West Control Solutions N4400 User Manual

Page 1
PROG
1
-DIN SETPOINT PROGRAMMER
4
Operator's Manual
59215-1
Page 2
PREFACE
This manual is intended for use in support of day-to-day operation of
the
-DIN Setpoint Programmer. For information on installation,
commissioning, configuration etc., refer to the associated Site Manual (see below).
Associated Documents
Title Part No.
1
-DIN Setpoint Programmer Site Manual 59xxxx
4
In normal operation, the operator must not remove the Setpoint Programmer from its housing or have unrestricted access to the rear terminals, as this would provide potential contact with hazardous live parts.
Installation and configuration must be undertaken only by personnel who are technically-competent and authorised to do so . This is covered in the Site Manual (see above).
Page 3
59215

Con tents

1 IN TRO DUC ING THE SET POINT PRO GRAM MER 1-1 2 FRONT PANEL CON TROLS, IN DI CA TORS & DIS PLAYS 2-1
2.1 CON TROLS ..................................2-1
2.2 IN DI CA TORS .................................2-2
2.3 DIS PLAYS ...................................2-3
2.4 ALARM STATUS IN DI CA TION ........................ 2-3
2.5 VIEW ING PRO GRAM AND CON TROL LER PA RAME TERS ......... 2-4
3 PRO GRAMS 3-1
3.1 SE LECT ING AND RUN NING A PRO GRAM ..................3-1
3.2 CHANG ING THE PRO GRAM TI ME BASE ...................3-1
3.3 HOLD ING A PRO GRAM MANU ALLY .....................3-1
3.4 JUMP ING TO THE NEXT SEG MENT ..................... 3-1
3.5 VIEW ING PRO GRAM PRO GRESS/STATUS .................3-2
3.6 ABORT ING A PRO GRAM ...........................3-3
3.7 “END OF PRO GRAM” IN DI CA TION......................3-3
3.8 VIEW ING PRO GRAM AND CON TROL LER PA RAME TERS ......... 3-3
4 AD JUST ING THE SET POINT 4-1 5 US ING THE SELF- TUNE FA CIL ITY 5-1 6 US ING THE PRE- TUNE FA CIL ITY 6-1 7 MAN UAL CON TROL 7-1 8 DE FIN ING AND VIEW ING A PRO GRAM (PRO GRAM DE FINE MODE) 8-1
8.1 EN TRY INTO PRO GRAM DE FINE MODE ..................8-1
8.2 PA RAME TERS COM MON TO ALL PRO GRAMS (GLOBAL)......... 8-2
8.3 PA RAME TERS WHICH AP PLY TO A SPE CIFIC PRO GRAM AS A WHOLE.8-3
8.4 PA RAME TERS IN ANY/EACH SEG MENT IN A SPE CIFIC PRO GRAM ... 8-5
8.5 US ING JOIN, RE PEAT AND END MARK ERS AND CY CLING PRO GRAMS.8-6
8.6 BA SIC RULES TO RE MEM BER........................8-8
8.7 EX IT ING PRO GRAM DE FINE MODE ..................... 8-8
59215-FM (iii)
Page 4
59215
9 DE FIN ING THE CON TROL LER PA RAME TERS (CON TROL LER DE FINE
MODE) 9-1
9.1 CON TROL LER PA RAME TERS ........................9-2
9.2 BASE MODE DIS PLAYS...........................9-10
9.3 LOOP ALARM AND LOOP ALARM TIME ..................9-10
9.4 EX IT ING CON TROL LER DE FINE MODE .................. 9-11
Al pha betic In dex
(iv) 59215-FM
Page 5

1 INTRODUCING THE SETPOINT PROGRAMMER

59215
The Setpoint Programmer is a powerful, easy-to-use capability (complete with Self-Tune/Pre-Tune facilities). Its standard features are:
Up to eight programs of up to 16 free-format (e.g. dwell, ramp, join or end)
*
segments each. Facility to join programs to one another in any sequence (maximum
*
program length 121 segments). User can change currently-running program segment.
*
Delayed Start of Program facility.
*
End of Program relay output.
*
Universal input - thermocouple, RTD (Pt100) or DC linear
*
- user- selectable). Universal power supply (90 - 264V ac 50/60Hz).
*
Configurable from front panel.
*
1
-DIN instrument with full PID control
4
Comprehensive front panel displays.
*
Front panel sealing to NEMA 4 standard.
*
Behind-panel depth only 100mm.
*
Optional features include:
Remote control and selection of program (plug-in option).
*
Up to four Event relay outputs (plug-in option).
*
Second control output.
*
Recorder output (setpoint or process variable).
*
RS485 serial communications.
*
User-definable program tag names
*
Real Time Clock
*
Support software (Off-Line Configurator, On-Line Graphic Program
*
Editor) - operates via RS485 communications link.
59215-1 Page 1-1
Page 6
59215
The Setpoint Programmer has four operating modes:
Base Mode: Day-to-day PID control operations with no program running. In this mode, a program may be selected to run.
Program Run Mode: A selected program is running, held or waiting for a pre-defined delay before starting. In this mode, the operator can view status and program information.
Program Define Mode 1: Used to view/create/edit programs. This mode is entered either from Base Mode (selected program may be edited/created) or from Program Run Mode (currently-running program may be edited).
Controller Define Mode 2: Used to define the Controller characteristics.
1 Entry via Lock Code; also optional Program Lock prevents changing of program definitions while a
program is running.
2 Entry via a Lock Code.
Page 1-2 59215-1
Page 7
59215

