Welch Vacuum 8925 User Manual

OWNER’S MANUAL
FOR
DIRECTORR® DIRECT-DRIVE VACUUM PUMP
MODELS:
8905 8907 8912 8917 8920 8925
WARNING
Do not block the exhaust port. Pressure will build up with the
potential of oil case bursting with possible injury to personnel.
WARNING
Pumps being run continuously above 1 torr should use an
exhaust oil recycler.
WARNING
Pumps not recommended for filtration, aspiration or drying
electrophoresis gels.
Gardner Denver Welch Vacuum Technology, Inc. 5621 W. Howard Street Niles, IL 60714 Phone: (847) 676-8800 Fax: (847) 677-8606 (Technical Support) E-Mail: welchvacuum@gd-thomas.com Part No. 67-1483R2.5 Web-Page: www.welchvacuum.com Printed in USA
For outside of U.S. and Canada, contact your local Gardner Denver sales office, see back page
INSTRUCTION
WARNING AND CAUTION
PLEASE READ BEFORE OPERATION
While reading your manual, please pay close attention to areas labeled:
WARNING AND CAUTION.
The description of each is found below.
WARNING
Warnings are given where failure to observe instruction could
result in injury or death to people.
CAUTION
Cautions are found where failure to observe the
instruction could result in damage to the equipment,
associated equipment and process.
These units conrm to the SI International system of units of measurement.
The following symbols (with recommendation of IEC1010 ) of warning will be found on the pump.
Caution - refer to accompanying documents
Caution - risk of electrical shock
Caution - hot surface
WARNING
Motor includes a self resetting thermal cutout and the pump could
restart without actuation under fault condition.
2
TABLE OF CONTENTS
SECTION PAGE
Section 01 - Installation 05
1.01 Unpacking 05
1.02 Pump Mounting 05
1.03 Pump Location / Environmental Conditions 05
1.04 Exhaust Provisions 05
1.05 Electric Power 06
1.06 Vacuum Connections 07
1.07 Vacuum Gauges 07
1.08 Vacuum Pump Oil 07
Section 02 - Pump Features & Principles of Operation 08
2.01 General Description 08
2.02 Principles of Vacuum Pump Operation 09
2.03 Effects of Continued Pressure Reduction 09
2.04 Ultimate Pressure 09
2.05 Pump Mechanism Description 09
2.06 Intake Anti-Suckback Protection 10
2.07 Pump Lubrication 10
2.08 Exhaust Filter 10
2.09 Gas Ballast Valve 10
2.10 UNIBARBTM Intake Fitting 11
Section 03 - Specications 12
3.01 Specication Chart 12
Section 04 - Motor Power Specications / Features 14
4.01 Motor Specications Chart 14
4.02 Changing the voltage setting; 8907, 8912 & 8917 “A” Models 15
4.03 Changing the voltage setting; 8907, 8912 & 8917 “C” Models 15
4.04 Changing the voltage setting; 8905, 8920 & 8925 “A” Models 16 (Includes instructions to attach solenoid valve)
4.05 Other Electrical Congurations 16
4.06 Explosion Proof Pumps 16
Section 05 - Operation 17
5.01 Starting Procedure 17
5.02 High Pressure Operation 17
5.03 Shutdown Procedures 17
3
TABLE OF CONTENTS
SECTION PAGE
Section 06 - Maintenance 18
6.01 Vacuum Problems 18
6.02 Oil Change 19
6.03 Developing a Maintenance Schedule 19
6.04 Lip Seal / Gasket Change 20
Section 07 - Trouble Shooting 24
7.01 Leak Detection Problems 24
7.02 Trouble Shooting Guide 25
Section 08 - Specications 26
8.01 Shaft Seal Replacement 26
8.02 Minor Repair Kits 26
8.03 Major Factory Repair 26
Section 09 - Accessories 27
9.01 Pump Oil 27
9.02 Exhaust Filter 27
Section 10 - Drawings and Speed Curve 28
10.10 Speed Curve 28
10.20 Dimensional Drawing 29
10.30 Pump Exploded Views and Parts List 30
10.40 Module Exploded Views and Parts List 36
10.50 Oil Case Exploded View and Parts List 39
Section 11 - Warranty 40
Section 12 - MSDS Sheet for 8995P 41
4
Section 1: INSTALLATION
1.01 Unpacking
Carefully remove the pump from the shipping carton. Keep all paperwork and inspection tags for future reference. If shipping damage has occurred, a claim must be led with the carrier immediately; keep the
shipping container for inspection by the carrier.
