West Control Solutions N8840 User Manual

profiler 8840
Operating manual
English
9499-040-70711
Valid from: 8405
8800/8840 Configurator
More efficiency in engineering, more overview in operating: The projecting environment for the West controllers 8800/8840
ATTENTION!
Mini Version and Updates on
www.westinstruments.com
Description of symbols:
g General information a General warning l Attention: ESD sensitive devices
© West Instruments Printed in Germany
All rights reserved. No part of this document may bereproduced or published in any form or by any means without prior written permission from the copyright
Content2
1. Mounting 5
2. Electrical connections 6
2.1 Connecting diagram .....................6
2.2 Terminal connection .....................7
3. Operation 11
3.1 Front view..........................11
3.2 Behaviour after power-on ..................12
3.3 Operating level .......................12
3.4 Error list / Maintenance manager ..............13
3.5 Self-tuning .........................15
3.5.1 Preparation for self-tuning ..................16
3.5.2 Optimization after start-up or at the set-point ........16
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)........17
3.5.4 Self-tuning start ........................21
3.5.5 Self-tuning cancellation ...................22
3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning
22
3.5.7 Examples for self-tuning attempts ............23
3.6 Manual self-tuning .....................24
3.7 Second PID parameter set..................25
3.8 Alarm handling .......................26
3.9 Operating structure .....................28
4. Configuration level 29
4.1 Configuration survey .................29
4.2 Adjustment: .......................29
4.3 Configuration parameters ..................30
4.4 Set-point processing.....................47
4.5 8840 profiler cooling functions ...............48
4.5.1 Standard ( CyCl= 0 )....................48
4.5.2 Heating and cooling with constant period ( CyCl= 3 )...48
4.6 Configuration examples...................49
4.6.1 On-Off controller / Signaller (inverse) ............49
4.6.2 2-point controller (inverse) ..................50
4.6.3 3-point controller (relay & relay) ...............51
4.6.4 3-point stepping controller (relay & relay) ..........52
4.6.5 Continuous controller (inverse) ................53
4.6.6 ∆ - Y - Off controller / 2-point controller with pre-contact . 54
KS90-1p 3
4.6.7 8840 profiler with measured value output ..........55
4.6.8 Continuous controller with integrated positioner ( Cntr/ C.Fnc = 6 ) 56
5. Parameter setting level 57
5.1 Parameter survey .....................57
5.2 Parameters ........................58
5.3 Input scaling.........................61
5.3.1 Input Inp.1 and InP.3 ..........61
5.3.2 Input InP.2 .........................61
6. Calibration level 62
7. Programmer level 65
7.1 Parameter survey .....................65
7.2 Parameters ........................66
7.3 Programmer description...................68
7.3.1 General ............................68
7.3.2 Programmer set-up: ......................69
7.3.3 Operation ...........................71
7.3.4 Programmer display .....................72
7.3.5 Segment type .........................73
7.3.6 Bandwidth monitoring ...................74
7.3.7 Search run at programmer start ................74
7.3.8 Behaviour after mains recovery or sensor error .......74
8. Special functions 75
8.1 8840 profiler as Modbus master ..............75
8.2 Linearization ........................76
9. 8800/8840 Configurator 77
10. Versions 78
11. Technical data 79
12. Safety hints 84
12.1 Resetting to factory setting ................85
13. Notes 88
4 8840 profiler
1 Mounting
*
Mounting
min.48 (1.89")
(0.4")
10
118
WEST
96 (3.78")
48 (1.89")
(4.65")
8840
RUN
-PrgEdit-
1..10
(0.04..0.4")
+0,6
45
(1.77" )
+0.02
Loc
security switch
+0,8
+0.03
92
max.
(3.62" )
max. 95% rel.
60°C
0°Cmin.
%
Ü
or
Ü
*
Safety switch:
For access to the safety switch, the controller must be withdrawn from the housing. Squeeze the top and bottom of the front bezel between thumb and forefinger and pull the controller firmly from the housing.
