•Consider piping and installation when
determining boiler location.
•Any claims for damage or shortage in shipment
must be filed immediately against the
transportation company by the consignee.
When calling or writing about the boiler— Please have the boiler model number from the
boiler rating label and the CP number from the boiler jacket. You may list the CP number in
the space provided on the Installation and service certificate found on page 33.
Failure to adhere to the guidelines on this page can result in severe personal injury, death
or substantial property damage.
When servicing boiler —
•To avoid electric shock, disconnect electrical
supply before performing maintenance.
•To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation —
•Do not block flow of combustion or ventilation
air to boiler.
•Should overheating occur or gas supply fail to shut
off, do not turn off or disconnect electrical supply
to circulator. Instead, shut off the gas supply at a
location external to the appliance.
•Do not use this boiler if any part has been under
water. Immediately call a qualified service
technician to inspect the boiler and to replace any
part of the control system and any gas control that
has been under water.
Follow all instructions in
User
•This manual is for use only by your qualified
heating installer/service technician.
•Please refer to the User’s Information Manual for
your reference.
•We recommend regular service by a qualified
service technician, at least annually
and/or property may result.
•Continual fresh makeup water will reduce boiler
life. Mineral buildup in sections reduces heat
transfer, overheats cast iron, and causes section
failure. Addition of oxygen and other gases can
cause internal corrosion. Leaks in boiler or piping
must be repaired at once to prevent makeup water.
•Do not add cold water to hot boiler. Thermal
shock can cause sections to crack.
Glycol — potential fire hazard —
All glycol is flammable when exposed to high
temperatures. If glycol is allowed to accumulate in or
around the boiler or any other potential ignition
source, a fire can develop. In order to prevent potential
severe personal injury, death or substantial property
damage from fire and/or structural damage:
.
Boiler water —
•Do not use petroleum-based cleaning or sealing
compounds in boiler system. Water seal
deterioration will occur, causing leakage between
sections. This can result in substantial property
damage.
•Do not use "homemade cures" or "boiler patent
medicines". Serious damage to boiler, personnel
Part Number 550-110-593/10995
•Never store glycol of any kind near the boiler or
any potential ignition source.
•Monitor and inspect the system and boiler
regularly for leakage. Repair any leaks immediately
to prevent possible accumulation of glycol.
•Never use automotive antifreeze or ethylene glycol
in the system. Using these glycols can lead to
hazardous leakage of glycol in the boiler system.
Page 3
Page 4
GOLD CGa Gas-Fired Water Boiler
How it works . . .
①
②
③
Control module
The control module (used on spark-ignited pilot boilers) responds to signals from the room thermostat and
boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and vent damper. When room thermostat
calls for heat, the control module starts the system circulator and activates the vent damper (causing it to drive
open).
When the vent damper has opened completely, the control module opens the pilot valve and activates pilot ignition
spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within 15 seconds, the
control module will turn off the gas valve, flash the Flame light, and immediately start a new cycle. This will
continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven, the control
module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve and deactivates the vent damper
(causing it to close).
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs,
the control module flashes combinations of lights to indicate the most likely reason for the problem. See page 52
for details.
Standing pilot boilers (controls not shown) use the pilot thermocouple to prove flame. If the thermocouple is
satisfied, the gas valve and vent damper will open on a call for heat and close afterwards.
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Draft hood
The draft hood provides a minimum draft for the boiler, assuring adequate air for combustion if installed in
accordance with manual and not modified in any way.
④
⑤
⑦
Spill switch
The spill switch will shut down the boiler (requiring manual reset of the switch reset button) if the vent system
becomes blocked.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting.
(The circulator will continue to run as long as there is a call for heat.)
Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and
can be mounted on either the boiler supply or return piping. The factory-installed circulator wiring harness
provides ample length for either location. NOTE — The control module provides a pump exercising routine. If the
boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
Vent damper
The vent damper closes during off cycles to reduce heat loss from the house up the vent.
Other boiler components:
a supply to system
b return from system
c flue outlet
d burner manifold
e gas valve
fpressure/temperature gauge
g relief valve
h air vent connection
iflame rollout switch
jburner orifice
k pilot burner, typical
lstainless steel burners
m cast iron boiler sections
n flue collector
o junction box
2Part Number 550-110-593/1099
Page 5
GOLD CGa Gas-Fired Water Boiler
Contents
Standing pilotSpark-ignited pilot
How it works2–3
Hazard definitions4
Please read before proceeding5
1. Prepare boiler location6–11
2. Prepare boiler12–15
3. Water piping16–25
4. Gas piping26
5. Field wiring27
6. Start-up28–32
7. Check-out procedure33
8. Operation — standing pilot boilers
9. Operation — spark-ignited pilot boilers37–43
10. Service and maintenance44–49
11. Troubleshooting
12. Replacement parts60–65
13. Dimensions and ratings66–67
34–36
49–50, 5149–50, 51–59
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of
various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial
property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial
property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but
not related to personal injury or property damage.
4Part Number 550-110-593/1099
Page 6
GOLD CGa Gas-Fired Water Boiler
1a
Prepare boiler location —
codes & checklist
Installations must follow these codes:
•Local, state, provincial, and national codes, laws,
regulations and ordinances.
•National Fuel Gas Code, ANSI Z223.1–latest edition.
•Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1,
when required.
•National Electrical Code.
•For Canada only: B149.1 or B149.2 Installation
Code, CSA C22.1 Canadian Electrical Code Part 1
and any local codes.
Before locating the boiler, check the following:
•Check for nearby connection to:
•System water piping
•Venting connections
•Gas supply piping
•Electrical power
•Check area around boiler. Remove any combustible
materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible
materials, gasoline and other flammable liquids and
vapors can result in severe personal injury, death or
substantial property damage.
•Boiler must be installed so that gas control system
components are protected from dripping or
spraying water or rain during operation or service.
•If new boiler will replace existing boiler, check for
and correct system problems, such as:
1. System leaks causing oxygen corrosion or
section cracks from hard water deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing
system and boiler to freeze and leak.
Figure 1
Minimum clearances
(see page 7)
7
6
3
Top view
6Part Number 550-110-593/1099
2
Fresh air
opening
59305
6
35
7
6
Side elevation
Page 7
Boiler Manual
Prepare boiler location — clearances1b
Service clearances
1. Provide the following clearances for cleaning and
servicing the boiler and for access to controls and
components:
Clearance from:Minimum
Top
(for cleaning flueways)
Front
(for access to controls and components)
Back 7"
Left side
Right side 7"
(for cleaning and servicing)
35"
18"
24"
2. Provide at least screwdriver clearance to jacket front
panel screws for removal of front panel for
inspection and minor service. If unable to provide
at least screwdriver clearance, install unions and
shutoff valves in system so boiler can be moved for
servicing.
Small space installations
1. Provide the following clearances to combustible
material for small space installations.
(See Figure 1, page 6):
Clearance from combustible
materials (closet installations):
Top
(for cleaning flueways)
Front
(provide means of access)
Back 7"
Left side
Right side 2"
(provide means of access)
Minimum
35"
3"
6"
Flooring and foundation
Flooring
The CGa boiler is approved for installation on
combustible flooring, but must never be installed on
carpeting.
Do not install boiler on carpeting
even if foundation is used. Fire can
result, causing severe personal
injury, death or substantial property
damage.
Foundation
1. Provide a solid brick or minimum 2-inch thick
concrete foundation pad if any of the following is
true:
Take the following special precautions when installing
Hot water pipes must be at least ¹⁄₂" from
2.
combustible material.
the boiler in a residential garage. If the boiler is located
in a residential garage, per ANSI Z223.1, paragraph
5.1.9:
3. Single-wall vent pipe must be at least 6 inches
from combustible material.
•Mount the boiler a minimum of
the floor
of the garage to assure the burner and
18 inches above
ignition devices will be no less than 18 inches above
4. Type B double-wall metal vent pipe — refer to
vent manufacturer’s recommendation for clearances
to combustible material.
Part Number 550-110-593/10997
the floor.
•Locate or protect the boiler so it cannot be
damaged by a moving vehicle.
Page 8
GOLD CGa Gas-Fired Water Boiler
Prepare boiler location — vent system1c
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe
personal injury or death.
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause
severe personal injury or death.
Do not alter boiler draft hood or place any obstruction or non-approved vent damper in breeching or vent system.
CSA certification will become void. Flue gas spillage and carbon monoxide emissions will occur causing severe
personal injury or death.
When removing boiler from
existing common vent system:
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining
connected to the common venting system are not in
operation.
a.
Seal any unused openings in the common venting
system.
Visually inspect the venting system for proper
b.
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion or other
deficiencies which could cause an unsafe condition.
c. Test vent system — Insofar as is practical, close all
building doors and windows and all doors between
the space in which the appliances remaining
connected to the common venting system are
located and other spaces of the building. Turn on
clothes dryers and any appliance not connected to
the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace
dampers.
d.
Place in operation the appliance being inspected.
Follow the lighting/operating instructions. Adjust
thermostat so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame
of a match or candle.
f. After it has been determined that
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers,
and any other gas-burning appliance to their
previous conditions of use.
Any improper operation of common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1-latest edition.
Correct by resizing to approach the minimum size as
determined using the appropriate tables in Part 11 of
that code. Canadian installations must comply with
B149.1 or B149.2 Installation Code.
each appliance
Chimney or vent requirements
1. Venting must be installed according to Part 7,
Venting of Equipment, of National Fuel Gas Code,
ANSI Z223.1-latest edition and applicable building
codes. Canadian installations must comply with
B149.1 or B149.2 Installation Codes.
2. See Ratings table on page 67 for minimum chimney
or vent sizes. A chimney or vent
should extend at least 3 feet above the highest
cap
where it passes through a roof of a building
point
and at least 2 feet higher than any portion of a
building within a horizontal distance of 10 feet
A chimney or vent must not extend less than the
distances stated above.
3. A lined chimney is preferred and must be used when
required by local, state, provincial and national
codes, laws, regulations and ordinances. Vitreous tile
linings with joints that prevent retention of moisture
and linings made of noncorrosive materials are best.
Advice for flue connections and chimney linings can
be obtained from local gas utility.
wall metal vent pipe or single-wall vent pipe may
be used as a liner.
4. Cold masonry chimneys, also known as outside
chimneys, typically have one or more walls exposed
to outside air. When any atmospheric gas-fired
boiler with automatic vent damper is vented
through this type of chimney, the potential exists
for condensation to occur. Condensation can
damage a masonry chimney. Weil-McLain
recommends the following to prevent possible
damage.
a. Line chimney with corrosion-resistant metal
liner such as AL29-4C® single-wall stainless steel
or B-vent. Size liner per National Fuel Gas Code
ANSI Z223.1-latest edition.
b. Provide drain trap to remove any condensate.
5. Where two or more gas appliances vent into a
common chimney or vent, equivalent area should
at least equal to area of vent outlet on largest
be
appliance plus 50 percent of vent outlet area on
additional appliance.
without a listed
Type B double-
.
8Part Number 550-110-593/1099
Page 9
Boiler Manual
1d
Prepare boiler location — air contamination
Please review the following information on potential
combustion air contamination problems.
To prevent potential of severe personal injury or death, check for products or areas listed below
before installing boiler. If any of these contaminants are found:
•remove contaminants permanently
— OR —
•isolate boiler and provide outside combustion air. See national, provincial or local codes
for further information.