1.02 Pump Mounting
Rubber bumpers are supplied with the pump base. They isolate noise and eliminate creeping. For more rigid mounting requirements the pump base can be bolted directly to a surface by removing the bumpers
from the base and using the mounting holes and slots featured on the base.
1.03 Pump Location / Environmental Conditions
The pump should be located in a clean and well-ventilated area and adequate space should be provided wherever possible for routine maintenance such as oil changes. For best performance, the pump should be located as closely as possible to its system. Determining factors for pump location should include length and size of connections, the number of bends, and the type of exhaust connections.
1.04 Exhaust Provisions
Exhaust connections will be determined by the type of system to be exhausted and the desired cleanliness of the air surrounding the pump. Under normal pumping conditions the optional exhaust lter will be adequate. Refer to Section 9, Accessories for available exhaust lters. Where extreme exhaust conditions are encountered, it is best to pipe the exhaust out of the building. Always use thick walled rubber vacuum hose, wire reinforced PVC tubing or metal pipe for exhaust lines to avoid the possibility of the line becoming crimped or collapsing resulting in dangerous exhaust line blockage.
The exhaust connection is a 1”-20 threaded port for all Models except 8905 which is 3/4”-20. The port is located on top of the oil reservoir. See section 9.02 Exhaust Filters to nd the correct lter for each pump. If a hose nipple is preferred for the exhaust port, use part number 1393K for models 8907, 8912 and 8917. Call Welch customer support (847) 676-8800, ext. 1, prior to start-up if you have any questions.
WARNING
Never block or impede air flow from the exhaust port. High
pressure can build up within the oil reservoir if the exhaust port
is blocked. Check frequently, especially if exhaust is piped
out of the building.
5
1.05 Electric Power For Model 8905
Compare the pump motor rating, printed on a label on the side of the motor and on the serial number tag, to the power source, to be sure they agree in voltage, phase, and frequency. Pump installation must comply with local electrical codes which dictate appropriate protection devices such as fuses or circuit breakers. Know the location of the circuit breaker protecting the electrical outlet for the pump.
For Models 8907, 8912 & 8917
Compare the pump motor rating, printed on a label on the side of the motor and on the serial number tag, to the power source, to be sure they agree in voltage, phase, and frequency. Pump installation must comply with local electrical codes which dictate appropriate protection devices such as fuses or circuit breakers. Know the location of the circuit breaker protecting the electrical outlet for the pump. Only the Models 8907C, 8912C and 8917C have “global motors” that operate over a wide range of voltages (100-120V, 200-30V). They also operate at frequencies of 50Hz and 60 Hz. Power is single phase.
For Models 8920 & 8925
Compare the pump motor rating, printed on a label on the side of the motor and on the serial number tag, to the power source, to be sure they agree in voltage, phase, and frequency. Pump installation must comply with local electrical codes which dictate appropriate protection devices such as fuses or circuit breakers. Know the location of the circuit breaker protecting the electrical outlet for the pump.
CAUTION
Make certain the power settings on the pump match your power
source before attempting to operate the pump.
(Additional information can be found in section 4: Motor Power).
6
1.06 Vacuum Connections
TM
The pump inlet is equipped with a UNIBARB
7/16” and 13/16” hose tting. The inlet is located next to the pump handle. It contains a screen to collect any debris from getting into the pump. An extensive line of vacuum pump ISO ttings, hoses, traps, etc. is available from Welch to meet the requirements of most vacuum systems. For the best vacuum, use a hose clamp in conjunction with a vacuum hose to hose nipple connections. Welch offers a number of different types of vacuum tubing
and connectors.
