Weishaupt W-FM 100, W-FM 200 Installation And Operating Instruction

Page 1
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
83054802 1/2018-07
Page 2
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
1 User instructions.............................................................................................................. 8
1.1  Target group.................................................................................................................. 8
1.2  Symbols.......................................................................................................................... 8
1.3  Guarantee and Liability............................................................................................... 9
2 Safety .................................................................................................................................. 10
2.1  When gas can be smelled.......................................................................................10
2.2  Safety measures.........................................................................................................10
2.3  Alterations to the construction of the equipment ...............................................11
2.4  Noise emission ...........................................................................................................11
2.5  Disposal .......................................................................................................................11
3 Product description ..................................................................................................... 12
3.1  Variations .....................................................................................................................12
3.2  Function........................................................................................................................12
3.2.7.1  Gas direct ignition....................................................................................... 15
3.2.7.2  Gas with ignition pilot valve ......................................................................16
3.2.7.3  Light oil direct ignition................................................................................ 18
3.2.7.4  Heavy oil direct ignition.............................................................................. 20
3.2.7.5  Heavy oil with gas pilot ignition................................................................ 22
3.3  Inputs ............................................................................................................................24
83054802 1/2018-07 La
2-228
Page 3
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3.4  Outputs ........................................................................................................................36
3.5  Technical data.............................................................................................................42
4 Installation........................................................................................................................ 46
4.1  Installing O2 sensor ..................................................................................................46
5 Installation........................................................................................................................ 48
5.1  Electrical connection.................................................................................................48
6 Operation .......................................................................................................................... 53
6.1  Operating interface....................................................................................................53
6.2  Displaying and adjusting parameters ....................................................................55
6.3  Menu structure............................................................................................................57
6.4  Operation and system information.........................................................................66
6.5  Setting the display.....................................................................................................71
83054802 1/2018-07 La
3-228
Page 4
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6.6  Interfaces .....................................................................................................................73
6.7  Manual / Automatic / Off..........................................................................................76
6.8  Burner Control............................................................................................................77
6.9  Electronic compound................................................................................................84
6.10  O2 controller ............................................................................................................97
83054802 1/2018-07 La
4-228
Page 5
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6.11  CO monitor and CO controller ......................................................................... 116
6.12  Load controller ...................................................................................................... 119
6.12.12.1  Multi-stage switch differentials ........................................................ 131
6.12.12.2  Multi-stage switch threshold ............................................................ 132
6.12.12.3  Low impact start.................................................................................. 132
6.13  Actuators................................................................................................................ 138
6.14  VSD / Frequency converter................................................................................ 140
6.15  Flue Gas Recirculation........................................................................................ 142
6.15.1.1  Fan on burner.......................................................................................... 142
6.15.1.2  Separate fan............................................................................................ 144
83054802 1/2018-07 La
5-228
Page 6
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6.16  Data backup ..........................................................................................................151
6.17  TÜV Test................................................................................................................. 153
7 Commissioning............................................................................................................154
7.1  Prerequisite .............................................................................................................. 154
7.2  Adjusting the burner............................................................................................... 155
7.2.1.1  Carry out speed standardisation .......................................................... 157
7.2.1.2  O2 module presetting ............................................................................. 158
7.2.1.3  Deactivate flue gas recirculation........................................................... 159
7.3  Load controller......................................................................................................... 176
7.3.2.1  Modulating load control .......................................................................... 178
7.3.2.2  Modulating load control .......................................................................... 179
7.3.2.3  Boiler cold start function ........................................................................ 180
7.4  O2 controller............................................................................................................ 182
7.5  CO controller ........................................................................................................... 186
7.6  Flue gas recirculation (temperature compensated) ........................................ 188
7.7  Set pressure switches ........................................................................................... 190
7.8  Concluding work..................................................................................................... 190
7.9  Check combustion.................................................................................................. 191
7.10  Calculate gas throughput................................................................................... 192
7.11  Ratings apportionment........................................................................................ 193
83054802 1/2018-07 La
8 Servicing..........................................................................................................................194
8.1  Notes on servicing.................................................................................................. 194
8.2  Service plan.............................................................................................................. 195
9 Troubleshooting ..........................................................................................................196
9.1  Procedures for fault conditions............................................................................ 196
9.2  Fault............................................................................................................................ 198
9.3  Lockout...................................................................................................................... 199
9.4  Rectifying faults....................................................................................................... 200
6-228
Page 7
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
10 Technical documentation.......................................................................................218
10.1  Frequency converter............................................................................................ 218
11 Key word index ............................................................................................................222
83054802 1/2018-07 La
7-228
Page 8

1 User instructions

Translation of original
operating instructions
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
1 User instructions
This manual forms part of the equipment and must be kept on site. Carefully read the manual prior to working on the unit.

1.1 Target group

The manual is intended for the operator and qualified personnel. They should be observed by all personnel working with the unit.
Work on the unit must only be carried out by personnel who have the relevant train­ing and instruction.
Persons with limited physical, sensory or mental capabilities may only work on the unit if they are supervised or have been trained by an authorised person.
Children must not play with the unit.

1.2 Symbols

Immediate danger with high risk. Non observance can lead to serious injury or death.
DANGER
Danger with medium risk. Non observance can lead to environmental damage,
WARNING
CAUTION
Range of values
serious injury or death.
Danger with low risk. Non observance can cause damage to the equip­ment and injury to personnel.
Important information
Requires direct action Result after an action Itemisation
83054802 1/2018-07 La
8-228
Page 9
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
1 User instructions

1.3 Guarantee and Liability

Guarantee and liability claims for personal and equipment damage are excluded, if they can be attributed to one or more of the following causes:
non approved application, non-observance of the manual, operation with faulty safety equipment, continual operation despite a fault, improper installation, commissioning, operation and service, repairs, which have been carried out incorrectly, the use of non original Weishaupt parts, force majeure, unauthorised modifications made to the unit, the installation of additional components, which have not been tested with the unit, the installation of combustion chamber inserts, which impede full flame forma­tion, unsuitable fuels, defects in the inlet lines.
83054802 1/2018-07 La
9-228
Page 10

2 Safety

Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
2 Safety
The combustion manager W-FM 100/200 is suitable for use with:
oil burners gas burner dual fuel and triple fuel burners, dual gas burners.
Improper use could:
endanger the health and safety of the user or third parties, cause damage to the unit or other material assets.

2.1 When gas can be smelled

Avoid open flames and spark generation, for example:
do not operate light switches, do not operate electronic equipment, do not use mobile telephones.
Open doors and windows. Close gas isolating valve. Warn the inhabitants, do not ring door bells. Leave the building. Inform the heating contractor or gas supplier from outside of the building.

2.2 Safety measures

Safety relevant fault conditions must be eliminated immediately. Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution. The design lifespan of the components is listed in the service plan [ch.8.2].

2.2.1 Normal operation

All labels on the unit must be kept in a legible condition. Stipulated settings, service and inspection work should be carried out at regular intervals. Only operate the unit with its cover closed. Do not touch moving parts during operation. Do not touch the oil carrying parts of medium and heavy oil burners during oper­ation.

2.2.2 Electrical connection

For work carried out on live components:
Observe the accident prevention instructions DGUVRegulation3 and adhere to local directives, tools in accordance with EN 60900 should be used.
83054802 1/2018-07 La
10-228
Page 11
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
2 Safety

2.2.3 Gas supply

Only the gas supply company or an approved agent may carry out installation, al­teration and maintenance work on gas appliances in buildings and properties. Pipework must be subject to a combined load and valve proving test and/or us­ability testing relative to the pressure range intended, e. g. DVGW-TRGI, work­sheet G 600. Inform the gas supply company about the type and size of plant prior to installa­tion. Local regulations and guidelines must be observed during installation, e. g. DVGW-TRGI, worksheet G 600; TRF Band 1 and Band 2. The gas supply pipework should be suitable for the type and quality of gas and should be designed in such a way that it is not possible for liquids to form, e. g. condensate. Observe vaporisation pressure and vaporisation temperature of li­quid petroleum gas. Use only tested and approved sealing materials, whilst observing all process in­formation. Re-commission the appliance when changing to a different type of gas. Chan­ging from LPG to Natural Gas and visa versa requires a conversion. Carry out soundness test after each service and fault rectification.

2.3 Alterations to the construction of the equipment

All conversions require written approval from Max Weishaupt GmbH.
No additional components may be fitted, which have not been tested for use with the equipment. Do not use combustion chamber inserts, which hinder flame burnout. Use only original Weishaupt replacement parts.

2.4 Noise emission

The noise emissions are determined by the acoustic behaviour of all components fitted to the combustion system.
Prolonged exposure to high noise levels can lead to loss of hearing. Provide oper­ating personnel with protective equipment.
Noise emissions can further be reduced with a sound attenuator.

2.5 Disposal

Dispose of all materials and components in a safe and environmentally friendly way at an authorised location. Observe local regulations.
83054802 1/2018-07 La
11-228
Page 12

3 Product description

Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3 Product description

3.1 Variations

Type Version Functions
W-FM 100 LMV51.0… Burner Control
Low gas programme Valve proving
LMV51.1… as type LMV51.0…
Load controller
W-FM 200 LMV52.2… as type LMV51.1…
Variable speed drive O2 trim
LMV52.4… as type LMV52.2…
FGR with temperature compensation CO monitor and CO controller function

3.2 Function

3.2.1 Burner Control

A burner control for oil, gas and dual fuel burners is integrated in the combustion manager.
It controls the sequence of operation, monitors the flame and communicates with all components.

3.2.2 Low gas programme

The low gas pressure switch monitors the gas connection pressure from phase21. If the gas pressure set at the low gas pressure switch is not achieved, the combus­tion manager initiates a safety shutdown and starts the low gas programme. In the low gas programme, the combustion manager initiates a restart after the low gas waiting time (Parameter: DelayLackGas). This low gas waiting time doubles after every unsuccessful start attempt. If the start attempts exceed the repetition limit value (Parameter: StartRelease) the combustion manager goes to lockout. The repetition counter and the low gas waiting time are automatically reset when the burner starts.
83054802 1/2018-07 La
12-228
Page 13
Installation and operating instruction
V1
V2PP
3 s 10 s 10 s3 s
80 81 82 83
A
V1
V2
P
P
V1
V2
P
P
B
C
1
2
4
1
2
4
1
2
4
1 2 3 4 5
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.2.3 Valve proving

The valve proving gas pressure switch checks if the valves are tight. It signals the combustion manager if the pressure increases or decreases to an impermissible level during valve proving.
Valve proving is carried out automatically by the combustion manager:
after every controlled shutdown, prior to burner start following lockout or power outage.
1. Test phase (function sequence for valve proving valve1): Valve1 remains closed, valve2 opens, the gas escapes and the pressure between valve1 and valve2 reduces, valve 2 closes again, both valves remain closed for 10 seconds.
If the pressure increases to above the value set during these 10 seconds, valve1 is leaking. The combustion manager initiates a controlled shutdown.
2. Test phase (function sequence for valve proving valve2): Valve 1 opens, valve 2 remains closed, pressure between valve1 and valve2 increases, valve 1 closes again, both valves remain closed for 10 seconds.
If the pressure decreases to below the value set during these 10 seconds, valve2 is leaking. The combustion manager initiates a controlled shutdown.
83054802 1/2018-07 La
1 Valve 1 2 Valve 2 3 Pressure between valve 1 and valve 2 4 Valve proving gas pressure switch 5 Operating phases
A Direct ignition B Ignition gas tube C Gas ignition device
13-228
Page 14
3 Product description
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.2.4 Load controller

The W-FM 200 is equipped with an internal PID load controller as standard, with the W-FM 100 the internal load controller is optional.
The load controller is suitable for multi-stage and modulating burners. In modulating operation, control variables calming reduces the drive impulses and protects the actuators. It is possible to choose between two setpoints using an external contact. The boiler cold start function reduces the thermal load of the heat exchanger during burner start.

3.2.5 Variable speed drive

Only the W-FM 200 is equipped with a frequency converter module for variable speed control.
Via an analogue output (0/4-20 mA), the W-FM 200 control the frequency con­verter of the fan motor and matches the speed to the burner capacity. This reduces electrical consumption. The speed and the rotation direction are monitored by an inductive proximity switch and an asymmetrical transmitter disc.

3.2.6 O2 trim / monitoring

Only the W-FM 200 is equipped with an O2 trim function. An additional O2 module (PLL52…) is required for O2 trim.
A sensor measures the O2 content in the flue gas. During operation, the W-FM 200 compares the O2 content with the setpoints determined during commissioning. If deviations occur, the W-FM 200 activates the air regulating devices and corrects the O2 content. This increases the boiler efficiency.
83054802 1/2018-07 La
14-228
Page 15
Installation and operating instruction
79 8382818070 72 74 76 786260544438363432302422212012100100 4240
X4-01:1 X3-04:1
X10-...
(2
X3-02:1 X4-01:3
X7-03:2 X9-03:4 X9-03:3 X9-03:2
X3-01:1 X4-02:3
79 8382818070 72 74 76 786260544438363432302422212012100100 4240
79 8382818070 72 74 76 786260544438363432302422212012100100 4240
X4-03:3
(4
X9-01:1
X9-01:4 X9-01:3
(1
(1
(3
(3
(3
1
3
2
Lockout phase
Safety phase
Home run
Standby
Start-up
Start release
Fan ON
Pre-purge position
Pre-purge
Ignition position
Pre-ignition
Fuel release
Ignition OFF
Flame Signal
Partial load position
Operating setting 1
Operating setting 2
Post burn time
Post-purge position
Post-purge
Direct start
Drain valve train
Test without pressure
Fill valve train
System pressure test
Valve
proving
Inputs
Fuel selection
Safety circuit
Heat demand
Flame Signal
Air pressure switch
Fan contactor contact
Start release Gas
Low gas pressure switch
High gas pressure switch
VP gas pressure switch
Outputs
Burner motor / Fan
Ignition
Pressure switch release
Start signal
Safety valve Fuel valve 1 Fuel valve 2
Actuators
Full load
Pre-purge position
Post-purge position
Partial load
Ignition position
Standby position
Combustion manager W-FM 100 und W-FM 200