Table 1Corrosive contaminants and likely locations
Products to avoidAreas likely to have contaminants
Spray cans containing chloro/fluorocarbonsDry cleaning/laundry areas and establishments
Chlorine-based swimming pool chemicalsBeauty shops
Calcium chloride used for thawingRefrigeration repair shops
Sodium chloride used for water softeningPhoto processing plants
Refrigerant leaksAuto body shops
Paint or varnish removersPlastic manufacturing plants
Hydrochloric acid/muriatic acidFurniture refinishing areas and establishments
Cements and gluesNew building construction
Antistatic fabric softeners used in clothes dryersRemodeling areas
Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and
other similar products
Part Number 550-110-593/10999
Page 10
GOLD CGa Gas-Fired Water Boiler
MODEL
CGi
Prepare boiler location — air openings1c
Combustion air and ventilation openings must comply
with Section 5.3, Air for Combustion and Ventilation,
of National Fuel Gas Code ANSI Z223.1-latest edition,
or applicable local building codes. Canadian
installations must comply with B149.1 or B149.2
Installation Codes.
Provide adequate combustion and
ventilation air to assure proper
combustion and reduce the risk of
severe personal injury, death or
substantial property damage caused
by flue gas spillage and carbon
monoxide emissions.
Air from inside building
(boiler in interior room - Figure 2)
1. Tightly constructed buildings must be provided with
openings to outside for combustion and ventilation
air. These openings must be sized to handle all fuel
burning appliances, exhaust or ventilation fans and
fireplaces.
2. When openings to boiler room are taken to interior
spaces, provide two permanent openings:
•One air opening within 12 inches of floor.
•A second opening within 12 inches of ceiling.
Air directly from outside toboiler room
1. Tightly constructed buildings must be provided with
combustion and ventilation air openings to boiler
room, which are adequate to handle the boiler needs
plus the needs of all other fuel burning appliances,
exhaust or ventilation fans and fireplaces.
2. When combustion air is supplied to the boiler space
directly through outside walls (Figure 3): Provide
two permanent openings:
•One air opening within 12 inches of floor.
•A second opening within 12 inches of ceiling.
Each opening must provide a minimum free area
of
1 square inch per 4,000 Btuh of input of all
appliances in room plus requirements for any
exhaust fans in room.
Each opening must provide a minimum free area
1 square inch per 1,000 Btuh of input of all
of
appliances in room plus requirements for any
exhaust fans in room. The interior space supplying
combustion and ventilation air must have adequate
infiltration from outside.
MODEL
CGi
10Part Number 550-110-593/1099
Page 11
Boiler Manual
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction
where:
a. Walls and ceilings exposed to the outside
atmosphere have a continuous water vapor retarder
with a rating of 1 perm or less with openings
gasketed, and . . .
b. Weather-stripping has been added on openable
windows and doors, and . . .
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between
sole plates and floors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing,
electrical, and gas lines, and in other openings.
Other
appliances
CGa
boiler
0 to 12"
For buildings with such construction, provide air
openings into the building from outside, sized per the
appropriate case in
Figure 3 if appliances are to use
inside air for combustion and ventilation.
Air
opening
Air
0 to 12"
Part Number 550-110-593/109911
opening
Page 12
GOLD CGa Gas-Fired Water Boiler
2a
Prepare boiler — placement and setup
Place boiler/crate near position
1. Leave boiler in crate and on pallet until installation
site is ready.
2. Move entire crate and pallet next to selected
location.
3. Remove crate.
4. Remove boiler from pallet as follows:
a. Tilt left side of boiler up and place a board
under left legs.
b. Tilt boiler the other way and place a board
under right legs.
c. Slide boiler backwards off pallet and into
position.
5. Check level.
a. Shim legs, if necessary.
b. Do not alter legs.
Leave boiler on pallet.
Do not drop boiler or bump jacket
on floor or pallet. Damage to boiler
can result.
Inspect orifices and burners
1. Remove front jacket door. Remove base access panel
(See Figure 32, item 4, page 62).
2. Check for correctly-sized manifold orifices. See
below for sizing. (The orifice size is stamped on
2
the orifice spud barrel.)
Correctly-sized manifold orifices
must be used. Failure to do so will
result in severe personal injury,
death or substantial property
damage.
3. Level and straighten burners.
Burners must be properly seated in
slots in burner rest with their
openings face up. Main burner
orifices must inject down center of
Table
4. Reinstall access panel.
Orifice replacement procedure
(when required)
1. Remove access panel.
2. On gas manifold, mark location of main burner with
attached pilot assembly.
3. Remove main burner with attached pilot assembly
from manifold. Remove all remaining burners.
4. Remove and discard all main burner orifices in gas
manifold.
5. Apply a small amount of pipe dope to each of the
new orifices and install in the manifold. Make sure
the orifices are aligned correctly, not cross-threaded
in the manifold tappings.
6. Reinstall main burner with attached pilot assembly
at location marked on gas manifold. Reinstall all
remaining burners.
burner. Failure to properly seat
burners will result in severe personal
injury, death or substantial property
damage.
Do not operate boiler without access
panel secured in place. Failure to
comply could cause momentary
flame rollout on ignition of main
flame, resulting in possible fire or
personal injury hazard.
Use only pipe dope compatible with
propane gas, even if boiler is to be
operated on natural gas. Failure to
comply could result in severe
personal injury, death or substantial
property damage.
Table 2 Manifold orifice sizing
LocationNatural gasPropane gas
U. S.
Canada
Note 1:
12Part Number 550-110-593/1099
For elevations above 2,000 feet, contact your local Weil-McLain sales office for details.
0-2,000 ftover 2,000 ft0-2,000 ftover 2,000 ft
2.00 mm(Note 1)1.30 mm(Note 1)
0-2,000 ft2,000-4,5000-2,000 ft2,000-4,500
2.00 mm1.90 mm1.30 mm1.20 mm
Page 13
Boiler Manual
2b
Prepare boiler — pressure test
Perform hydrostatic pressure test
Pressure test boiler before attaching water or gas piping
or electrical supply (except as noted below).
Prepare boiler for test
1. Remove the shipping nipple (from CGa supply
tapping) and remove the boiler relief valve.
Temporarily plug the relief valve tapping with a ¾"
NPT pipe plug.
2. Remove 1¼" nipple, reducing tee and drain valve
from accessory bag. Install in boiler return
connection as shown on page 3 or in Figure 34, item
3, page 64. Install circulator on either the return or
supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/
temperature gauge from accessory bag. Pipe to boiler
supply connection as shown in
(Use pipe dope sparingly.)
4. Connect a hose to boiler drain valve, the other end
connected to a fresh water supply. Make sure hose
can also be used to drain boiler after test.
5. Connect a nipple and shutoff valve to system supply
connection on the 1¼" tee. This valve will be used
to bleed air during the fill. (Valve and nipple are not
included with boiler.)
Figure 34, page 64.
3. When water flows from shutoff valves, close boiler
drain valve.
4. Close shutoff valves.
5. Slowly reopen boiler drain valve until test pressure
of not more than 45 psi is reached on the pressure/
temperature gauge.
6. Test at no more than 45 psi for no more than 10
minutes.
Do not leave boiler unattended. A
cold water fill could expand and
cause excessive pressure, resulting in
severe personal injury, death or
substantial property damage.
7. Make sure constant gauge pressure has been
maintained throughout test. Check for leaks. Repair
if found.
Leaks must be repaired at once.
Failure to do so can damage boiler,
resulting in substantial property
damage.
Do not use petroleum-based
cleaning or sealing compounds in
boiler system. Severe damage to
boiler will occur, resulting in
substantial property damage.
6. Connect a nipple and shutoff valve to system return
connection (at circulator flange if circulator installed
on return). This valve will be used to bleed air during
the fill. (Valve and nipple are not included with
boiler.)
Fill and pressure test
1. Open the shutoff valves you installed on supply and
return connections.
2. Slowly open boiler drain valve and fresh water
supply to fill boiler with water.
Part Number 550-110-593/109913
Drain and remove fittings
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever
provides best access to drain. Remove hose after
draining if used to drain boiler.
3. Remove nipples and valves unless they will remain
for use in the system piping.
4. Remove plug from relief valve tapping. See Section 3
to replace relief valve.
Page 14
GOLD CGa Gas-Fired Water Boiler
14Part Number 550-110-593/1099
Page 15
Boiler Manual
Prepare boiler — vent damper installation
These systems are used on gas-fired boilers with vent dampers as shipped from factory. Boiler will not operate
without vent damper installed.
Only vent dampers listed in the Replacement parts list on page 61 are certified for use with CGa boilers. Any
other vent damper installed could cause severe personal injury or death.
Damper blade
Standing pilot ignition systems— Refer to vent
manufacturer’s instructions to install plug (shipped with
damper) in damper hole. For standing pilot boilers only,
install plug with
hole.
Spark-ignited pilot systems— Refer to vent
manufacturer’s instructions to install plug (shipped with
damper) in damper hole. For spark-ignited pilot boilers only,
install plug with no hole in veper
3
/
" diameter hole in vent damper
8
4. Read and apply the harness plug warning label
(shown above) so that it is visible after installation.
5. Plug damper harness receptacle into damper harness
Figure 8 Vent damper assemblies
plug.
Bypassing (jumpering) vent damper
will cause flue products such as
carbon monoxide to escape into the
house. This will cause severe
personal injury or death.
After boiler has operated once, if
either end of harness is
disconnected, the system safety
shutdown will occur. The boiler will
not operate until harness is
reconnected.
Effikal damper — Damper hold
open switch must be in Automatic
Operation position for system to
operate properly.
Part Number 550-110-593/109915
Page 16
GOLD CGa Gas-Fired Water Boiler
Water piping — general information3a
General piping information
If installation is to comply with ASME or Canadian requirements, an
additional high temperature limit is needed. Install control in supply piping
between boiler and isolation valve. Set second control to minimum 20 °F
above setpoint of first control. Maximum allowable setpoint is 240 °F. See
page 34 or 38, for wiring.
A low water cutoff device is required when boiler is installed above
radiation level or by certain state or local codes or insurance companies.
Use low water cutoff designed for water installations. Electrode probe-type
is recommended. Purchase and install in tee in supply piping above boiler.
backflow check valve in cold water supply as required by local codes.
Use
Pressure/temperature gauge
Install pressure/temperature gauge in tee on supply piping (as shown in
drawing on page 3). The gauge well is a self-closing valve, allowing removal
of the gauge without draining the system.
Relief valve
Install relief valve vertically in ¾" tapping on side of boiler. See Figure 9 or
and the tag attached to the relief valve for manufacturer’s instructions.
10
To avoid water damage or scalding due to relief valve
operation:
•Discharge line must be connected to relief valve outlet and run to a
safe place of disposal
possibility of severe burns should the valve discharge.
•Discharge line must be as short as possible and be the
the valve discharge connection
•Discharge line must pitch downward from the valve and terminate
at least 6" above the floor drain where any discharge will be clearly
visible.
•The discharge line shall terminate plain, not threaded, with a
material serviceable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
•
•No shutoff valve shall be installed between the relief valve and boiler,
or in the discharge line. Do not plug or place any obstruction in the
discharge line.
•Failure to comply with the above guidelines could result in failure of
the relief valve to operate, resulting in possibility of severe personal
injury, death or substantial property damage.
•Test the operation of the valve after filling and pressurizing system
by lifting the lever. Make sure the valve discharges freely. If the valve
fails to operate correctly, replace it with a new relief valve.
. Terminate the discharge line to eliminate
same size as
throughout its entire length.