See Section 9 - Accessories or call Welch customer support (847) 676-8800, Extension 1. The choice of connections and ttings can have a very marked effect on the pumping speed at the vacuum chamber. Any connection placed between the pump and the chamber creates an impedance to the ow of gas. This is particularly true at low pressures in the millitorr range where the gas ow is substantially molecular in character. The gas ow is then dependent upon the kinetic activity of the molecules to bring it to the pump intake. This impedance is described by the term “conductance”. The conductance of a tube is proportional to the cube of its diameter and inversely proportional to its
length. Therefore, connecting lines should be as large in diameter and as short in length as practical.
For best results the diameter of the connecting tube should be at least as large as the diameter of the pump intake. To avoid a large reduction in pumping speed at the vacuum chamber, the conductance of the line must be considerably greater than the speed of the pump. Sharp bends in vacuum lines also contribute to conductance. To avoid reductions in pumping speed, minimize the number of 90º angles in the vacuum system.
1.07 Vacuum Gauges
The type of vacuum gauge to be used in a system is determined largely by the pressure range to be measured. A thermocouple or pirani gauge is recommended for measuring pressures in the range produced by these pumps. See Website or call for additional information.
1.08 Vacuum Pump Oil
WARNING
The vacuum pump is shipped witout oil inside to prevent possible
spillage during shipment. Oil must be added prior to use.
Filling with Fresh Oil Be sure the pump is lled with oil to the level indicated on the oil ll window. When additional oil is required, use only DIRECTORR® Gold Vacuum Oil , pump performance is not guaranteed with other brands of oil. Do not overll the pump, and be sure to replace the oil ll plug. Remove the oil ll plug located on the top of the oil case and add the oil supplied in a bottle packaged
with each pump.
WARNING
Use only DIRECTORR® Premium or Gold Vacuum Pump Oil.
The ll plug has a raised middle section and a center slot for easy turning either by hand or with a screwdriver. After the pump has been running for at least 15 minutes, check the oil level again. The oil level should be maintained at the “full” mark on the oil level window while the pump is operating. Do not overll, excess oil tends to be splashed out the pump exhaust. Guidelines for the frequency of oil changes and the oil changing procedure can be found in Section 6-2: Oil Change
7
Section 2: PUMP FEATURES AND PRINCIPLES OF OPERATION
2.01 General Description
All of the Welch Vacuum Pumps are two-stage, rotary-vane, oil sealed vacuum pumps. These Vacuum Pumps offer a number of features that improve performance, or protect the pump or vacuum system under specic operating conditions.
2.02 Principles of Vacuum Pump Operation
The main purpose of a vacuum pump is to reduce the pressure in a vessel or a closed system. The
degree of pressure reduction is dependent upon the requirements of the application and the type of
vacuum pump employed. Rotary vane, oil-sealed vacuum pump operation is described in this section.
Pressure reduction in a closed system is accomplished by repeatedly removing a portion of the original volume of gas contained in the system. Removal is performed by the action of the rotating elements of the pump which cause a given space to be successfully enlarged and diminished. Figure 2.1 illustrates a section through a typical stage of rotary-vane pump. Note that this gure is not intended to illustrate exactly the internal components of the pumps; its purpose is to illustrate the general operating principles of vacuum pumps.
The rotary action of the pump creates a hollow space of chamber (1) which expands as the pump rotates. As the chamber expands, the pressure in the chamber decreases. As a result, gas is drawn into the chamber due to the difference in pressure between the chamber and the inlet (4) to the chamber. (The inlet is the only place where gas can ow into the chamber.) Once the vane (3) moves past the inlet (4), it seals the inlet against the chamber (1) and the gas becomes trapped between the vanes (2 and 3). The chamber (1) formed by the enclosed space between the vanes then begins to decrease in volume as the rotor revolves, compressing the gas. The pressure of the compressed gas becomes greater than atmospheric pressure. When the vane (2) moves past the exhaust port (5) the compressed gas in the chamber is forced out through the exhaust port.
