WESTCODE An IXYS Company French Ferrule Type Fuses 700V
Electrical Characteristics:
Times vs current characteristics
The following curves indicate, for each rated current, pre-arcing time as a function of RMS value of prearcing current I.
Tolerance for mean pre-arcing current: ±10% = ratings from 1, 2, 4A
± 8% = ratings from 6 to 63A
Fuses with gR characteristics can eliminate all overloads. They do not show a minimum breaking
capacity but limit currents of non-operation or operation in compliance with standard VDE 636/23.
I ≤ 4I ≥ 6
Total clearing I²t:
Horizontal curves show maximum values of total clearing I2t (I2tt) for each rated current as a function of
prospective current Ip @ 690V cosϕ = 0.15 (for 63A @ 600V cosϕ = 0.15). Oblique lines indicate total
clearing duration Tt, with associated pre-arcing duration in brackets.
Data Sheet F070BxxxN/S Issue 1 Page 3 of 5 March, 2005
![](/html/8e/8eed/8eed8d0dd681edb81e4373352cf2c9f408b792306c7b8eaa53d77fddadb939fa/bg2.png)
WESTCODE An IXYS Company French Ferrule Type Fuses 700V
Cut off Characteristics:
The curves below show, for each rating, value of peak let-through current IC as a function of available
fault current Ip.
I ≤ 4I ≥ 6
Corrective Factor: Peak Arc Voltage:
Mean curves showing variation of total clearing
2
time (I
tt) and total clearing duration Tt as a
function of operating voltage U.
Curves showing peak value Um of arc voltage
which appears across fuse-link as a function of
operating voltage U @ cosϕ = 0.15.
(1) 63A rating – 600V
(2) (2) 1-50A rating – 690V
Data Sheet F070BxxxN/S Issue 1 Page 4 of 5 March, 2005