System water piping
See Figure 9 (diaphragm-type or bladder-type
expansion tank) or
tank) on page 21, and Table 3 below, for near-boiler and
single-zone systems designed for return water at least
130 °F.
See pages 18-19 to complete multiple-zone piping or
pages 20-25 to complete piping for radiant heating
systems or converted gravity systems.
Refer to page 25 for boilers used with refrigeration systems.
Note: Circulator flange supplied with boiler is same size as
recommended piping above.
•Chilled medium, if used, is piped in parallel with
heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. Consult
I=B=R Installation and Piping Guides.
•If boiler is connected to heating coils located in air
handling units where they can be exposed to
refrigerated air, use flow control valves or other
automatic means to prevent gravity circulation
during cooling cycle. Circulation of cold water
through the boiler could result in damage to the heat
exchanger, causing possible severe personal injury,
death or substantial property damage.
Figure 10 (closed-type expansion
system
From
system
Install boiler such that —
16Part Number 550-110-593/1099
Page 17
Boiler Manual
3b
Water piping — single-zone system
Expansion tank
Diaphragm-type or bladder-type
expansion tank — Figure 9
1. Ensure expansion tank size will handle boiler and
system water volume and temperature. Tank must
be located in boiler return piping as close to boiler
as possible, before inlet side of circulator. See tank
manufacturer’s instructions for details.
2. Install an automatic air vent as shown.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water
to be added through fill valve. Eventual section failure can result.
Use Figure 9 or Figure 10 only for single-zone systems designed for return water at least 130 °F.
For systems with low return water temperature possible, such as converted gravity systems and
radiant heating systems, refer to the special piping suggestions of pages 20-25. Failure to prevent
low return water temperature to the boiler could cause corrosion of the boiler sections or
burners, resulting in severe personal injury, death or substantial property damage.
Figure 9
Diaphragm- or bladder-type expansion tank
Piping to single-zone system using
diaphragm-type or bladder-type expansion
tank. See Table 3 for piping sizes.
From
system
Cold
water
fill
To DIAPHRAGM
expansion tank
and fittings
Closed-type expansion tank — Figure 10
1. Ensure expansion tank size will handle boiler and
system water volume and temperature. See tank
manufacturer’s instructions for details.
2. Connect tank to ½" NPT tapping located behind
supply outlet, using ½" NPT piping. Pitch any
horizontal piping up towards tank 1 inch per 5 feet
of piping.
Figure 10 Closed-type expansion tank
Piping to single-zone system using closedtype expansion tank. See Table 3 for piping
sizes.
CLOSED-type
expansion tank
Isolation
valve
Isolation
valve
From
system
Cold water fill
Isolation
valve
Relief
valve
To system
Circulator*
Isolation
valve
To system
Relief
Automatic
air vent
D
L
O
G
CGa
Drain
valve
Circulator
*Alternate
59306
Part Number 550-110-593/109917
location
valve
Circulator
59307
*Alternate
location
Drain
valve
Circulator*
D
L
O
G
CGa
Page 18
GOLD CGa Gas-Fired Water Boiler
Water piping — multiple zones
Failure to prevent low return water temperature to the boiler could cause corrosion of the
boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 13 or14 on page 21. Alternatively,
use the method of either
(system-bypass), because this method does not control radiant system supply temperature.
17
If radiant system tubing has no oxygen barrier, a
Figure 15 or Figure 16 on page 23. Do not use the piping of Figure
heat exchanger must be used.
18Part Number 550-110-593/1099
Page 19
Boiler Manual
Typical piping — multiple-zone installations
Figure 11
Zoning with circulators
— return water 130 °F or higher.
ZONE 2
ZONE 1
1
2
11
Cold
water
6
9
11
fill
12
10
13
CGa
GOLD
Figure 12
Zoning with zone valves
— return water 130 °F or higher.
ZONE 2
ZONE 1
Cold
water
1
6
11
9
11
fill
12
6
Alternate
circulator
location
10
GOLD
CGa
1
2
3
6
1
5
13
59308
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator
5 Zone valve
6 Drain valve
9 Relief valve
10 Automatic air vent (with diaphragm-type expansion
59309
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from
top of air separator to tank fitting as in Figure 10.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the
expansion tank, regardless of location of expansion
tank circulator or air separator.
tank), or connect to tank fitting (closed-type
expansion tank).
DO NOT use an automatic air vent
when using closed-type expansion tank. It would
allow air to leave the system, causing waterlogging
of the expansion tank.
For systems with possible low return-water temperature (such as converted gravity systems,
radiant heating systems and heat pump systems), refer to the special piping suggestions of
Figures 13 – 17, as applies. Failure to prevent sustained low return water temperature to the
boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death or
substantial property damage.
Part Number 550-110-593/109919
Page 20
GOLD CGa Gas-Fired Water Boiler
3d
Primary/secondary
(preferred) bypass
piping method
Temperature gauges
Water piping — low temp systems
Primary/secondary bypass piping is preferred because the flow rate and temperature drop in
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of
the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and
temperature distribution.
Figures 13 and 14 show suggested bypass arrangements using primary/secondary bypass
piping (preferred) for low temperature systems such as radiant heating systems or converted
gravity systems
The bypass valves (items
system return water — set to assure a minimum return water temperature (at least 130 °F) to
the boiler. Set the valves as explained below.
Gauge 4a is suggested, but optional on any system.
Gauge 4b is optional on converted gravity systems, but required on radiant heating systems —
to display the water temperature being supplied to the radiant tubing.
8 is required on all systems to assure the return water temperature is accurately set for
Gauge
a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the
boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return water
is cold (approximately 60 °F water temperature).
. For alternatives, see pages 22 through 25.
7a and 7b) provide mixing of hot boiler outlet water with cooler
Valve adjustment
(Figure 13 and 14 only)
1. Set the valves while the system is cool, setting for the coldest expected water temperature
(usually 60 °F since the system will often drop to room temperature between cycles).
2. Start with valve
3. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads
130 °F when gauge 4a reads 60 °F.
4. Note that valve 7a regulates the amount of hot water from the boiler supply which mixes
with return water. Valve 7b regulates the amount of system water flowing through the
boiler secondary loop.
Failure to prevent low return water temperature to the boiler could cause corrosion of the
boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating system piping should include a means of
temperature
pumping control
Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control.
temperature
Weil-McLain representative for suggested piping and control methods.
Failure to
to the sections or burners, resulting in possible severe personal injury, death or substantial
property damage.
Instead, provide controls and piping which can regulate the boiler return water
prevent cold return water temperature to the boiler could cause corrosion damage
7a fully closed and 7b fully open.
regulating the boiler return water
and the system supply temperature (such as provided by an injection
).
at no less than 130 °F regardless of system supply temperature. Contact your
20Part Number 550-110-593/1099
Page 21
Boiler Manual
Primary/secondary (preferred) piping —
for radiant heating or converted gravity systems
Figure 13
Zoning with circulators
ZONE 2
ZONE 1
1
Cold
water
4a4b
2
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
Alternate
circulator
location
10
GOLD
CGa
13
Figure 14
Zoning with zone valves
ZONE 2
ZONE 1
1
2
3
1
Cold
water
1
4a4b
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
10
13
Alternate
circulator
location
GOLD
CGa
3
1
5
1
59310
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator (circulator should cycle
with zone valve and switches, using circulator valve
or zone control panel)
4 System temperature gauges
5 Zone valve
6 Drain valve
7 System temperature valves (see instructions to the
left for adjusting valves)
8 Blend temperature gauge
9 Relief valve
59311
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion
tank). DO NOT use an automatic air vent when using
closed-type expansion tank. It would allow air to leave
the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank, if
used (For closed-type expansion tank, pipe from top
of air separator to tank fitting as in Figure 10.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion
tank, regardless of location of expansion tank, circulator
or air separator.)
Part Number 550-110-593/109921
Page 22
GOLD CGa Gas-Fired Water Boiler
3e
Boiler-bypass piping
method
Temperature gauges
Water piping — low temp systems
This piping method is called a boiler-bypass because part of the circulator flow is bypassed
around the boiler (through valve 7a). This method reduces the flow rate throughout the boiler,
in order to raise the average water temperature in the boiler enough to prevent flue gas
condensation. Boiler-bypass piping is effective for some boilers — including the CGa —
provided the flow rates are adjusted according to the instructions following.
Figures 15 and16 are alternative piping suggestions for converted gravity (large water content
or steam systems) or
be applied. (Figure 17 is another alternative, using system bypass in place of boiler-bypass
piping.
protect the radiant system from possible high water temperature.)
Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low as
possible, helping to equalize the building heat distribution.
Gauge 4a is optional if the bypass valves will be adjusted using cold (or room temperature)
return water to the boiler. (When setting the valves without gauge
room temperature water — assume the return water temperature to be 60 °F. Set the valves so
gauge
Gauge 4b is optional on converted gravity systems, but required on radiant heating systems —
to display the water temperature being supplied to the radiant tubing.
Gauge
boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is
not installed.
Figure 17 however, is not suitable for radiant heating applications because it does not
8 reads at least 120 °F.
8 is required on all systems to assure reliable adjustment of the bypass valves. The
radiant heating system — for use when primary/secondary piping can’t
4a installed — using cold or
Valve adjustment
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads 60 °F
higher than gauge
enough flow rate and high enough average temperature to prevent condensation even with
low system return water temperature.
3. Valve 7a regulates the system flow rate, while valve 7b regulates the boiler flow rate.
4. The boiler-mounted temperature/pressure gauge may be used in place of a separate gauge 8.
Failure to prevent low return water temperature to the boiler could cause corrosion of the
boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating system piping should include a means of
temperature
pumping control
Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control
temperature
Weil-McLain representative for suggested piping and control methods.
Failure to
to the sections or burners, resulting in possible severe personal injury, death or substantial
property damage.
and the system supply temperature (such as provided by an injection
. Instead, provide controls and piping which can regulate the boiler return water
prevent cold return water temperature to the boiler could cause corrosion damage
4a. A minimum 60 °F temperature rise through the boiler assures a low
regulating the boiler return water
).
at no less than 130 °F regardless of system supply temperature. Contact your
22Part Number 550-110-593/1099
Page 23
Boiler Manual
Boiler-bypass (alternate) piping —
for radiant heating or converted gravity systems
Figure 15 Boiler-bypass piping
Zoning with circulators
(Alternative to primary/secondary piping
Figures 13 and 14)
ZONE 2
ZONE 1
1
4a4b
2
7b
10
13
8
GOLD
CGa
Cold
water
11
66
7a
9
11
fill
12
Figure 16 Boiler-bypass piping
Zoning with zone valves
(Alternative to primary/secondary piping
Figures 13 and 14)
ZONE 2
1
2
3
4a
Cold
water
11
fill
12
3
ZONE 1
Alternate
circulator
location
7a
7b
9
10
11
4b
66
8
GOLD
CGa
5
13
59312
1 Boiler isolation (balancing) valves
59313
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type
2 Flow/check valve
3 System or zone circulator
4 System temperature gauges
5 Zone valve
6 Drain valve
7 System temperature valves (see instructions to the left
for adjusting valves)
8 Blend temperature gauge
9 Relief valve
expansion tank). DO NOT use an automatic air vent
when using closed-type expansion tank. It would
allow air to leave the system, causing waterlogging
of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from
top of air separator to tank fitting as in
13 Air separator and automatic vent, if used (Note that
Figure 10.)
the fill valve must always be connected to the
expansion tank, regardless of location of expansion
tank, circulator or air separator.)
