West Control Solutions N8100 User Manual

1
-DIN,
4
1
-DIN &
8
1
-DIN
16
TEMPERATURE CONTROLLERS
59125-3

PREFACE

This manual comprises two volumes:
Volume 1: This supports normal operation of the
1
-DIN,
4
1
-DIN and
8
1
16
-DIN Temperature Controllers. In normal operation, all actions taken by the user are to be in front of the panel.
Volume 2: This supports the installation, commissioning and configuring of
the
1
-DIN,
4
1
-DIN and
8
1
-DIN Temperature Controllers. It is
16
intended for use only by personnel who are trained, equipped and authorised to carry out these functions.
59125
1
-DIN,
4
1
-DIN &
8
1
1 6
-DIN
TEMPERATURE CONTROLLERS
PRODUCT MANUAL
VOLUME 1
OPERATING INSTRUCTIONS
In normal operation, the operator must not remove the Controller from its housing or have unrestricted access to the rear terminals, as this would provide potential contact with hazardous live parts.
Installation and configuration must be undertaken by technically-competent servicing personnel. This is covered in Volume 2 of this manual.
Contents - Volume 1
1 OPERATOR MODE 1-1
1.1 INTRODUCTION 1-1
1.2 DISPLAYS AVAILABLE 1-2
1.3 ADJUSTING THE SETPOINT/SETPOINT RAMP RATE 1-3
1.4 ALARM STATUS DISPLAY 1-3
1.5 OVER-RANGE/UNDER-RANGE DISPLAYS 1-4
1.6 SENSOR BREAK INDICATION 1-4
1.7 MANUAL CONTROL MODE 1-4
1.8 PRE-TUNE FACILITY 1-5
1.9 SELF-TUNE FACILITY 1-6
1.10 VIEWING THE HARDWARE DEFINITION CODE 1-7
O054-V1 (iii)
59125
2 SET UP MODE 2-1
2.1 ENTRY INTO SET UP MODE 2-1
2.2 SET UP MODE PARAMETERS 2-2
2.3 OPERATOR MODE DISPLAYS 2-13
2.4 TUNING THE CONTROLLER MANUALLY 2-13
2.5 SELF-TUNE AND PRE-TUNE FACILITIES 2-14
2.6 EXIT FROM SET UP MODE 2-15
3 RS485 SERIAL COMMUNICATIONS 3-1
3.1 COMMUNICATIONS ENABLE/DISABLE 3-1
3.2 PHYSICAL REQUIREMENTS 3-1
3.3 INDIVIDUAL PARAMETERS 3-5
3.4 ERROR RESPONSE 3-10
(iv ) O054-V1
59125

1 OPERATOR MODE

1.1 INTRODUCTION

This Section covers the routine operation of the Controller, once it has been installed and configured as described in Volume 2 of this manual. The Controller front panel indicators and keys are shown in Figure 1-1.
Figure 1-1 Front Panel Controls and Indicators
O054-1 1-1
59125

1.2 DISPLAYS AVAILABLE

After the Controller has performed its power-up self-test (during which, if the Function key is held down during power-up, the current Controller firmware revision is displayed), the initial displays appear. The available displays are dependent upon (a) whether the Controller has been configured for Single Setpoint operation or Dual Setpoint operation and (b) the setting of the Setpoint Strategy parameter in Set Up Mode.
1.2.1 Single Setpoint Operation
In single setpoint operation, the available displays are:
1 -2 O054-1
59125
1.2.2 Dual Setpoint Operation
In dual setpoint operation, the available displays are:

1.3 ADJUSTING THE SETPOINT/SETPOINT RAMP RATE

The setpoint/setpoint ramp rate (whichever is selected - see previously) may be adjusted using the Raise/Lower keys. The ramp rate may be adkusted in the range 1 to 9999. Any attempt to increase the ramp rate value beyond 9999 will cause the upper display to go blank and setpoint ramping to be switched OFF. Setpoint ramping can be resumed by decreasing the ramp rate value to 9999 or less.

1.4 ALARM STATUS DISPLAY

If one or more of the Controller’s alarms is (are) active, the alarm status display is included in the available display sequence. The Alarm Status display is selected by depressing the Function key repeatedly until the display appears (see Figure 1-2).
O054-1 1-3
Figure 1 -2 Alarm Status Display

1.5 OVER-RANGE/UNDER-RANGE DISPLAYS

59125
The upper display will indicate if the process variable is higher than the input scale maximum limit (over-range), or lower than the input scale minimum limit (under-range) as shown on the right.

1.6 SENSOR BREAK INDICATION

If a break is detected in the sensor circuit, the upper display shows:
The reaction of the outputs and alarms to a detected sensor break is dependent upon the input type and is defined in Appendix A.

1.7 MANUAL CONTROL MODE

If selection of Manual Control Mode is enabled, the Manual Control Mode may
be entered (via a bumpless transfer) by depressing the Auto/Manual key. The SET
indicator will then flash continuously whilst the Controller is in Manual Control Mode. The output power will then be displayed and may be adjusted with the Raise/Lower keys.A return can be made to Automatic Control Mode (via a bumpless transfer) by simply depressing the Auto/Manual key again, which causes the usual process variable display to appear.
1 -4 O054-1
59125

1.8 PRE-TUNE FACILITY

This facility may be used to set the Controller’s PID parameters to values which are approximately correct, in order to provide a base from which the Self-Tune facility may subsequently optimise tuning. Pre-Tune may be engaged (and subsequently dis-engaged) as follows:
NOTE: The Pre-Tune facility will not engage if (a) the setpoint is currently ramping, (b) the process variable is within 5% of input span of the setpoint, or (c) an erroneous key sequence is used.
O054-1 1-5
59125
Since Pre-Tune is a single-shot operation, it will automatically dis-engage itself once the operation is complete.

1.9 SELF-TUNE FACILITY

This facility is be used to optimise tuning whilst the Controller is operating. Self-Tune may be activated as follows:
1-6 O054-1
59125

1.10 VIEWING THE HARDWARE DEFINITION CODE

Figure 1 -3 Viewing the Hardware Definition Code
NOTE: An automatic return is made to the normal Operator Mode display after 30 seconds.
The Hardware Definition Code has the following significance:
Value 0 1 2 3 4 5 7 8
Input RTD/
Linear DC (mV)
Output
1
Output 2Not
fitted
Output 3Not
fitted
Relay SSR
Relay SSR
Relay SSR
Thermo-
couple
DriveDC(0 - 10V)DC(0 - 20mA)DC(0 - 5V)DC(4 - 20mA)
DriveDC(0 - 10V)DC(0 - 20mA)DC(0 - 5V)DC(4 - 20mA)
DriveDC(0 - 10V)DC(0 - 20mA)DC(0 - 5V)DC(4 - 20mA)
Linear
DC (mA)
Linear DC
(V)
Solid State
Solid State
Solid State
O054-1 1-7

2 SET UP MODE

2.1 ENTRY INTO SET UP MODE

See Figure 2-1.
59125
Figure 2-1 Entry into Set Up Mode
2-1 O054-2
59125
NOTE: If, on entry into Set Up Mode, the upper display initially shows all decimal point positions illuminated), this indicates that one or more of the critical configuration parameters - typically input range or output use/type - have been altered in value/setting and, as a consequence, all Set Up Mode parameters have been automatically set to their default values/settings. To clear this display, simply alter the value/setting of any Set Up Mode parameter (see below).

