8.1.4Signal end ................................48
8.2Determining the timer run-time ..................48
8.3Starting the timer........................ 48
9BlueControl ............................ 49
10Versions .............................. 50
11Technical data .......................... 51
12Safety hints ............................ 55
12.1Resetting to factory setting .................... 56
4Operating KS4x-1
1Mounting
SP.X
run
Err
Ada
SP.x
run
Err
Adada
SP.x
run
Err
Ada
Mounting
(0.4")
10
118
96 (3.78")
KS 40-1 universal
48 (1.89")
(4.65")
126
125
min.48
Loc
Safety switch
Ü
(1.89")
1..10
(0.04..0.4")
+0,6
45
+0.02
(1.77" )
10V i mA/Pt
or:
Front view KS41-1
max.
60°C
max.
95% rel.
0°Cmin.
48 (1.89")
%
+0.03
+0,8
92
(3.62")
126.
125
KS 41-1 universal
96 (3.78")
Front view KS42-1
126.
Loc10VmA/Pt
Loc10VmA/Pt
Loc 10V mA/Pt
(3.78")
96
KS 42-1 universal
125
96 (3.78")
Ü
a
*
*
Safety switch:
For access to the safety switches, the controller must be withdrawn from the hou
sing. Squeeze the top and bottom of the front bezel between thumb and forefinger
and pull the controller firmly from the housing..
10V i mA/Ptright 1Current signal / Pt100 / thermocouple at InP.1
leftVoltage signal at InP.1
LocopenAccess to the levels is as adjusted by means of BlueControl
(engineering tool)
2
closed 1all levels accessible wihout restriction
1 Factory setting2 Default setting: display of all levels
suppressed, password PASS = OFF
Safety switch 10V i mA/Ptalways in position left or right. Leaving the
safety switch open may lead to faulty functions!
-
l
Caution! The unit contains ESD-sensitive components.
Operating KS4x-15
Electrical connections
2Electrical connections
2.1 Connecting diagram
di2
di3
T
U
Modbus RTU
RXD-B
RGND
DATA B
DATA A
RS485RS422
GND
RXD-A
TXD-B
TXD-A
Option
1
(2)
3
4
5
6
7
8
9
10
11
12
13
14
15
(16)
17
a
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
L
N
e
Logic
90...250V
24V AC/DC
d
c
b
U
HC
mA
OUT1
OUT2
OUT3
INP2
di1
mA
0..10 V*
INP1
b
c
d
a
*Safety switch mA i V in position left
g
Dependent of order, the controller is fitted with :
flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244 or
*Interface description Modbus RTU in seperate manual: see page 50.
KS4x-1 connecting example:
L1
L2
RGNDRGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
DATA B
DATA A
J
KS 40-1
Logic
fuse
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
SSR
contactor
+
fuse
heating
12
13
14
15
(16)
17
10
11
12
13
14
15
RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
PC
R=100 Ohm
converter
RS485-RS232
max. 1000m
”Twisted Pair”
TB 40-1
1
Temperature limiter
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
RT
R = 120...200 OhmT
fuse
reset
+
N1
N2
1 TB 40-1 Temperature limiter
Standard version (3 relays):
TB40-100-0000D-000
other versions on requestr
a
CAUTION:Using a temperature limiter is recommendable in
systems where overtemperature implies a fire hazard or
other risks.
Operating KS4x-19Terminal connection
Operation
KS 40-1 universal
125
126.
SP.x
run
Err
Ada
123OK
3
1
2
3
4
0
5
!
6
"
7
8
§
9
$
%
KS 42-1 universal
125
126.
SP.x
run
Err
Ada
KS42-1
KS 41-1 universal
125
126.
