West Control Solutions N8080 User Manual

1
-DIN
8
DUAL COLOUR DISPLAY
TEMPERATURE INDICATOR
Product Manual
59135-2

HOW TO USE THIS MANUAL

This manual comprises two volumes:
59135
-DIN DUAL COLOUR DISPLAY
TEMPERATURE INDICATOR
Product Manual
Contents - Volume I
1 OPERATION MODE 1-1
1.1 FRONT PANEL 1-1
1.2 PARAMETER SEQUENCE 1-2
1.3 INPUT OVER-RANGE OR UNDER-RANGE 1-3
1.4 SENSOR BREAK 1-3
1.5 CHANGING AN ALARM VALUE 1-3
1.6 RESETTING A LATCHED ALARM 1-4
1.7 ALARM HYSTERESIS 1-4
1.8 SUMMARY OF PARAMETER IDENTIFIERS (SECONDARY DISPLAY) 1-4
2 PROGRAM MODE 2-1
2.1 ENTRY/EXIT 2-1
2.2 PARAMETER SELECTION 2-1
2.3 EDITING THE DISPLAYED PARAMETER (EDIT MODE) 2-2
2.4 PARAMETER SEQUENCE 2-3
3 SERIAL COMMUNICATIONS 3-1
3.1 DATA FORMAT/BAUD RATE 3-1
3.2 PROTOCOL 3-1
3.3 MESSAGE FORMAT 3-1
3.4 ERROR CONDITIONS 3-4

OM090-FM Volume I (iii)

1 OPERATION MODE

This mode covers day-to-day operation of the Indicator.

1.1 FRONT PANEL

59135
Key/Display/Indicator Function
Down key (Ú ) In Edit Mode, decrements the flashing digit in the Primary Display. Scroll key (Ø ) Puts Indicator into Edit Mode; in Edit Mode, selects digit to be altered
(selected digit is flashing) in Primary Display. Wrap-around occurs from right-most digit to left-most digit.
Program Key (PGM ) Selects parameter to be viewed/edited. In Edit Mode, confirms changed
parameter value.
Reset key (RST ) If the process variable is displayed, resets the latched Alarm 1. If the
Maximum (High) Value, Minimum (Low) Value or Alarm 1 Elapsed Time is displayed, resets the displayed parameter.
Down (Ú ) and Scroll (Ø ) keys
Primary Display Normally displays the process variable value. Displays other Operation
Secondary Display Shows a single-character identifier for the parameter value being
OP1 indicator ON when Alarm 1 is active. OP2 indicator ON when Alarm 2 is active.
If pressed simultaneously in Edit Mode, will abort the Edit operation and will restore the parameter to its initial value.
Mode parameters when the Program (PGM) key is used. If the Help Facility is enabled (see Subsection 2.4), this display shows the parameter description for three seconds before displaying the parameter value.
displayed (blank for process variable).
1-1 Volume I OM090-1
59135

1.2 PARAMETER SEQUENCE

OM090-1 Volume I 1-2

1.3 INPUT OVER-RANGE OR UNDER-RANGE

If the input becomes over-range or under-range, the primary display will show:
The display will disappear when the input returns within the input scale range.

1.4 SENSOR BREAK

This indicates that there is a break in the input sensor circuit.
59135

1.5 CHANGING AN ALARM VALUE

1-3 Volume I OM090-1
59135

1.6 RESETTING A LATCHED ALARM

If Relay 1 is configured to act as a latched Alarm 1 relay, when this alarm is active, it can be reset by selecting the process variable display and then pressing the Reset (RST) key. The alarm will not be reset if the alarm condition exists at the
time reset is attempted.

1.7 ALARM HYSTERESIS

The Alarm Hysteresis parameter applies a hysteresis band on the “safe” side of the Alarm value. The effect of the hysteresis value (a percentage of input span) on the operation of the different types of alarm is illustrated below:

1.8 SUMMARY OF PARAMETER IDENTIFIERS (SECONDARY DISPLAY)

Secondary Display Displayed Parameter
Blank Process variable
Maximum (High) value Minimum (Low) value Alarm 1 Elapsed Time Alarm 1 value Alarm 1 Hysteresis value Alarm 2 value Alarm 2 Hysteresis value
OM090-1 Volume I 1-4
59135

2 PROGRAM MODE

2.1 ENTRY/EXIT

Use the Program (PGM) key in the same way to exit Program Mode (i.e. return to Operation Mode).