2 FRONT PANEL CONTROLS, INDICATORS & DISPLAYS

2.1 CONTROLS

MODE key: Changes mode of instrument.
PROG key: Cycles through Program Numbers.
Scroll key: Displays the next parameter in the sequence (indicated by
Message Display - see Subsection 2.3).
RUN/HOLD key: Runs, holds or aborts current program.
Down key: Decrements displayed parameter value/cycles through options.
Up key: Increments displayed parameter value/cycles through options.
Up and MODE keys: Selects/de-selects Self-Tune or
Pre-Tune (when Message Display shows appropriate message.
Up and PROG keys: Jumps to next segment, when a program is running.
Scroll and MODE keys: Selects/de-selects Manual Control (see Section 7).
Up and Down keys: Sets a segment to Dwell when defining a program.
59215-2 Page 2-1
Page 8
59215

2.2 INDICATORS

AT ON when Self-Tune is active; flashes when
ALM Flashes when any alarm is active. OP1 ON when primary control output is active. OP2 ON when secondary control output (if fitted)
MAN ON when Manual Control is selected.
RUN ON - Program running or (if HLD ON also)
Control Status Indicators
Pre-Tune is active.
is active.
Run Status Indicators
held Flashing - Program in Delayed state
HLD ON - Program held
Flashing - Program in Auto-Hold
x60 OFF - timebase = hours/minutes
Event Indicators
Each indicates the status (active or inactive) of a user-defined event (OFF = inactive, ON = active).
Mode Indicators
SET ON when Controller Define Mode or Program
Define Mode is entered; flashes when
viewing parameters in Controller Define
Mode or Program Define Mode after entry
from Base Mode.
PRG ON when Program Define Mode is entered.
Page 2-2 59215-2
Page 9

2.3 DISPLAYS

59215

2.4 ALARM STATUS INDICATION

When any alarm is active, the ALM indicator will flash. To view the alarm status in the Message Display, press the Scroll key until a display appears of the form:
59215-2 Page 2-3
Page 10
59215

2.5 VIEWING PROGRAM AND CONTROLLER PARAMETERS

In Base Mode (i.e. with no program currently running or held), the MODE key gives “view only” access to Program Define Mode and Controller Define Mode:
Page 2-4 59215-2
Page 11
59215

3 PROGRAMS

3.1 SELECTING AND RUNNING A PROGRAM

When no program is running, the Setpoint Programmer is in Base Mode and the RUN and HLD indicators are OFF. In this mode, select a program as follows:
1. Hold down the PROG key un til the re quired pro gram number is dis played.
2. Press the Run/Hold key once to start the pro gram. The RUN in di ca tor will then go ON; the Set point Pro gram mer is now in Pro gram Run Mode.

3.2 CHANGING THE PROGRAM TIMEBASE

Whilst a program is running, the normal timebase is hours/minutes. To change to a timebase of minutes/seconds (i.e. select the x60 facility), press the Up key for more than five seconds, whereupon the x60 indicator will go ON. To cancel operation on the x60 timebase, press the Down key for more than five seconds, whereupon the x60 indicator will go OFF.

3.3 HOLDING A PROGRAM MANUALLY

The operator may hold or freeze a program by momentarily pressing the Run/Hold key. The HLD indicator will then go ON (the RUN indicator staying ON) and the program will stop execution. The progam may subsequently be restarted by momentarily pressing the Run/Hold key again.
HLD INDICATOR FLASHING: If, before the operator holds the program manually, the HLD indicator starts flashing, this indicates that the program is currently subject to an Auto-Hold (see Subsection 8.3 and Figure 8 -1 ). If the Run/Hold key is pressed (for a manual Hold), the HLD indicator will go ON continuously. When the operator removes the manual Hold (by pressing the Run/Hold key again), the HLD indicator will either flash (indicating that the Auto-Hold conditions still prevail) or go OFF (indicating that the Auto-Hold conditions no longer exist).
RUN INDICATOR FLASHING: This indicates that the program is in a Delay state i.e. is timed to start after a user-defined delay has elapsed. When the delay period has elapsed, the program will run and the RUN indicator will come on continuously.

3.4 JUMPING TO THE NEXT SEGMENT

At any time during a program’s execution, the operator may jump forward to the next segment by simultaneously pressing the PROG and Up keys.
Note that, since pro grams may be joined or set to cy cle, jump ing past the last seg ment in a pro gram may re sult in changes in the Pro gram Num ber and Cy cle Count.
59215-3 Page 3-1
Page 12
59215

3.5 VIEWING PROGRAM PROGRESS/STATUS

In Program Run Mode, a number of displays are made available to the operator (in the Message Display area) which indicate program progress/status. Whilst the current program is running, held or delayed, press the Scroll key to cycle through a sequence of program status displays with the following legends in the Message Display:
In the case of Segment Time Remaining or Auto-Hold Time display, the time is in hours/minutes (if the x60 indicator is OFF) or minutes/seconds (if the x60 indicator is ON). The Delay Time display is always in hours/minutes.
NOTE: If the Scroll key is held for two seconds or longer, the Setpoint Programmer will auto-scroll through the above display cycle (with the exception of the Self-Tune and Pre-Tune displays). To stop the Auto-scroll, press any key other than the Scroll key.
Af ter all ap pli ca ble pro gram status/prog ress dis plays have been shown, press the Scroll key to re turn to the Base Mode dis plays.
Page 3-2 59215-3
Page 13
59215

3.6 ABORTING A PROGRAM

The operator may abort (i.e. terminate) the current program by holding down the Run/Hold key for more than five seconds. When the program is aborted, a return is made to the Base Mode and the Message Display will show:
This message will be removed by the next keypress.