3.2.7 Program sequence

3.2.7.1 Gas direct ignition
3 Product description
(1
Signal only required to jump to Phase 79 (direct start)
(2
with QRI / QRA7x: Input X10-02:6 with ionisation electrode: Input X10-03:1
(3
Only with continuous running fan
(4
Signal is dependent on parameter: Start/PS valve (start signal or pressure switch release)
83054802 1/2018-07 La
Signal on input / output activated No signal on input Input without influence Signal optional or depending on parameter settings
1 Fuel actuator 2 Actuators air, Aux1, Aux2 / frequency converter 3 Actuator flue gas recirculation
15-228
Page 16
3 Product description
79 8382818070 72 74 76 786260544438363432302422212012100100 4240 50 52
X4-01:1 X3-04:1
X10-...
(2
X3-02:1 X4-01:3
X7-03:2 X9-03:4 X9-03:3 X9-03:2
X3-01:1 X4-02:3
79 8382818070 72 74 76 786260544438363432302422212012100100 4240 50 52
79 8382818070 72 74 76 786260544438363432302422212012100100 4240 50 52
X4-03:3
(4
X9-01:1
X9-01:2 X9-01:4 X9-01:3
(1
(1
(3
(3
(3
(5
1
3
2
Lockout phase
Safety phase
Home run
Standby
Start-up
Start release
Fan ON
Pre-purge position
Pre-purge
Ignition position
Pre-ignition
Fuel release
Ignition OFF
Flame Signal
Partial load position
Operating setting 1
Operating setting 2
Post burn time
Post-purge position
Post-purge
Direct start
Drain valve train
Test without pressure
Fill valve train
System pressure test
Valve
proving
Inputs
Fuel selection
Safety circuit
Heat demand
Flame Signal
Air pressure switch
Fan contactor contact
Start release Gas
Low gas pressure switch
High gas pressure switch
VP gas pressure switch
Outputs
Burner motor / Fan
Ignition
Pressure switch release
Start signal
Safety valve
Ignition pilot valve
Fuel valve 1
Actuators
Full load
Pre-purge position
Post-purge position
Partial load
Ignition position
Standby position
Flame stabilisation
Ignition pilot valve OFF
Fuel valve 2
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3.2.7.2 Gas with ignition pilot valve
(1
Signal only required to jump to Phase 79 (direct start)
(2
with QRI / QRA7x: Input X10-02:6 with ionisation electrode: Input X10-03:1
(3
Only with continuous running fan
(4
Signal is dependent on parameter: Start/PS valve (start signal or pressure switch release)
(5
If a pilot valve is fitted between fuel valve 1 and 2: Signal from Phase 40 If a gas ignition device is fitted in front of fuel valve 1: Signal from Phase 50
83054802 1/2018-07 La
16-228
Page 17
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Signal on input / output activated No signal on input Input without influence Signal optional or depending on parameter settings
1 Fuel actuator 2 Actuators air, Aux1, Aux2 / frequency converter 3 Actuator flue gas recirculation
3 Product description
83054802 1/2018-07 La
17-228
Page 18
3 Product description
7970 72 74 76 786260544438363432302422212012100100 4240
X4-01:2 X3-04:1
X10-...
(2
X3-02:1 X4-01:3
X5-01:2 X5-02:2 X6-01:1
X3-01:1 X6-02:3 X4-02:3
7970 72 74 76 786260544438363432302422212012100100 4240
7970 72 74 76 786260544438363432302422212012100100 4240
X4-03:3
(6
X6-03:3
X8-02/03
X7-02:3
X7-01:3
(1
(1
(3
(3
(3
(4
(5
(5
(4
(5
(5
1
3
2
Lockout phase
Safety phase
Home run
Standby
Start-up
Start release
Fan ON
Pre-purge position
Pre-purge
Ignition position
Pre-ignition
Fuel release
Ignition OFF
Flame Signal
Partial load position
Operating setting 1
Operating setting 2
Post burn time
Post-purge position
Post-purge
Direct start
Inputs
Fuel selection
Safety circuit
Heat demand
Flame Signal
Air pressure switch
Fan contactor contact
Minimum oil pressure switch
Max. oil pressure switch
Start release Oil
Outputs
Burner motor / Fan
Ignition
Pressure switch release
Start signal
Anti syphon valve
Fuel valve 1 Fuel valve 2
Actuators
Full load
Pre-purge position
Post-purge position
Partial load
Ignition position
Standby position
Fuel valve 3
Magnetic coupling / Oil pump
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3.2.7.3 Light oil direct ignition
(1
Signal only required to jump to Phase 79 (direct start)
(2
with QRI / QRA7x: Input X10-02:6 with QRA2: Input X10-03:1 with QRB: Input X10-02:1
(3
Only with continuous running fan
(4
Signal depends on parameter: OnIgnPointOilIgnition (long or short pre-ignition)
(5
Signal depends on parameter: OilPumpCoupling (direct coupling)
(6
Signal depends on parameter: Start/PS valve
83054802 1/2018-07 La
18-228
Page 19
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Signal on input / output activated No signal on input Input without influence Signal optional or depending on parameter settings
1 Fuel actuator 2 Actuators air, Aux1, Aux2 / frequency converter 3 Actuator flue gas recirculation
3 Product description
83054802 1/2018-07 La
19-228
Page 20
3 Product description
(5
(5
7970 72 74 76 786260544438363432302422212012100100 4240
X4-01:2 X3-04:1
X10-...
(2
X3-02:1 X4-01:3
X5-01:2 X5-02:2
X3-01:1 X6-02:3 X4-02:3
7970 72 74 76 786260544438363432302422212012100100 4240
7970 72 74 76 786260544438363432302422212012100100 4240
X4-03:3
(6
X6-03:3
X8-02/03
X7-02:3
X7-01:3
(1
(1
(3
(3
(3
(4
(4
X6-01:1 X6-01:3
(5
(5
1
3
2
Lockout phase
Safety phase
Home run
Standby
Start-up
Start release
Fan ON
Pre-purge position
Pre-purge
Ignition position
Pre-ignition
Fuel release
Ignition OFF
Flame Signal
Partial load position
Operating setting 1
Operating setting 2
Post burn time
Post-purge position
Post-purge
Direct start
Inputs
Fuel selection
Safety circuit
Heat demand
Flame Signal
Air pressure switch
Fan contactor contact
Minimum oil pressure switch
Max. oil pressure switch
Start release Oil
Outputs
Burner motor / Fan
Ignition
Pressure switch release
Start signal
Anti syphon valve
Fuel valve 1 Fuel valve 2
Actuators
Full load
Pre-purge position
Post-purge position
Partial load
Ignition position
Standby position
Fuel valve 3
Magnetic coupling / Oil pump
Heavy oil immediate start
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3.2.7.4 Heavy oil direct ignition
(1
Signal only required to jump to Phase 79 (direct start)
(2
with QRI / QRA7x: Input X10-02:6 with QRA2: Input X10-03:1 with QRB: Input X10-02:1
(3
Only with continuous running fan
(4
Signal depends on parameter: OnIgnPointOilIgnition (long or short pre-ignition)
(5
Signal depends on parameter: OilPumpCoupling (direct coupling)
(6
Signal depends on parameter: Start/PS valve
83054802 1/2018-07 La
20-228
Page 21
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Signal on input / output activated No signal on input Input without influence Signal optional or depending on parameter settings
1 Fuel actuator 2 Actuators air, Aux1, Aux2 / frequency converter 3 Actuator flue gas recirculation
3 Product description
83054802 1/2018-07 La
21-228
Page 22
3 Product description
(5
(5
7970 72 74 76 786260544438363432302422212012100100 4240
X4-01:2 X3-04:1
X10-...
(2
X3-02:1 X4-01:3
X5-01:2 X5-02:2
X3-01:1 X6-02:3 X4-02:3
7970 72 74 76 786260544438363432302422212012100100 4240
7970 72 74 76 78626054
52
52
52
50
50
504438363432302422212012100100 4240
X4-03:3
(6
X6-03:3
X8-02/03
X7-02:3
X7-01:3
(1
(1
(3
(3
(3
(4
(4
X6-01:1 X6-01:3
X9-03:4 X9-03:3
X7-03:2
(5
(5
X9-01:1
X9-01:2
1
3
2
Lockout phase
Safety phase
Home run
Standby
Start-up
Start release
Fan ON
Pre-purge position
Pre-purge
Ignition position
Pre-ignition
Fuel release
Ignition OFF
Flame Signal
Partial load position
Operating setting 1
Operating setting 2
Post burn time
Post-purge position
Post-purge
Direct start
Inputs
Fuel selection
Safety circuit
Heat demand
Flame Signal
Air pressure switch
Fan contactor contact
Minimum oil pressure switch
Max. oil pressure switch
Start release Oil
Outputs
Burner motor / Fan
Ignition
Pressure switch release
Start signal
Anti siphon valve Oil
Fuel valve 1 Oil Fuel valve 2 Oil
Actuators
Full load
Pre-purge position
Post-purge position
Partial load
Ignition position
Standby position
Fuel valve 3 Oil
Magnetic coupling / Oil pump
Heavy oil immediate start
Flame stabilisation
Ignition pilot valve OFF
Low gas pressure switch
Start release Gas
High gas pressure switch
Safety valve Gas
Ignition pilot valve Gas
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3.2.7.5 Heavy oil with gas pilot ignition
(1
Signal only required to jump to Phase 79 (direct start)
(2
(3
(4
(5
(6
with QRI / QRA7x: Input X10-02:6 with ionisation electrode on gas ignition device: Input X10-03:1
Only with continuous running fan Signal depends on parameter: OnIgnPointOilIgnition (long or short pre-ignition) Signal depends on parameter: OilPumpCoupling (direct coupling) Signal depends on parameter: Start/PS valve
83054802 1/2018-07 La
22-228
Page 23
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Signal on input / output activated No signal on input Input without influence Signal optional or depending on parameter settings
1 Fuel actuator 2 Actuators air, Aux1, Aux2 / frequency converter 3 Actuator flue gas recirculation
3 Product description
83054802 1/2018-07 La
23-228
Page 24
3 Product description
2 3 4 5
X3-04
PE
N
L
L
PE
N
L
SAFETY LOOP
LINE
VOLTAGE
1
2 3 4 5
X3-04
PE
N
L
L
SAFETY LOOP
LINE
VOLTAGE
1
1 2
X3-03
L
FLANGE
P
2 3 4 5
X3-04
PE
N
L
L
PE
N
L
SAFETY LOOP
LINE
VOLTAGE
1
1 2
X3-01
L
L MOTOR
ALARM
2 3 4
X4-01
RESET
OIL
GAS
1
(2(1
1 2
X3-02
P
L
P
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3 Inputs

3.3.1 Voltage supply

The voltage supply is connected to inputsX3-04:3-5.

3.3.2 Safety circuit

In the diagnostic code, the inputsX3-03:1/2 and X3-04:1/2 are combined as safety circuit. If one of the inputs is open the W-FM carries out at least one safety shutdown. If the repetition value is exceeded an open input leads to lockout.
The repetition value can be set in parameter RepetitCounter under SafetyLoop, see [ch.6.8.12].
At inputX3-04:1/2 all external components of the safety circuit are switched in se­quence, these include:
Emergency-Off switch Safety time limiter (STL) Low water safety interlock, etc.
The burner flange limit switch is connected to inputX3-03:1/2.

3.3.3 Reset

A reset button can be connected to inputX4-01:4. Pressing this button in lockout will reset the combustion manager.
With lockout function
(1
If the push button is also required for manual lockout, it must be connected to mains inputX3-04:5(L). If the combustion manager is in an operating phase press­ing the button will initiate a manual lockout.
Without lockout function
(2
If the push button is not required to carry out manual lockout it must be connected to alarm outputX3-01:2.

3.3.4 Air pressure switch

Depending on the burner configuration, the input is activated at the factory in the OEM level.
The input is activated for:
gas burner dual fuel burners, oil burners with separately driven pump.
In these cases, the closing contact of the air pressure switch is connected to in­putX3-02:1. The fan will only start, if no signal is present at the input during start release. If the signal is missing once the fan has started, the combustion manager
83054802 1/2018-07 La
initiates a lockout.
24-228
Page 25
Installation and operating instruction
2
3
4
X4-01
RESET
OIL
GAS
1
1
2
X3-02
P
L
P
1
2
X3-01
L
L MOTOR
ALARM
(1
2 3 4
X4-01
RESET
OIL
GAS
1
2 3 4
X5-03
ON/OFF
1
3
2
L
0 1 2
2 3
X5-01
PE
min
1
P
L
P
2 3
X5-02
PE
max
1
P
L
P
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.3.5 Fan contactor contact

The auxiliary contact (closer) of the fan contactor is connected to inputX4-01:3. The fan will only start, if no signal is present at the input during start release. If the signal is missing once the fan has started, the combustion manager initiates a lock­out.
(1
Only with frequency converter: For fans with frequency converter, the signal is generated via a bridge from out­putX3-01:1 (burner motor / fan).

3.3.6 Fuel selection

The fuel selection switch is connected to inputX4-01:1/2. The fuel selection switch has priority over fuel selection via display and operating unit(ABE) or build­ing management system (BMS). Fuel selection via ABE or BMS is only possible if no signal is present at input X4-01:1/2. There is no priority between ABE and BMS, the last fuel selection is valid and is retained after power failure.

3.3.7 Minimum oil pressure switch

The closing contact of the minimum oil pressure switch is connected to in­putX5-01. On burners without minimum oil pressure switch the input is deactiv­ated.
In oil operation the combustion manager expects a signal at inputX5-01:2 from Phase 38, in Phase44 with heavy oil with gas ignition device. If the pressure falls below the value set, the pressure switch contact opens and the combustion man­ager initiates a lockout. In Phase38 (in Phase44 with heavy oil with gas ignition device ) lockout occurs after a waiting time of 3seconds, in the following phases lockout is immediate.
To avoid a lockout caused by pressure fluctuations during fuel release, the input re­acts time delayed in Phase40 and42. The time delay can be adjusted in parameter PressReacTime, see [ch.6.8.1].

3.3.8 Max. oil pressure switch

The opening contact of the max. oil pressure switch is connected to inputX5-02. On burners without maximum oil pressure switch the input is deactivated.
In oil operation the combustion manager expects a signal at inputX5-02:2 from Phase 22. If the value set at the pressure switch is exceeded, the pressure switch contact opens and the combustion manager initiates a lockout. In Phase21 (start release) lockout occurs after a waiting time of 120seconds, in the following phases lockout is immediate.
To avoid a lockout caused by pressure fluctuations during fuel release, the input re­acts time delayed in Phase40 and42. The time delay can be adjusted in parameter PressReacTime, see [ch.6.8.1].
83054802 1/2018-07 La
25-228
Page 26
3 Product description
2 3
X6-01
4
1
L
START
L
2 3
X6-01
4
1
L
START
L
2 3
X7-03
1
PE
L
START CPI
L
2 3
X9-03
max
min
4
1
P
P
P
P
LT (CPI)
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3.9 Start release Oil

The start conditions for the oil operation are interrogated via inputX6-01:1, e.g.:
oil shut off combination limit switch, oil temperature release contact (for heavy oil), cooling air fan contact (WK burners with hot air, version ZMH).
For burners without start conditions, a bridge is connected between terminals1 and2.
In oil operation the combustion manager expects a signal at inputX6-01:1from Phase 21. If the signal is missing after Phase21, the combustion manager initiates a shutdown.

3.3.10 Heavy oil immediate start

The input is only activates on heavy oil burners with return flow temperature sensor. The release contact of the return flow temperature sensor is connected to in­putX6-01:3.
In heavy oil operation, the combustion manager carries out a nozzle circulation for maximum 45seconds. If the signal is present at inputX6-01:3 before this time has elapsed, the nozzle circulation is shortened accordingly. If the signal is missing after this time has elapsed, the combustion manager initiates a home run with sub­sequent repetition.
Depending on the burner nozzle circulation is carried out in phase:
38 (with direct ignition), 44 (with gas ignition device).
If the signal fails after Phase44, the combustion manager initiates a safety shut­down.

3.3.11 Start release Gas

The input is activated in gas operation and in heavy oil operation with gas ignition device.
The combustion manager expects a signal at inputX7-03:2 from Phase21. If the signal is missing after Phase21, the combustion manager initiates a shutdown.

3.3.12 Valve proving gas pressure switch

The opening contact of the valve proving gas pressure switch is connected to in­putX9-04:2. InputX9-04:2 is only activated during valve proving [ch.3.2.3].
If the pressure set is not achieved in Phase81 (test without pressure), the contact closes. If the pressure set is exceeded in Phase83 (test with system pressure), the contact opens.
83054802 1/2018-07 La
26-228
Page 27
Installation and operating instruction
L
2 3
X9-03
max
min
4
1
P
P
P
P
LT (CPI)
L
2 3
X9-03
max
min
4
1
P
P
P
LT (CPI)
P
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.3.13 High gas pressure switch

The input is activated in gas operation and in heavy oil operation with gas ignition device. The opening contact of the high gas pressure switch is connected to in­putX9-03:3. On burners without high gas pressure switch the input is deactivated.
The combustion manager expects a signal at inputX9-03:3 from Phase40. If the value set at the pressure switch is exceeded, the pressure switch contact opens and the combustion manager initiates a lockout.
To avoid lockouts caused by pressure fluctuations when the valves open, the input reacts time delayed in Phase40, 42 and50. The time delay can be adjusted in parameter PressSigReactTime ,see [ch.6.8.1].

