All rights reserved. No part of this document may bereproduced or published in
any form or by any means without prior written permission from the copyright
owner.
A publication of West Instruments, The Hyde Business Park,
Brighton BN2 4JU, England
Content2
1. Mounting5
2. Electrical connections6
2.1 Connecting diagram .....................6
2.2 Terminal connection .....................7
3. Operation11
3.1 Front view..........................11
3.2 Behaviour after power-on ..................12
3.3 Operating level .......................12
3.4 Error list / Maintenance manager ..............13
3.5 Self-tuning.........................15
3.5.1 Preparation for self-tuning ..................16
3.5.2 Optimization after start-up or at the set-point ........16
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)........17
7.3.7 Search run at programmer start ................74
7.3.8 Behaviour after mains recovery or sensor error .......74
8. Special functions75
8.1 8840 profiler as Modbus master ..............75
8.2 Linearization ........................76
9. 8800/8840 Configurator77
10. Versions78
11.Technical data79
12. Safety hints84
12.1 Resetting to factory setting ................85
13. Notes88
48840 profiler
1Mounting
*
Mounting
min.48 (1.89")
(0.4")
10
118
WEST
96 (3.78")
48 (1.89")
(4.65")
8840
RUN
-PrgEdit-
1..10
(0.04..0.4")
+0,6
45
(1.77")
+0.02
Loc
security switch
+0,8
+0.03
92
max.
(3.62")
max.
95% rel.
60°C
0°Cmin.
%
Ü
or
Ü
*
Safety switch:
For access to the safety switch, the controller must be withdrawn from the
housing. Squeeze the top and bottom of the front bezel between thumb and
forefinger and pull the controller firmly from the housing.
LocopenAccess to the levels is as adjusted by means of 8800/8840
Configurator (engineering tool)
closed 1all levels accessible wihout restriction
1 Factory setting2Default setting: display of all levels
suppressed, password PASS = OFF
2
l
Caution! The unit contains ESD-sensitive components.
8840 profiler5
Electrical connections
U
2Electrical connections
2.1 Connecting diagram
3
1
2
90...250V
24 V UC
OUT1
OUT2
OUT3
OUT4
!
V
V
d
b
c
e
8
9
0
RGND
DATA B
DATA A
RS485RS422
Modbus RT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
a
+24V DC
OUT5
OUT6
24V GND
RXD-B
RXD-A
TXD-B
TXD-A
GND
di2
di3
U
1
2
3
di1
7
di2
4
5
6
7
g
HC
mA
INP2
f
5
8
9
10
11
(mV)
0%
100%
mA
INP3
6
12
13
14
15
mA
Volt
INP1
4
(16)
Option
1
(2)
3
4
5
10
11
12
13
14
15
(16)
17
6
7
8
9
VP (5V)
DGND
RxD/TxD-N
RxD/TxD-P
Schirm/
Screen
T
17
PROFIBUS-DP
(mV)
a
b
390 [
220 [
Adapter
390 [
cd
DGND
9
8
7
VP (5V)
6
Profibus DP
e
max.
1200m
5
4
3
2
1
5
9
4
8
3
7
2
6
1
g
Dependent of order, the controller is fitted with :
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or
*Interface description Modbus RTU in speperate manual: see page 78.
8840 profiler9Terminal connection
Electrical connections
3OUT3 as logic output with solid-state relay (series and parallel connection)
Series connection
SSR
I =22mA
max
_
4V
+
SSR
_
4V
+
SSR
_
4V
+
12V
10
11
12
Logic
SSR
SSR
Parallel connection
I =22mA
max
_
+
_
+
12V
10
11
12
8840 profilerconnecting example:
L1
L2
fuse
8840 profiler
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Logic
10
11
12
13
14
(16)
1
2
3
4
5
6
7
8
9
15
17
SSR
_
+
fuse
contactor
+
heating
1
6700 Limit controller
Standard version:
N6700Z21
00
other versions on requestr
1
6700
Limit
controller
fuse
N1
N2
a
CAUTION:Using a Limit controller is recommendable in systems
where overtemperature implies a fire hazard or other risks.
