Date:- 18 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
European Square Body Type Fuses – 700V
German Standard DIN 80
Voltage Rating from 500V to 700V
Current Rating from 80A to 400A
aR Characteristics
Size 000
Key Features:
Extremely high interrupting rating fuses for the protection of power semiconductors according to
60269.1 and 4
690V voltage rating for currents ratings of 20A to 400A
Non Magnetic construction
aR Characteristics with ratings from 80 to 400A according to VDE 636-23 and IEC 60269.4
All models comply with DIN80 standard with blown fuse indication, available with or without trip
indicator.
Microswitch system reference : MS 4L 2-5 B6+PRES
Data Sheet. 070GQCAxxxxF/N & 070GTCAxxxxF Issue 1 Page 1 of 5 March, 2005
WESTCODE An IXYS Company German Standard DIN 80 Knife Blade Fuses – 700V
Main Characteristics:
German Standard DIN 80, aR, Size 000 with indicator, silicated.
IN(A)
80
100
125
160
200
250
350
400
Pre-arcing
2
I
t @ 1 ms
2
I
tp(A2s)
390 2500 11.6 21
690 4200 12.7 23
1300 8900 14.3 26
2700 16000 17 31
5250 31500 19.8 36
9900 52000 24.8 45
15500 82000 31.9 58
22400 110000 31.9 58
33200 160000 36.3 66
Voltage
Rating
(V)
U
N
690V
690V +6%
500V
Ref:
070GQCA0080F
070GQCA0100F
070GQCA0125F
070GQCA0160F
070GQCA0200F
070GQCA0250F
070GQCA0315F
050GQCA0350F
050GQCA0400F
Micro
Switch
N
N
N
N
N
N
N 315
N
N
Current
rating
Note: Minimum operating voltage for integrated trip indicator = 20V
German Standard DIN 80, aR, Size 000 without indicator, silicated.
IN(A)
80
100
125
160
200
350
400
Pre-arcing
2
I
t @ 1 ms
2
I
tp(A2s)
390 2500 11.6 21
690 4200 12.7 23
1300 8900 14.3 26
2700 16000 17.0 31
5250 31500 19.8 36
9900 52000 24.8 45
15500 82000 31.9 58
22400 110000 31.9 58
33200 160000 36.3 66
Voltage
Rating
(V)
U
N
690V
690V +6%
500V
Ref: MC
070GQCA0080N
070GQCA0100N
070GQCA0125N
070GQCA0160N
070GQCA0200N
070GQCA0250N
070GQCA0315N
050GQCA0350N
050GQCA0400N
Current
rating
N
N
N
N
N
N 250
N 315
N
N
Total Clearing
2
I
t @ UN I2t
(A2s)
Total Clearing
2
I
t @ UN I2t
(A2s)
Power Losses
t
0.8I
Power Losses
t
0.8I
N
I
N
Tested Interrupting
I
N
Tested Interrupting
N
rating
200kA @ 690V
120Ka @ 500V
rating
200kA @ 690V
120Ka @ 500V
German Standard DIN 80, aR, Size 000 Trip (Tag) Indicator, micro switch capable, non-silicated.
Voltage
Rating
U
(V)
N
690V
690V +6%
500V
Ref: MC
070GTCA0080F
070GTCA0100F
070GTCA0125F
070GTCA0160F
070GTCA0200F
070GTCA0250F
070GTCA0315F
050GTCA0350F
050GTCA0400F
Current
rating
Y
Y
Y
Y
Y
Y
Y 315
Y
Y
IN(A)
80
100
125
160
200
250
350
400
Pre-arcing
2
I
t @ 1 ms
2
tp(A2s)
I
Total Clearing
2
I
t @ UN I2t
(A2s)
t
Watt Losses
0.8I
N
390 2500 11.6 21
690 4200 12.7 23
1300 8900 14.3 26
2700 16000 17 31
5250 31500 19.8 36
9900 52000 24.8 45
15500 82000 31.9 58
22400 110000 31.9 58
33200 160000 36.3 66
I
Tested Interrupting
N
200kA @ 660V
120Ka @ 500V
rating
Notes: Minimum operating voltage for integrated trip indicator = 20V
DIN80 aR Size 000 - 070GTCAxxxxF with blow fuse trip indicator may be adapted to use Micro switch ref: MS 4L 2-5 B6
Data Sheet 070GQCAxxxxF/N & 070GTCAxxxxF Issue 1 Page 2 of 5 March, 2005