7.48800 process controller as Modbus master ............75
88800/8840 configurator ......................76
9Versions ..............................77
10Technical data ..........................78
11Safety hints ............................81
11.1Resetting to factory setting.....................82
12Notes ................................83
48800 process controller
1Mounting
*
Mounting
min.48 (1.89")
(0.4")
10
118
WEST
96 (3.78")
Process Controller
48 (1.89")
(4.65")
8800
1..10
(0.04..0.4")
+0,6
45
(1.77")
+0.02
Loc
security switch
+0,8
+0.03
92
max.
(3.62")
max.
95% rel.
60°C
0°Cmin.
%
Ü
or
Ü
*
Safety switch:
For access to the safety switch, the controller must be withdrawn from the
housing. Squeeze the top and bottom of the front bezel between thumb and
forefinger and pull the controller firmly from the housing.
LocopenAccess to the levels is as adjusted by means of 8800/8840 configurator
(engineering tool) 2
closed 1all levels accessible wihout restriction
1 Factory setting2 Default setting: display of all levels
suppressed, password PASS = OFF
l
8800 process controller5
Caution! The unit contains ESD-sensitive components.
Electrical connections
3
2Electrical connections
2.1 Connecting diagram
1
2
90...250V
24 V UC
OUT1
OUT2
OUT3
OUT4
!
V
V
d
b
c
e
8
9
0
RGND
DATA B
DATA A
RS485RS422
Modbus RTU
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
a
+24V DC
OUT5
OUT6
24V GND
RXD-B
RXD-A
TXD-B
TXD-A
GND
di2
di3
U
1
2
3
di1
7
di2
4
5
6
7
g
HC
mA
INP2
f
5
8
9
10
11
(mV)
0%
100%
mA
INP3
6
12
13
14
15
mA
Volt
INP1
4
(16)
Option
1
(2)
3
4
5
10
11
12
13
14
15
(16)
17
6
7
8
9
VP (5V)
DGND
RxD/TxD-N
RxD/TxD-P
Schirm/
Screen
T
17
PROFIBUS-DP
(mV)
a
b
390 [
220 [
Adapter
390 [
cd
DGND
9
8
7
VP (5V)
6
Profibus DP
e
max.
1200m
5
4
3
2
1
5
9
4
8
3
7
2
6
1
g
Dependent of order, the controller is fitted with :
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or
*Interface description Modbus RTU in speperate manual: see page 75.
8800 process controller9Terminal connection
Electrical connections
3 OUT3 as logic output with solid-state relay (series and parallel connection)
Series connection
SSR
I =22mA
max
_
4V
+
SSR
_
4V
+
SSR
_
4V
+
12V
10
11
12
Logic
SSR
SSR
Parallel connection
I =22mA
max
_
+
_
+
12V
10
11
12
8800 process controller connecting example:
L1
L2
fuse
8840 profiler
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Logic
10
11
12
13
14
(16)
1
2
3
4
5
6
7
8
9
15
17
SSR
_
+
fuse
contactor
+
heating
1
6700 Limit controller
Standard version:
N6700Z21
00
other versions on requestr
1
6700
Limit
controller
fuse
N1
N2
a
CAUTION:Using a Limit controller is recommendable in systems
where overtemperature implies a fire hazard or other risks.
Terminal connection108800 process controller
3Operation
1
2
3
4
5
6
$
7
8
%
&
(
/
9
0
§"
!
3.1 Front view
Operation
1 Status of switching outputs
OuT.1... 6
2 Process value display
3 Set-point, controller output
4 Signals display on °C or °F
5 Signals ConF and PArA level
6 Signals aktive function key
7 Self-tuning active
8 Entry in error list
9 Bargraph or clear text display
0 SP.2 is effective
! SP.E is effective
" Set-point gradient effective
§ Manual/automatic switch-over:
Off:Automatic
On:Manual (changing possible)
Blinks:Manual (changing not
possible
(r ConF/ Cntr/ MAn)
$ Enter key:
calls up extended operating
level / error list
% Up/down keys:
changing the set-point or the
controller output value
& Manual mode /spec. function
(→ ConF / LOGI )
LED colours:
LED 1, 2, 3, 4:yellow
Bargraph:red
other LEDs:red
/ Freely programmable function
key
( PC connection for
8800/8840 configurator
(engineering tool)
g
In the upper display line, the
process value is always
At parameter, configuration,
calibration as well as extended
operating level, the bottom
display line changes cyclically between parameter name and parameter value.
displayed.
8800 process controller11Front view
Operation
A
M
l
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the operating level.
The unit is in the condition which was active before power-off.
If the 8800 process controller was in manual mode at supply voltage switch-off,
the controller will re-start with the last output value in manual mode at power-on.
3.3 Operating level
The content of the extended operating level is determined by means of 8800/8840
configurator (engineering tool). Parameters which are used frequently or the
display of which is important can be copied to the extended operating level.
time
out
utomatic
1199
1200
È
Ì
Ù
1199
Y21
only
display
i
Ò
Ò
i
anua
1199
Y21
È
Ì
Ù
1199
1200
È
Ì
time
out
Ù
Ù
Extended operating level
time
out
Error list (if error exists)
126
FbF.1
Err
Behaviour after power-on128800 process controller
Display
switching
126
2
Err
3.4 Error list / Mainenance manager
With one or several errors, the extended operating level
always starts with the error list. Signalling an actual entry
in the error list (alarm, error) is done by the Err LED in the
display. To reach the error list press Ù twice.
Err LED statusSignificationProceed as follows
blinks
(status 2)
lit
(status 1)
off
(status 0)
Alarm due to existing
error
Error removed, alarm
not acknowledged
No error, all alarm
entries deleted
Determine the error type in the error list
-
After error correction the unit changes to status 1
-
Acknowledge the alarm in the error list pressing key ÈorÌ
- e.g. EMC trouble- Keep measurement and power supply
cables in separate runs
- Ensure that interference suppression
of contactors is provided
- wrong configuration
- missing configuration
- Check interaction of configuration /
parameters
- Contact West service
hardware are not
identical
-
Sensor defective
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
-
Faulty cabling
- Elektronic-/Optioncard must be
exchanged
-
Replace INP1 sensor
-
Check INP1 connection
-
Replace INP1 sensor
-
Check INP1 connection
-
Reverse INP1 polarity
-
Replace INP2 sensor
-
Check INP2 connection
-
Replace sensor INP2
-
Check INP2 connection
-
Reverse INP2 polarity
-
Replace INP3 sensor
-
Check INP3 connection
-
Replace sensor INP3
-
Check INP3 connection
-
Reverse INP3 polarity
8800 process controller13Error list / Mainenance manager
Operation
Name
HCA
SSr
LooP
AdA.H
AdA.C
LiM.1
Lim.2
Lim.3
Inf.1
Inf.2
E.5
dp.1
dp.2
dp.3
DescriptionReasonPossible remedial action
Heating current
alarm (HCA)
Heating current circuit
-
interrupted, I< HC.A or
Check heating current circuit
If necessary, replace heater band
-
I> HC.A (dependent of
configuration)
Heater band defective
-
Heating current
short circuit (SSR)
Current flow in heating
circuit with controller
Check heating current circuit
If necessary, replace solid-state relay
-
off
SSR defective
-
Control loop alarm
(LOOP)
Input signal defective or
not connected correctly
Output not connected
correctly
Check heating or cooling circuit
Check sensor and replace it, if
necessary
Check controller and switching
device
Self-tuning heating
alarm
See Self-tuning heating
error status
see Self-tuning heating error status
-
(ADAH)
Self-tuning heating
alarm cooling
(ADAC)
stored limit alarm 1- adjusted limit value 1
See Self-tuning cooling
error status
see Self-tuning cooling error status
-
- check process
exceeded
stored limit alarm 2- adjusted limit value 2
- check process
exceeded
stored limit alarm 3- adjusted limit value 3
- check process
exceeded
time limit value
message
duty cycle message
(digital ouputs)
Internal error in DP
module
- adjusted number of
operating hours reached
- adjusted number of duty
cycles reached
-
self-test error
-
internal communication
- application-specific
- application-specific
-
Switch on the instrument again
-
Contact West service
interrupted
No access by bus
master
-
bus error
-
connector problem
-
no bus connection
Faulty configuration-Faulty DP
configuration telegram
Inadmissible
parameter setting
telegram sent
-
Faulty DP parameter
setting telegram
-
Check cable
-
Check connector
-
Check connections
-
Check DP configuration telegram in
master
-
Check DP parameter setting
telegram in master
-
Check cable connection
-
Check address
-
Check master setting
dp.4
No data
communication
-
Bus error
-
Address error
-
Master stopped
Error list / Mainenance manager148800 process controller
Operation
g
g
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3, the è-key or the Ò-key.
Configuration, see page 37: ConF / LOGI / Err.r
If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Impulse tuning failedThe control loop is perhaps not closed: check sensor, connections
and process
DAC function ( DAC) error status:
Error
status
0
3
4
5
6
No error
Output is blockedCheck the drive for blockage
Wrong method of operationWrong phasing, defect motor capacitor
Fail at Yp measurementCheck the connection to the Yp input
Calibration errorManual calibration necessary
DescriptionBehaviour
8800 process controller15Error list / Mainenance manager
Operation
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt,
whereby the process characteristics are used to calculate the parameters for fast
line-out to the set-point without overshoot.
The following parameters are optimized when self-tuning:
Parameter set 1:
Pb1- Proportional band 1 (heating) in engineering units [e.g. °C]
ti1- Integral time 1 (heating) in [s]
r only, unless set to OFF
td1- Derivative time 1 (heating) in [s]
r only, unless set to OFF
t1- Minimum cycle time 1 (heating) in [s]
r only, unless Adt0 was set to “no self-tuning” during
configuration by means of 8800/8840 configurator
®
.
Pb2- Proportional band 2 (cooling) in engineering units [e.g. °C]
ti2- Integral time 2 (cooling) in [s]
r only, unless set to OFF
td2- Derivative time 2 (cooling) in [s]
r only, unless set toOFF
t2- Minimum cycle time 2 (cooling) in [s]
r only, unless Adt0 was set to “no self-tuning” during
configuration by means of 8800/8840 configurator
Parameter set 2: analogous to parameter set 1 (see page25)
3.5.1 Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set values
w
rnG.L and rnG.H to the limits of subsequent control.
(ConfigurationrControllerrlower and upper control range limits)
ConFr Cntr rrnG.L and rnG.H
Determine which parameter set shall be optimized.
w
-The instantaneously effective parameter set is optimized.
r Activate the relevant parameter set (1 or 2).
®
.