3.7 “END OF PROGRAM” INDICATION

When the program has reached its End Marker, the Message Display shows:
and a return is made to Base Mode.

3.8 VIEWING PROGRAM AND CONTROLLER PARAMETERS

In Program Run Mode (i.e. with a program currently running or held), the MODE key gives “view only” access to Program Define Mode and Controller Define Mode:
59215-3 Page 3-3
Page 14
59215

4 ADJUSTING THE SETPOINT

With the Setpoint Programmer in Base Mode (i.e. with the RUN , HLD , SET and PRG indicators OFF), the two main displays will show the process variable value (upper display) and the setpoint value (lower display - Read Only). To change the setpoint value:
1. Press the Scroll key; the Mes sage Area will dis play one of:
ac cord ing to in put range.
2. Use the Up and Down keys to change the set point value (in the lower dis play) as re quired.
3. When the set point value is set as de sired, press the Scroll key again to re turn to the ini tial dis play.
Page 4-1 59215-4
Page 15
59215

5 USING THE SELF-TUNE FACILITY

The Self-Tune facility is used to optimise tuning whilst the Controller part of the Setpoint Programmer is operating. Self Tune may be activated as follows:
1. With the Set point Pro gram mer in Base Mode (with the RUN and HLD in di ca tors OFF), press the Scroll key un til the Mes sage Dis play shows:
and the lower Main Dis play shows:
2. Press the MODE and Up keys to change the lower Main Dis play to:
in di cat ing that the Self- Tune fa cil ity is now ac ti vated.
To de-activate the Self-Tune facility, press the Scroll key to obtain the same Message Display as above; then press the MODE and Up keys simultaneously to change the lower Main Display from On to OFF.
59215-5 Page 5-1
Page 16
59215

6 USING THE PRE-TUNE FACILITY

The Pre-Tune facility is used to set the Setpoint Programmer’s PID control parameters to values which are approximately correct in order to provide a base from which the Self-Tune facility may subsequently optimise tuning. Pre-Tune may be activated as follows:
1. With the Set point Pro gram mer in Base Mode (with the RUN and HLD in di ca tors OFF), press the Scroll key un til the Mes sage Dis play shows:
and the lower Main Dis play shows:
2. Press the MODE and Up keys to change the lower Main Dis play to:
in di cat ing that the Pre- Tune fa cil ity is now ac ti vated.
NOTES
1. If the process variable is within 5% of the input span from the setpoint, the Pre-Tune facility cannot be activated and any attempt to do so will have no effect.
2. Since the Pre-Tune facility is a single-shot operation, it will automatically de-activate itself once the operation is complete.
To de-activate the Pre-Tune facility manually (with the Setpoint Programmer in Base Mode), press the Scroll key to obtain the same Message Display as above; then press the MODE and Up keys to change the lower Main Display from On to OFF.
Page 6-1 59215-6
Page 17
59215

7 MANUAL CONTROL

In any mode except Configuration Mode or Calibration Mode, the operator may select manual control of the process by simultaneously pressing the Scroll and MODE keys. The Setpoint Programmer will then enter Base Mode or (if a program is currently running) Program Run Mode with the program held. The Message Display will show
and the lower Main Display will show the power output value, which may then be adjusted using the Up and Down keys. Whilst manual control is being exercised, the power output display is included in the displays available in Base Mode and Program Run Mode.
To cancel manual control, press the Scroll and MODE keys simultaneously, whereupon the power out value display and the Power Message Display will disappear and the Setpoint Programmer will remain in whatever mode prevailed when manual control was cancelled (if this is Program Run Mode, the currently-running program will be resumed from the point at which it was held).
59215-7 Page 7-1
Page 18
59215
8 DEFINING AND VIEWING A PROGRAM
(PROGRAM DEFINE MODE)
The Setpoint Programmer may be put into Program Define Mode from either Base Mode or Program Run Mode (i.e. with a program currently running).

8.1 ENTRY INTO PROGRAM DEFINE MODE

1. Press the Scroll and Up keys si mul ta ne ously. The lower Main Dis play will show 0 and the Mes sage Dis play will show:
2. Use the Up and Down keys to set the value in the lower Main Dis play to the Pro gram De fine Mode Lock Value and press the Scroll key.
The Setpoint Programmer will enter Program Define Mode, the SET and PRG indicators will go ON and the operator will be able to edit programs and segments. The MODE key can then be used (a) to switch to Controller Define Mode (see Section 9), and then (b) to show a Message Display:
To return to Program Define Mode (and re-start the Program Define/Controller Define/Exit? display cycle), press the MODE key; to return to Base Mode, press the Scroll key.
If an incorrect lock value is entered, the Setpoint Programmer will return to Base Mode. Program parameters are divided into three categories:
(a) Those com mon to all pro grams - global pa rame ters (b) Those com mon to all seg ments in a spe cific pro gram (c) Those rele vant to a spe cific seg ment in a spe cific pro gram
Upon entry into Program Define Mode, the operator will be presented with the first of a sequence of parameter displays (see following Subsections). The operator may then step through the sequence, using the Scroll key. The displayed Program Number may be changed using the PROG key and the displayed Segment Number may be changed using the Run/Hold key.
NOTE: If en try is made from Pro gram Run Mode and Pro gram Lock is On, only Con trol ler De fine Mode will be ac ces si ble.
Page 8-1 59215-8
Page 19