Terminal connection108840 profiler
RUN
-PrgEdit-
WEST
8840
1
2
3
4
5
6
%
7
8
&
(
)
/
°C
°F
9
0
RUN
§
$
!"
3Operation
3.1 Front view
LED colours:
LED 1, 2, 3, 4:yellow
Bargraph:red
other LEDs:red
g
In the upper display line, the
process value is always
displayed. At parameter,
configuration, calibration as
well as extended operating
level, the bottom display line
changes cyclically between
parameter name and
parameter value.
Operation
1 Status of switching outputs
OuT.1... 6
2 Process value display
3 Set-point, controller output
4 Signals display on °C or °F
5 Signals ConF and PArA level
6 Signals aktive function key
7 Self-tuning active
8 Entry in error list
9 Bargraph or clear text display
0 SP.2 is effective
! SP.E is effective
" Set-point gradient effective
§ Manual/automatic switch-over:
Off:Automatic
On:Manual(changing possible)
Blinks:Manual (changing not
possible (r ConF/ Cntr/ MAn)
$ Enter key:
calls up error list / extended
operating level /
% Up/down keys:
changing the set-point or the
controller output value
& Manual mode /spec. function
(→ ConF / LOGI )
/ switchover programmer /
controller operation or, with pure
controller operation, freely
programmable function key
( programmer: run/stop
controller: automatic/manual
other function (→ ConF / LOGI)
) PC connection for 8800/8840
Configurator (engineering tool)
8840 profiler11Front view
Operation
P
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the operating level.
The unit is in the condition which was active before power-off.
If the 8840 profiler was in manual mode at supply voltage switch-off, the
controller will re-start with the last output value in manual mode at power-on.
3.3 Operating level
The content of the extended operating level is determined by means of 8800/8840
Configurator (engineering tool). Parameters which are used frequently or the
display of which is important can be copied to the extended operating level.
Controller
Automatic
1199
1200
time
out
1199
Y21
Ù
Ù
i
È
Ì
display
only
Ò
Ò
i
Hand
1199
Y21
Ù
1199
1200
Ù
Extended Operating Level
time
out
Errorlist (when errors exist)
126
FbF.1
Err
Display
Changes
126
2
Err
È
Ì
time
out
È
Ì
/
è
Ù
rogrammer
67
0
10 OFF
run
Ò
67
69
10/00:10
run
Ò
119
120
10-01:23
run
>3 Sec.
Ò
230
230
10 End
run
Behaviour after power-on128840 profiler
3.4 Error list / Maintenance manager
With one or several errors, the extended
operating level always starts with the error list.
Signalling an actual entry in the error list (alarm,
error) is done by the Err LED in the display. To
reach the error list press Ù twice.
Err LED status SignificationProceed as follows
blinks(status 2)Alarm due to existing
error
lit(status 1)Error removed, alarm
not acknowledged
off(status 0)No error, all alarm
entries deleted
Determine the error type in the error list After error
correction the unit changes to status 1
Acknowledge the alarm in the error list pressing key
- e.g. EMC trouble- Keep measurement and power
supply cables in separate runs
- Ensure that interference
suppression of contactors is
provided
- wrong configuration
- missing configuration
- Check interaction of configuration
/ parameters
- Contact West service
hardware are not
identical
-
Sensor defective
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Elektronic-/Optioncard must be
exchanged
-
Replace INP1 sensor
-
Check INP1 connection
-
Replace INP1 sensor
-
Check INP1 connection
-
Reverse INP1 polarity
-
Replace INP2 sensor
-
Check INP2 connection
-
Replace sensor INP2
-
Check INP2 connection
-
Reverse INP2 polarity
-
Replace INP3 sensor
-
Check INP3 connection
-
Replace sensor INP3
-
Check INP3 connection
-
Reverse INP3 polarity
-
8840 profiler13Error list / Maintenance manager
Operation
Name
HCA
SSr
LooP
AdA.H
AdA.C
LiM.1
Lim.2
Lim.3
Inf.1
Inf.2
E.5
dp.1
dp.2
dp.3
dp.4
DescriptionReasonPossible remedial action
Heating current
alarm (HCA)
Heating current circuit
-
interrupted, I< HC.A or
Check heating current circuit
If necessary, replace heater band
-