Determine which parameter set shall be optimized (see tables above).
w
Select the self-tuning method
w
see chapter 3.5.3
-Step attempt after start-up
-Pulse attempt after start-up
-Optimization at the set-point
Self-tuning168800 process controller
3.5.2 Optimization after start-up or at the set-point
The two methods are optimization after start-up and at the set-point.
As control parameters are always optimal only for a limited process range,
various methods can be selected dependent of requirements. If the process
behaviour is very different after start-up and directly at the set-point, parameter
sets 1 and 2 can be optimized using different methods. Switch-over between
parameter sets dependent of process status is possible (see page 25).
Optimization after start-up: (see page25 )
Optimization after start-up requires a certain separation between process value
and set-point. This separation enables the controller to determine the control
parameters by evaluation of the process when lining out to the set-point.
This method optimizes the control loop from the start conditions to the set-point,
whereby a wide control range is covered.
We recommend selecting optimization method “Step attempt after start-up”
with tunE = 0 first. Unless this attempt is completed successfully, we
recommend a “Pulse attempt after start-up”.
Operation
Optimization at the set-point: (see page 18)
For optimizing at the set-point, the controller outputs a disturbance variable to the
process. This is done by changing the output variable shortly. The process value
changed by this pulse is evaluated. The detected process parameters are
converted into control parameters and saved in the controller.
This procedure optimizes the control loop directly at the set-point. The advantage
is in the small control deviation during optimization.
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)
Selection criteria for the optimization method:
Step attempt after start-upPulse attempt after start-upOptimization at the set-point
tunE =0
tunE =1
tunE =2
sufficient set-point reserve is
provided
sufficient set-point reserve is
provided
always step attempt after
start-up
Sufficient set-point reserve:
inverse controller:(with process value < set-point- (10% of rnGH - rnGL)
direct controller:(with process value > set-point + (10% of rnGH - rnGL)
sufficient set-point reserve is not
provided
sufficient set-point reserve is not
provided
Step attempt after start-up
Condition:- tunE = 0 and sufficient set-point reserve provided or
- tunE =2
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start-conditions on page 16).
Subsequently, a correcting variable step change to 100% is output.
8800 process controller17Self-tuning
Operation
The controller attempts to calculate the optimum control parameters from the
process response. If this is done successfully, the optimized parameters are taken
over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100%
cooling energy) is output from the set-point. After successfull determination of
the “cooling parameters”, line-out to the set-point is using the optimized
parameters.
Pulse attempt after start-up
Condition: - tunE = 1 and sufficient set-point reserve provided.
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start conditions page 16)
Subsequently, a short pulse of 100% is output (Y=100%) and reset.
The controller attempts to determine the optimum control parameters from the
process response. If this is completed successfully, these optimized parameters
are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described and line-out to the set-point, correcting
variable "heating" remains unchanged and a cooling pulse (100% cooling energy)
is output additionally. After successful determination of the “cooling
parameters”, the optimized parameters are used for line-out to the set-point.
Optimization at the set-point
Conditions:
A sufficient set-point reserve is not provided at self-tuning start (see page 17).
w
tunE is0or1
w
With Strt = 1 configured and detection of a process value oscillation by
w
more than ± 0,5% of (rnG.H - rnG.L) by the controller, the control
parameters are preset for process stabilization and the controller realizes an
optimization at the set-point (see figure “Optimization at the set-point”).
when the step attempt after power-on has failed
w
with active gradient function ( PArA/ SETP/ r.SP≠ OFF), the set-point
w
gradient is started from the process value and there isn't a sufficient set-point
reserve.
Self-tuning188800 process controller
Operation
Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In
lined out condition, the controller makes a pulse attempt. This pulse reduces the
correcting variable by max. 20% 1, to generate a slight process value
undershoot. The changing process is analyzed and the parameters thus calculated
are recorded in the controller. The optimized parameters are used for line-out to
the set-point.
Optimization at the set-point
set-point
process value
correcting
variable
With a 3-point controller, optimization for the “heating“ or “cooling” parameters
occurs dependent of the instantaneous condition.
These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is
increased by max. 20%.
8800 process controller19Self-tuning
Operation
Optimization at the set-point for 3-point stepping controller
With 3-point stepping controllers, the pulse attempt can be made with or without
position feedback. Unless feedback is provided, the controller calculates the
motor actuator position internally by varying an integrator with the adjusted
actuator travel time. For this reason, precise entry of the actuator travel time
(tt), as time between stops is highly important. Due to position simulation, the
controller knows whether an increased or reduced pulse must be output. After
supply voltage switch-on, position simulation is at 50%. When the motor actuator
was varied by the adjusted travel time in one go, internal calculation occurs, i.e.
the position corresponds to the simulation:
Simulationactual position
Internal calculation
tt
Internal calculation always occurs, when the actuator was varied by travel time
tt in one go
variation, internal calculation is cancelled. Unless internal calculation occurred
already after self-tuning start, it will occur automatically by closing the actuator
once.
Unless the positioning limits were reached within 10 hours, a significant
deviation between simulation and actual position may have occurred. In this case,
the controller would realize minor internal calculation, i.e. the actuator would be
closed by 20 %, and re-opened by 20 % subsequently. As a result, the controller
knows that there is a 20% reserve for the attempt.
, independent of manual or automatic mode. When interrupting the
Self-tuning208800 process controller
3.5.4 Self-tuning start
Start condition:
For process evaluation, a stable condition is required. Therefore, the
w
controller waits until the process has reached a stable condition after
self-tuning start.
The rest condition is considered being reached, when the process value
oscillation is smaller than ± 0,5% of (rnG.H - rnG.L).
For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)
w
is required.
Operation
g
Self-tuning start can be blocked via 8800/8840 configurator®(engineering tool)
( P.Loc).
Strt = 0Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.
Strt = 1Manual start by press keys Ùand È simultaneously
via interface and automatic start after power-on and detection
of process oscillations.
Ada LED statusSignification
blinksWaiting, until process
calms down
litSelf-tuning is running
offSelf-tuning not activ
or ended
°C
°F
3.5.5 Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È
key simultaneously.With controller switch-over to manual mode after self-tuning
start, self-tuning is cancelled. When self-tuning is cancelled, the controller will
continue operating using the old parameter values.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning
is prevented due to the control conditions. In this case, self-tuning was cancelled
by the controller. The controller continues operating with the old parameters in
automatic mode. In manual mode it continues with the old controller output
value.
3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning
8800 process controller21Self-tuning
Operation
1.Press keys Ù and È simultaneously:
2.Press key Ò (if configured):
3.Press key Ù :
Cancellation causes:
r page 15: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
The controller continues controlling using the old parameters in automatic
mode. The Err LED continues blinking, until the self-tuning error was
acknowledged in the error list.
The controller goes to manual mode. The Err LED continues blinking,
until the self-tuning error was acknowleged in the error list.
Display of error list at extended operating level. After acknowledgement
of the error message, the controller continues control in automatic mode using
the old parameters.
Self-tuning228800 process controller
3.5.7 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Operation
Start: heating power switched on
Heating power Y is switched off (1).
X
W
2
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning
100%
0%
Y
Star t r
1
3
t reversal point
attempt is finished and the new
parameter are used for controlling to
blinks
set-point W.
Start: heating power switched off
X
W
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning
attempt is finished and control to the
set-point is using the new parameters.
Self-tuning at the set-point a
100%
0%
Y
start r
1
blinks
2
t reversal point
The process is controlled to the
set-point. With the control deviation
constant during a defined time (1)
(i.e. constant separation of process value
X
W
r
2
t
and set-point), the controller outputs a
reduced correcting variable pulse (max.
20%) (2). After determination of the
control parameters using the process
characteristic (3), control is started
using the new parameters (4).
Three-point controller a
The parameter for heating and cooling are
100%
0%
Start r
X
W
Y
1
blinks
3
4
3
rt
determined in two attempts. The heating
power is switched on (1). Heating
parameters Pb1, ti1, td1 and t1 are
determined at the reversal point. Control to
the set-point occurs(2). With constant
control deviation, the controller provides a
+100%
Y0%
-100%
Start r
1
t reversal
point
2
4
cooling correcting variable pulse (3).
After determining its cooling parameters
Pb2, ti2, td2 and t2 (4) from the
process characteristics , control operation is started using the new parameters (5).
t
t
t
t
5
a
During phase 3, heating and cooling are done simultaneously!
8800 process controller23Self-tuning
Operation
y
3.6 Manual self-tuning
The optimization aid can be used with units on which the control parameters shall
be set without self-tuning.
For this, the response of process variable x after a step change of correcting
variable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T
and x
g
(step change from 0 to 100 %) or ∆t and ∆x (partial step
max
response) can be used to determine the maximum rate of increase v
100%
Y
h
0%
x
t
Tg
X
max
{X
{t
max
.
Tu
t
y=correcting variable
Y
h
=control range
Tu=delay time (s)
Tg=recovery time (s)
X
V
max
max
=maximum process value
Xmax
=
Tg
∆∆x
=
= max. rate of increase of process value
t
The control parameters can be determined from the values calculated for delay
time T
, maximum rate of increase v
u
, control range Xhand characteristic K
max
according to the formulas given below. Increase Pb1, if line-out to the set-point
oscillates.
Manual self-tuning248800 process controller
Operation
Parameter adjustment effects
ParameterControlLine-out of disturbancesStart-up behaviour
Pb1 higherincreased damping slower line-outslower reduction of duty cycle
lower reduced dampingfaster line-outfaster reduction of duty cycle
td1 higherreduced dampingfaster response to disturbances faster reduction of duty cycle
lower increased
damping
slower response to
disturbances
slower reduction of duty cycle
Formulas
K = Vmax * Tucontroller behaviorPb1 [phy. units]td1 [s]ti1 [s]
PID1,7*K2*Tu2*Tu
With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 ≤ 0,25 * Tu
PD0,5 * KTuOFF
PI2,6 * KOFF6*Tu
PKOFFOFF
3-point-stepping1,7 * KTu2 * Tu
3.7 Second PID parameter set
The process characteristic is frequently affected by various factors such as
process value, correcting variable and material differences.
To comply with these requirements, the 8800 process controller can be switched
over between two parameter sets.
Parameter sets PArA and PAr.2 are provided for heating and cooling.
Dependent of configuration ( ConF/LOG/Pid.2), switch-over to the second
parameter set ( ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3,
key è or interface (OPTION).
g
Self-tuning is always done using the active parameter set, i.e. the second
parameter set must be active for optimizing.
8800 process controller25Second PID parameter set
Operation
3.8 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs.
