Weishaupt WEM-RG1 Installation And Operating Instruction Manual

Page 1
Installation and operating instruction
Room device WEM-RG1
83310002 1/2017-11
Page 2
Installation and operating instruction Room device WEM-RG1
1 User instructions.............................................................................................................. 3
1.1  Target group.................................................................................................................. 3
1.2  Symbols.......................................................................................................................... 3
1.3  Guarantee and Liability............................................................................................... 4
2 Safety ..................................................................................................................................... 5
2.1  Designated application............................................................................................... 5
2.2  Safety measures........................................................................................................... 5
2.3  Disposal ......................................................................................................................... 5
3 Product description ........................................................................................................ 6
3.1  Type key ......................................................................................................................... 6
3.2  Technical data............................................................................................................... 7
4 Installation ........................................................................................................................... 8
5 Operation .......................................................................................................................... 10
5.1  Display and operating unit .......................................................................................10
5.2  Display..........................................................................................................................11
5.3  ManualOperation........................................................................................................12
5.4  Absence .......................................................................................................................12
5.5  Party mode ..................................................................................................................13
5.6  Automatic operation .................................................................................................. 13
5.7  Set room setpoint temperature............................................................................... 14
5.8  Service level ................................................................................................................ 15
6 Key word index .............................................................................................................. 17
7 Notes ................................................................................................................................... 18
83310002 1/2017-11 La
2-20
Page 3
Installation and operating instruction
Translation of original
operating instructions
Room device WEM-RG1

1 User instructions

1 User instructions
This manual forms part of the equipment and must be kept on site. Carefully read the manual prior to working on the unit. It is supplemented by the installation and operating instructions for the condensing
unit.

1.1 Target group

The manual is intended for the operator and qualified personnel. They should be observed by all personnel working with the unit.
Work on the unit must only be carried out by personnel who have the relevant train­ing and instruction.
In accordance with EN 60335-1 the following requirements apply
This appliance can be used by children 8 years and above as well as by persons with limited physical, sensory or mental capacities or lack of experience and know­ledge, provided they are supervised or have been instructed regarding the safe use of the appliance and understand the resulting danger. Children must not play with the appliance. Cleaning and operator maintenance must not be carried out by chil­dren without supervision.

1.2 Symbols

DANGER
WARNING
CAUTION
Range of values
Immediate danger with high risk. Non observance can lead to serious injury or death.
Danger with medium risk. Non observance can lead to environmental damage, serious injury or death.
Danger with low risk. Non observance can cause damage to the equip­ment and injury to personnel.
Important information
Requires direct action Result after an action Itemisation
83310002 1/2017-11 La
3-20
Page 4
1 User instructions
Installation and operating instruction Room device WEM-RG1

1.3 Guarantee and Liability

Guarantee and liability claims for personal and equipment damage are excluded, if they can be attributed to one or more of the following causes:
non approved application, non-observance of the manual, operation with faulty safety equipment, continual operation despite a fault, improper installation, commissioning, operation and service, repairs, which have been carried out incorrectly, the use of non original Weishaupt parts, force majeure, the installation of additional components, which have not been tested with the unit.
83310002 1/2017-11 La
4-20
Page 5
Installation and operating instruction Room device WEM-RG1

2 Safety

2 Safety

2.1 Designated application

The room device in conjunction with the Weishaupt Energy ManagementWEM is suitable for the operation of a heating circuit.
The unit should only be used in enclosed rooms. The installation location must comply with local regulations and must be frost-proof. Improper use could:
endanger the health and safety of the user or third parties, cause damage to the unit or other material assets.

2.2 Safety measures

Safety relevant fault conditions must be eliminated immediately.