2.2 SET UP MODE PARAMETERS

The parameter sequence for view/adjustment in Set Up Mode is shown in Table 2 -1 . Use the Function key to step through the parameters. In each case, the legend will be shown in the lower display and the current value/setting will be shown in the upper display. The value/setting may be altered using the Raise/Lower keys. A detailed description of each of these parameters is given in the following Subsections.
2.2.1 Input Filter Time Constant
The Controller input is equipped with a digital filter which is used to filter out any extraneous impulses on the process variable. This filtered PV is used for all PV-dependent functions (control, alarms etc.).
CAUTION: If this parameter value is set excessively high, the control quality may be significantly impaired. The value chosen should be sufficiently large to attenuate stray noise on the process variable signal but no larger.
2.2.2 Process Variable Offset
This parameter is used to modify the actual process variable value (measured at the Controller’s input terminals) in the following manner:
Offset PV value = Actual PV value + Process Variable Offset value.
For Controllers fitted with a linear input, the displayed process variable value is limited by Scale Range Maximum (see Subsection 2.2.30) and Scale Range Minimum (see Subsection 2.2.31). The offset process variable value is used for all PV-dependent functions (control, display, alarm, recorder output etc.).
NOTE: This parameter value should be chosen with care. Any adjustment to this parameter is, in effect, a calibration adjustment. Injudicious application of values to this parameter could lead to the displayed process variable value bearing no meaningful relationship to the actual process variable value. There is no front
panel indication when this parameter is in effect (i.e. has been set to a non-zero value).
O054-2 2-2
Table 2 -1 Set Up Mode Parameters
Parameter Legend Adjustment Range Default Value
59125
Digital Filter Time Constant OFF, 0.5 to 100.0 secs. In
2.0 seconds
0.5 sec. increments
Process Variable Offset
Span of Controller 0
±
Output Power 0 to 100% Read only
Output Power 2
Proportional Band 1 0.0 (ON/OFF control) to
5
0 to 100% Read only
10.0%
999.9% of input span
Proportional Band 2
15,
0.0 (ON/OFF control) to
10.0%
999.9% of input span
Reset (Integral Time Const.)
Rate (Derivative Time Const.)
Overlap/Deadband
15,
1
1
1s to 99m 59s and OFF 5m 00s
00s to 99m 59s 1m 15s
-20% to +20% (of
0% Proportional Band 1 + Proportional Band 2)
Manual Reset (Bias)
1
0% to 100% (Output 1 only)
25%
-100% to +100% (Output 1 & Output 2)
ON/OFF Differential
2
0.1% to 10.0% of input span 0.5%
Output 1 only
Output 2 only
Output 3 only
5
5
Setpoint High Limit Setpoint to Range Maximum Range Maximum
Setpoint Low Limit Range Minimum to Setpoint Range Minimum
Recorder Output Scale Max. -1999 to 9999 Range Maximum
Recorder Output Scale Min. -1999 to 9999 Range Minimum
Output 1 Power Limit
Output 1 Cycle Time 0.5, 1, 2, 4, 8, 16, 32, 64,
1
0% to 100% of full power 100%
32 secs. 128, 256 or 512 secs.
Output 2 Cycle Time 0.5, 1, 2, 4, 8, 16, 32, 64,
32 secs. 128, 256 or 512 secs.
Process High Alarm 1 value
Process Low Alarm 1 value
Band Alarm 1 value
3
Deviation Alarm 1 value
Process High Alarm 2 value
Process Low Alarm 2 value
Band Alarm 2 value
3
Deviation Alarm 2 value
3
3
Range Min. To Range Max. Range Max.
Range Min. To Range Max. Range Min.
0 to span from Limit SP 5 units
3
3
3
±Span from Limit SP 5 units
Range Min. To Range Max. Range Max.
Range Min. To Range Max. Range Min.
0 to span from Limit SP 5 units
3
±Span from Limit SP 5 units
2-3 O054-2
59125
Table 2 -1 Set Up Mode Parameters (cont.)
Parameter Legend Adjustment Range Default Value
Loop Alarm Enable 0 (Disabled) or 1 (Enabled) 0
Loop Alarm Time
Scale Range Decimal Point
Scale Range Maximum
Scale Range Minimum
Auto Pre-Tune Enable/Disable 0 (Disabled) or 1 (Enabled) 0
6
4
4
4
1s to 99m 59s 99m 59s
0, 1, 2 or 3 1
-1999 to 9999 1000
-1999 to 9999 0000
Manual Control
0 (Disabled) or 1 (Enabled) 0
Enable/Disable
Setpoint Ramp Enable/Disable 0 (Disabled) or 1 (Enabled) 0
Setpoint Strategy 1, 2, 3, 4 or 5 1
Communications Enable
8
0 (Disabled) or 1 (Enabled) 1 (Enabled)
Lock Code 0 to 9999 10
Operator Mode Displays (still accessible in Set Up Mode):
Process Variable Read Only -
Setpoint
10
Setpoint Low Limit to Setpoint
Setpoint Low Limit High Limit
Ramping Setpoint value
Setpoint Ramp Rate
Alarm Status Read Only (see Subsection
7
9
Read only
1 to 9999 and OFF OFF (blank)
-
1.3)
O054-2 2-4
59125
2.2.3 Output Power 1
This parameter is the current Output 1 power level. It is a “Read Only” parameter and is not adjustable.
2.2.4 Output Power 2
This parameter is the current Output 2 power level (if Output 2 is fitted). It is a “Read Only” parameter and is not adjustable. If Output 2 is not fitted, this parameter display is not applicable.
2.2.5 Proportional Band 1
This parameter is the portion of the input span of the Controller over which the Output 1 power level is proportional to the displayed process variable value. The function of the Proportional Band 1 is illustrated in Figure 2 -2 .
2.2.6 Proportional Band 2
This parameter is the portion of the input span of the Controller over which the Output 2 power level is proportional to the displayed process variable value. In Figure 2-2 , Proportional Band 2 is shown (a) with a non-zero value (Case 1 and Case 2) - PID control, and (b) with a zero value (Case 3) - ON/OFF control.
2.2.7 Reset ( Integral Time Constant)
This parameter is not applicable if Proportional Band 1 (see Subsection 2.2.5 ) is set to 0 (ON/OFF control).
2.2.8 Rate ( Derivative Time Constant)
This parameter is not applicable if Proportional Band 1 (see Subsection 2.2.5 ) is set to 0 (ON/OFF control).
2.2.9 O verlap/Deadband
This defines the portion of the Proportional Band (Proportional Band 1 + Proportional Band 2) over which both outputs are active (or, in the case of a deadband, neither output is active). The function of the overlap/deadband is illustrated in Figure 2 - 2 . This parameter is not applicable if Proportional Band 1 = 0 or if Output 2 is not fitted. Note that, with Output 2 set to ON/OFF control (Figure 2-2 Case 3), the Overlap/Deadband parameter has the effect of moving the ON Differential band of Output 2 to create an overlap (positive values) or a deadband (negative values). When Overlap/Deadband = 0, the “Output 2 OFF” edge of the Output 2 ON/OFF Differential band coincides with the point at which Output 1 reaches 0%.
2-5 O054-2
59125
Figure 2-2 Proportional Band and Deadband/Overlap
O054-2 2-6
59125
2.2.10 Bias (Manual Reset)
This bias to the output power is expressed as a percentage of output power. This parameter is not applicable if Proportional Band 1 = 0.
2.2.11 ON/OFF Differential
This is a switching differential used when one or both outputs have been set to ON/OFF control (i.e. Proportional Band 1 or Proportional Band 2 or both = 0).
2.2.12 Setpoint High Limit
This is the maximum limit for setpoint adjustment. It should be set to a value which prevents the setpoint being given a value which will cause damage to the process being controlled.
2.2.13 Setpoint Low Limit
This is the minimum limit for setpoint adjustment. It should be set to a value which prevents the setpoint being given a value which will cause damage to the process being controlled.
2.2.14 Recorder Output Scale Maximum
This parameter defines the value of process variable or setpoint (whichever is applicable) at which the Recorder Output reaches its maximum value; for example, for a 0 - 5V Recorder Output, this value corresponds to 5V. The decimal point position for the Recorder Output is always the same as that for the process variable input range. This parameter is not applicable if the Recorder Output option is not fitted.
NOTE: If this parameter is set to a value less than that for the Recorder Output Scale Minimum (see Subsection 2.2.15 ), the relationship between the process variable/setpoint value and the Recorder Output is reversed.
2.2.15 Recorder Output Scale Minimum
This parameter defines the value of the process variable or setpoint (whichever is applicable) at which the Recorder Output reaches its minimum value; for example, for a 0 - 5V Recorder Output, this value corresponds to 0V. The decimal point position for the Recorder Output is always the same as that for the process variable input range. This parameter is not applicable if the Recorder Output option is not fitted.
NOTE: If this parameter is set to a value greater than that for the Recorder Output Scale Maximum (see Subsection 2.2.14 ), the relationship between the process variable value and the Recorder Output is reversed.
2 -7 O054-2
59125
2.2.16 Output 1 Power Limit
This parameter is used to limit the power level of Output 1 and may be used to protect the process being controlled. If no protection is required, this parameter may be set to 100%. IThis parameter is not applicable if Proportional Band 1 is set to 0.
2.2.17 Output 1 Cycle Time
The cycle time value required is dependent upon the process being controlled and the type of output being used for Output 1. For a Relay Output, the cycle time should be as large as possible (whilst remaining compatible with the process control requirements) in order to maximise relay life. For an SSR Output, the cycle time may have a lower value (and thus satisfy the requirements of a fast-changing process variable e.g. flow or pressure). This parameter is not applicable if Proportional Band 1 is set to 0 or if Output 1 is a DC linear output..
2.2.18 Output 2 Cycle Time
The cycle time value required is dependent upon the process being controlled and the type of output being used for Output 2. For a Relay Output, the cycle time should be as large as possible (whilst remaining compatible with the process control requirements) in order to maximise relay life. For an SSR Output, the cycle time may have a lower value (and thus satisfy the requirements of a fast-changing process variable e.g. flow or pressure). This parameter is not applicable if Proportional Band 1 or Proportional Band 2 is set to 0 or if Output 2 is a DC linear output.
2.2.19 Process High Alarm 1 Value
This parameter, applicable only when Alarm 1 is selected to be a Process High alarm, defines the process variable value at or above which Alarm 1 will be active. The operation of a process high alarm is illustrated in Figure 2-3.
2.2.20 Process Low Alarm 1 Value
This parameter, applicable only when Alarm 1 is selected to be a Process Low alarm, defines the process variable value at or below which Alarm 1 will be active. The operation of a process low alarm is illustrated in Figure 2-3.
2.2.21 Band Alarm 1 Value
This parameter, applicable only if Alarm 1 is selected to be a Band Alarm, defines a band of process variable values, centred on the setpoint value. If the process variable value is outside this band, the alarm will be active. The operation of a band alarm is illustrated in Figure 2-3.
O054-2 2-8
59125
Figure 2-3 Alarm Operation
2-9 O054-2
59125
2.2.22 Deviation (High/Low) Alarm 1 Value
This parameter, applicable only if Alarm 1 is selected to be a Deviation High/Low Alarm, defines a value above (positive value - Deviation High alarm) or below (negative value - Deviation Low alarm) the setpoint; if the process variable deviates from the setpoint by a margin greater than that defined by this parameter, Alarm 1 goes active. The operation of Deviation Alarms is illustrated in Figure 2-3.
2.2.23 Process High Alarm 2 Value
This parameter, applicable only when Alarm 2 is selected to be a Process High alarm, defines the process variable value at or above which Alarm 2 will be active. The operation of a process high alarm is illustrated in Figure 2-3.
2.2.24 Process Low Alarm 2 Value
This parameter, applicable only when Alarm 2 is selected to be a Process Low alarm, defines the process variable value at or below which Alarm 2 will be active. The operation of a process low alarm is illustrated in Figure 2-3.
2.2.25 Band Alarm 2 Value
This parameter, applicable only if Alarm 2 is selected to be a Band Alarm, defines a band of process variable values, centred on the setpoint value. If the process variable value is outside this band, the alarm will be active. The operation of a band alarm is illustrated in Figure 2-3.
2.2.26 Deviation (High/Low) Alarm 2 Value
This parameter, applicable only if Alarm 2 is selected to be a Deviation High/Low Alarm, defines a value above (positive value - Deviation High alarm) or below (negative value - Deviation Low alarm) the setpoint; if the process variable deviates from the setpoint by a margin greater than that defined by this parameter, Alarm 2 goes active. The operation of Deviation Alarms is illustrated in Figure 2-3.
2.2.27 Loop Alarm Enable
This parameter is the means by which the user can enable or disable the Loop Alarm. The Loop Alarm is a special alarm which detects faults in the control feedback loop by continuously monitoring process variable response to the control output(s).
The Loop Alarm facility, when enabled, repeatedly checks the control output(s) for saturation i.e. either or both outputs being at the maximum or minimum limit. If an output is found to be in saturation, the Loop Alarm facility starts a timer; thereafter,
O054-2 2-10
59125
if the saturated output has not caused the process variable to be corrected by a pre-determined amount V after a time T has elapsed, the Loop Alarm goes active. Subsequently, the Loop Alarm facility repeatedly checks the process variable and the control output(s). When the process variable starts to change value in the correct sense or when the saturated output comes out of saturation, the Loop Alarm is de-activated.
For PID control, the Loop Alarm Time T is always set to twice the value of the Reset (Integral Time Constant) parameter. For On/Off control, the user-defined value of the Loop Alarm Time Set Up parameter (see Subsection 2.2.28) is used.
The value of V is dependent upon the input type:
°C ranges: C or 2.0 °C °F ranges: F or 3.0 °F
Linear ranges: 10 least significant display units
For single output Controllers, the saturation limits are 0% and Out1Max%. For dual output Controllers, the saturation limits are –100% and Out1Max%.
NOTES
1. Correct operation of the Loop Alarm depends upon reasonably accurate PID tuning.
2. The Loop Alarm is automatically disabled during Manual Control Mode and during execution of the Pre-Tune facility. Upon exit from Manual Control Mode or after completion of the Pre-Tune routine, the Loop Alarm is automatically re-enabled.
2.2.28 Loop Alarm Time
When full ON/OFF control is selected (i.e. Proportional Band 1 is set to 0) and Loop Alarm is enabled, this parameter determines the duration of the saturation condition after which the Loop Alarm will be activated. This parameter is omitted from the Set Up display sequence if ON/OFF control is not selected or Loop Alarm is disabled.
2.2.29 Scale Range Decimal
Value Decimal Point Position
Point
0 xxxx
This parameter, applicable only if a linear input is fitted, defines the position of the decimal point in values of the process variable, setpoint, alarm levels and recorder outputs as shown on the right.
2 -11 O054-2
1 xxx.x
2 xx.xx
3 x .xxx
59125
2.2.30 Scale Range Maximum
This parameter, applicable only if a linear input is fitted, defines the scaled input value when the process variable input hardware is at its maximum value. This parameter can be set to a value less than (but not equal to) Scale Range Minimum, in which case the sense of the input is reversed. Decimal point position is defined by the Scale Range Decimal Point parameter (see Subsection 2.2.29 ).
2.2.31 Scale Range Minimum
This parameter, applicable only if a linear input is fitted, defines the scaled input value when the process variable input hardware is at its minimum value. This parameter can be set to a value greater than (but not equal to) Scale Range Maximum, in which case the sense of the input is reversed. Decimal point position is defined by the Scale Range Decimal Point parameter (see Subsection 2.2.29 ).
2.2.32 Auto Pre-Tune Enable/Disable
This parameter determines whether or not the Controller’s Pre-Tune facility is activated automatically on power-up or not.
2.2.33 Manual Control Enable/Disable
This parameter determines whether operator selection of manual control is enabled or disabled.
2.2.34 Setpoint Ramp Enable/Disable
This parameter enables/disables use of the setpoint ramping feature at user level.
2.2.35 Setpoint Strategy
This parameter enables the user to select the required Operator Mode setpoint display strategy - see Subsections 1.2.1 (Single Setpoint operation) and 1.2.2 (Dual Setpoint operation).
2.2.36 Communications Enable/Disable
This parameter enables/disables Write operations (i.e. the changing of parameter values/settings) via the RS485 communications link, if the Communications Option PCB is fitted. Parameters can be interrogated via the link, regardless of the setting of this parameter.
2.2.37 Lock Value
This parameter defines the four-digit code required to enter Set Up Mode.
O054-2 2-12
59125

