Weil-McLain GV 3, GV 4 User Manual

GOLD
GV
Water Boiler — Series 3 & 4
Venting Supplement
Z-Vent II
Special gas vent system vent and combustion air supplement
Z-Flex®, Inc. Z-Vent II AL29-4C® Stainless Steel Special Gas Vent System may be used in new installations of GV-3 through GV-6 boilers.
Hazard definitions
The following defined terms are used throughout these Instructions to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage. Indicates presence of hazards that can cause severe personal injury, death or substantial property damage. Indicates presence of hazards that will or can cause minor personal injury or property damage. Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
To the installer:
This Venting Supplement must only be used by a qualified installer/service technician. Read these Instructions completely before beginning the installation. Failure to follow all instructions can cause severe personal injury, death or substantial property damage.
To install a new vent system follow instructions in:
This Venting Supplement.
GV Boilers Vent/Air Intake Termination Assembly Instructions, if using Weil-McLain Vent/Air Intake Termination Kit. — OR —
GV Water Boiler Series 3 & 4 Direct Vent Through-Roof or Through­Unused-Chimney Venting Supplement, if using Weil-McLain Through-Roof or Through-Unused-Chimney Termination Kit.
Z-Vent II manufacturer’s instructions supplied with vent material.
For installations above 5,500 feet use only direct vent (ducted combustion air) when sidewall venting. All of the vertical (through-roof or through­unused-chimney) methods in this Venting Supplement are acceptable and can result in severe personal injury, death or substantial property damage if ignored.
Part number 550-110-266/0601
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Combustion air supply
Special note
Refer to GV Boiler Manual for sizing free area of combustion/ventilation air openings. All boilers experience some condensation in section assembly during start-up. Unlike most conventional boilers, condensation is minimized in the GV Boiler by a built-in mixing system, maintaining boiler return water temperature above 130 0F, during steady state operation. Flue gas condensate is slightly acidic. In most cases pH level is not harmful to vents or drains. When combustion air is contaminated by vapors from products and areas, listed in Table 1 below, condensate acidic levels increase. Higher acidic levels attack many materials, including stainless steel commonly used in high efficiency systems. You may choose to use outside combustion air for any of the following reasons:
Installation is in an area containing contaminants listed in Table 1 below, which will induce acidic contamination.
You want to reduce infiltration into your home through openings around windows and doors.
T able 1 Corrosive contaminants
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
Permanent wave solutions Swimming pools
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and clean­ing solvents found in household laundry rooms
Remodeling areas
Garages with workshops
Adhesives used to fasten building products and other similar products
To prevent the potential of severe personal injury or death, check for areas and products listed above before installing boiler. If found:
remove products permanently — OR —
provide outside combustion air
2
Part number 550-110-266/0601
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Vent termination
Venting method definitions
Direct vent — Uses outside combustion air with
combustion air connector piping sealed at all joints and seams. Also known as “sealed combustion”.
Non-Direct vent — Uses inside combustion air with no
combustion air connector piping.
Properly locate vent termination
Follow instructions on this page when determining vent location to avoid possibility of severe personal injury, death or substantial property damage.
1. When using direct vent method — Refer to separate instructions packed with Weil-McLain direct vent termination kit and vent pipe manufacturer's instructions for additional locations.
2. For location of non-direct vent vertical termination, see vent pipe manufacturer's instructions.
3. Gases will form white plume in winter. Plume could obstruct window view.
4. Prevailing winds could cause freezing of condensate and water/ice buildup on building, plants or roof.
5. Locate or guard vent to prevent accidental contact by people or pets.
6. Do not terminate vent in window well, stairwell, alcove, courtyard, or other recessed areas.
7. Non-Direct vent installations only — Vent must
terminate more than 4 feet below or to side of all doors or windows.
8. Vent must terminate more than 1 foot above grade or anticipated snow line. In addition, vent termination must be at least 7 feet above public walkway and 3 feet above any forced air intake within 10 feet. Stay well away from trees, shrubs, and decorative items. Site conditions may dictate greater clearances. See Figure 1.
9. Vent must terminate at least 4 feet horizontally, and in no case above or below, unless a 4 foot horizontal distance is maintained, from electric meters, gas meters, regulators, relief valves, and other equipment.
