West Control Solutions Pro-4 User Manual

Page 1
West Pro-4 user manual – 59559
Page 2
û
BlueControl
More efficiency in engineering,
more overview in operating:
The projecting environment for the BluePort
controllers
Description of symbols:
g General information a General warning l Attention: ESD sensitive devices
© PMA Prozeß- und Maschinen-Automation GmbH Printed in Germany
All rights reserved. No part of this document may bereproduced or published in any form
or by any means without prior written permission from the copyright owner.
A publication of PMA Prozeß- und Maschinen Automation
P.O.Box 310229
D-34058 Kassel
Page 3
Contents
1 Mounting ..............................5
2 Electrical connections .......................6
2.1 Connecting diagram .......................6
2.2 Terminal connection.........................7
3 Operation .............................11
3.1 Front view ............................11
3.2 Behaviour after power-on .....................12
3.3 Operating level ...........................12
3.4 Error list / Maintenance manager .................13
3.5 Self-tuning .............................16
3.5.1 Preparation for self-tuning .......................16
3.5.2 Optimization after start-up or at the set-point ..............17
3.5.3 Selecting the method ( ConF/ Cntr/ tunE).............17
3.5.4 Step attempt after start-up ......................18
3.5.5 Pulse attempt after start-up .......................18
3.5.6 Optimization at the set-point ......................18
3.5.7 Optimization at the set-point for 3-point stepping controller ......20
3.5.8 Self-tuning start .............................21
3.5.9 Self-tuning cancellation ........................21
3.5.10 Acknowledgement procedures in case of unsuccessful self-tuning . 22
3.5.11 Examples for self-tuning attempts ..................23
3.6 Manual self-tuning .........................24
3.7 Second PID parameter set .....................25
3.8 Alarm handling...........................26
3.9 Operating structure.........................28
4 Configuration level ........................29
4.1 Configuration survey ....................29
4.2 Configuration parameters ....................30
4.3 Set-point processing ........................43
4.3.1 Set-point gradient / ramp ........................43
4.4 Switching behaviuor ........................44
4.4.1 Standard ( CyCl= 0 ) .........................44
4.4.2 Switching attitude linear ( CyCl= 1 ).................44
KS 90-1 / KS 92-1 3
Page 4
4.4.3 Switching attitude non-linear ( CyCl= 2 )...............45
4.4.4 Heating and cooling with constant period ( CyCl= 3 )........46
4.5 Configuration examples ......................47
4.5.1 On-Off controller / Signaller (inverse) .................47
4.5.2 2-point controller (inverse) .......................48
4.5.3 3-point controller (relay & relay) ....................49
4.5.4 3-point stepping controller (relay & relay) ...............50
4.5.5 Continuous controller (inverse) .....................51
4.5.6 ∆ - Y - Off controller / 2-point controller with pre-contact ......52
4.5.7 Continuous controller with position controller .............53
4.5.8 Measured value output .........................54
5 Parameter setting level ......................55
5.1 Parameter survey ........................55
5.2 Parameters .............................56
5.3 Input scaling ............................59
5.3.1 Input Inp.1 and InP.3 .............60
5.3.2 Input InP.2...............................60
6 Calibration level .........................61
7 Special functions .........................64
7.1 DAC®– motor actuator monitoring ...............64
7.2 O2measurement ..........................66
7.2.1 Connection ...............................66
7.2.2 Configuration: ..............................67
7.3 Linearization ............................68
7.4 Loop alarm .............................69
7.5 Heating current input / heating current alarm ...........69
7.6 KS90-1 as Modbus master .....................70
7.7 Back-up controller (PROFIBUS) .................70
8 BlueControl ............................71
9 Versions ..............................72
10 Technical data ..........................73
11 Safety hints ............................77
11.1 Resetting to factory setting, ....................78
4 KS 90-1 / KS 92-1
Page 5
1 Mounting
9
min.48 (1.89")
92
Mounting
+0,8
10
(3.78")
96
48 (1.89")
max.
(0.4")
118
1199
1199
°C
°C
°F
°F
para
para
func
func
Ada
Ada
Err
Err
F
F
è
KS 92-1 advanced
KS 90-1
60°C
0°Cmin.
(4.65")
123
1234
1200
1200
SP.E
SP.2
SP.E
SP.2
advanced
+0.03
+0,8
1..10
92
(0.04..0.4")
4
(3.62" )
2
1
3
4
+0,8
2
920.1
+0,6
45
(1.77" )
+0.02
Loc
security switch
Ü
or:
96
para func
Ada
Err
F
KS 92-1 advanced
o
C
921.2
run
SP.E
SP.2
run
SP.E
SP.2
96
118
10
max. 95% rel.
l
Ü
%
*
*
Safety switch:
For access to the safety switch, the controller must be withdrawn from the hou sing. Squeeze the top and bottom of the front bezel between thumb and forefinger and pull the controller firmly from the housing.
Loc open Access to the levels is as adjusted by means of BlueControl (engineering tool) 2
closed 1 all levels accessible wihout restriction
1 Factory setting 2 Default setting: display of all levels
suppressed, password PASS = OFF
Caution! The unit contains ESD-sensitive components.
-
KS 90-1 / KS 92-1 5
Page 6
Electrical connections
6
2 Electrical connections
2.1 Connecting diagram
3
1
2
90...250V 24VUC
OUT1
OUT2
OUT3
KS90-1. -4 ... KS90-1. -5 ...
OUT4
KS90-1. -25...
!
V
V
d b
c
e
8
9
0
RGND
DATA B
DATA A
RS485 RS422
Modbus RTU
1 2 3
4 5 6
7 8 9
10 11 12
13 14 15
a
+24V DC
OUT5 OUT6
24V GND
RXD-B
RXD-A
TXD-B
TXD-A
GND
di2
di3
U
1 2 3
di1
7
di2
4 5 6
7
g
HC
mA
INP2
f
5
8 9
10 11
(mV)
0%
100%
mA
INP3
KS90-1..-.1...
12 13
14 15
mA
Volt
INP1
4
(16)
Option
1
(2)
3
4
5
10
11
12
13
14
15
(16)
17
6
7
8
9
VP (5V)
DGND
RxD/TxD-N
RxD/TxD-P
Schirm/ Screen
T
17
PROFIBUS-DP
(mV)
a
b
390 [
220 [
Adapter
390 [
cd
DGND
9
8
7
VP (5V)
6
Profibus DP
e
max.
1200m
5
4
3
2
1
5
9
4
8
3
7
2
6
1
g
Dependent of order, the controller is fitted with :
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or
w
screw terminals for 0,5 to 2,5mm²
w
On instruments with screw terminals, the insulation must be stripped by min. 12 mm. Choose end crimps accordingly!
Connecting diagram 6 KS 90-1 / KS 92-1
Page 7
2.2 Terminal connection
Power supply connection 1
See chapter "Technical data"
Electrical connections
Connection of outputs OUT1/2 2
2 OUT1/2 heating/cooling
Relay outputs (250V/2A), potential-free changeover contact
L
Connection of outputs OUT3/4 3
a relay (250V/2A), potential-free
changeover contact
universal output
b current (0/4...20mA) c voltage (0/2...10V) d transmitter supply e logic (0..20mA / 0..12V)
Connection of input INP1 4
N
Input mostly used for variable x1 (pro­cess value)
a thermocouple b resistance thermometer (Pt100/ Pt1000/ KTY/ ...) c current (0/4...20mA) d voltage (0/2...10V)
1
2
3
4
5
6
7
8
9
10 11 12
13 14 15
10 11 12
13 14
(16)
1 2 3
4 5 6 7 8 9
15
17
+
Connection of input INP2 5
f heating current input (0..50mA AC)
or input for ext. set-point (0/4...20mA) g potentiometer input for position feedback
Connection of input INP2 5
a Heating current input (0...50mA AC)
or input for ext. Set-point (0/4...20mA) b Potentiometer input for position
feedback
Connection of input INP3 6
As input INP1, but without voltage
Connection of inputs di1, di2 7
Digital input, configurable as switch or push-button
5 INP2 current tansformer
L
1 2
3 4
5 6
7 8
N
Logik
9
10 11 12
13 14 15
10 11 12
13 14 15
(16)
17
1 2 3
4 5
6 7
8 9
SSR
_
+
KS 90-1 / KS 92-1 7 Terminal connection
Page 8
Electrical connections
Connection of inputs di2/3 8 (option)
Digital inputs (24VDC external), galvanically isolated, configurable as switch or push-button
Connection of output U
9 (option)
T
Supply voltage connection for external energization
Connection of outputs OUT5/6 0 (option)
Digital outputs (opto-coupler), galvanic isolated, common positive control volta ge, output rating: 18...32VDC
Connection of bus interface ! (option)
PROFIBUS DP or RS422/485 interface with Modbus RTU protocol
89 di2/3, 2-wire transmitter supply
OUT3
J
10 11
12
13 14 15
Option
15
(16)
17
13 14
-
+
-
g
+24VDC
3
0V
+
1
2
-
17,5V 22mA
K
5mA
5mA
+
-
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
J
Analog outputs OUT3 or OUT4 and transmitter supply UTare connected to different voltage potentials. Therefore, take care not to make an external galvanic connection between OUT3/4 and U
with analog outputs!
T
Terminal connection 8 KS 90-1 / KS 92-1
Page 9
3 OUT3 transmitter supply
Electrical connections
3
13V
22mA
1
K
2
-
+
10 11
12
13 14 15
11 12
15
(16)
17
13 14
+
-
9 RS485 interface (with RS232-RS485 interface converter) *
R = 120...200 OhmT
RT
RGND connection optional
RGND
DATA B
DATA A
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
J
10
11
12
13
14
15
RGND
DATA B
DATA A
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
10
11
12
13
14
15
max. 1000m
"Twisted Pair” cable
RGND
DATA B
DATA A
R=100 Ohm
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
RT
R = 120...200 OhmT
10
11
12
13
14
15
PC
RS485-RS232
converter
* Interface description Modbus RTU in speperate manual: see page 71.
KS 90-1 / KS 92-1 9 Terminal connection
Page 10
Electrical connections
3 OUT3 as logic output with solid-state relay (series and parallel connection)
Series connection
SSR
I =22mA
max
_
4V
+
SSR
_
4V
+
SSR
_
4V
+
12V
10 11
12
Logic
SSR
SSR
Parallel connection
I =22mA
max
_
12V
+
_
+
10 11
12
KS90-1 connecting example:
L1
L2
Fuse
1 2
3 4
5 6
7 8 9
10 11
12
13 14 15
KS90-1
Logik
10 11 12
13 14
(16)
1 2 3
4 5 6 7 8 9
SSR
_
+
15
17
Contactor
+
Fuse
Heating
1 TB 40-1 Temperaturelimiter
Standard-version (3 Relays): TB40-100-0000D-000
further versions on requestr
1
2
3
4
1
TB 40-1
Temperaturelimiter
5
6
7
8
9
10
11
12
13
14
15
+
Reset­key
Fuse
N1
N2
a
CAUTION: Using a temperature limiter is recommendable in systems where overtemperature implies a fire hazard or other risks.
Terminal connection 10 KS 90-1 / KS 92-1
Page 11
3 Operation
1 2 3
4
F
SP.E
SP.2
920.1
921.2
C
para
func
Ada
Err
SP.E
SP.2
o
1200
1199
°C °F
SP.2
SP.E
para func
Ada
Err
F
123
4
1
2
3
4
5 6
$
7 8
%
&
(
/
p
9
0
SP
§"
!
92
4
C
9
0
!
§"
7 8
$
%
&
/
(
5 6
1
2
3
3.1 Front view
Operation
1 Statuses of switching outputs OuT.1... 6 2 Process value display 3 Setpoint or correcting variable display 4 °C or °F display signalling 5 Signals ConF- and PArA level 6 Signals activated function key 7 Selft-tuning active 8 Entry into the error list 9 Bargraph or plain text display 0 Setpoint SP.2 is effective ! Setpoint SP.E is effective " Setpoint gradient is effective
§ Manual-automatic switchover: Off: automatic On: manual mode (adjustment possible) Blinks: manual mode (adjustment not possible (r ConF/ Cntr/ MAn))
$ Enter key: call up extented operating level / error list % Up/ down keys: changing setpoint or correcting variable & automatic/manual or other functions ( r ConF /LOGI) / freely configurable function key with pure controller operation ( PC connection for BlueControl (engineering tool)
g
LED colours: LED 1, 2, 3, 4: yellow, Bargraph: red, other LEDs: red
In the upper display line, the process value is always displayed. At parameter, configuration, calibration as well as extended operating level, the bottom display line changes cyclically between parameter name and parameter value.
KS 90-1 / KS 92-1 11 Front view
Page 12
Operation
A
M
l
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the operating level. The unit is in the condition which was active before power-off. If the controller was in manual mode at supply voltage switch-off, the controller will re-start with the last output value in manual mode at power-on.
3.3 Operating level
The content of the extended operating level is determined by means of BlueCon trol (engineering tool). Parameters which are used frequently or the display of which is important can be copied to the extended operating level.
time
out
utomatic
1199
1200
È Ì
Ù
1199
Y21
i
Ò
Ò
i
anua
1199
Y21
È Ì
Ù
1199
1200
time
out
-
È
Ù
only
display
Ù
Ì
Extended operating level
time
out
Error list (if error exists)
126
FbF.1
Err
Display
switching
126
2
Err
Behaviour after power-on 12 KS 90-1 / KS 92-1
Page 13
3.4 Error list / Maintenance manager
Operation
With one or several errors, the extended operating level al
­ways starts with the error list. Signalling an actual entry in the error list (alarm, error) is done by the Err LED in the display. To reach the error list press Ù twice.
Err LED status Signification Proceed as follows
blinks
(status 2)
lit
(status 1)
off
(status 0)
Alarm due to existing error
Error removed, alarm not acknowledged
No error, all alarm entries deleted
Determine the error type in the error list
­After error correction the unit changes to status 1
­Acknowledge the alarm in the error list pressing key ÈorÌ
­The alarm entry was deleted (status 0).