2.3 OPERATOR MODE DISPLAYS

Once the complete cycle of Set Up Mode parameters has been displayed, the user may then step through the Operator Mode displays (see Subsection 1.2), making adjustments where required, before re-starting the Set Up Mode parameter cycle, as shown in Table 2-1.

2.4 TUNING THE CONTROLLER MANUALLY

2.4.1 Controllers Fitted with Output 1 Only
Before starting to tune the Controller to the load, check that the Setpoint High and
Low Limits (SPhi and SPLo) are set to safe levels - see Subsections 2.2.12 and
2.2.13 .
The following simple technique may be used to determine values for proportional
band (Pb1), derivative time constant (rAtE) and integral time constant (rSEt).
NOTE: This technique is suitable only for processes which are not harmed by large fluctuations in the process variable. It provides an acceptable basis from which to start fine tuning for a wide range of processes.
1. Set the setpoint to the normal operating process value (or to a lower value if overshoot beyond this value is likely to cause damage).
2. Select ON/OFF Control (i.e. set Pb1 = 0).
3. Switch on the process. The process variable will oscillate about the setpoint. Note (a) The peak-to-peak variation (P) of the first cycle i.e. the difference between the highest value of the first overshoot and the lowest value of the first undershoot, and (b)tThe cycle time (T) of this oscillation in minutes (see Figure 2-4)
4. The control parameters should then be set as follows:
=
= T minutes
P
x 100
ScaleRange
T
=
minutes
6
NOTE: After setting up the parameters, set the Controller to Operator Mode (see Subsection 2.6) to prevent unauthorised adjustment to the values.
2 -13 O054-2
59125
Figure 2 -4 Manual Tuning Parameters - Output 1 only
2.4.2 Controllers Fitted with Output 1 and Output 2
Before starting to tune the Controller to the load, check that the Setpoint High and
Low Limits (SPhi and SPLo) are set to safe levels - see Subsections 2.2.12 and
2.2.13 .
The following simple technique may be used to determine values for proportional
band (Pb1), derivative time constant (rAtE) and integral time constant (rSEt).
NOTE: This technique is suitable only for processes which are not harmed by large fluctuations in the process variable. It provides an acceptable basis from which to start fine tuning for a wide range of processes.
1. Tune the Controller using Output 1 only as described in Subsection 2.4.1.
2. Set Pb2 to the same value as Pb1 and monitor the operation of the
Controller in dual output mode. If there is a tendency to oscillate as control
passes into the Output 2 proportional band, increase the value of Pb2. If
the process appears to be over-damped in the region of the Output 2
proportional band, decrease the value of Pb2.
3. When values of proportional bands, integral time constant and derivative time constant have been determined for tuning, if there is a “kick” as
control passes from one output to the other, set OL to a positive value to introduce some overlap. Adjust the value of OL by trial and error until
satisfied.

2.5 SELF-TUNE AND PRE-TUNE FACILITIES

Once the Controller has been manually tuned, the Self-Tune and Pre-Tune facilities may be used in Operator Mode to enhance further the response of the Controller (see Subsections 1.9 and 1.8 respectively).
O054-2 2-14
59125

2.6 EXIT FROM SET UP MODE

To leave Set Up Mode, select the initial Operator Mode display (normally process variable) then depress the Raise and Function keys simultaneously, whereupon the Controller will return to Operator Mode. NOTE: An automatic return to Operator mode will be executed if there is no key activity in Set Up Mode for two minutes.
2-15 O054-2
59125

3 RS485 SERIAL COMMUNICATIONS

The Controller may be equipped with a two-wire RS485-compatible serial communications facility, by which means communication may occur between the Controller and a master device (e.g. a computer or terminal).

3.1 COMMUNICATIONS ENABLE/DISABLE

When Communications are enabled (in Set Up Mode - see Subsection 2.2.36), the Controller parameters may be adjusted by the master device via the serial communications link. If communications are disabled, the Controller will not adjust or change any parameters in response to commands received from the master device and will send a negative acknowledgement in response to such commands. Whether communications are enabled or disabled, the Controller will return the requested information in response to a Type 2 Interrogation message (see Subsection 3.2.5 ) from the master device.