Part Number 550-110-593/109923
Page 24
GOLD CGa Gas-Fired Water Boiler
3f
System-bypass
piping method
Water piping — low temp systems
This piping method is called a system-bypass because part of the circulator flow bypasses the
system (through valve 7a). This bypassed hot water from the boiler outlet mixes with cooler
system return water temperature in order to provide minimum 130 °F return water to the
boiler. Valve 7b will most often be full open, but may need to be slightly closed on some low
pressure drop systems in order to cause enough flow through valve 7a.
Figure 17 is an alternative piping method that provides return water temperature control for
boilers installed on
Do not apply the piping of Figure 17 on radiant heating systems. It provides no method of
regulating the water temperature provided to the system and could result in excessive water
temperature in the radiant tubing.
System-bypass piping as shown in Figure 17 can be used with either zone valve or circulator
zoning. When used with circulator zoning however, the boiler circulator (item
piped as shown. It cannot be used as one of the zoning circulators.
Do not apply system-bypass piping if the reduced flow in the system could cause poor heat
distribution. That is, system-bypass piping reduces the flow in the system and increases the
water temperature supplied to the system. This can cause increased heat from radiators at the
beginning of the system and reduced heat from radiators near the end of the system.
converted gravity systems (large water content or steam systems).
3), must be
Valve adjustment
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve
least 130 °F at all times.
3. Valve
4. The valve adjustment should be done with the system at the coldest expected temperature
Failure to prevent low return water temperature to the boiler could cause corrosion of the
boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating system piping should include a means of
temperature
pumping control
Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control
temperature
Weil-McLain representative for suggested piping and control methods.
7a regulates the amount of boiler supply water mixed with return water. Valve 7b
causes a pressure drop in the system needed to balance flow through valve 7a and the
system.
(60 °F for converted gravity systems or high mass radiant systems).
and the system supply temperature (such as provided by an injection
. Instead, provide controls and piping which can regulate the boiler return water
at no less than 130 °F regardless of system supply temperature. Contact your
7a while closing valve 7b until the temperature at gauge 8 reads at
regulating the boiler return water
).
Failure to prevent cold return water temperature to the boiler could cause corrosion damage
to the sections or burners, resulting in possible severe personal injury, death or substantial
property damage.
24Part Number 550-110-593/1099
Page 25
Boiler Manual
3f
System-bypass
(alternate)
piping —
for converted gravity (or steam) systems
Cold
water
59314
fill
11
12
8
7a
To systemFrom system
7b
Alternate
circulator
location
9
10
CGa
GOLD
Figure 17 System-bypass piping
Zoning with zone valve or circulators, return
water 130 °F or higher.
(Alternative to boiler-bypass piping Figures15 and 16)
3 System or zone circulator
7 System temperature valves (see instructions to the left for
adjusting valves)
8 Blend temperature gauge
9 Relief valve
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion
tank). DO NOT
closed-type expansion tank. It would allow air to leave
the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank, if used
(For closed-type expansion tank, pipe from top of air
separator to tank fitting as in Figure 10.)
use an automatic air vent when using
3g
Water piping — Refrigeration system
Figure 18 Piping refrigeration systems
System
supply
Circulator
System
return
59315
Water
chiller
Strainer
Check
valve
Expansion tank
Balancing
valve
Shut-off
valve
Boiler
GOLD
CGa
Prevent chilled water from
entering boiler
Install boiler so that chilled medium
is piped in parallel with the heating
boiler. Use appropriate valves to
prevent chilled medium from
entering boiler. See
typical installation of balancing
valve and check valve.
If boiler is connected to heating coils
located in air handling units where
they can be exposed to refrigerated
air, use flow control valves or other
automatic means to prevent gravity
circulation during cooling cycle.
Figure 18 for
Part Number 550-110-593/109925
Page 26
GOLD CGa Gas-Fired Water Boiler
4
Gas piping
Natural Gas:
1. Refer to
on rated boiler input (divide by 1,000 to obtain cubic
feet per hour). Table 4 is only for gas with specific
gravity 0.60, with a pressure drop through the
gas piping of 0.30" w.c. For additional gas pipe
sizing information, refer to ANSI Z223.1 (or B149.1
or B149.2 for Canadian installations).
2. Inlet pressure required at gas valve inlet:
•Maximum: 13" w.c.
•Minimum: 5" w.c.
•Manifold gas pressure: 3.5" w.c.
3. Install 100% lockup gas pressure regulator in supply
line if inlet pressure exceeds 13" w.c. Adjust for
13" w.c. maximum.
Propane Gas:
1. Contact gas supplier to size pipes, tanks and 100%
lockup gas pressure regulator.
Table 4 for pipe length and diameter. Base
Table 4Pipe capacity for 0.60 specific gravity natural gas
Gas pipe
length
(feet)
1013227852010501600
20921903507301100
3073152285590860
4063130245500760
505611 5215440670
754593175360545
1003879150305460
1503164120250380
½"¾"1"1¼"1½"
Capacity of pipe for pipe size of:
(Capacity in cubic feet gas per hour)
2. Adjust propane supply regulator provided by gas
supplier for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
•Maximum: 13" w.c.
•Minimum: 11" w.c.
•Manifold gas pressure: 10" w.c.
Figure 19 Gas supply piping
Manual main
shutoff gas valve
(when required)
Ground joint union
(when required)
Tee
Nipple
Cap
59322
26Part Number 550-110-593/1099
Page 27
Boiler Manual
5
Field wiring
For your safety, turn off electrical power supply at
service entrance panel before making any electrical
connections
Failure to do so can cause severe personal injury or
death.
Wiring must be N.E.C. Class 1.
If rollout thermal fuse element wire as supplied with
boiler must be replaced, type
must be used. If other original wiring as supplied with
boiler must be replaced, use only type
equivalent.
Boiler must be electrically grounded as required by
National Electrical Code ANSI/NFPA 70-latest edition.
Electrical installation must
comply with:
1. National Electrical Code and any other national,
state, provincial or local codes or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code
Part 1, and any local codes.
Wiring connections
Boiler is shipped with controls completely wired, except
spill switch and vent damper. Refer to wiring diagrams
shown on page 34 for standing pilot ignition boiler or
page 38 for spark-ignited pilot boiler.
to avoid possible electric shock hazard.
200 °C wire or equivalent
105 °C wire or
Thermostat
1. Connect thermostat as shown on wiring diagram
on boiler.
2. Install on inside wall away from influences of drafts,
hot or cold water pipes, lighting fixtures, television,
sunrays or fireplaces.
3. If thermostat has a heat anticipator, set heat
anticipator in thermostat to match power
requirements of equipment connected to it. If
connected directly to boiler, set for 0.1 amps plus
gas valve current. See information on the wiring
diagram shown in
Figure 25b, page 39. For other
devices, refer to manufacturer’s specifications.
Wiring diagram on boiler gives setting for control
module and gas valve. Also see instructions with
thermostat.
Junction box (furnished)
1. Connect 120 VAC power wiring (Figure 20).
2. Fused disconnect or service switch (15 amp.
recommended) may be mounted on this box. For
those installations with local codes which prohibit
installation of fused disconnect or service switch on
boiler, install a 2 x 4 cover plate on the boiler
junction box and mount the service switch remotely
as required by the code.
Wiring multiple zones
Refer to zone valve manufacturer’s literature for wiring
and application. A separate transformer is required to
power zone valves. Zoning with circulators requires a
relay for each circulator.
Figure 20
Field wiring connections —
service switch and
thermostat (or end switch)
provided by installer
Part Number 550-110-593/109927
Service
(not provided)
Field wiring
Factory wiring
120 VAC
HotNeutral
switch
BlackWhiteGreen
Junction box,
boiler left side
Ground
Thermostat
or end switch
(not provided)
Ground screwWire nuts
BlackBlack
Thermostat
leads, through
jacket left side
59323
Service
switch
(not provided)
Thermostat
or end switch
(not provided)
Page 28
GOLD CGa Gas-Fired Water Boiler
Start-up — preparation6a
Check for gas leaks
Before starting the boiler, and during initial operation, smell near the floor and around the
boiler for gas odorant or any unusual odor. Do not proceed with start-up if there is any indication
of a gas leak. Repair any leak at once.
Propane boilers only — Your propane supplier mixes an odorant with the propane to make
its presence detectable. In some instances, the odorant can fade and the gas may no longer have
an odor.
•Propane gas can accumulate at floor level. Smell near the floor for the gas odorant or any
unusual odor. If you suspect a leak, do not attempt to light the pilot.
•Use caution when attempting to light the propane pilot. This should be done by a qualified
service technician, particularly if pilot outages are common.
•Periodically check the odorant level of your gas.
•Inspect boiler and system at least yearly to make sure all gas piping is leak-tight.
•Consult your propane supplier regarding installation of a gas leak detector. There are some
products on the market intended for this purpose. Your supplier may be able to suggest an
appropriate device.
Determine if water treatment is needed
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage
to boiler will occur, resulting in substantial property damage.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can
build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
Verify water chemistry
Consult local water treatment companies for unusually hard water areas (above 7 grains
hardness) or low pH water conditions (below 7.0). Boiler water pH of 7.0 to 8.5 is recommended.
Freeze protection (when used)
Use antifreeze made especially for hydronic systems. Inhibited propylene glycol is recommended.
Do not use ethylene glycol, automotive or undiluted antifreeze. Severe personal injury or
death can result.
1. Determine antifreeze quantity according to system water content. Boiler water content is
listed on page 67. Remember to include expansion tank water content.
2. Follow antifreeze manufacturer's instructions.
3. A 50% solution of propylene glycol/water provides maximum protection to about -30 °F.
4. Local codes may require
5. When using antifreeze in a system with automatic fill, install a water meter to monitor
water makeup. Glycol will leak before the water begins to leak, causing glycol level to drop.
Added water will dilute the antifreeze, reducing the freeze protection level.
back flow preventer or actual disconnect from city water supply.
28Part Number 550-110-593/1099
Page 29
Boiler Manual
Fill the system with water
1. Close manual and automatic air vents and boiler drain cock.
2. Fill to correct system pressure. Correct pressure will vary with each application. Typical
cold water fill pressure for a residential system is 12 psi.
3. Purge air from system:
a. Connect a hose to the purge valve (see drain valves, item 6, in suggested piping diagrams
on pages 17 through 23,
water can drain and be seen.
b. Close the boiler or system isolation valve between the purge valve and fill connection
to the system.
c. Close zone isolation valves.
d. Open quick-fill valve on cold water makeup line.
e. Open purge valve.
f. One zone at a time, open the isolation valves. Allow water to run through the zone,
pushing out the air. Run until no noticeable air flow is present. Close the zone isolation
valves and proceed with the next zone. Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve and remove the hose. Open all isolation
valves. Watch that system pressure rises to correct cold-fill pressure.
h. After the system has operated for a while, eliminate any residual air by using the manual
air vents located throughout the system.
i. If purge valves are not installed in system, open manual air vents in system one at a
time, beginning with lowest floor. Close vent when water squirts out. Repeat with
remaining vents.
Figure 9 through Figure 16). Route hose to an area where
4. Open automatic air vent (diaphragm-type or bladder-type expansion tank systems only)
one turn.
5. Open other vents:
a. Starting on the lowest floor, open air vents one at a time until water squirts out.
b. Repeat with remaining vents.
6. Refill to correct pressure.
Inspect system water piping
After filling the boiler and system with water, inspect all piping throughout the system for
leaks. If found, repair immediately. Repeat this inspection after the boiler has been started and
the system has heated up.