8.2 PARAMETERS COMMON TO ALL PROGRAMS (GLOBAL)

59215
Parameter Message
Function Available Settings
Display
Start On Setpoint value at start of each
program
End On Setpoint value at end of each
program
Delay Time Delay (hours/minutes) between
program initiation and program
start
Program Lock Operator changes permitted to
program definitions whilst a
program is running/held?
Power Fail
Recovery
RTC Time
4
Response to restoration of power
after a power failure
Real Time Clock initial setting
(hours.minutes)
RTC Day
4
Real Time Clock initial setting
(day of week)
External
Selection
Lock Code
5
Functions which may be
controlled externally
Lock Code for Program Define
Mode
(Lower Main Display)
Current SP
Current PV
Final SP
1
Controller SP
Numerical value (decimal point id de-limiter between hours and minutes)
Not permitted
Permitted
0.000 or 1.000 if no RTC;
0.00 or Time (0.01 - 24.00) if RTC fitted.
0.00 = Cold Start
1.00 or Time = Warm Start
2
3
0.10 - 24.00
Sun, Mon, tuE, WEd, thu, Fri or SAt
No external selection
Program selection only
Run, Hold, Abort, x60 functions only
All program and run control selections
0 - 9999. Default = 10.
1 The final setpoint value for the End Marker of each program - see Subsection 8.4. 2 Cold Start = Base Mode with Program No. as when power failed and Segment No. blank. 3 Warm Start = resumption from point when power failed (with RTC, if time has not expired,
otherwise Cold Start). 4 Available only if RTC option fitted. 5 Only applicable if Setpoint Programmer is configured to have two lock codes.
59215-8 Page 8-2
Page 20
59215
8.3 PARAMETERS WHICH APPLY TO A SPECIFIC PROGRAM AS A
WHOLE
Parameter Message
Display
Cycle Count Defines the number of times a
program will be executed
Auto Hold Selects operation of Auto Hold
facility (relative to setpoint) - see
Hold Band Defines the width of the Hold
Hold on Defines whether the Auto Hold
facility is used on Ramps only, on
Dwells only or on both Ramps
Pre-x60 Defines whether the timebase for
the program is pre-selected to be
Function Available Settings
Figure 8-1.
Band - see Figure 8-1
and Dwells
hours/minutes or minutes/seconds
(Lower Main Display)
1 - 9999 Program will execute the
set number of cycles Program will repeat
indefinitely No Auto Hold
Auto Hold above SP only
Auto Hold below SP only
Auto Hold above and below SP
Numerical value - 0 to span
Auto Hold on Ramps and Dwells
Auto Hold on Dwells only
Auto Hold on Ramps only
No pre-selection
Minutes/seconds
Hours/minutes
Timer
(RTC only)
Start Hour
(Timer On)
Start Day
(Timer On)
Selects/de-selects timer control of
program
Defines start time for program 24.00 (0.00) to 23.59
Defines day(s) for program to be
run
Sun , Mon , tuE , WEd , thu , Fri, SAt, 5 dY (Mon - Fri), 6 dY (Mon
- Sat) or ALL (all seven days of the week)
or
This se quence may be viewed/ed ited for any pro gram by sim ply chang ing the Pro gram Num ber with the PROG key, then step ping through the pa rame ters with the Scroll key.
Page 8-3 59215-8
Page 21
59215

