Multiple transmitter and temperature controller KS 816
Multiple transmitter and temperature controller KS 816
49499 040 55811
Multiple transmitter and temperature controller KS 816
1Safety hints
Following the enclosed safety hints 9499 047 07101 is indispensable!
For hints on the mains unit to be used, see section 4.3 Power supply.
1.1 Electromagnetic compatibility
The unit conforms to European guideline 89/336/EEC and is provided with CE marking. The following European generic standards are met:
Electromagnetic emission: EN 50081-1 and electromagnetic immunity: EN
50082-2
For compliance with EN50082-2, the analog input leads must be screened.
The unit is suitable for use in industrial areas (in residential areas, it may cause RF
interference). The electromagnetic emission can be reduced decisively by installing
the unit in a grounded metal control cabinet).
9499 040 55811
5
Multiple transmitter and temperature controller KS 816
2General
KS 816 is a microcomputer-based multi-loop temperature controller. Functions "setpoint reduction" and "heating/cooling with four alarms" make it particularly suitable
for temperature control on plastics processing machinery, heated moulds, packaging machines, tempering units and similar thermal processes. With high-power
heating elements (e.g. in hot-runner moulds), the selectable functions “start-up circuit” and “output hold” in case of sensor break ensure increased element life and
prevent interruptions during production. The self-tuning feature guarantees very
short start-up times.
2.1 Versions
This operating note is valid for three versions, which are only distinguished by the
communication interface.
9407 481 00001KS 816-RS with RS485 / RS422 interface and
ISO 1745 protocol
9407 481 30001KS 816-DP for Profibus DP (in preparation)
9407 481 60001KS 816-CAN for CANopen
69499 040 55811
3Installation
3.1 Mounting
Multiple transmitter and temperature controller KS 816
KS 816 is provided for mounting on rails 35 x 7,5 (top-hat rail) to EN 50 022,
EN 50 035, EN 50 045.
Grounding is via a spring on the top-hat rail. Therefore, note that there must be a
good conducting connection with the grounded mounting wall (layer of lacquer instead of conducting mounting wall, Eloxal, ...). If necessary, the clip-on rail must be
grounded with a separate connection.
Single unit: For mounting, pull the two lateral catches upwards by approx. 5 mm
via a stop and snap the unit onto the rail.
Press the catches down to fix the unit to the rail.
Several units: For mounting several units side by side, snap the first unit onto the
rail and lock only the side at which no further unit must be mounted. Mount the second unit accordingly, approx. 2 cm beside the first one, and connect it to the first
one by shifting it laterally (pins locked into position). Press down the second catch
of the first unit only now.
9499 040 55811
7
Multiple transmitter and temperature controller KS 816
3.2 Dismounting
For dismounting, the leads need not be disconnected. Before removing the upper
parts of the connectors, the upper parts and the corresponding lower parts must be
marked, because these terminals are distortion-proof but not confusion-proof. For
releasing the upper part of a terminal, the two red ejectors of a terminal row must
be pressed towards the p.c.b. using a screwdriver, if necessary. To release the unit
from the mounting rail, pull the two lateral catches forwards by approx. 5 mm (unit
is released) and remove the unit from the rail by tipping it upwards or downwards.
For replacing an “inner” unit of several ones mounted side by side, start by releasing the catch of a unit (and the catch of the next one!) at one end of the row and
shift the unit laterally. Repeat this procedure up to the unit to be replaced. When its
catches are released at both sides, it can be removed from the rail by tipping it up
or downwards.
89499 040 55811
Multiple transmitter and temperature controller KS 816
4Electrical connection
• The max. permissible voltage against ground of the input and signal leads is 50
Veff.
• Power supply leads must be kept separate from signal and input leads.
• For output protection and interference suppression, connected contactors must
be provided with protective circuitry to manufacturer specifications.
4.1 Terminals
All terminals leading to the process are designed as (plug-in type) screw or
screwless spring-clamp terminals.
The terminals are not delivered with the unit and must be ordered separately.
Make: PHOENIX COMBICON
Two types are available:
Screw terminal5 x FRONT-MSTB 2,5/18-ST-5,08 1 x FRONT-MSTB 2,5/8-ST-5,08
PMA order no.
Spring-clamp terminal
PMA order no.
9407 799 000019407 799 00011
5 x FK-MSTBP 1,5/18-ST-5,088-pole only screw terminals
- - - - - - - - - - - -
Note: The spring-clamp terminals are shown in the KS 816 figures. These have a
separate "test socket".
With screw terminals, the screw heads are used for test measurements.