Leaks must be repaired at once. Failure to do so can damage the boiler, resulting in substantial
property damage.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage
to boiler will occur, resulting in substantial property damage.
Part Number 550-110-593/109929
Page 30
GOLD CGa Gas-Fired Water Boiler
Start-up — preparationcontinued6a
Inspect base insulation
The boiler contains ceramic fiber and fiberglass materials. Use care when
handling these materials per instructions on page 68 of this manual. Failure
to comply could result in severe personal injury.
Failure to replace damaged insulation or reposition insulation can result
in a fire hazard, causing severe personal injury, death or substantial property
damage.
Check to make sure insulation is secure against all four sides of the base. If insulation is
damaged or displaced,
do not operate boiler. Replace or reposition insulation.
Start-up — operate boiler6b
DO NOT proceed with boiler operation unless boiler and system have been
filled with water and all instructions and procedures of previous manual
sections have been completed. Failure to do so could result in severe personal
injury, death or substantial property damage. Before starting the boiler . . .
Section 8/9 and the Lighting/Operating instruction
Start-up preparation procedures of Section 6 have been
Natural or
Propane
Natural or
Propane
35 Honeywell VR8204/VR8304 Natural40
Robertshaw 7200Natural41
White-Rodgers 36ENatural42
35 Honeywell VR8204/VR8304 Natural40
30Part Number 550-110-593/1099
Page 31
Boiler Manual
Start-up — operate boilercontinued6b
Start the boiler
•Follow the Lighting/Operating Instructions from
Section 8 or 9 to start the boiler. Remove boiler
jacket door and note the gas valve manufacturer and
model number. Use only the lighting/operating
instruction which applies to this gas valve (see Table
Check system and boiler
Eliminate all system leaks. Continual fresh makeup
water will reduce boiler life. Minerals can build up in
sections, reducing heat transfer, overheating cast iron,
and causing section failure.
If you discover evidence of any gas leak, shut down the
boiler at once. Find the leak source with bubble test and
repair immediately. Do not start boiler again until
corrected. Failure to comply could result in severe
personal injury, death or substantial property damage.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.
1. Check system piping for leaks. If found, shut down
boiler and repair immediately.
5, page 30). (The lighting instruction label on the
boiler provides the same information.)
•See Section 6c, below, if boiler fails to start.
2. Vent air from system using manual vents. Air in
the system will interfere with circulation and cause
heat distribution problems and noise.
3. Inspect vent system thoroughly for signs of
deterioration from corrosion, physical damage or
sagging. Verify that masonry chimney liners are in
good condition, with no obstructions, and there are
no openings into the chimney.
Check around the boiler for gas odor following the
4.
procedure of section 6a, page 28 of this manual.
5. Verify operation per section 6d, page 32. Perform
check-out procedure in section 7, page 33, and fill
in the Installation and service certificate.
Start-up — if boiler doesn’t start . . .6c
Check for:
1. Loose connections, blown fuse or service switch off?
2. High limit switch set below boiler water temperature?
3. Thermostat set below room temperature?
Part Number 550-110-593/109931
4. Gas not turned on at meter or boiler?
5. Incoming gas pressure less than:
5" w.c. for natural gas? 11" w.c. for propane gas?
6. If none of the above corrects the problem, refer to
Troubleshooting, section 11, page 49 of this manual.
Page 32
GOLD CGa Gas-Fired Water Boiler
Start-up — verify operation6d
The boiler model suffix will be “SPD”. For spark-ignited
pilot boilers (suffix “
operation and lighting/operating information.
PID”), see Section 8 or 9 for
Figure 21 Typical pilot burner flame
Figure 22 Typical main burner flame
32Part Number 550-110-593/1099
Page 33
Boiler Manual
Check-out procedure — checklist7
❏Boiler and heat distribution units filled with water?
❏Automatic air vent, if used, open one full turn?
❏Air purged from system?
❏Air purged from gas piping? Piping checked for leaks?
❏Correctly sized manifold orifices installed? Refer to Table 2,
page 12 to check size and fuel type.
Correctly sized manifold orifices must be used.
Failure to do so will cause severe personal
injury, death or substantial property damage.
❏Followed lighting/operating instructions on boiler or in
manual section
start-up?
❏Proper burner flame observed? Refer to Check burner flame,
manual section 6d, page 32.
❏Test limit control — While burners are operating, move
indicator on limit control below actual boiler water
temperature. Burners should go off while circulator
continues to operate. Raise setting on limit control above
boiler water temperature and burners should reignite.
❏Test additional field-installed controls — If boiler has a low
water cutoff, additional high limit or other controls, test for
operation as outlined by manufacturer. Burners should be
operating and should go off when controls are tested. When
controls are restored, burners should reignite.
❏Botton on spill switch pushed in?
❏Test ignition system safety device:
a.
Standing pilot — Turn gas cock knob to PILOT
position and extinguish pilot flame. Pilot gas flow
should stop in less than 3 minutes. Put system back
into operation (see section 6, pages 28-32).
b.Spark-ignited pilot — Connect manometer to outlet
side of gas valve. Start boiler, allowing for normal startup cycle to occur and main burners to ignite. With
main burners on, manually shut off gas supply at
manual main shutoff gas valve. Burners should go off.
8, page 34 or section 9, page 37 for proper
Open manual main shutoff gas valve. Manometer
should confirm there is no gas flow. Pilot will relight,
flame sensing element will sense pilot flame and main
burners reignite.
❏Set limit control(s) to system temperature requirements.
Adjust balancing valves and controls to provide design
temperature to system.
❏For multiple zones, adjust flow so it is about the same in
each zone.
❏Verify thermostat heat anticipator (if available) set properly?
Refer to
Thermostat(s).
❏Cycle boiler with thermostat — Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to
lowest setting and verify boiler goes off.
❏Measure natural gas input:
a.Operate boiler 10 minutes.
b.Turn off other appliances.
c.At natural gas meter, measure time (in seconds)
d.Calculate gas input:
e.Btuh calculated should approximate input rating on
❏Check manifold gas pressure by connecting manometer to
downstream test tapping on main gas valve. Manifold
pressure for natural gas should be 3.5" w.c. and for propane
gas should be 10" w.c.
❏Observe several operating cycles for proper operation.
❏Set room thermostat to desired room temperature.
❏Fill in Installation and service certificate below?
❏Review all instructions shipped with this boiler with owner
or maintenance person. Return instructions to envelope and
give to owner or place in pocket inside front panel in boiler.
Field wiring, manual section 5, page 27,
required to use one cubic foot of gas.
3600 x 1000
number of seconds from step c
boiler rating label.
= Btuh
Installation and service certificate
Boiler model __________________ Series __________ CP number ___________ Date installed _______________
❏ Check out sequence has been performed.
❏ Above information is certified to be correct.
❏ Information received and left with owner/maintenance person
_____________________________________
(installer’s signature)
Page 34
GOLD CGa Gas-Fired Water Boiler
Operation — standing pilot boilers8a
Figure 23 Wiring diagram — Standing pilot system
SCHEMATIC WIRING DIAGRAM
ADDITIONAL
LIMITS
(NOTE 6)
EQUIPMENT
GROUND
(NOTE 7)
SERVICE
SWITCH
(BY OTHERS)
H
N
Y
W
CIRCULATOR
NOTES:
1. ALL WIRING MUST BE INSTALLED IN ACCORDANCE WITH:
A. U.S.A. - NATIONAL ELECTRICAL CODE AND ANY OTHER NATIONAL, STATE OR LOCAL
CODE REQUIREMENTS.
B. CANADA - C.S.A. C22.1 CANADIAN ELECTRICAL CODE PART 1 AND ANY OTHER
2. ALL CONTACTS SHOWN WITHOUT POWER APPLIED-OFF SHELF CONDITION.
3. IF ORIGINAL ROLLOUT TFE WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED,
4. REFER TO CONTROL COMPONENT INSTRUCTIONS PACKED WITH BOILER FOR APPLICATION INFORMATION.
5. THERMOSTAT - FOR SINGLE ZONE SYSTEMS, THERMOSTAT ANTICIPATOR SETTING IS 0.40 AMPS.
6. L.W.C.O., ADDITIONAL HIGH LIMIT, ETC., WIRED IN SERIES.
7. DENOTES FIELD INSTALLED CHASSIS GROUND.
o
TYPE 200 C WIRE OR ITS EQUIVALENT MUST BE USED. IF OTHER ORIGINAL WIRE AS
SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, TYPE 105 C OR ITS EQUIVALENT MUST
BE USED.
EMCS - FOR EMCS CONNECTION IN PLACE OF THERMOSTAT, REFER TO
BK
BK
Y
G
BK
W
WIRE NUT
NATIONAL, PROVINCIAL OR LOCAL CODE REQUIREMENTS.
FOR MULTIPLE ZONE SYSTEMS USING ZONE VALVES OR CIRCULATORS, REFER
TO COMPONENT MANUFACTURER’S INSTRUCTIONS FOR
APPLICATION WIRING AND THERMOSTAT ANTICIPATOR SETTING.
EMCS INSTALLATION/OPERATING MANUAL.
G
C
BK
Y
ELECTRICAL SHOCK HAZARD, CAN CAUSE SEVERE
INJURY OR DEATH. DISCONNECT POWER
BEFORE INSTALLING AND/OR SERVICING.
SPILL
SWITCH
BKBK
THERMOSTAT
OR EMCS
(NOTE 5)
BK
W
R
TRANSFORMER
120/24 V.A.C.
PLUG-IN
DPST
RELAY
JUNCTION BOX
LIMIT
CONTROL
ROLLOUT
TFE
THERMO-
COUPLE
o
Y
Y
G
BK
BL
DAMPER
CONNECTOR
GAS
VALV E
PILOT
CGa
CABLE
TO
DAMPER
25 thru 8
H
RC
BL
Y
LADDER WIRING DIAGRAM
120 V.A.C.
SERVICE SWITCH
(BY OTHERS)
CR2
THERMOSTAT
OR EMCS
(NOTE 5)
CR1
ADDITIONAL
LIMITS
(NOTE 6)
SPILL
SWITCH
LOW VOLTAGE FIELD
HIGH VOLTAGE FIELD
LOW VOLTAGE FACTORY
HIGH VOLTAGE FACTORY
THERMOCOUPLE
Standing Pilot
Natural Or Propane Gas
Forced Hot Water
G
LIMIT
CONTROL
PRIMARY
24 V.A.C.
1
ROLLOUT
Weil-McLain
PART NUMBER
CIRCULATOR
RELAY COIL
CR
CABLE
TO
DAMPER
536
2
4
6315
FUSE
TFE
2
4
DAMPER
CONNECTOR
A United Dominion Company
500 Blaine St.
Michigan City, IN 46360-2388
550-225-009/0999
N
EQUIPMENT
GROUND
(NOTE 7)
34Part Number 550-110-593/1099
Page 35
Boiler Manual
Lighting instructions — CGa-25 to CGa-88b
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot, which must be lighted
by hand. When lighting the pilot, follow these
instructions exactly.
B. Before LIGHTING, smell all around the appliance
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle
on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
C. Use only your hand to push down the reset button or turn the gas
D. Do not use this appliance if any part has been under water.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. Turn gas control knob clockwise
7. When equipped with vent damper, verify damper blade is
in full open position.
8. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas,
go to the next step.