SP.x
run
Err
Ada
KS41-1
KS40-1
3Operation
3.1 Front view
LED colours:
LED 1, 2, 3:yellow
LED OK:green
other LEDs:red
1 Status of switching outputs
OuT.1... 3
2 Lit with limit value 1 ( PArA /
Lim ) not exceeded
3 Process value display
4 Set-point, controller output
5 Signals ConF and PArA level
6 Programmer or timer running
7 Self-tuning active
8 Entry in error list
9 Set-point SP.2 or SP.E is
changing the set-point or the
controller output value
$ Manual mode /spec. function
(® ConF / LOGI )
% PC connection for
BlueControl (engineering
tool)
g
In the upper display line, the process value is always displayed. At parameter,
configuration, calibration as well as extended operating level, the bottom display
line changes cyclically between parameter name and parameter value.
Front view10Operating KS4x-1
3.2 Behaviour after power-on
A
M
l
After supply voltage switch-on, the unit starts with the operating level.
The unit is in the condition which was active before power-off.
If KS4x-1 was in manual mode before power-off, the controller starts with cor
recting value Y2 after switching on again.
3.3 Operating level
Operation
-
The content of the extended operating level is determined by means of BlueCon
trol (engineering tool). Parameters which are used frequently or the display of
which is important can be copied to the extended operating level.
time
out
utomatic
126
125
È
Ì
Ù
126
i
Ò
Ò
i
anua
126
y21
Ù
126
È
Ì
time
out
-
y21
only
display
Ù
125
È
Ì
Ù
Extended operating level
time
out
Errorliste (if error exists)
126
FbF.1
display
switching
Err
126
2
Err
Operating KS4x-111Behaviour after power-on
Operation
3.4 Maintenance manager / Error list
With one or several errors, the extended operating level
always starts with the error list. Signalling an actual entry
in the error list (alarm, error) is done by the Err LED in
the display. To reach the error list press Ù twice.
SP.x
Err LED statusSignificationProceed as follows
blinks
(Status 2)
lit
(Status 1)
off
(Status 0)
Alarm due to existing
error
Error removed,
Alarm not acknowledged
No error,
all alarm entries deleted
Determine the error type in the error list via the
error number
-Change to status 1 after error removal.
Acknowledge the alarm in the error list pressing
key È or Ì
The alarm entry was deleted (Status 0).
-
-Not visible except when acknowledging
126
125
run
Ada
Err
Name
E.1
E.2
E.4
FbF.1
Sht.1
POL.1
FbF.2
Sht.2
POL.2
HCA
SSr
Error list:
DescriptionCausePossible remedial action
Internal error,
cannot be removed
Internal error, can be
reset
Hardware error- Codenumber and hardware
Sensor break INP1
Short circuit INP1
INP1polarity error
Sensor break INP2
Short circuit INP2
INP2 polarity
Heating current alarm
(HCA)
Heating current short
circuit (SSR)
- E.g. defective EEPROM- Contact PMA service
- Return unit to our factory
- e.g. EMC trouble- Keep measurement and power supply
cables in separate runs
- Ensure that interference suppression of
contactors is provided
- Contact PMA service
are not identical
- Elektronic-/Optioncard must be
exchanged
-
Sensor defective
-
Faulty cabling
-
Sensor defective
-
Faulty cabling
-
Faulty cabling
-
Sensor defective
-
Faulty cabling
-
Sensor defective
-
Faulty cabling
-
Faulty cabling
-
Heating current circuit
interrupted, I< HC.A or I>
-
Replace INP1 sensor
-
Check INP1 connection
-
Replace INP1 sensor
-
Check INP1 connection
-
Reverse INP1 polarity
-
Replace INP2 sensor
-
Check INP2 connection
-
Replace sensor INP2
-
Check INP2 connection
-
Reverse INP2 polarity
-
Check heating current circuit
-
If necessary, replace heater band
HC.A (dependent of
configuration)
-
Heater band defective
-
Current flow in heating
circuit with controller off
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3 or the Ò-key.