I> HC.A (dependent of
configuration)
Heater band defective
-
Heating current short
circuit (SSR)
Control loop alarm
(LOOP)
Current flow in heating
circuit with controller off
SSR defective
Input signal defective or
not connected correctly
Output not connected
correctly
Check heating current circuit
If necessary, replace solid-state
relay
Check heating or cooling circuit
Check sensor and replace it, if
necessary
Check controller and switching
device
Self-tuning heating
alarm
See Self-tuning heating
error status
see Self-tuning heating error status
-
(ADAH)
Self-tuning heating
alarm cooling
(ADAC)
stored limit alarm 1- adjusted limit value 1
See Self-tuning cooling
error status
see Self-tuning cooling error status
-
- check process
exceeded
stored limit alarm 2- adjusted limit value 2
- check process
exceeded
stored limit alarm 3- adjusted limit value 3
- check process
exceeded
time limit value
message
duty cycle message
(digital ouputs)
Internal error in DP
module
- adjusted number of
operating hours reached
- adjusted number of duty
cycles reached
- self-test error
-
internal communication
- application-specific
- application-specific
- Switch on the instrument again
-
Contact West service
interrupted
No access by bus
master
Faulty configuration-Faulty DP configuration
Inadmissible
parameter setting
telegram sent
No data
communication
-
bus error
-
connector problem
-
no bus connection
telegram
-
Faulty DP parameter
setting telegram
-
Bus error
-
Address error
-
Master stopped
-
Check cable
-
Check connector
-
Check connections
-
Check DP configuration telegram
in master
-
Check DP parameter setting
telegram in master
-
Check cable connection
-
Check address
-
Check master setting
Error list / Maintenance manager148840 profiler
Operation
g
g
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3, the è-key or the Ò-key.
Configuration, see page 37: ConF / LOGI / Err.r
If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Error statusDescriptionBehaviour
0
3
4
5
6
7
8
9
No error
Faulty control actionRe-configure controller (inverse i direct)
No response of process
Danger of exceeded
set-point (parameter
determined)
Output step change
too small (∆y > 5%)
Set-point reserve too
small
Impulse tuning failedThe control loop is perhaps not closed: check sensor,
The control loop is perhaps not closed: check sensor,
connections and process
decrease ( ADA.C) min. output limiting Y.Lo
If necessary, increase (inverse) or reduce (direct) set-point
Increase ( ADA.H) max. output limiting Y.Hi or reduce
( ADA.C) min. output limiting Y.Lo
Acknowledgment of this error message leads to switch-over
to automatic mode.If self-tuning shall be continued,
increase set-point (invers), reduce set-point (direct)
or decrease set-point range
(r PArA / SEtp / SP.LO and SP.Hi )
connections and process
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt,
whereby the process characteristics are used to calculate the parameters for fast
line-out to the set-point without overshoot.
The following parameters are optimized when self-tuning:
Parameter set 1:
Pb1- Proportional band 1 (heating) in engineering units [e.g. °C]
ti1- Integral time 1 (heating) in [s]
r only, unless set to OFF
td1- Derivative time 1 (heating) in [s]
r only, unless set to OFF
t1- Minimum cycle time 1 (heating) in [s]
r only, unless Adt0 was set to “no self-tuning” during
configuration by means of 8800/8840 Configurator.
Pb2- Proportional band 2 (cooling) in engineering units [e.g. °C]
8840 profiler15Self-tuning
Operation
ti2- Integral time 2 (cooling) in [s]
r only, unless set to OFF
td2- Derivative time 2 (cooling) in [s]
r only, unless set toOFF
t2- Minimum cycle time 2 (cooling) in [s]
r only, unless Adt0 was set to “no self-tuning” during
configuration by means of 8800/8840 Configurator .
Parameter set 2: analogous to parameter set 1 (see page 25)
3.5.1 Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set
w
values rnG.L and rnG.H to the limits of subsequent control.