Loc open Access to the levels is as adjusted by means of 8800/8840
Configurator (engineering tool)
closed 1 all levels accessible wihout restriction
1 Factory setting 2 Default setting: display of all levels
suppressed, password PASS = OFF
2
l
Caution! The unit contains ESD-sensitive components.
8840 profiler 5
Electrical connections
U
2 Electrical connections
2.1 Connecting diagram
3
1
2
90...250V 24 V UC
OUT1
OUT2
OUT3
OUT4
!
V
V
d b
c
e
8
9
0
RGND
DATA B
DATA A
RS485 RS422
Modbus RT
1 2 3
4 5 6
7 8 9
10 11 12
13 14 15
a
+24V DC
OUT5 OUT6
24V GND
RXD-B
RXD-A
TXD-B
TXD-A
GND
di2
di3
U
1 2 3
di1
7
di2
4 5 6
7
g
HC
mA
INP2
f
5
8 9
10 11
(mV)
0%
100%
mA
INP3
6
12
13 14 15
mA
Volt
INP1
4
(16)
Option
1
(2)
3
4
5
10
11
12
13
14
15
(16)
17
6
7
8
9
VP (5V)
DGND
RxD/TxD-N
RxD/TxD-P
Schirm/ Screen
T
17
PROFIBUS-DP
(mV)
a
b
390 [
220 [
Adapter
390 [
cd
DGND
9
8
7
VP (5V)
6
Profibus DP
e
max.
1200m
5
4
3
2
1
5
9
4
8
3
7
2
6
1
g
Dependent of order, the controller is fitted with :
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or
w
screw terminals for 0,5 to 2,5mm²
w
Connecting diagram 6 8840 profiler
2.2 Terminal connection
Power supply connection 1
See chapter 11 "Technical data"
Electrical connections
Connection of outputs OUT1/2 2
Relay outputs (250V/2A), potential-free changeover contact
Connection of outputs OUT3/4 3
a relay (250V/2A), potential-free
changeover contact, universal output
b current (0/4...20mA) c voltage (0/2...10V) d transmitter supply e logic (0..20mA / 0..12V)
Connection of input INP1 4
Input mostly used for variable x1 (process value)
a thermocouple b resistance thermometer (Pt100/ Pt1000/ KTY/ ...) c current (0/4...20mA) d voltage (0/2...10V)
2 OUT1/2 heating/cooling
L
N
1 2
3
4
5
6
7
8
9
10 11 12
13 14 15
10 11 12
13 14
(16)
1 2 3
4 5 6 7 8 9
15
17
+
Connection of input INP2 5
f heating current input (0..50mA AC)
or input for ext. set-point (0/4...20mA)
g potentiometer input for position
feedback
Connection of input INP3 6
As input INP1, but without voltage
Connection of inputs di1, di2 7
Digital input, configurable as switch or push-button
Connection of inputs di2/3 8 (option)
Digital inputs (24VDC external), galvanically isolated, configurable as switch or push-button
5 INP2 current tansformer
L
1 2
3 4
5 6
7 8
Logik
9
10 11 12
13 14 15
10 11 12
13 14 15
(16)
17
1 2 3
4 5
6 7
8 9
SSR
_
+
8840 profiler 7 Terminal connection
Electrical connections
Connection of output UT9 (option)
Supply voltage connection for external energization
Connection of outputs OUT5/6 0 (option)
Digital outputs (opto-coupler), galvanic isolated, common positive control voltage, output rating: 18...32VDC
Connection of bus interface ! (option)
PROFIBUS DP or RS422/485 interface with Modbus RTU protocol
89 di2/3, 2-wire transmitter supply
10
OUT3
11 12
13
+
+24VDC
+
3
0V
1
2
-
K
J
17,5V 22mA
13 14 15
5mA
5mA
+
-
Option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
14
(16)
17
15
-
J
a
Terminal connection 8 8840 profiler
If the universal output OUT3 or OUT4 is used there may be no external galvanic connection between measuring and output circuits!