3.3.14 Low gas pressure switch

The input is activated in gas operation and in heavy oil operation with gas ignition device. The closing contact of the low gas pressure switch is connected in­putX9-03:4.
In gas operation, the combustion manager expects a signal at inputX9-03:4 from Phase21. If the pressure drops below the value set, the pressure switch contact opens and the combustion manager starts the low gas programme [ch.3.2.2].
To avoid lockouts caused by pressure fluctuations when the valves open, the input reacts time delayed in Phase40, 42 and50. The time delay can be adjusted in parameter PressSigReactTime ,see [ch.6.8.1].
83054802 1/2018-07 La
27-228
Page 28
3 Product description
QRB
POWER QRI
L
N
PE
QRI / FSV
2 3
X10-02
4 5 6
1
BN
BK
QRB
POWER QRI
L
N
PE
QRI / FSV
2 3
X10-02
4 5 6
1
QRI
+
BN
BU
BK
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3.15 Flame sensor

If the flame signal from Phase 44 does not correspond to the value required, the combustion manager initiates safety shutdown with restart. The number of safety shutdowns set in parameter LossOfFlame in sequence lead to lockout [ch.6.8.12]. Depending on parameter ReactionExtranL , a flame signal in Standby (Phase12) will lead to start prevention or lockout. A flame signal during pre-purge (Phases30 to36) or post-purge (Phase76 and78) leads to lockout after one repetition and repeated occurrence. The OperationalStat shows the current flame signal as a percentage value.
QRB…
The flame sensorQRB… (photo resistor) is connected to inputX10-02:1/4. The flame sensor QRB is not suitable for continuous operation.
If the combustion manager is installed in a control panel, the sensor cable must be routed separately (max100m).
Flame signal Sensor current Display
Minimum flame signal DC30μA approx. 35 % Maximum flame signal DC70μA approx. 100 % Extraneous light detection
from
DC5μA -
QRI
The flame sensor QRI (infrared) is connected to inputX10-02:2/4/6. The flame sensor QRI is suitable for continuous operation. The combustion man­ager tests the flame sensor in cycles in operating position (Phase60) by simulating a flame failure. The voltage at outputX10-02:2 is increased from14V to 21V for
0.5seconds. The signal voltage at the flame sensor therefore drops to 0V and the combustion manager receives the expected Off signal at inputX10-02:6.
If the combustion manager is installed in a control panel, the sensor cable must be routed separately (max100m).
Flame Signal Display
Min. signal voltage: DC 3.5 V (X10-02:6) approx. 50 %
28-228
83054802 1/2018-07 La
Page 29
Installation and operating instruction
QRB
POWER QRI
L
N
PE
QRI / FSV
2 3
X10-02
4 5 6
1
45213
PE
45613
PE
+
UV
M
QRA73
AGM23
X10-03
ION
1
Combustion manager W-FM 100 und W-FM 200
3 Product description
QRA73
The flame sensorQRA73 (UV cell) is connected to inputX10-02:2-6 using plugAGM23. The flame sensorQRA73 is suitable for continuous operation. The combustion manager tests the flame sensor in cycles in operating position (Phase60) by simu­lating a flame failure. The voltage at output X10-02:2 is increased 14 V to 21 V for
0.5 seconds. The signal voltage at the flame sensor therefore drops to 0 V and the combustion manager receives the expected Off signal at input X10-02:6.
If the combustion manager is installed in a control panel, the connection must be divided into 2 lines after theAGM23 plug and routed separately (max100m):
Supply line: Core 1, 2 and PE (L / N / PE), Signal line (screened): Core 3, 4 and 5 (POWER QRI / N / QRI).
Flame Signal Display
Min. signal voltage: DC 3.5 V (X10-02:6) approx. 50 %
Ionisation electrode
The ionisation electrode is connected to inputX10-03:1. If the combustion manager is installed in a control panel, the sensor cable must be
routed separately:
Max. length: 100 m, Line capacity: 100 pF/m.
Flame signal Sensor current Display
Minimum flame signal DC6μA approx. 50 % Maximum flame signal DC85μA approx. 100 %
83054802 1/2018-07 La
29-228
Page 30
3 Product description
2 3 4
X5-03
ON/OFF
1
3
2
L
P
P
2 3 4
X5-03
ON/OFF
1
3
2
L
2 3 4
X5-03
ON/OFF
1
3
2
L
P
P
P
P
P
2 3 4
X5-03
ON/OFF
1
3
2
L
P
P
2 3 4
X5-03
ON/OFF
1
3
2
L
P
P
2 3 4
X5-03
ON/OFF
1
3
2
L
P
P
2 3 4
X5-03
ON/OFF
1
3
2
L
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3.16 External load controller (X5-03)

For operation with load controller via contacts, parameter LC_OptgMode must be set to ExtLC X5-03 see [ch.6.12.2]. The contact for heat demand is connected to inputX5-03:1 (burner ON/OFF).
Modulating operation with load controller
If inputX5-03:2 (CLOSED) is activated, the burner capacity reduces. If inputX5-03:3 (OPEN) is activated, the burner capacity increases. If none of the two inputs is activated, the burner capacity remains unchanged.
Modulating operation with thermostat
If thermostats or pressure regulators are connected to inputsX5-03, the modulat­ing fuel can only be operated in sliding two stage operation.
At heat demand inputX5-03:2 (CLOSED) is activated and the burner drives to par­tial load. If the temperature drops below the value set, inputX5-03:3 (OPEN) is ac­tivated and the burner drives to full load.
Multi-stage operation (fuel oil only)
Two and three stage:
Input Operating mode
two stage three stage X5-03:1 Stage 1 Stage 1 X5-03:2 Stage 1 Stage 2 X5-03:3 Stage 2 Stage 3
Low impact start: At heat demand and with the bridge between terminal 1 and 2 the burner ignites in
stage 1 and then automatically drives to stage 2. If input X5-03:3 is also activated the burner drives to stage3. Alternatively, low impact start can be carried using a change-over contact.
Change-over release: A bridge connects terminals2 and3. At heat demand the burner drives to stage1.
If inputsX5-03:2/3 are then activated simultaneously the burner drives via stage2 to stage3.
83054802 1/2018-07 La
30-228
Page 31
Installation and operating instruction
2 3 4
X5-03
ON/OFF
1
3
2
L
2 3 4 5
X62
0-10V
4-20mA
0
FE
1
+-
0/2 ... 10 V
0/4 ... 20 mA
X50
interface
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.3.17 External load controller (X62)

For operation with external load controller on the analogue input, parameter LC_OptgMode must be set to Ext LC X62 see [ch.6.12.2]. The contact for heat demand is connected to inputX5-03:1 (burner ON/OFF). The analogue load signal is connected to terminalsX62:2/4(0/2-10V) or X62:3/4(0/4-20mA). In parameter Ext Inp X62 U/I the input must be matched to the analogue signal [ch.6.12.4].
Modulating operation
In modulating operation, parameter MinActuatorStep determines the minimum correcting element step [ch.6.12.9].
Signal on X62 Load W-FM
3 … 4 mA 20 % 20 mA 100 %
Multi-stage operation (fuel oil only)
In multi-stage operation a hysteresis of 1mA exists between the operating points, which eliminates unnecessary load changes.
Two stage:
Signal on X62 Load W-FM
3 … 5 … 12 mA Stage 1 13 … 15 … 20 mA Stage 2
Three stage:
Signal on X62 Load W-FM
3 … 5 … 7 mA Stage 1 8 … 10 … 12 mA Stage 2 13 … 15 … 20 mA Stage 3

3.3.18 External load controller (Bus)

For the operation with external load controller via Bus connection, parameter LC_OptgMode must be set to ExtLCBus ,see [ch.6.12.2]. The building management system specifies the load signal via the bus connection.
In modulating operation, parameter MinActuatorStep determines the minimum correcting element step [ch.6.12.9].
83054802 1/2018-07 La
31-228
Page 32
3 Product description
W1
2 3 4 5
X62
0-10V
4-20mA
0
FE
1
W2
2 3 4 5
X62
0-10V
4-20mA
0
FE
1
W1
0-10V
4-20mA
2 3 4 5
X62
0-10V
4-20mA
0
FE
1
X50
W1
interface
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3.19 Setpoint switch-over

When operating with internal load controller it is possible to switch between 2 set­points. To do this, a potential free contact is connected to terminalX62:1/2.
Operating mode IntLC
Two internal setpoints(W1/W2) are available in operating mode IntLC . The contact is used to switch between the setpoints.
Open: Setpoint W1 activated Closed: Setpoint W2 activated
Operating mode IntLC X62
In operating mode IntLC X62 the building management system provides the setpoint for the internal load controller via the analogue input. In parameter Ext Inp X62 U/I , the input has to be matched to the analogue signal [ch.6.12.4]. Parameters Ext Setpoint min/-max can be used to limit the external setpoint [ch.6.12.6].
The contact is used to switch from the external setpoint to the internal setpoint W1. If a voltage signal is present at inputX62:2, the voltage signal has to be separated from inputX62:2 when switching over to the internal setpoint W1.
Open: External setpoint activated Closed: Internal setpoint W1 activated
Operating mode IntLC Bus
In operating mode Int LC Bus the building management system provides the setpoint for the internal load controller via the Bus connection. The contact is used to switch from the external setpoint to the internal setpoint W1.
Open: External setpoint activated Closed: Internal setpoint W1 activated
83054802 1/2018-07 La
32-228
Page 33
Installation and operating instruction
FE
2 3
X60
4 5
1
Pt100
Pt/Ni 1000
Pt100Pt/Ni 1000
P /
FE
0
4-20 mA
0-10 V2
3
X61
4 5
1
Power Supply Sensor
TEMP.TEMP./PRES. INPUT
4...20 mA
GND
IN
0....10 V
FE
0
RESERVE
Pulse-In
Usensor
2 3
X70
5
4
1
2 wire
3 wire
BN
BU
BN
BK
BU
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.3.20 Temperature sensor

If the internal load controller is activated in parameter LC_OptgMode , a temper­ature sensor has to be connected to input X60 or a temperature or pressure sensor has to be connected to input X61.
On W-FM 200 with flue gas recirculation(FGR), the FGR temperature sensor is connected to inputX60:3/4 as standard and is not available for the load controller. As an alternative, the flue gas temperature sensor on the O2 module (accessory) can be used as FGR temperature sensor [ch.3.3.23]. The sensor used must be defined in parameter FGR-sensor, see [ch.6.15.3].
On W-FM 200 with CO control the combustion air sensor is fitted to inputX60:3/4 and is not available for the load controller. Parameter AirTempX60PT1000 (OEM level) must be set to activated .
The internal temperature monitor function is only possible with temperature sensor on input X60. If there is no external safety temperature limiter available in the safety circuit, two temperature sensors (Pt100/Pt1000 or Pt100/Ni1000) must be con­nected for the internal temperature monitor function. With different cable resistances in the three-wire circuit (Pt100) line compensation is required.
Depending on the circuitry, the inputs must be configured via the following para­meters:
Sensor selection [ch.6.12.3] Ext Inp X61 U/I [ch.6.12.4] Measuring range [ch.6.12.5] Additional sensor for boiler start function [ch.6.12.14].
The voltage supply (20VDC) on terminalX61:1 can not be changed.
83054802 1/2018-07 La

3.3.21 Speed measurement

For operation with frequency converter (W-FM 200 only) the proximity switch for speed measurement is connected to input X70.
Via the transmitter disc, the proximity switch detects 3 impulses per rotation. The number of impulses must be defined in parameter Num Puls per R, see [ch.6.14.2]. The direction of rotation is detected by the asymmetrical transmitter disc (60°, 120°, 180°).
33-228
Page 34
3 Product description
FE
0
Pulse-In
Usensor
2 3
X71
4
1
GAS
2 wire
3 wire
FE
0
Pulse-In
Usensor
2 3
X72
4
1
OIL
2 wire
3 wire
2 3
X86
1
Pt/Ni 1000
FUEL GAS
Pt/Ni 1000
2 3
X87
1
Pt/Ni 1000
COMBUS-
TION. AIR
Pt/Ni 1000
2 3
X87
1
Pt/Ni 1000
COMBUS-
TION. AIR
Pt/Ni 1000
COx >max
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.3.22 Fuel Meter

It is possible to connect 2 fuel meters to the W-FM 200:
Gas meter: X71 Oil meter: X72
Supply (PIN 1) approx. 10 V DC / max 45 mA Input (PIN 2) max 10 V DC
High level: min 3 V DC Low level: max 1.5 V DC
Sensor Inductive sensor to DIN 19234 (Namur)
Open Collector (pnp) Reed contact
Frequency max 300 Hz
The number of impulses per unit of volume must be set in parameter Pulse- Value… .

3.3.23 Flue gas temperature sensor

The flue gas temperature sensor is connected to the O2 module input X86 (access­ory). The sensor has to be configured in parameter FlueGasTempSens, see [ch.6.10.9].
Alternatively, the flue gas temperature sensor can be used as FGR temperature sensor (flue gas recirculation). In parameter FGR sensor X86PtNi1000 must then be defined as FGR temperature sensor [ch.6.15.3].

3.3.24 Combustion air sensor / CO resistance circuit board

The combustion air temperature sensor is connected to the O2 module inputX87 (accessory). The sensor has to be configured in parameter SupAirTempSens, see [ch.6.10.9].
In conjunction with CO control, a resistance circuit board is connected to input X87. The digital output3 of the CO measurement amplifier is connected to the O2 module via the resistance circuit board. The combustion air sensor then has to be connected to input X60:3/4 [ch.3.3.20].
83054802 1/2018-07 La
34-228
Page 35
Installation and operating instruction
2 3
X81
4 5 6
1
QGO...
B1
M
B2
M
G2
U3
B1
M
B2
M
G2
U3
Q4
Q5
QGO...
GND
2 3
X89-2
1
QGO...
PE
NLQ5
Q4
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.3.25 O2 sensor

The O2 sensor is connected to the O2 module (accessory). Connect the signal cable (3x2x0.25 mm2), twisted in pairs, to X81. Connect the screen to one side of the creen clamp of the O2 module, cable length maximum 10m. Connect separate cable (3x0.75 mm2) for the sensor heating to outputX89-2:Q4/Q5.
The O2 sensor has to be configured in parameter O2 Sensor, see [ch.6.10.7].
Terminal Function
B1 / M Nernst voltage depending on the current O2 content
[ch.6.10.16].
B2 / M Thermo element of the O2 sensor (0…33mV), 700°C equal to
approx. 29.1mV.
Current operating temperature [ch.6.10.20]. G2 Voltage supply for temperature compensation U3 Signal of temperature compensation L (Q4)
N (Q5)
Pulsed voltage supply for sensor heating230V,N(Q5) is
switched. Parameter QGO HeatingLoad shows the current
heating capacity [ch.6.10.21].
83054802 1/2018-07 La
35-228
Page 36
3 Product description
1 2
X3-01
L
L
MOTOR
ALARM
1 2
X3-01
L
L
MOTOR
ALARM
M
N
L
1 2
X6-02
3
PE
N
L
M
~
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.4 Outputs

3.4.1 Alarm

In lockout position (Phase00) a mains voltage signal is emitted at alarm out­putX3-01:2. Additionally, it is also possible to signal prevention. To do this parameter Alarm- StartPrev is set to activated [ch.6.8.2]. The time, before a start prevention trig­gers an alarm is set in parameter AlarmDelay, see [ch.6.8.1]. Parameter Alarm act/deact is used to deactivate the alarm signal [ch.9.1.1]. The deactivation only affects the alarm output, lockout or start prevention are not reset. Reset or burner start are reset automatically by the deactivation and the alarm output is ready of use again.

3.4.2 Motor

The fan motor is connected to outputX3-01:1 via contactor or star delta switching. Depending on parameter ContinuousPurge the output is controlled from Phase22 or continuously [ch.6.8.7]. If an air pressure switch is fitted, continuous running fan is only possible via pres­sure switch relief. To do this, a vent valve has to be fitted and connected to out­putX4-03.