Generally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If
more than one signal is linked to one output the signals are OR linked. Each of
the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min),
which can be switched off individually (parameter = “OFF”). Switching
difference HYS.x and delay dEl.x of each limit value is adjustable.
The variable to be monitored can be selected seperately for each alarm via
configuration
The following variables can be monitored:
process value
w
control deviation xw (process value - set-point)
w
control deviation xw + suppression after start-up or set-point change
w
After switching on or set-point changing, the alarm output is suppressed,
until the process value is within the limits for the first time. At the latest after
expiration of time 10 ti1, the alarm is activated. (ti1 = integral time 1;
parameter r Cntr)
If ti1 is switched off (ti1 = OFF), this is interpreted as Î, i.e. the alarm
is not activated, before the process value was within the limits once.
Measured value INP1
w
Measured value INP2
w
Measured value INP3
w
effective set-point Weff
w
correcting variable y (controller output)
w
Deviation from SP internal
w
Process value - x2
w
g
If measured value monitoring + alarm status storage is chosen ( ConF / Lim /
Fnc.x=2/4), the alarm relay remains switched on until the alarm is resetted in
the error list ( Lim 1..3 = 1).
8800 process controller27Alarm handling
Operation
3.9 Operating structure
After supply voltage switch-on, the controller starts with the operating levels.
The controller status is as before power off.
g
g
1199
1200
Ù
3 sec.
1199
PArA
para
Ì
Ù
1199
ConF
para
Ì
PASS
Ù
1199
CAL
PASS
Ù
PASS
1199
Ù
Ì
PArA - level:At PArA - level, the right decimal point of the bottom
display line is lit continuously.
ConF - level:At ConF - level, the right decimal point of bottom
display line blinks
.
When safety switch Loc is open, only the levels enabled by
PASS
of 8800/8840 configurator (engineering tool). Individual parameters accessible
without password must be copied to the extended operating level.
means of 8800/8840 configurator (engineering tool) are visible
and accessible by entry of the password also adjusted by means
End
g
g
Operating structure288800 process controller
Factory setting:Safety switch Loc closed: all levels accessible without
restriction, password PASS = OFF.
All levels locked with a password are locked only if safety switch Loc is closed.
The configuration can be adjusted by means of keys ÈÌ .
w
Transition to the next configuration is by pressing key Ù .
w
After the last configuration of a group, donE is displayed and followed by
w
automatic change to the next group
Return to the beginning of a group is by pressing the Ù key for 3 sec.
8800 process controller29Configuration survey
Configuration level
4.2 Configuration parameters
Cntr
NameValue rangeDescriptionDefault
SP.Fn
C.tYP
C.Fnc
C.dif
mAn
C.Act
FAIL
Basic configuration of setpoint processing
0
set-point controller can be switched over to external set-point
(-> LOGI/ SP.E)
8
standard controller with external offset (SP.E)
Calculation of the process value
0
1
2
3
standard controller (process value = x1)
ratio controller (x1/x2)
difference (x1 - x2)
Maximum value of x1and x2. It is controlled with the bigger
value. At sensor failure it is controlled with the remaining
actual value.
4
Minimum value of x1and x2. It is controlled with the smaller
value. At sensor failure it is controlled with the remaining
actual value.
5
Mean value (x1, x2). With sensor error, controlling is
continued with the remaining process value.
6Switching between x1 and x2 (-> LOGI/ I.ChG)
7O
8O
function with constant sensor temperature
2
function with measured sensor temperature
2
Control behaviour (algorithm)
0
1
2
on/off controller or signaller with one output
PID controller (2-point and continuous)
∆ / Y / Off, or 2-point controller with partial/full load
switch-over
3
4
5
6
2 x PID (3-point and continuous)
3-point stepping controller
3-point stepping controller with position feedback Yp
continuous controller with integrated positioner
Output action of the PID controller derivative action
0
1
Derivative action acts only on the measured value.
Derivative action only acts on the control deviation
(set-point is also differentiated)
Manual operation permitted
0
1
no
yes (r LOGI / mAn)
Method of controller operation
0
1
inverse, e.g. heating
direct, e.g. cooling
Behaviour at sensor break
0
1
2
controller outputs switched off
y=Y2
y = mean output. The maximum permissible output can be
adjusted with parameter Ym.H. To prevent determination of
inadmissible values, mean value formation is only if the
control deviation is lower than parameter L.Ym.
0
0
1
0
0
0
1
Configuration parameters308800 process controller
Configuration level
NameValue rangeDescriptionDefault
rnG.L
rnG.H
CYCL
tunE
Strt
Adt0
-1999...9999
-1999...9999
X0 (low limit range of control) 1
X100 (high limit range of control) 1
Characteristic for 2-point- and 3-point-controllers
0
1
2
3
standard
water cooling linear
water cooling non-linear
with constant cycle (see page 51)
Auto-tuning at start-up (see page 16 )
0
At start-up with step attempt, at set-point with impulse
attempt
1
At start-up and at set-point with impulse attempt. Setting for
fast controlled systems (e.g. hot runner control)
2Always step attempt at start-up
Start of auto-tuning
0
1
Manual start of auto-tuning
Manual or automatic start of auto-tuning at power on or
when oscillating is detected
Optimization of T1, T2 (only visible with 8800/8840
configurator!)
0
1
Automatic optimization
No optimization
-100
1200
0
0
0
0
1 rnG.L and rnG.H are indicating the range of control on which e.g. the
self-tuning is refering
InP.1
NameValue rangeDescriptionDefault
I.fnc
INP1 function selection
0
1
2
3
4
5
No function (following INP data are skipped)
Heating current input
External set-point SP.E (switch-over -> LOGI/ SP.E)
Position feedback Yp
Second process value x2 (ratio, min, max, mean)
External positioning value Y.E
(switch-over r LOGI / Y.E)
6
7
No controller input (e.g. limit signalling instead)
Process value x1
7
8800 process controller31Configuration parameters
Configuration level
NameValue rangeDescriptionDefault
S.tYP
S.Lin
Corr
In.f
fAI1
-1999...9999
10
18
20
21
22
23
24
30
40
41
42
50
51
52
53
Sensor type selection
0
1
2
3
4
5
6
7
8
9
thermocouple type L (-100...900°C) , Fe-CuNi DIN
thermocouple type J (-100...1200°C) , Fe-CuNi
thermocouple type K (-100...1350°C), NiCr-Ni
thermocouple type N (-100...1300°C), Nicrosil-Nisil
thermocouple type S (0...1760°C), PtRh-Pt10%
thermocouple type R (0...1760°C), PtRh-Pt13%
thermocouple type T (-200...400°C), Cu-CuNi
thermocouple type C (0...2315°C), W5%Re-W26%Re
thermocouple type D (0...2315°C), W3%Re-W25%Re
thermocouple type E (-100...1000°C), NiCr-CuNi
1
thermocouple type B (0/100...1820°C), PtRh-Pt6%
special thermocouple
Pt100 (-200.0 ... 100,0 °C)
Pt100 (-200.0 ... 850,0 °C)
Pt1000 (-200.0 ... 850.0 °C)
special 0...4500 Ohm (preset to KTY11-6)
special 0...450 Ohm
none
Linearization to specification. Creation of linearization table
with 8800/8840 configurator (engineering tool) possible.
The characteristic for KTY 11-6 temperature sensors is
preset.
Measured value correction / scaling
0
1
2
3
Without scaling
Offset correction (at CAL level)
2-point correction (at CAL level)
Scaling (at PArA level)
Alternative value for error at INP1
Forcing INP1 (only visible with 8800/8840 configurator!)
0
1
No forcing
Forcing via serial interface
0
OFF
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
Configuration parameters328800 process controller
Configuration level
InP.2
NameValue rangeDescriptionDefault
I.Fnc
S.tYP
Corr
In.F
fAI2
Function selection of INP2
0
1
2
3
4
5
no function (subsequent input data are skipped)
heating current input
External set-point SP.E (switch-over -> LOGI/ SP.E)
Position feedback Yp
Second process value x2 (ratio, min, max, mean)
External positioning value Y.E
(switch-over r LOGI / Y.E)
6
7
no controller input (e.g. transmitter input instead)
Process value x1
0Without scaling
1Offset correction (at CAL level)
22-point correction (at CALlevel)
3Scaling (at PArA level)
-1999...9999
Alternative value for error at INP2
Forcing INP2 (only visible with 8800/8840 configurator!)
0
1
No forcing
Forcing via serial interface
1
30
OFF
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
InP.3
NameValue rangeDescriptionDefault
I.Fnc
Function selection of INP3
0
1
2
3
4
5
no function (subsequent input data are skipped)
heating current input
External set-point SP.E (switch-over -> LOGI/ SP.E)
Yp input
Second process value X2
External positioning value Y.E
(switch-over r LOGI / Y.E)
6
7
no controller input (e.g. transmitter input instead)
Process value x1
1
8800 process controller33Configuration parameters
Configuration level
NameValue rangeDescriptionDefault
S.tYP
S.Lin
Corr
In.F
fAI3
-1999...9999
10
18
20
21
22
23
24
30
41
42
50
51
52
53
Sensor type selection
0
1
2
3
4
5
6
7
8
9
thermocouple type L (-100...900°C) , Fe-CuNi DIN
thermocouple type J (-100...1200°C) , Fe-CuNi
thermocouple type K (-100...1350°C), NiCr-Ni
thermocouple type N (-100...1300°C), Nicrosil-Nisil
thermocouple type S (0...1760°C), PtRh-Pt10%
thermocouple type R (0...1760°C), PtRh-Pt13%
thermocouple type T (-200...400°C), Cu-CuNi
thermocouple type C (0...2315°C), W5%Re-W26%Re
thermocouple type D (0...2315°C), W3%Re-W25%Re
thermocouple type E (-100...1000°C), NiCr-CuNi
30
thermocouple type B (0/100...1820°C), PtRh-Pt6%
special thermocouple
Pt100 (-200.0 ... 100,0 °C)
Pt100 (-200.0 ... 850,0 °C)
Pt1000 (-200.0 ... 850.0 °C)
special 0...4500 Ohm (preset to KTY11-6)
special 0...450 Ohm
none
Linearization to specification. Creation of linearization table
with 8800/8840 configurator (engineering tool) possible.
The characteristic for KTY 11-6 temperature sensors is
preset.
Measured value correction / scaling
0
(only at S.tYP = 23,24,30,41 and 42 adjustable)
0
1
2
3
4
0
1
Without scaling
Offset correction (at CAL level)
2-point correction (at CAL level)
Scaling (at PArA level)
Automatic calibration (DAC)
Alternative value for error at INP3
Forcing INP3 (only visible with 8800/8840 configurator!)