-
-Not visible except when acknowledging
-
Error list:
Name
E.1
E.2
E.3
E.4
FbF.1
Sht.1
POL.1 FbF.2
Sht.2
POL.2 FbF.3
Sht.3
POL.3
Description Cause Possible remedial action
Internal error, cannot be removed
Internal error, can be reset
- E.g. defective EEPROM - Contact PMA service
- Return unit to our factory
- e.g. EMC trouble - Keep measurement and power supply cables in separate runs
- Ensure that interference suppression of contactors is provided
Configuration error, can be reset
- wrong configuration
- missing configuration
Hardware error - Codenumber and
hardware are not identical
Sensor break INP1
-
Sensor defective
-
Faulty cabling
Short circuit INP1-Sensor defective
-
Faulty cabling
INP1polarity error
-
Faulty cabling
Sensor break INP2-Sensor defective
-
Faulty cabling
Short circuit INP2-Sensor defective
-
Faulty cabling
INP2 polarity
-
Faulty cabling
Sensor break INP3-Sensor defective
-
Faulty cabling
Short circuit INP3-Sensor defective
-
Faulty cabling
INP3 polarity
-
Faulty cabling
- Check interaction of configuration / parameters
- Contact PMA service
- Elektronic-/Optioncard must be exchanged
-
Replace INP1 sensor
-
Check INP1 connection
-
Replace INP1 sensor
-
Check INP1 connection
-
Reverse INP1 polarity
-
Replace INP2 sensor
-
Check INP2 connection
-
Replace sensor INP2
-
Check INP2 connection
-
Reverse INP2 polarity
-
Replace INP3 sensor
-
Check INP3 connection
-
Replace sensor INP3
-
Check INP3 connection
-
Reverse INP3 polarity
1199
°C
°F
1200
para func
Ada
Err
SP.E
SP.2
KS 90-1 / KS 92-1 13 Error list / Maintenance manager
Page 14
Operation
Name
HCA
SSr
LooP
AdA.H
AdA.C
LiM.1
Lim.2
Lim.3
Inf.1
Inf.2
E.5
dp.1
dp.2
dp.3
Description Cause Possible remedial action
Heating current alarm (HCA)
Heating current circuit
­interrupted, I< HC.A or
Check heating current circuit
­If necessary, replace heater band
-
I> HC.A (dependent of configuration) Heater band defective
-
Heating current short circuit (SSR)
Current flow in heating
­circuit with controller
Check heating current circuit
­If necessary, replace solid-state relay
-
off SSR defective
-
Control loop alarm (LOOP)
Input signal defective or
­not connected correctly Output not connected
­correctly
Check heating or cooling circuit
­Check sensor and replace it, if
­necessary Check controller and switching
­device
Self-tuning heating alarm
See Self-tuning heating
­error status
see Self-tuning heating error status
-
(ADAH) Self-tuning heating
alarm cooling (ADAC)
stored limit alarm 1 - adjusted limit value 1
See Self-tuning cooling
­error status
see Self-tuning cooling error status
-
- check process
exceeded
stored limit alarm 2 - adjusted limit value 2
- check process
exceeded
stored limit alarm 3 - adjusted limit value 3
- check process
exceeded
time limit value message
duty cycle message (digital ouputs)
Internal error in DP module
- adjusted number of operating hours reached
- adjusted number of duty cycles reached
-
self-test error
-
internal communication
- application-specific
- application-specific
-
Switch on the instrument again
-
Contact PMA service
interrupted
No access by bus master
-
bus error
-
connector problem
-
no bus connection
Faulty configuration-Faulty DP
configuration telegram
Inadmissible parameter setting telegram sent
-
Faulty DP parameter setting telegram
-
Check cable
-
Check connector
-
Check connections
-
Check DP configuration telegram in master
-
Check DP parameter setting telegram in master
No data
dp.4
Error list / Maintenance manager 14 KS 90-1 / KS 92-1
communication
-
Bus error
-
Address error
-
Master stopped
-
Check cable connection
-
Check address
-
Check master setting
Page 15
Operation
g
g
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital input di1/2/3, the è-key or the Ò-key. Configuration, see page 37: ConF / LOGI / Err.r
If an alarm is still valid that means the cause of the alarm is not removed so far (Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Error
status
Description Behaviour
0
No error
3
Faulty control action Re-configure controller (inverse i direct)
4
No response of process variable
5
Low reversal point Increase ( ADA.H) max. output limiting Y.Hi or decrease (
The control loop is perhaps not closed: check sensor, connections and process
ADA.C) min. output limiting Y.Lo
6
Danger of exceeded
If necessary, increase (inverse) or reduce (direct) set-point set-point (parameter determined)
7
Output step change too small (dy > 5%)
8
Set-point reserve too small
Increase ( ADA.H) max. output limiting Y.Hi or reduce (
ADA.C) min. output limiting Y.Lo
Acknowledgment of this error message leads to switch-over to
automatic mode.If self-tuning shall be continued,
increase set-point (invers), reduce set-point (direct)
or decrease set-point range
(r PArA / SEtp / SP.LO and SP.Hi )
9
Impulse tuning failed The control loop is perhaps not closed: check sensor, connections
and process
DAC function ( DAC) error status:
Error status
0 3 4 5 6
KS 90-1 / KS 92-1 15 Error list / Maintenance manager
No error Output is blocked Check the drive for blockage Wrong method of operation Wrong phasing, defect motor capacitor Fail at Yp measurement Check the connection to the Yp input Calibration error Manual calibration necessary
Description Behaviour
Page 16
Operation
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt, where by the process characteristics are used to calculate the parameters for fast line-out to the set-point without overshoot.
The following parameters are optimized when self-tuning: Parameter set 1:
Pb1 - Proportional band 1 (heating) in engineering units [e.g. °C] ti1 - Integral time 1 (heating) in [s]r only, unless set to OFF td1 - Derivative time 1 (heating) in [s]r only, unless set to OFF t1 - Minimum cycle time 1 (heating) in [s]r only, unless Adt0 was
set to “no self-tuning” during configuration by means of BlueControl
®
.
Pb2 - Proportional band 2 (cooling) in engineering units [e.g. °C] ti2 - Integral time 2 (cooling) in [s]r only, unless set to OFF td2 - Derivative time 2 (cooling) in [s]r only, unless set to OFF t2 - Minimum cycle time 2 (cooling) in [s] r only, unless Adt0
was set to “no self-tuning” during configuration by means of BlueControl
®
.
-
Parameter set 2: analogous to parameter set 1 (see page 25)
3.5.1 Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set values
w
rnG.L and rnG.H to the limits of subsequent control. (ConfigurationrControllerrlower and upper control range limits) ConFrCntrr rnG.L and rnG.H
Determine which parameter set shall be optimized.
w
-The instantaneously effective parameter set is optimized. r Activate the relevant parameter set (1 or 2).
Determine which parameter set shall be optimized (see tables above).
w
Select the self-tuning method
w
see chapter 3.5.3
-Step attempt after start-up
-Pulse attempt after start-up
-Optimization at the set-point
Self-tuning 16 KS 90-1 / KS 92-1
Page 17
3.5.2 Optimization after start-up or at the set-point
The two methods are optimization after start-up and at the set-point. As control parameters are always optimal only for a limited process range, vari ous methods can be selected dependent of requirements. If the process behaviour is very different after start-up and directly at the set-point, parameter sets 1 and 2 can be optimized using different methods. Switch-over between parameter sets dependent of process status is possible (see page ).
Optimization after start-up: (see page 4) Optimization after start-up requires a certain separation between process value and set-point. This separation enables the controller to determine the control pa rameters by evaluation of the process when lining out to the set-point. This method optimizes the control loop from the start conditions to the set-point, whereby a wide control range is covered. We recommend selecting optimization method “Step attempt after start-up” with tunE = 0 first. Unless this attempt is completed successfully, we recom mend a “Pulse attempt after start-up”.
Operation
-
-
-
Optimization at the set-point: (see page 18) For optimizing at the set-point, the controller outputs a disturbance variable to the process. This is done by changing the output variable shortly. The process value changed by this pulse is evaluated. The detected process parameters are conver­ted into control parameters and saved in the controller. This procedure optimizes the control loop directly at the set-point. The advantage is in the small control deviation during optimization.
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)
Selection criteria for the optimization method:
Step attempt after start-up Pulse attempt after start-up Optimization at the set-point
tunE =0 tunE =1 tunE =2
sufficient set-point reserve is
provided
sufficient set-point reserve is
provided
always step attempt after
start-up
Sufficient set-point reserve:
inverse controller:(with process value < set-point- (10% of rnGH - rnGL) direct controller: (with process value > set-point + (10% of rnGH - rnGL)
sufficient set-point reserve is not
provided
sufficient set-point reserve is not
provided
KS 90-1 / KS 92-1 17 Self-tuning
Page 18
Operation
3.5.4 Step attempt after start-up
Condition: - tunE = 0 and sufficient set-point reserve provided or - tunE =2
The controller outputs 0% correcting variable or Y.Lo and waits, until the process is at rest (see start-conditions on page 8). Subsequently, a correcting variable step change to 100% is output. The controller attempts to calculate the optimum control parameters from the pro cess response. If this is done successfully, the optimized parameters are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”. After completing the 1st step as described, a correcting variable of -100% (100% cooling energy) is output from the set-point. After successfull determination of the “cooling parameters”, line-out to the set-point is using the optimized parame ters.
-
-
3.5.5 Pulse attempt after start-up
Condition: - tunE = 1 and sufficient set-point reserve provided. The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start conditions page 8) Subsequently, a short pulse of 100% is output (Y=100%) and reset. The controller attempts to determine the optimum control parameters from the process response. If this is completed successfully, these optimized parameters are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described and line-out to the set-point, correcting variable "heating" remains unchanged and a cooling pulse (100% cooling energy) is output additionally. After successful determination of the “cooling parame ters”, the optimized parameters are used for line-out to the set-point.
3.5.6 Optimization at the set-point
Conditions:
A sufficient set-point reserve is not provided at self-tuning start (see page 17).
w
tunE is0or1
w
With Strt = 1 configured and detection of a process value oscillation by
w
more than ± 0,5% of (rnG.H - rnG.L) by the controller, the control parameters are preset for process stabilization and the controller realizes an optimization at the set-point (see figure “Optimization at the set-point”). when the step attempt after power-on has failed
w
with active gradient function ( PArA/ SETP/ r.SPOFF), the set-point
w
gradient is started from the process value and there isn't a sufficient set-point reserve.
-
Self-tuning 18 KS 90-1 / KS 92-1
Page 19
Operation
Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In li ned out condition, the controller makes a pulse attempt. This pulse reduces the correcting variable by max. 20% 1, to generate a slight process value unders hoot. The changing process is analyzed and the parameters thus calculated are re corded in the controller. The optimized parameters are used for line-out to theset-point.
Optimization at the set-point
-
set-point
process value
-
-
correcting variable
With a 3-point controller, optimization for the “heating“ or “cooling” parameters occurs dependent of the instantaneous condition. These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is increased by max. 20%.
KS 90-1 / KS 92-1 19 Self-tuning
Page 20
Operation
3.5.7 Optimization at the set-point for 3-point stepping controller
With 3-point stepping controllers, the pulse attempt can be made with or without position feedback. Unless feedback is provided, the controller calculates the mo tor actuator position internally by varying an integrator with the adjusted actuator travel time. For this reason, precise entry of the actuator travel time (tt), as time between stops is highly important. Due to position simulation, the controller knows whether an increased or reduced pulse must be output. After supply volta ge switch-on, position simulation is at 50%. When the motor actuator was varied by the adjusted travel time in one go, internal calculation occurs, i.e. the position corresponds to the simulation:
Simulation actual position
-
-
Internal calculation
tt
Internal calculation always occurs, when the actuator was varied by travel time
tt in one go
, independent of manual or automatic mode. When interrupting the variation, internal calculation is cancelled. Unless internal calculation occurred already after self-tuning start, it will occur automatically by closing the actuator once.
Unless the positioning limits were reached within 10 hours, a significant deviati
­on between simulation and actual position may have occurred. In this case, the controller would realize minor internal calculation, i.e. the actuator would be clo
­sed by 20 %, and re-opened by 20 % subsequently. As a result, the controller knows that there is a 20% reserve for the attempt.
Self-tuning 20 KS 90-1 / KS 92-1
Page 21
3.5.8 Self-tuning start
Start condition:
For process evaluation, a stable condition is required. Therefore, the
w
controller waits until the process has reached a stable condition after self-tuning start. The rest condition is considered being reached, when the process value
oscillation is smaller than ± 0,5% of (rnG.H - rnG.L). For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)
w
is required.
Operation
g
Self-tuning start can be blocked via BlueControl®(engineering tool) ( P.Loc).
Strt = 0 Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.
Strt = 1 Manual start by press keys Ù and È simultaneously
via interface and automatic start after power-on and detection of process oscillations.
Ada LED status Signification
blinks Waiting, until process
calms down
lit Self-tuning is running
off Self-tuning not activ
or ended
3.5.9 Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È key simultaneously.With controller switch-over to manual mode after self-tuning start, self-tuning is cancelled. When self-tuning is cancelled, the controller will continue operating using the old parameter values.
1199
°C
°F
1200
para func
Ada
Err
SP.E
SP.2
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning is prevented due to the control conditions. In this case, self-tuning was cancelled by the controller. The controller continues operating with the old parameters in automatic mode. In manual mode it continues with the old controller output va
-
lue.
KS 90-1 / KS 92-1 21 Self-tuning
Page 22
Operation
3.5.10 Acknowledgement procedures in case of unsuccessful self-tuning
1. Press keys Ù and È simultaneously:
The controller continues controlling using the old parameters in automatic mode. The Err LED continues blinking, until the self-tuning error was acknowledged in the error list.
2. Press key Ò (if configured):
The controller goes to manual mode. The Err LED continues blinking, until the self-tuning error was acknowleged in the error list.
3. Press key Ù :
Display of error list at extended operating level. After acknowledgement of the error message, the controller continues control in automatic mode using the old parameters.
Cancellation causes:
r page 15: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
Self-tuning 22 KS 90-1 / KS 92-1
Page 23
3.5.11 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Operation
Start: heating power switched on
Heating power Y is switched off (1). When the change of process value X was constant during one minute (2), the power is switched on (3). At the reversal point, the self-tuning at
­tempt is finished and the new parameter are used for controlling to set-point W.
Start: heating power switched off
The controller waits 1,5 minutes (1). Heating power Y is switched on (2). At the reversal point, the self-tuning attempt is finished and control to the set-point is using the new parameters.