Configuration, see page 27: ConF / LOGI / Err.r
If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:
DescriptionBehaviour
No error
Faulty control actionRe-configure controller (inverse i direct)
No response of process
Danger of exceeded set-point
(parameter determined)
Output step change too small
(dy > 5%)
Set-point reserve too smallIncrease set-point (invers), reduce set-point (direct)
The control loop is perhaps not closed: check sensor,
connections and process
decrease ( ADA.C) min. output limiting Y.Lo
If necessary, increase (inverse) or reduce (direct) set-point
Increase ( ADA.H) max. output limiting Y.Hi or reduce
( ADA.C) min. output limiting Y.Lo
or increase set-point range
(r PArA / SEtp / SP.LO and SP.Hi )
Operating KS4x-113Maintenance manager / Error list
Operation
3.5 Self-tuning
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt, where
by the process characteristics are used to calculate the parameters for fast line-out
to the set-point without overshoot.
The following parameters are optimized when self-tuning:
Parameter set 1:
Pb1- Proportional band 1 (heating) in engineering units [e.g. °C]
ti1- Integral time 1 (heating) in [s] r only, unless set to OFF
td1- Derivative time 1 (heating) in [s] r only, unless set to OFF
-
t1- Minimum cycle time 1 (heating) in [s] r only, unless Adt0 was set to
“no self-tuning” during configuration by means of BlueControl
Pb2- Proportional band 2 (cooling) in engineering units [e.g. °C]
ti2- Integral time 2 (cooling) in [s] r only, unless set to OFF
td2- Derivative time 2 (cooling) in [s] r only, unless set toOFF
t2- Minimum cycle time 2 (cooling) in [s] r only, unless Adt0 was set to
“no self-tuning” during configuration by means of BlueControl
3.5.1 Preparation for self-tuning
Adjust the controller measuring range as control range limits. Set values
w
rnG.L and rnG.H to the limits of subsequent control. (Configuration
rControllerrlower and upper control range limits)
ConFrCntrr rnG.L and rnG.H
Determine which parameter set shall be optimized (see tables above).
w
3.5.2 Self-tuning sequence
®.
®
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start-conditions on page 8).
Subsequently, a correcting variable step change to 100% is output.
The controller attempts to calculate the optimum control parameters from the
process response. If this is done successfully, the optimized parameters are taken
over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100%
cooling energy) is output from the set-point.
After successfull determination of the “cooling parameters”, line-out to the
set-point is using the optimized parameters.
Self-tuning14Operating KS4x-1
Start condition:
Rest condition
w
For process evaluation, a stable condition is required. Therefore, the controller
waits until the process has reached a stable condition after self-tuning start.
The rest condition is considered being reached, when the process value oscillati
on is smaller than ± 0,5% of (rnG.H - rnG.L).
Set-point reserve
After having come to rest with 0% correcting variable or with Y.Lo, the
controller requires a sufficient set-point reserve for its self-tuning attempt, in
order to avoid overshoot.
Sufficient set-point reserve:
inverse controller:(with process value<set-point-(10% of SP.Hi - SP.LO)
direct controller:(with process value>set-point+ (10% of SP.Hi - SP.LO)
3.5.3 Self-tuning start
Operation
-
g
3.5.4 Self-tuning cancellation
Self-tuning start can be locked via BlueControl
(engineering tool) ( P.Loc).
The operator can start self-tuning at any time.
For this, keys Ù and È must be pressed simultaneously. The AdA LED starts blinking. The
controller outputs 0% or Y.Lo, waits until the
process is at rest and starts self-tuning (AdA
LED lit permanently).
After successful self-tuning, the AdA-LED is off and the controller continues
operating with the new control parameters.
By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È
key simultaneously. With manual-automatic switch-over configured via Ò key,
self-tuning can also be canceled by actuating Ò key. The controller continues
operating with the old parameters in automatic mode in the first case and in ma
nual mode in the second case.
By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning
is prevented due to the control conditions. In this case, self-tuning was cancelled
by the controller.
Dependent of control type, the output status is:
3-pnt. stepping controller:
w
actuator is closed (0% output)
2-pnt./ 3-pnt./ continuous controller:
w
If self-tuning was started from the automatic mode, the controller output is
0%. With self-tuning started from manual mode, the controller output is Y2.