Spring-clamp terminal5 x connector strip CAGE CLAMP connection
WAGO-order-no. 231-318/026-000
PMA-order-no. 9463 000 05341
1 x connector strip with CAGE CLAMP connection
WAGO-order-no. 231-308/026-000
PMA-order-no. 9463 000 05321
Connecting capacityonly one conductor: 0,08 - 2,5 mm
2
, single-wire,
multi-wire, fine wire,
end crimp, cable shoe
9
Multiple transmitter and temperature controller KS 816
Galvanic isolations
The KS 816 galvanic isolations are shown below:
Identical block shading means that the blocks are galvanically connected. (All inputs are galvanically connected.)
4.3 Power supply
KS 816 is designed for 24V DC nominal supply voltage, range 18V to 30V, 5%
ripple. The supply voltage must meet the conditions for protective low voltage
(SELV) to CEI 364-4-41 [VDE 0100-410].
Power supply load by one KS 816:approx. 5 W
Energization is via terminals 7 (+) and 8 (-) of connector X3.
.
4.4 Fuses
Each unit must be protected with a separate 2A slow-blowing fuse (fitted in the terminal). We recommend using terminals with built-in fuses.
Unless LED "PWR" is lit with the supply voltage applied (check fuse and polarity),
the unit is defective and must be returned to the manufacturer.
109499 040 55811
5Inputs
Multiple transmitter and temperature controller KS 816
(The complete KS 816 connecting diagram is given in section 7.).
Illustrations with connecting examples are given in section 5.6.
For all inputs, the following rules are applicable:
Unused inputs must be short-circuited!
Thermocouples and DC voltage:
Terminal + and - of an input must be connected.
Resistance thermometer:
Configure unused controllers as for thermocouples or voltage. Shortcircuit
the + and - terminal of an input.
The inputs of channel 1...16 are the process value inputs of individual channels and
can be configured for thermocouple, resistance thermometer or voltage.
Within an instrument, "mixed operation" of inputs is possible.
Accordingly, each individual channel can be configured freely for controller (continuous, 2- or 3-wire) or for transmitter (0...20mA or 4...20mA) operation.
The following thermocouple types to DIN/EN 60584 can be connected:
Thermocouple
type
L
J
K
N
S
R
T
W *)
E
*) not to DIN/EN
The upper measuring limit of KS 816 is defined by the upper temperature limit of
the thermocouple type. The thermocouples are monitored for wrong polarity and
break. The action can be configured (upscale/downscale).
All thermocouples must be connected with correct polarity to terminals INx+ and
INx-.
With thermocouples to DIN 43710, the plus arm is red and the minus arm corresponds to the thermocouple colour.
Acc. to DIN/IEC 584, the plus arm has the colour of the thermocouple type and the
minus arm is white.
Multiple transmitter and temperature controller KS 816
The controller inputs are not galvanically isolated. Therefore, thermocouple measurements above approx. 700°C and unsuitable thermocouples imply a risk of measurement errors.
This effect is due to the fact that the isolation value between protective tube and
thermocouple, dependent of construction type and insulation material, decreases to
values of some kOhm from these values. Additionally, ionization of hot gases can
cause potential differences between the thermocouples, which can cause measurement errors or trouble due to compensating currents.
For the same reason, there may be problems when using mixed grounded and insulated thermocouples.
The max. permissible potential difference between thermocouples is 7V
We urgently recommend to avoid using mixed thermocouples.
If using grounded and insulated thermocouples in an installation should be
unavoidable due to other reasons, the negative arm of the insulated thermocouple must be grounded at KS 816.
.
pp
Already grounded thermocouples must not be grounded for a second time!
When replacing insulated thermocoupl es by non-insulated ones, removing
the ground connection of the negative arm at KS 816 is indispensable.
5.1.1 Cold junction temperature compensation
The four possibilities of temperature compensation are:
1. The temperature compensation is ineffective (for PT 100- or U/I inputs)
2. Internal temperature compensation. Compensating lead is used up to the
KS 816.
3. External temperature compensation. Compensating lead is used only up to the
cold junction reference, the lead between reference and KS 816 can be of copper
4. Cold junction reference remote measurement. Input IN16 can be configured so
that it operates as input of the temperature sensor of a remote cold junction reference.