Self-tuning at the set-point a
The process is controlled to the set-point. With the control deviation constant during a defined time (1) (i.e. constant separation of process value and set-point), the controller outputs a reduced correcting variable pulse (max. 20%) (2). After determination of the control parameters using the process characteristic (3), control is started using the new parameters (4).
100%
100%
X
W
100%
0%
Start r
X
W
Y
0%
Star t r
X
W
Y
0%
Y
start r
1
blinks
1
blinks
2
r
1
blinks
t
3
2
2
3
4
t
t reversal point
t
t reversal point
t
Three-point controller a
The parameter for heating and cooling are
X
W
3
rt
determined in two attempts. The heating power is switched on (1). Heating para meters Pb1, ti1, td1 and t1 are de termined at the reversal point. Control to the set-point occurs(2). With constant control deviation, the controller provides a cooling correcting variable pulse (3). Af
-
-
+100%
Y0%
-100%
Start r
1
t reversal
point
2
4
t
5
-
ter determining its cooling parameters Pb2, ti2, td2 and t2 (4) from the process characteristics , control operation is started using the new parameters (5).
a
KS 90-1 / KS 92-1 23 Self-tuning
During phase 3, heating and cooling are done simultaneously!
Page 24
Operation
y
3.6 Manual self-tuning
The optimization aid can be used with units on which the control parameters shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting varia ble y can be used. Frequently, plotting the complete response curve (0 to 100%) is not possible, because the process must be kept within defined limits. Values T
and x be used to determine the maximum rate of increase v
(step change from 0 to 100 %) or t and x (partial step response) can
max
.
max
100%
Y
h
0%
x
t
Tg
X
max
-
g
{X
{t
Tu
y = correcting variable
Y
h
Tu = delay time (s) Tg = recovery time (s) X
max
V
max
The control parameters can be determined from the values calculated for delay time T according to the formulas given below. Increase Xp, if line-out to the set-point oscillates.
= control range
= maximum process value
Xmax
=
Tg
, maximum rate of increase v
u
{{x
=
= max. rate of increase of process value
t
, control range Xhand characteristic K
max
t
Manual self-tuning 24 KS 90-1 / KS 92-1
Page 25
Operation
Parameter adjustment effects
Parameter Control Line-out of disturbances Start-up behaviour
Pb1 higher increased damping slower line-out slower reduction of duty cycle
lower reduced damping faster line-out faster reduction of duty cycle
td1 higher reduced damping faster response to disturbances faster reduction of duty cycle
lower increased damping slower response to disturbances slower reduction of duty cycle
ti1 higher increased damping slower line-out slower reduction of duty cycle
lower reduced damping faster line-out faster reduction of duty cycle
Formulas
K = Vmax * Tu controller behavior Pb1 [phy. units] td1 [s] ti1 [s]
PID 1,7*K 2*Tu 2*Tu With 2-point and 3-point controllers,
the cycle time must be adjusted to
t1 / t2 ≤ 0,25 * Tu
PD 0,5 * K Tu OFF
PI 2,6 * K OFF 6*Tu
PKOFF OFF
3-point-stepping 1,7 * K Tu 2 * Tu
3.7 Second PID parameter set
The process characteristic is frequently affected by various factors such as pro­cess value, correcting variable and material differences. To comply with these requirements, KS 90-1 can be switched over between two parameter sets. Parameter sets PArA and PAr.2 are provided for heating and cooling.
Dependent of configuration ( ConF/LOG/Pid.2), switch-over to the second pa­rameter set ( ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3, key è or interface (OPTION).
g
Self-tuning is always done using the active parameter set, i.e. the second parameter set must be active for optimizing.
KS 90-1 / KS 92-1 25 Second PID parameter set
Page 26
Operation
3.8 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Ge nerally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If more than one signal is linked to one output the signals are OR linked. Each of the 3 li mit values Lim.1 Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off individually (parameter = “OFF”). Switching difference HYS.x and delay dEl.x of each limit value is adjustable.
Ü Operaing principle absolut alarm
L.1 = OFF
InL.1
H.1
HYS.1
LED
InH.1
* Operating principle relative alarm
L.1 = OFF
SP
InL.1
H.1
HYS.1
-
-
InH.1
LED
H.1 = OFF
InL.1
InL.1
H.1
L.1
LED
L.1
HYS.1
LED
HYS.1 HYS.1
InH.1
InH.1
LED
H.1 = OFF
InL.1
InL.1
2
LED
LED
HYS.1
HYS.1
L.1
SP
InH.1
L.1
SP
InH.1
H.1
HYS.1
LED
2
1: normally closed ( ConF/ Out.x/O.Act=1 ) (see examples in the drawing) 2: normally open ( ConF/ Out.x/O.Act= 0 )(inverted output relay action)
Alarm handling 26 KS 90-1 / KS 92-1
Page 27
Operation
g
The variable to be monitored can be selected seperately for each alarm via configuration The following variables can be monitored:
process value
w
control deviation xw (process value - set-point)
w
control deviation xw + suppression after start-up or set-point change
w
After switching on or set-point changing, the alarm output is suppressed,
until the process value is within the limits for the first time. At the latest after expiration of time 10 ti1, the alarm is activated. (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = OFF), this is interpreted as Î, i.e. the alarm
is not activated, before the process value was within the limits once. Measured value INP1
w
Measured value INP2
w
Measured value INP3
w
effective set-point Weff
w
correcting variable y (controller output)
w
Deviation from SP internal
w
x1-x2
w
control deviation xw + suppression after start-up or setpoint change
w
without time limit.
- after switch-on or setpoint change, alarm output is suppressed, until the process value was within the limits once.
g
w w
If measured value monitoring + alarm status storage is chosen ( ConF / Lim / Fnc.x=2/4), the alarm relay remains switched on until the alarm is resetted in the error list ( Lim 1..3 = 1).
KS 90-1 / KS 92-1 27 Alarm handling
Page 28
Operation
3.9 Operating structure
After supply voltage switch-on, the controller starts with the operating levels. The controller status is as before power off.
1199
g
1200
Ù
3 sec.
1199
PArA
para
Ì
Ù
1199
ConF
para
PASS
Ù
PASS
1199
Ù
Ì
CAL
1199
Ì
PArA - level: At PArA - level, the right decimal point of the bottom
display line is lit continuously.
End
PASS
Ù
g
g
ConF - level: At ConF - level, the right decimal point of bottom
display line blinks.
When safety switch Loc is open, only the levels enabled by me
PASS
(engineering tool). Individual parameters accessible without password must be copied to the extended operating level.
Factory setting:Safety switch Loc closed: all levels accessible without restriction, password PASS = OFF.
Safety switch Loc
closed OFF / password disabled / enabled open OFF / password disabled open OFF enabled open Password enabled
ans of BlueControl (engineering tool) are visible and accessible by entry of the password also adjusted by means of BlueControl
Password entered with BluePort®
Function disabled or enabled with BluePort®
Access via the instrument front panel:
enabled disabled enabled enabled after password entry
-
Operating structure 28 KS 90-1 / KS 92-1
Page 29
4 Configuration level
4.1 Configuration survey
ConF Configuration level
Configuration level
Control and self-tuning
Cntr
È
SP.Fn I.Fnc I.Fnc I.Fnc Fnc.1 O.Act
Ì
C.tYP StYP StYP S.Lin Src.1 Y.1 O.Act O.Act SP.2 Addr C.Fnc S.Lin Corr S.Typ Fnc.2 Y.2 OuT.0 Y.1 SP.E PrtY C.dif Corr In.F Corr Src.2 Lim.1 Out.1 Y.2 Y.2 dELY mAn In.F In.F Fnc.3 Lim.2 O.Src Lim.1 Y.E dp.Ad C.Act Src.3 Lim.3 O.FAI Lim.2 mAn bc.up FAIL HC.AL dAc.A Y.1 Lim.3 C.oFF O2 rnG.L LP.AL LP.AL Y.2 dAc.A m.Loc Unit rnG.H dAc.A HC.AL Lim.1 LP.AL Err.r dP CYCL HC.SC Lim.2 HC.AL Pid.2 LEd tunE P.End Lim.3 HC.SC I.Chg dISP Strt FAi.1 dAc.A P.End di.Fn C.dEl
Input 1
InP.1
InP.2
Input 2
Input 3
InP.3
Limit value functions
Lim
OUt.1
Output 1
OUt.2
Output 2
O.tYP O.tYP
See output 1
FAi.2 LP.AL FAi.1 FAi.3 HC.AL FAi.2 dP.Er HC.SC FAi.3
FAi.1 OuT.0 FAi.2 Out.1 FAi.3 O.Src dP.Er
OUt.3
Output 3
OUt.4
Output 4
Out.5/6
Output 5/6
LOGI
L_r bAud
See output 1
Digital inpu ts
operation, interface
Othr Display,
Adjustment:
The configuration can be adjusted by means of keys ÈÌ .
w
Transition to the next configuration is by pressing key Ù .
w
After the last configuration of a group, donE is displayed and followed by
w
automatic change to the next group
Return to the beginning of a group is by pressing the Ù key for 3 sec.
KS 90-1 / KS 92-1 29 Configuration survey
Page 30
Configuration level
4.2 Configuration parameters
Cntr
Name Value range Description Default
SP.Fn
C.tYP
C.Fnc
C.dif
mAn
C.Act
FAIL
Basic configuration of setpoint processing
0
set-point controller can be switched over to external set-point (-> LOGI/ SP.E)
8
standard controller with external offset (SP.E)
Calculation of the process value
0 1 2 3
standard controller (process value = x1) ratio controller (x1/x2) difference (x1 - x2) Maximum value of x1and x2. It is controlled with the bigger value.
At sensor failure it is controlled with the remaining actual value.
4
Minimum value of x1and x2. It is controlled with the smaller value. At sensor failure it is controlled with the remaining actual value.
5
Mean value (x1, x2). With sensor error, controlling is continued
with the remaining process value. 6 Switchover between x1 and x2 (-> LOGI/ I.ChG) 7O 8O
function with constant sensor temperature
2
function with measured sensor temperature
2
Control behaviour (algorithm)
0 1 2
3 4 5 6
on/off controller or signaller with one output
PID controller (2-point and continuous)
/ Y / Off, or 2-point controller with partial/full load switch-over
2 x PID (3-point and continuous)
3-point stepping controller
3-point stepping controller with position feedback Yp
continuous controller with integrated positioner
Output action of the PID controller derivative action
0 1
Derivative action acts only on the measured value.
Derivative action only acts on the control deviation
(set-point is also differentiated)
Manual operation permitted
0 1
no
yes (r LOGI / mAn)
Method of controller operation
0
inverse, e.g. heating
The correcting variable increases with decreasing process value and
decreases with increasing process value.
1
direct, e.g. cooling
The correcting variable increases with increasing process value and
decreases with decreasing process value.
Behaviour at sensor break
0 1 2
controller outputs switched off
y=Y2
y = mean output. The maximum permissible output can be adjusted
with parameter Ym.H. To prevent determination of inadmissible
values, mean value formation is only if the control deviation is
lower than parameter L.Ym.
0
0
1
0
0
0
1
Configuration parameters 30 KS 90-1 / KS 92-1
Page 31
Configuration level
Name Value range Description Default
rnG.L rnG.H CYCL
tunE
Strt
Adt0
-1999...9999
-1999...9999
X0 (start of control range) 1
X100 (end of control range) 1
Characteristic for 2-point- and 3-point-controllers
0 1 2 3
standard
water cooling linear (siehe Seite 44)
water cooling non-linear
with constant cycle
Auto-tuning at start-up
0 1
At start-up with step attempt, at set-point with impulse attempt
At start-up and at set-point with impulse attempt. Setting for fast
controlled systems (e.g. hot runner control) 2 Always step attempt at start-up
Start of auto-tuning
0 1
Manual start of auto-tuning
Manual or automatic start of auto-tuning at power on or when
oscillating is detected
Optimization of T1, T2 (only visible with BlueControl!)
0 1
Automatic optimization
No optimization
-100
1200
0
0
0
0
1 rnG.L and rnG.H are indicating the range of control on which e.g. the
self-tuning is refering
InP.1
Name Value range Description Default
I.fnc
S.tYP
10 18
INP1 function selection
0 1 2 3 4 5
No function (following INP data are skipped)
Heating current input
External set-point SP.E (switch-over -> LOGI/ SP.E)
Position feedback Yp
Second process value x2 (ratio, min, max, mean)
External positioning value Y.E
(switch-over r LOGI / Y.E)
6 7
No controller input (e.g. limit signalling instead)
Process value x1
Sensor type selection
0 1 2 3 4 5 6 7 8 9
thermocouple type L (-100...900°C) , Fe-CuNi DIN
thermocouple type J (-100...1200°C) , Fe-CuNi
thermocouple type K (-100...1350°C), NiCr-Ni
thermocouple type N (-100...1300°C), Nicrosil-Nisil
thermocouple type S (0...1760°C), PtRh-Pt10%
thermocouple type R (0...1760°C), PtRh-Pt13%
thermocouple type T (-200...400°C), Cu-CuNi
thermocouple type C (0...2315°C), W5%Re-W26%Re
thermocouple type D (0...2315°C), W3%Re-W25%Re
thermocouple type E (-100...1000°C), NiCr-CuNi
thermocouple type B (0/100...1820°C), PtRh-Pt6%
special thermocouple
7
1
KS 90-1 / KS 92-1 31 Configuration parameters
Page 32
Configuration level
Name Value range Description Default
S.Lin
Corr
In.f
fAI1
-1999...9999
20
21 22 23 24 30 40 41 42 50 51 52 53
Pt100 (-200.0 ... 100,0 °C) ( -200,0 ... 150,0°C with reduced lead resistance: measuring resistance + lead resistance ß160 [ )
Pt100 (-200.0 ... 850,0 °C) Pt1000 (-200.0 ... 850.0 °C) special 0...4500 Ohm (preset to KTY11-6) special 0...450 Ohm
0...20mA / 4...20mA 1
0...10V / 2...10V 1 special -2,5...115 mV 1 special -25...1150 mV 1 potentiometer 0...160 Ohm 1 potentiometer 0...450 Ohm 1 potentiometer 0...1600 Ohm 1 potentiometer 0...4500 Ohm 1
Linearization (only at S.tYP = 23 (KTY 11-6), 24 (0...450 ), 30
0
(0..20mA), 40 (0..10V), 41 (0...100mV) and 42 (special -25...1150 mV))
0 1
none Linearization to specification. Creation of linearization table with
BlueControl (engineering tool) possible. The characteristic for KTY 11-6 temperature sensors is preset.
