Thank you very much for buying an Universal Controller KS 45.
The universal controllers KS 45 are suitable for precise, cost-efficient contol tasks in all industrial applications.
For that you can choose between simple on/off-, PID- or motorstepping control.
The process-value signal is connected via an universal input. A second analog input can be used for heating-current
measurement or as external setpoint input.
The KS 45 has at least one universal input and two switching outputs. Optionally the controller can be fitted with an
universal output or with optocoupler outputs. The universal output can be configured as continuous output with current
or voltage, for triggering solid state relays or for transmitter supply.
Galvanic isolation is provided between inputs and outputs as well as from the supply voltage and the communication
interfaces.
Applications
The KS 45 as universal controller can be utilized in many applications, e.g.:
...
Furnaces
w
Burners and boilers
w
Dryers
w
Climatic chambers
w
Heat treatment
w
Sterilizers
w
Oxygen-control
w
As a positioner
w
General
At-a-glance survey of advantages
Compact construction, only 22,5 mm wide
Clips onto top-hat DIN rail
Plug-in screw terminals or spring clamp connectors
Dual-line LC display with additional display elements
Process values always in view
Convenient 3-key operation
Direct communication between rail-mounted transmitters
Universal input with high signal resolution (>14 bits) reduces stock keeping
Universal output with high resolution (14 bits) as combined current / voltage output
Quick response, only 100 ms cycle time, i.e. also suitable for fast signals
Logical linking of digital outputs, e.g. for common alarms
Second analog input for ext. setpoint, heating current or as universal input
Further documentation for universal controller KS 45:
–
Data sheet KS 459498 737 48513
–
Operating note KS 459499 040 71541
–
Interface description9499 040 72011
KS 455
General
1.1Application in thermal plants
In many thermal plants, only the use of approved control instruments is permissible.
There is a KS 45 version (KS45-1xx-xxxxx-Dxx) which meets the requirements as an electronic temperature controller
(TR, type 2.B) according to DIN 3440 and EN 14597.
This version is suitable for use in heat generating plants, e.g. in
building heating systems acc. to DIN EN 12828 (formerly DIN 4751)
•
large water boilers acc. to DIN EN 12953-6 (formerly DIN 4752)
•
heat conducting plants with organic heat transfer media acc. to DIN 4754
•
oil-fired plants to DIN 4755
•
…
Temperature monitoring in water, oil and air is possible by means of suitable approved probes.
Application in thermal plants6KS45
2Safety hints
.
This unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 and was delivered in safe condition.
The unit complies with European guideline 89/336/EWG (EMC) and is provided with CE marking.
The unit was tested before delivery and has passed the tests required by the test schedule. To maintain this condition
and to ensure safe operation, the user must follow the hints and warnings given in this operating manual.
Safety hints
a
a
The unit is intended exclusively for use as a measurement and control instrument in technical
installations.
Warning
If the unit is damaged to an extent that safe operation seems impossible, the unit must not be taken into operation.
ELECTRICAL CONNECTIONS
The electrical wiring must conform to local standards (e.g. VDE 0100). The input measurement and control leads must
be kept separate from signal and power supply leads.
In the installation of the controller a switch or a circuit-breaker must be used and signified. The switch or cir
cuit-breaker must be installed near by the controller and the user must have easy access to the controller.
COMMISSIONING
Before instrument switch-on, check that the following information is taken into account:
Ensure that the supply voltage corresponds to the specifications on the type label.
•
All covers required for contact protection must be fitted.
•
If the controller is connected with other units in the same signal loop, check that the equipment in
•
the output circuit is not affected before switch-on. If necessary, suitable protective measures must
be taken.
The unit may be operated only in installed condition.
•
Before and during operation, the temperature restrictions specified for controller operation must
•
be met.
-
a
a
Warning
The ventilation slots must not be covered during operation.
The measurement inputs are designed for measurement of circuits which are not connected directly with
the mains supply (CAT I). The measurement inputs are designed for transient voltage peaks up to 800V
against PE.
SHUT-DOWN
For taking the unit out of operation, disconnect it from all voltage sources and protect it against accidental operation.
If the controller is connected with other equipment in the same signal loop, check that other equipment in the output
circuit is not affected before switch-off. If necessary, suitable protective measures must be taken.
KS 457
Safety hints
2.1MAINTENANCE, REPAIR AND MODIFICATION
The units do not need particular maintenance.
There are no operable elements inside the device, so the user must not open the unit
Modification, maintenance and repair work may be done only by trained and authorized personnel. For this purpose,
the PMA service should be contacted.
a
l
g
Warning
When opening the units, or when removing covers or components, live parts and terminals may be exposed.
Connecting points can also carry voltage.
Caution
When opening the units, components which are sensitive to electrostatic discharge (ESD) can be exposed.
The following work may be done only at workstations with suitable ESD protection.
Modification, maintenance and repair work may be done only by trained and authorized personnel. For this purpose,
the PMA service should be contacted.
You can contact the PMA-Service under:
PMA Prozeß- und Maschinen-Automation GmbH
Miramstraße 87
D-34123 Kassel
The cleaning of the front of the controller should be done with a dry or a wetted (spirit, water)
handkerchief.
2.3Spare parts
As spare parts für the devices the following accessory parts are allowed:
DescriptionOrder-No.
Connector set with screw terminals9407-998-07101
Connector set with spring-clamp terminals9407-998-07111
Bus connector for fitting in top-hat rail9407-998-07121
MAINTENANCE, REPAIR AND MODIFICATION8KS45
3Mounting
A
.
Mounting
bmessungen / dimensions
56
22.5
(0,87”)
max.
117.5 (4,63”)
55°C
-10°Cmin.
111 (4, 37 ”)
max.
95% rel.
7
Klemme /
1516
8
terminal
17
12
18
Klemme /
terminal
%
Montage / mounting
5.5
(0,20”)
4
3
2.3
(0,08”)
click
99 (3,90”)
Demontage / dismantling
1
11 1 2
14
13
g
a
a
a
l
a
a
The unit is provided for vertical mounting on 35 mm top-hat rails to EN 50022.
If possible, the place of installation should be exempt of vibration, aggressive media (e.g. acid, lye), liquid, dust or
aerosol.
The instruments of the rail line series can be mounted directly side by side. For mounting and dismounting, min. 8 cm
free space above and below the units should be provided.
For mounting, simply clip the unit onto the top-hat rail from top and click it in position.
To dismount the unit, pull the bottom catch down using a screwdriver and remove the unit upwards.
Universal Controller KS 45 does not contain any maintenance parts, i.e. the unit need not be opened by the
customer.
The unit may be operated only in environments for which it is suitable due to its protection type.
The housing ventilation slots must not be covered.
In plants where transient voltage peaks are susceptible to occur, the instruments must be equipped with
additional protective filters or voltage limiters!
Caution! The instrument contains electrostatically sensitive components .
Please, follow the instructions given in the safety hints.
To maintain contamination degree 2 acc. to EN 61010-1, the instrument must not be installed below
contactors or similar units from which conducting dust or particles might trickle down.
KS 459
Mounting
3.1Connectors
g
a
The four instrument connectors are of the plug-in type. They plug into the housing from top or bottom and click in posi
tion (audible latching). Releasing the connectors should be done by means of a screwdriver.
Two connector types are available:
Screw terminals for max. 2,5 mm2conductors
•
Spring-clamp terminals for max. 2,5 mm2conductors
•
Before handling the connectors, the unit must be disconnected from
the supply voltage.
Tighten the screw terminals with a torque of 0,5 - 0,6 Nm.
With spring-clamp terminals, stiff and flexible wires with end crimp can be
introduced into the clamping hole directly. For releasing, actuate the (or
ange) opening lever.
Contact protection: Terminal blocks which are not connected should remain in the socket.
-
-
Connectors10KS 45
4Electrical connections
.
4.1Connecting diagram
Electrical connections
7
2
5
1
KS45-1xY-xxxxx-xxx
=0,1,2,3
Y
(mV)
a
e
b
c
d
INP2
INP1
OUT3
PWR
a
b
c
d
e
f
g
h
i
k
j
90...260V AC
24V AC/DC
5
1
mV
Logic
11
15
L
8
76
4
3
3
2
V
V
12
13
14
18
17
16
N
b
a
di1
OUT1
OUT2
RGND
Data A
Data B
RS 485
KS45-1xY-xxxxx-xxx
=4,5
Y
1234
3
9
0
1234
11 12 13 14
11 12 13 14
15 16 17 18
15 16 17 18
AC / DC
8
INP2
INP1
3
2
top
RGND
Data A
Data B
6
PWR
1
5
1
2
mV
24VDC
12
11
15
16
L
N
90...260V AC
24V AC/DC
b
a
8
76
3
3
13
17
di1
4
V
OUT1
14
OUT2
18
OUT3
4
4.2
a
g
Terminal connections
Faulty connection might cause destruction of the instrument !
1 Connecting the supply voltage
Dependent on order
90 … 260 V ACterminals: 15,16
•
24 V AC / DCterminals: 15,16
•
For further information, see section "Technical data"
Instruments with optional system interface:
Energization is via the bus connector of field bus coupler or power supply module. Terminals 15, 16 must
not be used.
Opto-coupler outputs with shared positive control voltage.
OUT1terminals: (11), 12, 13
•
OUT2terminals: (11), 12, 14
•
! Connecting relay output OUT3 (optional)
Relay output max. 250V/2A as nomally open contact.
OUT3terminals: 17, 18
•
Terminal connections12KS 45
4.3Connecting diagram
The instrument terminals used for the engineering can be displayed and printed out via BlueControlÒ( menu File \ Print
preview - Connection diagram).
Example:
Connecting diagram
Connector 1
Pin
Name
Connector 2
Pin
Name
Description
Process value x1
Description
Signal limit 1, signal INP1 fail
Electrical connections
Heating current input
Switch-over to SP2
Connector 3
Pin
Name
Controller output Y2
Controller output Y1
Description
KS 4513Connecting diagram
Electrical connections
2
4.4Connection examples
Example: INP2 with current trans- former and
SSR via opto-coupler
L
5
7
6
INP2
INP1
PWR
PWR
8
di1
4
3
2
1
SSR
_
+
OUT1
14
11
13
12
15
16
OUT2
18
17
N
Connection example: KS 45 and TB 45
L
L1
Fuse
INP2
INP1
KS 45
5
1
7
6
8
di1
4
3
2
Fuse
contactor
Example: heating / cooling OUT 1 /OUT2
L
5
7
6
1
11
15
5
1
2
12
16
TB 45
6
2
8
di1
4
3
+
14
13
OUT2
18
17
OUT1
7
8
di1
4
3
Resetbutton
N
Fuse
INP2
INP1
PWR
PWR
temperature limiter
INP1
heating
SSR
+
_
OUT3
PWR
PWR
Logic
14
11
13
12
18
15
17
16
+
+
PWR
PWR
14
11
13
12
18
15
17
16
LC
N1
N2
Example: RS 485 interface with RS 485-RS 232 converter
See documentation 9499-040-72011
Master z.B. / e.g.