(Configuration rControllerr lower and upper control range limits)
ConFrCntr r rnG.L and rnG.H
Determine which parameter set shall be optimized.
w
-The instantaneously effective parameter set is optimized.
r Activate the relevant parameter set (1 or 2).
Determine which parameter set shall be optimized (see tables above).
w
Select the self-tuning method
w
see chapter 3.5.3
-Step attempt after start-up
-Pulse attempt after start-up
-Optimization at the set-point
3.5.2 Optimization after start-up or at the set-point
The two methods are optimization after start-up and at the set-point.
As control parameters are always optimal only for a limited process range,
various methods can be selected dependent of requirements. If the process
behaviour is very different after start-up and directly at the set-point, parameter
sets 1 and 2 can be optimized using different methods. Switch-over between
parameter sets dependent of process status is possible (see page 25).
Optimization after start-up: (see page 17)
Optimization after start-up requires a certain separation between process value
and set-point. This separation enables the controller to determine the control
parameters by evaluation of the process when lining out to the set-point.
This method optimizes the control loop from the start conditions to the set-point,
whereby a wide control range is covered.
We recommend selecting optimization method “Step attempt after start-up”
with tunE = 0 first. Unless this attempt is completed successfully, we
recommend a “Pulse attempt after start-up”.
Self-tuning168840 profiler
Optimization at the set-point: (see page 18)
For optimizing at the set-point, the controller outputs a disturbance variable to the
process. This is done by changing the output variable shortly. The process value
changed by this pulse is evaluated. The detected process parameters are
converted into control parameters and saved in the controller.
This procedure optimizes the control loop directly at the set-point. The advantage
is in the small control deviation during optimization.
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)
Selection criteria for the optimization method:
Step attempt after start-upPulse attempt after start-upOptimization at the set-point
tunE =0
tunE =1
tunE =2
sufficient set-point reserve is
provided
sufficient set-point reserve is
provided
always step attempt after
start-up
Operation
sufficient set-point reserve is not
provided
sufficient set-point reserve is not
provided
Sufficient set-point reserve:
inverse controller:(with process value < set-point- (10% of rnGH - rnGL)
direct controller:(with process value > set-point + (10% of rnGH - rnGL)
Step attempt after start-up
Condition:- tunE = 0 and sufficient set-point reserve provided or
- tunE =2
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start-conditions on page 15).
Subsequently, a correcting variable step change to 100% is output.
The controller attempts to calculate the optimum control parameters from the
process response. If this is done successfully, the optimized parameters are taken
over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100%
cooling energy) is output from the set-point. After successfull determination of
the “cooling parameters”, line-out to the set-point is using the optimized
parameters.
8840 profiler17Self-tuning
Operation
Pulse attempt after start-up
Condition: - tunE = 1 and sufficient set-point reserve provided.
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start conditions page 15)
Subsequently, a short pulse of 100% is output (Y=100%) and reset.
The controller attempts to determine the optimum control parameters from the
process response. If this is completed successfully, these optimized parameters
are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described and line-out to the set-point, correcting
variable "heating" remains unchanged and a cooling pulse (100% cooling energy)
is output additionally. After successful determination of the “cooling
parameters”, the optimized parameters are used for line-out to the set-point.
Optimization at the set-point
Conditions:
A sufficient set-point reserve is not provided at self-tuning start (see page 17).
w
tunE is0or1
w
With Strt = 1 configured and detection of a process value oscillation by
w
more than ± 0,5% of (rnG.H - rnG.L) by the controller, the control
parameters are preset for process stabilization and the controller realizes an
optimization at the set-point (see figure “Optimization at the set-point”).
when the step attempt after power-on has failed
w
with active gradient function ( PArA/ SETP/ r.SP≠ OFF), the set-point
w
gradient is started from the process value and there isn't a sufficient set-point
reserve.
Self-tuning188840 profiler
Operation
Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In
lined out condition, the controller makes a pulse attempt. This pulse reduces the
correcting variable by max. 20% 1, to generate a slight process value
undershoot. The changing process is analyzed and the parameters thus calculated
are recorded in the controller. The optimized parameters are used for line-out to
the set-point.