Measured value correction / scaling
0 1
Without scaling Offset correction (at CAL level)
0
(controller offset adjustment is at CALlevel)
2
2-point correction (at CAL level) (calibration is at the controller CALlevel)
3 4
Scaling (at PArA level) Autom. calibration (only with positionfeedback Yp)
Alternative value for error at INP1
OFF
If a value is adjusted, this value is used for display and calculation in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered!
Forcing INP1 (only visible with BlueControl!)
0 1
No forcing Forcing via serial interface
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
InP.2
Name Value range Description Default
I.Fnc
0 1 2 3 4 5
Function selection of INP2
no function (subsequent input data are skipped) heating current input external set-point (SP.E) Yp input Second process value X2 External positioning value Y.E
(switch-over r LOGI / Y.E)
Configuration parameters 32 KS 90-1 / KS 92-1
1
Page 33
Configuration level
Name Value range Description Default
S.tYP
Corr
In.F
fAI2
6 7
30 31 50 51 52 53
0 Without scaling 1 Offset correction (at CAL level)
2 2-point correction (at CALlevel)
3 Scaling (at PArA level)
-1999...9999
0 1
no controller input (e.g. transmitter input instead) Process value x1
Sensor type selection
0...20mA / 4...20mA 1
0...50mA AC 1 Potentiometer ( 0...160 Ohm) 1 Potentiometer ( 0...450 Ohm) 1 Potentiometer ( 0...1600 Ohm) 1 Potentiometer ( 0...4500 Ohm) 1 Measured value correction / scaling 0
(offset entry is at controller CALlevel)
(calibration is at controller CALlevel)
Alternative value for error at INP2
If a value is adjusted, this value is used for display and calculation in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered! Forcing INP2 (only visible with BlueControl!) No forcing Forcing via serial interface
30
OFF
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
InP.3
Name Value range Description Default
I.Fnc
S.Lin
S.tYP
Function selection of INP3
0 1 2 3 4 5
no function (subsequent input data are skipped) heating current input External set-point SP.E (switch-over -> LOGI/ SP.E) Yp input Second process value X2 External positioning value Y.E
(switch-over r LOGI / Y.E)
6 7
no controller input (e.g. transmitter input instead) Process value x1
Linearization (only at S.tYP = 30 (0..20mA) and 40 (0..10V) adjustable)
0 1
none Linearization to specification. Creation of linearization table with
BlueControl (engineering tool) possible. The characteristic for KTY 11-6 temperature sensors is preset.
Sensor type selection
0 1
thermocouple type L (-100...900°C) , Fe-CuNi DIN thermocouple type J (-100...1200°C) , Fe-CuNi
1
0
30
KS 90-1 / KS 92-1 33 Configuration parameters
Page 34
Configuration level
Name Value range Description Default
Corr
In.F
fAI3
-1999...9999
10 18 20
21 22 23 24 30 41 42 50 51 52 53
2 3 4 5 6 7 8 9
thermocouple type K (-100...1350°C), NiCr-Ni thermocouple type N (-100...1300°C), Nicrosil-Nisil thermocouple type S (0...1760°C), PtRh-Pt10% thermocouple type R (0...1760°C), PtRh-Pt13% thermocouple type T (-200...400°C), Cu-CuNi thermocouple type C (0...2315°C), W5%Re-W26%Re thermocouple type D (0...2315°C), W3%Re-W25%Re thermocouple type E (-100...1000°C), NiCr-CuNi thermocouple type B (0/100...1820°C), PtRh-Pt6% special thermocouple Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring resistance + lead resistance ß160 [ )
Pt100 (-200.0 ... 850,0 °C) Pt1000 (-200.0 ... 850.0 °C) special 0...4500 Ohm (preset to KTY11-6) special 0...450 Ohm
0...20mA / 4...20mA 1 special -2,5...115 mV 1 special -25...115 0mV 1 potentiometer 0...160 Ohm 1 potentiometer 0...450 Ohm 1 potentiometer 0...1600 Ohm 1 potentiometer 0...4500 Ohm 1
Measured value correction / scaling
0 1
Without scaling Offset correction (at CAL level)
0
(offset entry is at controller CALlevel)
2
2-point correction (at CAL level) (calibration is at controller CALlevel)
3 4
Scaling (at PArA level) Automatic calibration (DAC)
Alternative value for error at INP3
OFF
If a value is adjusted, this value is used for display and calculation in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered!
Forcing INP3 (only visible with BlueControl!)
0 1
No forcing Forcing via serial interface
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
Configuration parameters 34 KS 90-1 / KS 92-1
Page 35
Configuration level
Lim
Name Value range Description Default
Fnc.1 Fnc.2 Fnc.3
Src.1 Src.2 Src.3
HC.AL
LP.AL
dAc.A
Hour
Swit
Function of limit 1/2/3
0 1 2
switched off measured value monitoring Measured value monitoring + alarm latch. A latched limit value
can be reset via error list or via a digital input, or by pressing key Ò or
3 4
signal change (change/minute) signal change and storage (change/minute)
è (-> LOGI/ Err.r)
Source of Limit 1/2/3
0 1 2
process value control deviation xw (process value - set-point) Control deviation Xw (=relative alarm) with suppression after
start-up and setpoint change After switch-on or setpoint change, alarm output is suppressed,
until the process value was within the limits once. At the latest after elapse of time 10 ti1 the alarm is activated. (ti1 = integral time 1; parameter r Cntr)
ti1 switched off (ti1 = 0) is considered as Î , i.e. the alarm is
not activated, until the process value was within the limits once.
3 4 5 6 7
measured value INP1 measured value INP2 measured value INP3 effective setpoint Weff correcting variable y (controller output)
8 control variable deviation xw (actual value - internal setpoint) =
deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process value function “mean value” for recognizing aged thermocouples
11
Control deviation (=relative alarm) with suppression after start-up and setpoint change without time limit
After switch-on or setpoint change, alarm output is suppressed, until the process was within the limits once.
Alarm heat current function (INP2)
0 1 2
switched off Overload short circuit monitoring Break and short circuit monitoring Monitoring of control loop interruption for heating (see page 68)
0 1
switched off / inactive active. If ti1=0 LOOP alarm is inactive! DAC alarm function (see page 68)
0
1 OFF...999999 OFF...999999
DAC alarm switched off / inactive DAC alarm active
Operating hours (only visible with BlueControl!) Output switching cycles (only visible with BlueControl!)
1
1
0
0
0
OFF OFF
KS 90-1 / KS 92-1 35 Configuration parameters
Page 36
Configuration level
Out.1 and Out.2
Name Value range Description Default
O.Act
Y.1 Y.2
Lim.1 Lim.2 Lim.3
dAc.A
LP.AL
HC.AL
HC.SC
FAi.1 FAi.2 FAi.3
dP.Er
fOut
Method of operation of output OUT1
0 1
direct / normally open inverse / normally closed
Controller output Y1/Y2
0 1
not active active
Limit 1/2/3 signal
0 1
not active active
Valve monitoring (DAC)
0 1
not active active
Interruption alarm signal (LOOP)
0 1
not active active
Heat current alarm signal
0 1
not active active
Solid state relay (SSR) short circuit signal
0 1
not active active
INP1/ INP2 / INP3 error signal
0 1
not active active PROFIBUS error
0 1
not active active: Profibus trouble, no communication with this
0
1
0
0
0
0
0
0
0
instrument.
Forcing OUT1 (only visible with BlueControl!)
0 1
No forcing Forcing via serial interface
0
Configuration parameters Out.2 = Out.1 except for: Default Y.1 =0 Y.2 =1
Out.3 and Out4
Name Value range Description Default
O.tYP
0 1 2 3 4 5
Configuration parameters 36 KS 90-1 / KS 92-1
Signal type selection OUT3
relay / logic (only visible with current/logic voltage) 0 ... 20 mA continuous (only visible with current/logic/voltage) 4 ... 20 mA continuous (only visible with current/logic/voltage)
0...10 V continuous (only visible with current/logic/voltage)
2...10 V continuous (only visible with current/logic/voltage) transmitter supply (only visible without OPTION)
0
Page 37
Configuration level
Name Value range Description Default
O.Act
Out.0
Out.1
O.Src
O.FAI
Y.1 Y.2
Lim.1 Lim.2 Lim.3
dAc.A
LP.AL
HC.AL
HC.SC
FAi.1 FAi.2 FAi.3
dP.Er
0 1
-1999...9999
-1999...9999
0 1 2 3 4 5 6 7 8 9
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
Method of operation of output OUT3 (only visible when O.TYP=0)
direct / normally open inverse / normally closed
Scaling of the analog output for 0% (0/4mA or 0/2V, only visible when O.TYP=1..5)
Scaling of the analog output for 100% (20mA or 10V, only visible when O.TYP=1..5)
Signal source of the analog output OUT3 (only visible when O.TYP=1..5)
not used controller output y1 (continuous) controller output y2 (continuous) process value effective set-point Weff control deviation xw (process value - set-point) measured value position feedback Yp measured value INP1 measured value INP2 measured value INP3 Failbehaviour, behaviour of the analog output, if the signal source
(O.Src) is disturbed. upscale downscale
Controller output Y1/Y2 (only visible when O.TYP=0)
not active active
Limit 1/2/3 signal (only visible when O.TYP=0)
not active active
Valve monitoring (DAC) (only visible when O.TYP=0)
not active active
Interruption alarm signal (LOOP) (only visible when O.TYP=0)
(Loop-Alarm) not active active
Heating current alarm signal (only visible when O.TYP=0)
not active active
Solid state relay (SSR) short circuit signal (only visible when O.TYP=0)
not active active
INP1/ INP2 / INP3 error (only visible when O.TYP=0)
not active active PROFIBUS error not active active: Profibus trouble, no communication with this instrument.
1
0
100
1
0
0
1
0
0
0
0
1
0
KS 90-1 / KS 92-1 37 Configuration parameters
Page 38
Configuration level
Name Value range Description Default
fOut
Out.5/ Out.6
Configuration parameters Out.2 = Out.1 except for: Default Y.1 =0 Y.2 =0
Forcing OUT3 (only visible with BlueControl!)
0 1
No forcing Forcing via serial interface
0
g
Method of operation and usage of output Out.1 to Out.6:
Is more than one signal chosen active as source, those signals are OR-linked.
LOGI
Name Value range Description Default
L_r
0 1 2 3 4 5
SP.2
0 2 3 4 5
SP.E
0 1 2 3 4 5
Y2
0 2 3 4 5 6
Local / Remote switching (Remote: adjusting of all values by front keys is blocked)
no function (switch-over via interface is possible) always active DI1 switches DI2 switches (basic instrument or OPTION) DI3 switches (only visible with OPTION) è - key switches
Switching to second setpoint SP.2
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION) è - key switches
Switching to external setpoint SP.E
no function (switch-over via interface is possible) always active DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION) è - key switches
Y/Y2 switching
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION)
è - key switches Ò - key switches
0
0
0
0
Configuration parameters 38 KS 90-1 / KS 92-1
Page 39
Configuration level
Name Value range Description Default
Y.E
mAn
C.oFF
m.Loc
Err.r
Pid.2
Switching to fixed control output Y.E
0
1
2
3
4
5
6
no function (switch-over via interface is possible) always activated (manual station) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION)
è - key switches Ò - key switches
Automatic/manual switching
0
1
2
3
4
5
6
no function (switch-over via interface is possible) always activated (manual station) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION)
è - key switches Ò - key switches
Switching off the controller
0
2
3
4
5
6
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION)
è - key switches Ò - key switches
Blockage of hand function
0
2
3
4
5
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION) è - key switches
Reset of all error list entries
0
2
3
4
5
6
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION)
è - key switches Ò - key switches
Switching of parameter set (Pb, ti, td)
0
2
3
4
5
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION) è - key switches
0
0
0
0
0
0
KS 90-1 / KS 92-1 39 Configuration parameters
Page 40
Configuration level
Name Value range Description Default
I.Chg
di.Fn
fDI1 fDI2 fDI3
othr
Switching of the actual process value between Inp1 and X2
0 2 3 4 5
no function (switch-over via interface is possible) DI1 switches DI2 switches (only visible with OPTION) DI3 switches (only visible with OPTION) è - key switches
Function of digital inputs (valid for all inputs)
0 1 2
direct inverse toggle key function Forcing di1/2/3 (only visible with BlueControl!)
0 1
No forcing Forcing via serial interface
0
0
0
Name Value range Description Default
bAud
Addr PrtY
dELY dP.AD bc.up
O2
Unit
dP
0
1
2
3
1...247
0
1
2
3
0...200
0...126
0
1
0
1
0
1
2
0
1
2
3
Baudrate of the interface (only visible with OPTION)
2400 Baud 4800 Baud 9600 Baud 19200 Baud
Address on the interace (only visible with OPTION) Data parity on the interface (only visible with OPTION)
no parity (2 stop bits) even parity odd parity no parity (1 stopbit)
Delay of response signal [ms] (only visible with OPTION) Profibus address Behaviour as backup controller (see page )
No backup functionality With backup functionality
Entering parameter for O2in ppm or %
Parameter for O2-function in ppm Parameter for O2-function in %
Unit
without unit °C °F
Decimal point (max. number of digits behind the decimal point)
no digit behind the decimal point 1 digit behind the decimal point 2 digits behind the decimal point 3 digits behind the decimal point
2
1 1
0
126
0
0
1
0
Configuration parameters 40 KS 90-1 / KS 92-1
Page 41
Configuration level
Name Value range Description Default
LED
dISP C.dEl
FrEq
MAst
CycL
AdrO
AdrU
Numb
ICof
IAda
IExo
ILat
Pass
IPar
ICnf
ICal
Function allocation of status LEDs1/2/3/4
10 11 12 13 14
OUT1, OUT2, OUT3, OUT4 Heating, alarm 1, alarm 2, alarm 3 Heating, cooling, alarm 1, alarm 2 Cooling, heating, alarm 1, alarm 2 Bus error
0...10 Display luminosity
0..200
Modem delay [ms]
Additional delay time, before the received message is evaluated in the Modbus. This time is required, unless messages are transferred continuously during modem transmission.