Converter RS 232-RS 485
RGND
3
LT 1
Data A
Data B
2
Data A
Data B
(ADAM-4520-D)
LT 1
DATA+ 1
DATA-
TX+
TXRX+
RX-
(R)+Vs
(B)GND 10
(RS-485)
(RS-422)
Connection examples14KS 45
4.5Hints for installation
Measurement and data lines should be kept separate from control and power supply cables.
w
Sensor measuring cables should be twisted and screened, with the screening connected to
w
earth.
External contactors, relays, motors, etc. must be fitted with RC snubber circuits to manufacturer
w
specifications.
The unit must not be installed near strong electric and magnetic fields.
w
The temperature resistance of connecting cables should be selected in accordance with the
w
local conditions.
Electrical connections
a
a
a
a
4.5.1cULus approval
The unit is not suitable for installation in explosion-hazarded areas.
Faulty connection can lead to the destruction of the instrument.
The measurement inputs are designed for measurement of circuits which are not connected directly with
the mains supply (CAT I). The measurement inputs are designed for transient voltage peaks up to 800V
against PE.
Please, follow the instructions given in the safety hints.
For compliance with cULus regulations, the following points must be taken into account:
Use only copper (Cu) wires for 60 / 75 °C ambient temperature.
q
q
The connecting terminals are designed for 0,5 – 2,5 mm2Cu conductors.
q
The screw terminals must be tightened using a torque of 0,5 – 0,6 Nm.
q
The instrument must be used exclusively for indoor applications.
q
For max. ambient temperature: see technical data.
q
Maximum operating voltage: see technical data.
KS 4515Hints for installation
Operation
5Operation
.
5.1Front view
1Line 1: process value display
2Display 2: setpoint /output value/ unit-display / extended
operating level / errolist / values from Conf- and
PArA-level special functions as A-M, Func, run, AdA
3operating mode “manual”
4Error list (2 x ô ), e.g.
· Fbf. xsensor fault INP. X
· sht. xshort circuit INP. X
· Pol. xwrong polarity INP. X
· Lim. xlimit value alarm
· ...
5Increment key
6Enter key to select extended operating level or error list
7Status indicator LEDs
·green:limit value 1 OK
·green blinking:no data exchange with bus coupler
(only on instruments with optional
system interface)
8Display elements, active as bars
9Status of switching output OUT1 active
0Status of switching output OUT2 active
!Decrement key
§PC connection for the BlueControl
Ò
engineering tool
g
+
Front view16KS 45
In the first LCD-display line the measured value is shown. The second LCD-line normally shows the
setpoint. When changing over to the parameter setting, configuration or calibration level and at the
extended operating level, the parameter name and value are displayed alternately.
§ : To facilitate withdrawal of the PC connector from the instrument, please, press the cable left.
5.2Operating structure
The instrument operation is divided into four levels:
Operation
450.3
450.0
äüüü
ME
1
2
The access to the parameter, configuration and calibrating level can be disabled using the following two methods:
w
3s
ô
Level disabling by adjustment in the engineering tool (IPar, ICnf, ICal). Display of disabled levels
is suppressed.
450.3
PARA
äüüü
ME
1
2
450.3
CONF
äüüü
1
ô
ME
2
450.3
CAL
äüüü
1
ô
ME
2
450.3
END
äüüü
1
2
ô
ME
PASS
PASS
PASS
ô
Operating level
Parameter level
Configuration level
Calibrating level
The access to a level can be disabled by entry of a pass number (0 … 9999). After entry of the
w
adjusted pass number, all values of the level are available.
With faulty input, the unit returns to the operating level.
Adjusting the pass number is done via BlueControl
Individual parameters which must be accessible without pass number, or from a disabled
parameter level, must be copied into the extended operating level.
Factory-setting:
all levels are accessible without restrictions,
pass number PASS = OFF
5.3Behaviour after supply voltage switch-on
After switching on the supply voltage, the instrument starts with the operating level.
The operating status is as before power-off.
If the device was in manual mode, when switching off the power-supply, it also starts up in manual mode with output
value Y2.
Ò
.
PASS
KS 4517Operating structure
Operation
ü
5.4Displays in the operating level
5.4.1Display line 1
The displayed value, also named process value, is shown in the first display line. This value is used as controlled value
(variable). It results from the configuration C.tYP. (also see chp./page 7-22.)
5.4.2Display line 2
The value to be displayed continuously in the second LCD line can be selected from different values via the
BlueControl
Normally the internal setpoint SP is set.
Ò
engineering tool.
1
450.3
450.0
äüüü
2
ME
1
g
g
By deleting the individual settings for display 2, it is resetted to setpoint display. Reset to display of the
engineering unit is possible by deleting the entry for line 2.
With faulty input values, signals dependent on the inputs (e.g. Inp1, Inp2, display value, Out3) also indicate FAIL.
5.4.3Switch-over with the enter-key
By using the enter-key, different values can be called in display 2. Every time you press the enter key, the display
jumps to the next feature as shown below.
2
450.3
mAn
ääüü
2
ME
1
1Default settings as setpoint
2Display of operating mode
automatic/manual
1
Displaying the defined display 2 value (via BlueControlÒ).
Standard setting is the internal setpoint
2
Displaying the output value, e.g. Y57
3
Calling up the error list, if messages are supplied.
If there is more than one message with every push of
the enter key the next message is displayed.
4
Calling up the extended operating level, if messages
are supplied.
If there is more than one message with every push of
the enter key the next message is displayed.
5
Returning to the original displayed value.
If for 30 s no key is pushed, the display automatically
returns to the origin.
1
2
3
4
5
ô
ô
ô
ô
ô
450.3
450.0
äüüü
ME
1
2
450.3
Y57
ä üüü
ME
1
2
450.3
FbF.1
ä üüü
ME
1
2
450.3
L.1
ä üüü
ME
1
2
450.3
450.0
äüüü
ME
1
2
ô
ô
Displays in the operating level18KS 45
5.5Extended operating level
The operation of important or frequently used parameters and signals can be allocated to the extended operating level.
This facilitates the access, e.g. travelling through long menu trees is omitted, or only selected values are operable, the
other data of the parameter level are e.g. disabled.
Display of the max. 8 available values of the extended operating level is in the second LCD line.
The content of the extended operating level is determined by means of the BlueControl
select entry "Operation level" in the "Mode" selection menu. Further information is given in the on-line help of the engi
neering tool.
450.3
äüüü
1
2
ô
ûC
M
E
Ò
engineering tool. For this,
Press key ô to display the first value of the extended
operating level (after display of error list, if necessary).
The selected parameters can be changed by
pressing keys Ì and È .
Operation
-
450.3
H.I
äüüü
2
ME
1
ô press to display the next parameter
450.3
500.0
äüüü
2
ME
1
ô
450.3
L.I
äüüü
2
ME
1
ô return to normal display after the last parameter
450.3
100.0
äüüü
2
ME
1
ô
Unless a key is pressed within a defined time (timeout = 30 s), the operating level is displayed again.
Extended operating level19KS 45
Operation
1
2
5.6Special change-over functions
In order to operate switch-over or -on functions needed more often via front, there are special functions available.
A-M
•
Switch-over automatic / manual-operation
ProG
•
starting / stopping the programmer
Func
•
Selection of different switching signals
Via the engineering tool BlueControl
function can be adjusted in the operating mode (sig
nals/logic). It can be assigned permanently to display 2
or the extended operating level.
5.6.1Automatic / manual switch-over
Ò
the desired
-
Between automatic and manual operation can be
switched with the A-M function via front.
g
g
5.6.2ProG - start programmer
g
For A-M function handling, the switch-over
source must be set to “Interface only” (Conf /
LoGI / mAn = 0).
Manual operation ist selected via the È - key. The
display element M is activated.
If adjustment of the output value is allowed
(Conf / Cntr / mAn = 1), the output value is displayed, otherwise display element (M) blinks.
The Ì - key switches to automatic operation. The function can be taken into the extended operating level, or perma nent in display 2.
If the programmer function is activated, (Conf / Cntr / SP.Fn = 1/9), with this function the programmer can
be started (run) or stopped (OFF) via front.
With the È - key the programm is started and stopped with the Ì - key.
After the end of a programm the stop function (OFF) must be selected before the programm can be started
again.
450.3
Auto
äüüü
2
ME
1
2
450.3
mAn
дьдьь
1
ME
5.6.3Func - switching function
The switching function Func takes the tasks of a function key. One or more signals switching at the same time, can be
selected via configuration (Conf / LOGI/x=5)ausgewählt werden.
The switching function is set to on (= 1) via the È - key and to OFF (= 0) via Ì - key.
+
Example: The setpoint range adjustable by the user is limited from 20 to 100. Nevertheless it shall be possible to
switch off the controller via front. This can be done by assigning Conf / LOGI / C.oFF= 5 and taking the
Func - value into the extended operating level.
g
Special change-over functions20KS 45
Function Func is not suitable for timer activation.
5.7Selecting the units
The unit to be displayed is determined via configuration D.Unt.
With selection “1 = temperature unit” , the displayed unit is determined by configuration Unit with the relevant
conversions for Fahrenheit and Kelvin.
By selecting D.Unt = 22, display of any max. 5-digit unit or text can be determined.
Operation
1
4.5
kWh
1Unit (example): kilowatt hour
2Text (example): TAG no.
äüüü
2
ME
2
1
450.3
TI451
äüüü
2
ME
1
For permanent display the value signals/other/D.Unt must be set in the mode "operating level" via the engineering
g
tool.
Selecting the units21KS 45
Functions
6Functions
.
The signal data flow of transmitter KS 45 is shown in the following diagram:
6.1Linearization
The input values of input INP1 or INP2 can be linearized via a table.
By means of tables, e.g. special linearizations for thermocouples or other non-linear input signals, e.g. a container
filling curve, are possible.