Optimization at the set-point
set-point
process value
correcting
variable
With a 3-point controller, optimization for the “heating“ or “cooling” parameters
occurs dependent of the instantaneous condition.
These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is
increased by max. 20%.
8840 profiler19Self-tuning
Operation
Optimization at the set-point for 3-point stepping controller
With 3-point stepping controllers, the pulse attempt can be made with or without
position feedback. Unless feedback is provided, the controller calculates the
motor actuator position internally by varying an integrator with the adjusted
actuator travel time. For this reason, precise entry of the actuator travel time
(tt), as time between stops is highly important. Due to position simulation, the
controller knows whether an increased or reduced pulse must be output. After
supply voltage switch-on, position simulation is at 50%. When the motor actuator
was varied by the adjusted travel time in one go, internal calculation occurs, i.e.
the position corresponds to the simulation:
Simulationactual position
Internal calculation
tt
Internal calculation always occurs, when the actuator was varied by travel time
tt in one go
variation, internal calculation is cancelled. Unless internal calculation occurred
already after self-tuning start, it will occur automatically by closing the actuator
once.
Unless the positioning limits were reached within 10 hours, a significant
deviation between simulation and actual position may have occurred. In this case,
the controller would realize minor internal calculation, i.e. the actuator would be
closed by 20 %, and re-opened by 20 % subsequently. As a result, the controller
knows that there is a 20% reserve for the attempt.
, independent of manual or automatic mode. When interrupting the
Self-tuning208840 profiler
3.5.4 Self-tuning start
Start condition:
For process evaluation, a stable condition is required. Therefore, the
w
controller waits until the process has reached a stable condition after
self-tuning start.
The rest condition is considered being reached, when the process value
oscillation is smaller than ± 0,5% of (rnG.H - rnG.L).
For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)
w
is required.
Operation
g
Self-tuning start can be blocked via 8800/8840 Configurator (engineering tool)
( P.Loc).
Strt = 0Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.
Strt = 1Manual start by press keys Ùand È simultaneously
via interface and automatic start after power-on and detection
of process oscillations.
Ada LED statusSignification
blinksWaiting, until process calms down
litSelf-tuning is running
°C
°F
RUN
offSelf-tuning not activ
or ended
8840 profiler21Self-tuning
Operation
3.5.5 Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È
key simultaneously.With controller switch-over to manual mode after self-tuning
start, self-tuning is cancelled. When self-tuning is cancelled, the controller will
continue operating using the old parameter values.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning
is prevented due to the control conditions. In this case, self-tuning was cancelled
by the controller. The controller continues operating with the old parameters in
automatic mode. In manual mode it continues with the old controller output
value.
3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning
1.Press keys Ù and È simultaneously:
The controller continues controlling using the old parameters in automatic
mode. The Err LED continues blinking, until the self-tuning error was
acknowledged in the error list.
2.Press key Ò (if configured):
The controller goes to manual mode. The Err LED continues blinking,
until the self-tuning error was acknowleged in the error list.
3.Press key Ù :
Display of error list at extended operating level. After acknowledgement
of the error message, the controller continues control in automatic mode using
the old parameters.
Cancellation causes:
r page 15: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
Self-tuning228840 profiler
3.5.7 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Operation
Start: heating power switched on
Heating power Y is switched off (1).
X
W
2
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning
100%
0%
Y
Star t r
1
3
t reversal point
attempt is finished and the new
parameter are used for controlling to
blinks
set-point W.
Start: heating power switched off
X
W
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning
attempt is finished and control to the
set-point is using the new parameters.
100%
0%
Y
start r
1
2
t reversal point
Self-tuning at the set-pointa
The process is controlled to the
set-point. With the control deviation
constant during a defined time (1)
(i.e. constant separation of process value
X
W
blinks
r
2
t
and set-point), the controller outputs a
reduced correcting variable pulse (max.