3 OUT3 transmitter supply
Electrical connections
3
13V
22mA
1
K
2
-
+
10 11
12
13 14 15
11 12
14
(16)
17
13
15
+
-
9 RS485 interface (with RS232-RS485 interface converter) *
R = 120...200 OhmT
RT
RGND connection optional
RGND
DATA B
DATA A
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
J
10
11
12
13
14
15
RGND
DATA B
DATA A
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
10
11
12
13
14
15
max. 1000m
"Twisted Pair” cable
RGND
DATA B
DATA A
R=100 Ohm
option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
RT
R = 120...200 OhmT
10
11
12
13
14
15
PC
RS485-RS232
converter
* Interface description Modbus RTU in speperate manual: see page 78.
8840 profiler 9 Terminal connection
Electrical connections
3 OUT3 as logic output with solid-state relay (series and parallel connection)
Series connection
SSR
I =22mA
max
_
4V
+
SSR
_
4V
+
SSR
_
4V
+
12V
10
11
12
Logic
SSR
SSR
Parallel connection
I =22mA
max
_
+
_
+
12V
10 11
12
8840 profilerconnecting example:
L1
L2
fuse
8840 profiler
1 2
3 4
5 6
7 8 9
10 11
12
13 14 15
Logic
10 11 12
13 14
(16)
1 2 3
4 5 6 7 8 9
15
17
SSR
_
+
fuse
contactor
+
heating
1
6700 Limit controller
Standard version: N6700Z21
00
other versions on requestr
1
6700 Limit
controller
fuse
N1
N2
a
CAUTION: Using a Limit controller is recommendable in systems
where overtemperature implies a fire hazard or other risks.
Terminal connection 10 8840 profiler
RUN
-PrgEdit-
WEST
8840
1
2
3
4 5 6
%
7 8
&
(
)
/
°C °F
9 0
RUN
§ $
!"
3 Operation
3.1 Front view
LED colours:
LED 1, 2, 3, 4: yellow Bargraph: red other LEDs: red
g
In the upper display line, the process value is always displayed. At parameter, configuration, calibration as well as extended operating level, the bottom display line changes cyclically between parameter name and parameter value.
Operation
1 Status of switching outputs
OuT.1... 6
2 Process value display 3 Set-point, controller output 4 Signals display on °C or °F 5 Signals ConF and PArA level 6 Signals aktive function key 7 Self-tuning active 8 Entry in error list 9 Bargraph or clear text display 0 SP.2 is effective ! SP.E is effective " Set-point gradient effective
§ Manual/automatic switch-over:
Off:Automatic On:Manual(changing possible) Blinks:Manual (changing not
possible (r ConF/ Cntr/ MAn)
$ Enter key:
calls up error list / extended operating level /
% Up/down keys:
changing the set-point or the controller output value
& Manual mode /spec. function
(ConF / LOGI )
/ switchover programmer /
controller operation or, with pure controller operation, freely programmable function key
( programmer: run/stop
controller: automatic/manual other function (ConF / LOGI)
) PC connection for 8800/8840
Configurator (engineering tool)
8840 profiler 11 Front view
Operation
P
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the operating level. The unit is in the condition which was active before power-off. If the 8840 profiler was in manual mode at supply voltage switch-off, the controller will re-start with the last output value in manual mode at power-on.
3.3 Operating level
The content of the extended operating level is determined by means of 8800/8840 Configurator (engineering tool). Parameters which are used frequently or the display of which is important can be copied to the extended operating level.
Controller
Automatic
1199
1200
time
out
1199
Y21
Ù
Ù
i
È Ì
display
only
Ò
Ò
i
Hand
1199
Y21
Ù
1199
1200
Ù
Extended Operating Level
time
out
Errorlist (when errors exist)
126
FbF.1
Err
Display
Changes
126
2
Err
È Ì
time
out
È Ì
/
è
Ù
rogrammer
67
0
10 OFF
run
Ò
67
69
10/00:10
run
Ò
119
120
10-01:23
run
>3 Sec.