Table “ Lin” is always used with sensor type S.TYP= 18: "Special thermocouple" in INP1 or INP2, or if linearization
S.Lin = 1: “Special linearization” are adjusted.
w
w
w
Non-linear signals can be linearized using up to 16 segment points. Each segment point comprises an input ( In.1
… In.16) and an output (Ou.1 … Ou.16). These segment points are interconnected automatically by straight
lines. The straight line between the first two segment points is extended downwards and the straight line between the
two highest segment points is extended upwards, i.e. a defined output value for each input value is provided.
With an In.x value switched to OFF, all further segments are switched off.
+
g
Required: Condition for the input values is an ascending order.
In.1 < In.2 < ...< In.16.
For linearization of special thermocouples, the ambient temperature range should be defined exactly,
becauseit is used to derive the internal temperature compensation.
The input signals must be specified in mV, V, mA, % or Ohm dependent on input type.
For special thermocouples (S.tYP = 18), specify the input values in mV, and the output values in
the temperature unit adjusted in U.LinT .
For special resistance thermometer (KTY 11-6) (S.tYP = 23), specify the input values in Ohm, and
the output values in the temperature unit adjusted in U.LinT.
See also page 60.
Linearization22KS 45
Ou.16
.
.
.
.
.
.
Ou.1
In
1In
1
Functions
g
The same linearization table is used for input 1 and input 2.
6.2Input scaling
Scaling of input values is possible. After any linearization, measurement value correction is according to the offset or
two-point method.
g
When using current or voltage signals as input variables for InP.x, the input and display values should
be scaled at the parameter level. Specification of the input value of the lower and upper scaling point is in
units of the relevant physical quantity.
Example for mA/V
mA / V
phys.
quantity
OuH.x
OuL.x
InL.x
InH.x
phys. quantity
mA/V
g
KS 4523Input scaling
Parameters InL, OuL, InH and OuH are visible only with ConF / InP / Corr = 3 selected.
Parameters InL and InH determine the input range.
Example with mA:
InL= 4 and InH = 20 means that measuring from 4 to 20 mA is required (life zero setting).
- preliminary -Functions
a
+
For using the pre-defined scaling with thermocouples and resistance thermometers (Pt100), the settings
for InL and OuL as well as for InH and OuH must correspond with each other.
For resetting the input scaling, the settings for InL and OuL as well as InH and OuH must
correspond.
6.2.1Input fail detection
For life zero detection of connected input signals, variable adjustment of the response value for FAIL detection is pos
sible according to formula:
Normally, resistance and resistance thermometer measurement is in three-wire connection, whereby the resistance of
all leads is equal.
Measurement in four-wire connection is also possible for input I. With this method, the lead resistance is determined
by means of reference measurement.
With two-wire measurement, the lead resistance is included directly as a falsification in the measurement result.
However, determination of the lead resistances by means of is possible.
-
g
+
Besides the connection of the both leads of the RTD / R
sensor the 3rd connector has to be short-circuited.
Procedure with Pt100, Pt1000
Connect a Pt100 simulator or a resistance decade instead of the
sensor at the test point so that the lead resistance is included and
calibrate the values by means of 2-point correction.
By means of measurement value correction the resulting
temperature value will be corrected, but not the resistance
input value. In this case the linearization error can increase.
Procedure with resistance measurement
Measure the lead resistance with an ohmmeter and subtract it from
the measured value via the scaling.
2
INP2
INP1
1
8
5
1
76
4
3
3
2
KS 4524Input scaling
6.3Filter
Input values can be smoothened with an 1st order mathematical filter. Time constant is adjustable.
6.4Substitue value for inputs
If a substitute value for an input is activated, this value is used for further calculation with a sensor fault, independent
of the selected input function. The selected controller output reaction on sensor fault, configuration FAIL, is omitted.
With factory setting, the substitute value is switched off.
Functions
a
Before activation of a substitute value In.F, the effect on the control loop must be considered.
6.5Input forcing
Setting f.AIx = 1 (only via BlueControl®) can be used for configuring the input for value entry via the interface (=forc
ing).
a
Please, check the effect on the control loop in case of failure of input value / communication and
exceeded measuring range.
6.6O2 measurement (optional)
This function is available only on instrument versions with INP2 .
Lambda probes (l probes) are used as input signals. The electromotive force (in volt) delivered by lambda probes is de-
pendent on the instantaneous oxygen content and on the temperature. Therefore, the device can only display accurate
measurement results, if the probe temperature is known.
The instrument calculates the oxygen content according the Nernst formula.
Distinction of heated and non-heated lambda probes is made.
Signals from both types can be handled by the device.
Heated lambda probes
Heated l probes are fitted with a controlled heating, which ensures a continuous temperature. This temperature must
be specified in parameter Probe temperature in transmitter CI 45.
Parameters ® Functions ® Pro be temperature tEmP ® ...°C (/°F/K - dependent on configuration)
-
Non-heated lambda probes
When the probe is always operated at a fixed, known temperature, the procedure is as with a heated probe.
A non-heated l probe is used, if the temperature is not constant. In this case, the temperature in addition to the
probe mV value must be measured. For this purpose, any temperature measurement with analog input INP2 can be
used. During function selection, input INP2 must be set for measurement (CONF/InP.2/I.Fnc=1).
Configuration:
O
-measurement must be adjusted in function 1 :
2
Func r Fnc.17
Connection
Connect the input for the lambda probe to INP1 . Use terminals I and 2.
If necessary, temperature measurement is connected to INP2.
Input 1 is used to adjust one of the high-impedance voltage inputs as sensor type:
Filter25KS 45
O2-measurement with constant probe temperature (heated
probe)
With O2 measurement, specification if parameters related to the measured value should be output in ppm
or % is required. This is done centrally during configuration.
othrr O20Unit: ppm
1Unit: %
Whether the temperature of the non-heated l probe is entered in °C, °F or K can be selected during
configuration.
othrr Unit1°C
2°F
3K
Displays
With configuration for O2 measurement (see above), the oxygen
content is displayed as process value with the selected unit (see
above) on line 1. Max. 4 characters can be displayed.
With display range overflow, “EEEE” is displayed .
Example: the ppm range is selected, but the value is a % value.
When exceeding the display span start, 0 is displayed.
20.95
üû/o
+
O2 measurement (optional)26KS 45
Tip: the unit can be displayed on line 2.
6.7Limit value processing
Max. three limit values can be configured for the outputs. Generally, each one of outputs Out.1... Out.3 can be
used for limit value or alarm signalling.
Several signals allocated to an output are linked by a logic OR function.
6.7.1Input value monitoring
Functions
g
g
The signal to be monitored can be selected separately for each alarm in the configuration. The following
signals are available:
Process value (display value)
•
Control deviation (process value - setpoint)
•
Control deviation with suppression at start up or setpoint modification
•
Measurement value INP1
•
Measurement value INP2 (option)
•
setpoint
•
Output value
•
* After switch-on or setpoint change, the alarm output is suppressed, until the process value is within the
limits for the first time.
If a time limit (Src.x = 2) was configured, the alarm is activated after elapse of time 10 x ti1 (paramter
ti1 = integral time). ti1 switched off (ti1 = OFF) is considered as ¥ , i.e. the alarm activation is
omitted until the process value is within the limits once.
Each of the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off
individually (parameter = “OFF”). The hysteresis HYS.x of each limit value is adjustable.
For the measured heating current; different alarms can be activated.
Overlaod heating current: Heating current is larger than limit value HC.A.
•
Interrupt heating current: Heating current is smaller than limit value HC.A.
•
For both, short-circuit alarm is integrated.
•
Short circuit monitoring
Current flow in the heating circuit although the controller output is switched off is considered as a short circuit e.g. in
the solid-state relay and error message SSr (as an alarm in the error list, if configured) is output.
L.1
HYS.1HYS.1
H.1
9999
LED
rot / red
-1999
LED
HYS.1
SP
L.1
H.1
HYS.1
9999
LED
g
g
g
g
If the heating current is not measured as an AC current input S.tYP = “31 current 0...50mA AC”, the filter
time constant must be t.Fx = 0, to prevent generation of an SSR alarm due to the filter effect.
With heating current measurement via INP1, note additionally that the cycle time of connected actuators
should be > 10 s due to internal hardware filters.
With SSR short circuit alarm output, the output will be within the limits again only after alarm
acknowledgement.
Heating current overload
If the current flow in the heating current circuit is higher than the adjusted heating current limit value ( HC.A), error
message HC.A (as an alarm in the error list, if configured) is output.
Heating current interruption
If the current flow in the heating current circuit is lower than the adjusted heating current limit value ( HC.A), error
message HC.A (as an alarm in the error list, if configured) is output.
With heating current alarm output, the output is within the limits again immediately, when the heating
current returns within the limits.
Limit value processing28KS 45
6.7.3Loop-alarm
An alarm can be activated, monitoring the control-loop for break.
A break of the heating current loop is recognized, when at output of correcting variable Y=100%
and elapsed sequence time 2 x ti1 (reset time), no appropriate reaction of the process value results.
Loop alarm can not be used with motor-stepping- or proportional-controller and signaller.
g
During self-tuning, loop monitoring is omitted.
g
6.7.4Monitoring the number of operating hours and switching cycles
Operating hours
The number of operating hours can be monitored. When reaching or exceeding the adjusted value, signal InF.1 is acti
vated (in the error list and via an output, if configured).
Functions
-
The monitoring timer starts when setting limit value C.Std. Reset of signal InF.1 in the error list will start a new moni
toring timer. Monitoring can be stopped by switching off limit value C.Std.
Adjusting the limit value for operating hours C.Std can be done only via BlueControl®.
g
The current counter state can be displayed in the BlueControl
The number of operating hours is saved once per hour. Intermediate values are lost when switching off.
g
Number of switching cycles
The output number of switching cycles can be monitored. When reaching or exceeding the adjusted limit value, signal
InF.2 is activated (in the error list and via an output, if configured).
The monitoring timer starts when setting limit value C.Sch. Reset of signal InF.2 in the error list will start a new moni toring timer. Monitoring can be stopped by switching off limit value C.Sch.
A switching cycle counter is allocated to each output. Limit value C.Sch acts on all switching cycle counters.
g
Adjusting the limit value for the number of switching cycles C.Sch can be done only via BlueControl®.
g
The current counter state can be displayed in the BlueControl
The number of switching cycles is saved once per hour. When switching off, intermediate values are lost.
g
®
expert version.