Effikal vent damper Model RVGP,
Johnson Controls vent damper
to OFF.
control knob. Never use tools. If the knob or reset button will not
operate by hand, don't try to repair it, call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
9. Remove access panel located above burners.
10. Find pilot — follow metal tube from gas
control. The pilot is between two burners
behind the access panel.
11. Turn gas control knob counterclockwise
to PILOT.
12. Push in red reset button and hold. Immediately light the
pilot with a match. Continue to hold reset button in for
about one (1) minute after the pilot is lit.
13. Release reset button. Pilot should remain lit. If pilot goes
out, repeat steps 6 through 13.
•If reset button stays depressed after release, stop and
immediately call your service technician or gas supplier.
•If the pilot will not stay lit after several tries, turn the
gas control knob clockwise
service technician or gas supplier.
14. Replace access panel.
15. Turn gas control knob counterclockwise
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service
switch in
18. Set thermostat to desired setting.
19. Replace front panel.
Automatic Operation position.
to OFF and call your
to ON.
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
Part Number 550-110-593/109935
3. Remove front panel.
4. Turn gas control knob clockwise
5. Replace front panel.
to OFF.
Page 36
GOLD CGa Gas-Fired Water Boiler
Lighting instructions — CGa-25 to CGa-88b
• Standing pilot• Gas valve manufacturer — Robertshaw
• Natural gas
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot, which must be lighted
by hand. When lighting the pilot, follow these
instructions exactly.
B. Before LIGHTING, smell all around the appliance
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle
on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
C. Use only your hand to depress the selector arm. Never use tools. If the
D. Do not use this appliance if any part has been under water.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP,
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. Depress and move selector arm left
7. When equipped with vent damper, verify damper blade is
in full open position.
Position
indicator
(shown in
position)OFF
59332
8. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas,
go to the next step.
Johnson Controls vent damper
to OFF.
Selector
arm
• Gas valve model(s) — 7200
selector arm will not move by hand, don't try to repair it, call a qualified
service technician. Force or attempted repair may result in a fire or
explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
9. Remove access panel located above burners.
10. Find pilot — follow metal tube from gas
control. The pilot is between two burners
behind the access panel.
11. Move selector arm on gas control right
to SET position.
12. Hold selector arm in
the pilot with a match. Continue to hold selector arm to
SET for about one-half (¹⁄₂) minute after the pilot is lit.
13. Release selector arm. If pilot does not remain lit, repeat steps
6 through 13.
•If the pilot will not stay lit after several tries, move
selector arm left to OFF and call your service
technician or gas supplier.
14. Replace access panel.
15. Turn selector arm left to ON.
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service
switch in Automatic Operation position.
18. Set thermostat to desired setting.
19. Replace front panel.
SET position and immediately light
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
36Part Number 550-110-593/1099
3. Remove front panel.
4. Depress and move selector arm left
5. Replace front panel.
to OFF.
Page 37
Boiler Manual
Operation — spark-ignited pilot boilers9a
Follow all procedures given in this manual and operating
instructions when operating the boiler. Failure to do so
could result in severe personal injury, death or
substantial property damage.
1. Standby: With no call for heat, the vent damper and
circulator are deenergized. No gas flows to pilot or main
gas valve.
2.
Call for heat (thermostat circuit closes):
a. Vent damper and circulator energized if pilot status
acceptable. Vent damper drives open. When vent
damper end switch makes circuit, ignition control
begins pilot ignition attempt.
b. Ignition control checks for false flame signal: If
ignition control senses pilot signal when no pilot
gas should be present, control will lockout,
requiring reset procedure as given in
Figure 24.
3. Pilot ignition: Control module sparks the pilot and
opens pilot valve in main gas valve.
a. If pilot does light and control module senses flame
current, spark generator is turned off and main
valve opens.
b. If pilot does not light within 15 seconds, pilot valve
is closed and spark generator is turned off. Control
module waits 5 minutes, then attempts to ignite
pilot again. This cycle will continue indefinitely if
pilot ignition control does not sense pilot flame.
Main burner operation:
4.
a. Control module monitors pilot flame current. If
signal is lost, main valve closes, spark generator
activates and sequence returns to step 4.
b. If power is interrupted, control system shuts off
pilot and main gas valves and restarts at step 1 when
power is restored.
c. In the event the limit control shuts down the boiler
— The control module closes the main gas valve,
but keeps the circulator operating and the vent
damper open.
5.
Thermostat satisfied (thermostat circuit opens) —
Pilot and main gas valves are closed — Vent damper is
deenergized, and cycles to closed position. Circulator
is shut off.
6. Boiler is now in the standby mode.
7. Thermostat anticipator setting: Set thermostat heat
anticipator as instructed in
Figure 25b, page 39.
Figure 24 Ignition control module sequence of operation — status light indications
Steps
(Following step 7,cycle goes back to step 1.)
Call for
heat?
POWERTSTAT
CIRC
LIMIT
DAMPER
FLAME
Timing
1. Standby
Waiting for call for heat·
2. Call for heat
·Circulator on
3. Limit circuit
·Limit controls closed
4. Damper circuit
·Damper proven open
5. Pilot flame proven *
·Gas valve open
·Pilot remains on
·Boiler producing heat
6. Limit cycle
·Limit circuit open
·Gas valve closed
7. Flame outage *
·Flame out
·Boiler recycles
8. Thermostat satisfied
·Circulator off
9. Circulator exercise routine
·Circulator turns on for 30 seconds
if boiler not operated for 30 days
* If pilot flame is not proven in 15 seconds, control module will flash the FLAME light, but will continue indefinitely with attempts to light the pilot burner.
The control module will not lockout on a failure to establish flame. It will lockout if line voltage polarity is reversed, stray voltage is sensed on thermostat
line, or if flame is sensed when it shouldn’t be there.
The boiler will reset after these lockouts if any of the following occurs:
• 1 hour waiting period • Opening and closing of thermostat circuit • Removal of 120 VAC power for at least 45 seconds.
NO
YES
YES
YES
YES
YES
YES
NO
NO
or
= "ON"
= "OFF"
—
—
—
—
15 sec
—
—
15 sec
30 sec
59340
Part Number 550-110-593/109937
Page 38
GOLD CGa Gas-Fired Water Boiler
Operation — spark-ignited pilot system continued9a
Figure 25a Schematic wiring diagram — Spark-ignited pilot system
White
Red
Plug-in
connectors
O
FF
O
N
38Part Number 550-110-593/1099
Page 39
Boiler Manual
Figure 25bLadder wiring diagram — Spark-ignited pilot system
Electrical shock hazard — can cause
severe injury or death. Disconnect
power before installing or servicing.
Legend for ladder wiring diagram
120 VAC field wiring
Low voltage field wiring
120 VAC factory wiring
Low voltage factory wiring
High voltage spark ignition wiring
Ground connectors
Table G: Gas valve terminals and anticipator settings
1. All wiring must be installed in accordance with:
A. U.S.A. — N.E.C.And any other national, state,
or local code requirements.
THERMOSTAT
TSTAT/CIRC
R
B. Canada — C.S.A. C22.1 C.E.C.Part 1 and any
other national, provincial, or local code requirements.
2. Pilot lead wires are not field replaceable. Replace pilot assembly if necessary.
3. If any of the original wire as supplied with the appliance must be replaced,use minimum 105 °C
wire or equivalent. Exception — wires to a rollout
TFE must be 200 °C or equivalent.
4. Thermostat anticipator setting (single zone) — see
Table G for anticipator setting, depending on
which gas valve is installed in boiler.
ROLLOUT
TFE
Additional
limits
(note 7)
TEMPERATURE
LIMIT SWITCH
WATER
SPILL
SWITCH
LIMIT
R
CONTROL MODULE
LOW VOLTAGE
SECTION
5. For multiple zoning, use either zone valves or
circulators. Refer to the component manufacturer's instructions and this manual for application and wiring suggestions.
6. Refer to control component instructions packed
with the boiler for application information.
7. Wire any additional limit controls (low water cutoff, additional high limit, etc.) in series with boiler
limit control as shown.
Part Number 550-110-593/109939
DAMPER END SWITCH
(INTERNAL TO DAMPER)
PILOT
FLAME
59347a
SENSOR
HIGH
VOLTAGE
DAMPER
R
FLAME
R
VENT
DAMPER
24VAC
CALL FOR
HEAT
PILOT GAS
VALVE
"C"
"A"
"B"
MAIN GAS
VALVE
See Table G
Page 40
GOLD CGa Gas-Fired Water Boiler
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor. See below.
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to turn the gas control knob. Never use tools. If
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP,
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which
automatically lights the pilot.
by hand.
7. Turn gas control knob clockwise
Open position indicated on damper assembly.
Do not try to light the pilot
to OFF.
the knob will not turn by hand, don't try to repair it, call a qualified
service technician. Force or attempted repair may result in a fire or
explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
8. When equipped with vent damper, verify damper blade is
in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Turn gas control knob counterclockwise
11. Turn on all electric power to the appliance.
12. When equipped with
switch in Automatic Operation position.
13. Set thermostat to desired setting.
Effikal vent damper, place service
STOP! Follow
to ON.
14. If the appliance will not operate, follow the instructions To
Turn Off Gas To The Appliance
technician or gas supplier.
15. Replace front panel.
and call your service
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove front panel.
40Part Number 550-110-593/1099
4. Turn gas control knob clockwise to OFF. Do not
force.
5. Replace front panel.
Page 41
Boiler Manual
Operating instructions — CGa-25 to CGa-69b
• Spark pilot• Gas valve manufacturer — Robertshaw
• Natural gas
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor. See below.
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to depress or move the selector arm. Never use
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP,
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which
automatically lights the pilot.
by hand.
7. Depress and move selector arm to OFF. Note: Selector arm
cannot be moved to OFF unless selector arm is depressed
slightly. Do not force.
Position
indicator
(shown in
Open position indicated on damper assembly.
Do not try to light the pilot
Selector
arm
position)OFF
• Gas valve model(s) — 7200
tools. If the selector arm will not depress or move by hand, don't try
to repair it, call a qualified service technician. Force or attempted repair
may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
8. When equipped with vent damper, verify damper blade is
in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Move selector arm to
11. Turn on all electric power to the appliance.
12. When equipped with Effikal vent damper, place service
switch in Automatic Operation position.
13. Set thermostat to desired setting.
14. If the appliance will not operate, follow the instructions To
Turn Off Gas To The Appliance
technician or gas supplier.
ON.
and call your service
STOP! Follow
59332
15. Replace front panel.
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove front panel.
Part Number 550-110-593/109941
4. Depress and move selector arm to
5. Replace front panel.
OFF. Do not force.
Page 42
GOLD CGa Gas-Fired Water Boiler
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
Do not try to
C. Use only your hand to turn the gas control knob. Never use tools. If
light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the
OPERATING, smell all around the
D. Do not use this appliance if any part has been under water.
floor because some gas is heavier than air and will
settle on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP,
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. This appliance is equipped with an ignition device which
automatically lights the pilot.
by hand.
7. Turn gas control knob clockwise to OFF.
Do not try to light the pilot
the knob will not turn by hand, don't try to repair it, call a qualified
service technician. Force or attempted repair may result in a fire or
explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
8. When equipped with vent damper, verify damper blade is
in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
STOP! Follow
go to the next step.
10. Turn gas control knob counterclockwise
to ON.
11. Turn on all electric power to the appliance.
12. When equipped with
Effikal vent damper, place service
switch in Automatic Operation position.