10. Locate or guard vent to prevent condensate from damaging exterior finishes.
11. Do not extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.
12. Vent must terminate at least 6 feet away from adjacent walls.
13. Do not terminate vent closer than 5 feet below roof overhang.
14. Do not terminate vent above any door or window. Condensate can freeze, causing ice formations.
15. Do not use existing chimney as raceway if another appliance or fireplace is vented into or through chimney.
16. Do not connect:
Any other appliance to vent pipe.
Multiple boilers to a common vent pipe.
17. Do not wrap or insulate vent pipe and fittings.
18. Canadian installations — See B149.1 or B149.2 Installation Code.
19. A gas vent extending through an exterior wall shall not
terminate adjacent to the wall or below building extensions such as eaves, parapets, balconies or decks. Failure to comply could result in severe personal injury, death or substantial property damage.
Figure 1 Vent termination locations
3 feet
If within 10 feet
7 feet
Public Walkway
Part number 550-110-266/0601
Forced
air intake
26607
1 foot
1 ft
1 ft
1 ft
Snow
26608
3
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Installation
Pre-installation planning
1. Follow national, state, local or provincial codes or regulations when venting GV boiler.
2. Choose vent method from those shown on page 5.
3. Select vent run components from Table 2. Table 3 states maximum vent run lengths and number of elbows. Do not exceed data in Table 3. See Figure 2 for slightly reduced boiler output.
4. If installing with direct vent method, use same maximum run length and number of elbows from step 2. Vent and combustion air connector piping configurations must match. Use suitable 3" material for combustion air connector piping, such as:
Dryer vent
Galvanized steel
PVC (3" I.D.)
5. Refer to vent termination WARNING, item 19 on page 3.
T able 2 Parts list
Description
Z-Flex
®
, Inc.
Part Number (Note 1)
GV starter tee SVEVST03 GV termination coupling SVSTPX03
45o elbow
o
90
elbow
SVEEWC0345
SVEEWC0390
6" pipe SVEPWC03.5 1' pipe SVEPWC0301 2' pipe SVEPWC0302 3' pipe SVEPWC0303 4' pipe SVEPWC0304 5' pipe SVEPWC0305 Locking band SVSLBX03 Weil-McLain Vent/Air Intake Termination Kit 382-200-430 (Note 2) Weil-McLain Through-Roof or Through-Unused-Chimney Termination Kit 382-200-435 (Note 2)
Notes
®
1. Z-Flex
2. Weil-McLain part number. Parts available through Weil-McLain distributor.
, Inc. part number. Parts available through Z-Flex®, Inc.
T able 3
Vent and combustion air connector piping lengths and number of elbows
Maximum vent length (feet)
GV-3 thru GV-5 100 80 70 60 50 40 30 20 GV-6 80 60 50 40 30 20 10 --
Total number of elbows
0 2 3 4 5 6 7 8
4
Figure 2 Boiler output
100
99
98
97
% Output
96
95
020 40 60
Total equivalent length (feet) of vent
26700
(from boiler to vent termination)
GV-3
GV-4
GV-5
GV-6
80
Part number 550-110-266/0601
100
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Installation continued
For altitudes more than 5,500 feet above sea level — Do not use non-direct vent through sidewall methods as shown in Figures 4 and 6 below. Can cause severe personal injury, death or substantial property damage if ignored.
Select vent method
Figure 3 GV direct vent through sidewall
(using Weil-McLain Vent/Air Intake Termination Kit)
Slope vent pipe downward, toward boiler, minimum ¼” per foot.
Vent pipe
Slope
Air pipe
Z-Vent II vent starter tee
26601
Figure 5 GV direct vent (using Weil-McLain
Through-Roof or Through-Unused Chimney Termination Kit)
Figure 4 GV non-direct vent through sidewall (using Weil-
McLain Vent/Air Intake Termination Kit) (See WARNING above.)
Slope
Slope vent pipe downward, toward boiler, minimum ¼” per foot.
Z-Vent II vent starter tee
Figure 6 GV non-direct vent through sidewall (using termina-
tion coupling) (See WARNING
Figure 7 GV non-direct vent through roof (See WARNING
above.)
26602
above.)
Z-Vent II vent starter tee
Part number 550-110-266/0601
Slope vent pipe downward, toward boiler, minimum ¼” per foot.
26603
Z-Vent II vent starter tee
Slope vent pipe downward, toward boiler, minimum ¼” per foot.