®
expert version.
-
KS 4529Limit value processing
Functions
6.8Analog output (optional)
6.8.1Analog output
The two output signals (current and voltage) are available simultaneously. Adjust ConF / Out.3 / O.tYP to se
lect the output type which should be calibrated.
Parameter O.Src defines the signal source of the output value.
Example:
O.Src=3signal source for Out.3 is
Scaling of the output range is done via parameters Out.0 and Out.1. The values are specified in units of the physical quantity.
Out.0=-1999...9999scaling Out.3
Out.1=-1999...9999scaling Out.3
Example: output of the full input range of thermocouple type J (-100 … 1200 °C)
Out.0 = -100
Out.1 = 1200
Example: output of a limited input range, e.g. 60.5 … 63.7 °C)
Out.0 = 60.5
Out.1 = 63.7
20mA
10V
the process value
for 0/4mA or 0/2V
for 20mA or 10V
mA / V
+
g
g
g
Analog output (optional)30KS 45
Please, note: the smaller the span, the higher the effect of input variations and resolution.
Using current and voltage output in parallel is possible only in galvanically isolated circuits.
Configuration O.tYP = 2 (4 … 20mA) or 4 (2...10V) means only allocation of the reference value (4 mA or 2V)
for scaling of output configuration Out.0. Therefore, output of smaller values is also possible rather than
output limiting by reference value 4mA / 2V.
Configuration O.tYP = 0/1 (0/4...20mA) or 2/3 (0/2...10V) determines, which output should be used as a
calibrated reference output.
6.8.2Logic output
The analog output can also be used as a logic output (O.typ = 0).
In this case, e.g. alarms or limit values can be output or the output can be used as controller output.
6.8.3Transmitter power supply
Two-wire transmitter power supply can be selected by adjusting O.typ =5.
In this case, the analog output of the device is no longer available.
Connecting example:
Functions
INP2
INP1
5
1
2
-
-
+
OUT3
PWR
12
11
15
16
6.8.4Analog output forcing
By adjusting f.Out = 1 (only via BlueControlÒ), the output can be configured for value input via interface, or by means of
an input value at extended operating level (=Forcing).
8
76
3
3
+
13
17
di1
4
?13V
22mA
2
3
K
14
18
OUT1
OUT2
1
g
g
KS 4531Analog output (optional)
This setting can be used also for e.g. testing the cables and units connected in the output circuit.
This function can also realize a setpoint potentiometer.
Functions
2
6.9Maintenance manager / error list
In case of one or several errors, the error list is always displayed at the beginning
of the extended operating level .
A current input in the error list (alarm or error) is always indicated by display of
Check heating current circuit
If necessary, replace solid-state relay
Check heating or cooling circuit
Check sensor and replace it, if necessary
Check controller and switching device
ûC
ME
Maintenance manager / error list32KS 45
Functions
g
g
Name
AdA.H
AdA.C
Lim.1
Lim.2
Lim.3
Inf.1
Inf.2
Latched alarms Lim1/2/3 (E-element displayed) can be acknowledged, i.e. reset via digital alarm di1.
For Configuration, see page : ConF / LOGI / Err.r
When an alarm is still pending, i.e. unless the error cause was removed ( E display blinks), latched alarms
cannot be acknowledged and reset.
DescriptionCausePossible remedial action
Self-tuning heating
alarm
(ADAH)
Self-tuning heating
alarm cooling
(ADAC)
Latched limit value
alarm 1
Latched limit value
alarm 2
Latched limit value
alarm 3
Time limit value
message
Switching cycle
message
(digital outputs)
See Self-tuning heating error
status
See Self-tuning cooling error
status
Adjusted limit value 1 exceeded Check process
Adjusted limit value 2 exceeded Check process
Adjusted limit value 3 exceeded Check process
Preset number of operating
hours reached
Preset number of switching cy
cles reached
see Self-tuning heating error status
see Self-tuning cooling error status
Application-specific
Application-specific
-
Error-stateSignification
2Pending errorChange to error status 1after error removal
1Stored errorChange to error status 0 after acknowledgement in error list 0
0no error/messageNot visible, except during acknowledgement
g
If sensor errors should not be on the error list any more after error correction without manual reset in the
error list, suppression via BlueControl
CONF / othr / ILat1blocked
This setting is without effect on limit values Lim.1 … 3 configured for storage.
6.9.2Error status self-tuning
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
Ò
is possible by means of setting ILat.
KS 4533Maintenance manager / error list
Functions
1
Error-Status
0
3
4
5
6
7
8
kein Fehler
falsche WirkungsrichtungRegler umkonfigurieren (invers i direkt)
keine Reaktion der Regelgröße eventuell Regelkreis nicht geschlossen: Fühler,
Sollwertüberschreitungsgefahr
(Parameter ermittelt)
Stellgrößensprung zu klein
({y > 5%)
Sollwertreserve zu kleinSollwert vergrößern (invers), verkleinern (direkt)
BeschreibungVerhalten
6.10Resetting to factory setting
In case of faulty configuration, the device can be reset to the default manufacturers condition.
For this, the operator must keep the
1
keys increment and decrement
pressed during power-on.
Then, press key increment to select
2
YES.
3
Confirm factory resetting with Enter
and the copy procedure is started
g
g
(display
4
Afterwards the device restarts.
In all other cases, no reset will occur
(timeout abortion).
If one of the operating levels was
blocked in BlueControl
factory setting is not possible.
If a pass number was defined (via
BlueControl® ), but no operating
level was blocked, enter the correct
pass number when prompted in 3.A
wrong pass number aborts the reset
action.
The ramp starts at the process value with the following switches:
–
Switching internal/ external setpoint
–
Switching SP / SP.2
–
Switching automatic/manual
–
at power on
Setpoint/ ext. setpoint
With a Setpoint/ ext. setpoint you can switch between internal setpoint SP and external setpoint SP.E. The signal for
switching is determined in the configuration LOGI/SP.E.
Setpoint with external offset
With a setpoint with external offset control, the internal setpoint SP determines the actual default setpoint.
It can be influenced by the external (additive) offset.
Programmer
With controlling via programmer the setpoint is determined by the internal programmer.
Programmer with external offset
With controlling via programmer with external offset the setpoint is determined by the internal programmer.
The programmer value can be influenced by the external (additive) offset.
Timer
The effective setpoint is determined by the timer depending on the chosen timermode (see chapter timer).
KS 4535Setpoint processing
Controlling
7.1.1Setpoint gradient / ramp
To prevent setpoint step changes, parameter r setpoint ramp r r.SP can be adjusted. This gradient is effective in
positive and negative direction.
With parameter r.SPset to OFF (default), the gradient is switched off and setpoint changes are realized directly.
7.1.2Setpoint limitation
The setpoint can be limited to a high and low value (SP.LO, SP.Hi). Exceeding these limits the limit value is acti
vated.
-
g
Those adjustments are not valid for the second setpoint SP.2.
7.1.3Second setpoint
It can always be switched to the second setpoint. The switching source is defined with LOGI/SP.2. With this function a
"safety setpoint" can be realised.
Setpoint processing36KS 45
7.2Configuration examples
7.2.1Signaller (inverse)/ On-Off controller
Controlling
SP.LOSP
SP.Hi
InH.1InL.1
InP.1Ê
100%
Out.1Â
0%
ConF / Cntr:SP.Fn=0setpoint controller
C.Fnc=0signaller with one output
C.Act=0inverse action (e.g. heating applications)
ConF / Out.1:O.Act=0action Out.1 direct
Y.1=1control output Y1 active
PArA / Cntr:SH=0...9999switching difference (symmetrical to the trigger
point)
PArA / SEtP:SP.LO=-1999...9999 setpoint limit low for SPeff
SP.Hi=-1999...9999 setpoint limit high for SPeff
SH
g
For direct signaller action, the controller action must be changed ( ConF / Cntr / C.Act = 1 )
Y.1=1control output Y1 active
Y.2=0control output Y2 not active
ConF / Out.2:O.Act=0action Out.2 direct
Y.1=0control output Y1 not active
Y.2=1control output Y2 active
PArA / Cntr:Pb1=0,1...9999proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
Pb2=0,1...9999proportional band 2 (cooling)
in units of phys. quantity (e.g. °C)
ti1=1...9999integral time 1 (heating) in sec.
ti2=1...9999derivative time 2 (cooling) in sec.
td1=1...9999integral time 1 (heating) in sec.
td2=1...9999derivative time 2 (cooling) in sec.
t1=0,4...9999min. cycle time 1 (heating)
t2=0,4...9999min. cycle time 2 (cooling)
SH=0...9999neutr. zone in units of phys.quantity
100%
Out.2
0%
PArA / SEtP:SP.LO=-1999...9999setpoint limit low for SPeff
Out.0=-1999...9999scaling analog output 0/4mA
Out.1=-1999...9999scaling analog output 20mA
PArA / Cntr:Pb1=0,1...9999proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1=1...9999integral time 1 (heating) in sec.
td1=1...9999derivative time 1 (heating) in sec.
t1=0,4...9999min. cycle time 1 (heating)
InH.1InL.1
g
g
PArA / SEtP:SP.LO=-1999...9999setpoint limit low for SPeff
SP.Hi=-1999...9999setpoint limit high for SPeff
For direct action of the continuous controller, the controller action must be changed
( ConF / Cntr / C.Act = 1 ).
To prevent control outputs Out.1 and Out.2 of the continuous controller from switching simultaneously,
the control function of outputs Out.1 and Out.2 must be switched off ( ConF / Out.1 and Out.2 / Y.1
and Y.2 = 0 ).
KS 4541Configuration examples
Controlling
7.2.6D - Y - Off controller / 2-point controller with pre-contact
Y.1=1control output Y1 active
Y.2=0control output Y2 not active
ConF / Out.2:O.Act=0action Out.2 direct
Y.1=0control output Y1 not active
Y.2=1control output Y2 active
d.SP
SP.Hi
InH.1InL.1
PArA / Cntr:Pb1=0,1...9999proportional band 1 (heating) in
units of phys. quantity (e.g. °C)
ti1=1...9999integral time 1 (heating) in sec.
td1=1...9999derivative time 1 (heating) in sec.
t1=0,4...9999min. cycle time 1 (heating)
SH=0...9999switching difference
d.SP=-1999...9999trigg. point separation suppl. cont.