The thermocouples of the individual channels are taken up to a common reference
by means of compensating leads. The lead between reference and KS 816 can be
of copper. The 16
correcting the input voltage accordingly. Because of the measuring accuracy, the
sensor should be a resistance thermometer. When using this temperature compensation method in an installation with several KS 816 units, this method mut be used
for each individual unit.
th
input is used for measuring the reference temperature and for
129499 040 55811
Multiple transmitter and temperature controller KS 816
5.2 Direct voltage
5.2.1 Range :-100mV...+100mV IN1T+...IN16T+
Direct voltages up to 100 mV can be connected instead of the thermocouples.
These values can be scaled via corresponding software settings.
The input resistance is approx. 100 kOhm.
5.2.2 Range : -10V...+10V IN1U+...IN16U+
Inputs INxU+ are provided for direct voltages within -10V and +10V.
These values can be scaled via corresponding software settings.
The input resistance is approx. 100kOhm.
Type PT 100 resistance thermometers acc. to DIN/IEC 751 can be connected in 2
or 3 wire circuit.
The max. measuring range is -100,0 ... 850,0°C, temperature-linear.
3-wire connection is possible without lead resistance adjustment, provided that the
cross-section of individual wires is equal.
With 2-wire connection, a calibrating resistor corresponding to the lead resistance
must be included. (If possible, 2-wire connection should not be used.)
The sensor is monitored for short circuit or break.
The action (upscale/downscale) is configurable.
5.4 0/4...20mA standard current signal (INI1+...INI16-)
For 0/4...20mA standard current signal. The values can be scaled via corresponding software settings.
The input resistance is 5 Ohm, i.e. the voltage requirement is 100 mV.
When operating KS 816 with current inputs, interlock diodes at the terminals must
be provided so that the current is not cut off when removing the terminals.
5.5 Screening of input leads
With long leads and/or considerable interference, we recommend using screened
connecting leads. The two methods for connecting the screening are:
5.6
9499 040 55811
1. Each input is provided with a grounded connection to which the screening of the
incoming cable must be connected. These interconnected screenings must be connected with ground potential (protective earth) via one of the ground terminals by
means of a short cable (approx. 20 cm).
2. Use of a commercially available connecting system.
13
Multiple transmitter and temperature controller KS 816
Input circuit examples
149499 040 55811
Multiple transmitter and temperature controller KS 816
6Outputs
KS 816 has no outputs in the conventional sense. These are output via the (field)
bus as
• correcting variable in %, for continuous controllers and
• digital information (on/off) for switching controllers
Control of the final elements (relays,contactors, solid-state relays, magnetic valves)
must be provided by a suitable output card of the control system.
6.1 Operation as a transmitter
Each KS 816 channel can be configured as a transmitter. This can be done only via
software, by means of the engineering tool, or via the bus by means of the control
system. The controller function is switched off and only the (corrected) process value is transmitted via the bus. The 4 limit values for each channel can be activated
also in the transmitter function. Conversion into (0...10V; 0/4...20mA) standard signal must be provided in the control system.
6.2 Alarm function
7
When using as a transmitter, the following information must be taken into account:
As the KS 816 scanning interval is approx. 1 s, the measurement values are also
updated only at intervals of one second.
KS 816 is not suitable for applications in which the measured value must be updated continuously, e.g. pressure measurement with peak value detection.
The alarms are also output via the (field) bus:
Process value alarm (absolute process value monitoring)
Control deviation (process value - set-point)
Correcting variable
Set-point
Limit values
4 limit values can be adjusted for each of the 16 channels: 2 low alarms and
2 high alarms
9499 040 55811
15
Multiple transmitter and temperature controller KS 816
Overall connecting diagram KS 816
169499 040 55811
Multiple transmitter and temperature controller KS 816
8Digital interfaces
The only possibility to communicate with controller KS 816 is via the digital interfaces. Process value read out as well as set-point or control parameter changing are
via these interfaces.
The two interface types are:
8.1 Engineering tool interface
The PC interface is provided on all instrument versions. It is a special interface according to the ISO 1745 protocol. The relevant software, i.e. the engineering tool,
provides access to all controller values.
E.g. for uncomplicated applications or tests, configuring an individual unit and operating the control loops normally are possible via this interface.
Connection is at the 4/4 FCC68 data connector (Western telephone connector) via
a special PC adaptor, order no. 9407 998 00001.
8.2 BUS interfaces
This interface is used for connecting the KS 816 to a PLC, a PC or a visualization
unit. Dependent of instrument version, it is used for CANbus, Profibus or as
RS 422/485 (see section 2.1).
The 9-pole sub-D connector and the socket are equivalent. They are used for "making a loop" through the bus with several connected units.
8.2.1 BUS connector
8.3 COM2 interface
9499 040 55811
17
Multiple transmitter and temperature controller KS 816
Address and Baudrate for the COM2 interface can be adjusted via hardware or
software for each KS 800.