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
0 1
50 Hz 60 Hz Modbus master/slave (see page ) (visible only with BlueControl®)
0 1
0...240
-32768...3276 7
-32768...3276 7
0...100
No Yes Master cycle (sec.) (see page ) (visible only with BlueControl®!) Destination address (see page ) (visible only with BlueControl®!)
Source address (see page ) (visible only with BlueControl®!) Number of data (see page ) (visible only with BlueControl®!)
Block controller off (only visible with BlueControl!)
0 1
Released Blocked Block auto tuning (only visible with BlueControl!)
0 1
Released Blocked Block extended operating level (only visible with BlueControl!)
0 1
Released Blocked Suppression error storage (visible only with BlueControl®!) 0
0 No: error message remain in the error list until
acknowledgement.
1 Yes alarms are deleted from the error list as soon as
corrected
OFF...9999
Password (only visible with BlueControl!) Block parameter level (only visible with BlueControl!)
0 1
Released Blocked Block configuration level (only visible with BlueControl!)
0 1
Released Block Block calibration level (only visible with BlueControl!)
0 1
Released Blocked
0
5 0
0
0
120
1100
1100
1 0
0
0
OFF
0
0
0
KS 90-1 / KS 92-1 41 Configuration parameters
Page 42
Configuration level
Name Value range Description Default
CDis3
0 1 2 3 4
TDis3
T.dis3 T.InF1 T.InF2
2...60 8 Zeichen 8 Zeichen 8 Zeichen
Display 3 controller operating level (only visible with BlueControl!) No value / only text Display of value Output value as bargraph Control deviation as bargraph Process value as bargraph
Display 3 display alternation time [s] (only visible with BlueControl!) Text display 3 (only visible with BlueControl!) Text Inf.1 (only visible with BlueControl!) Text Inf.2 (only visible with BlueControl!)
2
10
Lin (only visible with BlueControl
Name Value range Description Default
Lin
Linearization for inputs INP1 or INP3
Access to this table is always with selection special thermocouple for InP.1 or InP.3or with setting S.Lin = 1: special linearization for linearization. Default: KTY
11-6 (0...4,5 kOhm)
U.LinT
In.1
0 1 2
-999.0..99999
Unit of linearization table No unit In Celsius [°C] In Fahrenheit [°C]
Input value 1
0
1036
The signal is in [µV] or in [[] dependent of input type
Ou.1
0,001...9999 Output value 1
-49,94
Signal assigned to In.1
In.2
-999.0..99999 Input value 2
1150
The signal is in [µV] or in [[] dependent of input type
Ou.2
0,001...9999 Output value 2
-38,94
Signal assigned to In.2
: :
In.16
-999.0..99999 Input value 16
: :
: :
: :
4470
The signal is in [µV] or in [[] dependent of input type
Ou.16
0,001...9999 Output value 1 6
150,0
Signal assigned to In.16
+
BlueControl - the engineering tool for the BluePort controller series
3 engineering tools with different functionality facilitating the device configu
­ration and parameter setting are available (see chapter 9: Accessory equipment with ordering information). In addition to configuration and parameter setting, blue control data acquisition and offers long-term storage and print functions. Blue control
is used for
is connected to the device via the front-panel interface "BluePort" by means of PC (Windows 95 / 98 / NT) and a PC adaptor. Description BlueControl
Configuration parameters 42 KS 90-1 / KS 92-1
: see chapter 8: BlueControl (page 70).
Page 43
4.3 Set-point processing
The set-point processing structure is shown in the following picture:
Configuration level
1199
°C
°F
1200
para func Ada
Err
External set-point INP2
2. set-point
SP.E
SP.2
SP.E
0/4...20 mA
SP.2
Index:
Ü
: int/ext-setpoint switching
*
: configuration
Ö
: / switching
Xeff
Internal set-point
Ü
SP SP.2
SP.Fn
Ü
0
+
8
*
SP.Hi
SP.Lo
Limitation
Ö
r.SP
Ramp
Effektive set-point
- LED
The ramp starts at process value with the following switchings:
- int / ext-setpoint switching
- / switching
SP SP.2
- Manual-/ Automatic switching
- at power on
4.3.1 Set-point gradient / ramp
To prevent setpoint step changes, a maximum rate of change is adjustable for parameter r setpoint r r.SP. This gradient acts both in positive and negative direction.
With parameter r.SP set to OFFas in the factory setting, the gradient is switched off and setpoint changes are made directly.
KS 90-1 / KS 92-1 43 Set-point processing
Page 44
Configuration level
l
i
l
d
i
1
1
1
4.4 Switching behaviuor
With these controllers, configuration parameter CYCL (ConF/ Cntr/ CYCL) can be used for matching the cycle time of 2-point and 3-point controllers. This can be done using the following 4 methods.
4.4.1 Standard ( CyCl= 0 )
The adjusted cycle times t1 and t2 are valid for 50% or -50% correcting varia ble. With very small or very high values, the effective cycle time is extended to prevent unreasonably short on and off pulses. The shortest pulses result from ¼ x t1 or¼x t2. The characteristic curve is also called “bath tub curve”
T/T
1
6,0
5,0
on
4,0
urat
e
3,0
ve cyc
2,0
at re
1,0
0,0
5 101520253035404550556065707580859095
-
4xt
3xt
2xt
t1
Controller output [%]
Parameters to be adjusted: t1 : min. cycle time 1 (heating) [s] ( PArA/ Cntr) t2 : min. cycle time 2 (cooling) [s]
4.4.2 Switching attitude linear ( CyCl= 1 )
For heating (Y1), the standard method (see chapter 4.4.1) is used. For cooling (Y2), a special algorithm for cooling with water is used. Generally, cooling is en abled only at an adjustable process temperature (E.H2O), because low temperatu
-
-
res prevent evaporation with related cooling, whereby damage to the plant is avoided. The cooling pulse length is adjustable using parameter t.on and is fi xed for all output values.
-
The “off” time is varied dependent of output value. Parameter t.off is used for determining the min “off” time. For output of a shorter off pulse, this pulse is suppressed, i.e. the max. effective cooling output value is calculated according to formula t.on /(t.on + t.off) w 100%.
Parameters to be adjusted: E.H2O: minimum temperature for water cooling ( PArA / Cntr) t.on: pulse duration water cooling
t.off: minimum pause water cooling
Switching behaviuor 44 KS 90-1 / KS 92-1
Page 45
4.4.3 Switching attitude non-linear ( CyCl= 2 )
ff
Configuration level
With this method, the cooling power is nor
-
t.offt.on
mally much higher than the heating power, i.e. the effect on the behaviour during transi tion from heating to cooling may be negati ve. The cooling curve ensures that the control intervention with 0 to -70% correc
-
-
-
-82%
-87%
-90%
-92%
-95%
-67%
-80%
ting variable is very weak. Moreover, the correcting variable increases very quickly to max. possible cooling. Parameter F.H2O can be used for changing the characteristic curve. The standard method (see section 4.4.1) is also used for heating. Cooling is also enabled dependent of process temperature .
70
60
50
40
30
ective controller output
20
E
Water cooling non-linear, =1F.H2O Water cooling non-linear, =2F.H2O Water cooling non-linear, =0,5F.H2O Water cooling linear
Parameter:
t.on = 0.4 sec t.off = 0.2 sec
-100%
10
0
-100 -95 -90 -85 -80 -75 -70 -65 -60 -55 -50 -45 -40 -35 -30 -25 -20 -15 -10 -5
Controller output [%]
Parameters to be adjusted: F.H2O: adaptation of (non-linear) characteristic ( PArA / Cntr) Water cooling
t.on: Pulse duration water cooling t.off: min. pause water cooling E.H2O: min. temperature for water cooling
KS 90-1 / KS 92-1 45 Switching behaviuor
Page 46
Configuration level
p
4.4.4 Heating and cooling with constant period ( CyCl= 3 )
1 and t2 are met in the overall output range . To prevent unreasonably short pulses, parameter tp is used for adju
-
t
t1 t2/
sting the shortest pulse duration. With small correcting values which require a
50%
30%
20%
10%
pulse shorter than the value adjusted in
t1 t2/
50%
tp
70%
80%
90%
tp, this pulse is suppressed. However, the controller stores the pulse and totali zes further pulses, until a pulse of dura tion tp can be output.
-
-
Parameters to be adjusted: t1 : Min. cycle time 1 (heating) [s] ( PArA/ Cntr) t2 : min. cycle time 2 (cooling) [s]
tp: min. pulse length [s]
Switching behaviuor 46 KS 90-1 / KS 92-1
Page 47
4.5 Configuration examples
4.5.1 On-Off controller / Signaller (inverse)
Configuration level
g
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
100%
Out.1Â
0%
ConF / Cntr: SP.Fn = 0set-point controller
C.Fnc = 0signaller with one output C.Act = 0inverse action
ConF / Out.1: O.Act = 0action Out.1 direct
Y.1 =1control output Y1 active PArA / Cntr: Hys.l = 0...9999 switching difference below SP PArA / Cntr: Hys.H = 0...9999 switching difference above SP PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
For direct signaller action, the controller action must be changed (ConF / Cntr / C.Act = 1 )
SH
(e.g. heating applications)
process value
SH
setpoint
output
KS 90-1 / KS 92-1 47 Configuration examples
Page 48
Configuration level
4.5.2 2-point controller (inverse)
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
100%
PB1
Out.1Â
0%
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 1 2-point controller (PID) C.Act = 0 inverse action
(e.g. heating applications)
ConF / Out.1: O.Act = 0 action Out.1 direct
Y.1 = 1 control output Y1 active
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1 = 0,1...9999 integral time 1 (heating) in sec. td1 = 0,1...9999 derivative time 1 (heating) in sec. t1 = 0,4...9999 min. cycle time 1 (heating)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
g
For direct action, the controller action must be changed (ConF / Cntr / C.Act = 1 ).
setpoint
process value
output
Configuration examples 48 KS 90-1 / KS 92-1
Page 49
4.5.3 3-point controller (relay & relay)
Configuration level
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
100%
Out.1Â
0%
PB1
PB2
100%
Out.2Â
0%
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 3 3-point controller (2xPID) C.Act = 0 action inverse
(e.g. heating applications)
ConF / Out.1: O.Act = 0 action Out.1 direct
Y.1 = 1 control output Y1 active Y.2 = 0 control output Y2 not active
ConF / Out.2: O.Act = 0 action Out.2 direct
Y.1 = 0 control output Y1 not active Y.2 = 1 control output Y2 active
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
Pb2 = 1...9999 proportional band 2 (cooling)
in units of phys. quantity (e.g. °C)
ti1 = 0,1...9999 integral time 1 (heating) in sec. ti2 = 0,1...9999 derivative time 2 (cooling) in sec. td1 = 0,1...9999 integral time 1 (heating) in sec. td2 = 0,1...9999 derivative time 2 (cooling) in sec. t1 = 0,4...9999 min. cycle time 1 (heating) t2 = 0,4...9999 min. cycle time 2 (cooling) SH = 0...9999 neutr. zone in units of phys.quantity
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
KS 90-1 / KS 92-1 49 Configuration examples
Page 50
Configuration level
Â
4.5.4 3-point stepping controller (relay & relay)
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
100%
Out.1Â
0%
PB1
SH
100%
Out.2
0%
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 4 3-point stepping controller C.Act = 0 inverse action
(e.g. heating applications)
ConF / Out.1: O.Act = 0 action Out.1 direct
Y.1 = 1 control output Y1 active Y.2 = 0 control output Y2 not active
ConF / Out.2: O.Act = 0 action Out.2 direct
Y.1 = 0 control output Y1 not active Y.2 = 1 control output Y2 active
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1 = 0,1...9999 integral time 1 (heating) in sec. td1 = 0,1...9999 derivative time 1 (heating) in sec. t1 = 0,4...9999 min. cycle time 1 (heating) SH = 0...9999 neutral zone in units of phy. quantity tP = 0,1...9999 min. pulse length in sec. tt = 3...9999 actuator travel time in sec.
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
g
For direct action of the 3-point stepping controller, the controller output action must be changed ( ConF / Cntr / C.Act = 1 ).
setpoint
process value
output 1
output 2
Configuration examples 50 KS 90-1 / KS 92-1
Page 51
4.5.5 Continuous controller (inverse)
Configuration level
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
20 mA
PB1
Out.3Â
0/4 mA
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 1 continuous controller (PID) C.Act = 0 inverse action
(e.g. heating applications)
ConF / Out.3: O.tYP = 1 / 2 Out.3 type ( 0/4 … 20mA )
Out.0 = -1999...9999 scaling analog output 0/4mA Out.1 = -1999...9999 scaling analog output 20mA
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1 = 0,1...9999 integral time 1 (heating) in sec. td1 = 0,1...9999 derivative time 1 (heating) in sec. t1 = 0,4...9999 min. cycle time 1 (heating)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
g g
For direct action of the continuous controller, the controller action must be changed ( ConF / Cntr / C.Act = 1 ).
To prevent control outputs Out.1 and Out.2 of the continuous controller from switching simultaneously, the control function of outputs Out.1 and Out.2 must be switched off ( ConF / Out.1 and Out.2 / Y.1 and Y.2 = 0 ).
KS 90-1 / KS 92-1 51 Configuration examples
Page 52
Configuration level
4.5.6
∆ - Y - Off controller / 2-point controller with pre-contact
SP.LO SP
SP.Hi
InH.1InL.1
InP.1Ê
100%
PB1
Out.1Â
0%
Out.2Â
SH
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 2 -Y-Off controller C.Act = 0 inverse action
ConF / Out.1: O.Act = 0 action Out.1 direct
Y.1 = 1 control output Y1 active Y.2 = 0 control output Y2 not active
ConF / Out.2: O.Act = 0 action Out.2 direct
Y.1 = 0 control output Y1 not active Y.2 = 1 control output Y2 active
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
ti1 = 0,1...9999 integral time 1 (heating) in sec. td1 = 0,1...9999 derivative time 1 (heating) in sec. t1 = 0,4...9999 min. cycle time 1 (heating) SH = 0...9999 switching difference
d.SP
(e.g. heating applications)
in units of phys. quantity (e.g. °C)
d.SP = -1999...9999 trigg. point separation suppl. cont.