Fig ure 8-1 Auto Hold Op era tion

59215-8 Page 8-4
Page 22
59215
8.4 PARAMETERS IN ANY/EACH SEGMENT IN A SPECIFIC
PROGRAM
Parameter Message
Display
Final Setpoint
Value
(a) Segment
Time or (b)
Ramp Rate, as
selected in
Configuration
Mode (see Site
Manual)
7
Event
appropriate
or
as
Function Available Settings
Defines the final setpoint value for
this segment, selects a Dwell
segment or indicates a Join,
Repeat or End Marker
Defines (a) the duration in
hours.minutes (x60 OFF) or
minutes.seconds (x60 ON) or (b)
ramp rate in units/hour (x60 OFF)
or units/minute (x60 ON) for this
segment, or (c) whether it is a
Join Marker, Repeat Marker or
End Marker
Defines the states of the four
event outputs for this segment
6
(Lower Main Display)
Numeric value (limited by SPHi and SPLo) or (by pressing the Up and Down keys simultaneously) indicates a Dwell segment with:
or, if the segment is already a Join, Repeat or End Marker, as shown below.
Four-digit number (a) nn.nn (00:00 to 99.59) for Segment Time, (b) nnnn (0000 to 9999) for Ramp Rate or (c) negative values as follows:
J01 Join to Program 1 J02 Join to Program 2 J03 Join to Program 3 J04 Join to Program 4 J05 Join to Program 5 J06 Join to Program 6 J07 Join to Program 7 J08 Join to Program 8 REP Repeat Marker End End Marker
Four-bit binary number (0 - inactive, 1 = active):
6 If a segment is set to be a Join Marker, a Repeat Marker or an End Marker, the next depression of
the Scroll key will set the Segment Number to A and the first parameter common to the whole
program (Cycle Count - see Subsection 8.3) will be displayed. Otherwise, the next depression of
the Scroll key will display the next segment parameter - Event (for the current segment) if the Eve nt
Output hardware is fitted. 7 This parameter appears in the sequence only if the Event Output hardware is fitted, in which case
this parameter will be followed by the Final Setpoint Value parameter for the next segment. If the
Event Output hardware is not fitted, this parameter will be omitted from the parameter sequence
and the Segment Number will be advanced, causing the Final Setpoint Value parameter for the
next segment to appear immediately.
Page 8-5 59215-8
Page 23
59215
CANCELLING JOIN, REPEAT OR END MARKERS To cancel a Join, Repeat or End Marker:
(a) at the Fi nal Set point Value pa rame ter, press the Up and Down keys si mul ta ne ously to pro duce a Dwell seg ment, or
(b) at the Seg ment Time/Ramp Rate pa rame ter, in cre ment the value to 0 or a posi tive value.
8.5 USING JOIN, REPEAT AND END MARKERS AND CYCLING
PROGRAMS
By default, the Setpoint Programmer has eight programs, each 16 segments long (all 16 segments are active and, at the end of Segment 16 is an implicit End Marker). These programs can be made shorter (using End Markers) or longer (by creating program sequences with Join, Repeat and End Markers). The only limit to the size of a program sequence is a maximum length of 121 active segments plus seven Join Markers plus one End Marker (i.e. all eight programs joined to make one program sequence).
Segments follow a free format in that ramp or dwell can be followed by dwell or ramp, completely as desired.
Consider two example programs:
To join the two programs to form a program sequence, change the End Marker of Program 1 to a Join Marker (Segment Time/Ramp Rate set to J02 - Join Program 2):
59215-8 Page 8-6
Page 24
59215
There are no restrictions on joining programs; several programs can be joined to one program (e.g. to provide user-selectable warm-up programs, depending upon which program is run first).
The Cycle feature can be used to make more complex program sequences. Consider the two simple example programs previously described:
and consider the case in which Program 1 is set to perform two cycles and is joined to Program 2. When Program 1 is run, the result would be:
If Program 2 were now set to perform ten cycles, the result would be:
Now, with Pro gram 2 set to per form ten cy cles, if the the End Marker of Pro gram 2 were changed to a Re peat Marker (Seg ment Time/Ramp Rate set to REP), the re sult would be:
Page 8-7 59215-8
Page 25
At the end of the tenth cycle of Program 2, the program sequence would end.

8.6 BASIC RULES TO REMEMBER

In any program sequence:
59215
A pro gram end ing in a Join Marker will per form the re quired number
*
of cy cles of it self be fore join ing the new pro gram. A pro gram end ing in a Re peat Marker (hence, by defi ni tion, the last
*
pro gram in the se quence) will per form the re quired number of cy ­cles of it self be fore end ing the se quence.
A pro gram end ing in an End Marker (hence, by defi ni tion, the last
*
pro gram in the se quence) will per form its cy cle count on the en tire pro gram se quence be fore end ing that se quence.

8.7 EXITING PROGRAM DEFINE MODE

Press the MODE key until the Exit ? prompt appears in the Message Display, then press the Scroll key, which will cause a return to the mode from which entry was made.
NOTE: An auto matic re turn is made if there is no key ac tiv ity in Pro gram De fine Mode for five min utes.
59215-8 Page 8-8
Page 26
59215
9 DEFINING THE CONTROLLER PARAMETERS
(CONTROLLER DEFINE MODE)
Entry can be made into this mode from Program Define Mode, Program Run Mode or Base Mode.
To enter from Base Mode or Program Run Mode:
1. Press the Scroll and Up keys si mul ta ne ously. The lower Main Dis play will show 0 and the Mes sage Dis play will show:
2. Use the Up and Down keys to set the value in the lower Main Dis play to the Lock Code value (for Pro gram De fine Mode) and press the Scroll key. The Set point Pro gram mer is now in Pro gram De fine Mode.
NOTE: If an incorrect Lock Code Value is entered, the Setpoint Programmer will return to its original mode (i.e. Base Mode or Program Run Mode).
3. Press the MODE key. If the Set point Pro gram mer has been con fig ured to have only one Lock Code, en try into Con trol ler De fine Mode is im me di ate and no fur ther ac tion need be taken. If the Set point Pro gram mer is con fig ured to have two lock codes (one for Pro gram De fine Mode, one for Con trol ler De fine Mode), the lower Main Dis play will show 0 and the Mes sage Dis play will show:
4. Use the Up and Down keys to set the value in the lower Main Dis play to the Lock Code value (for Con trol ler De fine Mode) and press the Scroll key.
The Set point Pro gram mer is now in Con trol ler De fine Mode.
NOTE: If an incorrect Lock Code value is entered, the Setpoint Programmer will return to its original mode (i.e. Base Mode,
Program Run Mode or Prorgam Define Mode). To enter from Program Define Mode, perform Step 3 (and, if necessary, Step 4) above. Upon en try into Con trol ler De fine Mode, the SET in di ca tor will come ON and the first of the
Con trol ler pa rame ters (In put Fil ter Time Con stant) will be pre sented for ed it ing/view ing . Us ing the Scroll key, step through the se quence of Con trol ler pa rame ters, ed it ing as re quired (us ing the Up/Down keys).
Page 9-1 59215-9
Page 27