2.3 Disposal

Dispose of all materials and components in a safe and environmentally friendly way at an authorised location. Observe local regulations.
83310002 1/2017-11 La
5-20
Page 6

3 Product description

Installation and operating instruction Room device WEM-RG1
3 Product description

3.1 Type key

WEM-RG1 …
WEM Type: Weishaupt Energy Management RG1 Type: Room device basic version … Version
83310002 1/2017-11 La
6-20
Page 7
Installation and operating instruction
80 mm
80 mm
Room device WEM-RG1
3 Product description

3.2 Technical data

3.2.1 Electrical data

Voltage supply DC 15 … 30 V Consumption max 0.7 W Type of protection IP 20

3.2.2 Ambient conditions

Temperature in operation 0... +50°C Temperature during transport / storage 0... +50°C relative humidity max 85%, no dew point

3.2.3 Dimensions

83310002 1/2017-11 La
7-20
Page 8

4 Installation

WEM-FA-G
H L – +
H L – +
2
1
1
2
DANGER
Installation and operating instruction Room device WEM-RG1
4 Installation
Risk of electric shock
Working on the device when voltage is applied can lead to electric shock.
Isolate the device from the power supply prior to starting any work. Safeguard against accidental restart.
The electrical connection must only be carried out by qualified electricians. Ob­serve local regulations.
If only 2 wires are available on site, the connection can be made using the adapter set WEM-CAN 2 wire (RF / RG1) (accessory).
Secure wall bracket1 to the wall using the screws supplied. Feed the wires2 through and connect the plug to the wiring diagram.
Insert the lugs1 of the room device into the recesses2. Click room device into place downwards.
83310002 1/2017-11 La
8-20
Page 9
Installation and operating instruction Room device WEM-RG1
Pull off protective foil.
4 Installation
83310002 1/2017-11 La
9-20
Page 10

5 Operation

2
3
5
1
4
Installation and operating instruction Room device WEM-RG1
5 Operation

5.1 Display and operating unit

Keys
1 Manual Operation [ch.5.3] 2 Absent [ch.5.4] 3 Party mode [ch.5.5] 4 Automatic operation [ch.5.6]
Dial knob
5 turn select or change values
press briefly: confirm or save values
approx. 3seconds: back to standard display / abort
83310002 1/2017-11 La
10-20
Page 11
Installation and operating instruction
1
2 3 4 5
6
7
9
8
Room device WEM-RG1

5.2 Display

1 Active mode (e.g. manual operation) 2 Summer setting activated (no heating operation) 3 Setback activated (reduced temperature level) 4 Normal operation activated (normal temperature level) 5 Comfort mode activated (increased temperature level) 6 Fault 7 Current room temperature (standard display); parameters and values 8 Setting mode activated 9 Service note
(1
(2
5 Operation
Faults
(1
If there is a fault in the system, a warning symbol appears in the display.
If an interlocking fault occurs, the warning symbol flashes, the system goes to lock­out.
Notify Weishaupt Customer Service or your heating contractor.
Service note
(2
If the service interval of the condensing boiler has been exceeded, an spanner
wrench appears in the display.
Notify Weishaupt Customer Service or your heating contractor.
83310002 1/2017-11 La
11-20
Page 12
5 Operation
Installation and operating instruction Room device WEM-RG1

5.3 ManualOperation

Permanent temperature level according to the operating mode set, independent of the time program.
The following operating modes are possible:
Summer operation Setback operation Normal operation Comfort mode
Press Manual operation . Symbols for the operating modes are displayed flashing. Select the desired operating mode using the knob. Room setpoint temperature of the operating mode is displayed (except in sum­mer operation). Confirm operating mode using the dial knob. The operating mode selected is active after approx. 3 seconds.
Example: Activate permanent setback operation.

5.4 Absence

The heating mode can be temporarily interrupted (maximum 23 hours). During the time set, setback operation is activated.
Press Absence . The hour display is displayed flashing. Set and confirm hours required using the dial knob. After approx. 3 seconds, setback operation is active for the time set.
Example: Activate absence (setback operation) for 8 hours.
Once the time set has elapsed, the operating mode previously set is active again.
Display the time remaining
Press Absence . The time remaining is displayed flashing.
The standard display re-appears after approx. 30seconds.
83310002 1/2017-11 La
12-20
Page 13
Installation and operating instruction Room device WEM-RG1
5 Operation

5.5 Party mode

The heating mode can be temporarily increased (maximum 23 hours). During the time set, comfort mode is activated.
Press Party mode . The hour display is displayed flashing. Set and confirm hours required using the dial knob. After approx. 3 seconds, comfort mode is active for the time set.
Example: Activate party mode (comfort mode) for 4 hours.
Once the time set has elapsed, the operating mode previously set is active again.
Display the time remaining
Press Party mode . The time remaining is displayed flashing.
The standard display re-appears after approx. 30seconds.