Figure 2.1 Typical Rotary Vane Pump, Schematic Diagram
This expansion/compression cycle constitutes one complete cycle of the pump operation. This cycle is repeated as the vane (2) passes the intake port and seals it against the atmosphere. Therefore, two pump cycles are performed during each revolution of the pump rotor.
8
2.03 Effects of Continued Pressure Reduction
The quantity of gas in the vessel (6) is reduced with each evacuation cycle. The gas remaining in the vessel expands to ll the vessel and consequently with each cycle the pressure in the vessel is reduced. This is a manifestation of Boyle’s Law which states that, for a constant temperature, the volume of a body of gas is inversely proportional to its pressure; i.e., if the volume is enlarged the pressure must be
reduced.
As the amount of gas in the vessel is steadily diminished, its pressure is correspondingly reduced. The action of the pump must therefore compress a successively smaller quantity of gas with each cycle to something greater than atmospheric pressure in order to expel it from the pump. At the beginning of an evacuation sequence, the compression ratio is very small. In the rst cycle of operation the pump draws in a volume of gas at atmospheric pressure and expels it at approximately atmospheric pressure. In contrast, near its ultimate pressure, a pump draws in gas at (for example) 30 millitorr and must compress it to more than 760,000 millitorr (atmospheric pressure) in order to expel it from the pump. Since the exhaust valve is generally spring loaded to provide a good seal, the pressure
required to open it is somewhat greater than atmospheric pressure. Therefore, at an ultimate pressure
of 1.3 x 10-4 mbar 0.1 millitorr, (1 x 10-4 Torr) the compression ratio performed by the pump is greater than 1,000,000 to 1.
2.04 Ultimate Pressure
As described previously, a quantity of gas is removed from the system with each cycle of the pump. Therefore, the pressure of the gas remaining in the system is reduced with each pump cycle. Since the pump can remove only a small portion of the gas with each pump cycle, it is obvious that this method of evacuation can never completely remove all the gas in the vessel. In addition to this, all the components of the system contain minute sources of gas leakage which are impossible to seal completely against atmospheric pressure. Outgassing of materials within the system provide additional sources of gas. As a result, after prolonged pumping, a state of equilibrium is reached in which the gas introduced from all the leakage sources is balanced by the ability of the pump to remove gas from the system. This state of equilibrium is referred to as the ultimate pressure or blankoff pressure of the pump and its system. No matter how much additional pumping time is provided, no further reduction in system pressure will
be accomplished once ultimate pressure is attained.
2.05 Pump Mechanism Description
This vacuum pump incorporates two in-line rotary-vane stages with interconnecting ports. When in operation, the intake stage is at lower pressure and the exhaust stage is at higher pressure relative to each other. Each stage contains a rotor assembly consisting of a rotor with two vanes and a stator. The two
rotors are combined on one shaft, and the two stators are combined in a common housing. The pump
shaft turns the rotors, causing the vanes in each section to sweep the surface of their stators. The vanes
are pressed against the stators by centrifugal force.
Each stage has an exhaust valve. Gas expelled from the rst stage exhaust passes through an interstage port to the intake of the second stage. The second stage compresses the gas further, then expels it from the second stage exhaust valve to the atmosphere. An adjustable gas ballast valve is located in the pump’s exhaust stage. The purpose of the gas ballast is to reduce or eliminate vapor condensation in the pump. The function of the gas ballast valve is
described later in this section.
The pump is mounted inside an oil case which is a reservoir for the oil that lubricates the pump. The electric motor shaft drives the pump shaft via a coupling. There is a coupling body on the end of each shaft; a coupling spider between the two coupling bodies transfers the power from the motor shaft to the
pump shaft.
9
2.06 Intake Antisuckback Protection
When power to the pump is turned off, this device closes automatically, maintaining vacuum in the system being evacuated, and vents the inside of the pump to atmospheric pressure.