SP.x
126
125
run
Ada
Err
-
Operating KS4x-115Self-tuning
Operation
3.5.5 Acknowledgement procedures in case of unsuccessful self-tuning
1.Press keys Ù and È simultaneously:
The controller continues controlling using the old parameters in automatic
mode. The Err LED continues blinking, until the self-tuning error was
acknowledged in the error list.
2.Press key Ò (if configured):
The controller goes to manual mode. The Err LED continues blinking,
until the self-tuning error was acknowleged in the error list.
3.Press key Ù :
Display of error list at extended operating level. After acknowledgement
of the error message, the controller continues control in automatic mode using
the old parameters.
Cancellation causes:
r page 13: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"
3.5.6 Examples for self-tuning attempts
(controller inverse, heating or heating/cooling)
Start: heating power switched on
Heating power Y is switched off (1).
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning
attempt is finished and the new parameter are used for controlling to
set-point W.
Start: heating power switched off
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning
attempt is finished and control to the
set-point is using the new parameters.
X
W
100%
0%
X
W
100%
0%
Y
Star t r
Y
start r
1
1
blinks
2
2
3
t
t reversal point
t
t reversal point
blinks
Self-tuning16Operating KS4x-1
Operation
y
Start: at set-point
X
W
Heating power Y is switched off (1).
1
blinks
2
3
t reversal point
t
If the change of process value X was
constant during one minute and the
control deviation is > 10% of SP.Hi SP.LO (2), the power is switched on
(3). At the reversal point, the self-tu
ning attempt is finished, and control
to set-point W is using the new para
-
100%
Y
0%
start r
-
meters.
Three-point controller
The parameters for heating and coo
ling are determined in two attempts.
The heating power is switched on
(1). At reversal point 1, heating para
meters Pb1, ti1, td1 andt1
-
X
W
+100%
Y0%
-100%
start r
t reversal point 1
1
2
t reversal point 2
3
t
are determined. The process value is
lined out to the set-point (2). The
cooling power is switched on (3). At
reversal point 2, parameters Pb2, ti2, td2 and t2 are determined and the
self-tuning attempt is finished. Control to set-point W is using the new parameters.
3.6 Manual tuning
The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting va
riable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T
sponse) can be used to determine the maximum rate of increase v
100%
Y
0%
x
X
max
and x
g
(step change from 0 to 100 %) or Dt and Dx (partial step re
max
.
max
y=correcting variable
h
Y
=control range
h
Tu=delay time (s)
Tu
t
Tg
{X
{t
t
Tg=recovery time (s)
X
V
=maximum process value
max
{{x
=
t
max
Xmax
=
Tg
= max. rate of
increase of process value
-
-
Operating KS4x-117Manual tuning
Operation
The control parameters can be determined from the values calculated for delay
time T
cording to the formulas given below. Increase Xp, if line-out to the set-point os
cillates.
Parameter adjustment effects
ParameterControlLine-out of disturbancesStart-up behaviour
Pb1 higher increased dampingslower line-outslower reduction of duty cycle
td1 higher reduced dampingfaster response to disturbances faster reduction of duty cycle
ti1 higher increased dampingslower line-outslower reduction of duty cycle
, maximum rate of increase v
u
lowerreduced dampingfaster line-outfaster reduction of duty cycle
lowerincreased dampingslower response to disturbances slower reduction of duty cycle
lowerreduced dampingfaster line-outfaster reduction of duty cycle
, control range Xhand characteristic K ac
max
-
-
Formulas
K = Vmax * Tucontroller behaviorPb1 [phy. units]td1 [s]ti1 [s]
PID1,7*K2*Tu2*Tu
With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 £ 0,25 * Tu
PD0,5 * KTuOFF
PI2,6 * KOFF6*Tu
PKOFFOFF
3-point-stepping1,7 * KTu2 * Tu
3.7 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Ge
nerally, outputs OuT.1... OuT.3 can be used each for alarm signalling. If more
than one signal is linked to one output the signals are OR linked. Each of the 3 li
mit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which
can be switched off individually (parameter = “OFF”). Switching difference
HYS.x of each limit value is adjustable.
-
-
Alarm handling18Operating KS4x-1
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.