Westcode Semiconductors F070BxxxN, F070BxxxS Catalog Page

WESTCODE An IXYS Company French Ferrule Type Fuses 700V
Date:- 17 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
French Ferrule Type
French Ferrule Fuses
Voltage Rating 700V
Current Rating from 1A to 50A
Size 14x51
Key Features:
60269.1 and 4.
660V to 690V voltage rating complying with IEC 33
Non Magnetic construction
gR Characteristics with current ratings from 1A to 32A in accordance with VDE 636-23
¾ Clearing all overloads ¾ Improved safety and protection ¾ Enabling selective co-ordination among all distribution circuit fuses
All models available with or without trip-indicator
gRC fuses from 8A to 50A are 700VAC-DC UL recognised
Data Sheet F070BxxxN/S Issue 1 Page 1 of 5 March, 2005
WESTCODE An IXYS Company French Ferrule Type Fuses 700V
Main Characteristics:
Size
14x51
without
trip
indicator
Size
14x51
with Trip
indicator
Voltage
(V)
U
N
690
Voltage
U
(V)
N
690
Ref:
F070B001N
F070B002N
F070B004N
F070B006N
F070B008N
F070B010N
F070B012N
F070B016N
F070B020N
F070B025N
F070B032N
F070B040N
F070B050N
Ref:
F070B001S
F070B002S
F070B004S
F070B006S
F070B008S
F070B010S
F070B012S
F070B016S
F070B020S
F070B025S
F070B032S
F070B040S
F070B050S
Current
rating
(A)
I
N
1
2
4
6
8
10
12
16
20
25
32
40
50
Current
rating
(A)
I
N
1
2
4
6
8
10
12
16
20
25
32
40
50
Pre-arcing
2
I
t @ 1 ms
2
tp(kA2s)
I
0.31 1.4 0.17 0.35
1 4.3 0.33 0.60
6.7 30 0.77 1.4
1.4 19 1.3 2.5
2.4 30 1.5 3.0
4.3 44 1.75 3.3
5.4 65 2.25 4.25
13 110 2.5 4.8
27 175 2.75 5.25
53 300 3.0 5.8
97 550 3.5 7.0
210 1210 4.5 8.8
390 2250 5.0 10
Pre-arcing
2
I
t @ 1 ms
2
tp(kA2s)
I
0.8 3.5 0.17 0.35
1.5 6.7 0.33 0.60
7.2 33 0.77 1.4
1.4 19 1.3 2.5
2.4 30 1.5 3.0
4.3 44 1.75 3.3
5.4 65 2.25 4.25
13 110 2.5 4.8
27 175 2.75 5.25
53 300 3.0 5.8
97 550 3.5 7.0
210 1210 4.5 8.8
390 2250 5.0 10
Notes: Minimum operating voltage for integrated trip indicator = 20V
Total Clearing
2
t @ UN (kA2s)
I
Total Clearing
2
t @ UN (kA2s)
I
Watt Losses
0.8IN I
N
Watt Losses
0.8IN I
N
Tested
Interrupting
rating
100kA @ 690V
Tested
Interrupting
rating
100kA @ 690V
Data Sheet F070BxxxN/S Issue 1 Page 2 of 5 March, 2005