2.07 Pump Lubrication
To ensure efcient operation and proper maintenance, and to minimize noise and oil vapors, it is important to use the correct type and quantity of oil. DIRECTORR® Gold Vacuum Oil has been especially developed to have the proper viscosity, low vapor pressure, and chemical stability needed to produce peak pumping efciency. The ultimate vacuum guarantee on Welch pumps applies only when this oil is used. Therefore, DIRECTORR® Gold Vacuum Oil is the only oil recommended for use with these pumps. Each pump is supplied with sufcient oil for lling. Additional oil is available. See Section 9: Accessories.
2.08 Exhaust Filter
Any oil-sealed vacuum pump tends to discharge oil mist from its exhaust port when the pump operates under high-ow conditions, such as when the pump’s intake is at or near atmospheric pressure. Typically, oil mist in the form of a white puff of “smoke” can be seen from the exhaust port when no lter is used. Once the vacuum level and the corresponding air ow through the pump are reduced, very
little, if any, oil mist will be emitted.
An exhaust lter is recommended for any vacuum pump installation where the pump operates at high intake pressures for a prolonged period of time. Oil droplets entrained in the pump’s exhaust are removed by the exhaust lter element. Use of an exhaust lter typically reduces or bafes pump noise as well. Exhaust lters are sometimes referred to as Oil Mist Eliminators. See Section 9 - Accessories.
2.09 Gas Ballast Valve
The gas ballast valve can increase the pump’s water vapor tolerance. (The gas ballast valve is sometimes referred to as a vented exhaust valve.) In many vacuum pump applications the gases being pumped from a system are a combination of permanent gases and undesirable vapors such as water vapor. Under some conditions, the vapors condense in the second stage of the pump and contaminate the oil. The gas ballast valve reduces oil contamination by decreasing or eliminating vapor condensation. Vapor condensation is most likely to take place when the gas compression ratio is high, i.e. when the pump compresses a relatively large volume of gas to a small volume. Whether or not condensation takes place is dependent upon several factors, including the proportion of permanent gases to vapors at the pump intake. If the gases being pumped consist entirely of vapors, condensation will denitely occur unless the gas ballast valve is opened. The gas ballast valve adds a small amount of air at atmospheric
pressure to the gas being compressed in the second stage. This reduces the compression required to
push the gas out past the exhaust valve (less reduction in volume is required), and therefore reduces or
eliminates condensation.
When the gas ballast valve is open, the pump has to work a little harder, resulting in a slight increase in operating temperature. The increase in temperature is small, however, and is not harmful to the pump. Also, the pump is slightly noisier, and the pump’s ultimate pressure is somewhat reduced. Therefore, the gas ballast valve should be kept closed when it is not needed. Note that the gas ballast is not equally effective on all diffrent types of chemical vapors, so it may not always eliminate condensation
completely.
10
2.10 UNIBARB
TM
Intake Fitting - Simplies Small Hose Connections
The Unibarb intake tting allows the user to be able to use either 7/16” or 13/16” ID hose to connect to this system. However, the choice of hose size can have a very marked difference on pumping speed. It is the best to have the largest connection I.D.(internal diameters) as possible. However, we recognize many lab appliances use hose barbs accepting small I.D. hose.
The conductance of a tube is proportional to the cube of its diameter and inversely proportional to its
length. Therefore, connecting line should be as large in diameter and short in length as practical.
Included is a free hose clamp to hold the hose in place.