3.2 PHYSICAL REQUIREMENTS

3.2.1 Character Transmission
Data format is fixed to be even parity, seven data bits and one stop bit. The Baud rate may be selected to be 1200, 2400, 4800 (default) or 9600 Baud.
3.2.2 Line Turn-Round
The communications link is operated as a multi-drop half duplex system. When a device is transmitting, it drives the transmission lines to the appropriate levels; when it is not transmitting, its outputs are set to a high impedance in order that another device can transmit. It is important that a transmitter releases the transmission lines before another device starts transmission. This imposes the following restraints on the master device:
(a) The transmitter must release the transmission lines within 6ms of the end of the last character of a message being transmitted. Note that delays due to buffers such as those used in universal asynchronous receivers/trans-mitters (UARTs) within the master device must be taken into account.
(b) The transmitter must not start transmission until 6ms has elapsed since the reception of the last character of a message.
All Controllers in this range having an RS485 communications facility adhere to this standard; thus, provided that the master device conforms similarly to the standard, there should be no line contention problems.
O054-3 3-1
59125
3.2.3 Communications Protocol
The protocol assumes half duplex communications. All communication is initiated by the master device. The master sends a command or query to the addressed slave and the slave replies with an acknowledgement of the command or the reply to the query. All messages, in either direction, comprise:
(a) A Start of Message character (b) One or two address characters (uniquely defining the slave) (c) A parameter/data character string (d) An End of Message character
Messages from the master device may be one of four types:
Type 1: L {N} ? ? * Type 2: L {N} {P} {C} * Type 3: L {N} {P} # {DATA} * Type 4: L {N} {P} I *
Table 3 -1 {DATA} Element - Sign
and Decimal Point
where all characters are in ASCII code and:
L is the Start of Message
character (Hex 4C)
{N} is the slave Controller
address (in the range 1 -
32); addresses 1 - 9 may be
{DATA} Content Sign/Decimal Point
abcd0 +abcd
abcd1 +abc.d
abcd2 +ab.cd
abcd3 +a.bcd
abcd5 -abcd
abcd6 -abc.d
represented by a single digit (e.g. 7) or in two-digit form, the first digit being zero (e.g.
abcd7 -ab.cd
abcd8 -a.bcd
07).
{P} is a character which identifies the parameter to be
interrogated/modified.
{C} is the command (see below)
# indicates that {DATA} is to follow (Hex 23)
{DATA} is a string of numerical data in ASCII code (see Table 3 -1 )
* is the End of Message character (Hex 2A)
No space characters are permitted in messages. Any syntax errors in a received message will cause the slave controller to issue no reply and await the Start of Message character.
3-2 O054-3
59125
3.2.4 Type 1 Message
L {N} ? ? *
This message is used by the master device to determine whether the addressed slave Controller is active. The reply from the slave Controller, if it is active, is
L {N} ? A *
An inactive Controller will give no reply.
3.2.5 Type 2 Message
L {N} {P} {C} *
This type of message is used by the master device to interrogate or modify a parameter in the addressed Controller. {P} identifies the parameter and {C} represents the command to be executed, which may be one of the following:
+ (Hex 2B) - Increment the value of the parameter defined by {P} – (Hex 2D) - Decrement the value of the parameter defined by {P} ? (Hex 3F) - Determine the current value of the parameter defined by {P}
The reply from the addressed Controller is of the form:
L {N} {P} {DATA} A *
where {DATA} comprises five ASCII-coded digits whose format is shown in Table 3-1. The data is the value requested in a query message or the new value of the parameter after modification. If the action requested by the message from the master device would result in an invalid value for that parameter (either because the requested new value would be outside the permitted range for that parameter or because the parameter is not modifiable), the Controller replies with a negative acknowledgement:
L {N} {P} {DATA} N *
The {DATA} string in the negative acknowledgement reply will be indeterminate. If the process variable or the deviation is interrogated whilst the process variable is outside the range of the Controller, the reply is L{N}{P}<??>0A* if the process variable is over-range, or L{N}{P}<??>5A* if the process variable is under-range.
Scan Tables
A parameter identifier character “]” in the message from the master device indicates that a “Scan Table” operation is required. This provides a facility for
O054-3 3-3
59125
interrogating the values of a group of parameters and status in a single message from the master device. The reply to such a command would be in the form:
L {N} ] xx aaaaa bbbbb ccccc ddddd eeeee A *
where xx is the number of data digits to follow; this is 20 for a single-control-output instrument and 25 for a dual-control-output instrument. The digits are expressed as shown in Table 3 -1 . For further information, refer to Subsection 3.3.6 .
3.2.6 Type 3 Message
L {N} {P} # {DATA} *
This message type is used by the master device to set a parameter to the value specified in {DATA}. The command is not implemented immediately by the slave Controller; the slave will receive this command and will then wait for a Type 4 message (see below). Upon receipt of a Type 3 message, if the {DATA} content and the specified parameter are valid, the slave Controller reply is of the form:
L {N} {P} {DATA} I *
(where I = Hex 49) indicating that the Controller is ready to implement the command. If the parameter specified is invalid or is not modifiable or if the desired value is outside the permitted range for that parameter, the Controller replies with a negative acknowledgement in the form:
L {N} {P} {DATA} N *
3.2.7 Type 4 Message
L {N} {P} I *
This type of message is sent by the master device to the addressed slave Controller following a successful Type 3 message transmission and reply to/from the same slave Controller. Provided that the {DATA} content and the parameter specified in the preceding Type 3 message are still valid, the slave Controller will then set the parameter to the desired value and will reply in the form:
L {N} {P} {DATA} A *
where {DATA} is the new value of the parameter. If the new value or parameter specified is invalid, the slave Controller will give a negative acknowledgement:
L {N} {P} {DATA} N *
where {DATA} is indeterminate. If the immediately-preceding message received by the slave Controller was not a Type 3 message, the Type 4 message is ignored.
3-4 O054-3
59125

3.3 INDIVIDUAL PARAMETERS

The individual parameters and how they may be interrogated/modified are described below. Unless otherwise stated, the {DATA} element will follow the standard five-digit format and the decimal point position must be correct for the new value to be accepted and for modification to occur.
3.3.1 Input Parameters
Parameter Identifier Description
Process Variable
Process Variable Offset
Scale Range Max.
Scale Range Min.
M Read (Type 2 message) Only; If out of range, {DATA} will
contain <??>0 (over-range) or <??>5 (under-range).
v May be read (Type 2 message) or modified (Type 3/Type 4
message sequence). Modifies actual process variable value (as measured at the input terminals):
Modified PV value
= Actual PV value + PV offset value
Modified value is limited by Range Maximum and Range Minimum and is used for display/alarm purposes and for recorder outputs. Choose this value with care. In effect, it
modifies the Controller’s calibration. Lack of care could result in the displayed PV value having no meaningful relationship to the actual PV value.
G Adjustable only on DC inputs. May be read (Type 2
message) or modified (Type 3/Type 4 message sequence). Decimal point position is as for the input range. If less than
Scale Range Min. Value, sense of input is reversed.
H Adjustable only on DC inputs. May be read (Type 2
message) or modified (Type 3/Type 4 message sequence). Decimal point position is as for the input range. If greater
than Scale Range Max. Value, sense of input is reversed.
Scale Range Decimal Point
Input Filter Time Constant
O054-3 3-5
Q Adjustable on DC inputs only. May be read (Type 2
message) or modified (Type 3/Type 4 mesage sequence). Defines the decimal point position:
0 = abcd 1 = abc.d 2 = ab.cd 3 = a.bcd
m May be read or modified using a Type 2 message or a
Type 3/Type 4 message sequence.
3.3.2 Output Parameters
Parameter Identifier Description
59125
Power Output value
Output 1 Power Limit
Output 1 Cycle Time
Output 2 Cycle Time
W If Manual Control is not selected, may be read
only (Type 2 message). If Manual Control is selected, may be read (Type 2 message) or modified (Type 3/Type 4 message sequence).
B May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Defines power limit for Output 1.
N May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). NOTE: Value must be a power of 2 in the range 0.5 - 512 (i.e. 0.5, 1, 2, 4, 8 etc.). For a Relay Output, cycle time should be as large as possible (whilst remaining compatible with the process control requirements) in order to maximise relay life. For an SSR Output, the cycle time may have a lower value (and thus satisfy the requirements of a fast-changing process variable e.g. flow or pressure).
O May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). NOTE: Value must be a power of 2 in the range 0.5 - 512 (i.e. 0.5, 1, 2, 4, 8 etc.). For a Relay Output, cycle time should be as large as possible (whilst remaining compatible with the process control requirements) in order to maximise relay life. For an SSR Output, the cycle time may have a lower value (and thus satisfy the requirements of a fast-changing process variable e.g. flow or pressure).
Recorder Output Scale Max.
[ May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Corresponds to Input Scale Max. with decimal point position as for input. If less than Recorder Output Scale Min. sense of recorder output is reversed.
Recorder Output Scale Min.
\ May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Corresponds to Input Scale Min. with decimal point position as for input. If greater than Recorder Output Scale Max. sense of recorder output is reversed.
3-6 O054-3
59125
3.3.3 Setpoint Parameters
Parameter Identifier Description
Setpoint value
Setpoint Ramp Rate
Setpoint High Limit
Setpoint Low Limit
S May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Limited by Setpoint High Limit and Setpoint Low Limit (see below).
^ May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). May be set in the range 1 - 9999 increments/hour or OFF ({DATA} =0000). Decimal point position is as for input range.
A May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Defines maximum value for setpoint (in the range setpoint - Input Range Maximum). Decimal point position is as for input range.
T May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Defines minimum value for setpoint (in the range Input Range Minimum ­setpoint). Decimal point position is as for input range.
3.3.4 Alarm Parameters
Parameter Identifier Description
Alarm 1 value C May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point position is as for input range.
Alarm 2 value E May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point position is as for input range.
For descriptions of the operation of the different alarm types, see Figure 2-3 .
O054-3 3-7
3.3.5 Tuning Parameters
Parameter Identifier Description
59125
Rate (Derivative Time Constant)
Reset (Integral Time Constant)
Manual Reset (Bias)
ON/OFF Differential
D May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Defines the derivative time constant for the control algorithm. {DATA} is of the form mm.ss where mm = minutes and ss = seconds. The decimal point position must specify two decimal places, otherwise modification will not occur.
I May be read/modified using aType 2 message or a
Type 3/Type 4 message sequence. Defines the integral time constant for the control algorithm. {DATA} is of the form mm.ss where mm = minutes and ss = seconds. The decimal point position must specify two decimal places, otherwise modification will not occur.
1
J May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point position is as for input range.
F May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Defines the switching hysteresis for controllers with an ON/OFF control output. Decimal point position = 1.
Overlap /Deadband
Proportional Band 1 value
Proportional Band 2 value
K May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to a positive (overlap) or negative (deadband) value. Decimal point position = 0.
2
P May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to
0.0 (ON/OFF control) or within the range 0.5% -
999.9% of Output 1 power range. Decimal point position = 1.
U May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to
0.0 (ON/OFF control) or within the range 0.5% -
999.9% of Output 2 power range. Decimal point position = 1.
2
3-8 O054-3
59125
3.3.6 Status Parameters
Parameter Identifier Description
Controller Status
Arithmetic Deviation
Scan Tables
L Read Only (Type 2 message). Status information is
encoded in four digits as the decimal representation of a binary number; each bit in the binary number has a particular significance (see Figure 3-1 ).
V Read Only (Type 2 message). The difference between the
process variable value and the Limit Setpoint value.
] Read Only (Type 2 message). Response:
L{N}xxaaaaabbbbbcccccdddddeeeeeA*
where:
xx = Number of data digits in {DATA}
element (20 for single control output,
25 for dual control outputs) aaaaa = Current setpoint value bbbbb = Current process variable value ccccc = Current value of Output 1 Power
(0 - 100%) ddddd = Current value of Output 2 Power
(0 - 100%) - if applicable. eeeee = Controller Status (see Figure 3-1)
3.3.7 Controller Commands
Parameter Identifier Description
Controller Commands
Z Implemented by Type 3/Type 4 message sequence only.
In the Type 3 message, {DATA} must be one of eight five-digit numbers:
00010 Activate Manual Control 00020 Activate Automatic Control 00030 Activate Self-Tune 00040 De-activate Self-Tune 00050 Request Pre-Tune* 00060 Abort Pre-Tune 00130 Activate Loop Alarm 00140 De-activate Loop Alarm
The response from the Controller also contains the same {DATA} content, as does the response to the Type 4 message.
O054-3 3-9
59125
Figure 3-1 Controller Status Byte

3.4 ERROR RESPONSE

The circumstances under which a message received from the master device is ignored are:
Parity error detected Syntax error detected Timeout elapsed Receipt of a Type 4 message without a preceding Type 3 command message.
Negative acknowledgements will be returned if, in spite of the received message being notionally correct, the Controller cannot supply the requested information or perform the requested operation. The {DATA} element of a negative acknowledgement will be indeterminate.
3-10 O054-3
59125