/ Y / Off in units of phys. quantity
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
Configuration examples 52 KS 90-1 / KS 92-1
Page 53
4.5.7 Continuous controller with position controller
( Cntr/ C.Fnc =6)
SP
W
Configuration level
INP.1
INP.2
X
Master controller
Ypi d
Ycontinuous
X
Position controller
W
Y. 1
Y. 2
OUT.4
OUT.1
M
OUT.2
Basically, this controller function is a cascade. A slave controller with three-point stepping behaviour working with position feedback Yp as process value (INP2 or INP3) is added to a continuous controller.
ConF / Cntr SP.Fn = 0 setpoint controller
C.Fnc = 6 continuous controller with
position controller
C.Act = 0 inverse output action
(e.g. heating applications)
ConF / InP.2: I.Fnc = 3 position feedback Yp
S.typ = 50 sensor e.g. potentiometer 0..160
ConF / Out.1: O.Act = 0 direct output action Out.1
Y.1 = 1 control output Y1 active Y.2 = 0 control output Y2 not active
ConF / Out.2: O.Act = 0 direct output action Out.2
Y.1 = 0 control output Y1 not active Y.2 = 1 control output Y2 active
PArA / Cntr: Pb1 = 0,1...9999 proportional band 1 (heating)
in units of the physical quantity (e.g. °C)
ti1 = 1...9999 integral time 1 (heating) in sec. td1 = 1...9999 derivative time 1 (heating) in sec. t1 = 0,4...9999 min. cycle tim 1 (heating)
SH = 0...9999 switching difference
KS 90-1 / KS 92-1 53 Configuration examples
Page 54
Configuration level
4.5.8 Measured value output
phys.
quantity
Out.1
phys. quantity
90...250VAC 24VUC
OUT3
OUT4
mA / V
Out.0
0/4mA
0/2V
1
L
}
2
N
3
4 5 6
7 8 9
10 11 12
13 14
15
U
U
20mA
10V
1 2 3
4 5 6
7 8 9
10 11 12
13 14
(16)
15
17
INP1
+
ConF / Out.3 / 4: O.tYP = 1 Out.3/ 4 0...20mA continuous
= 2 Out.3/ 4 4...20mA continuous = 3 Out.3/ 4 0...10V continuous = 4 Out.3/ 4 2...10V continuous
Out.0 = -1999...9999 scaling Out.3/ 4
for 0/4mA or 0/2V
Out.1 = -1999...9999 scaling Out.3/ 4
for 20mA or 10V
O.Src = 3 signal source for Out.3/ 4 is
the process value
Configuration examples 54 KS 90-1 / KS 92-1
Page 55
5 Parameter setting level
5.1 Parameter survey
PArA Parameter setting level
Parameter setting level
È
Ì
Cntr Control and
Pb1 Pb12 SP.Lo InL.1 Inl.2 InL.3 L.1 Pb2 Pb22 SP.Hi OuL.1 OuL.2 OuL.3 H.1 ti1 ti12 SP.2 InH.1 InH.2 InH.3 HYS.1 ti2 ti22 r.SP OuH.1 OuH.2 OuH.3 dEl.1 td1 td12 tF.1 tF.2 tF.3 L.2 td2 td22 E.tc E.tc H.2 t1 HYS.2 t2 dEl.2 SH L.3 Hys.l H.3 Hys.H HYS.3 d.SP dEl.3 tP HC.A tt Y.Lo Y.Hi Y2 Y0 Ym.H L.Ym E.H2O t.on t.off FH2 oFFS tEmp
PAr.2
self-tuning
2. set of parameters
SEtP Set-point and
process value
InP.1 Input 1
InP.2 Input 2
InP.3 Input 3
Lim
Limit value functions
End
Adjustment:
The parameters can be adjusted by means of keys ÈÌ
w
Transition to the next parameter is by pressing key Ù
w
After the last parameter of a group, donE is displayed, followed by
w
automatic change to the next group.
g
Return to the beginning of a group is by pressing the Ù key for 3 sec.
If for 30 sec. no keypress is excecuted the controler returns to the process va lue and setpoint display ( Time Out = 30 sec. )
KS 90-1 / KS 92-1 55 Parameter survey
-
Page 56
Parameter setting level
5.2 Parameters
Cntr
Name Value range Description Default
Pb1 Pb2 ti1 ti2 td1 td2
t1
t2
SH
Hys.l Hys.H
d.SP
tP
tt Y.Lo Y.Hi
Y2
Y.0 Ym.H L.Ym
E.H2O
t.on
t.oFF
F.H2O
oFFS tEmp
1...9999 1
1...9999 1 0,1...9999 0,1...9999 0,1...9999 0,1...9999 0,4...9999
0,4...9999
0...9999
0...9999
0...9999
-1999...9999
0,1...9999
3...9999
-120...120
-120...120
-100...100
-100...100
-100...100
0...9999
-1999...9999
0,1...9999
1...9999
0,1...9999
-120...120
0...9999
Proportional band 1 (heating) in phys. dimensions (e.g. °C) Proportional band 2 (cooling) in phys. dimensions (e.g. °C) Integral action time 1 (heating) [s] Integral action time 2 (cooling) [s] Derivative action time 1 (heating) [s] Derivative action time 2 (cooling) [s] Minimal cycle time 1 (heating) [s]. The minimum impulse is
1/4xt1 Minimal cycle time 2 (heating) [s]. The minimum impulse is
1/4xt2 Neutral zone or switching differential for on-off control
[phys. dimensions) Switching difference Low signaller [engineering unit] Switching difference High signaller [engineering unit]
Trigger point seperation for additional contact /Y/Off [phys. dimensions]
Minimum impulse [s] Motor travel time [s] Lower output limit [%] Upper output limit [%]
2. correcting variable Working point for the correcting variable [%] Limitation of the mean value Ym [%] Max. deviation xw at the start of mean value calculation
[phys. dimensions] Min. temperature for water cooling. Below the set
temperature no water cooling happens Impulse lenght for water cooling. Fixed for all values of
controller output.The pause time is varied. Min. pause time for water cooling. The max. effective
controller output results from t.on/(t.on+t.off)·100% Modification of the (non-linear) water cooling characteristic
(see page 45) Zero offset Sensor temperature (in engineering units e.g. °C)
With oxygen measurement (O
) (see page 65)
2
100 100 180 180 180 180
10
10
2
1 1
100
OFF
60
0
100
0 0 5 8
0
1
10
1
0
750
1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.
Parameters 56 KS 90-1 / KS 92-1
Page 57
Parameter setting level
PAr.2
Name Value range Description Default
Pb12
1...9999 1
Proportional band 1 (heating) in phys. dimensions (e.g. °C),
100
2. parameter set
Pb22
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C),
100
2. parameter set
Ti22 Ti12 Td12 Td22
0,1...9999 0,1...9999 0,1...9999 0,1...9999
Integral action time 2 (cooling) [s], 2. parameter set Integral action time 1 (heating) [s], 2. parameter set Derivative action time 1 (heating) [s], 2. parameter set Derivative action time 2 (cooling) [s], 2. parameter set
10 10 10 10
SEtP
Name Value range Description Default
SP.LO SP.Hi
SP.2 r.SP
SP
-1999...9999
-1999...9999
-1999...9999
0...9999
-1999...9999
Set-point limit low for Weff Set-point limit high for Weff Set-point 2. Set-point gradient [/min] Set-point (only visible with BlueControl!)
0
900
0
OFF
0
g
SP.LO and SP.Hi should be within the limits of rnGH and rnGL see configuration r Controller page
InP.1
Name Value range Description Default
InL.1 OuL.1 InH.1 OuH.1
t.F1
Etc.1
-1999...9999
-1999...9999
-1999...9999
-1999...9999
0,0...9999
0...100 (°C)
32...212 (°F)
Input value for the lower scaling point Displayed value for the lower scaling point Input value for the upper scaling point Displayed value for the lower scaling point Filter time constant [s] External cold-junction reference temperature (external TC)
0
0 20 20
0,5
OFF
InP.2
Name Value range Description Default
InL.2 OuL.2 InH.2 OuH.2
t.F2
-1999...9999
-1999...9999
-1999...9999
-1999...9999 0,0...9999
Input value for the lower scaling point Displayed value for the lower scaling point Input value for the upper scaling point Displayed value for the upper scaling point Filter time constant [s]
0
0 50 50
0,5
InP.3
Name Value range Description Default
InL.3 OuL.3 InH.3 OuH.3
KS 90-1 / KS 92-1 57 Parameters
-1999...9999
-1999...9999
-1999...9999
-1999...9999
Input value for the lower scaling point Displayed value for the lower scaling point Input value for the upper scaling point Displayed value for the upper scaling point
0
0 20 20
Page 58
Parameter setting level
Name Value range Description Default
t.F3
Etc.3
-1999...9999
0...100 (°C)
32...212 (°F
Lim
Name Value range Description Default
L.1
H.1 HYS.1 dEl.1
L.2
H.2 HYS.2 dEl.2
L.3
H.3 HYS.3 dEl.3
HC.A
-1999...9999
-1999...9999
-1999...9999
-1999...9999
-1999...9999
-1999...9999
-1999...9999
0...9999
0...9999
0...9999
0...9999
0...9999
0...9999
Filter time constant [s] External cold-junction reference temperature (external TC)
Lower limit 1 Upper limit 1 Hysteresis limit 1 Alarm delay from limit value 1
0
OFF
10 10
1 0
Lower limit 2 OFF Upper limit 2 OFF Hysteresis limit 2 Alarm delay from limit value 2 Lower limit 3 Upper limit 3 Hysteresis limit 3 Alarm delay from limit value 3 Heat current limit [A]
1 0
OFF
-32000 1 0
50
g
Resetting the controller configuration to factory setting (Default) or resetting to the customer-specific default data set r chapter 11.179
Parameters 58 KS 90-1 / KS 92-1
Page 59
Parameter setting level
5.3 Input scaling
When using current, voltage or resistance signals as input variables for InP.1, InP.2 or/and InP.3 scaling of input and display values at parameter setting level
is required. Specification of the input value for lower and higher scaling point is in the relevant electrical unit (mA/V/).
phys.
quantity
OuH.x
mA / V
OuL.x
InL.x
InH.x
mA/V
phys. quantity
5.3.1 Input Inp.1 and InP.3
g
Parameters InL.x,OuL.x, InH.x and OuH.x are only visible if ConF / InP.x/Corr = 3 is chosen.
S.tYP Input signal InL.x OuL.x InH.x OuH.x
30
(0...20mA)
40
(0...10V)
0 … 20 mA 0 any 20 any 4 … 20 mA 4 any 20 any
0 … 10 V 0 any 10 any 2 … 10 V 2 any 10 any
In addition to these settings, InL.x and InH.x can be adjusted in the range (0...20mA / 0...10V / ) determined by selection of S.tYP .
a
For using the predetermined scaling with thermocouple and resistance thermometer (Pt100), the settings for InL.x and OuL.x and for InH.x and OuH.x must have the same value.
g
Input scaling changes at calibration level (r page 60) are displayed by input scaling at parameter setting level. After calibration reset (OFF), the scaling parameters are reset to default.
5.3.2 Input InP.2
S.tYP Input signal InL.2 OuL.2 InH.2 OuH.2
30 0 … 20 mA 0 any 20 any 31 0 … 50 mA 0 any 50 any
In addition to these settings, InL.2 and InH.2 can be adjusted in the range (0...20/ 50mA/) determined by selection of S.tYP.
KS 90-1 / KS 92-1 59 Input scaling
Page 60
Calibration level
6 Calibration level
Measured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1 or 2 is chosen.
The measured value can be matched in the calibration menu ( CAL). Two me thods are available:
Offset correction
( ConF/ InP.1 / Corr =1 ):
possible on-line at the
w
display
standard setting
offset correction
process
OuL.1
new
OuL.1old
InL.1
-
X
2-point correction
( ConF/ InP.1 / Corr = 2 ):
w
is possible off-line with process value simulator
display
OuH.1
OuH.1
OuL.1
new
OuL.1old
old
new
InL.1
standard setting
2-point correction
InH.1
X
60 KS 90-1 / KS 92-1
Page 61
Offset correction ( ConF/ InP.1 / Corr =1 ):
r
Calibration level
1199
°C
°F
1200
para func
Ada
Err
SP.E
SP.2
r
Ù
3 sec.
r
PArA
Ì
:
CAL
r
Ù
r
InP.1
r
Ù
r
r
r
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest. Subsequently, the operator acknowledges the input value by pressing key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration, OuL.1 is equal to InL.1. The operator can correct the display value by pressing keys ÈÌ . Subsequently, he confirms the display value by pressing key Ù.
InL.1
OuL.1
End
r
r
È Ì
Ù
r
Ù
Ù
KS 90-1 / KS 92-1 61
Page 62
Calibration level
Ù
2-point correction ( ConF/ InP.1 / Corr = 2):
1199
°C
°F
1200
para func Ada
Err
Ù
r
SP.E
SP.2
3 sec.
r
PArA
r
Ì
ConF
r
Ì
CAL
r
Ù
r
InP.1
È Ì
InP.2
È Ì
rr
Ù
InL.1
È
InL1
Ù
OuL.1
InH.1
r
È Ì
r
Ù
r
Ù
Ù
InP.3
È
È
InH.1
Ù
Ì
OuH.1
End
InL.1: The input value of the lower scaling point is displayed.
The operator must adjust the lower input value by means of a process value simulator and confirm the input value by pressing key Ù.
OuL.1: The display value of the lower scaling point is displayed.
Before calibration, OuL.1 equals InL.1. The operator can correct the lower display value by pressing the ÈÌ keys. Subsequently, he confirms the display value by pressing key Ù.
InH.1: The input value of the upper scaling point is displayed. .
The operator must adjust the upper input value by means of the process value simulator and confirm the input value by pressing key Ù.
OuH.1: The display value of the upper scaling point is displayed.
Before calibration OuH.1 equals InH.1. The operator can correct the upper display value by pressing keys ÈÌ Subsequently, he confirms the display value by pressing key Ù.