Ò
230
230
10 End
run
Behaviour after power-on 12 8840 profiler
3.4 Error list / Maintenance manager
With one or several errors, the extended operating level always starts with the error list. Signalling an actual entry in the error list (alarm, error) is done by the Err LED in the display. To reach the error list press Ù twice.
Err LED status Signification Proceed as follows
blinks(status 2) Alarm due to existing
error
lit(status 1) Error removed, alarm
not acknowledged
off(status 0) No error, all alarm
entries deleted
Determine the error type in the error list After error correction the unit changes to status 1
Acknowledge the alarm in the error list pressing key
Èor Ì The alarm entry was deleted (status 0).
-Not visible except when acknowledging
Operation
°C
°F
RUN
Error list:
Name
E.1
E.2
E.3
E.4
FbF.1
Sht.1
POL.1 FbF.2
Sht.2
POL.2 FbF.3
Sht.3
POL.3
Internal error, cannot be removed
Internal error, can be reset
Configuration error, can be reset
Hardware error - Codenumber and
Sensor break INP1
Short circuit INP1-Sensor defective
INP1polarity error Sensor break INP2-Sensor defective
Short circuit INP2-Sensor defective
INP2 polarity Sensor break INP3-Sensor defective
Short circuit INP3-Sensor defective
INP3 polarity
Description Reason Possible remedial action
- E.g. defective EEPROM - Contact West service
- Return unit to our factory
- e.g. EMC trouble - Keep measurement and power supply cables in separate runs
- Ensure that interference suppression of contactors is provided
- wrong configuration
- missing configuration
- Check interaction of configuration / parameters
- Contact West service
hardware are not identical
-
Sensor defective
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Elektronic-/Optioncard must be exchanged
-
Replace INP1 sensor
-
Check INP1 connection
-
Replace INP1 sensor
-
Check INP1 connection
-
Reverse INP1 polarity
-
Replace INP2 sensor
-
Check INP2 connection
-
Replace sensor INP2
-
Check INP2 connection
-
Reverse INP2 polarity
-
Replace INP3 sensor
-
Check INP3 connection
-
Replace sensor INP3
-
Check INP3 connection
-
Reverse INP3 polarity
-
8840 profiler 13 Error list / Maintenance manager
Operation
Name
HCA
SSr
LooP
AdA.H
AdA.C
LiM.1
Lim.2
Lim.3
Inf.1
Inf.2
E.5
dp.1
dp.2
dp.3
dp.4
Description Reason Possible remedial action
Heating current alarm (HCA)
Heating current circuit
-
interrupted, I< HC.A or
Check heating current circuit
­If necessary, replace heater band
-
I> HC.A (dependent of configuration) Heater band defective
-
Heating current short circuit (SSR)
Control loop alarm (LOOP)
Current flow in heating
­circuit with controller off SSR defective
­Input signal defective or
­not connected correctly Output not connected
­correctly
Check heating current circuit
­If necessary, replace solid-state
­relay
Check heating or cooling circuit
­Check sensor and replace it, if
­necessary Check controller and switching
­device
Self-tuning heating alarm
See Self-tuning heating
­error status
see Self-tuning heating error status
-
(ADAH) Self-tuning heating
alarm cooling (ADAC)
stored limit alarm 1 - adjusted limit value 1
See Self-tuning cooling
­error status
see Self-tuning cooling error status
-
- check process
exceeded
stored limit alarm 2 - adjusted limit value 2
- check process
exceeded
stored limit alarm 3 - adjusted limit value 3
- check process
exceeded
time limit value message
duty cycle message (digital ouputs)
Internal error in DP module
- adjusted number of operating hours reached
- adjusted number of duty cycles reached
- self-test error
-
internal communication
- application-specific
- application-specific
- Switch on the instrument again
-
Contact West service
interrupted
No access by bus master
Faulty configuration-Faulty DP configuration
Inadmissible parameter setting telegram sent
No data communication
-
bus error
-
connector problem
-
no bus connection
telegram
-
Faulty DP parameter setting telegram
-
Bus error
-
Address error
-
Master stopped
-
Check cable
-
Check connector
-
Check connections
-
Check DP configuration telegram in master
-
Check DP parameter setting telegram in master
-
Check cable connection
-