13. Set thermostat to desired setting.
Position
indicator
(shown in
position)ON
59333
Gas
control
knob
14. If the appliance will not operate, follow the instructions
Turn Off Gas To The Appliance
and call your service
technician or gas supplier.
15. Replace front panel.
To
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
4. Turn gas control knob clockwise
force.
5. Replace front panel.
3. Remove front panel.
42Part Number 550-110-593/1099
to OFF. Do not
Page 43
Boiler Manual
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor. See below.
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any phone in
your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to depress or turn the gas control knob. Never
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP,
place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which
automatically lights the pilot.
by hand.
7. Depress gas control knob slightly and turn clockwise
to OFF. Note: Knob cannot be turned to OFF unless knob
is depressed slightly. Do not force.
Open position indicated on damper assembly.
Do not try to light the pilot
use tools. If the knob will not depress or turn by hand, don't try to
repair it, call a qualified service technician. Force or attempted repair
may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
•Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire
department.
8. When equipped with vent damper, verify damper blade is
in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Turn gas control knob counterclockwise
11. Turn on all electric power to the appliance.
12. When equipped with
switch in Automatic Operation position.
13. Set thermostat to desired setting.
Effikal vent damper, place service
STOP! Follow
to ON.
14. If the appliance will not operate, follow the instructions
Turn Off Gas To The Appliance
technician or gas supplier.
15. Replace front panel.
and call your service
To
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove front panel.
Part Number 550-110-593/109943
4. Depress gas control knob slightly and turn clockwise
to OFF. Do not force.
5. Replace front panel.
Page 44
GOLD CGa Gas-Fired Water Boiler
Service and maintenance — schedule10a
Table 6Service and maintenance schedules (service technician and user)
Service technician
(see following pages for instructions)
Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners and base
Service:
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
Check/test:
ANNNUAL START-UP
• Gas piping
Owner maintenance
(see CGa User’s Information Manual for instructions)
• Check boiler area
Daily
Monthly
Periodically• Test low water cutoff (if used)
Every 6 months• Operate relief valve
• Check air openings
• Check boiler pressure/
temperature gauge
• Check boiler interior piping
• Check venting system
• Check air vents
• Check boiler relief valve
• Check automatic air vents (if
used)
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
End of season• Shut down procedure
Review:
• Review with owner
Follow the Service and maintenance procedures given throughout this manual and in component literature
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or
system. Failure to follow the directions in this manual and component literature could result in severe personal
injury, death or substantial property damage.
44Part Number 550-110-593/1099
Page 45
Boiler Manual
Service & maintenance — annual start-up10b
The boiler should be inspected and started annually, at the beginning of the heating season, only by a qualified
service technician
following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and
maintain the boiler and system could result in equipment failure.
. In addition, the maintenance and care of the boiler designated in Table 6 and explained on the
❏ Inspect . . . . . . . . . .
Reported problems
Inspect any problems reported by owner and correct
before proceeding.
Boiler area
1. Verify that boiler area is free of any combustible
materials
liquids.
2. Verify that boiler area (and air intake) is free of any
of the contaminants listed in Table 1 on page 9 of
this manual. If any of these are present in the boiler
intake air vicinity, they must be removed. If they
cannot be removed, install combustion air piping
to the boiler in accordance with national, provincial
or local codes.
Air openings
1. Verify that combustion and ventilation air openings
to the boiler room and/or building are open and
unobstructed. Check operation and wiring of
automatic combustion air dampers, if used.
, gasoline and other flammable vapors and
2. Verify that boiler vent discharge and air intake are
clean and free of obstructions.
Flue gas vent system
1. Visually inspect entire flue gas venting system
for blockage, deterioration or leakage. Repair any
joints that show signs of leakage in accordance with
vent manufacturer’s instructions.
2. Verify that masonry chimneys are lined, lining is in
good condition, and there are not openings into the
chimney.
Failure to inspect for the above
conditions and have them repaired
can result in severe personal injury
or death.
Pilot and main burner flames
1. Visually inspect pilot burner and main burner
flames as directed under section 6d, page 32 of this
manual.
Water piping
1. Check the boiler interior piping and all system
piping for signs of leaks.
2. Repair any leaks before proceeding.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these
materials per instructions on page 68 of this manual. Failure to comply could result in severe
personal injury.
Part Number 550-110-593/109945
Page 46
GOLD CGa Gas-Fired Water Boiler
Service & maint. — annual start-up continued10b
❏ Inspect . . . . . . . . . .
Electrical shock hazard — Turn off power to the boiler
before any service operation
noted otherwise in this instruction manual. Failure to
turn off electrical power could result in electrical shock,
causing severe personal injury or death.
Do not use petroleum-based cleaning or sealing
compounds
will occur, resulting in substantial property damage.
Eliminate all system or boiler leaks. Continual fresh
makeup water will reduce boiler life. Minerals can build
up in sections, reducing heat transfer, overheating cast
iron, and causing section failure. Leaking water may also
cause severe property damage.
in boiler system. Severe damage to boiler
Boiler heating surfaces
1. Disconnect the vent pipe at the boiler draft hood
and remove draft hood after turning off power to
the boiler.
2. Use a bright light to inspect the boiler flue collector
and heating surfaces.
3. If the vent pipe or boiler interior surfaces show
evidence of soot, follow
surfaces
collector and clean the boiler if necessary after closer
inspection of boiler heating surfaces.
4. If there is evidence of rusty scale deposits on boiler
surfaces, check the water piping and control system
to make sure the boiler return water temperature is
properly maintained (per this manual).
5. Reconnect vent and draft hood. Replace all boiler
in this manual section. Remove the flue
on the boiler except as
Cleaning boiler heating
components before returning to service.
6. Check inside and around boiler for evidence of any
leaks from the boiler. If found, locate source of leaks
and repair.
Burners and base
1. After turning off power to the boiler, remove the jacket
door and base access panel (Figure 32, item 4,
page 62).
2. Inspect burners and all other components in the
boiler base.
3. If burners must be cleaned, raise rear of each burner
to release from support slot, slide forward and
remove. Then brush and vacuum the burners
thoroughly, making sure all ports are free of debris.
Carefully replace all burners, making sure burner
with pilot bracket is replaced in its original position
and all burners are upright (ports up).
4. Inspect the base insulation.
a. Pay attention to the WARNINGS on page 68
regarding working with insulation materials.
b. Verify that the insulation is intact and secure
against all four sides of the base.
If insulation is damaged or
displaced, do not operate the boiler.
Replace or reposition insulation as
necessary. Failure to replace
damaged insulation can result in a
fire hazard, causing severe personal
injury, death or substantial property
damage.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these
materials per instructions on page 68 of this manual. Failure to comply could result in severe
personal injury.
❏ Service . . . . . . . . . .
Oiled-bearing circulators
1. The circulator shipped with the CGa boiler is waterlubricated. No oiling is required.
46Part Number 550-110-593/1099
2. Check other circulators in the system. Oil any
circulators requiring oil, following circulator
manufacturer’s instructions. Over-oiling will
damage the circulator.
Page 47
Boiler Manual
59342
A
B
❏ Start-up . . . . . . . . .
1. Perform start-up procedures section 6, pages 28-32,
including procedure to verify operation of burners
and vent damper on page 32.
2. Verify cold fill pressure is correct and that fill system
is working properly.
3. Verify antifreeze level (if used) is at the right
concentration and that inhibitor level is correct.
❏ Check/test . . . . . . .
Gas piping
1. Sniff near floor and around boiler area for any
indication of a gas leak.
2. Test gas piping using bubble test, per section 4,
page 26 of this manual, if there is any indication of
a leak.
Cold fill and operating pressures
1. While the system is cold, note the pressure reading
on the boiler pressure/temperature gauge. Verify that
cold fill pressure is correct.
4. Check gas piping, per manual sections 4 and 6,
verifying no indications of leakage and all piping
and connections are in good condition.
5. Read the Lighting or Operating instructions
(manual section 8 or 9) applying to the boiler.
6. Start the boiler following the Lighting or Operating
instructions
temperature. Boiler should cycle off. Return dial to
original setting.
2. Inspect and test additional limit controls or low
water cutoffs installed on system.
Figure 26 Automatic air vent, typical
(manual section 8 or 9).
2.
Watch the pressure as the boiler and system heat
up to ensure pressure rise is normal. Too high a rise
would indicate a waterlogged or undersized
expansion tank.
Air vents and air elimination
1. Inspect automatic air vents (if used). Also inspect
air separators to ensure they are operational.
2. The cap must be unscrewed one turn to allow air to
escape.
3. See Figure 26. If the air vent is leaking, remove cap
A and briefly push valve B and then release to clean
the valve seat.
4. Replace cap
and then unscrewing one turn.
A by twisting all the way onto valve B
Limit controls and cutoffs
1. Inspect and test the boiler limit control. Verify
operation by turning control set point below boiler
Part Number 550-110-593/109947
Expansion tank
1. Expansion tanks provide space for water to move in
an out as the heating system water expands due to
temperature increase or contracts as the water cools.
Tanks may be open, closed or diaphragm or bladder
type. See section 3, page 16 of this manual for
suggested best location of expansion tanks and air
eliminators.
Open-type — located above highest radiator or
baseboard unit, usually in the attic or closet. Has a
gauge glass and overflow pipe to a drain.
Closed-type — welded gas tight and located above
boiler. Tank is partially filled with water, leaving an
air cushion for expansion.
•Make sure this type of tank is fitted with a tank
, such as the B & G Tank-Trol or Taco
fitting
Taco-Trol. This fitting reduces gravity
Page 48
GOLD CGa Gas-Fired Water Boiler
Service & maint. — annual start-up continued10b
❏ Check/test . . . . . . .
circulation of air-saturated tank water back to
the system and prevents the air from bubbling
up through the water as it returns from the
system.
•
Do not use automatic air vents in systems
with closed-type tanks.
from the system instead of returning to the tank.
Eventually, the tank will waterlog and no longer
control pressurization. The boiler relief valve
will weep frequently.
Diaphragm- or bladder-type — welded gas tight
with a rubber membrane to separate the tank
pressurizing air and the water. May be located at
any point in the system, but most often found near
the boiler.
•Systems with this type of expansion tank
require at least one automatic air vent,
preferably located on top of an air eliminator,
as shown in examples in manual section
pages 16-25.
2. If relief valve has tended to weep frequently, the
expansion tank may be waterlogged or undersized.
The air will escape
3,
Closed-type tank — tank is most likely
waterlogged. Install a tank fitting if not already
installed. Then check fill level per fitting
manufacturer’s instructions. If fill level is correct,
check tank size against manufacturer’s instructions.
Replace with a larger tank if necessary.
Diaphragm- or bladder-type — first, check tank
size to be sure it is large enough for the system. If
size is too small, add additional tank(s) as necessary
Figure 27 Relief valve, typical
59343
48Part Number 550-110-593/1099
Page 49
Boiler Manual
❏ Review with owner . . . . . . . .
1. Review the
owner.
2. Emphasize the need to perform the maintenance
schedule specified in the
Manual
3. Remind the owner of the need to call in a licensed
User’s Information Manual with the
User’s Information
(and in this manual as well).
contractor should the boiler or system exhibit any
unusual behavior.
4. Remind the owner to follow the proper shutdown
procedure and to schedule an annual start-up at the
beginning of the next heating season.
❏ Cleaning boiler heating surfaces
1. Shut down boiler:
•Follow “
instructions on boiler and Lighting or
Operating instructions
•Do not drain boiler unless it will be exposed to
freezing temperatures. If using antifreeze in
system, do not drain.