Alphabetic Index - Volume 1

A
Alarm 1 Value
Band Alarm 2-3 Deviation Alarm 2-3 Process High Alarm 2-3 Process Low Alarm 2-3
Alarm 2 Value
Band alarm 2-3 Deviation alarm 2-3 Process High alarm 2-3 Process Low alarm 2-3
Alarm Operation
Illustration of2-9
Alarm Status
Display of 1-3 Displaying (Set Up mode)2-4
Auto Pre-Tune Enable/Disable 2-12
H
Hardware Definition Code
Explanation of 1-7 Viewing 1-7
I
Input Filter Time Constant 2-2 Input Over-Range
Indication of 1-4
Input Scale Range
Decimal point position 2-4 Input Scale Range Maximum 2-4 Input Scale Range Minimum 2-4 Input Under-Range
Indication of 1-4 Integral Time Constant (Reset) 2-5
B
Band Alarm 1 2-8 Band Alarm 2 2-10 Bias (Manual Reset) 2-7
C
Communications Line Release Time
Maximum Value 3-1
Communications Message Format 3-2
D
Deadband 2-5 Decimal Point Position
Input scale range 2-4 Derivative Time Constant (Rate) 2-5 Deviation Alarm 1 2-10 Deviation Alarm 2 2-10 Digital Filter Time Constant 2-3
L
Lock Value 2-12 Loop Alarm 2-10 Loop Alarm Enable 2-10 Loop Alarm Time 2-11
M
Manual Control Mode
De-selection of 1-4 Indication of 1-4 Selection of 1-4
Manual Control Selection Enable/Disable 2-12
Manual Reset (Bias) 2-7 Manual Tuning
Controllers with Output 1 and Output 2 2-14
Controllers with Output 1 only 2-13
O056-IDX 1
59125
O
ON/OFF Differential 2-7 Output 1 Cycle Time 2-8 Output 1 Power Limit 2-8 Output 2 Cycle Time 2-8 Output Power 1 2-5 Output Power 2 2-5 Overlap 2-5
P
Pre-Tune Facility
Activation of 1-5 Process High Alarm 1 2-8 Process High Alarm 2 2-10 Process Low Alarm 1 2-8 Process Low Alarm 2 2-10 Process Variable Offset 2-2 Proportional Band 1 2-5 Proportional Band 2 2-5
R
Rate (Derivative Time Constant)2-5 Recorder Output Scale Maximum
2-7 Recorder Output
Scale Minimum 2-7 Reset2-5 Reset (Integral Time Constant) 2-5
End of Message character 3-2
Error response 3-10 Line turn-round time 3-1 Message Types 3-2 Protocol 3-2 Scan Tables command 3-3 Start of Message
character 3-2 Type 2 message 3-3 Type 3 message 3-4 Type 4 message 3-4
Set Up Mode
Entry into 2-1 Exit from 2-15 Lock code 2-4
Set Up Parameters at default
Indication of 2-2
Setpoint
Adjustment of 1-3
Setpoint Display Strategy
Single Setpoint operation1-2 Setpoint High Limit2-7 Setpoint Low Limit 2-7 Setpoint Ramp Rate
Viewing/adjusting 1-3 Setpoint Ramping
Adjusting the
ramping rate 1-3
Enabling/disabling 2-12 Setpoint Strategy 2-12
Dual Setpoint operation 1-3
S
Scale Range Decimal Point 2-11 Scale Range Maximum 2-12 Scale Range Minimum 2-12 Self-Tune Facility
Activation of 1-6
Sensor Break
Indication of 1-4
Serial Communications
Data Format 3-1
Enabling/disabling2-4, 2-12
2 O056-IDX
59125
1
-DIN,
4
1
-DIN &
8
1
1 6
-DIN
TEMPERATURE CONTROLLERS
PRODUCT MANUAL
VOLUME 2
INSTALLATION & CONFIGURATION
INSTRUCTIONS
The procedures described in this Volume must be undertaken only by technically-competent servicing personnel.
Contents - Volume 2
1 INSTALLATION 1-1
1.1 UNPACKING 1-1
1.2 PANEL-MOUNTING 1-1
1.3 CONNECTIONS AND WIRING 1-4
2 INTERNAL LINKS AND SWITCHES 2-1
2.1 REMOVING THE CONTROLLER FROM ITS HOUSING 2-1
2.2 REMOVING/REPLACING THE OUTPUT 2/OUTPUT 3 OPTION PCBs 2-3
2.3 REMOVING/REPLACING THE RS485 COMMUNICATIONS OPTION PCB OR DUAL SETPOINT OPTION PCB 2-3
2.4 REPLACING THE CONTROLLER IN ITS HOUSING 2-3
2.5 SELECTION OF INPUT TYPE 2-4
2.6 SELECTION OF OUTPUT 1 TYPE 2-5
2.7 OUTPUT 2 TYPE/OUTPUT 3 TYPE 2-5
3 CONFIGURATION MODE 3-1
3.1 ENTRY INTO CONFIGURATION MODE 3-1
S056-V2 (i)
59125
3.2 HARDWARE DEFINITION CODE 3-2
3.3 OPTION SELECTION 3-3
3.4 CONFIGURATION MODE PARAMETERS 3-4
3.5 ALARM HYSTERESIS OUTPUTS 3-8
3.6 EXIT FROM CONFIGURATION MODE 3-9
Appendices
A PRODUCT SPECIFICATION A-1
A.1 UNIVERSAL INPUT A-1
A.2 DUAL SETPOINT SELECTION INPUT (OPTION) A-3
A.3 OUTPUT 1 A-4
A.4 OUTPUT 2 A-5
A.5 OUTPUT 3 A-7
A.6 LOOP CONTROL A-8
A.7 ALARM CONTROL A-9
A.8 PERFORMANCE A-9
A.9 ENVIRONMENTAL A-11
A.10 PHYSICAL A-12
(ii) S056-V2
59125

1 INSTALLATION

1.1 UNPACKING

1. Remove the Controller from its packing. The Controller is supplied with a panel gasket and push-fit fixing strap. Retain the packing for future use, should it be necessary to transport the Controller to a different site or to return it to the supplier for repair/testing.
2. Examine the delivered items for damage or deficiencies. If any is found, notify the carrier immediately.

1.2 PANEL-MOUNTING

The panel on which the Controller is to be mounted must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-out required for a single Controller is as shown in Figure 1 -1 .
Figure 1-1 Cut-out Dimensions
Several controllers may be installed in a single cut-out, side-by-side. For n Controllers mounted side-by-side, the width of the cut-out would be:
1
-DIN &
16
1
-DIN: (96n - 4) millimetres or (7.56n - 0.16) inches
4
1
-DIN: (48n - 4) millimetres or (3.78n - 0.16) inches
8
The main dimensions of the Controller are shown in Figure 1 -2 .
O054-1 1-1
59125
Figure 1-2 Main Dimensions
The procedure to panel-mount the Controller is shown in Figure 1 -3 .
CAUTION: Do not remove the panel gasket, as this may result in inadequate clamping of the instrument in the panel.
NOTE: The mounting clamp tongues may engage the ratchets either on the sides of the Controller housing or on the top/bottom faces of the Controller housing. Therefore, when installing several Controllers side-by-side in one cut-out, use the ratchets on the top/bottom faces.
1-2 O054-1
59125
Figure 1-3 Panel-Mounting the Limit Controller
Once the Controller is installed in its mounting panel, it may be subsequently removed from its housing, if necessary, as described in Subsection 2.1.
O054-1 1-3

1.3 CONNECTIONS AND WIRING

59125
The rear terminal connections are illustrated in Figure 1-4 ( controllers) and Figure 1-5 (
1
-DIN controllers).
16
1
-DIN and
4
1
-DIN
8
Figure 1 -4 Rear Terminals (
1
-DIN &
4
1
-DIN Controllers)
8
1 -4 O054-1
59125
Figure 1 -5 Rear Terminals (
1
-DIN Controllers)
16
O054-1 1-5
59125
1.3.1 Mains (Line) Input
The Controller will operate on 96 - 264V AC 50/60Hz mains (line) supply. The power consumption is approximately 4 VA.
CAUTION: This equipment is designed for installation in an enclosure which
provides adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be given to prevention of access to the power terminations by unauthorised personnel. Power should be connected via a two-pole isolating switch (preferably situated near the equipment) and a 1A fuse, as shown in Figures 1 -4 and 1 -5 .
If the Controller has relay outputs in which the contacts are to carry mains (line) voltage, it is recommended that the relay contact mains (line) supply should be switched and fused in a similar manner but should be separate from the Controller mains (line) supply.
1.3.2 24V (Nominal) AC/DC Supply
The supply connections for the 24V AC/DC option of the Controller are as shown in Figures 1-4 and 1 -5 . Power should be connected via a two-pole isolating switch and a 315mA slow-blow (anti-surge Type T) fuse. With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges:
24V (nominal) AC 50/60Hz - 20 - 50V 24V (nominal) DC - 22 - 65V
1.3.3 Thermocouple Input
The correct type of thermocouple extension leadwire or compensating cable must be used for the entire distance between the Controller and the thermocouple, ensuring that the correct polarity is observed throughout. Joints in the cable should be avoided, if possible. The Controller’s CJC facility must be enabled (normal conditions) for this input (see Page 3-8 ).
NOTE: Do not run thermocouple cables adjacent to power-carrying conductors. If the wiring is run in a conduit, use a separate conduit for the thermocouple wiring. If the thermocouple is grounded, this must be done at one point only. If the thermocouple extension lead is shielded, the shield must be grounded at one point only.
1.3.4 RTD Inputs
The compensating lead should be connected to Terminal 4 ( Terminal 3 (
1
(
-DIN controllers) or Terminals 2 and 3 (
16
1
-DIN and
4
1
-DIN controllers). For two-wire RTD inputs, Terminals 4 & 5
8
1
-DIN and
4
1
-DIN controllers) should be
8
linked. The extension leads should be of copper and the resistance of the wires
1 - 6 O054-1
1
-DIN controllers) or
16
59125
connecting the resistance element should not exceed 5 ohms per lead (the leads
should be of equal resistance).
1.3.5 Linear Inputs
For linear mA input ranges, connection is made to Terminals 4 and 6 ( controllers) or Terminals 4 and 1 (
1
-DIN &
4
1
-DIN controllers) in the polarity shown in
8
16
1
-DIN
Figures 1-4 and 1-5. For linear mV and V ranges, connection is made to Terminals 4 and 5 (
1
-DIN controllers) or Terminals 3 and 2 (
16
1
-DIN &
4
1
-DIN controllers) in the
8
polarity shown in Figures 1-4 and 1-5. For details of the linear input ranges available, refer to Appendix A.
1.3.6 Dual Setpoint Selection Input
With the Dual Setpoint option fitted, Terminals 11 and 12 ( Terminals 16 and 17 (
1
-DIN &
4
1
-DIN controllers) are used for external selection of
8
the active setpoint. These terminals may be connected to (a) the voltage-free contacts of a switch or relay, or (b) a TTL-compatible voltage. Setpoint selection is as follows:
Voltage-Free: Contacts open - Setpoint 1 selected
Contacts closed - Setpoint 2 selected
TTL-compatible: >2.0V - Setpoint 1 selected
<0.8V - Setpoint 2 selected
1
-DIN controllers) or
16
NOTE: The Dual Setpoint option and the RS485 Serial Communications option are mutually exclusive.
1.3.7 Relay Outputs
The contacts are rated at 2A resistive at 120/240V AC.
1.3.8 SSR Drive Outputs
These outputs produce a time-proportioned non-isolated DC signal (0 - 4.2V nominal into 1k minimum).
1.3.9 Solid State Outputs
These outputs provide up to 1A AC drive with a longer lifetime than an electromechanical relay. For further details, refer to Appendix A.
1.3.10 DC Outputs
See Appendix A.
O054-1 1-7
59125
1.3.11 RS485 Serial Communications Link
The cable used should be suitable for data transfer at the selected rate (1200, 2400, 4800 or 9600 Baud) over the required distance. Transmitters/receivers conform to the recommendations in the EIA Standard RS485.
The “A” terminal on the Controller should be connected to the “A” terminal on the master device; the “B” terminal on the Controller should be connected to the “B” terminal on the master device. Where several Controllers are connected to one master port, the master port transceiver in the active state should be capable of driving a load of 12k per Controller; the master port transceiver in the passive state must have pull-up/pull-down resistors of sufficiently low impedance to ensure that it remains in the quiescent state whilst supplying up to Controller transceivers in the high impedance state.
NOTE: The RS485 Serial Communications option and the Dual Setpoint option are mutually exclusive.
100µA each to the
±
1-8 O054-1
59125