Check address
-
Check master setting
Error list / Maintenance manager 14 8840 profiler
Operation
g
g
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital input di1/2/3, the è-key or the Ò-key. Configuration, see page 37: ConF / LOGI / Err.r
If an alarm is still valid that means the cause of the alarm is not removed so far (Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Error status Description Behaviour
0 3 4
5
6
7
8
9
No error Faulty control action Re-configure controller (inverse i direct) No response of process
variable Low reversal point Increase ( ADA.H) max. output limiting Y.Hi or
Danger of exceeded set-point (parameter determined)
Output step change too small (y > 5%)
Set-point reserve too small
Impulse tuning failed The control loop is perhaps not closed: check sensor,
The control loop is perhaps not closed: check sensor, connections and process
decrease ( ADA.C) min. output limiting Y.Lo If necessary, increase (inverse) or reduce (direct) set-point
Increase ( ADA.H) max. output limiting Y.Hi or reduce ( ADA.C) min. output limiting Y.Lo
Acknowledgment of this error message leads to switch-over to automatic mode.If self-tuning shall be continued,
increase set-point (invers), reduce set-point (direct) or decrease set-point range (r PArA / SEtp / SP.LO and SP.Hi )
connections and process
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible. After starting by the operator, the controller makes an adaptation attempt, whereby the process characteristics are used to calculate the parameters for fast line-out to the set-point without overshoot.
The following parameters are optimized when self-tuning: Parameter set 1:
Pb1 - Proportional band 1 (heating) in engineering units [e.g. °C] ti1 - Integral time 1 (heating) in [s]
r only, unless set to OFF
td1 - Derivative time 1 (heating) in [s]
r only, unless set to OFF
t1 - Minimum cycle time 1 (heating) in [s]
r only, unless Adt0 was set to “no self-tuning” during configuration by means of 8800/8840 Configurator.
Pb2 - Proportional band 2 (cooling) in engineering units [e.g. °C]
8840 profiler 15 Self-tuning
Operation
ti2 - Integral time 2 (cooling) in [s]
r only, unless set to OFF
td2 - Derivative time 2 (cooling) in [s]
r only, unless set to OFF
t2 - Minimum cycle time 2 (cooling) in [s]
r only, unless Adt0 was set to “no self-tuning” during configuration by means of 8800/8840 Configurator .
Parameter set 2: analogous to parameter set 1 (see page 25)
3.5.1 Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set
w
values rnG.L and rnG.H to the limits of subsequent control. (Configuration rControllerr lower and upper control range limits)
ConF r Cntr r rnG.L and rnG.H
Determine which parameter set shall be optimized.
w
- The instantaneously effective parameter set is optimized.
r Activate the relevant parameter set (1 or 2).
Determine which parameter set shall be optimized (see tables above).
w
Select the self-tuning method
w
see chapter 3.5.3
-Step attempt after start-up
- Pulse attempt after start-up
- Optimization at the set-point
3.5.2 Optimization after start-up or at the set-point
The two methods are optimization after start-up and at the set-point. As control parameters are always optimal only for a limited process range, various methods can be selected dependent of requirements. If the process behaviour is very different after start-up and directly at the set-point, parameter sets 1 and 2 can be optimized using different methods. Switch-over between parameter sets dependent of process status is possible (see page 25).
Optimization after start-up: (see page 17) Optimization after start-up requires a certain separation between process value and set-point. This separation enables the controller to determine the control parameters by evaluation of the process when lining out to the set-point. This method optimizes the control loop from the start conditions to the set-point, whereby a wide control range is covered. We recommend selecting optimization method “Step attempt after start-up” with tunE = 0 first. Unless this attempt is completed successfully, we recommend a “Pulse attempt after start-up”.