9.1 CONTROLLER PARAMETERS

The Controller parameters appear in the following sequence:
59215
Parameter Message
Function Available Settings/Values
Display
Input Filter Time Constant
Defines time constant for input filter (removes extraneous impulses from the process variable input
Process Variable
1
Offset
Modifies actual PV value: Offset PV + Actual PV = PV used
Output 1 Power Indicates current Output 1
power level.
Output 2 Power
2
Indicates current Output 2 power level.
Proportional Band 1 (PB1)
Defines portion of input span in which the Output 1 power level is proportional to the (offset) process variable value (see Figure 9-1).
Proportional Band 2 (PB2)
Defines portion of input span in which the Output 2 power level is proportional to the (offset) process variable value (see Figure 9-1).
3
Reset Rate
3
Integral Time Constant 1sec. to 99mins. 59secs. Derivative Time Constant 00secs. to 99mins. 59secs.
(Lower Main Display)
0.0secs. (filter OFF) to
100.0secs. on 0.5-sec. increments.
Default = 2.0secs.
For linear input, limited by Scale Range Max. and Scale Range Min.
Default = 0.
Read Only
Read Only
0.0% (ON/OFF control) to
999.9% of input span.
Default = 10%.
0.0% (ON/OFF control) to
999.9% of input span.
Default = 10%.
Overlap or Deadband
4
Defines the proportion of the Proportional Band (PB1 + PB2) over which both outputs are active (Overlap) or neither
20% to +20% (negative value = Deadband, positive value = Overlap)
Default = 0%.
output is active (Deadband) ­see Figure 9-1.
Bias (Manual Reset)
ON/OFF Differential
3
5
Bias applied to output power, expressed as a percentage of output power.
Switching differential for one output (Diff 1 or Diff 2 ) or both
0% to 100% (Output 1 only);
100% to +100% (Output 1 & Output 2)
0.1% to 10.0% of input span.
Default = 0.5%.
outputs (Diff) set to ON/OFF control (PB1, PB2 or both = 0%)
Setpoint High
6
Limit
The maximum limit for setpoint adjustment. Should be set to a
value which prevents setpoint
Current setpoint value to Input Range Maximum.
Default = Input Range Max.
values causing damage to the process.
59215-9 Page 9-2
Page 28
59215
Parameter Message
Setpoint Low
6
Limit
Motor Travel
11
Time Minimum Motor
ON Time
Recorder Output Scale Maximum
Recorder Output Scale Minimum
Output Power Limit
11
7
7
3
Display
Function Available Settings/Values
The minimum limit for setpoint adjustment. Should be set to a
value which prevents setpoint values causing damage to the process.
Time taken for valve to travel from one end stop to the other
Minimum drive effort required to initiate movement in a stationary valve
The value of the process variable or setpoint (as applicable) for which the recorder output is a maximum.
The value of the process variable or setpoint (as applicable) for which the recorder output is a minimum.
Limits the power level of Output 1 (used to protect the process)
(Lower Main Display)
Input Range Minimum to current setpoint value.
Default = Input Range Min.
5secs. to 5mins.
Default = 1min.
0.0secs. to (Motor Travel Time + 10).
Default = 1.0sec.
1999 to 9999 (decimal point position as per process variable input range).
Default = Input Range Max.
1999 to 9999 (decimal point position as per process variable input range).
Default = Input Range Min.
0% to 100%.
Output 1 Cycle
8
Time
Output 2 Cycle
8
Time
Process High Alarm 1 value
Process Low Alarm 1 value
Band Alarm 1 value
Limits the frequency of operation of the output relay to optimise relay life
Limits the frequency of operation of the output relay to optimise relay life
If Alarm 1 is a Process High Alarm, this defines the level of the process variable at or above which Alarm 1 will be active (see Figure 9 -2 )
If Alarm 1 is a Process Low Alarm, this defines the level of the process variable at or below which Alarm 1 will be active (see Figure 9 -2 )
If Alarm 1 is a Band Alarm, this defines the band of process variable value (centred on the setpoint) outside which the process variable will cause the alarm to become active (see Figure 9-2).
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512secs.
Default = 30secs.
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512secs.
Default = 30secs.
Input Range Maximum to Input Range Minimum.
Default = Input Range Max.
Input Range Minimum to Input Range Maximum.
Default = Input Range Min.
± (input span) from setpoint.
Default = 5 input units.
Page 9-3 59215-9
Page 29
59215
Parameter Message
Deviation (High/Low) Alarm 1 value
Alarm 1 Hysteresis value
Process High Alarm 2 value
Process Low Alarm 2 value
Display
Function Available Settings/Values
If Alarm 1 is a Deviation (High/Low) Alarm, this defines a level above (positive value) or below (negative value) the setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 9-2)
Defines a hysteresis band on the "safe" side of the Alarm 1 value (see Figure 9-3).
If Alarm 2 is a Process High Alarm, this defines the level of the process variable at or above which Alarm 2 will be active (see Figure 9 -2 )
If Alarm 2 is a Process Low Alarm, this defines the level of the process variable at or below which Alarm 2 will be active (see Figure 9 -2 )
(Lower Main Display)
±(input range) from setpoint.
Default = 5 input units.
1 LSD to 10% of input span (0 is an invalid value).
Input Range Maximum to Input Range Minimum.