11
Section 3: PUMP SPECIFICATIONS
SPECIFICATION 8905 8920 8925
Free Air Displacement CFM (L/min) @ 60Hz 1.8 (52) 7.7 (218) 11.3 (320) (L/min) m3h @ 50Hz (43) 1.5 (182) 10.8 (266) 16.0
Normal Pumping Speed CFM (L/min) @ 60Hz 1.5 (43) 7.4 (210) 10.0 (283) (L/min) m3h @ 50Hz (36) 1.3 (175) 10.5 (236) 14.2
Guaranteed Ultimate Pressure* Torr
2 x 10
-3
3 x 10
-4
4 x 10
-4
Water Vapor Tolerance (capacity), Torr 6 15 15 Water Vapor Tolerance (capacity), g/hr 30 180 180
Sound Level dBA 56 54 55
Motor/Pump Speed RPM @ 60Hz 3450 1725 1725 RPM @ 50Hz 2875 1425 1425
Motor Voltage 50/60Hz Single Phase Current 115V (230V) @ 60Hz 3.8A (1.9A) 6.8A (3.4A) 10.0A (5.0A) Current 230V @ 50Hz 1.2A 3.4A 5.0A
Motor Horsepower 1/4 1/2 3/4
Oil Capacity , quarts (liters) 0.42 (0.4) 1.3 (1.2) 1.2 (1.1)
Unibarb for Unibarb for Unibarb for
3/16" and 7/16" 9/16" and 13/16" 9/16" and 13/16"
Intake Connection I.D. Hose, I.D. Hose, I.D. Hose,
Threaded for Threaded for Threaded for
3/4"-20 1-1/8"-20 1-1/8"-20
Tubing needed, I.D. in inches 3/16 or 7/16 9/16 or 13/16 9/16 or 13/16 in mm 5 or 11 14 or 20 14 or 20
Exhaust Connection 3/4"-20 Thread 1"-20 Thread 1"-20 Thread
Gas Ballast Connection 10-32 Thread 10-32 Thread 10-32 Thread
Pump Weight lbs. 24.5 58.5 63 Kg. 11.1 26.6 31.3
Overall Dimensions Length (inch / cm) 14.5 / 36.8 20.8 / 52.8 22.2 / 56.4 Width (inch / cm) 5.1/ 13 7.1 / 17.9 7.1 / 17.9 Height (inch / cm) 8.4 / 21.3 11.0 / 27.9 11.0 / 27.9
Shipping Weight lbs. 26 71 77 Kg. 11.8 32.2 34.6
Shipping Carton Dimensions Length (inch / cm) 21 / 53.3 29 / 73.7 29 / 73.7 Width (inch / cm) 6.5 / 16.5 10 / 25.4 10 / 25.4 Height (inch / cm) 11.2 / 28.6 14 / 35.6 14 / 35.6
Exhaust Filter (Optional) Cat. No. 1416B / 1417 1417P-10 / 1416C 1417P-10 / 1416C
Oil Type Cat. No. 8995P / 8995G 8995P / 8995G 8995P / 8995G
3.01 Specication Chart
* Partial measurement based upon the American Vacuum Society Test Procedure No. AVS 5.1-1963 using a trapped McLeod Gauge.
12
SPECIFICATION 8907 8912 8917
Free Air Displacement CFM (L/min) @ 60Hz 2.6 (70) 3.8 (108) 6.1 (173) (L/min) m3h @ 50Hz (56) 3.68 (86) 5.37 (138) 8.63
Normal Pumping Speed CFM (L/min) @ 60Hz 2.3 (64) 3.4 (96) 5.3 (150) (L/min) m3h @ 50Hz (53) 3.2 (80) 4.78 (125) 7.51
Guaranteed Ultimate Pressure* Torr
1 x 10
-4
1 x 10
-4
1 x 10
-4
Water Vapor Tolerance (capacity), Torr 19 12 12 Water Vapor Tolerance (capacity), g/hr - - -
Sound Level dBA 50 50 50
Motor/Pump Speed RPM @ 60Hz 1725 1725 1725 RPM @ 50Hz 1425 1425 1425
Motor Voltage 50/60Hz Single Phase Current 115V (230V) @ 60Hz 4.6A (2.3A) 4.6A (2.3A) 4.6A (2.3A) Current 230V @ 50Hz 2.1A 2.1A 2.1A
Motor Horsepower 1/2 1/2 1/2
Oil Capacity , quarts (liters) 1.0 (0.95) 0.9 (0.86) 0.8 (0.76)