È Ì
r
Ù
g
The parameters (OuL.1, OuH.1) changed at CAL level can be reset by adjusting the parameters below the lowest adjustment value (OFF) by means of decrement key Ì .
62 KS 90-1 / KS 92-1
Page 63
7 Special functions
7.1 DAC®– motor actuator monitoring
(Digital Actor Control DAC
®
)
Special functions
With all controllers with position feedback Yp, the motor actuator can be monito red for functional troubles. The DAC
®
function can be started by chosing the pa
-
rameter C.Fnc = 5 or 6 at the configuration level ( ConF):
ConF / Cntr / C.Fnc = 5 3-point-stepping controller with
w
position feedback Yp as potentiometer
ConF / Cntr / C.Fnc = 6 Continuous controller with integrated
w
positioner and position feedback Yp as potentiometer
If an error occures, the controller switches to manual operation (ò - LED blinks) and no impulses are given out any longer. If one of the relays shall switch when a
®
DAC
error occures, parameter dAC.A = 1 and inverse action O.Act = 1 must
be selected for the relevant output OUT.1 OUT.4 in the ConF menu ( OUt.3 and 4 only possible if O.tYP = 0 [relay/logic]):
ConF / OUt.x/dAc.A = 1 Motor actuator monitoring (DAC) aktive
w
The system detects the following stepping controller errors:
defective motor
w
defective capacitor (wrong rotating direction)
w
wrong phase followers (wrong rotating direction)
w
defective force transmission at spindle or drive
w
excessive backlash due to wear
w
jamming of the control valve e.g. due to foreign body
w
-
In these cases the controller will change to manual operation and the outputs will be switched off. Is the controller switched to automatic operation again or any modification is done the controller activates the DAC function again and the out puts will be setted.
Resetting of a DAC error:
After solving the technical problem the DAC errror can be acknowledged in the error list. Thereafter the controller works again in normal operation mode.
See also chapter 3.4 "Mainenance manager / Error list", page 12 ff.
KS 90-1 / KS 92-1 63 DAC®– motor actuator monitoring
-
Page 64
Special functions
Functioning of the DAC function
No input filter should be defined for the Yp input ( PArA / InP.x/t.Fx=0). Therewith no wrong detection of blocking or wrong method of operation can be recognized. The automatic calibration can be used with drives outfitted with spring assembly.
Execution of the calibration:
It is controlled if the mean alteration between two messurements is enough for the DAC monitoring. The calibration will be stopped if the alteration between two messurements is too small. The position of 0% is searched. Therefor the drive will be closed until there is no changing of the input signal for 0,5 sec. Assuming that the drive is outfitted with spring assembly, the drive is opened for 2,8 sec. The drive should then still be within the spring assembly. This position is allocated and stored as 0%. With the same procedure the position for 100% is allocated and stored. Simultaneously the motor running time is determined and saved as parameter tt. Afterwards the controller sets the drive in the position before calibration. Was the controller in automatic mode before calibration it will be set to automatic mode again otherwise it remains in manual mode.
g
g
g
The following errors can be occure during calibration:
the change of the Yp input is to small, no monitoring is possible
w
the motion is in wrong direction
w
the Yp input is broken
w
In these cases the automatic calibration will be stopped and the controller remains in manual mode.
If the automatic calibration leads to no resonable results the calibration of the Yp input can be done manual.
If the conroller reaches the positions of 0% or 100% the outputs will be switched off. Also in manual mode it is not possible to exceed these limits.
Because no controller with continuouse output and Yp input is defined there won't be the DAC function for this controlling type.
®
DAC
– motor actuator monitoring 64 KS 90-1 / KS 92-1
Page 65
7.2 O2measurement
This function is available only on the instrument version with INP3.
Special functions
As the O
-measurement result range can extend over many decades, automatic
2
display switch-over between“%”and“ppm“ was realized.
The instantaneous unit is displayed in the lower line.
With set-point changing via keys I or D, the unit of the set-point and of the other parameters is displayed.
Lambda probes (λ probes) are used as sensors.
The electromotive force (in Volts) generated by λ probes is dependent of instan
­taneous oxygen content and temperature. Therefore, KS 90-1 can only evaluate exact measurement results, if it knows the sensor temperature. Distinction of heated and non-heated lambda probes is made. Both can be evalua ted by KS 90-1.
Heated lambda probes Controlled heating which ensures constant temperature is integrated in the heated
λ probe. This temperature must be entered in KS 90-1 parameter Probe tempera­ture.
-
Parameter r Controller r Probe temperature r .....°C (/°F - dependent of confi-
guration)
Non-heated lambda probes
With the probe always operated at a fixed, known temperature, a procedure as used for a heated probe can be used.
A non-heated λ probe is used, unless the temperature is constant. In this case, the probe temperature in addition to the probe mV value must be measured. For this purpose, any temperature measurement with one of the analog inputs INP2 or INP3 can be used. During function selection, the input must be set to X2 (second process value).
7.2.1 Connection
Connect the input for the lambda probe to INP1. Use terminals A15 and A17. If necessary, temperature measurement must be connected to INP2 or INP3.
Cntr r tEmP temp. 0...9999
KS 90-1 / KS 92-1 65 O2measurement
Page 66
Special functions
7.2.2 Configuration:
Oxygen measurement
Oxygen measurement with heated lambda probe Controller r Process value processing r 7: O temperature
Oxygen measurement with non-heated lambda probe Controller r Process value processing r O temperature
Input 1 r Function INP1 r 7: process value X1
functions with constant probe
2
Cntr r C.tYP 7 O2-const
functions with measured probe
2
Cntr r C.tYP 8 O2+temp
InP.1 r 1.Fnc 7 X1-Input
g
In input 1, the sensor type is set for one of the high-impedance voltage inputs: Input 1 r Sensor type r 42: special (-25...1150 mV) or
41: special (-2,5...115 mV)
InP.1 r S.tyP 41 115 mV
InP.1 r S.tyP 42 1150 mV
Input 1 r meas. value correction r 0: no correction
InP.1 r S.Lin 0no
Temperature measurement (required with non-heated lambda probe)
Any temperature measurement with one of analog inputs INP2 or INP3 can be used. Select input X2 during function selection (second set-point).
With O2measurement, evaluation in ppm or % must be specified for all parameters related to the process value. This is done centrally during configuration.
Other r Parameter unit for O
othrr O2 0 unit : ppm othrr O2 1 unit : %
r 0: parameter for O2function in ppm
2
1: parameter for O
function in %
2
g
Whether the temperature of the non-heated λ probe is specified in °C or °F can be selected during configuration. Other r Unit r 1: in Celsius
2: in Fahrenheit
othrr Unit C othrr Unit F
O2measurement 66 KS 90-1 / KS 92-1
Page 67
7.3 Linearization
I
Linearization for inputs INP1 or INP3 Access to table “ Lin” is always with selection of sensor type S.TYP = 18:
special thermocouple in INP1 or INP3, or with selection of linearization S.Lin 1: special linearization.
Dependent of input type, the input signals are specified in µV or in Ohm dependent of input type.
With up to 16 segment points, non-linear signals can be simulated or linearized. Every segment point comprises an input (In.1 In.16) and an output (Ou.1Ou.16). These segment points are interconnected automatically by means of straight lines. The straight line between the first two segments is extended downwards and the straight line between the two largest segments is extended upwards. I.e. a defined output value is also provided for each input value.
When switching an In.x value to OFF, all other ones are switched off. Condition for these configuration parameters is an ascending order. In.1 < In.2 < ...< In.16 and Ou.1 < Ou.2 ...< Ou.16.
Special functions
n.16
. . . . . .
In 1
Ou.1 Ou.16.....................
KS 90-1 / KS 92-1 67 Linearization
Page 68
Special functions
7.4 Loop alarm
The loop alarm monitors the control loop for interruption (not with three-point stepping controller and not with signallers.) With parameter LP.AL switched to 1(= loop alarm active), an interruption of the control loop is detected, unless the process value reacts accordingly with Y=100% after elapse of 2xTi. The loop alarm shows that the control loop is interrupted. You should check hea ting or cooling circuit, sensor, controller and motor actuator. During self-tuning, the control loop is not monitored (loop alarm is not active).
7.5 Heating current input / heating current alarm
The heating current alarm monitors the heating current. In addition to short circuit monitoring, checking either for overload (current > heating current limit value) or for interruption (current < heating current limit va lue) is done. Each of the analog inputs can be used as measurement input. If electrical heating is concerned, INP2 which is always provided can be configu­red for measuring range 0...50mA AC and connected directly using a heating cur­rent transformer.
-
-
a
With t1 < 400 ms or tp < 200 ms (effective time!), heating current monitoring is ineffective.
Loop alarm 68 KS 90-1 / KS 92-1
Page 69
7.6 KS90-1 as Modbus master
Special functions
a
This function is only selectable with BlueControl (engineering tool)!
Additions othr (only visible with BlueControl!)
Name Value range Description Default
MASt
Cycl
AdrO
AdrU
Numb
0 1
0...200
1...65535
1...65535
0...100
Controller is used as Modbus master
Slave Master Cycle time [ms] for the Modbus master to transmit its data
to the bus. Target address to which the with AdrU specified data is
given out on the bus. Modbus address of the data that Modbus master gives to
the bus. Number of data that should be transmitted by the Modbus
master.
The KS90-1 can be used as Modbus master ( ConF / othr / MASt =1).The Modbus master sends ist data to all slaves (Broadcast message, controller adress
0). It transmits its data (modbus adress AdrU) cyclic with the cycle time Cycl to the bus. The slave controller receives the data transmitted by the masters and al­locates it to the modbus target adress AdrO. If more than one data should be transmitted by the master controller ( Numb > 1) , the modbus adress AdrU in­dicates the start adress of the data that should be transmitted and AdrO indicates the first target adress where the received data should be stored. The following data will be stored at the logically following modbus target adresses. With this it is possible e.g. to specify the process value of the master controller as set-point for the slave controllers.
0
60
1
1
0
7.7 Back-up controller (PROFIBUS)
Back-up operation: calculation of the control outputs is in the master. The con troller is used for process value measurement, correcting variable output and for display. With master or communication failure, control is taken over independently and bumplessly by the controller.
KS 90-1 / KS 92-1 69 KS90-1 as Modbus master
-
Page 70
BlueControl
8 BlueControl
BlueControl is the projecting environment for the BluePortcontroller series of PMA. The following 3 versions with graded functionality are available:
The mini version is - free of charge - at your disposal as download at PMA home­page www.pma-online.de or on the PMA-CD (please ask for).
At the end of the installation the li cence number has to be stated or DEMO mode must be chosen.
At DEMO mode the licence num ber can be stated subsequently un der Help r Li
cence r Change.
-
-
-
-
70 KS 90-1 / KS 92-1
Page 71
9 Versions
Versions
Unit/f ront according to customer specification XX
Accessories delivered with the unit
Operating manual (if selected by the ordering code)
2 fixing clamps
w
operating note in 12 languages
w
Accessory equipment with ordering information
Description Order no.
Heating current transformer 50A AC 9404-407-50001 PC-adaptor for the front-panel interface 9407-998-00001 Standard rail adaptor 9407-998-00061 Operating manual German 9499-040-62918 Operating manual English 9499-040-62911 Operating manual French 9499-040-62932 Interface description Modbus RTU German 9499-040-63718 Interface description Modbus RTU English 9499-040-63711 BlueControl (engineering tool) Mini Download www.pma-online.de BlueControl (engineering tool) Basic 9407-999-11001 BlueControl (engineering tool) Expert 9407-999-11011
KS 90-1 / KS 92-1 71
Page 72
Technical data
10 Technical data
INPUTS
PROCESS VALUE INPUT INP1
Resolution: > 14 bits Decimal point: 0 to 3 digits behind the decimal
point Dig. input filter: adjustable 0,000...9999 s Scanning cycle: 100 ms Measured value
correction:
2-point or offset correction
Thermocouples
r Table 1 (page 76 )
Internal and external temperature compensation
Input resistance: Effect of source resistance: 1 µV/
≥1MΩ
Internal temperature compensation
Maximal additional error: ± 0,5 K
Sensor break monitoring
Sensor current: Configurable output action
≤1µ
A
Thermocouple to specification
Measuring range -25...75mV in conjunction with the linearization can be used for connecting thermocouples which are not included in Table 1.
Current and voltage signals
r Table 3 (page 76 )
Span start, end of span: anywhere within measuring
range Scaling: selectable -1999...9999 Linearization: 16 segments, adaptable with
BlueControl Decimal point: adjustable Input circuit monitor: 12,5% below span start (2mA,
1V)
SUPPLEMENTARY INPUT INP2
Resolution: > 14 bits Scanning cycle: 100 ms
Heating current measurement
via current transformer (Accessory equipment)
Measuring range: 0...50mA AC Scaling: adjustable -1999...0,000...9999 A
Current measuring range
Technical data as for INP1
Potentiometer
r Table 2 (page 76 )
Connection: 2-wire Lead resistance: max. 30 Ohm Input circuit monitor: Break
Resistance thermometer
r Table 2 (page 76 )
Connection: 3-wire Lead resistance: max. 30 Ohm Input circuit monitor: break and short circuit
Special measuring range
BlueControl (engineering tool) can be used to match the input to sensor KTY 11-6 (character istic is stored in the controller).
Physical measuring range: 0...4500 Ohm Linearization segments 16
SUPPLEMENTARY INPUT INP3 (OPTION)
Resolution: > 14 bits Scanning cycle: 100 ms
Technical data as for INP1 except 10V range.
CONTROL INPUTS DI1, DI2
Configurable as switch or push-button!
-
Connection of a potential-free contact suitable for switching “dry” circuits.
Switched voltage: 5 V Current: 100µA
72 KS 90-1 / KS 92-1
Page 73
Technical data
CONTROL INPUTS DI2, DI3 (OPTION)
The functions of control input di2 on the analog card and of di2 on the options card are logically ORed. Configurable as direct or inverse switches or keys. Optocoupler input for active triggering.
Nominal voltage 24 V DC external Current sink (IEC 1131 type 1) Logic “0” -3...5 V Logic “1” 15...30 V Current requirement approx.. 5 mA
TRANSMITTER SUPPLY UT (OPTION)
Power: 22 mA /≥18 V
As analog outputs OUT3 or OUT4 and trans mitter supply U
are connected to different
T
-
voltage potentials, an external galvanic connec tion between OUT3/4 and U
is not permissible
T
with analog outputs.