5.6 Automatic operation

Temperature level according to predetermined time program. The time programs can be interrogated and set using the display and operating unit
of the condensing boiler.
Press Automatic operation . Automatic operation is activate after approx. 3 seconds.
83310002 1/2017-11 La
13-20
Page 14
5 Operation
Installation and operating instruction Room device WEM-RG1

5.7 Set room setpoint temperature

Room setpoint temperature can be changed in each operating mode (except in summer operation).
Press dial knob. Display changes to the the setting of the room setpoint temperature. The room setpoint temperature set is displayed flashing. Set and confirm the required room temperature using the dial knob. Room setpoint temperature has been changed.
Example: Increase room setpoint temperature in normal operation from 21.0 °C to
22.5 °C.
Following a change, the room setpoint temperature at the respective temperature level is permanently changed.
83310002 1/2017-11 La
14-20
Page 15
Installation and operating instruction Room device WEM-RG1
5 Operation

5.8 Service level

5.8.1 Check assignment

The heating circuit to which the room device is assigned can be displayed with parameter 0F .
Press Manual operation and Automatic operation simultaneously for ap­prox.2seconds. The service level is activated. Press dial knob. The address of the heating circuit accessed is displayed.
The assignment can be changed using the display and operating unit of the con­densing boiler.
The standard display re-appears after approx. 30seconds.

5.8.2 Adjusting the room temperature

If no optimal placement of the room device is possible or a measurement error is to be compensated, the measured room temperature can be adjusted.
Setting range: -5.0 ... 5.0 K Factory setting: 0.0
Press Manual operation and Automatic operation simultaneously for ap­prox.2seconds. The service level is activated. Turn dial knob until parameter 1F is displayed. Press dial knob. Current room senor adjustment is displayed flashing. Set and confirm adjustment required using the dial knob. The value has been saved.
83310002 1/2017-11 La
The standard display re-appears after approx. 30seconds.
15-20
Page 16
5 Operation
Installation and operating instruction Room device WEM-RG1

5.8.3 Set brightness in setting mode

Adjust the brightness of the display in setting mode.
Setting range: 0 ... 30 Factory setting: 30
Press Manual operation and Automatic operation simultaneously for ap­prox.2seconds. The service level is activated. Turn dial knob until parameter 2F is displayed. Press dial knob. Current value of brightness is displayed flashing. Set and confirm value required using the dial knob. The value has been saved.
The standard display re-appears after approx. 30seconds.

5.8.4 Set brightness in standby mode

Adjust the brightness of the display in standby mode.
Setting range: 0 ... 30 Factory setting: 0
Press Manual operation and Automatic operation simultaneously for ap­prox.2seconds. The service level is activated. Turn dial knob until parameter 3F is displayed. Press dial knob. Current value of brightness is displayed flashing. Set and confirm value required using the dial knob. The value has been saved.
Setting range: 0 ... 30 Factory setting: 0
83310002 1/2017-11 La
The standard display re-appears after approx. 30seconds.
16-20
Page 17
Installation and operating instruction Room device WEM-RG1