3.4.3 Oil pump / magnetic coupling

Either the magnetic coupling, a separate oil pump or the anti syphon valve are con­nected to outputX6-02.
The type of oil pump coupling is set in parameter OilPumpCoupling, see [ch.6.8.4].
Magnetic coupling / separate oil pump
On dual fuel burners with magnetic coupling or on burners with separate oil pump, parameter OilPumpCoupling is set to Magnetcoupl . The switch-on point of the ignition should be set to short pre-ignition (on in Ph38). In light oil opera­tion, the output is controlled from the start of pre-ignition (phase38) to operating setting2 (phase62). In heavy oil operation, the output is controlled in phase36, to ensure oil pressure is available for the subsequent nozzle circulation.
Direct coupling
On oil burners with the oil pump directly coupled to the burner motor, the anti sy­phon valve is connected to outputX6-02. Parameter OilPumpCoupling must be set to Directcoupl, this means that long ignition is activated automatically. The output is controlled together with the fan from phase22 and remains activated for a further 15seconds after the fan has switched off.
83054802 1/2018-07 La
36-228
Page 37
Installation and operating instruction
1 2
X4-03
3
PE
N
L
M
P
P
+
-
1 2
X4-03
3
PE
N
L
M
P
P
+
(START)
(START)
1 2
X4-02
3
PE
N
L
IGNITION
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.4.4 Start signal, pressure switch relief

OutputX4-03 is controlled depending on parameter Start/PS valve, see [ch.6.8.10].
Start signal
If parameter Start/PS valve is set to Start signal , the output is con­trolled in phase21 to phase79.
Pressure switch relief
If an air pressure switch is fitted, continuous venting or direct start is only possible via pressure switch relief. To do this, a normally open vent valve has to be fitted to the air pressure switch and parameter Start/PS valve must be set to PS Reli_Inv The output is controlled together with the fan motor, except at start release (phase21) and direct start (phase79). The output is not controlled in phase21 and79, the air pressure switch de-energises via the open vent valve and the signal at inputX3-02:1 corresponds to the program sequence.

3.4.5 Ignition

The ignition unit is connected to outputX4-02.
Ignition behaviour Gas
In gas operation, the output is controlled in phase38 and40. The pre-ignition time in phase 38 can be adjusted in parameter PreignitionT- Gas, see [ch.6.8.1].
Ignition behaviour Oil
The switch-on point of the ignition is determined in parameter IgnOilPump­Start, see [ch.6.8.4]. The pre-ignition time in phase38 can be adjusted in parameter Preignition­TOil, see [ch.6.8.1].
ParameterIgnOilPumpStart Application on in Ph38
Output is controlled in phase38 and40 (short pre-ignition).
on in Ph22 Output is controlled in phases22 to40 (long pre-ignition).
Dual fuel burners with magnetic coupling between burner motor and oil pump.
Burners with separate pump or pump station.
Burners with oil pump coupled directly to the burner motor.
83054802 1/2018-07 La
37-228
Page 38
3 Product description
1 2
X6-03
3
PE
N
L
SV
1 2
X6-02
3
PE
N
L
M
1 2
X3-01
L
L
MOTOR
ALARM
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.4.6 Anti syphon valve

If an anti syphon valve is fitted in the oil supply, the valve can be connected to out­putX6-03, X6-02 or X3-01.
Output X6-03:
Dual fuel burners with magnetic coupling between burner motor and oil pump Oil and dual fuel burners with separately driven oil pump
Output X6-02:
Oil burners with oil pump coupled directly to the burner motor (without continu­ous running fan)
Output X3-01:
Dual fuel burners with oil pump coupled directly to the burner motor (without continuous running fan) Oil burners with oil pump coupled directly to the burner motor (with continuous running fan)
83054802 1/2018-07 La
38-228
Page 39
Installation and operating instruction
L
1 2
X7-01
3
PE
N
L
V2
1 2
X7-02
3
PE
N
L
V3
1 2
X8-02
3 4
N
PE
V1
L
1 2
X8-03
3 4
N
PE
V1
2
1
3
2
1
MSEL
1
2
X7-01
3
PE
N
L
V2
L
1
2
X8-02
3
4
N
PE
V1
MS
EL
L
1
2
X8-02
3
4
N
PE
V1
L
1
2
X8-03
3
4
N
PE
V1
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.4.7 Oil fuel valves

The oil solenoid valves are connected to the outputsX7-01, X7-02, X8-02 and X8-03. The outputs are controlled according to the program sequence [ch.3.2.7].
Multi-stage operation
Output Light oil (EL)
Heavy oil (MS) three stage
X7-01 Stage 2 Stage 1 X7-02 Stage 3 Stage 2 X8-02 Stage 1 ­X8-03 Additional solenoid valve Additional solenoid valve
Nozzle circulation via outputX8-03 is not possible on three stage heavy oil burners, as the combustion manager controls outputsX8-02 andX8-03 simultaneously. The solenoid valve for nozzle circulation is connected to outputX4-02 (ignition) and parameter IgnOilPumpStart must be set to on in Ph22 (long pre­ignition) [ch.6.8.4].
Heavy oil (MS) two stage
Modulating operation
Output Light oil (EL) Heavy oil (MS)
X7-01 - Nozzle solenoid (nozzle head) X8-02 Nozzle solenoid (nozzle head)
-or-
Solenoid valves
X8-03 Additional solenoid valves
(1
The solenoid valve in the supply is always switched electrically in series with the
(1
(1
Additional solenoid valves Bypass valve (only with separate
pump station)
-
(1
solenoid valve in the return.
83054802 1/2018-07 La
39-228
Page 40
3 Product description
N PE
2
1
1 2
X9-02
N
PE
L
1 2
X9-01
3 4
SV
L
PV
L V2
L
V1
SV
PV
L
1 2
X9-01
SV
L
PV
L
1 2
X9-01
SV
L
PV
(1
(2
V2 / V1
2
1
N PE
L
1 2
X9-01
3 4
SV
L PV
L
V2
L V1
P
1 2
X9-02
N
PE
L
1 2
X9-01
3 4
SV
L PV
L V2
L
V1
M1
M
2
1 2
X8-01
GAS
N
OIL
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.4.8 Fuel valves Gas

The fuel valves are connected to outputX9-01. The contacts are controlled in ac­cordance with the program sequence [ch.3.2.7].
Output Fuel valve
X9-01:1 (SV) External gas solenoid valve (optional) X9-01:2 (PV) Ignition gas valve(1
- or -
Gas ignition device Main gas
X9-01:3 (V2) X9-01:4 (V1)
(1
Only for burners with ignition gas tube.
(2
Only for heavy oil burners with gas ignition
Double gas valve
Valve 2
Valve 1
(2
83054802 1/2018-07 La
Valve lift monitoring
The two actuators (SKP15) of double gas valves type VGD (from DN125) are equipped with limit switches. The limit switches monitor the valve lift and are switched in sequence with the voltage supply of actuatorV2. At burner start, the limit switches are bridged via a timer relay for approx.25 seconds. If both limit switches are closed once this time has elapsed, valveV2 re­mains open. If a valve does not maintain the minimum lift, the relevant limit switch opens and in­terrupts the voltage from actuatorV2. ValveV2 closes and the combustion man­ager initiates a safety shutdown with restart. The number of safety shutdowns in se­quence set in parameter LossOfFlame result in a lockout [ch.6.8.12].
Alternatively with pressure regulator on double gas valve: If a pressure regulator (SKP25) is mounted on the gas double valve, a low gas pressure switch monitors the valve lift. In this case, the contact of the gas pressure switch is connected in series with the power supply of actuator V2. When starting the burner, the gas pressure switch is bridged by a time relay for approx. 5 seconds.

3.4.9 Operational display

OutputX8-01 is controlled together with valve1 of the current fuel. The output may only be used as the operating display.
40-228
Page 41
Installation and operating instruction
FE
1 2
X63
3
0
4-20 mA
FE
1 2
X73
3 4
6
5
Start OUT
0
U1
WH
BN
GN
YE
GY
Combustion manager W-FM 100 und W-FM 200
3 Product description

3.4.10 Analogue output

If the combustion manager is equipped with an internal load controller, a system value can be issued at output X63 via an analogue signal(0/4 … 20mA). The out­put can be configured in parameter Analog Output, see [ch.6.12.7].
Load signal
If the parameter Selection analog output is set to Load the analogue signal corresponds to defined values. For different scaling, the parameter has to be set to Load 0 .
Modulating operation:
Burner capacity OFF 0 % 100 % Analogue signal 4 mA 4 mA 20 mA
Multi-stage operation:
Burner capacity OFF Stage 1 Stage 2 Stage 3 Analogue signal 4 mA 5 mA 10 mA 15 mA

3.4.11 Frequency converter

The frequency converter is connected to output X73 using a screened cable (W-FM 200 only). The screen must be connected to ground on both sides.
Terminal (W-FM 200)
X73:1/2 Enable contact:
X73:3 Alarm input:
X73:4/5 Setpoint output (0/4…20mA):
Function
The enable contact for the frequency converter closes from a de-
sired speed greater than 0%.
The switch status in phase10 (home run) for the standby position
(0%) can be specified via parameter ReleasecontctVSD, see
[ch.6.14.1].
A signal from the frequency converter(DC12…24V) results in
a safety shutdown.
The output and input (W-FM 200 / frequency converter) must be
matched. The output signal can be set in parameter Setpoint
Output, see [ch.6.14.5].
83054802 1/2018-07 La
41-228
Page 42
3 Product description
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.5 Technical data

3.5.1 Electrical data

Combustion Manager
Mains voltage / Mains frequency (120) 230 V / 50 … 60 Hz Consumption max 30 W Internal unit fuse T6.3H, IEC 127-2/5 External fuse max 16 AB Type of protection IP 00
Total contact load outputs max 5A Fan motor (output X3-01:1) 1A Alarm (output X3-01:2) 1A Ignition (output X4-02) (1.6) 2A Pressure switch relief (output X4-03) 0.5A Magnetic coupling (output X6-02) (1.6) 2A Oil fuel valves (1.6) 1A Fuel valves Gas (1.6) 2A
Display and operating unit (ABE)
Mains voltage AC 24 V Consumption max 50 mW Type of protection (front) Type of protection (rear)
Transformer
Mains voltage / Mains frequency (120) 230 V / 50 … 60 Hz Secondary 1 AC 12 V Secondary 2 2 x AC 12 V
Actuator
SQM45… SQM48.497A SQM48.697A SQM91.391A9
Mains voltage AC 2 x 12 V AC 2 x 12 V AC 2 x 12 V AC 2 x 12 V Consumption 9 … 15 VA 26 … 34 VA 26 … 34 VA approx. 40 VA Torque 3 Nm 20 Nm 35 Nm 60 Nm Setting time 10 s / 90° 30 s / 90° 60 s / 90° 30 s / 90° Type of protection IP 54 IP 54 IP 54 IP 66
IP54 to ICE 529 IP00 to ICE 529
83054802 1/2018-07 La
42-228
Page 43
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
3 Product description
O2 module
Mains voltage / Mains frequency (120) 230 V / 50 … 60 Hz Consumption O2 module
Consumption O2 sensor Internal unit fuse 2.5 T, IEC 127-2/1 External fuse max 16 AB Type of protection IP 44
O2 sensor
Mains voltage / Mains frequency (120) 230 V / 50 … 60 Hz Consumption max 90 W Type of protection IP 44 Permissible flue gas velocity 1 … 10 m/s Flue gas temperature max 300 °C Permissible fuels QGO 20:
max 4 W max 90 W
Natural and Liquid Petro­leum Gas Fuel oil EL
QGO 21:
Natural and Liquid Petro­leum Gas Fuel oil EL Heavy oil to DIN 51603-3 and DIN 51603-5

3.5.2 Ambient conditions

Temperature in operation –20 … +60 °C Temperature during transport / storage –20 … +60 °C relative humidity max 95 %, no dew point
83054802 1/2018-07 La
43-228
Page 44
3 Product description
82 mm
260 mm
232 mm
250 mm
19
24
49 mm
96 mm
90,2 mm
135,8 mm
126 mm
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

3.5.3 Dimensions

Combustion Manager
Display and operating unit (ABE)
Recess dimension: 127 x 91 mm ± 0.5 mm
83054802 1/2018-07 La
44-228
Page 45
Installation and operating instruction
79,5 mm
102,5 mm
120 mm
10,5 mm
40,5 mm
55,5 mm
9 mm
87 mm
66,5 mm
Combustion manager W-FM 100 und W-FM 200
Transformer
3 Product description
83054802 1/2018-07 La
45-228
Page 46

4 Installation

90 mm
51 mm
180 / 260 mm
53,5 mm
48 mm
QGO 21
QGO 20
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
4 Installation

4.1 Installing O2 sensor

O2 trim is only possible with W-FM 200 with O2 module. For O2 measurement, an O2 sensor must be fitted in the flue gas pipe and connec­ted to the O2 module. The distance between O2 sensor and O2 module must be no more than 10m.
Flange dimensions
CAUTION
Prerequisite
Damage to the O2 sensor caused by overheating
Flue gas temperature above 300°C can damage the O2 sensor.
Avoid flue gas temperatures above 300°C at the O2 sensor.
Install O2 sensor only with the corresponding flange. It must not be possible for extraneous air to enter in front of the sensor and at a distance of 2xØ of the flue gas pipe behind the sensor.
83054802 1/2018-07 La
46-228
Page 47
Installation and operating instruction
45°
45°
QGO 21
QGO 20
min 1 x Ø
Ø
1
≥ 10 mm
2
3
2
31
QGO 20
QGO 21
4
Combustion manager W-FM 100 und W-FM 200
4 Installation
Installation position
Install the sensor as close as possible to the flue gas outlet of the boiler, but at least at a distance of 1xØ of the flue gas pipe. Sensor in the horizontal part of the flue gas pipe:
QGO 20: vertically from above or at an angle of 45°. QGO 21: horizontal
Sensor in the vertical part of the flue gas pipe:
With a downward inclination of approx. 5°.
Installation
Weld flange gastight to flue gas pipe1, with QGO20 observe the position of the flue gas outlet openings4. Install O2 sensor2, ensuring correct alignment of the seal3. Cable entry must be made on the opposite side to the flue gas flow.
83054802 1/2018-07 La
47-228
Page 48

5 Installation

DANGER
WARNING
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
5 Installation