2 INTERNAL LINKS AND SWITCHES

NOTE: The operations described in this Section should be performed only by personnel trained and authorised to do so.

2.1 REMOVING THE CONTROLLER FROM ITS HOUSING

CAUTION: Before removing the Controller from its housing, ensure that all
power has been removed from the rear terminals.
To withdraw the Controller from its housing, simply grip the side edges of the front panel (there is a finger grip on each edge) and pull the Controller forwards. This will release the Controller from its rear connectors in the housing and will give access to the Controller PCBs. Take note of the orientation of the Controller for subsequent replacement into the housing.The positions of the PCBs in the Controller are shown in Figure 2-1.
Figure 2-1 PCB Positions
S054-2 2-1
59125
Figure 2-2 Removing the Output 2/Output 3 Option PCBs
2-2 S054-2
59125
2.2 REMOVING/ REPLACING THE OUTPUT 2/OUTPUT 3
OPTION PCBs
With the Controller removed from its housing:
1. Gently push the rear ends of the CPU PCB and Power Supply PCB apart slightly, until the two tongues on each of the Output 2/Output 3 Option PCBs become dis-engaged - see Figure 2-2B; The Output 2 Option PCB tongues engage in holes in the Power Supply PCB and the Output 3 Option PCB tongues engage in holes on the CPU PCB.
2. Carefully pull the required Option PCB (Output 2 or Output 3) from its connector (Output 2 Option PCB is connected to the CPU PCB and Output 3 Option PCB is connected to the Power Supply PCB) - see Figure 2-2C. Note the orientation of the PCB in preparation for its replacement.
Adjustments may now be made to the link jumpers on the CPU PCB, the Output 2/Output 3 Option PCBs (if DC output) and (on
1
-DIN Controllers, if fitted) the DC
16
Output 1 PCB. The replacement procedure is a simple reversal of the removal procedure.
2.3 REMOVING/REPLACING THE RS485
COMMUNICATIONS OPTION PCB OR DUAL SETPOINT OPTION PCB
This Option PCB is mounted on the inner surface of the Power Supply PCB and can be removed when the Controller is removed from its housing (see Subsection 2.1 ). Figure 2 -3 illustrates the removal/replacement procedure. It is not necessary to
remove the Output 2/Output 3 Option PCBs to perform this procedure.

2.4 REPLACING THE CONTROLLER IN ITS HOUSING

To replace the Controller, simply align the CPU PCB and Power Supply PCB with their guides and connectors in the housing and slowly but firmly push the Controller into position.
CAUTION: Ensure that the instrument is correctly orientated. A stop will operate if an attempt is made to insert the instrument in the wrong orientation (e.g. upside-down). This stop must not be over-ridden.
S054-2 2-3
59125
Figure 2-3 Removing the RS485 Communications Option PCB
or the Dual Setpoint Option PCB

2.5 SELECTION OF INPUT TYPE

2.5.1
The selection of input type is accomplished on link jumpers on the CPU PCB. The CPU PCB may be either of two forms: (a) for a relay or SSR Output 1 (see Figure 2-4) or for a DC Output 1 (see Figure 2-5). Input type selection is as shown on the right.
2.5.2
1
-DIN Controllers
16
1
-DIN and
4
1
-DIN
8
Controllers
The selection of input type is accomplished on link jumpers on the CPU PCB (see Figure 2-6). Input type selection is as shown on the right.
Input Type Link Jumpers Fitted
RTD or DC (mV) None (Parked)
Thermocouple LJ3
DC (mA) LJ2
DC (V) LJ1
Input Type Link Jumpers Fitted
RTD or DC (mV) None (Parked)
Thermocouple LJ3
DC (mA) LJ2
DC (V) LJ1
2 -4 S054-2
59125

2.6 SELECTION OF OUTPUT 1 TYPE

2.6.1
1
-DIN Controllers
16
The required type of Output 1 is selected by Link Jumpers LJ4, LJ5, LJ6 and LJ7 on the Relay/SSR Output 1 CPU PCB (see Figure 2-4) or, on the DC Output 1 CPU PCB, Link Jumpers LJ8 and LJ9 (see Figure 2 -5 ). Output type selection is as shown on the right.
2.6.2
1
-DIN and
4
1
-DIN
8
Controllers
The required type of Output 1 is selected by Link Jumpers LJ4, LJ5, LJ6, LJ7, LJ8 and LJ9 on the PSU PCB (see Figure 2 -7 ). Output type selection is as shown on the right.
Output 1 Type Link Jumpers Fitted
Relay or Solid State LJ5 & LJ6
SSR Drive LJ4 & LJ7
DC (0 - 10V) LJ8
DC (0 - 20mA) LJ9
DC (0 - 5V) LJ8
DC (4 - 20mA) LJ9
Output 1 Type Link Jumpers Fitted
Relay or Solid State LJ5 & LJ6
SSR Drive LJ4 & LJ7
DC (0 - 10V) LJ8
DC (0 - 20mA) LJ9
DC (0 - 5V) LJ8
DC (4 - 20mA) LJ9

2.7 OUTPUT 2 TYPE/ OUTPUT 3 TYPE

The type of output for Output 2 and Output 3 is determined by the Option PCB fitted in the appropriate position (see Figure 2 -1 ). There are four types of option PCB which may be used for Output 2 and Output 3:
1. Relay Output Option PCB (no link jumpers)
2. Solid State Output Option PCB (no link jumpers)
3. SSR Output Option PCB (no link jumpers)
4. DC Output Option PCB (link jumpers as shown in Figure 2-8)
In the case of the DC Output Option PCB being fitted, DC output range is selected using link jumpers LJ8 and LJ9, as shown on the right.
DC Output Range Link Jumpers Fitted
DC (0 - 10V) LJ8
DC (0 - 20mA) LJ9
DC (0 - 5V) LJ8
DC (4 - 20mA) LJ9
S054-2 2-5
59125
Figure 2-4 CPU PCB (Relay/SSR Drive/Solid State Output 1) -
Figure 2 -5 CPU PCB (DC Output 1) -
1
-DIN Controllers
16
1
-DIN Controllers
16
2 -6 S054-2
59125
Figure 2 -6 CPU PCB -
1
-DIN &
4
1
-DIN Controllers
8
Figure 2 -7 PSU PCB -
1
-DIN &
4
1
-DIN Controllers
8
S054-2 2-7
59125
Figure 2 -8 DC Output Option PCB PCB (Output 2/Output 3)
2 -8 S054-2
59125

3 CONFIGURATION MODE

3.1 ENTRY INTO CONFIGURATION MODE

See Figure 3 -1 .
Figure 3 -1 Entry into Configuration Mode
NOTE: Changes to the value/setting of certain Configuration Mode parameters (e.g. input range, output use and type) will cause the Set Up Mode parameters to be automatically set to their default values the next time Set Up Mode is entered (see also Volume 1, beginning of Section 2 ).
S054-3 3-1

3.2 H ARDWARE DEFINITION CODE

This parameter is a special facility in Configuration Mode, which is used to represent the hardware fitted (input type, Output 1 type, Output 2 type and Output 3 type); this must be compatible with the hardware actually fitted. For access to, and adjustment of, the Hardware Definition Code, see Figure 3-2.
59125
Figure 3-2 Hardware Definition Code - Access and Adjustment
3-2 S054-3
59125
Table 3 -1 Hardware Definition Code - Input/Output Type Selection
Value 0 1 2 3 4 5 7 8
Input RTD/
Linear
Thermo­couple
Linear DC mA
Linear DC V
DC mV
Output 1
Output 2/3
Not fitted
Relay SSR
Drive
Relay SSR
Drive
DC 0 - 10VDC0 - 20mADC0 - 5VDC4 - 20mA
DC 0 - 10VDC0 - 2-mADC0 - 5VDC4 - 20mA
Solid State
Solid State
NOTES: 1. If Output 2 is set to be a relay/SSR drive/solid state
output, it may be a control output (COOL) or an alarm output; if it is set to be a DC output, it can only be a control output (COOL).
2. If Output 3 is set to be a relay/SSR drive/solid state output, it can only be an alarm output; if it is set to be a DC output, it can only be a recorder (i.e. re-transmitted process variable or setpoint) output.
The maximum setting available for this code is 4888. For example, the code for a thermocouple input, DC 4 - 20mA primary output (Output 1) and relay Output 3 would be 2701.
NOTE: It is essential that this code is changed promptly whenever there is a change to the Controller’s hardware configuration (change of input/output type, alarm/recorder output added/removed etc.). The Controller software depends upon this code to ensure that the Controller operates correctly.
This code may be viewed as a Read Only display in Operator Mode (see Volume 1, Subsection 1.10).