6 Key word index

A
Absence................................................................................12
Access...................................................................................15
Adjustment ...........................................................................15
Ambient conditions............................................................... 7
Assignment...........................................................................15
Automatic operation ...........................................................13
B
Brightness ............................................................................16
C
Click into place...................................................................... 8
Consumption.......................................................................... 7
D
Dial knob ...............................................................................10
Display........................................................................... 10, 11
Disposal ..................................................................................5
E
Electrical connection............................................................ 8
Electrical data ........................................................................ 7
F
Faults .....................................................................................11
6 Key word index
P
Party mode ...........................................................................13
Protective foil ......................................................................... 9
R
Room sensor........................................................................15
Room setpoint temperature..............................................14
Room temperature..............................................................15
S
Safety measures.................................................................... 5
Service...................................................................................11
Service note .........................................................................11
Spanner wrench..................................................................11
Storage.................................................................................... 7
T
Temperature........................................................................... 7
Time remaining ............................................................ 12, 13
Transport................................................................................. 7
Type key .................................................................................. 6
Type of protection................................................................. 7
V
Version..................................................................................... 6
Voltage supply ....................................................................... 7
G
Guarantee............................................................................... 4
H
Humidity .................................................................................. 7
I
Illumination............................................................................16
Installation location ............................................................... 5
K
Key..........................................................................................10
L
Liability..................................................................................... 4
Light .......................................................................................16
Lockout..................................................................................11
M
Manual operation ................................................................12
Measurement error .............................................................15
O
Operating panel ..................................................................10
Operating unit......................................................................10
W
Wall bracket........................................................................... 8
Warning symbol ..................................................................11
Warning triangle..................................................................11
83310002 1/2017-11 La
17-20
Page 18

7 Notes

Installation and operating instruction Room device WEM-RG1
7 Notes
83310002 1/2017-11 La
18-20
Page 19
83310002 1/2017-11 La
Page 20
multiflam®Burners up to 23,000 kW
This innovative Weishaupt technology for medium and large burners provides minimum emission values at capacities up to 17 MW. The burners with the patented mixing head are available for oil, gas and dual fuel operation.
The complete program: Reliable technology and prompt, professional service
W Burners up to 570 kW
The compact burners, proven millions of times over, are economical and reliable. Available as gas, oil and dual fuel burners for domestic and commercial applications. The purflam
®
burner version with special mixing head gives almost soot-free combustion of oil with greatly reduced NOx emissions.
monarch®WM Burners and Industrial Burners up to 11,700 kW
These legendary industrial burners are durable and versatile. Numerous variations of oil, gas and dual fuel burners meet a wide range of applications and capacity requirements.
MCR Technology / Building Automation from Neuberger
From control panels to complete building management systems - at Weishaupt you can find the entire spectrum of modern control technology. Future orientated, economical and flexible.
Service
Weishaupt customers can be assured that specialist knowledge and tools are available whenever they are needed. Our service engineers are fully qualified and have extensive product knowledge, be it for burners, heat pumps, condensing boilers or solar collectors.
Max Weishaupt GmbH · 88475 Schwendi
Weishaupt close by? Addresses, telephone numbers etc. can be found at www.weishaupt.de
We reserve the right to make changes. All rights reserved.
Water heaters / energy storage tanks
This attractive program for domestic water heating includes classic water heaters, solar storage tanks, heat pump storage tanks and energy storage tanks.
Solar systems
The stylish flat-plate collectors are the ideal complement for any Weishaupt heating system. They are suitable for solar water heating and for combined heating support. With versions for on-roof, in-roof and flat roof installations, solar energy can be utilised on almost any roof.
Wall-hung condensing boilers for gas up to 240 kW
The wall-hung condensing boilers WTC-GW have been developed to meet the highest demands in ease of operation and efficiency. Modulating operation means these units operate quietly and economically.
Floor standing condensing boiler for oil and gas up to 1,200 kW
The floor-standing boilers WTC-GB and WTC-OB are efficient, low in emissions and versatile. Higher capacities are achieved by cascading up to four gas-fired condensing boilers.
Heat pumps up to 180 kW
The heat pump range offers solutions for the utilisation of heat from the air, the soil or ground water. Some systems are also suitable for cooling buildings.
Geothermal probe drilling
With its daughter company, BauGrund Süd, Weishaupt also offers geothermal probe and well drilling. With the experience of more than 10,000 systems and more than 2 million meters of drilling, BauGrund Süd offers a comprehensive service program.
WK Burners up to 32,000 kW
These industrial burners of modular construction are adaptable, robust and powerful. Even on the toughest industrial applications these oil, gas and dual fuel burners operate reliably.