by-pass functionality in RFR-12-FB secures connection in case of power failure in
one of the switches. If a switch has power loss an internal relay in RFR-12-FB will by-pass
the switch and bridge two Ethernet ports.
By-pass interfaces
In case of power failure X9 will be by-passed to X11 and X10 will be by-passed to X12.
Internally the switch will bypass
X9.1
X9.2X11.1
X9.3X11.4
X9.4X11.3
X10.1X12.2
Connected to
X10.2X12.1
X10.3X12.4
X10.4X12.3
Note! Make sure that the maximum distance between switches will not exceed the
standard (100 m) in case of by-passing one or more switches.
X11.2
X9
X11
X12
Switch 1Switch 2Switch 3
X11
X12
X10
X9
X10
14
6641-2222
Mounting
There are four 6 mm bore holes intended for mounting the unit. The unit can be
mounted vertical or horizontal. Use four M5 screws with 12 mm washer on a flat and
stable surface.
Connection of cables
Recommended tightening torque for the M12 connectors: 0.6 Nm.
Note that unused connectors must be covered by a protective cap (delivered with the
unit), tightened to the specified torque, in order to fulfill the specified ingress protection
code.
Removal
Disconnect all cables and unscrew the unit from the wall.
Time For Replacement < 15 minutes
Cooling
This unit relies on convection cooling. Make sure that it is installed so that the ambient
temperature is within the specified temperature range, e.g. by avoiding obstruction of
the airflow around the unit.
6641-2222
15
Dimensions
142 ±1 11 ±1
164 ±1
175 ±1
22 ±1
28 ±0,5
M5
2,5 ±0,5
100 ±1
56 ±0,5
6,5
-0
0,5
(4x)
0
24,5
15,5
31
46,5
62
77,5
93
0
18,4
36,8
55,2
22,4
11,5 ±0,5
3 ±0,5
133,0 ±1,5
144,5 ±1,5
Material / Remark
Designation / Dimension
Description
Quantity
Pos No
1:1.5
Scale
Status
Designer
Drawing No.
PaPu
Sheet
1(1)
Denomination
RFR-series
Approved
Date
130225
ToDu
ToDu
130225
Created
01
PaPu
Approved
Date
Rev
Designer
Description
Measurements are stated in millimeters.
16
6641-2222
Getting Started
This product runs Westermo Operating System (WeOS) which provides several
management tools that can be used for configuration of the unit.
• IPConfig tool
This is a custom Westermo tool used for discovery of attached Westermo units.
• Web
Configuration of the unit using the web browser.
• CLI
Configuration of the unit via the Command Line Interface.
If the computer is located in the same subnet as the switch you can easily use a web
browser to configure the unit. Within the web you can configure most of the available
functions.
For advanced network settings and more diagnostic information, please use the CLI.
Detailed documentation is available in the chapter ”The Command Line Management
Tool” in the WeOS management guide.
Factory default IP address:192.168.2.200
Netmask:255.255.255.0
Gateway:Disabled
Note! If you are not sure about the subnet – consult your network administrator.
Configuration
Configure the unit via Webbrowser
The unit can easily be configured via a Web browser.
Open the link http://192.168.2.200 in your web browser, and you will be prompted with
a Login screen, where the default settings for Username and Password are:
Username: admin
Password: westermo
Once you have logged in, you can use the extensive integrated help function describing
all configuration options. Two common task when configuring a new switch is to assign
appropriate IP settings, and to change the password of the admin account.
The password can be up to 64 characters long, and should consist of printable ASCII
characters (ASCII 33-126); 'Space' is not a valid password character.
Note! Version of IP Config tool must be 10.4 or higher.
6641-2222
17
Referring documents
TypeDescriptionDocument number
Management GuideWestermo OS management guide
6101-3201
Factory default on RFR-12-FB
It is possible to set the unit to factory default settings by using Ethernet M-12 cables.
1. Power off the switch and disconnect all Ethernet cables.
2. Connect the first Ethernet cable between Ethernet port X1 and Ethernet port X6.
Then connect the second Ethernet cable between Ethernet port X2 and Ethernet
port X5.
The ports need to be connected directly by an Ethernet cable, i.e., not via a hub or
switch. Use a straight cable – not a cross-over cable – when connecting the ports.
3. Power on the unit.
4. Wait for the unit to start up. Control that the ON LED is flashing red.
The ON LED flashing indicates that the unit is now ready to be reset to factory
default. You now have the choice to go ahead with the factory reset, or to skip
factory reset and boot as normal.
• Go ahead with factory reset:
Acknowledge that you wish to conduct the factory reset by unplugging one of the
Ethernet cables. The ON LED will stop flashing.
This initiates the factory reset process*, and the unit will restart with factory
default settings. When the switch has booted up, the ON LED will show a green
light, and is now ready to use.
• Skip the factory reset:
To skip the factory reset process, just wait for approximately 30 seconds
(after the ON LED starts flashing RED) without unplugging the Ethernet cable.
The switch will conduct a normal boot with the existing settings.
* Note Do not power off the unit while the factory reset process is in progress.
18
6641-2222
6641-2222
19
Westermo • SE-640 40 Stora Sundby, Sweden
Tel +46 16 42 80 00 Fax +46 16 42 80 01
Sales Units
Westermo Data Communications
E-mail: info@westermo.com
www.westermo.com
China
sales.cn@westermo.com
www.cn.westermo.com
France
infos@westermo.fr
www.westermo.fr
Germany
info@westermo.de
www.westermo.de
For complete contact information, please visit our website at www.westermo.com/contact or scan the QR code
REV. E 6641-2222 2015-05 Westermo Teleindustri AB, Sweden – A Beijer Electronics Group Company
North America
info@westermo.us
www.westermo.us
Singapore
sales@westermo.com.sg