No forcing
Forcing via serial interface
OFF
0
1 with current and voltage input signals, scaling is required (see chapter 5.3)
Configuration parameters348800 process controller
Configuration level
Lim
NameValue range DescriptionDefault
Fnc.1
Src.1
Fnc.2
Function of limit 1
0
1
2
switched off
measured value monitoring
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è-key, Ò-key or a
digital input ( -> LOGI/ Err.r)
3
4
signal change (change/minute)
signal change and storage (change/minute)
Source of imit 1
0
1
2
process value
control deviation xw (process value - set-point)
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the first
time. At the latest after elapse of time 10 ti1the alarm is
activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î , i.e.
the alarm is not activated, before the process value was within the
limits once.
3
4
5
6
7
measured value INP1
measured value INP2
measured value INP3
effective setpoint Weff
correcting variable y (controller output)
8control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function “mean value” for recognizing aged
thermocouples
Function of limit 2
0
1
2
switched off
measured value monitoring
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è-key, Ò-key or a
digital input ( -> LOGI/ Err.r)
3
4
signal change (change/minute)
signal change and storage (change/minute)
1
1
0
8800 process controller35Configuration parameters
Configuration level
NameValue range DescriptionDefault
Src.2
Fnc.3
Source of limit 2
0
1
2
process value
control deviation xw (process value - set-point)
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the
first time. At the latest after elapse of time 10 ti1the alarm
is activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î ,
i.e. the alarm is not activated, before the process value was
within the limits once.
3
4
5
6
7
measured value INP1
measured value INP2
measured value INP3
effective setpoint Weff
correcting variable y (controller output)
8control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function “mean value” for recognizing aged
thermocouples
Function of limit 3
0
1
2
switched off
measured value monitoring
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è-key, Ò-key or a
digital input ( -> LOGI/ Err.r)
3
4
signal change (change/minute)
signal change and storage (change/minute)
0
0
Configuration parameters368800 process controller
Configuration level
NameValue range DescriptionDefault
Src.3
HC.AL
LP.AL
dAc.A
Hour
Swit
Source of limit 3
0
1
2
process value
control deviation xw (process value - set-point)
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the
first time. At the latest after elapse of time 10 ti1 the alarm
is activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î ,
i.e. the alarm is not activated, before the process value was
within the limits once.
3
4
5
6
7
measured value INP1
measured value INP2
measured value INP3
effective setpoint Weff
correcting variable y (controller output)
8control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function “mean value” for recognizing aged
thermocouples
Alarm heat current function (INP2)
0
1
2
switched off
Overload short circuit monitoring
Break and short circuit monitoring
Monitoring of control loop interruption for heating
0
1
switched off / inactive
active.
If ti1=0 LOOP alarm is inactive!
DAC alarm function
0
1
OFF...999999
OFF...999999
DAC alarm switched off / inactive
DAC alarm active
Operating hours (only visible with 8800/8840 configurator!)
Output switching cycles (only visible with 8800/8840
configurator!)
0
0
0
0
OFF
OFF
Out.1
NameValue rangeDescriptionDefault
O.Act
0
1
Y.1
0
1
Method of operation of output OUT1
direct / normally open
inverse / normally closed
Controller output Y1
not active
active
8800 process controller37Configuration parameters
0
1
Configuration level
NameValue rangeDescriptionDefault
Y.2
Lim.1
Lim.2
Lim.3
dAc.A
LP.AL
HC.AL
HC.SC
FAi.1
FAi.2
FAi.3
fOut
Controller output Y2
0
1
not active
active
Limit 1 signal
0
1
not active
active
Limit 2 signal
0
1
not active
active
Limit 3 signal
0
1
not active
active
Valve monitoring (DAC)
0
1
not active
active
Interruption alarm signal (LOOP)
0
1
not active
active
Heat current alarm signal
0
1
not active
active
Solid state relay (SSR) short circuit signal
0
1
not active
active
INP1 error signal
0
1
not active
active
INP2 error signal
0
1
not active
active
INP3 error signal
0
1
not active
aktiv
Forcing OUT1 (only visible with 8800/8840 configurator!)
relay / logic (only visible with current/logic voltage)
0 ... 20 mA continuous (only visible with
current/logic/voltage)
2
4 ... 20 mA continuous (only visible with
current/logic/voltage)
3
4
5
0...10 V continuous (only visible with current/logic/voltage)
2...10 V continuous (only visible with current/logic/voltage)
transmitter supply (only visible without OPTION)
Method of operation of output OUT3 (only visible when
O.TYP=0)
0
1
direct / normally open
inverse / normally closed
Controller output Y1 (only visible when O.TYP=0)
0
1
not active
active
Controller output Y2 (only visible when O.TYP=0)
0
1
not active
active
Limit 1 signal (only visible when O.TYP=0)
0
1
not active
active
Limit 2 signal (only visible when O.TYP=0)
0
1
not active
active
Limit 3 signal (only visible when O.TYP=0)
0
1
not active
active
Valve monitoring (DAC) (only visible when O.TYP=0)
0
1
not active
active
Interruption alarm signal (LOOP) (only visible when
O.TYP=0)
0
1
not active
active
Heating current alarm signal (only visible when O.TYP=0)
0
1
not active
active
Solid state relay (SSR) short circuit signal (only visible
when O.TYP=0)
0
1
not active
active
0
1
0
0
1
0
0
0
0
0
0
8800 process controller39Configuration parameters
Configuration level
NameValue rangeDescriptionDefault
FAi.1
FAi.2
FAi.3
Out.0
Out.1
O.Src
fOut
0
1
0
1
0
1
-1999...9999
-1999...9999
0
1
2
3
4
5
6
7
8
9
0
1
INP1 error (only visible when O.TYP=0)
not active
active
INP2 error (only visible when O.TYP=0)
not active
active
INP3 error (only visible when O.TYP=0)
not active
aktiv
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when O.TYP=1..5)
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
Signal source of the analog output OUT3 (only visible when
O.TYP=1..5)
not used
controller output y1 (continuous)
controller output y2 (continuous)
process value
effective set-point Weff
control deviation xw (process value - set-point)
measured value position feedback Yp
measured value INP1
measured value INP2
measured value INP3
Forcing OUT3 (only visible with 8800/8840 configurator!)
No forcing
Forcing via serial interface
1
0
0
0
100
1
0
Out.4
NameValue rangeDescriptionDefault
O.tYP
O.Act
Signal type selection OUT4
0
1
relay / logic (only visible with current/logic voltage)
0 ... 20 mA continuous (only visible with
current/logic/voltage)
2
4 ... 20 mA continuous (only visible with
current/logic/voltage)
3
4
5
0...10 V continuous (only visible with current/logic/voltage)
2...10 V continuous (only visible with current/logic/voltage)
transmitter supply (only visible without OPTION)
Method of operation of output OUT4 (only visible when
O.TYP=0)
0
1
direct / normally open
inverse / normally closed
0
0
Configuration parameters408800 process controller
Configuration level
NameValue rangeDescriptionDefault
Y.1
Y.2
Lim.1
Lim.2
Lim.3
dAc.A
LP.AL
HC.AL
HC.SC
FAi.1
FAi.2
FAi.3
Out.0
Out.1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
-1999...9999
-1999...9999
Controller output Y1 (only visible when O.TYP=0)
not active
active
Controller output Y2 (only visible when O.TYP=0)
not active
active
Limit 1 signal (only visible when O.TYP=0)
not active
active
Limit 2 signal (only visible when O.TYP=0)
not active
active
Limit 3 signal (only visible when O.TYP=0)
not active
active
Valve monitoring (DAC) (only visible when O.TYP=0)
not active
active
Interruption alarm signal (LOOP) (only visible when
O.TYP=0)
not active
active
Heat current alarm signal (only visible when O.TYP=0)
not active
active
Solid state relay (SSR) short circuit signal (only visible
when O.TYP=0)
not active
active
INP1 error (only visible when O.TYP=0)
not active
active
INP2 error (only visible when O.TYP=0)
not active
active
INP3 error (only visible when O.TYP=0)
not active
aktiv
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when O.TYP=1..5)
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
Signal source of the analog output OUT4 (only visible when
0
O.TYP=1..5)
0
1
2
3
4
5
6
0
1
not used
controller output y1 (continuous)
controller output y2 (continuous)
process value
effective set-point Weff
control deviation xw (process value - set-point)
measured value position feedback Yp
Forcing OUT1 (only visible with 8800/8840 configurator!)
No forcing
Forcing via serial interface
Method of operation and usage of output Out.1 toOut.6:
Is more than one signal chosen active as source, those signals are
OR-linked.
LOGI
NameValue rangeDescriptionDefault
L_r
SP.2
Local / Remote switching (Remote: adjusting of all values
by front keys is blocked)
0
1
2
3
4
5
no function (switch-over via interface is possible)
always active
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Switching to second setpoint SP.2
0
2
3
4
5
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
0
0
Configuration parameters428800 process controller
Configuration level
NameValue rangeDescriptionDefault
SP.E
Y2
Y.E
mAn
C.oFF
m.Loc
Switching to external setpoint SP.E
0
1
2
3
4
5
no function (switch-over via interface is possible)
always active
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Y/Y2 switching
0
2
3
4
5
6
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Ò - key switches
Switching to fixed control output Y.E
0
1
2
3
4
5
6
no function (switch-over via interface is possible)
always activated (manual station)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Ò - key switches
Automatic/manual switching
0
1
2
3
4
5
6
no function (switch-over via interface is possible)
always activated (manual station)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Ò - key switches
Switching off the controller
0
2
3
4
5
6
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Ò - key switches
Blockage of hand function
0
2
3
4
5
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
0
0
0
0
0
0
8800 process controller43Configuration parameters
Configuration level
NameValue rangeDescriptionDefault
Err.r
Pid.2
I.Chg
di.Fn
fDI1
fDI2
fDI3
Reset of all error list entries
0
2
3
4
5
6
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Ò - key switches
Switching of parameter set (Pb, ti, td)
0
2
3
4
5
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Switching of the actual process value between Inp1 and X2
0
2
3
4
5
no function (switch-over via interface is possible)
DI1 switches
DI2 switches (only visible with OPTION)
DI3 switches (only visible with OPTION)
è - key switches
Function of digital inputs (valid for all inputs)
0
1
2
direct
inverse
toggle key function
Forcing di1 (only visible with 8800/8840 configurator!)
0
1
No forcing
Forcing via serial interface
Forcing di2 (only visible with 8800/8840 configurator!)