Via hardware, the address is adjustable within ”01” and ”99”. In position ”00”, the
address stored in EEPROM which can be changed via software will be used when
switching on. Priority is given to the address adjusted via switch position. This
address cannot be changed via software.
The same applies to the Baudrate: in Position ”0”, the EEPROM Baudrate is effective at first. This address can be changed via software. The digits on the switch correspond to the values used for determination of the Baudrate during configuration in
C902.
8.4
Switch positionRS485CANbus
0from EEPROM or via softwarefrom EEPROM or via software
12400 Bd 20 kBd
24800 Bd125 kBd
39600 Bd500 kBd
419200 Bd 1 Mbd
5invalid setting 10 kBd
6invalid setting 50 kBd
7invalid setting250 kBd
8invalid setting800 kBd
9invalid settinginvalid setting
As the baudrate is adjusted automatically with the PROFIBUS DP-version, manual
adjustment is omitted.
189499 040 55811
Termination resistors
All KS 816 versions are delivered without termination resistors at the bus connections.
The resistors required for each bus must be added externally at the last unit on
both ends of the bus cable: either in the last connector (socket) or in a separate
termination connector (socket), which plugs into the free bus connection of the last
unit.
CAN-BUS: 9-pole sub-D socket with termination resistor. Only termination resistor,
not suitable for connecting a cable. PMA order no. 9407 800 90021
PROFIBUS: e.g. Siemens, bus connector,
types: 6ES7972-OBB10-OXAO or 6ES7972-OBB20-OXAO, or
6GK1 500-OEAOO. This connector is not available from PMA.
The standards or standard drafts valid for the relevant bus system are applicable.
9Indicator LEDs
Multiple transmitter and temperature controller KS 816
There are 5 LEDs with the following signification above the lower input terminals:
PWR
This LED is on with the supply voltage applied.
COM
With CAN_BUS and RS422/485, this LED indicates data transmission between KS
816 and control system (PC or visualization) by flashing.
With PROFIBUS, the 4 different statuses are:
LED off: error signalling for "no bus access" (not addressed by the master)
LED on: OK cyclic data transmission running.
LED blinks: (2Hz) data transmission interrupted.
LED blinks: (4Hz) PROFIBUS parameters or configuration error.
AL1...AL3
With KS 816 configured so that it provides alarm functions, these LEDs are lit, when
the relevant alarm is pending.
9499 040 55811
19
Multiple transmitter and temperature controller KS 816
10Maintenance and behaviour in case of failure
KS 816 requires no special maintenance and does not contain parts which require
preventive maintenance or care.
10.1 Cleaning
If necessary, the aluminium and plastics parts must be cleaned carefully with spirit.
Do not use agents which contain solvents or scouring powder.
10.2 Trouble-shooting
To start with, all possibilities of error in other equipment and connections (input
leads, cables, equipment connected in the output circuit) should be examined.
If the error cannot be located with the hints given in this section, we recommend
returning the unit to the manufacturer.
PMA Prozeß- und Maschinen- Automation GmbH
Service Department
Miramstraße 87
If the trouble is due to failure of a fuse, the cause must be determined and removed. The spare fuse must be of the same rating as the original type.
If the PWR LED is not lit despite correct supply voltage polarity, KS 816 is defective
and must be returned to the manufacturer for repair.
Before disconnecting the unit, switch off the power supply of the installation and
check that other equipment in the installation is not affected.
WARNING!
When safe operation seems not possible any more, shut down the unit and
protect it against accidental switch-on.
For dismounting the unit, see section 3.2
209499 040 55811
r
PMA Prozeß- und Maschinen-Automation GmbH
UL-Zulassung
Damit das Gerät die Anforderungen der
UL-Zulassung erfüllt, sind folgende Punkte
zu beachten:
.
NurLeiteraus60/75oder75°CKupfer
(Cu) verwenden..
Die Klemmenschrauben sind mit einem
Drehmoment von 0,5 - 0,6 Nm anzuziehen.
UL certification
ForcompliancewithULcertificate,
the following information must be
taken into account:
Use only 60 / 75 or 75°C coppe
(Cu) wire.
Tighten the terminal-screws
withatorqueof0,5-0,6Nm
No. / Nr. 9499 047 09541
valid from / gültig ab: 8367
Subject to change without notice. PMA Prozeß- und Maschinen-Automation GmbH
Printed in Germany 9499 040 55811 (0207) Postfach 31 02 29, D - 34058 Kassel