26604
Z-Vent II vent starter tee
26605b
5
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Installation — assembly
Connect vent starter tee to boiler
Follow the instructions in the GV Boiler Manual to connect the vent starter tee to the boiler.
Construct vent and optional combustion air run
Follow vent pipe manufacturer's instructions for sealing the vent. Vent and combustion air connector piping must be sealed gas-tight to prevent possibility of flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
1. Follow Z-Vent II manufacturer's instructions to construct vent run and for methods of supporting vent runs.
Clean joints before sealing. See vent pipe manufacturer's instructions to clean joints.
Use their specified sealant (maximum 250 °F flue temperature). Do not use screws.
Do not mix types or manufacturers of vent materials.
Maintain minimum one-inch clearance from combustible materials to vent pipe; 0"
clearance for noncombustible materials.
Install vent pipe with seams on top of vent runs.
If needed, male end of vent pipe may be cut to provide correct length. See vent pipe
manufacturer's instructions for use.
2. If installing with direct vent through sidewall method, use instructions provided with Weil-McLain Vent/Air Intake Termination Kit. See Figure 3 on page 5.
Connect vent run to termination
V enting through sidewall
1. If using Weil-McLain Vent/Air Intake Termination Kit, see instructions provided in that kit. Applies to direct (Figure 3, page 5) or non-direct vent (Figure 4, page 5) method.
2. If using non-direct method with termination coupling only, see Figures 8 and 9.
If passing through noncombustible wall, provide hole diameter large enough to insert
the slip connector through. Sleeve and spacers are not required.
3. Maintain minimum one-inch clearance from combustible materials to vent pipe; 0" clearance for noncombustible materials.
4. Refer to vent termination WARNING, item 19 on page 3.
V enting through existing chimney or roof
1. Direct vent method — follow instructions supplied in Weil-McLain Through-Roof or Through-Unused-Chimney Termination Kit to assemble termination.
2. Non-Direct vent method (only through the roof, not through chimney):
Vent pipe must extend through roof flashing, jacket or thimble. See Figure 10.
Vent may pass through floor, inside wall or concealed space when installed according
to vent pipe manufacturer's instructions.
2. Maintain minimum one-inch clearance from combustible materials to vent pipe.
6
Part number 550-110-266/0601
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Installation — assembly continued
Figure 8 Sidewall termination installation (non-direct venting)
¼" to ¾" between stop on termination and metal plate
Spacers (2) (to support and center vent in sleeve)
Metal plate
Pipe section
Sealant
Termination coupling
Figure 9 Non-direct vent through sidewall
(using termination coupling) Follow Z-Vent II
manufacturer’s instructions for proper installation of vent runs, including slope and support.
4" galvanized sleeve (through 4 " hole for
combustible
Sealant
¹⁄₈
wall)
Pipe section
Metal plate
Spacers (2) (to support and center vent in sleeve)
26609
Figure 10 Non-direct vent through roof
Follow Z-Vent II manufacturer’s instructions for proper installation of vent runs, including slope and support.
Z-Vent II vent starter tee
Part number 550-110-266/0601
26604b
Z-Vent II vent starter tee
26605b
7
GOLD GV Series 3 & 4 — Z-Vent II Venting Supplement
Installation — assembly continued
Finish the vent installation
Installing condensate tubing
1. See Figure 11 to install condensate tubing (provided by others). Use condensate pump if floor drain is higher than condensate drain on boiler.
If required:
use a low-profile pump — OR —
set boiler on foundation (see GV Boiler
Manual) to allow gravity flow to discharge.
2. Size pump in gal/hr (boiler model):
0.78 (GV-3)
1.17 (GV-4)
1.56 (GV-5)
1.95 (GV-6) Refer to pump manufacturer's instructions. Drain
to a non-freezing area.
If vent pipe or combustion air pipe must be reassembled
When vent pipe or combustion air pipe is disconnected for any reason, it must be reassembled and resealed according to this Venting Supplement, the direct vent termination kit instructions and the vent pipe manufacturer's instructions.
Sealant recommended by vent pipe manufacturer must be used as indicated in their instructions. Vent and combustion air connector piping must be sealed gas-tight to prevent possibility of flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
Figure 11 Installation of condensate tubing
Z-Vent II vent starter tee
Vent
5/8" O.D. tubing,
26606
provided by others
8
Part number 550-110-266/0601
Loading...