Default = Input Range Max.
Input Range Minimum to Input Range Maximum.
Default = Input Range Min.
Band Alarm 2 value
Deviation (High/Low) Alarm 2 value
Alarm 2 Hysteresis value
Loop Alarm Enable
If Alarm 2 is a Band Alarm, this defines the band of process variable value (centred on the setpoint) outside which the process variable will cause the alarm to become active (see Figure 9-2).
If Alarm 2 is a Deviation (High/Low) Alarm, this defines a level above (positive value) or below (negative value) the setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 9-2)
Defines a hysteresis band on the "safe" side of the Alarm 2 value (see Figure 9-3).
Enables/disables Loop Alarm (see Subsection 9.3).
± (input span) from setpoint.
Default = 5 input units.
±(input range) from setpoint.
Default = 5 input units.
1 LSD to 10% of input span (0 is an invalid value).
0 (disabled) or 1 (enabled).
Default = 0 (disabled).
59215-9 Page 9-4
Page 30
59215
Parameter Message
Function Available Settings/Values
Display
Loop Alarm Time If ON/OFF control is selected
(i.e PB1 = 0) and Loop Alarm is enabled, this defines the duration of the saturation condition after which the Loop Alarm is activated (see Subsection 9.3)
Scale Range Decimal Point Position
Scale Range Maximum
9
9
For linear inputs, defines the decimal point position.
For linear inputs, defines the scaled input value when the process variable input is at its maximum value.
Scale Range Minimum
9
For linear inputs, defines the scaled input value when the process variable input is at its minimum value.
(Lower Main Display)
1sec. to 99mins. 59secs.
Default = 99mins. 59secs.
0 (xxxx) 1 (xxx.x) 2 (xx.xx) 3 (x.xxx)
Default = 1 (xxx.x)
1999 to 9999 (decimal point position as defined by Scale Range Decimal Point Position parameter).
Default = 100.0
1999 to 9999 (decimal point position as defined by Scale Range Decimal Point Position parameter).
Default = 0.0
Auto Pre-Tune Enable/Disable
Determines whether the Pre-Tune facility is activated
OFF = disabled; On = enabled.
Default = OFF (disabled).
automatically at power-up.
Manual Control Enable/Disable
Communications Write Enable/Disable
Lock Value
12
10
or
Enables/disables operator selection of Manual Control.
Enables/disables changing of parameter values or settings via the RS485 Communications link
Defines the four-digit code required to enter Controller
OFF = disabled; On = enabled.
Default = OFF (disabled).
OFF = disabled; On = enabled.
Default = OFF (disabled).
0 to 9999.
Default = 10.
Define Mode (and, if a common lock code is used, Program Define Mode).
NOTES ON CONTROLLER DEFINE MODE PARAMETERS
1. The Process Variable Offset value should be chosen with care. Any adjustment to this parameter is, in effect, a calibration adjustment. Injudicious application of values to this parameter could lead to the displayed process variable value bearing no meaningful relationship to the actual process varia ble value. There is no front panel indication when this parameter is in effect (i.e. has been set to a
non-zero value).
2. These parameters are applicable only if the secondary Control (COOL) ooutput is fitted.
3. These parameters are not applicable if Proportional Band 1 is set to 0 (i.e. ON/OFF control for Output 1).
4. This parameter is not applicable if Proportional Band 1 is set to 0 or if Output 2 (COOL) is not fitted.
5. The Message Display will show Diff 1 for ON/OFF control on Output 1, Diff 2 for ON/OFF control on Output 2 or Diff for ON/OFF control on both Output 1 and Output 2.
Page 9-5 59215-9
Page 31
59215
NOTES ON CONTROLLER DEFINE MODE PARAMETERS (Cont.)
6. Internal software prevents (a) the Setpoint High Limit being given a value less than any setpoin t value contained in currently-resident programs, and (b) the Setpoint Low Limit being given a value greater than any setpoint value contained in currently-resident programs.
7. Thes parameters are not applicable if the Recorder Output Option is not fitted.
8. Output 1 Cycle Time is not applicable if Proportional Band 1 is set to 0 or if Output 1 is a DC Linear output. Output 2 Cycle Time is not applicable if Proportional Band 1 is set to 0, if Proportional B and 2 is set to 0, if Outptu 2 is not fitted or if Output 2 is a DC Linear output.
9. These parameters are applicable only if a linear input is fitted.
10. Applicable only if the RS485 Communications Option is fitted.
11. Applicable to Valve Motor Drive control only.
12. If the Setpoint Programmer is configured to have only one lock Code (Message Display will show Lock ), this value is used to enter Program Define Mode and Controller Define Mode. If two lock codes are to be used (Message Display will show Lock C), this value applies to Controller Define Mode only.
59215-9 Page 9-6
Page 32
59215

Fig ure 9-1 Pro por tional Band and Dead band/Over lap

Page 9-7 59215-9
Page 33
59215

Fig ure 9-2 Alarm Operation

59215-9 Page 9-8
Page 34
59215

Fig ure 9-3 Alarm Hys tere sis Operation

Page 9-9 59215-9
Page 35
59215

9.2 BASE MODE DISPLAYS

Once the complete cycle of Controller Define Mode parameters has been displayed, the user may then step through the Base Mode displays (controller setpoint - alarm status ­Self Tune - Pre-Tune), making adjustments where required, before re-starting the Controller Define Mode parameter cycle.