0
1
No forcing
Forcing via serial interface
Forcing di3 (only visible with 8800/8840 configurator!)
0
1
No forcing
Forcing via serial interface
0
0
0
0
0
0
0
othr
NameValue rangeDescriptionDefault
bAud
Addr
0
1
2
3
1...247
Baudrate of the interface (only visible with OPTION)
2400 Baud
4800 Baud
9600 Baud
19200 Baud
Address on the interace (only visible with OPTION)
Configuration parameters448800 process controller
2
1
Configuration level
NameValue rangeDescriptionDefault
PrtY
dELY
O2
Unit
dP
LED
dISP
C.dEl
dP.AD
bc.up
FrEq
ICof
Data parity on the interface (only visible with OPTION)
0
1
2
3
0...200
no parity (2 stop bits)
even parity
odd parity
no parity (1 stopbit)
Delay of response signal [ms] (only visible with OPTION)
Entering parameter for O2in ppm or %
0
1
Parameter for O2-function in ppm
Parameter for O2-function in %
Unit
0
1
2
without unit
°C
°F
Decimal point (max. number of digits behind the decimal
point)
0
1
2
3
no digit behind the decimal point
1 digit behind the decimal point
2 digits behind the decimal point
3 digits behind the decimal point
Additional delay time, before the received message is
evaluated in the Modbus. This time is required, unless
messages are transferred continuously during modem
transmission.
0...126
Profibus address
Behaviour as backup controller
0
1
No backup functionality
With backup functionality
Switching 50 Hz / 60 Hz (only visible with 8800/8840
configurator!)
0
1
50 Hz
60 Hz
Block controller off (only visible with 8800/8840
Block auto tuning (only visible with 8800/8840
configurator!)
Released
Blocked
Block extended operating level (only visible with
8800/8840 configurator!)
Released
Blocked
Password (only visible with 8800/8840 configurator!)
Block parameter level (only visible with 8800/8840
configurator!)
Released
Blocked
Block configuration level (only visible with 8800/8840
configurator!)
Released
Block
Block calibration level (only visible with 8800/8840
configurator!)
Released
Blocked
Display 3 controller operating level (only visible with
8800/8840 configurator!)
No value / only text
Display of value
Output value as bargraph
Control deviation as bargraph
Process value as bargraph
Display 3 display alternation time [s] (only visible with
8800/8840 configurator!)
display 3 programmer-operating level
Segm.-No., Segm.-Type, Progr.-remaining time
Segm.-No., Segm.-Type, Segm.-remaining time
Segm.-No., Segm.-Type, net-time
Segm.-No., Segm.-Type, Progr.-remaining time
Segm.-No., Segm.-Type, Segm.-remaining time
Segm.-No., Segm.-Type, net-time
Text display 3
Text Inf.1
Text Inf.2
Text Program 1
Text Program 2
Text Program16
0
0
OFF
0
0
0
2
10
0
Configuration parameters468800 process controller
Configuration level
Lin (only visible with 8800/8840 configurator
NameValue rangeDescriptionDefault
Lin
In.1
Ou.1
In.2
Ou.2
:
:
In.16
Ou.16
-999.0..99999
0,001...9999Output value 1
-999.0..99999 Input value 2
0,001...9999Output value 2
:
:
-999.0..99999 Input value 16
0,001...9999Output value 1 6
Linearization for inputs INP1 or INP3
Access to this table is always with selection special
thermocouple for InP.1 or InP.3or with setting
S.Lin = 1: special linearization for linearization.
Default: KTY 11-6 (0...4,5 kOhm)
Input value 1
The signal is in [µV] or in [[] dependent of input type
Signal assigned to In.1
The signal is in [µV] or in [[] dependent of input type
Signal assigned to In.2
:
:
The signal is in [µV] or in [[] dependent of input type
Signal assigned to In.16
1036
-49,94
1150
-38,94
:
:
4470
150,0
g
+
Resetting the controller configuration to factory setting (Default)
r chapter 11.1 (page 82)
8800/8840 configurator - the engineering tool for the West controller series
3 engineering tools with different functionality facilitating 8800 process
controller configuration and parameter setting are available (see chapter 9:
Accessory equipment with ordering information).
In addition to configuration and parameter setting, 8800/8840 configurator is
used for data acquisition and offers long-term storage and print functions.
8800/8840 configurator is connected to 8800 process controller via the
front-panel interface by means of PC (Windows 95 / 98 / NT) and a PC adaptor.
Description 8800/8840 configurator: see chapter 8: 8800/8840 configurator
(page 74).
8800 process controller47Configuration parameters
Configuration level
4.3 Set-point processing
The set-point processing structure is shown in the following picture:
The ramp starts at process value with the following switchings:
- int / ext-setpoint switching
-/switching
SP SP.2
- Manual-/ Automatic switching
- at power on
4.3.1 Set-point gradient / ramp
To prevent set-point step changes, parameter
r set-point r r.SPcan be adjusted
to a maximum rate of change. This gradient is effective in positive and negative
direction..
With parameter r.SP set to OFF (default), the gradient is switched off and
set-point changes are realized directly.
(for parameter: see page48 )
Set-point processing488800 process controller
4.4 Switching behaviuor
[%]
With 8800 process controller, configuration parameter CYCL (ConF/ Cntr/
CYCL) can be used for matching the cycle time of 2-point and 3-point
controllers. This can be done using the following 4 methods.
4.4.1 Standard ( CyCl= 0 )
The adjusted cycle times t1 and t2 are valid for 50% or -50% correcting
variable. With very small or very high values, the effective cycle time is extended
to prevent unreasonably short on and off pulses. The shortest pulses result from
¼x t1 or¼x t2. The characteristic curve is also called “bath tub curve”
T/T
1
6,0
5,0
Configuration level
4,0
3,0
2,0
relative cycle duration
1,0
0,0
5 101520253035404550556065707580859095
Controller output
Parameters to be adjusted:t1 : min. cycle time 1 (heating) [s]
( PArA/ Cntr)t2 : min. cycle time 2 (cooling) [s]
4.4.2 Switching attitude linear ( CyCl= 1 )
For heating (Y1), the standard method
(see chapter 4.4.1) is used. For
cooling (Y2), a special algorithm for
cooling with water is used. Generally,
cooling is enabled only at an
adjustable process temperature
(E.H2O), because low temperatures
prevent evaporation with related
cooling, whereby damage to the plant is avoided. The cooling pulse length is
adjustable using parameter t.on and is fixed for all output values.
The “off” time is varied dependent of output value. Parameter t.off is used for
determining the min “off” time. For output of a shorter off pulse, this pulse is
suppressed, i.e. the max. effective cooling output value is calculated according to
formula t.on /(t.on + t.off) w 100%.
-6%
4xt1
3xt1
2xt1
t1
t.offt.on
-10%
-20%
-30%
-50%
-67%
-80%
-100%
8800 process controller49Switching behaviuor
Configuration level
0
]
Parameters to be adjusted:E.H2O: minimum temperature for water cooling
( PArA / Cntr)t.on:pulse duration water cooling
t.off: minimum pause water cooling
4.4.3 Switching attitude non-linear ( CyCl= 2 )
With this method, the cooling power
is normally much higher than the
heating power, i.e. the effect on the
behaviour during transition from
heating to cooling may be negative.
The cooling curve ensures that the
control intervention with 0 to -70%
correcting variable is very weak.
Moreover, the correcting variable increases very quickly to max. possible
cooling. Parameter F.H2O can be used for changing the characteristic curve. The
standard method (see section 4.4.1) is also used for heating. Cooling is also
enabled dependent of process temperature .
Y.1= 1control output Y1 active
Y.2= 0control output Y2 not active
ConF / Out.2:O.Act= 0action Out.2 direct
Y.1= 0control output Y1 not active
Y.2= 1control output Y2 active
PArA / Cntr:Pb1= 1...9999proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
Pb2= 1...9999proportional band 2 (cooling)
in units of phys. quantity (e.g. °C)
ti1= 0,1...9999integral time 1 (heating) in sec.
ti2= 0,1...9999derivative time 2 (cooling) in sec.
td1= 0,1...9999integral time 1 (heating) in sec.
td2= 0,1...9999derivative time 2 (cooling) in sec.
t1= 0,4...9999min. cycle time 1 (heating)
t2= 0,4...9999min. cycle time 2 (cooling)
SH= 0...9999neutr. zone in units of phys.quantity
PArA / SEtP:SP.LO= -1999...9999 set-point limit low for Weff
Y.1= 1control output Y1 active
Y.2= 0control output Y2 not active
ConF / Out.2:O.Act= 0action Out.2 direct
Y.1= 0control output Y1 not active
Y.2= 1control output Y2 active
PArA / Cntr:Pb1= 1...9999proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1= 0,1...9999integral time 1 (heating) in sec.
td1= 0,1...9999derivative time 1 (heating) in sec.
t1= 0,4...9999min. cycle time 1 (heating)
SH= 0...9999neutral zone in units of phy. quantity
tP= 0,1...9999min. pulse length in sec.
tt= 3...9999actuator travel time in sec.
PArA / SEtP:SP.LO= -1999...9999 set-point limit low for Weff
SP.Hi= -1999...9999 set-point limit high for Weff
For direct action of the 3-point stepping controller, the controller output action
must be changed ( ConF / Cntr / C.Act = 1 ).
Out.0= -1999...9999 scaling analog output 0/4mA
Out.1= -1999...9999 scaling analog output 20mA
PArA / Cntr:Pb1= 1...9999proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1= 0,1...9999integral time 1 (heating) in sec.
td1= 0,1...9999derivative time 1 (heating) in sec.
t1= 0,4...9999min. cycle time 1 (heating)
PArA / SEtP:SP.LO= -1999...9999 set-point limit low for Weff
SP.Hi= -1999...9999 set-point limit high for Weff
g
g
For direct action of the continuous controller, the controller action must be
changed ( ConF / Cntr / C.Act = 1 ).
To prevent control outputs Out.1 and Out.2 of the continuous controller from
switching simultaneously, the control function of outputs Out.1 and Out.2 must
be switched off ( ConF / Out.1 and Out.2 / Y.1 and Y.2 = 0 ).
Configuration examples568800 process controller
Configuration level
4.5.6
∆ - Y - Off controller / 2-point controller with pre-contact
Y.1= 1control output Y1 active
Y.2= 0control output Y2 not active
ConF / Out.2:O.Act= 0action Out.2 direct
Y.1= 0control output Y1 not active
Y.2= 1control output Y2 active
PArA / Cntr:Pb1= 1...9999proportional band 1 (heating)
ti1= 0,1...9999integral time 1 (heating) in sec.
td1= 0,1...9999derivative time 1 (heating) in sec.
t1= 0,4...9999min. cycle time 1 (heating)
SH= 0...9999switching difference
d.SP
(e.g. heating applications)
in units of phys. quantity (e.g. °C)
d.SP= -1999...9999 trigg. point separation suppl. cont.