D / Y / Off in units of phys. quantity
PArA / SEtP:SP.LO=-1999...9999setpoint limit low for SPeff
SP.Hi=-1999...9999setpoint limit high for SPeff
Configuration examples42KS 45
7.3Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt, whereby the process characteristics are
used to calculate the parameters for fast line-out to the setpoint without overshoot.
The following parameters are optimized when self-tuning:
Pb1 - Proportional band 1 (heating) in engineering units [e.g. °C]
ti1 - Integral time 1 (heating) in [s]r only, unless set to OFF
td1 - Derivative time 1 (heating) in [s] r only, unless set to OFF
t1 - Minimum cycle time 1 (heating) in [s] r only, unless Adt0 was set to
Pb2 - Proportional band 2 (cooling) in engineering units [e.g. °C]
ti2 - Integral time 2 (cooling) in [s] r only, unless set to OFF
td2 - Derivative time 2 (cooling) in [s] r only, unless set to OFF
t2 - Minimum cycle time 2 (cooling) in [s] r only, unless Adt0 was set to
“no self-tuning” during configuration by means of BlueControl
“no self-tuning” during configuration by means of BlueControl
Controlling
®.
®
7.3.1Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set values rnG.L and rnG.H to the
•
limits of subsequent control. (ConfigurationrControllerrlower and upper control range limits)
ConFrCntrr rnG.L and rnG.H
Determine which parameter set shall be optimized (see tables above).
•
7.3.2Self-tuning sequence
The controller outputs 0% correcting variable or Y.Lo and waits, until the process is at rest (see start-conditions
below).
Subsequently, a correcting variable step change to 100% is output.
The controller attempts to calculate the optimum control parameters from the process response. If this is done
successfully, the optimized parameters are taken over and used for line-out to the setpoint.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100% cooling energy) is output from the
setpoint.
After successfull determination of the “cooling parameters”, line-out to the setpoint is using the optimized parameters.
Start condition:
Rest condition
w
For process evaluation, a stable condition is required. Therefore, the controller waits until the process has
reached a stable condition after self-tuning start. The rest condition is considered being reached, when the
process value oscillation is smaller than ± 0,5% of (rnG.H - rnG.L).
setpoint reserve
w
After having come to rest with 0% correcting variable or with Y.Lo, the controller requires a sufficient
setpoint reserve for its self-tuning attempt, in order to avoid overshoot.
Sufficient setpoint reserve:
w
inverse controller:(with process value <setpoint-(10% of SP.Hi - SP.LO)
direct controller: (with process value >setpoint+ (10% of SP.Hi - SP.LO)
KS 4543Self-tuning
Controlling
2
7.3.3Self-tuning start
g
Self-tuning start can be locked via BlueControlÒ(engineering tool) ( IAda).
The operator can start self-tuning at any time. For this, keys ô and È must
be pressed simultaneously.
The controller outputs 0% or Y.Lo, and the text .A.d.A. is indicated in the
second display line. The controller waits until the process is at rest. As soon
as a sufficient setpoint reserve is present, he starts with the real selfoptimization by jumping to a setpoint of 100% .
The second display line shows .AdA
After successful self-tuning, the AdA-display is off and the controller
continues operating with the new control parameters.
7.3.4Self-tuning cancellation
By the operator:
Self-tuning can always be cancelled by the operator. For this, press ô and È key simultaneously. With manual-au
tomatic switch-over configured via A-M function, self-tuning can also be canceled by actuating. The controller contin
ues operating with the old parameters in automatic mode in the first case and in manual mode in the second case.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning is prevented due to the control condi tions. In this case, self-tuning was cancelled by the controller.
Dependent of control type, the output status is:
3-pnt. stepping controller: actuator is closed (0% output)
•
2-pnt./ 3-pnt./ continuous controller:
•
If self-tuning was started from the automatic mode, the controller output is 0%. With self-tuning
started from manual mode, the controller output is Y2.
450.3
.A.d.A.
äüüü
1
450.3
äüüü
1
ME
.AdA
ME
2
-
-
7.3.5Acknowledgement procedures in case of unsuccessful self-tuning
1.Press keys ô and È simultaneously:
–
The controller continues controlling using the old parameters in automatic mode.
–
The Err LED continues blinking, until the self-tuning error was acknowledged in the error list.
2.Press A-M function (if configured):
–
The controller goes to manual mode. The Err LED continues blinking, until the self-tuning error was
acknowleged in the error list.
3.Press key ô :
–
Display of error list at extended operating level. After acknowledgement of the error message, the controller
continues control in automatic mode using the old parameters.
Cancellation causes:
r page 33: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
Self-tuning44KS 45
7.3.6Examples for self-tuning attempts
.A.d.d.A.A
.A.d.d.A.A
.A.d.d.A.A
.A.d.d.A.A
(controller inverse, heating or heating/cooling)
Start: heating power switched on
Heating power Y is switched off (1). When the change
of process value X was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning attempt is finished
and the new parameter are used for controlling to
setpoint SP.
Start: heating power switched off
The controoler waits until the process value has a con
stant change of more than one minute. This possibly
takes place already at start up (1). Heating power Y is
switched on (2). At the reversal point, the self-tuning at
tempt is finished and control to the setpoint is using the
new parameters.
Start: at setpoint
Heating power Y is switched off (1). If the change of
process value X was constant during one minute and the
control deviation is > 10% of SP.Hi - SP.LO (2), the
power is switched on (3). At the reversal point, the
self-tuning attempt is finished, and control to setpoint SP
is using the new parameters.
Three-point controller
The parameters for heating and cooling are determined in
one attempt. The heating power is switched on (1). At reversal point 1, heating parameters Pb1, ti1, td1 and
t1 are determined. The process value is lined out to the
setpoint (2). The cooling power is switched on (3). At reversal point 2, parameters Pb2, ti2, td2 and t2 are
determined and the self-tuning attempt is finished. Control
to setpoint SP is using the new parameters.
Controlling
X
SP
100%
0%
Y
Star t r
X
SP
1
.A.A.d.d.A.A.
2
t
t Wendepunkt
3
reversal point
AdA
“ - “
-
100%
100%
X
X
SP
SP
+100%
+100%
Y0%
Y0%
-100%
-100%
Y
0%
X
SP
Y
0%
Star t r
Start r
Start r
Star t r
.A
.A
1
.A.A.d.d.A.A.
.A.A.d.d.A.A.
1
1
2
1
.
.
2
t Wendepunkt
reversal point
AdA
t Wendepunkt 1
t Wendepunkt 1
AdA
AdA
“ - “
3
t Wendepunkt
reversal point
AdA
“ -”
reversal point 1
reversal point 1
2
2
3
3
.A
.A
.“ - “
.“ - “
t Wendepunkt 2
t Wendepunkt 2
-
t
t
reversal point 2
reversal point 2
t
t
KS 4545Self-tuning
Controlling
y
7.4Manual tuning
The optimization aid should be used with units on which the control parameters shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting variable y can be used . Frequently, plot
ting the complete response curve (0 to 100%) is not possible, because the process must be kept within defined limits.
Values T
maximum rate of increase v
100%
0%
X
max
g
Y
and x
h
x
(step change from 0 to 100 %) or Dt and Dx (partial step response) can be used to determine the
max
max
.
y= correcting variable
Y
= control range
h
Tu= delay time (s)
Tg= recovery time (s)
Tg
t
X
V
= maximum process value
max
max
Xmax
=
Tg
{{x
=
t
-
{X
{t
Tu
t
The control parameters can be determined from the values calculated for delay time T
v
, and characteristic K according to the formulas given below. Increase Pb1, if line-out to the setpoint oscillates.
max
max. rate of increase of process value
, maximum rate of increase
u
Parameter adjustment effects
ParameterControlLine-out of disturbancesStart-up behaviour
Pb1 higherincreased damping slower line-outslower reduction of duty cycle
lowerreduced dampingfaster line-outfaster reduction of duty cycle
td1 higherreduced dampingfaster response to disturbancesfaster reduction of duty cycle
lowerincreased damping slower response to disturbancesslower reduction of duty cycle
ti1 higherincreased damping slower line-outslower reduction of duty cycle
lowerreduced dampingfaster line-outfaster reduction of duty cycle
Formulas
K = Vmax w Tucontroller behaviorPb1 [phy.units]td1 [s]ti1 [s]
PID1,7 w K2w Tu2 w Tu
With 2-point and 3-point con
trollers, the cycle time must be
adjusted to
t1 / t2 £ 0,25 * Tu
Manual tuning46KS 45
-
PD0,5 w KTuOFF
PI2,6 w KOFF6 w Tu
PKOFFOFF
3-point-stepping1,7 w KTu2w Tu
8Programmer
.
Programmer
SP,X
SP.01
SP.02
SP.03
SP.04
SP,X
Pt.01
Programmer set-up:
For using the controller as a programmer, select parameter SP.Fn = 1 in the ConF menu (r page 53). The pro
grammer is started via digital inputs di1or the operating function Func.
By selecting the appropriate parameter P.run =2/5,ConF-menu (r page 55), is defined which input is used for
starting the programmer.
If the end of the program shall appear as digital signal at one of the relay outputs, the appropriate parameter
P.End = 1 must be selected for this output ( OUT.1...OUT.3, ConF-menu r page 58, 59).
Programmer parameter setting:
A programmer with 4 segments is available to the user. Determine a segment duration Pt.01 .. Pt.04 (in minutes)
and a segment target set-point SP.01 .. SP.04 for each segment in the PArA menu. (r page 62).
Pt.02
Pt.03
Pt.04
SP
t
-
g
+
Starting/stopping the programmer:
There are different possibilities for starting the programmer according to configuration:
Starting the programmer with a digital signal at the selected input di1.
•
If the Func-function is set as permanent display2 (selectable via BlueControl®), the program can be
•
started (on)with the È-key and stopped with Ì (OFF).
If the Func-function was placed at the extended operating level, this element is selected with the
ô -key. The function works as described above.
If the ProG-function is placed in display2 (selectable via BlueControl®), the program can be started
•
with the È-key (run), and stopped with the Ì-key (OFF). The ProG-function can also be
placed in the extended operating level.
The ProG-function can also be used for displaying the programmerstatus.
If the ProG-function was selected, configuration P.run = 0 should be adjusted to avoid double operation.
The programmer calculates the setpoint gradient which shall reach the segment end setpoint
out of segment end setpoint and segment time. This gradient is always effective. As the programmer starts the first
segment at the real process value, the actual running time of the first segment can change (process value ¹ setpoint).