9.3 LOOP ALARM AND LOOP ALARM TIME

The Loop Alarm is a special alarm which detects faults in the control feedback loop by continuously monitoring process variable response to the control output(s).
The Loop Alarm facility, when enabled, repeatedly checks the control output(s) for saturation i.e. either or both outputs being at the maximum or minimum limit. If an output is found to be in saturation, the Loop Alarm facility starts a timer; thereafter, if the saturated output has not caused the process variable to be corrected by a pre-determined amount V after a time T has elapsed, the Loop Alarm goes active. Subsequently, the Loop Alarm facility repeatedly checks the process variable and the control output(s). When the process variable starts to change value in the correct sense or when the saturated output comes out of saturation, the Loop Alarm is de-activated.
For PID control, the Loop Alarm Time T is always set to twice the value of the Reset (Integral Time Constant) parameter. For On/Off control, the user-defined value of the Loop Alarm Time parameter is used.
The value of V is dependent upon the input type:
o
C ranges: 2oC or 2.0oC
o
F ranges: 3oF or 3.0oF
Lin ear ranges: 10 least sig nifi cant dis play units
For single output Controllers, the saturation limits are 0% and Output Power Limit. For dual output Controllers, the saturation limits are –100% and Output Power Limit.
NOTES
1. Correct operation of the Loop Alarm depends upon reasonably
accurate PID tuning.
2. The Loop Alarm is automatically disabled during Manual Control
Mode and during execution of the Pre-Tune facility. Upon exit from
Manual Control Mode or after completion of the Pre-Tune routine,
the Loop Alarm is automatically re-enabled. When full ON/OFF con trol is se lected (i.e. Pro por tional Band 1 is set to 0) and Loop Alarm
is en abled, the Loop Alarm Time pa rame ter de ter mines the du ra tion of the satu ra tion con di tion af ter which the Loop Alarm will be ac ti vated. It may be ad justed within the range 1 sec ond to 99minutes 59 sec onds. This pa rame ter is omit ted from the dis play se quence if ON/OFF con trol is not se lected or Loop Alarm is dis abled. The de fault set ting is 99:59.
59215-9 Page 9-10
Page 36
59215

9.4 EXITING CONTROLLER DEFINE MODE

The operator may exit from Controller Define Mode by pressing the MODE key until the Exit ? prompt appears in the Message Display, then pressing the Scroll key, which will
cause a return to the mode from which entry was made.
NOTE: An auto matic re turn is made if there is no key ac tiv ity in Con trol ler De fine Mode for five min utes.
Page 9-11 59215-9
Page 37

Al pha betic In dex

59215
A
Aborted Program
Indication of 3-3
Alarm Status
Display of 2-3, 3-2
ALM Indicator
Function 2-2
AT Indicator
Function 2-2
Auto-Hold
Indication of 3-1
Auto-Hold Time
Display of 3-2
Auto-Scroll Feature 3-2
C
E
End Marker
Cancellation of 8-6
End of Program Sequence
Indication of 3-3
Event Indicators
Functions 2-2
F
Front Panel Displays
Functions 2-3
Front Panel Keys
Functions 2-1
H
HLD Indicator
Function 2-2
Control Status Indicators
Functions 2-2
Controller Define Mode
Entry from Base Mode or Program Run Mode 9-1
Entry from Program Define Mode 9-1
Indication of entry 9-1
Controller Define Mode Parameters
"Read Only" access from Base Mode 2-4
"Read Only" access from Program Run Mode 3-3
D
Delay State
Indication of 3-1
Delay Time Remaining
Display of 3-2
J
Join Marker
Cancellation of 8-6
L
Loop Alarm
Description 9-10
Loop Alarm Time
Definition 9-10
M
MAN Indicator
Function 2-2
Manual Control
Front panel display 7-1 Selection/de-selection 7-1
Manual Program Hold
Indication of 3-1
59215-IDX 1
Page 38
59215
Mode Indicators
Functions 2-2
N
Next Segment
Jump to 3-1
Number of Cycles Completed
Display of 3-2
O
OP1 Indicator
Function 2-2
OP2 Indicator
Function 2-2
P
Pre-Tune Facility
Limitations on use 6-1
Program Timebase
Changing 3-1
R
Repeat Marker
Cancellation of 8-6
RUN Indicator
Function 2-2
Run Status Indicators
Functions 2-2
S
Segment Time Remaining
Display of 3-2
Self-Tune Facility
Selection/de-selection 5-1 Status Display 3-2
Selection/de-selection 6-1 Status display 3-2
PRG Indicator
Function 2-2
Program Define mode
Indication of 8-1
Program Define Mode
Entry into 8-1 Global parameters 8-2 Parameters specific to a segment
8-5
Program Define Mode Parameters
"Read Only" access from Base Mode 2-4
"Read Only" access from Program Run Mode 3-3
Program Running 3-1
SET Indicator
Function 2-2
Setpoint
Adjustment of4-1
X
x60 Indicator
Function 2-2
Program Selection 3-1 Program Tag
Display of 3-2
2 59215-IDX
Loading...