Self-tuning 16 8840 profiler
Optimization at the set-point: (see page 18) For optimizing at the set-point, the controller outputs a disturbance variable to the process. This is done by changing the output variable shortly. The process value changed by this pulse is evaluated. The detected process parameters are converted into control parameters and saved in the controller. This procedure optimizes the control loop directly at the set-point. The advantage is in the small control deviation during optimization.
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)
Selection criteria for the optimization method:
Step attempt after start-up Pulse attempt after start-up Optimization at the set-point
tunE =0
tunE =1
tunE =2
sufficient set-point reserve is
provided
sufficient set-point reserve is
provided
always step attempt after
start-up
Operation
sufficient set-point reserve is not
provided
sufficient set-point reserve is not
provided
Sufficient set-point reserve:
inverse controller: (with process value < set-point- (10% of rnGH - rnGL) direct controller: (with process value > set-point + (10% of rnGH - rnGL)
Step attempt after start-up
Condition: - tunE = 0 and sufficient set-point reserve provided or
- tunE =2
The controller outputs 0% correcting variable or Y.Lo and waits, until the process is at rest (see start-conditions on page 15). Subsequently, a correcting variable step change to 100% is output. The controller attempts to calculate the optimum control parameters from the process response. If this is done successfully, the optimized parameters are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”. After completing the 1st step as described, a correcting variable of -100% (100% cooling energy) is output from the set-point. After successfull determination of the “cooling parameters”, line-out to the set-point is using the optimized parameters.
8840 profiler 17 Self-tuning
Operation
Pulse attempt after start-up
Condition: - tunE = 1 and sufficient set-point reserve provided. The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start conditions page 15) Subsequently, a short pulse of 100% is output (Y=100%) and reset. The controller attempts to determine the optimum control parameters from the process response. If this is completed successfully, these optimized parameters are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”. After completing the 1st step as described and line-out to the set-point, correcting variable "heating" remains unchanged and a cooling pulse (100% cooling energy) is output additionally. After successful determination of the “cooling parameters”, the optimized parameters are used for line-out to the set-point.
Optimization at the set-point
Conditions:
A sufficient set-point reserve is not provided at self-tuning start (see page 17).
w
tunE is0or1
w
With Strt = 1 configured and detection of a process value oscillation by
w
more than ± 0,5% of (rnG.H - rnG.L) by the controller, the control parameters are preset for process stabilization and the controller realizes an optimization at the set-point (see figure “Optimization at the set-point”). when the step attempt after power-on has failed
w
with active gradient function ( PArA/ SETP/ r.SPOFF), the set-point
w
gradient is started from the process value and there isn't a sufficient set-point reserve.
Self-tuning 18 8840 profiler
Operation
Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In lined out condition, the controller makes a pulse attempt. This pulse reduces the correcting variable by max. 20% 1, to generate a slight process value undershoot. The changing process is analyzed and the parameters thus calculated are recorded in the controller. The optimized parameters are used for line-out to the set-point.
Optimization at the set-point
set-point
process value
correcting variable
With a 3-point controller, optimization for the “heating“ or “cooling” parameters occurs dependent of the instantaneous condition. These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is increased by max. 20%.
8840 profiler 19 Self-tuning
Operation
Optimization at the set-point for 3-point stepping controller
With 3-point stepping controllers, the pulse attempt can be made with or without position feedback. Unless feedback is provided, the controller calculates the motor actuator position internally by varying an integrator with the adjusted actuator travel time. For this reason, precise entry of the actuator travel time (tt), as time between stops is highly important. Due to position simulation, the controller knows whether an increased or reduced pulse must be output. After supply voltage switch-on, position simulation is at 50%. When the motor actuator was varied by the adjusted travel time in one go, internal calculation occurs, i.e. the position corresponds to the simulation:
Simulation actual position
Internal calculation
tt
Internal calculation always occurs, when the actuator was varied by travel time
tt in one go
variation, internal calculation is cancelled. Unless internal calculation occurred already after self-tuning start, it will occur automatically by closing the actuator once.
Unless the positioning limits were reached within 10 hours, a significant deviation between simulation and actual position may have occurred. In this case, the controller would realize minor internal calculation, i.e. the actuator would be closed by 20 %, and re-opened by 20 % subsequently. As a result, the controller knows that there is a 20% reserve for the attempt.