Unibarb for Unibarb for Unibarb for
7/16" and 13/16" 7/16" and 13/16" 7/16" and 13/16"
Intake Connection I.D. Hose, I.D. Hose, I.D. Hose,
Threaded for Threaded for Threaded for
1-1/8"-20 1-1/8"-20 1-1/8"-20
Tubing needed, I.D. in inches 7/16 or 13/16 7/16 or 13/16 7/16 or 13/16 in mm 11 or 20 11 or 20 11 or 20
Exhaust Connection 1"-20 Thread 1"-20 Thread 1"-20 Thread
Gas Ballast Connection 10-32 Thread 10-32 Thread 10-32 Thread
Pump Weight lbs. 40 41 48 Kg. 18 18 22
Overall Dimensions Length (inch / cm) 18.8 / 47.7 18.8 / 47.7 18.8 / 47.7 Width (inch / cm) 6.5 / 16.6 6.5 / 16.6 6.5 / 16.6 Height (inch / cm) 9.6 / 24.4 9.6 / 24.4 9.6 / 24.4
Shipping Weight lbs. 46 46 53 Kg. 21 21 24
Shipping Carton Dimensions Length (inch / cm) 28.9 / 73.5 28.9 / 73.5 28.9 / 73.5 Width (inch / cm) 10.8 / 27.5 10.8 / 27.5 10.8 / 27.5 Height (inch / cm) 13.7 / 35.0 13.7 / 35.0 13.7 / 35.0
Exhaust Filter (Optional) Cat. No. 1416C / 1417P-7 1416C / 1417P-7 1416C / 1417P-7
Oil Type Cat. No. 8995P / 8995G 8995P / 8995G 8995P / 8995G
* Partial measurement based upon the American Vacuum Society Test Procedure No. AVS 5.1-1963 using a trapped McLeod Gauge.
13
Section 4: MOTOR SPECIFICATIONS, POWER / FEATURES
Cat. No.
V
oltage Freq. Ph. H.P. Factory Wired fo
r
Special Feature
A
pproval
8905A 115 / 230 60 1 1/4 115V 60Hz Standard Model CSA
8905C-01 115 / 230 60 1 1/4 115V 60Hz 230V US Cord Plug CSA
8905C-02 230 50 1 1/4 230V 50Hz European "Schuko" Cord Plug CE
8905C-10 115 / 230 60 1 1/4 230V 60Hz European "Schuko" Cord Plug CSA
8907A 115 / 230 60 1 1/2 115V 60Hz Standard Model CSA
8907C-02 230 50 1 1/2 230V 50Hz European "Schuko" Cord Plug CE
8907C-05 100 50/60 1 1/2 100V For Japan with US Cord Plug -
8912A 115 / 230 60 1 1/2 115V 60Hz Standard Model CSA
8912C-02 230 50 1 1/2 230V 50Hz European "Schuko" Cord Plug CE
8912C-05 100 50/60 1 1/2 100V For Japan with US Cord Plug -
8917A 115 / 230 60 1 1/2 115V 60Hz Standard Model CSA
8917C-02 230 50 1 1/2 230V 50Hz European "Schuko" Cord Plug CE
8917C-05 100 50/60 1 1/2 100V For Japan with US Cord Plug -
8917W 115 60 1 1/2 115V 60Hz To be wired by qualified electrician -
8920A 115 / 208-230 50/60 1 3/4 115V 60Hz Standard Model CSA
8920C-01 115 / 208-230 50/60 1 3/4 230V 60Hz 230V US Cord Plug CSA
8920C-02 115 / 208-230 50/60 1 3/4 230V 50Hz European "Schuko" Cord Plug CE
8925A 115 / 208-230 50/60 1 3/4 115V 60Hz Standard Model CS
A
8925C-01 115 / 208-230 50/60 1 3/4 230V 60Hz 230V US Cord Plug CSA
8925C-02 115 / 208-230 50/60 1 3/4 230V 50Hz European "Schuko" Cord Plug CE
8925W 115 60 1 1/2 115V 60Hz To be wired by qualified electrician -
4.01 Motor Specication Chart
14
Loading...
+ 32 hidden pages