3.3 OPTION SELECTION

This indicates the option fitted (Communications Option, Dual Setpoint Option no option at all). It is accessed whilst the Hardware Definition Code is displayed (see Figure 3-3 ).
S054-3 3-3
59125
Figure 3 -3 Option Selection

3.4 CONFIGURATION MODE PARAMETERS

Parameter Identifier Description
Input Range
Output 1 Action
Alarm 1 Type
A four-digit code (see Appendix A). Default settings:
Thermocouple - 1419 (Type J, 0 - 761 °C) RTD/Linear mV - 7220 (RTD Pt100 0 - 800°C)
Linear mA - 3414 (4 - 20mA) Linear V - 4446 (0 - 10V)
Reverse-acting
Direct-acting
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
No alarm
3-4 S054-3
59125
Parameter Identifier Description
Alarm 2 Type
Alarm Inhibit
Process High Alarm
Process Low Alarm (default)
Deviation Alarm
Band Alarm
No alarm
No alarms inhibited
Alarm 1 inhibited
Alarm 2 inhibited
Both Alarm 1 & Alarm 2 inhibited
S054-3 3-5
Parameter Identifier Description
59125
Output 2 Usage
Output 2 secondary control (COOL) output
Alarm 2 hardware output, direct-acting. Avail­able only if relay/SSR drive/solid state output.
Alarm 2 hardware output, reverse-acting. Avail­able only if relay, SSR drive or solid state output.
Direct-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Direct-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Loop Alarm output, direct-acting. Available only if relay, SSR drive or solid state output.
Loop Alarm output, reverse-acting. Available only if relay, SSR drive or solid state output.
Alarm Hysteresis output, direct-acting. Available only if relay, SSR drive or solid state output.
Alarm Hysteresis output, reverse-acting. Available only if relay, SSR drive or solid state output.
Example of Logical Combination of Alarms - Logical OR of Alarm 1 & Alarm 2
Direct-acting Reverse-acting
AL1 OFF, AL2 OFF: Relay de-energised AL1 OFF, AL2 OFF: Relay energised
AL1 ON, AL2 OFF: Relay energised AL1 ON, AL2 OFF: Relay de-energised
AL1 OFF, AL2 ON: Relay energised AL1 OFF, AL2 ON: Relay de-energised
AL1 ON, AL2 ON: Relay energised AL1 ON, AL2 ON: Relay de-energised
3-6 S054-3
59125
Parameter Identifier Description
Output 3 Usage
Alarm 1 hardware output, direct-acting. Avail­able only if relay/SSR drive/solid state output.
Alarm 1 hardware output, reverse-acting. Avail­able only if relay, SSR drive or solid state output.
Direct-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical OR of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Direct-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Reverse-acting output for Logical AND of Alarm 1 and Alarm 2. Available only if relay, SSR drive, or solid state output.
Loop Alarm output, direct-acting. Available only if relay, SSR drive or solid state output.
Loop Alarm output, reverse-acting. Available only if relay, SSR drive or solid state output.
Alarm Hysteresis output, direct-acting. Available only if relay, SSR drive or solid state output.
Alarm Hysteresis output, reverse-acting. Available only if relay, SSR drive or solid state output.
Recorder Output - Setpoint (DC output only)
Recorder Output - Process Variable (DC Output only)
Example of Logical Combination of Alarms - Logical AND of Alarm 1 & Alarm 2
Direct-acting Reverse-acting
AL1 OFF, AL2 OFF: Relay de-energised AL1 OFF, AL2 OFF: Relay energised
AL1 ON, AL2 OFF: Relay de-energised AL1 ON, AL2 OFF: Relay energised
AL1 OFF, AL2 ON: Relay de-energised AL1 OFF, AL2 ON: Relay energised
AL1 ON, AL2 ON: Relay energised AL1 ON, AL2 ON: Relay de-energised
S054-3 3-7
Parameter Identifier Description
59125
Comms. Baud
Selectable: 1200, 2400, 4800, 9600 Baud
Rate
Comms. Address Unique address assigned to the controller;
in the range 1 - 32.
Cold Junction
Enabled (default) Compensation Enable/Disable*
Disabled
Lock Code Read Only display of current four-digit Set Up
Mode Lock Code.

3.5 ALARM HYSTERESIS OUTPUTS

An alarm hysteresis output is active only when both alarms are active; it becomes subsequently inactive only when both alarms become inactive. Thus, the status of the Alarm Hysteresis output when one alarm is active and the other is inactive depends upon the alarm status immediately prior to that alarm being activated; thus, with two process high alarms:
3 -8 S054-3
59125

3.6 EXIT FROM CONFIGURATION MODE

NOTE: An automatic exit to Operator Mode will be made if, in Configuration Mode, there is no front panel key activity for two minutes.
The exit is made via the power-up self-test routines which include a lamp test.
S054-3 3-9

A PRODUCT SPECIFICATION

A.1 UNIVERSAL INPUT
General
Maximum per Controller: One
Input Sample Rate: Four samples/second
Digital Input Filter: Time constant selectable from front panel -
0.0 (i.e. OFF), 0.5 to 100.0 seconds in
0.5-second increments.
Input Resolution: 14 bits approximately; always four times
better than display resolution.
59125
Input Impedance: Greater than 100M Ω resistive (except for
DC mA and V inputs).
Isolation: Universal input isolated from all outputs
except SSR at 240V AC.
Process Variable Offset:
Thermocouple: Ranges selectable from front panel (with displayed codes):
Type Input Range Dislayed Code Type Input Range Displayed Code
R
R
S
S
J
J
J
0 - 1650 °C
32 - 3002 °F
0 - 1649°C
32 - 3000°F
0.0 - 205.4°C
32.0 - 401.7 °F 0 - 450 °C
1127 J
1128 T
1227 T
1228 T
1415 T
1416 K
1417 K
Adjustable ±input span.
32 - 1401 °F
-200 - 262 °C
-328 - 503 °F
0.0 - 260.6°C
32.0 - 501.0 °F
-200 - 760°C
-328 - 1399 °F
1420
1525
1526
1541
1542
6726
6727
J
J
A-1 S054-A
32 - 842°F
0 - 761 °C *
1418 K
1419 K
-200 - 1373 °C
-328 - 2503 °F
6709
6710
59125
Type Input Range Dislayed Code Type Input Range Displayed Code
L
L
0.0 - 205.7°C
32.0 - 402.2 °F
L
L
L
0 - 450°C
32 - 841°F
0 - 762°C
1815 L
1816 B
1817 B
1818 N
1819 N
32 - 1403°F
211 - 3315°F
100 - 1824°C
0 - 1399°C
32 - 2550°F
1820
1934
1938
5371
5324
Calibration: Complies with BS4937, NBS125 and IEC584.
Sensor Break Protection: Break detected within two seconds. Control
outputs set to OFF (0% power); Alarms operate as if the process variable has gone over-range.
Resistance Temperature Detector (RTD) and DC mV: Ranges selectable from front panel (with displayed codes):
Input Range Displayed Code Input Range Displayed Code
0 - 800 °C *
7220
0.0 - 100.9 °C
2295
32 - 1471°F
32 - 571°F
-100.9 - 100.0°C
-149.7 - 211.9°F 0 - 300 °C
7221
2229
2230
2231
2251
32.0 - 213.6 °F
-200 - 206°C
-328 - 402°F
-100.9 - 537.3°C
-149.7 - 999.1°F
2296
2297
2298
7222
7223
Type and Connection: Three-wire Pt100
Calibration: Complies with BS1904 and DIN43760.
Lead Compensation: Automatic scheme.
RTD Sensor Current: 150µA (approximately)
Sensor Break Protection: Break detected within two seconds. Control
outputs set to OFF (0% power). Alarm operation is as follows:
S054-A A-2
59125
Input
Type
RTD Sensor or Terminal 1 Sensor or Terminal 6 As if Process Variable is over-range
RTD Terminal 3 or 2 Terminal 4 or 5 As if Process Variable is under-range
DC (mV) - - As if Process Variable is over-range
1
-DIN or
4
Location of Break
1
-DIN Controller
8
1
-DIN Controller
16
Alarm Operation
DC Linear: Ranges Selectable from Front Panel (with displayed codes):
Input Range Displayed Code Input Range Displayed Code
0 - 20mA 3413 0 - 5V 4445
4 - 20mA * 3414 1 - 5V 4434
0 - 50mV 4443 0 - 10V * 4446
10 - 50mV 4499 2 - 10V 4450
(Changes may also be required to the CPU PCB link jumpers - see Subsection 2.5)
Scale Range Maximum: –1999 to 9999. Decimal point as required.
Scale Range Minimum: –1999 to 9999. Decimal point as for Scale
Range Maximum.
Minimum Span: 1 display LSD.
Sensor Break Protection: Applicable to 4 - 20mA, 1 - 5V and 2 - 10V
ranges only. Break detected within two seconds. Control outputs set to OFF (0% power); Alarms operate as if the process variable has gone under-range.