, independent of manual or automatic mode. When interrupting the
Self-tuning 20 8840 profiler
3.5.4 Self-tuning start
Start condition:
For process evaluation, a stable condition is required. Therefore, the
w
controller waits until the process has reached a stable condition after self-tuning start. The rest condition is considered being reached, when the process value
oscillation is smaller than ± 0,5% of (rnG.H - rnG.L). For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)
w
is required.
Operation
g
Self-tuning start can be blocked via 8800/8840 Configurator (engineering tool) ( P.Loc).
Strt = 0 Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.
Strt = 1 Manual start by press keys Ù and È simultaneously
via interface and automatic start after power-on and detection of process oscillations.
Ada LED status Signification
blinks Waiting, until process calms down
lit Self-tuning is running
°C
°F
RUN
off Self-tuning not activ
or ended
8840 profiler 21 Self-tuning
Operation
3.5.5 Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È key simultaneously.With controller switch-over to manual mode after self-tuning start, self-tuning is cancelled. When self-tuning is cancelled, the controller will continue operating using the old parameter values.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning is prevented due to the control conditions. In this case, self-tuning was cancelled by the controller. The controller continues operating with the old parameters in automatic mode. In manual mode it continues with the old controller output value.
3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning
1. Press keys Ù and È simultaneously:
The controller continues controlling using the old parameters in automatic mode. The Err LED continues blinking, until the self-tuning error was acknowledged in the error list.
2. Press key Ò (if configured): The controller goes to manual mode. The Err LED continues blinking,
until the self-tuning error was acknowleged in the error list.
3. Press key Ù :
Display of error list at extended operating level. After acknowledgement of the error message, the controller continues control in automatic mode using the old parameters.
Cancellation causes:
r page 15: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
Self-tuning 22 8840 profiler
3.5.7 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Operation
Start: heating power switched on
Heating power Y is switched off (1).
X
W
2
When the change of process value X was constant during one minute (2), the power is switched on (3). At the reversal point, the self-tuning
100%
0%
Y
Star t r
1
3
t reversal point
attempt is finished and the new parameter are used for controlling to
blinks
set-point W.
Start: heating power switched off
X
W
The controller waits 1,5 minutes (1). Heating power Y is switched on (2). At the reversal point, the self-tuning attempt is finished and control to the set-point is using the new parameters.
100%
0%
Y
start r
1
2
t reversal point
Self-tuning at the set-point a
The process is controlled to the set-point. With the control deviation constant during a defined time (1) (i.e. constant separation of process value
X
W
blinks
r
2
t
and set-point), the controller outputs a reduced correcting variable pulse (max. 20%) (2). After determination of the control parameters using the process characteristic (3), control is started
100%
0%
Start r
Y
1
3
4
using the new parameters (4).
blinks
Three-point controller a
The parameter for heating and cooling are
X
W
3
rt
determined in two attempts. The heating power is switched on (1). Heating parameters Pb1, ti1, td1 and t1 are determined at the reversal point. Control to the set-point occurs(2). With constant control deviation, the controller provides a
+100%
Y0%
-100%
Start r
1
t reversal
point
2
4
cooling correcting variable pulse (3). After determining its cooling parameters Pb2, ti2, td2 and t2 (4) from the process characteristics , control operation is started using the new parameters (5).
t
t
t
t
5
a
During phase 3, heating and cooling are done simultaneously!
8840 profiler 23 Self-tuning
Operation
y
3.6 Manual self-tuning
The optimization aid should be used with units on which the control parameters shall be set without self-tuning. For this, the response of process variable x after a step change of correcting variable y can be used. Frequently, plotting the complete response curve (0 to 100%) is not possible, because the process must be kept within defined limits.