GALVANIC ISOLATION
Safety isolation Function isolation
Process value input INP1
Mains supply Supplementary input INP2
Optional input INP3
Digital input di1, di2 Relay OUT1 RS422/485 interface Relay OUT2 Digital inputs di2, 3 Relay OUT3 Universal output OUT3 Relay OUT4 Universal output OUT4
Transmitter supply U
T
OUT5, OUT6
OUTPUTS
RELAY OUTPUTS OUT1...OUT4
Contact type: potential-free changeover contact Max.contact rating: 500 VA, 250 V, 2A at 48...62 Hz,
resistive load Min. contact rating: 6V, 1mA DC Number of electical
switching cycles:
for I = 1A/2A: 800.000 / 500.000
(at ~ 250V (resistive load)
Note:
If the relays operate external contactors, these must be fitted with RC snubber circuits to man ufacturer specifications to prevent excessive switch-off voltage peaks.
OUT3, 4 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable resolution: 11 bits
Current output
0/4...20 mA configurable. Signal range: 0...approx.22mA Max. load: Load effect: no effect Resolution: Accuracy
500
≤22µ ≤40µ
A (0,1%) A (0,2%)
Voltage output
-
0/2...10V configurable Signal range: 0...11 V Min. load: 2k Load effect: no effect Resolution: Accuracy
11 mV (0,1%)
20 mV (0,2%)
OUT3, 4 used as transmitter supply
Output power: 22 mA /≥13 V
OUT3, 4 used as logic output
Load≤500 Load > 500
0/≤20 mA 0/> 13 V
OUTPUTS OUT5/6 (OPTION)
Galvanically isolated opto-coupler outputs. Grounded load: common positive voltage. Output rating: 18...32 VDC; 70 mA Internal voltage drop: 1 V with I Protective circuit: built-in against short circuit, overload, reversed polarity (free-wheel diode for relay loads).
max
-
KS 90-1 / KS 92-1 73
Page 74
Technical data
POWER SUPPLY
Dependent of order:
AC SUPPLY
Voltage: 90...260 V AC Frequency: 48...62 Hz Power consumption approx. 8,0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage: 20,4...26,4 V AC Frequency: 48...62 Hz DC voltage: 18...31 V DC Power consumption: approx.. 8,0 VA
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters and adjusted set-points, control mode: Non-volatile storage in EEPROM
BLUEPORT FRONT INTERFACE
Connection of PC via PC adapter (see "Acces­sory equipment"). The BlueControl software is used to configure, set parameters and operate the device.
Humidity
75% yearly average, no condensation
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency: 10...150 Hz Unit in operation: 1g or 0,075 mm Unit not in operation: 2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock: 15g Duration: 11ms
Electromagnetic compatibility
Complies with EN 61 326-1 (for continuous, non-attended operation)
GENERAL
Housing
Material: Makrolon 9415 flame-retardant Flammability class: UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
BUS INTERFACE (OPTION)
Galvanically isolated Physical: RS 422/485 Protocol: Modbus RTU Transmission speed: 2400, 4800, 9600, 19.200 bits/sec Address range: 1...247 Number of controllers per bus: 32 Repeaters must be used to connect a higher number of
controllers.
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel: IP 65 (NEMA 4X) Housing: IP 20 Terminals: IP 00
Permissible temperatures
For specified accuracy: 0...60°C Warm-up time: 15 minutes For operation: -20...65°C For storage: -40...70°C
Safety test
Complies with EN 61010-1 (VDE 0411-1): Overvoltage category II Contamination class 2 Working voltage range 300 V Protection class II
Certifications
Type-tested to DIN 3440 (applied for)
For use in:
w
Heat generating plants with outflow temperatures up to 120°C to DIN 4751
w
Hot water plants with outflow temperatures above 110°C to DIN 4752
w
Thermal transfer plants with organic transfer media to DIN 4754
w
Oil-heated plants to DIN 4755
74 KS 90-1 / KS 92-1
Page 75
cUL certification
(Type 4x, indoor use) For compliance with cUL certificate,the follow ing information must be taken into account:
Use only 60 / 75 or 75°C copper (Cu) wire.
w
Tighten the terminal- screws with a torque
w
of 0,5 - 0,6 Nm
Ambient temperature: 40°C Power supply: 250VAC
Electrical connections
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to
w
DIN 46 244 or screw terminals for 0,5 to 2,5mm²
w
On instruments with screw terminals, the insulation must be stripped by min. 12 mm. Choose end crimps accordingly.
Technical data
-
Mounting
Panel mounting with two fixing clamps at top/ bot­tom or right/left, high-density mounting possible
Mounting position: uncritical Weight: 0,27kg
Accessories delivered with the unit
Operating manual Fixing clamps
KS 90-1 / KS 92-1 75
Page 76
Technical data
Table 1 Thermocouples measuring ranges
Thermoelementtype Measuring range Accuracy Resolution (Ô) L Fe-CuNi (DIN) -100...900°C -148...1652°F ß 2K 0,1 K J Fe-CuNi -100...1200°C -148...2192°F ß 2K 0,1 K K NiCr-Ni -100...1350°C -148...2462°F ß 2K 0,2 K N Nicrosil/Nisil -100...1300°C -148...2372°F ß 2K 0,2 K S PtRh-Pt 10% 0...1760°C 32...3200°F ß 2K 0,2 K R PtRh-Pt 13% 0...1760°C 32...3200°F ß 2K 0,2 K T Cu-CuNi -200...400°C -328...752°F ß 2K 0,05 K C W5%Re-W26%Re 0...2315°C 32...4199°F ß 2K 0,4 K D W3%Re-W25%Re 0...2315°C 32...4199°F ß 2K 0,4 K E NiCr-CuNi -100...1000°C -148...1832°F ß 2K 0,1 K B * PtRh-Pt6% 0(100)...1820°C 32(212)...3308°F ß 2K 0,3 K
* Specifications valid for 400°C
Table 2 Resistance transducer measuring ranges
Type Signal Current Measuring range Accuracy Resolution (Ô) Pt100 Pt100 -200...850°C -140...1562°F ß 1K 0,1K Pt1000 -200...850°C -140...1562°F ß 2K 0,1K KTY 11-6 * -50...150°C -58...302°F ß 2K 0,05K Spezial 0...4500 Spezial 0...450 Poti 0...160 Poti 0...450 Poti 0...1600 Poti 0...4500
* Or special **Measuring range 150°C with reduced lead resistance. Max. 160 [ for meas. and lead resistances (150°C = 157,33 [).
0,2mA
-200...100°C (150**) -140...212°F ß 1K 0,1K
ß 0,02 % 0,01 %
Table 3 Current and voltage measuring ranges
Measuring range Input impedance Accuracy Resolution (Ô) 0-10 Volt
-2,5-115 mV
-25-1150 mV 0-20 mA
~ 110 k
? 1M ? 1M
20
ß 0,1 % 0,6 mV
ß 0,1 % ß 0,1 %
ß 0,1 %
6 µV 60 µV 1,5 µA
76 KS 90-1 / KS 92-1
Page 77
11 Safety hints
This unit was
built and tested in compliance with VDE 0411-1 / EN 61010-1 and
delivered in safe condition.
complies European guideline 89/336/EWG (EMC) and is provided with CE marking.
tested before delivery and passed the tests required by test schedule.
To maintain this condition and to ensure safe operation, the user must follow
the hints and warnings given in this operating manual.
Safety hints
a
The unit is intended exclusively for use as a measurement and control instru
-
ment in technical installations.
Warning
If the unit is damaged to an extent that safe operation seems impossible, the unit must not be taken into operation.
ELECTRICAL CONNECTIONS
The electrical wiring must conform to local standards (e.g. VDE 0100).
The input measurement and control leads must be kept separate from signal
and power supply leads. In the installation of the controller a switch or a circuit-breaker must be used
and signified.
The switch or circuit-breaker must be installed near by the controller and the user must have easy access to the controller.
COMMISSIONING
Before instrument switch-on, check that the following information is taken into account:
Ensure that the supply voltage corresponds to the specifications on the type label.
w
All covers required for contact protection must be fitted.
w
If the controller is connected with other units in the same signal loop, check
w
that the equipment in the output circuit is not affected before switch-on. If necessary, suitable protective measures must be taken. The unit may be operated only in installed condition.
w
Before and during operation, the temperature restrictions specified for
w
controller operation must be met.
SHUT-DOWN
For taking the unit out of operation, disconnect it from all voltage sources and protect it against accidental operation. If the controller is connected with other equipment in the same signal loop, check that other equipment in the output circuit is not affected before switch-off. If ne cessary, suitable protective measures must be taken.
KS 90-1 / KS 92-1 77
-
Page 78
Safety hints
MAINTENANCE, REPAIR AND MODIFICATION
The units do not need particular maintenance.
a
l
a
Warning
When opening the units, or when removing covers or components, live parts and terminals may be exposed.
Before starting this work, the unit must be disconnected completely.
After completing this work, re-shut the unit and re-fit all covers and components. Check if specifications on the type label must be changed and correct them, if necessary.
Caution
When opening the units, components which are sensitive to electrostatic dischar ge (ESD) can be exposed. The following work may be done only at workstations with suitable ESD protection.
Modification, maintenance and repair work may be done only by trained and aut­horized personnel. For this purpose, the PMA service should be contacted. The cleaning of the front of the controller should be done with a dry or a wetted (spirit, water) handkerchief.
-
78 KS 90-1 / KS 92-1
Page 79
11.1 Resetting to factory setting,
or to a customer-specific data set In case of faultyconfiguration, the device can be reset to a default condition. Unless changed, this basic setting is the manufacturer-specific controller default setting.
Safety hints
However, this setting may have been changed by means of the BlueControl software. This is recommendable e.g. when completing commissioning in order to cancel accidental alteration easily. Resetting can be activated as follows:
1
ÌÈ + Power on
FAC
Tory
1.
Press keys È and Ì simultaneously FACtory is displayed after power on,
after approx. 2 seconds, the display changes to FACno.
Keys È and Ì can be used for switch-over between no and yEs in the se­cond line.
FAC
no
2.
2
È
FAC
YEs
®
1
When pressing the Enter key with ”no”, the unit starts without copying the default data.
When pressing the Enter key with ”yEs”, there are four possibilities:
FAC
COPY
2
FAC
COPY
3
FAC
PASS
8.8.8.8.
8.8.8.8.
4
KS 90-1 / KS 92-1 79 Resetting to factory setting,
Page 80
Safety hints
g
g
Safety switches
1 closed any any always 2 open free none Factory reset without 3 open free defind Factory reset after entry 4 open min. 1
Timeout Unless a key is pressed during 10 seconds, a timeout occurs and the instruments starts without copying the default data.
The process COPY can take several seconds. Subsequently, the instrument changes to normal operation.
Levels Password Instrument reaction after confirming
YES” by pressing Ù
factory reset
prompt for the password
of the correct pass number
any Factory reset is omitted
disabled
Resetting to factory setting, 80 KS 90-1 / KS 92-1
Page 81
0-9
Index
Water cooling non-linear ......45
Current signal measuring range ....73
2-point correction............61
A
Alarm handling ..........26-27
B
Bargraph ................11
BlueControl...............71
Bus interface
Technical Data ............74
C
Calibration level (CAL)......61-63
Certifications ..............75
Configuration examples
2-point controller ..........48
3-point controller ..........49
3-point stepping controller......50
Continuous controller ........51
D - Y -Off controller.........52
Measured value output........54
Signaller ...............47
Configuration level
Configuration parameters ....30-42
Parameter survey ..........29
Connecting diagram ...........6
Connecting examples
di2/3, 2-wire transmitter supply....8
INP2 current transformer .......7
OUT1/2 heating/cooling .......7
OUT3 as logic output ........10
OUT3 transmitter supply .......9
RS485 interface ............9
Control inputs di1, di2, di3
Technical data ............73
Cooling functions
Constant period ...........46
Standard ...............44
D
DAC................64-65
Digital inputs di1, di2, di3
Configuration ............38
Technical data ............73
E
Environmental conditions .......75
Equipment ...............72
Error list ................13
F
Front view ...............11
I
Input INP1
Configuration ............31
Parameters ..............59
Technical data ............73
Input INP2
Configuration ............32
Parameters ..............59
Technical data ............73
Input INP3
Configuration ............33
Parameters ..............59
Technical data ............73
Input scaling ............59-60
L
LED
Ada-LED..............11
Err-LED ..............11
func-LED..............11
ì -LED...............11
LED colours .............11
ò -LED...............11
para-LED..............11
KS 90-1 / KS 92-1 81
Page 82
SP.2-LED..............11
SP.x-LED..............11
Linearization ..............68
R
Ramp ..................43
Resetting to factory setting .......78
M
Mainenance manager .......13-15
Manual tuning .............24
Modbus master .............70
Mounting.................5
O
O2-measurement ............66
Offset correction ............61
Optimization at the setpoint ......18
Output OUT1
Configuration ............36
Technical data ............74
Output OUT2
Technical data ............74
Resistance thermometer measuring range
.....................73
S
Safety hints ............77-78
Safety switch...............5
Safety test................75
Self-tuning
Cancelation .............21
Cancelation causes..........22
SEtP ..................59
Set-point ................59
Set-point gradient............43
Set-point processing ..........43
T
Output OUT3
Configuration ............36
Technical data ............74
Output OUT4
Technical data ............74
Output OUT5
Configuration ............38
Technical data ............74
Output OUT6
Configuration ............38
Technical data ............74
Oxygen measurement .........66
P
Parameter setting level
Parameter survey ..........55
Parameters ...........56-58
Thermocouple measuring range ....73
V
Versions ................72
Voltage signal measuring range ....73
Power supply ..............74
82 KS 90-1 / KS 92-1
Page 83
Page 84
West Pro-4 user manual – 59559
Subject to alterations without notice © PMA Prozeß- und Maschinen-Automation GmbH Änderungen vorbehalten P.O.B. 310 229, D-34058 Kassel, Germany Sous réserve de toutes modifications Printed in Germany 9499-040-62911 (02/2005)
2
A5 auf A6 gefaltet, 2-fach geheftet, SW-Druck Normalpapier weiß 80g/m
Loading...