5.1 Electrical connection

Risk of electric shock
Working on the device when voltage is applied can lead to electric shock.
Isolate the device from the power supply prior to starting any work. Safeguard against accidental restart.
Electric shock despite disconnection from the voltage supply
It is possible that electrical components on burners with frequency converters con­tinue to carry voltage and cause electric shock even after the voltage supply has been disconnected.
Wait approx. 5 minutes before commencing work. Electric voltage has dissipated.
The electrical connection must only be carried out by qualified electricians. Ob­serve local regulations.
Connect combustion manager
Use cable entry grommets on the housing. Connect wiring to wiring diagram enclosed.
Control circuits, which are taken directly via a 16AB fuse from a 3 phase or single phase alternating current supply, must only be connected between a phase conductor and earth potential neutral conductor.
On mains supply, which does not have a neutral, the control voltage must be sup­plied via an isolating transformer. The pole of the transformer, which is to be used as the neutral conductor, must be earthed.
Phase L must not be mixed up with the neutral conductor N. Contact protection will otherwise no longer be given. Malfunctions, which endanger operational safety could occur.
The cable cross section of the voltage supply must be suitable for the nominal cur­rent of the external fuse (maximum 16AB). All other cable connections must be suitable for the relevant internal unit fuse (T6.3H).
Earthing and neutral conductor must conform to local regulations. The following applies for cable length:
all cable lengths maximum 100 m, use only original Weishaupt parts as Bus line, install Bus line as line configuration.
83054802 1/2018-07 La
48-228
Page 49
Installation and operating instruction
12V
12VUN12V
X10-01
G
G0LN
X52FEX51
X51
CANL
CANH
CANL
CANH
5
3
X3-04
NLPE
W-FM ...
5
12V
12VUN12V
SQM...
M
SQM...
M
SQM...
M
5
5
N
L
12V
12VUN12V
X10-01
GG0LNX52FEX51
X51
CANL
CANH
CANL
CANH
SQM...
M
SQM...
M
SQM...
M
5
5
5
5
5
O2
X3-04
NLPE
W-FM 200
4 AT
4 AT
4 AT
4 AT
6,3 AT
4 AT
4 AT
6,3 AT
6,3 AT
1
2
4
3
4
4
1
5
2
Combustion manager W-FM 100 und W-FM 200
5 Installation
Bus connection / supply voltage
The CAN Bus line must not exceed a total length of 100 m. A second source trans­former is required from a line length of 20m between the combustion manager and the last actuator, e.g. if the combustion manager is fitted to control panel. In this case transformer1 feeds the combustion manager and ABE, transformer2 feeds the actuators. In so doing, the power supply of the CAN bus line (AC1 and AC2) between combustion manager and the first actuator must not be connected.
The ends of the bus line must be terminated with a bus termination resistor. The bus termination is permanently installed in the ABE. On the last actuator or at the O2 module, the bus termination must be set via a jumper. Bus termination must be deactivated for all other participants.
The screen of the bus line must be terminated at both ends.
1 Burner 2 Bus termination 3 Control panel 4 Transformer 5 O2 module
83054802 1/2018-07 La
49-228
Page 50
5 Installation
1
2 3 4
5
6
7 8 9
18
CAN
X70
COM 2
X72
1
2 3 4
5
6
7 8 9
COM 1
X71
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Display and operating unit (ABE)
The ABE is equipped with 3 interfaces.
CAN (X70): CAN Bus connection to the combustion manager COM 1 (X71): RS-232 for PC connection COM 2 (X72): RJ45 connection building management system via Bus interface
The COM interfaces can not be used at the same time
PIN CAN (X70) COM 1 (X71) COM 2 (X72)
1 - - TXD 2 CAN L RXD ­3 GND TXD RXD 4 VAC 2 - GND 5 - GND U 1 6 - - GND 7 CAN H - U 2 8 VAC 1 - -
83054802 1/2018-07 La
50-228
Page 51
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
5 Installation
Connect burner / fan motor, pump station
The motor must be protected against thermal overload and short circuit. Weishaupt recommend the use of a motor protection switch.
Open terminal box on motor. Connect voltage supply to wiring diagram enclosed, observe motor rotation.
Variable speed drive (optional)
If the frequency converter is located on the motor, the cable to the frequency con­verter is not screened.
If the frequency converter is separate the control line and the motor connection must be screened.
Apply screen to the screen clamp on frequency converter. Use screen cable glands (metal) on the burner.
Connect gas valve train
Observe wiring diagram supplied.
Connect double gas valve (plug K32).
Solenoid coil on W-MF or DMV
Actuator on VGD. Connect limit switch for valve lift monitoring (plug S33 / S35), only with VGD. Connect ignition gas valve (plug K31). Connect low gas pressure switch (plug B31). Connect valve proving gas pressure switch (plug B32). If required, connect high gas pressure switch (plug B33). Connect connection cable to burner using cable entry W-FM.
83054802 1/2018-07 La
51-228
Page 52
5 Installation
2 3
X81
4 5 6
1
QGO...
B1
M
B2
M
G2
U3
GND
2 3
X89-2
1
QGO...
PE
NLQ5
Q4
Q5
Q4
G2
M
M
B1
U3
B2
PLL...QGO...
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Connect O2 sensor
The O2 sensor is connected to the O2 module (accessory). Connect the signal cable (3x2x0.25 mm2), twisted in pairs, to X81. Connect the screen to one side of the creen clamp of the O2 module, cable length maximum 10m. Connect separate cable (3x0.75 mm2) for the sensor heating to outputX89-2:Q4/Q5.
83054802 1/2018-07 La
52-228
Page 53
Installation and operating instruction
4
3
2
1
Combustion manager W-FM 100 und W-FM 200

6 Operation

6.1 Operating interface

6.1.1 Operating panel

Display and operating unit (ABE)
6 Operation
1 Dial knob navigation through parameter structure; chan-
ging values
2 [Enter] select 3 [esc] return/cancel 4 [info] return to operating display
OFF function
Press [ENTER] and [esc] simultaneously. Immediate lockout. The lockout is stored in the fault history.
83054802 1/2018-07 La
53-228
Page 54
6 Operation
1
Normal operation Status/Reset Fault history Lockout history
Normal operation Status/Reset Fault history Lockout history
Operating display Operation Manual operation Param & Display
Lockout
Air pressure is off
Safety shutdown
Safety loop is open
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.1.2 Display

The ABE is equipped with a 4 line display with 16 characters per line. The dial knob is used to scroll through the display, the cursor1 indicates the position se­lected.
Operating display
The [info] key is used to jump from any menu level to the operating display menu. The [esc] key is used to return the display to the menu point previously used.
Menu level 1
The [esc] key is used to leave any position and to go back all the way to menu level 1 [ch.6.3].
Fault display
During a fault condition, the display alternately shows the shutdown behaviour and the fault diagnosed as a plain text display.
The combustion manager is in lockout. Once the fault has been rectified, the combustion manager has to be reset for restart [ch.9.1].
The combustion manager initiates a safety shutdown. The burner restarts automatically once the fault condition has been rectified.
83054802 1/2018-07 La
54-228
Page 55
Call up menu level 1
Normal operation Status/Reset Fault history Lockout history
Operating display Operation Manual operation Param & Display
Updating Enter PW TÜV Test
Operating display Operation Manual operation Param & Display
Operating display Operation Manual operation Param & Display
Boiler setpoint User Maxload Fuel Date/Time
Boiler setpoint User Maxload Fuel Date/Time
Operating display Operation Manual operation Param & Display
Auto/Manuel/Off Time SwitchOffBeh ProgramStop
Program stop Curr: deactivated New: 36 Ignpos
Auto/Manuel/Off Time SwitchOffBeh ProgramStop
Program stop Curr: deactivated New: 36 Ignpos
Navigating through the level
One level lower
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.2 Displaying and adjusting parameters

Press [esc] key until menu level 1 is displayed.
Turn dial knob. Cursor switches to the next menu point.
If a level has more than 4 menu points, the display scrolls up and down.
Press [ENTER].
One level higher
Change value
Save value
Press [esc] key.
Press [ENTER]. Selected parameter is displayed. Turn dial knob. New value is displayed.
Press [ENTER]. The value changed is applied and saved.
Do not accept value:
Press [esc] without first confirming with [Enter] key. Exit parameter without changing the value.
83054802 1/2018-07 La
55-228
Page 56
6 Operation
Enter PW TÜV Test
Manual operation Param & Display Updating Enter PW
Access without PW Access with HE Access with OEM Access with SBT
Enter Password :9876••••
Operating display Operation Manual operation Param & Display
Param & Display Updating Enter PW Deactivate PW
Password has been deactivated
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.2.1 Password

Enter password
HE password: 9876 Select Enter PW in menu level1 and press the [Enter].
Select Access with HE and press [Enter]. Set first character using the dial knob and confirm with [Enter]. A star appears and the cursor moves to the next position. Repeat procedure until the password has been entered. Confirm password with [Enter]. Display changes to menu level 1.
Deactivating password
If no key is activated for 120 minutes, the combustion manager automatically deac­tivates the password and blocks the password level.
Select Deactivate PW in menu level 1 and press [Enter]. The display shows Password has been deactivated. Press [esc] key. Display changes to menu level 1.
83054802 1/2018-07 La
56-228
Page 57
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.3 Menu structure

Values in the square brackets show the factory setting.
Operating display
Normal operation Status/Reset Fault history Lockout history Alarm act/deact
Operation
Boiler setpoint
Setpoint W1 Setpoint W2
Load limitAB
UserMaxLoadMod [100 %] UserMaxLoadStg [S3]
Fuel
CurrentFuel FuelSelect
6 Operation
Date/Time
Display the clock
Date Time Weekday
Set the clock
Date Time Weekday
Hours run
Gas operation OilStage1/Mod OilStage2 OilStage3 TotalHoursReset TotalHours SystemOnPower
StartCounter
GasStartCount OilStartCount TotalStartCountR TotalStartCount
Fuel meter
(1
Curr Flow Rate Volume Gas Volume Oil Volume Gas R Volume Oil R Reset DateGas Reset DateOil
83054802 1/2018-07 La
Number of lockouts
57-228
Page 58
6 Operation
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Operation (continued)
O2 module
curr. O2 value O2 setpoint(1 Inlet air temperature Flue gas temperature(1 CombEfficiency
(1
(1
(1
Burner identification Operating mode selection
Interface PC GatewayBASon GatewayBASoff Type of Gateway [Modbus]
O2Ctrl activate
(1
Manual operation
SetLoad Autom/Manual/Off [Automatic]
Param & Display
Burner Control
(2
Times
TimeStartup1
MinTimeStartRel [1 s] FanRunUpTme [2 s] PrepurgeTmeGas [20 s] PrepurgeTmeOil [15 s] PrepurgeSafeGas [20 s] PrepurgeSafeOil [15 s] PrepurgePtl1Gas [0.2 s] PrpurgePt3Gas [0.2 s] PrepurgePt1Oil [0.2 s] PrepurgePt3Oil [0.2 s] PreIgnTime_Gas [2 s] PreIgnTime_Oil [2 s] MinOnTime Oil pump [1 s]
TimeStartup2
Interval1Gas [2 s] Interval1Oil [2 s] Interval2Gas [2 s] Interval2Oil [2 s] PressReacTime [2 s]
TimeShutdown
MaxTmeLowFire [45 s] AfterburnTme [8 s] PostpurgeT1Gas [0.2 s] PostpurgeT1Oil [0.2 s] PostpurgeT3Gas [5 s] PostpurgeT3Oil [5 s] PostpurgeT3long [0 s](1 DelayLackGas [10 s]
(1
W-FM 200 only
(2
only with HE password
83054802 1/2018-07 La
58-228
Page 59
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Times in general
AlarmDelay [35 s] DelayStartPrev [35 s] PostpurgeLockout [0.2 s] MaxTmeStartRel [120 s]
6 Operation
Configuration
ConfigGeneral
AlarmStartPrev [deactivated] StandbyError [deactivated] NormDirectStart[NormalStart] OilPumpCoupling IgnOilPumpStart ForcedIntermit [activated] Skip PrepurgeGas [deactivated] ContinuousPurge [deactivated]
ConfigIn/output
RotSpeed PS on(1 [80] RotSpeed PS off(1 [50] Config X5-03 [LMV5x hrs] Start/PS-Valve
ConfigFlamDet
ReacExtranLight [Startblock] FlameSignal
RepetCounter
LossOfFlame [2] HeavyOil [3] StartRelease [10] SafetyLoop [16]
(2
(2
(2
ProductID
ASN ProductionDate SerialNumber ParamSet Code ParamSet Vers
SW Version
Ratio control
SettingGas / Oil
SpecialPositions
HomePos PrepurgePos IgnitionPos PostpurgePos ProgramStop [deactivated] ResetIgnitPos
CurveParams LoadLimits
MinLoad [0 %] MaxLoad [100 %]
(1
W-FM 200 only
(2
only with HE password
(2
83054802 1/2018-07 La
59-228
Page 60
6 Operation
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Load mask out
LoadMaskLowLimit [0 %] LoadMaskHighLim [0 %]
FC(1 [activated] StartPoint Op [1]
Autom/Manual/Off [Automatic]
(2
Times
OperRampMod OperRampStage TimeNoFlame
ShutdownBehav(2 [Rest pos] ProgramStop(2 [deactivated]
O2Contr/Alarm
(1
Gas/Oil settings
Operating mode O2 trim
(2
O2 monitor
(2
(2
O2 Alarm O2 MaxValue [15] NumMinUntilDeact [1]
Controller parameter
PI LowFireAdaptPtNo(2 [2] O2CtrlThreshold(2 [0 %] LoadCtrlSuspend(2 [5 %] O2ModOffset(2 [0 %] Type Air Change(2 [like theory] O2MaxManVariable(2 [35%] O2MinManVariable(2 [-35%]
Startmode
O2InitOffset(2 [0 %] NoTauSuspend(2 [10] Adjust. Temp O2 [20 °C]
Type of Fuel Fuel user-def
V_LNmin V_afNmin V_atrNmin A2 B/1000
(2
COx
OptgMode COx Gas [deactivated] OptgMode COx Oil [deactivated] Time COx alarm [20 s]
(1
W-FM 200 only
(2
only with HE password
(2
(2
83054802 1/2018-07 La
60-228
Page 61
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Process data
CombEfficiency Man Var O2Ctrl State O2Ctrl Air-Related Load Diag Reg State
Load controller
Controller parameters
ContrlParamList
StandardParam P Part (Xp) [15 %] I Part (Tn) [320 s] D Part (Tv) [40 s]
MinActuatorStep [1 %] SW_FilterTmeCon [3 s] SetpointW1 SetpointW2 Sd_ModOn [1 %] Sd_ModOff [10 %] Sd_Stage1On [-2 %] Sd_Stage1Off [10 %] Sd_Stage2Off [8 %] Sd_Stage3Off [6 %] ThreshStage2On[300] ThreshStage3On [600]
TempLimiter
(2
TL_ThreshOff [95 °C] TL_SD_On [-5 %]
6 Operation
Cold start
ColdStartOn (2 [deactivated] ThresholdOn(2 [20 %] StageLoad(2 [15 %] StageSetp_Mod(2 [5 %] StageSetp_Stage(2 [5 %] MaxTmeMod(2 [3 min] MaxTmeStage(2 [3 min] ThresholdOff(2 [80 %] AdditionalSens(2 [deactivated] Temp. ColdStart SetpAddSensor Release Stages(2 [Release]
Configuration
LC_OptgMode [Int LR] Sensor Select(2 [Pt100] MeasureRangePtNi(2 [150 °C / 302 °F] var.RangePtNi(2 [850 °C] Ext Inp X61 U/I(2 [0 … 10 V] MRange TempSens(2 [90 °C] MRange PressSens(2 [2 bar] Ext Inp X62 U/I(2 [4 … 20 mA] Ext MinSetpoint(2 [0 %] Ext MaxSetpoint(2 [60 %]
(1
W-FM 200 only
(2
only with HE password
(2
83054802 1/2018-07 La
61-228
Page 62
6 Operation
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Analogue output
(2
OutValuSelection [Load] CurrMod 0/4mA [4 … 20 mA] Scale20mA perc [100 %] Scale20mA temp [850 °C] Scale20mA press [2 bar] Scale20mA angle [90°] Scale 0/4mA [0 %]
Adaption
StartAdaption AdaptionLoad [100 %]
SW Version
ABE
Times
Sum/WinterTime[Automatic] Time EU/US
Language DateFormat PhysicalUnits
eBUS
Address [1] SendCycleBU [30 s]
Modbus
Address [1] Baud rate [19200 bit/s] Parity [none] Timeout [30 s] Local / Remote Remote Mode W3
Display contrast ProductID
ASN ProductionDate SerialNumber ParamSet Code ParamSet Vers
SW Version
83054802 1/2018-07 La
Actuators
Addressing
1 AirActuator 2 GasActuator. (Oil) 3 OilActuator 4 AuxActuator 5 AuxActuator2(1 6 AuxActuator3
Rotation direction
DeleteCurves
(1
W-FM 200 only
(2
only with HE password
(2
(2
62-228
Page 63
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
ProductID
1 AirActuator 2 GasActuator. (Oil) 3 OilActuator 4 AuxActuator 5 AuxActuator2(1 6 AuxActuator3
SW Version
1 AirActuator 2 GasActuator. (Oil) 3 OilActuator 4 AuxActuator 5 AuxActuator2(1 6 AuxActuator3
VSD module
(1
Configuration
Releasecontct.VSD
(2
[closed]
6 Operation
Speed
Num Puls per R Standardisation StandardisedSp Absolute Speed Setpoint Output
Fuel meter
PulseValueGas [1] PulseValueOil [1]
Process data
Max Stat Dev Max Dyn Dev NumDev >0.3% NumDev >0.5% Absolute Speed
Product identification
ASN Production date SerialNumber ParamSet Code ParamSet Vers
SW Version
O2 module
(1
Configuration
O2 Sensor [no sensor] O2SensServTim [0] O2SensServTimRes SupAirTempSens [no sensor] FlueGasTempSens [no sensor] MaxTempFlGasGas [300 °C] MaxTempFlGasOil [300 °C]
(1
W-FM 200 only
(2
only with HE password
(2
[3]
(2
(2
(2
[4 … 20 mA]
(2
(2
83054802 1/2018-07 La
63-228
Page 64
6 Operation
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Process Data
Current O2 value O2 Setpoint SupplyAirTemp FlueGasTemp CombEfficiency QGO SensorTemp QGOHeatingLoad QGO Resistance
ProductID
ProductionDate SerialNumber ParamSet Code ParamSet Vers
SW Version
Flue gas recirculation
(1
FGR-Mode [Aux3 Curve] FGR-sensor [X86PtNi1000] actTmpFGR-sensor ThresholdFGR Gas ThresholdFGR Gas [300 s] FGR Factor Gas [100] Operating temp Gas ThresholdFGR Oil ThresholdFGR Oil [300 s] Factor FGR Oil [100] Operation TempOil FGR MinPos [0] FGR MaxPos Fact [10]
SystemConfig
LC_OptgMode [IntLC] Ext Inp X62 U/I(2 [4 … 20 mA]
TempLimiter
TL_Thresh_Off [95 °C] TL_SD_On [-5 %] Sensor Select [Pt100] MeasureRangePtNi [150 °C / 302 °F]
O2Ctrl/LimitrGas(2 [man deact] O2Ctrl/LimitrOil(2 [man deact] LC Analog output(2 [Load] allowed Pot.diff(2 [15]
Hours run
GasFiring OilStage1/Mod OilStage2 OilStage3 TotalHoursReset TotalHours SystemOnPower
(1
W-FM 200 only
(2
only with HE password
(2
83054802 1/2018-07 La
64-228
Page 65
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Reset
GasFiring OilStage1/Mod OilStage2 OilStage3 TotalHoursReset
StartCounter
GasStartCount OilStartCount TotalStartCountR TotalStartCount
Reset
GasStartCount OilStartCount TotalStartCountR
Fuel meter
Curr Flow Rate Volume Gas Volume Oil Volume Gas R Volume Oil R Reset DateGas Reset DateOil
6 Operation
Updating
ParamBackup
Backup info
Date TimeOfDay BU included? AZL included? LC included? SA1 included? SA2 included? SA3 included? SA4 included? SA5 included? SA6 included? VSD included? O2 included?
LMV5x -> AZL AZL -> LMV5x
Load SW from PC
(2
(2
(2
Enter PW Deactivate PW
(2
TÜV Test
LossFlameTest(2
SLT Test SLT TestlloadMod [100 %] SLT Testload Stg [S3]
(1
W-FM 200 only
(2
only with HE password
83054802 1/2018-07 La
65-228
Page 66
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.4 Operation and system information