∆ / Y / Off in units of phys. quantity
PArA / SEtP:SP.LO= -1999...9999 set-point limit low for Weff
SP.Hi= -1999...9999 set-point limit high for Weff
8800 process controller57Configuration examples
Configuration level
4.5.7 8800 process controller with measured value output
This is basically a cascade. A tracking controller with three-point stepping
behaviour which operates with Yp as process value (INP.2 / INP.3) is used with
the continuous controller.
ConF / CntrSP.Fn= 0Setpoint controller
C.Fnc= 6Continuous controller with
integrated positioner
C.Act= 0Direction of operation invers
(e.g. heating)
ConF / InP.2:I.Fnc= 3Position featback Yp
S.typ= 50Sensor e.g. potentiometer 0..160 Ω
ConF / Out.1:O.Act= 0Direction of operation Out.1 direct
The parameters can be adjusted by means of keys ÈÌ
w
Transition to the next parameter is by pressing key Ù
w
After the last parameter of a group, donE is displayed, followed by
w
automatic change to the next group.
g
Return to the beginning of a group is by pressing the Ù key for 3 sec.
If for 30 sec. no keypress is excecuted the controler returns to the process
value and setpoint display ( Time Out = 30 sec. )
Parameter survey608800 process controller
Parameter setting level
5.2 Parameters
Cntr
NameValue rangeDescriptionDefault
Pb1
Pb2
ti1
ti2
td1
td2
t1
t2
SH
Hys.l
Hys.H
d.SP
tP
tt
Y2
Y.Lo
Y.Hi
Y2
Y.0
Ym.H
L.Ym
E.H2O
t.on
t.oFF
F.H2O
oFFS
tEmp
1...9999 1
1...9999 1
0,1...9999
0,1...9999
0,1...9999
0,1...9999
0,4...9999
0,4...9999
0...9999
0...9999
0...9999
-1999...9999
0,1...9999
3...9999
-100...100
-120...120
-120...120
-100...100
-100...100
-100...100
0...9999
-1999...9999
0,1...9999
1...9999
0,1...9999
-120...120
0...9999
Proportional band 1 (heating) in phys. dimensions (e.g. °C)
Proportional band 2 (cooling) in phys. dimensions (e.g. °C)
Integral action time 1 (heating) [s]
Integral action time 2 (cooling) [s]
Derivative action time 1 (heating) [s]
Derivative action time 2 (cooling) [s]
Minimal cycle time 1 (heating) [s]. The minimum impulse is
1/4xt1
Minimal cycle time 2 (heating) [s]. The minimum impulse is
1/4xt2
Neutral zone or switching differential for on-off control
2. correcting variable
Working point for the correcting variable [%]
Limitation of the mean value Ym [%]
Max. deviation xw at the start of mean value calculation
[phys. dimensions]
Min. temperature for water cooling. Below the set
temperature no water cooling happens
Impulse lenght for water cooling. Fixed for all values of
controller output.The pause time is varied.
Min. pause time for water cooling. The max. effective
controller output results from t.on/(t.on+t.off)·100%
Modification of the (non-linear) water cooling characteristic
(see page 50)
Zero offset
Sensor temperature (in engineering units e.g. °C)
With oxygen measurement (O
) (see page 70)
2
100
100
180
180
180
180
10
10
2
1
1
100
OFF
60
0
0
100
0
0
5
8
0
1
10
1
0
750
1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.
8800 process controller61Parameters
Parameter setting level
PAr.2
NameValue rangeDescriptionDefault
Pb12
Pb22
Ti22
Ti12
Td12
Td22
1...9999 1
1...9999 1
0,1...9999
0,1...9999
0,1...9999
0,1...9999
SEtP
NameValue rangeDescriptionDefault
SP.LO
SP.Hi
SP.2
r.SP
SP
-1999...9999
-1999...9999
-1999...9999
0...9999
-1999...9999
Proportional band 1 (heating) in phys. dimensions (e.g. °C),
2. parameter set
Proportional band 2 (cooling) in phys. dimensions (e.g. °C),
2. parameter set
Integral action time 2 (cooling) [s], 2. parameter set
Integral action time 1 (heating) [s], 2. parameter set
Derivative action time 1 (heating) [s], 2. parameter set
Derivative action time 2 (cooling) [s], 2. parameter set
Set-point limit low for Weff
Set-point limit high for Weff
Set-point 2.
Set-point gradient [/min]
Set-point (only visible with 8800/8840 configurator!)
100
100
180
180
180
180
-100
1200
0
OFF
0
SP.LO and SP.Hi should be within the limits of rnGH and rnGL see
configuration r Controller page17
InP.1
NameValue rangeDescriptionDefault
InL.1
OuL.1
InH.1
OuH.1
t.F1
Etc.1
-1999...9999
-1999...9999
-1999...9999
-1999...9999
0,0...9999
0...100 (°C)
32...212 (°F)
Input value for the lower scaling point
Displayed value for the lower scaling point
Input value for the upper scaling point
Displayed value for the lower scaling point
Filter time constant [s]
External cold-junction reference temperature (external TC)
0
0
20
20
0,5
OFF
InP.2
NameValue rangeDescriptionDefault
InL.2
OuL.2
InH.2
OuH.2
-1999...9999
-1999...9999
-1999...9999
-1999...9999
Input value for the lower scaling point
Displayed value for the lower scaling point
Input value for the upper scaling point
Displayed value for the upper scaling point
0
0
50
50
1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.
Parameters628800 process controller
Parameter setting level
NameValue rangeDescriptionDefault
t.F2
0,0...999,9
Filter time constant [s]
0,5
InP.3
NameValue rangeDescriptionDefault
InL.3
OuL.3
InH.3
OuH.3
t.F3
Etc.3
-1999...9999
-1999...9999
-1999...9999
-1999...9999
0,0...999,9
0...100 (°C)
32...212 (°F
Input value for the lower scaling point
Displayed value for the lower scaling point
Input value for the upper scaling point
Displayed value for the upper scaling point
Filter time constant [s]
External cold-junction reference temperature (external TC)
0
0
20
20
0,5
OFF
Lim
NameValue rangeDescriptionDefault
-1999...9999
-1999...9999
0...9999
0...9999
-1999...9999
-1999...9999
0...9999
0...9999
-1999...9999
-1999...9999
0...9999
0...9999
Lower limit 1
Upper limit 1
Hysteresis limit 1
Alarm delay from limit value 1
Lower limit 2OFF
Upper limit 2OFF
Hysteresis limit 2
Alarm delay from limit value 2
Lower limit 3
Upper limit 3
Hysteresis limit 3
Alarm delay from limit value 3
g
L.1
H.1
HYS.1
dEl.1
L.2
H.2
HYS.2
dEl.2
L.3
H.3
HYS.3
dEl.3
Resetting the controller configuration to factory setting (Default)
r chapter 11.1 (page 82)
-10
10
1
0
1
0
OFF
OFF
1
0
8800 process controller63Parameters
Parameter setting level
5.3 Input scaling
When using current, voltage or resistance signals as input variables for InP.1,
InP.2 or/and InP.3 scaling of input and display values at parameter setting level
is required. Specification of the input value for lower and higher scaling point is
in the relevant electrical unit (mA/V/Ω).
phys.
quantity
OuH.x
mA / V
OuL.x
5.3.1 Input Inp.1 and InP.3
g
Parameters InL.x,OuL.x, InH.x and OuH.x are only visible if
ConF / InP.x/Corr = 3 is chosen.
S.tYPInput signalInL.xOuL.xInH.xOuH.x
30
(0...20mA)
40
(0...10V)
0 … 20 mA0any20any
4 … 20 mA4any20any
0 … 10 V0any10any
2 … 10 V2any10any
In addition to these settings, InL.x and InH.x can be adjusted in the range
(0...20mA / 0...10V / Ω) determined by selection of S.tYP .
InL.x
InH.x
phys. quantity
mA/V
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for InL.x andOuL.x and for InH.x and
OuH.x must have the same value.
g
Input scaling changes at calibration level (r page 65) are displayed by input
scaling at parameter setting level. After calibration reset (OFF), the scaling
parameters are reset to default.
5.3.2 Input InP.2
S.tYPInput signalInL.2OuL.2InH.2OuH.2
300 … 20 mA0any20any
310 … 50 mA0any50any
In addition to these settings, InL.2 and InH.2 can be adjusted in the range
(0...20/ 50mA/Ω) determined by selection of S.tYP.
Input scaling648800 process controller
Calibration level
6Calibration level
Measured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1
or 2 is chosen.
The measured value can be matched in the calibration menu ( CAL). Two
methods are available:
Offset correction
( ConF/ InP.1 / Corr =1 ):
possible on-line at the
w
process
display
OuL.1
standard setting
offset correction
new
2-point correction
( ConF/ InP.1 / Corr = 2 ):
w
is possible off-line with
process value simulator
OuL.1old
display
OuH.1
old
OuH.1
new
InL.1
standard setting
2-point correction
X
8800 process controller65
OuL.1
OuL.1old
new
InL.1
InH.1
X
Calibration level
Offset correction ( ConF/ InP.1 / Corr =1 ):
r
1199
°C
°F
1200
para
func
Ada
Err
SP.E
SP.2
r
Ù
3 sec.
r
PArA
Ì
:
CAL
r
Ù
r
InP.1
r
Ù
r
r
r
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration, OuL.1 is equal to InL.1.
The operator can correct the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.
InL.1
OuL.1
End
r
r
È
Ì
Ù
r
Ù
Ù
668800 process controller
2-point correction ( ConF/ InP.1 / Corr = 2):
Ù
1199
°C
°F
1200
para
func
Ada
Err
SP.E
SP.2
r
Ù
3 sec.
r
PArA
r
Ì
ConF
r
Ì
CAL
r
Ù
r
InP.1
È
Ì
InP.2
È
Ì
rr
Ù
InL.1
È
InL1
Ù
OuL.1
InH.1
Calibration level
r
Ù
È
r
Ì
r
Ù
Ù
InP.3
È
È
InH.1
Ù
Ì
OuH.1
End
InL.1: The input value of the lower scaling point is displayed.
The operator must adjust the lower input value by means of a
process value simulator and confirm the input value by pressing key Ù.
OuL.1: The display value of the lower scaling point is displayed.
Before calibration, OuL.1 equals InL.1.