20%) (2). After determination of the
control parameters using the process
characteristic (3), control is started
100%
0%
Start r
Y
1
3
4
using the new parameters (4).
blinks
Three-point controllera
The parameter for heating and cooling are
X
W
3
rt
determined in two attempts. The heating
power is switched on (1). Heating
parameters Pb1, ti1, td1 and t1 are
determined at the reversal point. Control to
the set-point occurs(2). With constant
control deviation, the controller provides a
+100%
Y0%
-100%
Start r
1
t reversal
point
2
4
cooling correcting variable pulse (3).
After determining its cooling parameters
Pb2, ti2, td2 and t2 (4) from the
process characteristics , control operation is started using the new parameters (5).
t
t
t
t
5
a
During phase 3, heating and cooling are done simultaneously!
8840 profiler23Self-tuning
Operation
y
3.6 Manual self-tuning
The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting
variable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T
and x
g
(step change from 0 to 100 %) or ∆t and ∆x (partial step
max
response) can be used to determine the maximum rate of increase v
100%
Y
h
0%
t
t
X
x
Tg
max
{X
{t
Tu
max
.
y=correcting variable
Y
=control range
h
Tu=delay time (s)
Tg=recovery time (s)
X
V
=maximum process value
max
max
Xmax
=
Tg
∆∆x
=
t
= max. rate of increase of process value
The control parameters can be determined from the values calculated for delay
time T
, maximum rate of increase v
u
, control range Xhand characteristic K
max
according to the formulas given below. Increase Pb1, if line-out to the set-point
oscillates.
Manual self-tuning248840 profiler
Operation
Parameter adjustment effects
ParameterControlLine-out of disturbancesStart-up behaviour
Pb1 higher increased dampingslower line-outslower reduction of duty cycle
lowerreduced dampingfaster line-outfaster reduction of duty cycle
td1 higher reduced dampingfaster response to disturbances faster reduction of duty cycle
lowerincreased dampingslower response to disturbances slower reduction of duty cycle
ti1 higher increased dampingslower line-outslower reduction of duty cycle
lowerreduced dampingfaster line-outfaster reduction of duty cycle
Formulas
K = Vmax * Tucontroller behaviorPb1 [phy. units]td1 [s]ti1 [s]
PID1,7*K2*Tu2*Tu
With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 ≤ 0,25 * Tu
PD0,5 * KTuOFF
PI2,6 * KOFF6*Tu
PKOFFOFF
3-point-stepping1,7 * KTu2 * Tu
3.7 Second PID parameter set
The process characteristic is frequently affected by various factors such as
process value, correcting variable and material differences.
To comply with these requirements, the 8840 profiler can be switched over
between two parameter sets.
Parameter sets PArA and PAr.2 are provided for heating and cooling.
Dependent of configuration ( ConF/LOG/Pid.2), switch-over to the second
parameter set( ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3,
key è or interface (OPTION).
g
Self-tuning is always done using the active parameter set, i.e. the second
parameter set must be active for optimizing.
8840 profiler25Second PID parameter set
Operation
3.8 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs.
Generally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If
more than one signal is linked to one output the signals are OR linked. Each of
the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min),
which can be switched off individually (parameter = “OFF”). Switching
difference HYS.x and delay dEl.x of each limit value is adjustable.
The variable to be monitored can be selected seperately for each alarm via
configuration
The following variables can be monitored:
process value
w
control deviation xw (process value - set-point)
w
control deviation xw + suppression after start-up or set-point change
w
After switching on or set-point changing, the alarm output is suppressed,
until the process value is within the limits for the first time. At the latest after
expiration of time 10 ti1, the alarm is activated. (ti1 = integral time 1;
parameter r Cntr)
If ti1 is switched off (ti1 = OFF), this is interpreted as Î, i.e. the alarm
is not activated, before the process value was within the limits once.
Measured value INP1
w
Measured value INP2
w
Measured value INP3
w
effective set-point Weff
w
correcting variable y (controller output)
w
Deviation from SP internal
w
Process value - x2
w
g
If measured value monitoring + alarm status storage is chosen ( ConF / Lim /
Fnc.x=2/4), the alarm relay remains switched on until the alarm is resetted in
the error list ( Lim 1..3 = 1).
8840 profiler27Alarm handling
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.