Starting conditions you'll find in the following drawing.
KS 4547
Programmer
S
Process value = setpoint:
1
Programmer starts at the setpoint
with the defined segment time
Process value between setpoint and
2
segmentend value SP.01 shortened
segment duration.
Process value bigger/smaller than
3
SP.01; segment time 1 is skipped.
Process value bigger/smaller as the
4
setpoint: Program starts at segment
start1.
After the program has elapsed the con
troller works with the latest tracking
setpoint. The display shows the value
End.
If the program is stopped whilst running
(e.g. resetting the digital signal to di1),
the programmer returns to the start point
an waits for a new start signal. The de
vice goes to it's latest setpoint.
3
2
1
4
4
1
2
3
P, X
XSP.01?
SP<X<SP.01
X=SP
X<SP
SP,X
X>SP
X=SP
SP>X>SP.01
X<SP.01
P
start
Pstart
Pstart
start
P
Pt.01
Pstart
Pt.01
Pstart
Pstart
SP.01
Pt.02Pt.03
SP.01
Pstart
Pt.02Pt.03
SP.02
SP.02
+
Program parameter changing while the program is running is possible.
Changing the segment time:
Changing the segment time leads to re-calculation of the required gradient. When the segment time has already elap sed, the new segment starts directly, whereby the set-point changes stepwise.
Changing the segment end setpoint:
Changing the set-point leads to re-calculation of the required gradient, in order to reach the new set-point during the
segment rest time, whereby the polarity sign of the required gradient can change.
48KS 45
9Timer
.
9.1Setting up the timer
9.1.1Operating modes
6 different timer modes are available to the user. The relevant timer mode can be set via parameter SP.Fn in the
Conf menu (r page 53).
Mode 1 (—)
After timer start, control is to the adjusted set-point . The timer
(t.SP) runs as soon as the process value enters or leaves the
band around the set-point (x = SP _ b.ti). After timer elapse,
the controller returns to Y2. End and the output value are dis
played alternately in the display line2.
IfY2=0isset, a switch off function of the outputs can be
g
realised
Mode 2 (····)
Mode 2 corresponds to mode1, except that control is continued
with the relevant setpoint after timer (t.SP) elapse.
-
start
SPb.ti_
t.SP
Timer
2
1
End
Mode 3 (—)
After timer start, control is to the adjusted set-point. The timer
(t.SP) starts immediately after switch-over. After timer elapsing
the controller switches to Y2 and display 2 shows End alternately with the output value.
Mode 4 (····)
Mode 4 corresponds to mode 3, except that control is continued
with the relevant set-point after timer (t.SP)elapse.
Mode 5 (delay)
The timer starts immediately. The controller output remains on
Y2. After timer (t.SP) elapse, control starts with the adjusted
set-point.
Mode 6
After set-point switch-over (SPr SP.2), control is to SP.2. The
timer (t.SP) starts when the process value enters the adjusted
band around the set-point (x = SP.2 _ b.ti). After time elapse
the controller returns to SP. End and the set-point are dis
played alternately in the lower display line.
SP
SP
-
start
start
SP.2b.ti_
t.SP
t.SP
SP.2
3
4
End
End
SPSP
start
KS 4549Setting up the timer
t.SP
Timer
9.1.2Tolerance band
Timer modes 1,2 and 6 are provided with a freely adjustable tolerance band. The tolerance band around the set-point
can be adjusted via parameter b.ti in the Conf menu (x = SP.2 _ b.ti )
(r page 53)
9.1.3Timer start
Various procedures for starting the timer are possible:
Y2 r Y switching via digital input di1 12xddddd-
SP r SP.2 switching via digital input di1 1x 2-----d
Power On0xddddd-
Changing t.ti>0 (extended operating level)xxdddddd
Serial interface (if provided)xxdddddd
Operation via BlueControl
Start viaLOGIMode
Y2
=
x 0-----d
Ò
(online operation)xxdddddd
SP.2=123456
when using a digital input, adjust parameter di.Fn = 2 ( ConF/ LOGI) ( key function)
g
g
1
xno effect
-not applicable
When using the digital input as a switch (di.Fn=0/1)orwhen using the Func switch-over function, the
timer is re-started automatically after elapsing. Switch-over, e.g. opening, will cancel the timer function.
Using the Func function as a switch for starting the timer is not recommendable, because the timer would
be re-started immediately after elapsing.
9.1.4Signal end
If one of the relays shall switch after timer elapse, parameter TimE = 1 and inverse action O.Act = 1 must be
selected for the relevant output OUT.1 … OUT.3 in the ConF menu (r page 57, 58). If direct action is selected,
the relevant output signals the active timer.
9.2Determining the timer run-time
The timer run-time can be determined via parameter t.SP in the PArA menu. The timer run-time must be specified
in minutes with one digit behind the decimal point (0,1 minutes = 6 seconds).
Alternatively, the timer run-time can be determined directly at extended operating level ( r chapter 9.3).
Determining the timer run-time50KS 45
9.3Starting the timer
Dependent of configuration, the timer start is as follows:
at controller switch-on (power-on)
•
by adjusting the timert.ti > 0 (at
•
extended operating level)
by a positive edge at digital input di1 with
•
configured SP r SP.2 or Y2 r Y
switch-over.
via the serial interface.
•
Timer
450.3
run
äüüü
g
g
Display: the timer run is indicated by texts on LCD line 2,
1
which appear alternately with the other displays:
LCD-display 2Signification
.r.u.n.
run
End
off• deletion of End display by pressing any key
With active timer, the time can be adjusted by changing parameter t.ti at extended operating level.
The status of an active timer can be output (Conf / Out.x / timE). A timer is set when started and
reset by elapsing or cancelation.
timer is started
•
timer is not running yet
•
timer is started
•
timer is running
•
Timer elapsed
•
Timer canceled
•
• timer is off
ME
9.4End / cancelation of the timer
The timer can be canceled. After elapse of the timer, the controller continues operating using the function dependent
on operating mode.
Cancelation is possible by:
changing the timer settingt.ti = 0 (at extended operating level)
•
switching over digital input di1 (SP.2 r SP or Y r Y2 switch-over) configured as a push-button).
•
via the serial interface
•
g
If the digital input is defined as a switch or if the Func function with SP/SP2 or Y/Y2 switch-over is
configured, the signal change will cancel the timer.
KS 4551Starting the timer
Timer
Mode
Behaviour after
1display:
controller:
2display:
controller:
3display:
controller:
4display:
controller:
5 *display:
controller:
6Anzeige:
Regler:
elapse
End
Y2
End
SP
End
Y2
End
SP
none
SP
End
SP
Behaviour after
changing
t.ti =0
display:
controller:
display:
controller:
display:
controller:
display:
controller:
display:
controller:
Anzeige:
Regler:
none
Y2
none
SP
none
Y2
none
SP
none
SP
keine
SP
Cancelation
(before reaching
the timer band)
display:
controller:
display:
controller:
none
Y2
none
Y2
-display: con
-display:
-display:
Anzeige:
Regler:
keine
SP
Cancelation
(after reaching the timer
band)
display:
controller:
display:
controller:
troller:
-
End
Y2
End
Y2
End
Y2
End
controller:
Y2
none
controller:
Anzeige:
Regler:
SP
End
SP
Das Timersignal timEwird mit Start des Timers gesetzt, mit Ende oder Abbruch zurückgesetzt.
* Der Timerstart erfolgt über Umschaltung Y2 r Y, der Timer schaltet auf Y2, beim Ende wird von Y2 r Y
umgeschaltet.
End / cancelation of the timer52KS 45
10Configuration level
.
10.1Configuration survey
Dependent on the device version and further adjusted configurations, configurationdata can be hidden.
process value = x1
ratio controller (x1+oFFS)/x2
difference (x1 - x2)
max (x1, x2)
min (x1, x2)
mean value (x1, x2)
Switch-over (x1, x2)
Oxygen measurement with const. probe temperature
Oxygen measurement with measured probe temperature
control behaviour
signaller (on/off controller)
PID controller (2-point and continuous)
D/Y switch-over
2 x PID (3-point and continuous)
3-point stepping controller
automatic/manual switching
Manual operation not permitted
Manual operation admitted
direction of operation
inverse, e.g. heating
direct, e.g. cooling
behaviour at sensor break
outputs off
switch to Y2
mean correcting value
lower control range [phys]
upper control range [phys]
Tuning of cycle time
Configurations54KS 45
Inputs InP.1 and InP.2
NameValue range Description
I.Fnc
S.tYP
4wir
S.Lin
Corr
In.F
fAI1
(fAI2)
0
1
2
4
6
7
0
1
2
3
4
5
6
7
8
9
10Thermocouple type Typ B (0/100...1820°C), PtRh-Pt6%
no function
heating current input
External setpoint
2nd process value X2
no controller input
process value X1
sensor type
Thermocouple type L (-100...900°C), Fe-CuNi DIN
Thermocouple type J (-100...1200°C), Fe-CuNi
Thermocouple type K (-100...1350°C), NiCr-Ni
Thermocouple typeN (-100...1300°C), Nicrosil-Nisil
Thermocouple type S (0...1760°C), PtRh-Pt10%
Thermocouple type R (0...1760°C), PtRh-Pt13%
Thermocouple type T (-200...400°C), Cu-CuNi
Thermocouple type C (0...2315°C), W5%Re-W26%Re
Thermocouple type D (0...2315°C), W3%Re-W25%Re
Thermocouple type Typ E (-100...1000°C), NiCr-CuNi
special thermocouple (Linearization necessary)
Pt100 (-200.0 ... 100,0 (150)°C)
Pt100 (-200.0 ... 850,0 °C)
Pt1000 (-200.0...850.0 °C)
Special 0...4500 Ohm (default as KTY11-6)
Special 0...450 Ohm
Special 0...1600 Ohm
Special 0...160 Ohm
Current 0/4...20mA
Current: 0...50 mA AC (HC input Inp2 only)
Voltage 0...10V / 2...10 V (Inp1 only)
Special (-2,5...115 mV)
Special (-25...1150 mV)
Special (-25...90 mV)
Special (-500...500 mV)
Special (-5...5 V) (Inp1 only)
Special (-10...10 V) (Inp1 only)
Special (-200..200 mV)
Potentiometer 0...160 Ohm
Potentiometer 0...450 Ohm
Potentiometer 0...1600 Ohm
Potentiometer 0...4500 Ohm
Resistance connection type(only for Inp.1)
3 wire connection
4 wire connection
linearization
no linearization
special linearization
measured value correction
no correction
offset correction
2-point correction
scaling
alternative value INP
Forcing of analog input INP1, INP2 µ (only visible with BlueControlÒ!)
not active
the value for this analog input is defined via interface.
