West Control Solutions 6170+, 8170+, 4170+ Data Sheet

West 6170+,8170+ & 4170+ Valve Motor Controller
Jumperless Configuration
Auto Detected Hardware Process & Loop Alarms Modbus Communications Auto or Manual Tuning Motorised Valve Control Valve Position Indication Remote/Dual Setpoint Options Available in 1/16, 1/8 & 1/4 DIN Format
The new Plus Series VMD Controllers have been specifically designed for open loop valve motor drive
applications and feature the improved Plus Series interface and greater field flexibility.
Specification
Features
Control Types Full PID with Pre-tune, Self-tune and manual tuning modes. Valve Control Open Loop Valve Motor Drive. Auto/Manual
Output Configuration Up to 4 possible, two required for valve control, additional outputs for alarm, 24VDC transmitter
Alarm 1 & 2 Types Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process
Human Interface 4 button operation, dual 4 digit 10mm & 8mm (6170+ and 8170+) and 13mm & 10mm (4170+) high
PC Configuration Off-line configuration from PC serial port to dedicated configuration socket (communications option
power supply or retransmit of process value or setpoint.
control security. Process alarms have adjustable hysteresis.
LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED indicators
not required). Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
Input
Thermocouple J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%. RTD 3 Wire PT100, 50 per lead maximum (balanced) DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Impedance >10M for Thermocouple and mV ranges, 47K for V ranges and 5 for mA ranges Accuracy ±0.1% of input range ±1 LSD (T/C CJC better than 1°C) Sampling 4 per second, 14 bit resolution approximately Sensor Break Detection <2 seconds (except zero based DC ranges), control O/P’s turn off, high alarms activate for T/C and
Scaleable -1999 to 9999, with adjustable decimal point
mV ranges, low alarms activate for RTD, mA or V ranges
Output & Options
Control & Alarm Relays Contacts SPDT 2 Amp resistive at 240V AC (120V AC Max for direct VMD), >500,000 operations.
Control SSR Driver Outputs Triac Outputs 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz. 140V Max for direct VMD. DC Linear Outputs 0 to 20mA, 4 to 20mA into 500 max, 0 to 10V, 2 to 10V, 0 to 5V into 500 min.
Transmitter Power Supply Output 24VDC (nominal) into 910 minimum to power external devices Serial Communications 2 Wire RS485, 1200 to 19200 Baud, Modbus protocol
Digital Input Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input
(1A 2xSPST 200,000 operations for Dual Relay) Drive capability >10V DC in 500 minimum
Accuracy ±0.25% at 250 (degrades linearly to 0.5% for increasing burden to specified limits) Retransmit of PV or SP Only.
Ref DS-Px170-1209-1-EN
© West Control Solutions 2009