The operator can correct the lower display value by pressing the ÈÌ
keys. Subsequently, he confirms the display value by pressing key Ù.
InH.1: The input value of the upper scaling point is displayed. .
The operator must adjust the upper input value by means of the
process value simulator and confirm the input value by pressing key Ù.
OuH.1: The display value of the upper scaling point is displayed.
Before calibration OuH.1 equals InH.1.
The operator can correct the upper display value by pressing keys ÈÌ
Subsequently, he confirms the display value by pressing key Ù.
È
Ì
r
Ù
g
The parameters (OuL.1, OuH.1) changed at CAL level can be reset by adjusting
the parameters below the lowest adjustment value (OFF) by means of decrement
key Ì .
8800 process controller67
Special functions
7Special functions
7.1 DAC®– motor actuator monitoring
(Digital Actor Control DAC
®
)
With all controllers with position feedback Yp, the motor actuator can be
monitored for functional troubles. The DAC
®
function can be started by chosing
the parameter C.Fnc = 5 or 6at the configuration level ( ConF):
ConF / Cntr / C.Fnc = 53-point-stepping controller with
w
position feedback Yp as potentiometer
ConF / Cntr / C.Fnc = 6Continuous controller with integrated
w
positioner and position feedback Yp as
potentiometer
If an error occurs, the controller switches to manual operation (ò - LED blinks)
and no impulses are given out any longer. If one of the relays switches when a
®
DAC
error occurs, parameter dAC.A = 1 and inverse action O.Act = 1 must
be selected for the relevant output OUT.1 … OUT.4 in the ConF menu
( OUt.3 and 4 only possible if O.tYP = 0 [relay/logic]):
The system detects the following stepping controller errors:
defective motor
w
defective capacitor (wrong rotating direction)
w
wrong phase followers (wrong rotating direction)
w
defective force transmission at spindle or drive
w
excessive backlash due to wear
w
jamming of the control valve e.g. due to foreign body
w
In these cases the controller will change to manual operation and the outputs will
be switched off. Is the controller switched to automatic operation again or any
modification is done the controller activates the DAC function again and the
outputs will be setted.
Resetting of a DAC error:
After solving the technical problem the DAC errror can be acknowledged in the
error list. Thereafter the controller works again in normal operation mode.
See also chapter 3.4 "Mainenance manager / Error list", page 12 ff.
DAC®– motor actuator monitoring688800 process controller
Special functions
Functioning of the DAC function
No input filter should be defined for the Yp input ( PArA / InP.x/t.Fx=0).
Therewith no wrong detection of blocking or wrong method of operation can be
recognized.
The automatic calibration can be used with drives outfitted with spring assembly.
Execution of the calibration:
It is controlled if the mean alteration between two messurements is enough for
the DAC monitoring. The calibration will be stopped if the alteration between
two messurements is too small.
The position of 0% is searched. Therefor the drive will be closed until there is no
changing of the input signal for 0,5 sec.
Assuming that the drive is outfitted with spring assembly, the drive is opened for
2,8 sec. The drive should then still be within the spring assembly. This position is
allocated and stored as 0%.
With the same procedure the position for 100% is allocated and stored.
Simultaneously the motor running time is determined and saved as parameter tt.
Afterwards the controller sets the drive in the position before calibration.
Was the controller in automatic mode before calibration it will be set to automatic
mode again otherwise it remains in manual mode.
g
g
g
The following errors can be occure during calibration:
the change of the Yp input is to small, no monitoring is possible
w
the motion is in wrong direction
w
the Yp input is broken
w
In these cases the automatic calibration will be stopped and the controller remains
in manual mode.
If the automatic calibration leads to no resonable results the calibration of the Yp
input can be done manual.
If the conroller reaches the positions of 0% or 100% the outputs will be switched
off. Also in manual mode it is not possible to exceed these limits.
Because no controller with continuouse output and Yp input is defined there
won't be the DAC function for this controlling type.
8800 process controller69DAC®– motor actuator monitoring
Special functions
7.2 O2measurement
This function is available only on the instrument version with INP3.
As the O
-measurement result range can extend over many decades, automatic
2
display switch-over between“%”and“ppm“ was realized.
The instantaneous unit is displayed in
the lower line.
With set-point changing via keys I or
D, the unit of the set-point and of the
other parameters is displayed.
Lambda probes (λ probes) are used as
sensors.
The electromotive force (in Volts) generated by λ probes is dependent of
instantaneous oxygen content and temperature. Therefore, the 8800 process
controller can only evaluate exact measurement results, if it knows the sensor
temperature.
Distinction of heated and non-heated lambda probes is made. Both can be
evaluated by the 8800 process controller.
Heated lambda probes
Controlled heating which ensures constant temperature is integrated in the heated
λ probe. This temperature must be entered in the 8800 process controller
parameter Probe temperature.
Parameter r Controller r Probe temperature r .....°C (/°F - dependent of
configuration)
Non-heated lambda probes
With the probe always operated at a fixed, known temperature, a procedure as
used for a heated probe can be used.
A non-heated λ probe is used, unless the temperature is constant. In this case, the
probe temperature in addition to the probe mV value must be measured. For this
purpose, any temperature measurement with one of the analog inputs INP2 or
INP3 can be used. During function selection, the input must be set to X2 (second
process value).
7.2.1 Connection
Connect the input for the lambda probe to INP1.
Use terminals A15 and A17.
If necessary, temperature measurement must be connected to INP2 or INP3.
Cntr r tEmPtemp.0...9999
O2measurement708800 process controller
7.2.2 Configuration:
Oxygen measurement
Oxygen measurement with heated lambda probe
Controller r Process value processing r 7: O
temperature
Oxygen measurement with non-heated lambda probe
Controller r Process value processing r O
temperature
Input 1 r Function INP1 r 7: process value X1
InP.1 r1.Fnc7X1-Input
functions with constant probe
2
Cntr r C.tYP7O2-const
functions with measured probe
2
Cntr r C.tYP8O2+temp
Special functions
g
In input 1, the sensor type is set for one of the high-impedance voltage inputs:
Input 1 r Sensor type r 42: special (-25...1150 mV) or
41: special (-2,5...115 mV)
InP.1 rS.tyP41115 mV
InP.1r S.tyP421150 mV
Input 1 r meas. value correction r 0: no correction
InP.1 rS.Lin0no
Temperature measurement (required with non-heated lambda probe)
Any temperature measurement with one of analog inputs INP2 or INP3 can be
used. Select input X2 during function selection (second set-point).
With O2measurement, evaluation in ppm or % must be specified for all
parameters related to the process value.
This is done centrally during configuration.
Other r Parameter unit for O
othrrO20unit : ppm
othrrO21unit : %
r 0: parameter for O2function in ppm
2
1: parameter for O
function in %
2
g
Whether the temperature of the non-heated λ probe is specified in °C or °F can
be selected during configuration.
Other r Unit r 1: in Celsius
2: in Fahrenheit
othrrUnit1°C
othrrUnit2°F
8800 process controller71O2measurement
Special functions
I
7.3 Linearization
Linearization for inputs INP1 or INP3
Access to table “ Lin” is always with selection of sensor type S.TYP = 18:
special thermocouple in INP1 or INP3, or with selection of linearization S.Lin
1: special linearization.
Dependent of input type, the input signals are specified in µV or in Ohm
dependent of input type.
With up to 16 segment points, non-linear signals can be simulated or linearized.
Every segment point comprises an input (In.1 … In.16) and an output (Ou.1
… Ou.16). These segment points are interconnected automatically by means of
straight lines. The straight line between the first two segments is extended
downwards and the straight line between the two largest segments is extended
upwards. I.e. a defined output value is also provided for each input value.
When switching an In.x value to OFF, all other ones are switched off.
Condition for these configuration parameters is an ascending order.
This function is only selectable with 8800/8840 configurator (engineering tool)!
Additions othr (only visible with 8800/8840 configurator!)
NameValue rangeDescriptionDefault
MASt
Cycl
AdrO
AdrU
Numb
0
1
0...200
1...65535
1...65535
0...100
Controller is used as Modbus master
Slave
Master
Cycle time [ms] for the Modbus master to transmit its data
to the bus.
Target address to which the with AdrU specified data is
given out on the bus.
Modbus address of the data that Modbus master gives to
the bus.
Number of data that should be transmitted by the Modbus
master.
The 8800 process controller can be used as Modbus master ( ConF / othr /
MASt = 1 ). The Modbus master sends ist data to all slaves (Broadcast message,
controller adress 0). It transmits its data (modbus adress AdrU) cyclic with the
cycle time Cycl to the bus. The slave controller receives the data transmitted by
the masters and allocates it to the modbus target adress AdrO. If more than one
data should be transmitted by the master controller ( Numb > 1) , the modbus
adress AdrU indicates the start adress of the data that should be transmitted and
AdrO indicates the first target adress where the received data should be stored.
The following data will be stored at the logically following modbus target
adresses.
With this it is possible e.g. to specify the process value of the master controller as
set-point for the slave controllers.
0
60
1
1
0
8800 process controller738800 process controller as Modbus master
8800/8840 configurator
88800/8840 configurator
8800/8840 configurator is the projection environment for thecontroller series of
West. The following 3 versions with graded functionality are available:
FunctionalityMiniBasicExpert
parameter and configuration setting
controller and control loop simulation
download: writes an engineering to the controller
online mode/ visualisation
creation of user defined linearizations
configuration of extended operating level
upload: reads an engineering from the controller
diagnosis function
file, save engineering data
printer function
online documentation, help system
measurement correction (calibration procedure)
program editor
data acquisition and trend function
network and multiuser licence
personal assistant function
extended simulation
yesyesyes
yesyesyes
yesyesyes
SIM onlyyesyes
yesyesyes
yesyesyes
SIM onlyyesyes
nonoyes
noyesyes
noyesyes
yesyesyes
yesyesyes
nonoyes
SIM onlyyesyes
nonoyes
yesyesyes
nonoyes
The mini version is - free of charge - at your disposal as download at West
homepage www.westinstruments.com or on the West-CD (please ask for).
At the end of the installation the licence number has to be stated or DEMO
mode must be chosen. At DEMO mode the licence number can be stated
subsequently under Help r Licence r Change.