Configuration level
KS 4555Configurations
Configuration level
Limits Lim1...Lim3
NameValue rangeDescription
Fnc.1
(Fnc.2)
(Fnc.3)
Src.1
(Src.2)
(Src.3)
HC.AL
LP.AL
C.Std
C.Sch
0
1
2
0
1
2
3
4
6
7
11
0
1
2
0
1
OFF; 1 …
9999999
OFF; 1 …
9999999
function of limit 1 (2, 3)
switched off
measurement value
measurement value with latch
source of limit 1 (2, 3)
process value
control deviation
deviation + suppression
INP1
INP2
Setpoint
output value
deviation + suppression without time limit
heating current alarm
switched off
overload + short circuit
break + short circuit
loop alarm
no LOOP alarm
LOOP alarm active
Control operating hours (only visible with BlueControlÒ!)
Control alternation number (only visible with BlueControl
Ò!)
Outputs Out.1, Out.2, Out.3,(relay/analog) µ
NameValue rangeDescription
O.tYP
0
1
2
3
4
5
O.Act
0
1
Y.1
0
1
Y.2
0
1
Lim.1
0
1
Lim.2
0
1
Lim.3
0
1
LP.AL
0
1
HC.AL
0
1
type of OUT (only Out.3 - analog) µ
relay/logic
0 ... 20 mA continuous
4 ... 20 mA continuous
0 ... 10 V continuous
2 ... 10 V continuous
transmitter supply
direction of operation
direct
inverse
controller output Y1
not active
active
controller output Y2
not active
active
signal limit 1
not active
active
signal limit 2
not active
active
signal limit 3
not active
active
loop alarm
not active
active
heating current alarm
not active
active
Configurations56KS 45
NameValue rangeDescription
HC.SC
0
1
timE
0
1
P.End
0
1
FAi.1
0
1
FAi.2
0
1
Sb.ER
0
1
Out.0
Out.1
-1999...9999
-1999...9999
O.Src
0
1
2
3
4
5
7
8
O.FAI
0
1
InF.1
InF.2
fOutforcing of the output (only visible with BlueControl
0
1
0
1
0
1
SSR short circuit
not active
active
timer run
not active
active
program end
not active
active
signal INP1 fail
not active
active
signal INP2 fail
not active
active
System bus error message µ
nicht aktiv
aktiv
scaling 0% (only for Out.3 analog) µ
scaling 100% (only for Out.3 analog) µ
signal source (only for Out.3 analog) µ
not active
controller output y1 (cont.)
controller output y2 (cont.)
process value
Effective setpoint
control deviation
INP1
INP2
fail behaviour µ
upscale
downscale
Status message for operating hours
nicht aktiv
aktiv
Status message for number of switching cycles
nicht aktiv
aktiv
not active
the value for this analog input is defined via interface.
Configuration level
Ò!)
Signal definition LOGI
NameValue range Description
di.Fn
0
1
2
L_r
0
1
2
5
7
8
9
KS 4557Configurations
function of inputs
direct
inverse
toggle key function
block front
(local/remote change Remote: front functions are blocked)
interface only
always on
di1 switches
Func switches
Limit 1 switches
Limit 2 switches
Limit 3 switches
Configuration level
NameValue range Description
SP.2
0
2
5
7
8
9
SP.E
0
1
2
5
7
8
9
Y2
0
2
5
7
8
9
mAn
0
1
2
5
7
8
9
C.oFF
0
2
5
7
8
9
Err.r
0
2
7
8
9
P.run
0
2
5
7
8
9
I.ChG
0
2
7
8
9
fDI1forcing of the digital input (only visible with BlueControlÒ!)
No parity, 2 stop bits
even parity
odd parity
No parity, 1 stop bit
response delay [ms] µ
system interface µ
switched off
switched on
display unit
no unit
temperature unit (see Unit)
O2 unit (see O2)
%
bar
mbar
Pa
kPa
psi
l
l/s
l/min
Ohm
kOhm
m0
A
mA
V
mV
kg
g
t
Text of physical unit
parameter unit for O2 µ
Parameter in ppm with O2 function
Parameter in % with O2 function
unit
no unit
°C
°F
Kelvin
decimal points
0 digits behind the decimal point
1 digits behind the decimal point
2 digits behind the decimal point
3 digits behind the decimal point
modem delay [ms]
Switch over 50/60 Hz (only visible with BlueControl
Netfrequency 50 Hz
Netfrequency 60 Hz
Configuration level
Ò
!)
KS 4559Configurations
Configuration level
NameValue range Description
ICof
0
1
IAda
0
1
ILat
0
1
IExo
0
1
PassOFF...9999
IPar
0
1
ICnf
0
1
ICal
0
1
T.Dis2
Block controller off (only visible with BlueControl
Released
Blocked
Block auto tuning (only visible with BlueControl
Released
Blocked
Block error memory (only visible with BlueControl
Released
Blocked
Block extended operating level (only visible with BlueControl
Released
Blocked
Password (only visible with BlueControl
Block parameter level (only visible with BlueControl
Released
Blocked
Block configuration level (only visible with BlueControl
Released
Blocked
Block calibration level (only visible with BlueControl
Released
Blocked
Settings for text in display 2 (max. 5 digits)
(only visible with BlueControl
Ò
!)
Ò
!)
Ò
!)
Ò
!)
Ò
!)
Ò
!)
Ò
!)
Ò
!)
Ò
!)
g
Linearization Lin
only visible with BlueControlÒ!
NameValue rangeDescription
U.LinT
0
1
2
3
In.1 … In.16OFF (ab In.3)
Ou.1 … Ou.16
Depending on equipment version and the configuration unused parameters are hidden.
Value U.LinT defines the unit of input values specified for linearization of temperature values. Value entry
in Celsius despite display of the measured value in Fahrenheit is possible.
Specify the input signals mV, V, mA, % or Ohm dependent on input type.
w
For special thermocouples (S.tYP = 18), specify the input values in mV and the output values in the
w
temperature unit adjusted in U.LinT.
For special resistance thermometer (KTY 11-6) (S.tYP = 23), specify the input values in Ohm and
w
the output value in the temperature unit adjusted in U.LinT .
-1999...9999
-999.0 … 9999output 1 … output 16
Temperature unit of the linearization table
without unit
in Celsius
in Fahrenheit
in Kelvin
input 1 … input 16
g
Configurations60KS 45
Resetting to factory setting (default)
r chapter 15.4
- preliminary -Parameter-level
11Parameter-level
.
11.1Parameter-survey
Dependent on device version und adjusted configurations values not needed become hidden.
The data which can be operated via the front panel are shown below.
Cntr
ô
Pb1
Pb2
ti1
ti2
td1
td2
t1
t2
SH
d.SP
tP
tt
Y2
Y.Lo
s
t
SEtP
ô
SP.LO
SP.Hi
SP.2
r.SP
t.SP
ô
t
s
ProG
SP.01
Pt.01
SP.02
Pt.02
SP.03
Pt.03
SP.04
Pt.04
ô
t
s
InP.1
ô
InL.1
OuL.1
InH.1
OuH.1
t.F1
b.F1
E.tc1
ô
t
s
InP.2
ô
ôô
InL.2
OuL.2
InH.2
OuH.2
t.F2
b.F
b.F2
E.tc2
ô
t
s
Lim
L.1
H.1
Hys.1
L.2
H.2
Hys.2
L.3
H.3
s
t
End
ô
Hys.3
HC.A
ô
g
Y.Hi
Y.0
Ym.H
L.Ym
oFFS
tEmP
ô
Parameters can be adjusted with ÈÌ - keys.
•
Stepping to the next parameter by pressing the ô - key.
•
After the last parameter of a group donE appears in the display and the controller steps
•
automatically to the next group.
Stepping back to the beginning of a group is done by pressing the ô - key for 3 s.
If, for 30 s no key is pressed, the controller returns to the operating level (Timeout = 30 s).
KS 4561Parameter-survey
Parameter-level
11.2Parameters
µ Entrys marked with this symbol are selectable only with existing device-option.
proportional band 1 [phys]
proportional band 2 [phys]
integral action 1 [s]
integral action 2 [s]
derivative action 1 [s]
derivative action 2 [s]
min. cycle time 1 [s]
min. cycle time 2 [s]
neutral zone [phys]
additional contactD/Y[phys]
min. pulse length [s]
motor travel time [s]
correcting variable 2
lower output range [%]
upper output range [%]
working point [%]
max. mean value [%]
max. deviation mean [phys]
ratio offset
probe temperature µ
Setpoint SEtP
NameValue rangeDescription
SP.LO
SP.Hi
SP.2
r.SP
t.SP
-1999...9999
-1999...9999
-1999...9999
off,0.01...9999
0.0...9999
Programmer ProG
NameValue rangeDescription
SP.01
Pt.01
SP.02
Pt.02
SP.03
Pt.03
SP.04
Pt.04
-1999...9999
0.0...9999
-1999...9999
0.0...9999
-1999...9999
0.0...9999
-1999...9999
0.0...9999
Inputs InP.1, InP.2
NameValue rangeDescription
InL.1
-1999...9999
(Inl.2)
Oul.1
-1999...9999
(OuL.2)
InH.1
-1999...9999
(InH.2)
OuH.1
-1999...9999
(OuH.2)
lower setpoint range [phys]
upper setpoint range [phys]
2nd setpoint [phys]
setpoint ramp [/min]
timer dwell time [min]
target setpoint 1
segment time 1 [min]
target setpoint 2
segment time 2 [min]
target setpoint 3
segment time 3 [min]
target setpoint 4
segment time 4 [min]
In the calibration menu ( CAL) the measured value can be adjusted.
g
The measured value correction ( CAL) is accessible only, if ConF / InP/ Corr = 1 or 2 was
selected.
g
g
+
Two methods are available
Offset - correction
•
2-point - correction
•
The InL.x and InH.x values are presented with one digit. As reference for the correcting calculation the
full resolution is used.
Deleting the correction values is done fastest by switching off the measured value correction Corr = 0
or setting the scaling parameters to a linear behaviour.
The values InL.x and InH.x show the real measured value. The output values OuL.x and OuH.x start
with the preset value.