6.4.1 Normal operation

Operating display Normal operation
In menu Normal operation you can switch between the standard display and the position display.
Press [ENTER]. Display changes.
Depending on the current operating phase, the standard display shows the follow­ing information:
Setpoint and actual value Fuel selected Current operating phase (clear text and number) Fuel and air actuator positions Current burner capacity and flame signal
The position display shows the following information:
Actuator positions Speed O2 content Burner capacity

6.4.2 Fuel selection

Operation Fuel Current fuel
Fuel selection
Current fuel
The fuel selected is shown in parameter CurrentFuel (read only).
Fuel selection
With dual-fuel burners you can switch between oil and gas operation. A fuel change during operation will initiate a restart.
Fuel selection is possible via:
Fuel selection switch on input X4-01:1/2 [ch.3.3.6] Parameter fuel selection (ABE) Building management system (BMS) on Bus connection.
The fuel selection switch on inputX4-01:1/2 has priority. Fuel selection via ABE or BMS is only possible if no signal is present at inputX4-01:1/2. There is not priority between ABE and BMS, the last fuel selection is valid and is retained after power failure.
83054802 1/2018-07 La
66-228
Page 67
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.4.3 Operating hours

Operation HoursRun
or
Param & Display HoursRun
Access in menu Operation/HoursRun is read only. The individual operating hours counters can be reset in Param & Display/ HoursRun/Reset/… .
Parameters Function
Gas operation Operating hours Gas (can be reset) OilStage1/Mod Operating hours Oil stage1 / modulating operation (can
OilStage2 Operating hours Oil stage2 (can be reset) OilStage3 Operating hours Oil stage3 (can be reset) TotalHoursReset Total operating hours (can be reset) TotalHours Total operating hours ( read only, can not be reset) SystemOnPower Operating hours with voltage applied to device (read only,
Reset Reset only possible under Param & Display /
6 Operation
be reset)
can not be reset)
HoursRun

6.4.4 Start-up counter

Operation StartCounter
or
Param & Display StartCounter
Access in menu Operation/StartCounter is read only. The individual start counters can be reset via Param & Display/Start- Counter/Reset/… .
Parameters Function
GasStartCount Burner starts Gas (can be reset) OilStartCount Burner starts Oil (can be reset) TotalStartCountR Total burner starts Gas and Oil (can be reset) TotalStartCount Total burner starts Gas and Oil (read only, can not be re-
Reset Reset only possible under Param & Display /
set)
StartCounter
83054802 1/2018-07 La
67-228
Page 68
Installation and operating instruction
Example
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.4.5 Fuel Meter

Only possible with W-FM 200.
Configuring the inputs
Param & Display VSD module Configuration Fuel Meter
In menu Fuel Meter , the input for the relevant fuel meter is configured [ch.3.3.22].
Parameters Function
PulseValueGas Number of impulses per volume unit of the gas meter at
input X71
PulseValueOil Number of impulses per volume unit of the oil meter at in-
put X72
The impulses per volume unit are entered in parameter Pulse value… with 4decimal places.
Using the number of impulses set in parameter Pulse value… the W-FM cal­culates the current fuel throughput. In full load, the impulse frequency must not exceed 300Hz. In partial load, the impulse frequency must be minimum 0.1Hz. If the fuel meter does not supply a signal for 10seconds, no fuel throughput is detected.
Gas meter: 100 impulses/m Full load throughput: 300 m3/h Partial load throughput: 50 m3/h
Full load frequency: 100 Imp/m3 x 300 m3/h = 30000 Imp/h
Partial load frequency: 100 Imp/m3 x 50 m3/h = 5000 Imp/h
3
30000 Imp/h ÷ 3600 s = 8.333 Hz
5000 Imp/h ÷ 3600 s = 1.389 Hz
Fuel throughput
Operation Fuel Meter
or
Param & Display Fuel Meter
If a fuel meter is connected, the parameters show the fuel consumption.
Parameters Function
Curr Flow Rate Current fuel throughput (read only, can not be reset) Volume Gas Total gas throughput (read only, can not be reset) Volume Oil Total oil throughput (read only, can not be reset) Volume Gas R Gas throughput (can be reset via Enter) Volume Oil R Oil throughput (can be reset via Enter) ResetDateGas Reset date fuel volume Gas ResetDateOil Reset date fuel volume Oil
83054802 1/2018-07 La
68-228
Page 69
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.4.6 Number of lockouts

Operation LockoutCounter
The parameterLockoutCounter shows the number of faults with lockout since commissioning (can not be reset).

6.4.7 Flame Signal

Param & Display Burner Control Configuration ConfigFlameDet Flame Signal
The parameter FlameSignal shows the current flame signal [ch.3.3.15].

6.4.8 Product identification

Param & Display Burner Control ProductID
or
Param & Display AZL ProductID
or
Param & Display Actuators ProductID
or
Param & Display VSD module ProductID
or
Param & Display O2 module ProductID
In menu ProductID the following information is displayed for all components selected:
ASN (type description) Production date Identification number Customer code parameters Version parameters

6.4.9 Software version

Param & Display Burner Control SW Version
or
Param & Display LoadController SW Version
or
Param & Display AZL SW Version
or
Param & Display Actuators SW Version
or
Param & Display VSD module SW Version
or
Param & Display O2 module SW Version
In parameter SW Version the software version of the selected components is shown.
83054802 1/2018-07 La
69-228
Page 70
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.4.10 Burner identification

Operation BurnerID
The parameter BurnerID shows the burner specific serial number. The burner identification serves as copy protection. Burner specific data in the memory of the ABE can not be transferred to another W-FM.
If a W-FM is delivered without burner identification and the backup copy from the ABE is installed, the W-FM adopts the burner identification of the backup copy [ch.6.16.1].
83054802 1/2018-07 La
70-228
Page 71
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.5 Setting the display

6.5.1 Setting the language

Param & Display AZL Language
The language for the display can be set in parameter Language . If the language required is not available, the display and operating unit (ABE) with the relevant group of languages should be used.
Group of languages (ABE) Languages
Western Europe 1 English, German, French, Italian, Spanish, Por-
tuguese
Western Europe 2 English, Dutch, Danish, Swedish, Norwegian,
Finnish
Eastern Europe 1 English, Polish, Hungarian, Czech, Croatian, Slove-
nian
Eastern Europe 2 English, German, Russian, Bulgarian, Turkish, Ru-
manian
6 Operation

6.5.2 Set contrast

Param & Display AZL Display Contrast
The contrast of the display can be changed and saved using parameter Display Contrast .
If the operating display is in normal operation, the contrast can be changed using the dial knob of the ABE.
Press and hold [Enter]. Set the contrast using the dial knob. The setting will remain until the power supply is interrupted
83054802 1/2018-07 La
71-228
Page 72
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.5.3 Date/Time

Display date and time
Operation Date/TimeOfDay DisplayClock
Set time
The date, time and weekday can be displayed in menu DisplayClock. The date, time and weekday are set using SetClock.
Summer/Winter time
Param & Display AZL Times Sum/WinterTime
Parameter Sum/WinterTime is used to select manual or automatic changeover from summertime to wintertime.
Parameter Time EU/US is used to select the European or American summer­time or wintertime.
Date TimeOfDay Weekday
Time EU/US
Date format
Param & Display AZL DateFormat
Parameter DateFormat is used to select the date formatDD.MM.YY or YY.MM.DD.

6.5.4 Units

Param & Display AZL PhysicalUnits
Parameter PhysicalUnits is used to select the formats °C/bar or °F/psi. All relevant values will be displayed and adjusted in the unit selected.
83054802 1/2018-07 La
72-228
Page 73
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.6 Interfaces

6.6.1 Select interfaces

Operation OptgModeSelect InterfacePC
Gateway BASon Gateway BASoff Type of Gateway
Menu OptgModeSelect is used to select the serial interface in the operating and display unit (COM1 or COM2) [ch.5.1]. The COM interfaces can not be used at the same time.
Interface for PC (COM 1)
The combustion manager can be programmed and operated via PC-Tool (Soft­ware: ACS450). The display and operating unit serves as interface.
Select parameter InterfacePC and confirm with [Enter]. The interface is activated until the [esc] key is used to exit from parameter In- terfacePC .
6 Operation
Interface for building management system (COM 2)
The building management system can be connected to the ABE using an external Bus interface allowing it to access the W-FM.
Activating the interface:
Select parameter Gateway BMS on and confirm with [Enter]. The interface in the display and operating unit (ABE) has been activated and the building management system can access the W-FM. The ABE remains func­tional.
Deactivating the interface:
Select parameter Gateway BMS off and confirm with [Enter]. The interface of the display and operating unit (ABE) for the building manage­ment system is deactivated. Only the ABE can access the W-FM.
Select Bus protocol:
Select Bus protocol in parameter Type of Gateway and confirm with [Enter].
eBus [ch.6.6.2]
Modbus [ch.6.6.3]
Data output [ch.6.6.4]
83054802 1/2018-07 La
73-228
Page 74
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.6.2 eBus

Param & Display AZL eBus Address
SendCycleBU
For Bus communication, the interface has to be activated and the bus protocol has to be defined.
eBus address
Parameter Address defines the eBus address, which is used to communicates with the W-FM.
Send cycle
Parameter SendCycleBU defines the time for the send cycle. The W-FM trans­mits its operating data to the eBus participants in the cycle set.

6.6.3 Modbus

Param & Display AZL Modbus
For Bus communication, the interface has to be activated and the bus protocol has to be defined.
The display and operating unit (ABE) operates as Slave in the Modbus protocol. The RTU-Modus is used for transfer.
Modbus address
Parameter Address determines the Modbus address of the display and operat­ing unit (ABE).
Baud rate
Parameter Baudrate determines the transfer speed. The Baud rate of the dis­play and operating unit (ABE) and the Modbus participant connected must be identical.
Parity
Parameter Parity determines the type of parity protocols. The parity of the dis­play and operating unit (ABE) and the Modbus participant connected must be identical.
Time out
Parameter Timout determines how long after Modbus communication fails the display and operating unit (ABE) switches from Remote to Local . If building management is deactivated or the Modbus connection fails, the internal load controller of the W-FM takes over the control and the internal setpoint (W1) is activated. Prerequisite is that the W-FM is equipped with an internal load controller and has been configured [ch.6.12].
83054802 1/2018-07 La
74-228
Page 75
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation
Local / Remote
Setting Function
local The operating modes for the load controller via Bus
ExtLC Bus or IntLC Bus have no influence
[ch.6.12.2]. The internal load controller takes over the control and the internal setpoint W1 is activated.
remote Setting for load control via Bus [ch.6.12.2].
If the operating mode ExtLC Bus has been selected, the building management system determines the load. If operating mode IntLC Bus has been selected, the building management system determines the setpoint.
If Modbus communication fails, the W-FM automatically changes into local mode. When communication is restored, the mode has to be set to remote either via the ABE or via Modbus signal.
Remote mode
Parameter Remote mode is read only, the setting is made via Modbus (building management system).
Setting Function
Auto Setpoint W3 is determined by the building management
system.
On Load is determined by the building management system. Off The internal load controller takes over the control.
External setpoint W3
Parameter W3 is read only, the setting is made via Modbus (building management system).

6.6.4 Trending data

Operation OptgModeSelect Type of Gateway Data output
In Bus protocol Data output the interface COM2 sends trending data for data recording. Interface configuration in menu Modbus is required for data output [ch.6.6.3].
Data recording is not possible for diagnostic purposes during servicing and without peripherals and software.
83054802 1/2018-07 La
75-228
Page 76
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.7 Manual / Automatic / Off

ManualOperation SetLoad
Autom/Manual/Off
or
Param & Display RatioControl Autom/Manual/Off
Operating mode
Parameter Autom/Manual/Off determines the operating mode. In Remote op­eration the parameter is read only and can not be altered [ch.6.6.3].
Setting Function
Automatic The burner starts if there is a heat demand at in-
putX5-03:1. The load controller determines the burner capacity.
Manuel The burner starts if there is a heat demand at input
X5-03:1. Parameter SetLoad determines the burner capacity.
Burner Off Burner drives to or remains in Standby (Phase12). A
message, that the W-FM is set to Burner Off in manual operation does not appear.
Target load
Load, to which the burner drives in Manuel operating mode. In modulating operation, the target load can be set within the load limits [ch.6.9.7]. In multi-stage operation, one of the stages can be selected as the target load.
83054802 1/2018-07 La
76-228
Page 77
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8 Burner Control