2.2 PARAMETER SELECTION

2.2.1 With Help Facility Enabled
2-1 Volume I OM090-2
59135
2.2.2 With Help Facility Disabled

2.3 EDITING THE DISPLAYED PARAMETER (EDIT MODE)

OM090-2 Volume I 2-2

2.4 PARAMETER SEQUENCE

The Program Mode parameter sequence is as follows:
Parameter
Description
(Primary
Display)
Parameter Description Adjustment Range
59135
Re­transmission Scale Minimum
Re­transmission Scale Maximum
Process Variable Offset
Input Filter Time Constant
Comm­unications Address
The lower end of the linear scale for the re-transmission output, expressed as the value corresponding to the minimum output signal.
The upper end of the linear scale for the re-transmission output, expressed as the value corresponding to the maximum output signal.
Corrects a known offset of the input in order to display more accurately the process value.
Filters the input over a user-definable time period to minimise the effect on the process variable of any extraneous impulses
The unique serial communications address of the instrument.
19999 to 99999 −19999
19999 to 99999
19999 to 99999
0.0 (OFF) to 100.0 2.0
1 to 99 1
99999
0.00
Baud Rate Serial communications
speed
Display Colour Change
Alarm Lock Enables/disables the
Help Prompt Determines whether the
Defines the colour of the primary and secondary displays prior to/after the preset value (e.g. Alarm level) is reached.
changing of alarm values via the front panel.
Primary Display shows the parameter description for 3 seconds before a parameter value is shown.
1200, 2400, 4800 or 9600 4800
Red
Green
Green to Red
Red to Green
Enabled
Disabled
Yes
No
Green to Red
Enabled
Yes
2 -3 Volume I OM090-2
59135

3 SERIAL COMMUNICATIONS

The Serial Communications option is a standard RS485 communications link. Up to 32 standard RS485 loads may be presented to a single loop on this link. Each Indicator presents ¼ standard, therefore up to 128 may be connected to a single loop (ignoring the load presented by the master device). However, addresses are restricted to the range 1 to 99.

3.1 DATA FORMAT/BAUD RATE

Data format is fixed at one start bit, seven data bits, 1 parity bit (even parity) and 1 stop bit i.e. a 10-bit data word. Baud rates supported are 1200, 2400, 4800 and
9600. The half-duplez line turn-round time is fixed at 6ms regardless of Baud rate.
The maximum inter-character delay is 120ms. The No Reply timeout is 2 seconds.
Data is expressed as a five-digit signed hexadecimal number in which the following characters are permitted:
0 1 2 3 4 5 6 7 8 9 A B C D E F
Note that all the non-numeric characters are upper case. The detection of any characters other than these will be regarded as a syntax error. Where a value carries a decimal point, the point position is implicit and the responsibility for interpreting it lies with the user.

3.2 PROTOCOL

The protocol operates on a single master basis only. All communication is initiated by the master device.
The communications addresses available are in the range 1 - 99. Address 0 is used for broadcast Parameter Write operation messages. When a message is broadcast, the receiving instruments will attempt to implement the instruction but will not reply.

3.3 MESSAGE FORMAT

Each message starts with a Start of Message character (L) and finishes with an End of Message character (*). A reply from the addressed instrument will contain either a positive acknowledgement or a negative acknowledgement. A positive acknowledgement has the character A immediately preceding the End of Message character; a negative acknowledgement has the character N immediately preceding the End of Message character.
There are three message formats; they permit instrument identification, Parameter Read operations and Parameter Write operations.
OM090-3 Volume I 3-1
59135
3.3.1 Form 1 Message
The master device sends a Form 1 message to ascertain whether a specific communications address is occupied by an instrument. If there is an instrument at that address, a reply (with a positive acknowledgement) is received. If there is no instrument at that address or if there is a communications link failure, no reply is received. The message from the master device is of the form:
Laa??*
where aa is the address (a two-digit hexadecimal number). The reply from the addressed instrument is of the form:
Laa?A*
where aa is the same address as in the received message.
3.3.2 Form 2 Message
This message implements a Parameter Read operation. The message from the master device is of the form:
Laap?*
where aa is the address (a two-digit hexadecimal number)
p is a single-character parameter identifier (see Table 3-1)
The reply, if the Parameter Read operation is successful, is of the form:
LaapnnnnnA*
where aa is the same address as in the received message
p is a single-character parameter identifier (see Table 3-1)
nnnnn is the data (a five-digit hexadecimal number)
If the specified parameter is invalid (e.g. not applicable to the addressed instrument), the reply is of the form:
Laap00000A*
where aa is the same address as in the received message
p is a single-character parameter identifier (see Table 3-1)
3-2 Volume I OM090-3
Loading...
+ 28 hidden pages