Values T
and x
g
(step change from 0 to 100 %) or t and x (partial step
max
response) can be used to determine the maximum rate of increase v
100%
Y
h
0%
t
t
X
x
Tg
max
{X
{t
Tu
max
.
y = correcting variable
Y
= control range
h
Tu = delay time (s) Tg = recovery time (s) X
V
= maximum process value
max
max
Xmax
=
Tg
∆∆x
=
t
= max. rate of increase of process value
The control parameters can be determined from the values calculated for delay time T
, maximum rate of increase v
u
, control range Xhand characteristic K
max
according to the formulas given below. Increase Pb1, if line-out to the set-point oscillates.
Manual self-tuning 24 8840 profiler
Operation
Parameter adjustment effects
Parameter Control Line-out of disturbances Start-up behaviour
Pb1 higher increased damping slower line-out slower reduction of duty cycle
lower reduced damping faster line-out faster reduction of duty cycle
td1 higher reduced damping faster response to disturbances faster reduction of duty cycle
lower increased damping slower response to disturbances slower reduction of duty cycle
ti1 higher increased damping slower line-out slower reduction of duty cycle
lower reduced damping faster line-out faster reduction of duty cycle
Formulas
K = Vmax * Tu controller behavior Pb1 [phy. units] td1 [s] ti1 [s]
PID 1,7*K 2*Tu 2*Tu With 2-point and 3-point controllers,
the cycle time must be adjusted to
t1 / t2 ≤ 0,25 * Tu
PD 0,5 * K Tu OFF
PI 2,6 * K OFF 6*Tu
PKOFF OFF
3-point-stepping 1,7 * K Tu 2 * Tu
3.7 Second PID parameter set
The process characteristic is frequently affected by various factors such as process value, correcting variable and material differences. To comply with these requirements, the 8840 profiler can be switched over between two parameter sets. Parameter sets PArA and PAr.2 are provided for heating and cooling.
Dependent of configuration ( ConF/LOG/Pid.2), switch-over to the second parameter set ( ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3, key è or interface (OPTION).
g
Self-tuning is always done using the active parameter set, i.e. the second parameter set must be active for optimizing.
8840 profiler 25 Second PID parameter set
Operation
3.8 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Generally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If more than one signal is linked to one output the signals are OR linked. Each of the 3 limit values Lim.1 Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off individually (parameter = “OFF”). Switching difference HYS.x and delay dEl.x of each limit value is adjustable.
Ü Operating principle absolute alarm
L.1 = OFF
InL.1
1
H.1
HYS.1
2
InH.1
LED
H.1 = OFF
InL.1
2
L.1
HYS.1
LED
1
InH.1
* Operating principle relative alarm
L.1 = OFF
SP
InL.1
H.1
HYS.1
1
2
H.1 = OFF
SP
InL.1
L.1
HYS.1
LED
2
1
InH.1
LED
InH.1
SP
InL.1
2
H.1
L.1
HYS.1 HYS.1
LED
1
2
InH.1
LED
InL.1
2
LED
HYS.1
L.1
H.1
HYS.1
1
InH.1
LED
2
1: normally closed ( ConF/ Out.x/O.Act=1 ) 2: normally open ( ConF/ Out.x/O.Act= 0 )
Alarm handling 26 8840 profiler
Operation
g
The variable to be monitored can be selected seperately for each alarm via configuration The following variables can be monitored:
process value
w
control deviation xw (process value - set-point)
w
control deviation xw + suppression after start-up or set-point change
w
After switching on or set-point changing, the alarm output is suppressed,
until the process value is within the limits for the first time. At the latest after expiration of time 10 ti1, the alarm is activated. (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = OFF), this is interpreted as Î, i.e. the alarm
is not activated, before the process value was within the limits once. Measured value INP1
w
Measured value INP2
w
Measured value INP3
w
effective set-point Weff
w
correcting variable y (controller output)
w
Deviation from SP internal
w
Process value - x2
w
g
If measured value monitoring + alarm status storage is chosen ( ConF / Lim / Fnc.x=2/4), the alarm relay remains switched on until the alarm is resetted in the error list ( Lim 1..3 = 1).
8840 profiler 27 Alarm handling
Loading...
+ 63 hidden pages