6.8.1 Times

Param & Display Burner Control Times TimesStartup1
TimesStartup2 TimesShutdown TimesGeneral
TimeStartup1
Time Parameters Function
Start release MinTimeStartRel Minimum residence time in phase21.
The W-FM remains at least the time set in phase21, even if the start criteria have already been met.
Fan run-up time FanRunupTime Residence time in phase22.
Once this time has elapsed the burner drives to pre­purge position.
Pre-purge PrepurgeTmeGas
PrepurgeTmeOil
PrepurgeSafeGas PrepurgeSafeOil
PrepurgePt1Gas PrepurgePt1Oil
PrepurgePt3Gas PrepurgePt3Oil
Pre-ignition Nozzle circulation
Oil pump ON time MinONTmeOilPump Residence time in phase36 (heavy oil operation only).
PreIgnitionTGas PreIgnitionTOil
Time from reaching the pre-purge position until driving to ignition position. The time is divided into the phases 30 to
34. The W-FM remains in phase 30 for the time set under PrepurgeTimeTl1… and then drives to phase 34 via phase 32. The rest of the time, the W-FM remains in phase34, or at least for the duration set under Pre- purgeTimeTl3… .
Pre-purge time after the following occurrences:
Lockout or safety shutdown Power failure Standby longer than 24h
For the duration of this time, auxiliary actuator 3 (FGR) re­mains in phase30 and the fuel actuators remain in standby position. The air determining actuators remain in pre-purge position.
Minimum duration in phase34. The air determining actu­ators and auxiliary actuator 3 (FGR) remain in pre-purge position. The fuel actuators remain in standby position.
Residence time in phase38. Once this time has elapsed, fuel is released for ignition. On heavy oil burners without return flow temperature sensor, nozzle circulation can be extended via Pre- IgnitionTOil .
In heavy oil operation, the time in phase36 can be exten­ded to allow oil pressure to build-up for ignition.
83054802 1/2018-07 La
77-228
Page 78
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation
TimeStartup2
Time Parameters Function
Flame stabilisation Interval1Gas
Interval1Oil
Residence time in phase44. Once this time has elapsed the burner drives to partial load.
Interval2Gas Interval2Oil
Residence time in phase52. Once this time has elapsed the burner drives to partial load.
Pressure switch reaction time
PressReacTime Time delay in phase40, 42 and 52.
The pressure switches are interrogated in phase 40, 42 and 52 by the time delay set. Prevents shutdown caused by pressure fluctuation when opening the fuel valves.
TimeShutdown
Time Parameters Function
Load shutdown MaxTmeLowFire Residence time in phase62.
If there is no longer a demand for heat, the W-FM re­duces the burner capacity and closes the fuel valves after the time set has elapsed. If partial load is reached before the time has elapsed, the fuel valves close immediately.
Anti siphon valve AfterburnTme Residence time in phase70.
Once the time has elapsed, the anti siphon valve at out­putX6-03 closes and the actuators for air and fuel drive to post-purge position.
Post-purge time PostpurgeT1Gas
PostpurgeT1Oil
Residence time in phase74. Post-purge time1 in phase74 is always executed. Once this time has elapsed, the auxiliary actuator 3 (FGR) drives to post-purge position.
Post-purgeT3Gas Post-purgeT3Oil
Residence time in phase78. Post-purge time3 in phase78 is interrupted at heat de­mand. Once the time has elapsed without heat demand, the W-FM goes to Standby.
PostpurgeT3long
(W-FM 200 only)
Additional residence time in phase78. The PostpurgeT3long is added to both fuel depend­ent times PostpurgeT3Gas / Oil .
Times in general
Time Parameters Function
Alarm delay during start preven­tion
AlarmDelay Time delay until a start prevention at heat demand is is-
sued at outputX3-01:2. The function Alarm during start prevention must be activated in parameter AlarmDelay.
Message start prevention DelayStartPrev Time delay until a start prevention at heat demand is
shown in the display of the ABE.
Post-purge time lockout PostpurgeLockout If lockout occurs, the fan motor at output X3-01:1 runs on
by the time specified.
Heavy oil immediate start MaxTmeStartRel Maximum waiting time for signal at inputX6-01:3.
83054802 1/2018-07 La
78-228
Page 79
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8.2 Signalling start prevention

Alarm at start prevention
Param & Display Burner Control Configuration ConfigGeneral AlarmStartPrev
If parameter AlarmStartPrev is activated, start prevention is also signalled at outputX3-01:2 [ch.3.4.1].
Start prevention in Standby
Param & Display Burner Control Configuration ConfigGeneral Standby Error
If parameter Standby error is activated, faults are also recognised as start prevention in Standby and are displayed in the ABE.

6.8.3 Normal or direct start

Param & Display Burner Control Configuration ConfigGeneral NormDirectStart
Start prevention at heat demand during shutdown in phase78.
Normal start
If NormalStart is activated, the fan switches off and the burner only starts after a home run in phase10.
Direct start
If DirectStart is activated the fan continues to run and the W-FM jumps via phase79 to phase24. In conjunction with an air pressure switch direct start is only possible with a release valve at outputX4-03 [ch.3.4.4]. In menu Config input /output the para­meter Start/PS-valve must therefore be set to PS Reli_Inv .
83054802 1/2018-07 La
79-228
Page 80
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8.4 Oil pump

Param & Display Burner Control Configuration ConfigGeneral OilPumpCoupling
IgnOilPumpStart
Control of oil pump and switch on point of pre-ignition in oil operation [ch.3.4.3].
Magnetic coupling / separate oil pump
For burners with magnetic coupling or separate oil pump:
Set parameter OilPumpCoupling to Magnetcoupl. Set parameter IgnOilPumpStart to On in Ph38 .
Direct coupling
For burners with oil pump coupled directly to the burner motor.
Set parameter OilPumpCoupling to Direct coupl . The long pre-ignition (on in Ph22) is automatically activated in parameter IgnOilPumpStart .

6.8.5 Forced intermittent

Param & Display Burner Control Configuration ConfigGeneral ForcedIntermit
With ForcedIntermit activated, the W-FM initiates a controlled shutdown with sub­sequent restart after 23h50min uninterrupted burner operation. If the burner is not suitable for continuous operation, forced intermittent has to be activated.

6.8.6 Pre-purge Gas

Param & Display Burner Control Configuration ConfigGeneral Skip PrepurgeGas
If the parameter is activated, the W-FM skips pre-purge in gas operation (Phase24 to34). According to EN 676 only allowed with Class A valves in conjunction with valve proving system.
Pre-purge is not skipped after:
Lockout 24 h Standby Power failure Safety shutdown due to low gas
83054802 1/2018-07 La
80-228
Page 81
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8.7 Continuous running fan

Param & Display Burner Control Configuration ConfigGeneral ContinuousPurge
If ContinuousPurge is activated, the fan runs in each operating phase. If an air pressure switch is fitted, continuous purge is only possible with a relief valve at outputX4-03 [ch.3.4.4]. For this, parameter Start/PS-valve must be set to PS Reli_Inv in menu Config Input /Output.
Setting Function
deactivated In phases00 to21, outputX3-01:1 (fan) is not activated.
In Phase00 to21, the frequency converter is controlled with the idle speed (HomePosVSD) set, even if the safety circuit / burner flange is open.
activated OutputX3-01:1 (fan) and the frequency converter are al-
ways activated, even if the safety circuit / burner flange are open.
off Sloop OutputX3-01:1 (fan) and the frequency converter are al-
ways activated, except if the safety circuit / burner flange are open.
deact/VSD-SL In phases00 to21, outputX3-01:1 (fan) is not activated.
In Phase00 to21, the frequency converter is controlled with the idle speed (HomePosVSD) set, except if the safety circuit / burner flange is open.

6.8.8 Additional air pressure switch

Param & Display Burner Control Configuration Config input/
output
The speed range set is monitored by an additional air pressure switch. In the OEM level, the additional air pressure switch is deactivated, the function is not used in standard applications.
Parameters Function
RotSpeed PS on The additional air pressure switch must supply an ON sig-
nal above the speed set.
RotSpeed PS off The additional air pressure switch must supply an OFF
signal below the speed set.
RotSpeed PS on RotSpeed PS off
83054802 1/2018-07 La
81-228
Page 82
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8.9 Configuring input X5-03

Param & Display Burner Control Configuration Config input/
output
Parameter Config X5-03 determines how the W-FM reacts to signals at in­putX5-03.
Load controller multi-stage operating mode
If a load controller is connected to inputX5-03 [ch.3.3.16], the parameter determ­ines the control of the operating stages.
Setting Input X5-03 Operating mode
Pin 2 Pin 3 two stage three stage
LMV2/3 inv
(Standard)
LMV5x std
(with KS40 load controller)
LMV2/3 std
(special applic­ation)
0 0 Stage 1 Stage 1 1 0 Stage 1 Stage 2 0 1 Stage 2 Stage 3 1 1 Stage 2 Stage 3 0 0 Stage 1 Stage 1 1 0 Stage 1 Stage 1 0 1 Stage 2 Stage 2 1 1 Stage 2 Stage 3 0 0 Stage 1 Stage 1 1 0 Stage 2 Stage 3 0 1 Stage 2 Stage 2 1 1 Stage 2 Stage 3
Config X5-03
Deactivate O2 trim / stop in phase 36
If function DeaO2/Stp36 is set in parameter Config X5-03 , inputX5-03 can be used to deactivate O2 trim or to trigger a stop function. For this setting, parameter LC_OptgMode must not be set to ExtLC X5-03 .
Input Function
Pin 2 (X5-03) Mains voltage input atX5-03:2 deactivates O2 trim and the
W-FM 200 operates to the compound curves. The function O2 alarm remains activated.
Pin 3 (X5-03) If no mains voltage is applied to inputX5-03:3, the burner stops
at the start in phase36. If the stop function is not used in con­junction with the O2 deactivation, fit a bridge at inputX5-03 between terminals3 and4.
Deactivate O2 trim via operating mode
If the function AutoDeactO2is set in parameter Config X5-03 and if mains voltage is applied to inputX5-03:2, the operating mode of the O2 controller changes from conAutoDeac to auto deact. The O2 controller is deactivated and the burner operates to the compound curves. The function O2 alarm remains activated. No message will be shown on the display. If voltage is no longer applied to inputX5-03:2, the operating mode changes back to conAutoDeac and O2 trim is reactivated [ch.6.10.1]. For this setting, parameter LC_OptgMode must not be set to ExtLC X5-03 .
83054802 1/2018-07 La
82-228
Page 83
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.8.10 Configuring output X4-03

Param & Display Burner Control Configuration Config input/
output
Parameter Start/PS valve determines if outputX4-03 is used for a start sig­nal or for pressure switch relief [ch.3.4.4].
Setting Function
Start signal OutputX4-03:3 is activated in phase21 to79. PS Relief OutputX4-03:3 is activated in phase79.
Function is not used.
PS Reli_Inv In phase21 and phase79 the relief valve at out-
putX4-03:3 is de-energised and the air pressure switch is tested.
Start/PS valve

6.8.11 Extraneous light

Param & Display Burner Control Configuration ConfigFlameDet ReacExtranLight
Parameter ReacExtranLight determines the reaction if extraneous light is present in Standby (Phase12).
Setting Function
Lockout Flame signal in phase12 triggers a lockout. Startblock A flame signal in phase 12 leads to start prevention.

6.8.12 Repetition counter

Param & Display Burner Control Configuration RepetitCounter
The parameters in menu RepetitCounter determine the number of safety shutdowns until shutdown with lockout is initiated. Changes in the repetition counter are only adapted after a reset or if the voltage supply has been interrupted.
Parameters Function
LossOfFlame Number of safety shutdowns due to missing flame signal.
Range: (1 … 2)
HeavyOil Number of safety shutdowns caused by return temperat-
ure sensor for nozzle circulation not being released [ch.3.3.10]. Range: (1 … 3 … 16(1)
StartRelease Number of start preventions with display messages nozzle
circulation [ch.3.3.10]. Range: (1 … 10 … 16(1)
SafetyLoop Number of safety shutdowns caused by the safety circuit
not being released [ch.3.3.2]. Range: (1 … 16(1)
(1
Repetition value 16 means not limited, no shutdown with lockout is initiated.
83054802 1/2018-07 La
83-228
Page 84
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9 Electronic compound

6.9.1 Actuator ramps

Param & Display RatioControl Times OperatRampMod
OperatRampStage Ramp
The ramps determine the speed of the actuators for a distance of 90°. The ramp times must not fall below the time of the slowest actuator, see actuator name plate.
Parameters Function
OperatRampMod Ramp time for modulating operation for phases60 and
62. In operating position, all actuators operate at this speed.
OperatRampStage Ramp time for multi-stage operation for phases60 and
62. In operating position, all actuators operate at this speed.
Ramp Ramp time outside the operating position for modulating
and multi-stage operation. All actuators operate at this speed in pre-purge, ignition, post-purge and standby po­sition.
Only in conjunction with frequency converter
The ramp time of the frequency converter must be less than the ramp time set in the W-FM (recommendation: 30%).

6.9.2 Shutdown behaviour

Param & Display RatioControl ShutdownBehav
Parameter ShutdownBehav determines the behaviour during lockout.
Setting Function
Unchanged The actuators remain in the position they were in at the
time of the lockout.
PostpurgeP If lockout occurs, the W-FM initiates a post-purge. HomePos If lockout occurs, the actuators drive to standby position.
83054802 1/2018-07 La
84-228
Page 85
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200

6.9.3 Operating behaviour of frequency converter

Only possible with W-FM 200.
Param & Display RatioControl GasSettings
OilSettings
Parameter VSD determines the operating behaviour of the frequency converter. The operating behaviour can be set individually for each fuel.
Setting Function
deactivated No frequency converter available.
The inputs and outputs for variable speed drive are not activated.
activated Only in conjunction with a frequency converter.
The inputs and outputs for variable speed drive are activ­ated.
air influen Only in conjunction with a frequency converter.
The inputs and outputs for variable speed drive are activ­ated and the frequency converter is included in O2 trim.
6 Operation
VSD
83054802 1/2018-07 La
85-228
Page 86
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9.4 SpecialPositions

Param & Display RatioControl GasSettings
OilSettings
If the burners is in operating position (phases60 and62), the actuators and the speed are driven by the compound curves. Outside of the operating position, the actuators and the speed are driven according to the SpecialPositions . In the special positions, the actuators can be set independently. Special positions are fuel specific and must be set separately for each fuel on dual fuel burners.
Setting Actuator
…PosGas: Gas butterfly valve …PosOil: Oil quantity regulator …PosAir: Air dampers …PosAux1: Adjustable mixing head …PosAux2: Auxiliary actuator for special applications (W-FM 200
only)
…PosAux3: Auxiliary actuator for special applications,
damper for flue gas recirculation (W-FM 200 only)
…PosVSD: VSD (only in conjunction with frequency converter,
W-FM 200)
SpecialPosi­tions
Home Pos PrepurgePos IgnitionPos PostpurgePos ProgramStop ResetIgnitPos
Standby positions
Parameter StandbyPos determines the positions for phases00 to22.
Pre-purge position
Parameter PrepurgePos determines the positions of the air influencing actuat­ors for pre-purge in phases30 to34. The exception is the auxiliary actuator3 (flue gas recirculation), which only drives to pre-purge position from phase 32.
Ignition position
Parameter IgnitionPos determines the positions for the ignition process in phases36 to54. Individual ignition positions can be deleted in parameter ResetIgnitPos . If a relevant ignition position is not defined, the W-FM initiates a start prevention at heat demand. Se installation and operating manual of burner for the ignition posi­tion.
83054802 1/2018-07 La
86-228
Page 87
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation
Post-purge position
Parameter PostpurgePos defines the positions for post-purge in phases74 to78. The exception is auxiliary actuator3 (flue gas recirculation), which only drives to the post-purge position after phase76. The speed PostpurgePosVSD must not be set below 10%.
Program stop
Using parameter ProgramStop, the program sequence can be stopped in defined phases. Parameter ProgramStop can also be called up in menu Param & Display/RatioControl.
Setting Function
deactivated No program stop 24 PrePurgP Stop in phase 24, pre-purge position 32 PrePFGR Stop in phase 32, auxiliary actuator3 in pre-purge position 36 IgnitPos Stop in phase 36, ignition position 44 Interv 1 Stop in phase 44, flame signal 52 Interv 2 Stop in phase 52, ignition pilot valve OFF 72 PostPPos Stop in phase 72, post-purge position 76 PostPFGR Stop in phase 76, auxiliary actuator3 in post-purge posi-
tion
83054802 1/2018-07 La
87-228
Page 88
Installation and operating instruction
Point|Load:15.0 |Fuel:10.0 Manual |Air :15.0 |Aux1: 0.0
2
1
0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
P1 P2 P3 P4 P5 P6 P7 P8 P9
2
1
4
5
6
7
3
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9.5 Creating load points, modulating operation