90..250V AC, 2 relays + 2xmA/logic4
24VAC / 18..30VDC, 2 relays + 2xmA/logic5
no option0
RS422/485 + U
PROFIBUS-DP + U
INP1 and INP20
INP1, INP2 and INP3 incl. O measuring
Standard configuration0
Configuration to specification9
no manual0
manual germanD
manual englishE
manual frenchF
Standard
UL certifiedU
DIN 3440 certifiedD
Unit/f ront accordingto customer specificationXX
+di2,di3+OUT5,OUT61
T
+ di2/di3 + OUT5/OUT62
T
2
0
1
0
Accessories delivered with the unit
Operating manual (if selected by the ordering code)
Measuring range: 0...50mA AC
Scaling:adjustable -1999...0,000...9999 A
Current measuring range
Technical data as for INP1
Potentiometer
r Table 2 (page 80 )
SUPPLEMENTARY INPUT INP3
(OPTION)
Resolution:> 14 bits
Scanning cycle:100 ms
Technical data as for INP1 except 10V range.
CONTROL INPUTS DI1, DI2
Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.
Switched voltage:5 V
Current:100µA
Current and voltage signals
r Table 3 (page 80 )
Span start, end of span: anywhere within measuring
range
Scaling:selectable -1999...9999
768800 process controller
Technical data
CONTROL INPUTS DI2, DI3 (OPTION)
The digital input di2 located on the A-card and
di2 located on the option card are or-linked.
Configurable as switch or push-button!
Optocoupler input for active triggering.
Nominal voltage24 V DC external
Current sink (IEC 1131 type 1)
Logic “0”-3...5 V
Logic “1”15...30 V
Current requirementapprox.. 5 mA
TRANSMITTER SUPPLY UT (OPTION)
Power:22 mA /≥18 V
If the universal output OUT3 or OUT4 is used
there may be no external galvanic connection
between measuring and output circuits!
GALVANIC ISOLATION
Operating life
(electr.):
Note:
If the relays operate external contactors, these
must be fitted with RC snubber circuits to
manufacturer specifications to prevent
excessive switch-off voltage peaks.
600.000 duty cycles with max.
contact rating
OUT3, 4 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable resolution:11 bits
Current output
0/4...20 mA configurable.
Signal range:0...approx.22mA
Max. load:
Load effect:no effect
Resolution:
Accuracy
Max.contact rating: 500 VA, 250 V, 2A at 48...62 Hz,
resistive load
Min. contact rating: 5V, 10 mA AC/DC
Voltage output
0/2...10V configurable
Signal range:0...11 V
Min. load:
≥ 2k
Ω
Load effect:no effect
Resolution:
Accuracy
11 mV (0,1%)
≤
20 mV (0,2%)
≤
OUT3, 4 used as transmitter supply
Output power:22 mA /≥13 V
OUT3, 4 used as logic output
Load≤500
Load > 500
Ω
Ω
0/≤20 mA
0/> 13 V
OUTPUTS OUT5/6 (OPTION)
Galvanically isolated opto-coupler outputs.
Grounded load: common positive voltage.
Output rating: 18...32 VDC; ≤ 70 mA
Internal voltage drop: ≤ 1 V with I
Protective circuit: built-in against short circuit,
overload, reversed polarity (free-wheel diode
for relay loads).
max
8800 process controller77
Technical data
POWER SUPPLY
Dependent of order:
AC SUPPLY
Voltage:90...260 V AC
Frequency:48...62 Hz
Power consumptionapprox. 7,0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:20,4...26,4 V AC
Frequency:48...62 Hz
DC voltage:18...31 V DC
Power consumption:approx.. 7,0 VA
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM
FRONT INTERFACE
Connection of PC via PC adapter (see
"Accessory equipment"). The 8800/8840
Configurator software is used to configure, set
parameters and operate the 8840 profiler.
Permissible temperatures
For specified
0...60°C
accuracy:
Warm-up time:
≥ 15 minutes
For operation:-20...65°C
For storage:-40...70°C
Humidity
75% yearly average, no condensation
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency:10...150 Hz
Unit in operation:1g or 0,075 mm
Unit not in operation: 2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:15g
Duration:11ms
Electromagnetic compatibility
Complies with EN 61 326-1
(for continuous, non-attended operation)
Resolution (Ô)
0,1 K
0,1 K
0,2 K
0,2 K
0,2 K
0,2 K
0,05 K
0,4 K
0,4 K
0,1 K
0,3 K
Resolution (Ô)
Pt100
Pt100-200...850°C-140...1562°F
Pt1000-200...850°C-140...392°F
KTY 11-6 *-50...150°C-58...302°F
Spezial0...4500
Spezial0...450
Poti0...160
Poti0...450
Poti0...1600
Poti0...4500
* Or special
0,2mA
-200...100°C-140...212°F
ß 1K
ß 1K
ß 2K
ß 2K
ß 0,02 %
Table 3 Current and voltage measuring ranges
Measuring rangeInput impedanceAccuracy
0-10 Volt
-2,5-115 mV
~ 110 kΩ
? 1MΩß 0,1 %
ß 0,1 %0,6 mV
0,1K
0,1K
0,1K
0,05K
0,01 %
Resolution (Ô)
6 µV
-25-1150 mV
0-20 mA
? 1MΩß 0,1 %
20 Ω
ß 0,1 %
808800 process controller
60 µV
1,5 µA
Safety hints
11Safety hints
This unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 and
was delivered in safe condition.
The unit complies with European guideline 89/336/EWG (EMC) and is provided
with CE marking.
The unit was tested before delivery and has passed the tests required by the test
schedule. To maintain this condition and to ensure safe operation, the user must
follow the hints and warnings given in this operating manual.
The unit is intended exclusively for use as a measurement and control instrument
in technical installations.
a
Warning
If the unit is damaged to an extent that safe operation seems impossible, the unit
must not be taken into operation.
ELECTRICAL CONNECTIONS
The electrical wiring must conform to local standards (e.g. VDE 0100). The input
measurement and control leads must be kept separate from signal and power
supply leads.
In the installation of the controller a switch or a circuit-breaker must be used and
signified. The switch or circuit-breaker must be installed near by the controller
and the user must have easy access to the controller.
COMMISSIONING
Before instrument switch-on, check that the following information is taken into
account:
Ensure that the supply voltage corresponds to the specifications on the type
w
label.
All covers required for contact protection must be fitted.
w
If the controller is connected with other units in the same signal loop, check
w
that the equipment in the output circuit is not affected before switch-on. If
necessary, suitable protective measures must be taken.
The unit may be operated only in installed condition.
w
Before and during operation, the temperature restrictions specified for
w
controller operation must be met.
SHUT-DOWN
For taking the unit out of operation, disconnect it from all voltage sources and
protect it against accidental operation.
If the controller is connected with other equipment in the same signal loop, check
that other equipment in the output circuit is not affected before switch-off. If
necessary, suitable protective measures must be taken.
8800 process controller81
Safety hints
MAINTENANCE, REPAIR AND MODIFICATION
The units do not need particular maintenance.
a
l
a
Warning
When opening the units, or when removing covers or components, live parts and
terminals may be exposed.
Before starting this work, the unit must be disconnected completely.
After completing this work, re-shut the unit and re-fit all covers and components.
Check if specifications on the type label must be changed and correct them, if
necessary.
Caution
When opening the units, components which are sensitive to electrostatic
discharge (ESD) can be exposed. The following work may be done only at
workstations with suitable ESD protection.
Modification, maintenance and repair work may be done only by trained and
authorized personnel. For this purpose, the West service should be contacted.
The cleaning of the front of the controller should be done with a dry or a wetted
(spirit, water) kerchief.
11.1 Resetting to factory setting
In case of faulty configuration, 8800 process controller can be reset to the default
condition.
For this, keep the following two keys pressed during power-on :
Controller reset to default is signalled by displayingFACTory shortly in the
display. Subsequently, the controller returns to normal operation.
FAC
torY
ÈÌ
Resetting to factory setting828800 process controller
12Notes
Notes
8800 process controller83
Notes
848800 process controller
Notes
8800 process controller85
Index
0-9
2-point correction............67
A
Alarm handling ..........28-29
Digital inputs di1, di2, di3
Configuration ..........44
Technical data ..........78
E
Environmental conditions .......81
Equipment ...............77
Error list ................15
B
Bargraph ................12
Bus interface
Technical Data..........81
C
Calibration level (CAL)......67-69
Certifications ..............82
Configuration examples
2-point controller ........55
3-point controller ........56
3-point stepping controller . . . 57
Continuous controller ......58
D - Y -Off controller.......59
Measured value output .....60
Signaller .............54
Configuration level
Configuration parameters. . 32 - 49
Parameter survey ........31
Connecting diagram ...........7
Connecting examples
di2/3, 2-wire transmitter supply . 9
INP2 current transformer .....8
OUT1/2 heating/cooling .....8
OUT3 as logic output ......11
OUT3 transmitter supply ....10
RS485 interface .........10
Control inputs di1, di2, di3
Technical data ..........78
Cooling functions
Constant period .........53
Standard .............51
Water cooling non-linear ....52
Current signal measuring range ....78
F
Front view ...............12
I
Input INP1
Configuration ..........33
Parameters ............64
Technical data ..........78
Input INP2
Configuration ..........35
Parameters ............64
Technical data ..........78
Input INP3
Configuration ..........35
Parameters ............65
Technical data ..........78
Input scaling ..............66
L
LED
Ada-LED............12
Err-LED............12
func-LED............12
ì -LED.............12
LED colours ...........12
ò -LED.............12
para-LED............12
SP.2-LED............12
SP.E-LED ...........12
Linearisierung .............74
M
Mainenance manager .......15-17
Manual tuning .............26
Modbus master .............75
Mounting.................6
D
DAC................70-71
8800 process controller86
N
Notes................86-87
O
O2-Messung ..............72
Offset correction ............67
Optimierung am Sollwert .......20
Output OUT1
Configuration ..........39
Technical data ..........79
Output OUT2
Configuration ..........40
Technical data ..........79
Output OUT3
Configuration ..........41
Technical data ..........79
Output OUT4
Configuration ..........42
Technical data ..........79
Output OUT5
Configuration ..........44
Technical data ..........80
Output OUT6
Configuration ..........44
Technical data ..........80
V
Versions ................77
Voltage signal measuring range ....78
P
Parameter setting level
Parameter survey ........62
Parameters .........63-65
Parameter Sollwertgradient ......64
R
Resetting to factory setting .......85
Resistance thermometer measuring range
.....................78
S
Safety hints ............84-85
Safety switch...............6
Safety test................81
Sauerstoffmessung ...........72
Self-tuning
Cancelation ...........23
Cancelation causes........24
Set-point processing ..........50
T
Thermocouple measuring range ....78
8800 process controller87
Subject to alterations without notice
West Instruments
The Hyde Business Park
Brighton
BN2 4JU
UK
Printed in Germany 9499-040-70611 (08/2003)
A6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.