64KS 45
12.1Offset-correction
The offset-correction shifts the input value by a pre-defined value.
Parameter setting:
w
( ConF/ InP/ Corr =1 )
On-line offset correction at the process is
possible.
display
OuL
OuLalt
Calibrating-level
standard
offset-correction
neu
450.3
450.0
äüüü
r
ô
3sec.
r
PArA
rr
ConF
CAL
r
ô
r
InP
r
ô
InL
r
r
r
InL
InL
ô
OuL
End
r
r
X
ô
ô
ô
InL:The actual input value of the scaling point is displayed.
The correction function is activated by means of keys ÈÌ ; the display changes from Off to
the measured value.
The operator must wait, until the process is at rest.
Subsequently, the input value has to be confirmed by pressing key ô .
OuL:The scaling point display value is indicated.
The operator can correct the display value by pressing keys ÈÌ. Subsequently, he presses key
ô to confirm the display value.
KS 4565Offset-correction
Calibrating-level
12.22-point-correction
2-point correction can change the offset and gradient of
the input curve.
Parameter setting:
( ConF/ InP/ Corr = 2 ):
2-point correction is possible off-line by
w
means of an input signal simulator,
or on-line in 2 steps: correct one value first
w
and the second value subsequently, e.g.
after heating up the furnace..
450.3
450.0
äüüü
r
ô
3sec.
r
PArA
ConF
rr
CAL
r
ô
r
InP
rr
display
OuH
OuH
OuL
OuLalt
ô
alt
neu
neu
InL
InL
ô
OuL
InL
standard
2-point-correction
r
ô
r
ô
InH
X
r
InH
InH
ô
OuH
r
InL:The input value of the lower scaling point is displayed.
The correction function is activated via keys ÈÌ ; the display changes from
Off to the measurement value.
Adjust the lower input value by means of an input signal simulator and press key ô to confirm
the input value.
OuL:The display value of the lower scaling point is indicated.
Press keys ÈÌ to correct the lower display value and press key ô to confirm the display va
lue.
InH:The input value of the second scaling point is displayed.
Activate the corrective function by pressing keys ÈÌ ; the display changes
from Off to the measured value.
Adjust the upper input value by means of the input signal simulator and confirm the input value
by pressing key ô .
OuH:The display value of the upper scaling point is indicated.
Correct the upper display value by pressing keys ÈÌ and press key ô to confirm the dis
play value.
End
r
ô
r
ô
ô
-
-
2-point-correction66KS 45
13Engineering Tool BlueControl
.
The Engineering Tool BlueControlÒis the projecting environment for the BluePortâcontroller series as for the rail
line family of PMA. The following 3 versions with graded functionality are available:
FunctionalityMiniBasicExpert
parameter and configuration settingyesyesyes
download: transfer of an engineering to the controlleryesyesyes
online-mode / visualizationSIM onlyyesyes
defining an application specific linearizationSIM onlyyesyes
configuration in the extended operating levelyesyesyes
upload: reading an engineering from the controllerSIM onlyyesyes
basic diagnostic functionsnonoyes
saving data file and engineeringnoyesyes
printer functionnoyesyes
online documentation, helpyesyesyes
implementation of measurement value correctionyesyesyes
data acquisition and trend displaySIM onlyyesyes
net- / multiple licencenoneinyes
wizard functionyesyesyes
extended simulationnonoyes
Ò
Engineering Tool BlueControl
Ò
The mini version is - free of charge - at your disposal as download at PMA homepage www.pma-online.de or on the
PMA-CD (please ask for).
At the end of the
installation the
licence number
has to be stated
or DEMO mode
must be chosen.
At DEMO mode
the licence num
ber can be stated
subsequently un
der Help r
Licence r
Change.
-
-
KS 4567
Versions
14Versions
.
K
Universalcontroller KS 45
1 universal input, 1 digital input
with display and BluePort -interface
no plug-in connectors
with screw-terminal plug-in connectors
90...260V AC, 2,
INP2 as current input (0...20mA)
18...30VAC/18...31VDC, 2,
INP2(0...20mA)
90...260V AC, mA/V/ logic + 2,
INP2(0...20mA)
18...30VAC/18...31VDC, mA/V/+2,
INP2(0...20mA)
90..260V AC, 2 optocoupler output, 1 relay,
INP2 as current input (0...20mA a.
0...50 mA AC)
18...30VAC/18..31VDC, 2 optocoupler output,
1 relay, INP2 as current input
(0...20mA u. 0...50 mA AC)
no option
RS 485 / MODBUS - protocol
System interface (eng for 24V option)
di1 as contact input
di1 as optocoupler input
INP2 as universal input, 0 -measurement,
di1 as
INP2
as universal input, 0 -measurement,
di1
as optocoupler input
standard
configuration to order
relay
as current input
as current input
as current input
contact input
S4 5 1
®
relay
relay
logicrelay
2
2
0
0
0
0
Accessories delivered with the
controller:
Operating note
•
Rail-to-bus connector for
0
1
0
•
the interface option
Additional equipment with ordering
data.
1
2
3
4
5
0
1
2
0
1
2*
3*
0
9
standard (CE-certified)
certified to EN 14597 (replaces DIN 3440)
* not with optocoupler outputs (KS45-1x4... und KS45-1x5...)
with basic-licence rail linegerman/english9407-999-12001
®
with expert-licence rail linegerman/english9407-999-12011
68KS 45
Technical data
15Technical data
.
INPUTS
UNIVERSAL INPUT INP1
Resolution:>14 bits
Decimal point:0 to 3 decimals
Digital input filter:adjustable 0.0...9,999 s
Scanning cycle:100 ms
Linearization:15 segments, adaptable with BlueControl®
Measurement value
correction:
Type:single-ended (except for thermocouples)
EMI measuring by means of INP1 (high-impedance mV inputs)
suitable for probes with
constant sensor temperature (heated probes), setting by means
•
of parameter
measured sensor temperature (non-heated probes),
•
measurement by means of INP2
ADDITIONAL INPUT INP2 (CURRENT)
Resolution:>14 bits
Digital input filter:adjustable 0.0...9,999 s
Scanning cycle:100 ms
Linearization:as for INP1
Measurement value correction:2-point or offset
Type:single-ended
Current measurement
Input resistance:approx. 49 W
Span start and span:anywhere between 0 and 20 mA
Scaling:freely selectable –1,999...9,999
Input circuit monitoring:12,5% below span start (2 mA)
* for INP1: high-impedance, without break monitoring
for INP2: high-impedance, break monitoring always active
ß 0,25 mA
-200...100 (150) °C-328...212°Fß 1K0,1 K
0,1 K
-200...850°C-328...1562°Fß 2K
0...4500 [**
ß 0,1 %
ß 0,1 %
ß 0,1 %
ß 0,1 %
ß 0,1 %
0,1 K
0,01 %
0,01 %
0,01 %
0,01 %
0,01 %
Heating current measurement
(via current transformer)
Input resistance:approx. 49 W
Measurement span:0...50 mA AC
Scaling:freely selectable –1,999...9,999 A
ADDITIONAL INPUT INP2 (UNIVERSAL, OPTION)
Resolution:>14 bits
Digital input filter:adjustable 0.0...9,999 s
Scanning cycle:100 ms
Linearization:as for INP1
Measurement value correcti
on:
Type:single-ended, exept
Thermocouples (Table 1)
Cold-junction compensation
•
internal,
- additional error:typ.:
max.:
-
2-point or offset
thermocouples
ß_ 0,5 K
ß -2,5 K
• external,
- constant setting0...100 °C
Remaining technical data as for INP1
Resistance thermometer (Table 2)
Connection technology:3-wire,
Remaining technical data as for INP1
Resistance measuring range
Remaining technical data as for INP1
Current and voltage measuring ranges
(Table 3)
Remaining technical data as for INP1 except
•
Voltage input ranges -10/0...10V, -5...5V are not possible.
•
Millivolt input ranges: high-impedance input for low-impedance
sources
CONTROL INPUT DI1
Configurable as direct or inverse switch or push button!
Contact input
Connection of potential-free contact that is suitable for switching
‘dry’ circuits.
70KS 45
Technical data
Switched voltage:5 V
Switched current:1 mA
Optocoupler input
For active control signals.
Nominal voltage:24 V DC, external supply
Logic ‘0’:-3...5 V
Logic ‘1’:15...30 V
Current demand:max. 6 mA
OUTPUTS
SURVEY OF OUTPUTS
* All logic signals can be ”OR-linked”.
RELAY OUTPUTS OUT1, OUT2, OUT3
Contact type:normally open *
Max. contact rating:500 VA, 250 V, 2A resistive load, 48...62 Hz,
Min. contact rating:6V, 1 mA DC
Swithing cycles (elec
trical):
* Versions with two relays OUT1 & OUT2 have a common terminal.
for I= 1A/2A:
-
? 800.000 / 500.000
(at ~ 250V (resistive load))
Ripple (related to span end): 0...130kHz
Current output
0/4...20 mA, configurable, short-circuit proof.
Control range:-0.5...23 mA
Load:ß700 W
Load effect:ß 0.02%
Resolution:ß 1.5 µA
Error:ß 0.1%
Voltage output
0/2...10V, configurable, not permanently short-circuit proof
Control range:-0.15...11.5 V
Load:³ 2kW
Load effect: ß 0.06%
Resolution:ß 0.75 mV
Error:ß 0.1%
Additional error whenß 0.09%
OUT3 as transmitter supply
using simultaneously the current output
Output:22 mA / ³ 13VDC
OUT3 as logic signal
Load ß 700 W0/ß 23 mA
Load > 500 W0/> 13 V
Note:
If the relays OUT1, 2 and 3 are used to operate external
contactors, these must be fitted with RC snubber circuits to
manufacturer specifications to prevent excessive voltage peaks at
switch-off.
OPTOCOUPLER OUTPUTS OUT1, OUT2
(OPTIONAL)
Galvanically isolated optocoupler outputs. Grounded load:
common ‘plus’ control voltage
Switch rating:18...32 V DC; max. 70 mA
Internal voltage drop:ß 1 V at Imax
Built-in protective circuits:
for short circuit, wrong polarity
Note:
A protective diode for inductive loads must be fitted externally.
OUT3 UNIVERSAL OUTPUT
Galvanically isolated from the inputs. Parallel current/voltage
output with common ‘minus’ terminal (combined use only in
galvanically isolated circuits).