A.2 DUAL SETPOINT SELECTION INPUT (OPTION)

Type: Voltage-free or TTL-compatible
Voltage-Free Operation: Connection to contacts of external switch
or relay; contacts open = Setpoint 1 selected (minimum contact resistance = 5000), contacts closed = Setpoint 2 selected (maximum contact resistance = 50).
TTL levels: To select Setpoint 1: –0.6V to 0.8V
To select Setpoint 2: 2.0V to 24V
A -3 S054-A
59125
Maximum Input Delay
1 second
(OFF-ON):
Minimum Input Delay
1 second
(ON-OFF):

A.3 OUTPUT 1

General
Types Available: Relay (as standard), SSR drive, solid state
and DC as options.
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k min. (
SSR > 4.3V into 250 min. (
1
-DIN)
16
1
-DIN &
4
Isolation: Not isolated from input or other SSR drive
outputs.
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
0.01 - 1A (full cycle rms on-state @ 25 °C); derates linearly above 40 °C to 0.5A @ 80 °C.
Max. Non-repetitive Surge
25A peak
Current (16.6ms):
1
-DIN)
8
Min. OFF-State
dv
@ Rated
dt
500V/µs
Voltage:
Max. OFF-State leakage @
1mA rms
Rated Voltage:
S054-A A-4
59125
Max. ON-State Voltage
1.5V peak.
Drop @ Rated Current:
Repetitive Peak OFF-state
600V minimum.
Voltage, Vdrm:
DC
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP switch and front panel
code.

A.4 OUTPUT 2

General
Types Available: Relay, SSR drive, solid state and DC.
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
A -5 S054-A
59125
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k min. (
SSR > 4.3V into 250 min. (
1
-DIN)
16
1
-DIN &
4
Isolation: Not isolated from input or other SSR drive
outputs.
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
0.01 - 1A (full cycle rms on-state @ 25 °C); derates linearly above 40 °C to 0.5A @ 80 °C.
Max. Non-repetitive Surge
25A peak
Current (16.6ms):
Min. OFF-State
dv
@ Rated
dt
500V/µs
Voltage:
1
-DIN)
8
Max. OFF-State leakage @
1mA rms
Rated Voltage:
Max. ON-State Voltage
1.5V peak.
Drop @ Rated Current:
Repetitive Peak OFF-state
600V minimum.
Voltage, Vdrm:
DC
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
S054-A A-6
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP switch and front panel
code.

A.5 OUTPUT 3

General
Types Available: Relay, SSR drive, solid state and DC linear
(Recorder Output only)
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
59125
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
SSR Drive/TTL
Drive Capability: SSR >4.2V DC into 1k min. (
SSR > 4.3V into 250 min. (
1
-DIN)
16
1
-DIN &
4
Isolation: Not isolated from input or other SSR drive
outputs.
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
0.01 - 1A (full cycle rms on-state @ 25 °C); derates linearly above 40 °C to 0.5A @ 80 °C.
1
-DIN)
8
Max. Non-repetitive Surge
25A peak
Current (16.6ms):
Min. OFF-State
dv
@ Rated
dt
500V/µs
Voltage:
Max. OFF-State leakage @
1mA rms
Rated Voltage:
A-7 S054-A
59125
Max. ON-State Voltage
1.5V peak.
Drop @ Rated Current:
Repetitive Peak OFF-state
600V minimum.
Voltage, Vdrm:
DC
Resolution: Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate: Every control algorithm execution.
Ranges: 0 - 20mA
4 - 20mA 0 - 10V 0 - 5V
(Changes between V and mA require link jumper movement.)
Load Impedance: 0 - 20mA: 500 maximum
4 - 20mA: 500 maximum 0 - 10V: 500 minimum 0 - 5V: 500 minimum
Isolation: Isolated from all other inputs and outputs.
Range Selection Method: Link jumper or DIP.

A.6 LOOP CONTROL

Automatic Tuning Types: Pre-Tune and Self-Tune.
Proportional Bands: 0 (OFF), 0.5% - 999.9% of input span at
0.1% increments.
Reset (Integral Time Constant):
Rate (Derivative Time Constant):
Manual Reset (Bias): Added each control algorithm execution.
1s - 99min 59s and OFF
0 (OFF) - 99 min 59 s.
Adjustable in the range 0 - 100% of output power (single output) or –100% to +100% of output power (dual output).
Deadband/Overlap: –20% to +20% of Proportional Band 1 +
Proportional Band 2.
S054-A A-8
59125
ON/OFF Differential: 0.1% to 10.0% of input span.
Auto/Manual Control: User-selectable with “bumpless” transfer
into and out of Manual Control.
Cycle Times: Selectable from
1
s to 512 secs in binary
2
steps.
Setpoint Range: Limited by Setpoint Maximum and Setpoint
Minimum.
Setpoint Maximum: Limited by Setpoint and Range Maximum.
Setpoint Minimum: Limited by Range Minimum and Setpoint.
Setpoint Ramp: Ramp rate selectable 1 - 9999 LSDs per
hour and infinite. Number displayed is decimal-point-aligned with selected range.

A.7 ALARM CONTROL

Maximum Number of Alarms:
Max. No. of Outputs Available:
Two “soft” alarms plus Loop Alarm
Up to two outputs can be utilised for alarm purposes.
Combinatorial Alarms: Logical OR or AND of alarms to an
individual hardware output is available.

A.8 PERFORMANCE

Reference Conditions
Generally as EN60546-1.
Ambient Temperature:
Relative Humidity: 60 - 70%
Supply Voltage:
Source Resistance: <10Ω for thermocouple input
Lead Resistance: <0.1Ω/lead balanced (Pt100)
20°C ±2°C
90 - 264V AC 50Hz ±1%
A -9 S054-A
59125
Performance Under Reference Conditions
Common Mode Rejection: >120dB at 50/60Hz giving negligible effect
at up to 264V 50/60Hz.
Series Mode Rejection: >500% of span (at 50/60Hz) causes
negligible effect.
DC Linear Inputs
Measurement Accuracy:
Thermocouple Inputs
Measurement Accuracy:
Linearisation Accuracy:
Cold Junction Compensation:
RTD Inputs
Measurement Accuracy:
Linearisation Accuracy:
±0.25% of span ±1LSD.
±0.25% of span ±1LSD. NOTE: Reduced
performance with Type “B” Thermocouple
between 100 - 600 °C (212 - 1112 °F). Better than ±0.2 °C any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C any point, any 1 °C range.
Better than ±0.7 °C.
±0.25% of span ±1LSD Better than ±0.2oC any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C any point, any 1 °C range.
DC Outputs - Accuracy
Output 1:
±0.5% (mA @ 250, V @ 2kΩ ); 2%
underdrive (4 - 20mA) and overdrive applies.
Output 2:
±0.5% (mA @ 250 , V @ 2kΩ ); 2%
underdrive (4 - 20mA) and overdrive applies.
Output 3 (Recorder Output):
±0.25% (mA @ 250 , V @ 2kΩ ); Degrades linearly to ± 0.5% for increasing burden (to
specification limits).
S054-A A-10
Operating Conditions
59125
Ambient Temperature
0 °C to 55 °C
(Operating):
Ambient Temperature
–20 °C to 80°C
(Storage):
Relative Humidity: 20% - 95% non-condensing
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC (option)
Source Resistance: 1000 maximum (thermocouple)
Lead Resistance: 50 per lead maximum balanced (Pt100)
Performance Under Operating Conditions
Temperature Stability:
0.01% of span/°C change in ambient
temperature.
Cold Junction
Better than ±1°C.
Compensation (thermocouple Only):
Supply Voltage Influence: Negligible.
Relative Humidity
Negligible
Influence:
Sensor Resistance Influence:
Thermocouple 100: <0.1% of span error Thermocouple 1000: <0.5% of span error RTD Pt100 50 /lead: <0.5% of span error

A.9 ENVIRONMENTAL

Operating Conditions: See Subsection A.8 - PERFORMANCE.
Approvals: CE, UL, ULC
EMI Susceptibility: Certified to EN50082-1:1992 and
EN50082-2:1995. NOTE: For line-conducted disturbances induced by RF fields (10V 80% AM 1kHz),
1
the
-DIN controller is self-recoverable in
16
the frequency bands 17 - 47MHz and 68 ­80MHz.
A-11 S054-A
59125
EMI Emissions: Certified to EN50081-1:1992 and
EN50081-2:1994.
Safety Considerations: Complies with EN61010-1:1993.
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC (option)
Power Consumption: 4 watts approximately.
Front Panel Sealing: To IP66 (NEMA 4).

A.10 PHYSICAL

Dimensions Depth: 110mm (
100mm (
Front Panel - Width: 48mm (
96mm (
Height: 48mm (
96mm (
1
-DIN controllers)
16
1
-DIN &
4
1
-DIN &
16
1
-DIN controllers)
4
1
-DIN controllers)
16
1
-DIN &
4
1
-DIN controllers)
8
1
-DIN controllers)
8
1
-DIN controllers)
8
Mounting: Plug-in with panel mounting fixing strap.
Panel cut-out: 45mm x 45mm (
45mm x 92mm ( 92mm x 92mm (
1
-DIN controllers)
16 1
-DIN controllers)
8
1
-DIN controllers)
4
Terminals: Screw type (combination head).
Weight: 0.21kg maximum
S054-A A -12

Alphabetic Index - Volume 2

59125
C
Configuration Mode
Entry into 3-1 Exit from 3-9
Controller Dimensions A-12
D
Dual Setpoint Option PCB
Removal/replacement 2-3
Dual Setpoint Selection
TTL-Compatible Input 1-7 Voltage-Free Contacts 1-7
H
Hardware Definition Code
Display of 3-2 Input/Output Type
selection 3-3
Hardware Definition Code
Adjustment of 3-2
I
Removal/replacement 2-3
Output 3 Type
Selection of 2-5
Output Connections
DC 1-7 Relay 1-7 SSR Drive 1-7
P
Panel-Mounting
Cut-out dimensions (multiple installation) 1-1
Cut-out dimensions (single installation) 1-1
Maximum panel thickness1-1
R
Rear Terminal Connections 1-4 Removing the Controller
from its Housing 2-1 Replacing the Controller
in its Housing 2-3 RS485 Communications Option PCB
Removal/replacement 2-3
Input Connections
Dual Setpoint Selection 1-7 Linear1-7 RTD 1-6 Thermocouple 1-6
Input Type
Selection of 2-4
O
Output 1 Type
Selection of 2-5
Output 2 Type
Selection of 2-5
Output 2/Output 3 Option PCB
1 S056-IDX
59125
S
Sensor Break
Effect on outputs (DC linear inputs) A-3
Effect on outputs (RTD inputs) A-2
Effect on outputs (thermocouple inputs) A-2
Serial Communications
Connections1-8
Supply Connections
24V AC/DC Option 1-6 Mains (Line) voltage 1-6
S056-IDX 2
Loading...