Param & Display RatioControl GasSettings
OilSettings
Depending on the load signal, the W-FM controls the actuators in compound in modulating operation. Each actuator has its own compound curve. The compound curves are formed from defined load points. 15load points can be defined for the compound curves, a minimum of 5load points are required. On dual fuel burners, the compound curves for each fuel can be set separately. In menu Point 1, load points can be adjusted or deleted to optimise combustion. In menu Manual 2 new load points are set.
During initial commissioning, set load points up to full load. Once full load has been regulated, optimise combustion in load point 1. Load point 1 must be within the ca­pacity graph and below below partial load. Now delete all load points between point 1 and full load. Starting at point 1, set new load points until full load is achieved. Optimise combustion in the current point before setting a new load point. To ensure an even speed characteristic curve, the speed of the new load points should not be altered. To ensure that control is possible across the entire load range in conjunction with O2 trim point 1 must be approx. 50% below partial load (point 2).
CurveParams Point
Man
83054802 1/2018-07 La
1 Burner capacity in % 2 Actuator position in degree of angle 3 Speed in % 4 Fuel Fuel 5 Air damper Air 6 Mixing head Aux1 7 Frequency converter VSD
88-228
Page 89
Installation and operating instruction
Point|Load:10.0 |Fuel:10.0 Manual |Air :15.0 |Aux1: 0.0
O2 XXXX
|Load:10.0 |Fuel:10.0 |Air :20.0 |Aux1: 0.0
Manual :10.0
O2 XXXX
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
Manual :15.0
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
O2 XXXX
Point
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
Manual
Point  :1
|Load:10.0 |Fuel:10.0 |Air :20.0 |Aux1: 0.0
O2 XXXX
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
O2 XXXX
Point  : 2
|Change |point? | |
Manual
Actuator positions With start Without start
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
O2 XXXX
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Save point->ENTER cancel->ESC
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Combustion manager W-FM 100 und W-FM 200
6 Operation
Setting new load points
Select Manual and confirm with [ENTER]. Increase burner rating using dial knob whilst observing combustion values (ex­cess air) and flame stability. Set load point using [ENTER] key if either:
the O2 content in the flue gas increases to above 7%,
the soot limit is reached,
the CO content increases,
the flame reaches the limit of stability.
The new load point is displayed in menu Point and can be adjusted.
Editing load points
Select Point and confirm with [ENTER]. Select load point using dial knob and confirm with [ENTER] key. Confirm query Change point? with [ENTER]. Confirm query With start with [ENTER]. The curve points can be changed and the actuators are synchronised. Select actuator using the dial knob and press [Enter]. Change values using the dial knob and confirm with [ENTER]. Once combustion has been optimised, exit point using [esc] and save with [Enter].
83054802 1/2018-07 La
89-228
Page 90
6 Operation
Point
|Load: 0.0 |Fuel:0.0 |Air :23.8 |Aux1: 5.0
Manual
Point  : 1
|Load:10.0 |Fuel:10.0 |Air :20.0 |Aux1: 0.0
O2 XXXX
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
O2 XXXX
Point  : 2
|Change |point? |delete? |
Manual
Point  : 2
|Load:24.3 |Fuel:22.1 |Air :32.9 |Aux1:27.6
O2 XXXX
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
Deleting load points
Select menu Point and confirm with [Enter]. Select load point using dial knob and confirm with [ENTER] key. Select Delete point? and confirm with [Enter]. Load point is deleted. Load points above this will be renumbered. The display shows the next higher load point in the current numbering. If the last load point was deleted, the actu­ator positions show XXXX .
83054802 1/2018-07 La
90-228
Page 91
Installation and operating instruction
Load [%] =
Throughput load point
Throughput full load
100
Point
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
Manual
Point  :1
|Load:10.0 |Fuel:10.0 |Air :20.0 |Aux1: 0.0
O2 XXXX
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :23.8 |Aux1: 5.0
O2 XXXX
Point  : 2
|Change |point? | |
Manual
Actuator positions With start Without start
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Point  : 2
|Load:29.3 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Point  : 2
|Load:29.3 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Save point->ENTER cancel->ESC
Point  : 2
|Load:15.0 |Fuel:14.4 |Air :28.5 |Aux1: 5.0
O2 XXXX
Combustion manager W-FM 100 und W-FM 200
6 Operation
Ratings apportionment
The load points are automatically assigned relative to the capacity. Incorrect load distribution can cause operating problems during the load control.
Assign capacity in % for load point using the following formula. Enter the calculated capacity for load point in Load.
Select Point and confirm with [ENTER]. Select load point using dial knob and confirm with [ENTER] key. Confirm query Change point? with [ENTER]. Confirm query With start with [ENTER]. Confirm line Load with [Enter]. Calculate actual load. Set load using dial knob and confirm with [Enter]. Exit point using [esc] and save with [ENTER].
83054802 1/2018-07 La
91-228
Page 92
Installation and operating instruction
2
1
5
3
4
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9.6 Operating and switch points, multi-stage operation

Param & Display RatioControl OilSettings CurveParams CurveSet
Two or three stage operation is specified depending on the burner execution. A three stage burner can also be operated two stage with low impact start or change-over release. The change-over behaviour between the operating stages is optimised via separate switch on and off points.
Operating stages
BS1, BS2, BS3
Switch-on points
ES2, ES3
Switch-off points
AS2, AS3
(1
BS3, ES3 and AS3 only with three stage operation
(1
(1
(1
Excess air for the relevant fuel quantity is set in the operating stages.
In the switch-on point, the air quantity for the change-over process into the next higher stage is set. If the switch-on point is exceeded, the solenoid valve of the next stage opens. If the switch-on point is activated directly the solenoid valve remains closed, only the air influencing actuators drive to the switch-on position and the flame stability can be checked prior to the change-over.
In the switch-off point, the air quantity for the change-over process into the next lower stage is set. If the switch-on point is not maintained, the solenoid valve of the previous stage closes. Switch-off points must not be activated directly, as the solenoid valve of the previous stage remains open and only the air influencing actuators drive to the switch off position. This leads to soot formation caused by insufficient air.
1 Air damper position 2 Operating stage 1 (BS1) 3 Switch-on point 2 (ES2), solenoid valve stage2 opens above 4 Operating stage 2 (BS2) 5 Switch-off point 2 (AS2), solenoid valve stage2 closes below
83054802 1/2018-07 La
92-228
Page 93
Installation and operating instruction
CurveSet
Actuator positions With start Without start
Point :AS2
|Air :30.0
O2 XXXX
|VSD : 100
Point :AS2
|Air :30.0
O2 XXXX
|VSD : 100
Point :AS2
|Air :25.0
O2 XXXX
|VSD : 100
Point :AS2
|Air :25.0
O2 XXXX
|VSD : 100
Save point->ENTER cancel->ESC
CurveSet
Point :BS1
|VSD : 100
|Air :20.0 | | |
O2 XXXX
Point :AS2
|VSD : 100
|Air :25.0 | | |
O2 XXXX
Combustion manager W-FM 100 und W-FM 200
6 Operation
Two options are available fort he setting of the operating and switch points. With start:
The actuator and frequency converter follow the current adjustment via dial knob. With this option, the operating stages and switch-on points are set during burner operation. In the operating stages, the combustion is optimised. In the switch-on points, the excess air for the change-over process to the next op­erating stage is determined. Excess air for the switch-on point is approx.7% O2 residual content. The switch-off points must not be activated during burner operation, as this leads to soot formation caused by insufficient air.
Without start: With this option, the operating stages and change-over points can be pre-set without the actuator and frequency converter following. Pre-setting values see in­stallation and operating manual of burner.
Setting operating and switch points
Select menu CurveSet and confirm with [Enter]. Choose appropriate option with the dial knob and confirm with [Enter].
With start: Optimise operating stages and switch-on points
Without start: Pre-set values and optimise switch-off points
Select operating stage or switch point using dial knob and confirm with [Enter]. Select Air actuator and confirm with [Enter]. The selection option VSD only appears in conjunction with a frequency con­verter. Use dial knob to change the value and confirm with [Enter]. Pre-setting values see installation and operating manual of burner. Exit entry using [esc] and save with [ENTER]. Exit level using the [esc] key.
83054802 1/2018-07 La
93-228
Page 94
Installation and operating instruction
0 % 100 %
P1
1
3
2
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9.7 Load range

LoadLimits
Param & Display RatioControl GasSettings
OilSettings
In modulating operation, the load limits restrict the load range within the compound curves programmed. On dual fuel burners, the load limits for each fuel can be set separately.
Minimum load: Parameter MinLoad_… limits the load range downward (partial load). Minimum load can not be set below load point1, in conjunction with O2 trim not below load point2.
Maximum load: Parameter MaxLoad_… limits the load range upwards (full load).
LoadLimits MinLoad_…
MaxLoad_…
1 Minimum load MinLoad_… 2 Maximum load MaxLoad_… 3 Load range
83054802 1/2018-07 La
94-228
Page 95
Installation and operating instruction
0 % 100 %
P1
1
3
2
Combustion manager W-FM 100 und W-FM 200
Fade-out partial range
Param & Display RatioControl GasSettings
OilSettings
Parameter Load Mask out can be used to fade out part of the load range, which could lead to operating problems due to site conditions. On dual fuel burn­ers, the partial range for each fuel can be set separately. The faded-out partial range can be driven through but not started directly. The burner drives from the bottom to the lower limit and passes through the partial range only when the load setpoint reached the upper limit. From the upper range, the burner remains at the upper limit and drives through the partial range only when the load setpoint has reached the lower limit.
Lower limit partial range: Parameter LoadMaskLowLimit determines the lower limit. The lower limit can not be set above the upper limit.
Upper limit partial range: Parameter LoadMaskHighLim determines the upper limit. The upper limit can not be set below the lower limit.
6 Operation
Load mask out LoadMaskLowLimit
LoadMaskHighLim
1 Lower limit partial range LoadMaskLowLimit 2 Upper limit partial range LoadMaskHighLim 3 Faded-out partial range
83054802 1/2018-07 La
95-228
Page 96
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.9.8 Load limit

Operation User Maxload User MaxLoadMod
User MaxLoad Stg
Parameters Function
User MaxLoadMod Load limit for modulating operation.
Further restricts full load within the load limits [ch.6.9.7].
User MaxLoadStg Load limit for multi-stage operation.
The burner drives only to the stage set.

6.9.9 Start point

Param & Display RatioControl GasSettings
OilSettings
Parameter StartPointOp determines the load point for partial load position in phase54. In phase54, the burner drives to the load point set, when the load point is reached, the W-FM changes over to phase60 and load control is released.
StartPointOp
83054802 1/2018-07 La
96-228
Page 97
Installation and operating instruction
0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
0102030405060708090100
2
1
3
4
5
6
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.10 O2 controller

O2 trim is only possible in modulating operation with W-FM 200 with O2 module. O2 trim is fuel specific and must be set separately for each fuel on dual fuel burn­ers.
O2 trim and O2 monitor in conjunction with the O2 residual content are at the com­bustion limit and the resulting O2 compound curve. An idealised minimum O2 value is advantages for the control behaviour. When op­timising the minimum O2 value increase rather than decrease. In conjunction with CO control (accessory) the minimum O2 value must be set to ap­prox.0.25to0.5percentage points below the combustion limit.
1 Burner capacity [%] 2 O2 content in the flue gas [%] 3 O2 residual content at the combustion limit 4 Minimum O2 value for O2 monitor 5 O2 setpoint for O2 trim 6 O2 compound, excess air in the load points 20to 25%
With frequency converter
On burners with frequency converter, parameter VSD can be used to determine if the frequency converter is to be included in O2 trim [ch.6.9.3].
Pre-control
The O2 controller is equipped with a pre-control function. The pre-control calcu­lates the air ratings reduction for the entire load range relative to the fuel on the basis of measured values during commissioning. If the load is changed, the air influ­encing actuators drive to the calculated position, whilst the fuel actuator drives to its load position. O2 trim is only activated if temperature or air pressure deviations occur and and then drives the air influencing actuators. To ensure the pre-control operates correctly, the load apportionment must match the fuel throughput in each load point [ch.6.9.5].
83054802 1/2018-07 La
97-228
Page 98
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation

6.10.1 O2 controller operating mode

Param & Display O2Ctrl/Limit GasSettings
OilSettings
or
Param & Display SystemConfig O2Ctrl/LimitGas
O2Ctrl/LimitOil
Using operating mode:
the O2 controller and O2-monitor can be activated or deactivated, the behaviour when a fault occurs can be defined.
The operating mode can be set separately for each fuel.
Deactivating manually (man deact)
Parameter man deact deactivates the O2 controller and O2 monitor and the burner operates to the compound curves. This parameter is only used to create the compound curve during commissioning, it is not suitable for normal operation.
O2 monitor only (O2 Alarm)
Parameter O2 Alarm only activates the O2 monitor. If the O2 sensor has not reached the operating temperature at burner start, a start
prevention is initiated. If the O2 monitor is triggered or if an O2 fault occurs, the W-FM initiates a controlled shutdown with single repetition, then lockout occurs.
Operating mode
O2 controller and O2 monitor (O2Control)
Parameter O2Control activates the O2 controller and O2 monitor. If the O2 sensor has not reached the operating temperature at burner start, a start
prevention is initiated. If the O2 monitor is triggered or if an O2 fault occurs, the W-FM initiates a controlled shutdown with single repetition, then lockout occurs.
Automatically deactivate control (conAutoDeac)
Parameter conAutoDeac activates the O2 controller and O2 monitor. The burner starts before the O2 sensor has reached operating temperature. O2 trim only starts once the operating temperature has been reached and the sensor test has been successfully carried out.
If the maximum O2 monitor is triggered or if an O2 fault occurs, the W-FM changes over to operating mode auto deact.
If the minimum O2 monitor is triggered the W-FM drives back to the compound curves. After a time of 3 times Tau the O2 content is tested again. The time con­stant Tau is determined automatically during standardisation [ch.6.10.4].
When the O2 content exceeds the minimum limit the W-FM releases O2 trim. If the O2 content drops below the minimum limit, the W-FM initiates a safety shutdown with repetition. The number of repetitions can be set in parameter NumMinUntilDeact , see [ch.6.10.2]. If the number of repetitions is ex­ceeded, the W-FM changes over to operating mode auto deact.
83054802 1/2018-07 La
98-228
Page 99
Installation and operating instruction Combustion manager W-FM 100 und W-FM 200
6 Operation
Automatic deactivation (auto deact)
Do not select this operating mode. Parameter auto deact is automatically activated when a fault occurs in operat­ing mode conAutoDeac . The O2 controller is deactivated and the burner oper­ates to the compound curves. A fault message appears in the display. If the operat­ing mode is changed over the fault message disappears [ch.6.10.23]. The O2 controller can also be deactivated via a signal at input X5-03:2 [ch.6.8.9].
83054802 1/2018-07 La
99-228
Page 100
Installation and operating instruction
Operating mode O2 trim O2 monitor Control parameters
O2 monitor O2 MaxValue NumMinUntilDeact
Point: 1 13.9% O2 MinValue :XXXX P-Air manual:
Point: 9 100% O2 MinValue :XXXX P-Air manual:
Point: 9 100% O2 MinValue :XXXX P-Air manual:
Point: 9 100% O2 MinValue :XXXX P-Air manual:
1
2
Combustion manager W-FM 100 und W-FM 200
6 Operation

6.10.2 O2 monitor

Param & Display O2Ctrl/Limit GasSettings
OilSettings
The W-FM monitors the O2 content in the flue gas using a sensor on the O2 mod­ule. The limit values for the O2 alarm are defined using parameters O2 MinValue and O2 MaxValue .
O2 minimum monitor
In parameter O2 Alarm , the setting under O2 MinValue stipulates the lower limit for the O2 monitor. If the O2 content in the flue gas drops below this lower limit for more than 3seconds, the W-FM reacts in accordance with the operating mode set [ch.6.10.1]. An O2 MinValue has to be defined as the lower limit in each load point. The O2 MinValue results from the O2 content in the flue gas at the combustion limit.
The O2 MinValue can be entered direct at each load point or can be determ­ined by reducing the air rating:
Select menu O2 Alarm and confirm with [Enter]. Select load point using dial knob and confirm with [ENTER] key. Select entry type1 or 2.
O2 Alarm O2 Alarm
O2 MaxValue NumMinUntilDeact
83054802 1/2018-07 La
1 Direct entry (O2 MinValue)
If the O2 min value for the load point is known, the value can be assigned dir­ectly.
2 Determine O2 min value (P-Air Manual)
The air rating is reduced manually in the load point, the O2 content is determ­ined and saved as O2 MinValue.
100-228
Loading...