2. Follow shutdown procedure.
3. Remove venting system connection to boiler.
4. Remove top jacket panel. Turn back insulation.
5. Remove flue collector. Clean sealant from assembly
and sections.
6. Remove radiation plates hanging between sections.
7. Remove burners from base. Brush and vacuum
burners to remove all dust and lint. Verify that all
burner ports are free of debris.
8. Place newspapers in base of boiler to collect soot.
9. Clean between sections with wire flue brush.
10. Remove newspaper and soot. Vacuum or brush base
To Turn Off Gas to Appliance”
.
and surrounding area.
11. Reinstall radiation plates.
12. Replace collector box/transition assembly. Seal with
sealant. Obtain gas-tight seal to prevent flue gas
spillage and carbon monoxide emissions, resulting
in severe personal injury or death.
13. Replace insulation and jacket top panel.
14. Start up boiler following section
this manual and the boiler Lighting or Operating
instructions
gas combustion. If found, check for proper
combustion and make any necessary adjustments.
. Excessive sooting indicates improper
The boiler contains ceramic fiber
and fiberglass materials. Use care
when handling these materials per
instructions on page 68 of this
manual. Failure to comply could
result in severe personal injury.
6, pages 28-32 of
Troubleshooting — procedure11a
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
Never jumper (bypass) rollout thermal fuse element or
any other device except for momentary testing as
outlined in Troubleshooting Charts. Severe personal
injury, death or substantial property damage can result.
Burner access panel must be in position during boiler
operation to prevent momentary flame rollout on
ignition of main flame. Severe personal injury or
substantial property damage will result.
See pages 50 through 59 for additional troubleshooting
information.
Part Number 550-110-593/109949
Before troubleshooting:
1. Have the following items:
a. Voltmeter that can check 120 VAC and 24
VA C .
b. Microammeter with a minimum scale range
of 0-25.
c. Continuity checker.
d. U-tube manometer.
2. Check for 120 VAC (minimum 102 VAC to
maximum 132 VAC) to boiler.
3. Make sure thermostat is calling for heat and contacts
(including appropriate zone controls) are closed.
Check for 24 VAC between thermostat wire nuts and
ground.
Page 50
GOLD CGa Gas-Fired Water Boiler
50Part Number 550-110-593/1099
Page 51
Boiler Manual
Damper harness
Continuity Table
6 Pin Molex
Pin Number
4 Pin Molex
Pin Number
Pin side of connectors
1
2
3
4
5
6
1
3
4
N/C
2
N/C
59341
Troubleshooting — standing pilot boilers11b
Chart 1 — Standing pilot — Boiler will not fire
Secure connections.
Is damper harness securely plugged in at both ends?
NoYes
Check for loose wire connections or bad relay on
transformer.
Check for open thermostat, LWCO, high limit, spill switch or
rollout thermal fuse element contacts or check for loose
wire connections.
If LWCO, spill switch or rollout thermal fuse
element contacts are open, determine cause
and correct condition. Failure to do so will
cause severe personal injury, death or
substantial property damage.
Check/repair out of round stack section. Does vent damper
rotate open?
NoYes
Replace actuator.
Retest.
Open thermostat contacts for 30 seconds. Vent damper will
rotate to closed position. Close thermostat contacts. Vent
damper will rotate to open position. Is 24VAC present
across gas valve terminals?
No
Yes
Is 24VAC present across transformer terminals C & Y?
NoYes
Is 24VAC present across transformer terminal C and yellow
wire on vent damper connector?
NoYes
Is vent damper rotated open?
No
Is 24VAC present across gas valve terminals?
NoYes
Is main flame on now?
NoYes
Is gas valve cock turned to ON position?
No
Yes
Retest
Yes
Part Number 550-110-593/109951
Check continuity of each wire in damper harness. Does
continuity exist for each wire? See Table below.
No
Replace damper
wiring harness.
Retest.
Replace gas valve.
Retest.
Remove damper harness from
damper harness plug.
TEMPORARILY install jumper
between terminal 2 and
terminal 5 on damper plug in
boiler wiring harness. See
figure, right. Does boiler fire?
NoYes
Yes
Replace damper
actuator. Retest.
Turn gas valve cock to
ON position. Retest.
Replace gas valve.
Retest
Page 52
GOLD CGa Gas-Fired Water Boiler
Troubleshooting — spark-ignited pilot boilers11c
The information on this page and pages 53 through 59
apply only to spark-ignited pilot CGa boilers. These
boilers are equipped with an ignition control module
that has indicator lights to show control status. Charts
through 7, pages 54-59, help you identify problems
based on indicator light conditions.
Make sure ground wiring is installed per wiring
diagram. Good grounding is extremely important for
proper operation.
Solder or water splatter between plugs and circuit
board can cause improper operation of control module.
Place a shield over the boiler internal controls and
components during installation. Failure to comply could
result in severe personal injury, death or substantial
property damage.
Figure 29 CGa Ignition control module
Control indicator lights —
lockout modes
See Charts 2 through 7, pages 54-59 in this section, for
2
detailed troubleshooting procedures.
To reset control after a lockout, turn off power at the
120 VAC service switch or turn down all thermostats.
Wait 45 seconds. Then restore power or call for heat.
POWER light flashing alone
Usually indicates reversed polarity of 120 VAC power
wires.
POWER and TSTAT CIRC lights flashing
Usually indicates stray voltage on external thermostat
circuit wires (usually due to miswired 3-wire zone valve).
POWER
Usually indicates vent damper failed to open within
5 minutes.
POWER
Usually indicates false flame sense or flame sensed when
it shouldn’t be there.
and DAMPER lights flashing
and FLAME lights flashing
Control indicator lights —
non-lockout modes
FLAME light flashing alone
Usually indicates pilot flame was not established within
15 seconds from application of spark. Control will flash
light, but will continue to cycle indefinitely until flame
is established or problem is corrected.
DAMPER light flashing alone
Usually indicates damper opened during run cycle.
Boiler will not lockout, but won’t heat unless problem
is corrected.
Troubleshooting the control
module
See Figure 30, page 53, for location of harness plug
59346
52Part Number 550-110-593/1099
receptacles and plugs on the control module.
Page 53
Boiler Manual
Figure 30 Control module connections
High voltage to
pilot spark electrode
Blue wire to
gas valve PV
Indicator lights
Red wire to
gas valve MV
24 VAC control
circuits
FLAME
DAMPER
LIMIT
TSTAT CIRC
POWER
Black
White
120 VAC H
120 VAC N
120 VAC to
transformer
Black wires to
thermostat circuit
White wire to
gas valve MV/PV
Yellow wires to limit control
and rollout switch
123
4
Connector plug
in vent damper
SJO cable
to J-box
24 VAC Common
Green
24 VAC call for heat
Green
120 VAC H
Entrance
ground
Chassis
ground
120 VAC N
Black
Green
Green
White
120 VAC IN
Red
24 VAC
24 VAC from transformer
(Constant)
24 VAC
4
1
Black
From end switch
2
5
6
24 VAC to
vent damper
Red
Jumpered to pin "4"
3
Green
Brown
High voltage to spark electrode
120 VAC to transformer
120 VAC IN
24 VAC control circuits
24 VAC from transformer
120 VAC H
120 VAC N
Yellow
White
120 VAC to circulator
24 VAC vent damper connections
120 VAC to circulator
59345
Sense wire to flame sensor
Flame sense wire to pilot
Part Number 550-110-593/109953
Page 54
GOLD CGa Gas-Fired Water Boiler
Troubleshooting — spark-ignited pilot boilers11c
Chart 2 — Spark-ignited pilot — Troubleshooting POWER light status
— Usually indicates reversed 120 VAC polarity if POWER light flashes by itself —
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Is POWER light off?
NoYes
Is POWER light...
Flashing
alone
TSTAT CIRC
light flashing
DAMPER
light flashing
FLAME
light flashing
For insufficient heat or no heat problem, go to
Chart 7 if POWER light is on steady, with no other
light flashing.
Flashing with
another light
Chart
3
Chart
4
Chart
5
On steady
(not flashing)
Chart
6
•Make sure service switch or circuit breaker is on or
fuses are good.
•Remove 120 VAC IN plug (Figure 30, Item 3, page
53) on control module.
•Using voltmeter, check across top and bottom pins
of 120 VAC IN plug.
Does voltmeter indicate 120 VAC?
NoYes
Problem is with incoming
electricity. Have licensed
electrician repair circuit.
•Reconnect 120 VAC IN plug.
•Remove 120 VAC transformer PRIMARY plug
(Figure 30, Item 2, page 53) on control module.
•Using voltmeter, check across top and bottom pins
of PRIMARY receptacle.
Does voltmeter indicate 120 VAC?
NoYes
•Usually indicates polarity on incoming 120 VAC power
line is wrong.
•▲TURN OFF POWER▲ at service switch or breaker,
then reverse the HOT and NEUTRAL wires entering
the boiler in the J-box.
•Restore POWER at service switch or breaker.
Is POWER light flashing now?
NoYes
Have system checked by a
licensed electricain.
If problem persists, call your
Boiler should now
operate normally.
local Weil-McLain sales
representative.
Replace control module.
Retest.
•Reinstall 120 VAC transformer PRIMARY plug.
•Remove 24 VAC transformer plug (Figure 30, Item 5,
page 53) on control module.
•Using voltmeter, check across pins of receptacle.
Does voltmeter indicate 120 VAC?
NoYes
Replace transformer.
Retest.
Replace control module.
Retest.
54Part Number 550-110-593/1099
Page 55
Boiler Manual
continued
Chart 3 — Spark-ignited pilot — TSTAT CIRC & POWER lights flashing
— Usually indicates 48 VAC on thermostat circuit (stray voltage) —
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Disconnect the two external wires connected to the boiler
thermostat leads (two black low voltage leads in J-box).
• Connect a voltmeter across these two incoming wires.
Close each thermostat, zone valve and relay in the
external circuit one at a time and check the voltmeter
reading across the wires.
• There should NEVER be a voltage reading.
Did you find a voltage across the two external thermostat circuit wires?
• Leave external boiler thermostat connection wires
disconnected from boiler.
• Troubleshoot the external thermostat circuit until you find
the source of the stray voltage. (Pay close attention to
the wiring connections to 3-wire zone valves.)
• Correct the problem and repeat the voltmeter test above,
verifying there is no longer a voltage reading under any
condition in the external thermostat circuit.
• If a voltage does occur under any condition, check and
correct the external wiring. (This is a common problem
when using 3-wire zone valves.)
• Once the external thermostat circuit wiring is checked and
corrected if necessary, reconnect the external thermostat
circuit wires to the boiler thermostat wires and allow the
boiler to cycle.
NoYes
• If no voltage is found under any condition of the external
thermostat circuit, connect the two boiler thermostat
connection leads together (or jumper the boiler aquastat
T-T terminals).
• Turn off power to the boiler for 1 minute.
• Turn on power and allow boiler to cycle.
Do the
TSTAT
NoYes
and
POWER
lights still flash?
• Boiler should now operate per the normal sequence of
operation shown in Figure 24, page 37.
Part Number 550-110-593/109955
• Replace control module.
• Retest.
Page 56
GOLD CGa Gas-Fired Water Boiler
Troubleshooting — spark-ignited pilot boilers11c
Chart 4 — Spark-ignited pilot — DAMPER light flashing
— If POWER light is flashing: Usually indicates vent damper failed to prove open within 5 minutes —
— If POWER light is steady: Usually indicates vent damper closed during run cycle —
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open. The TSTAT CIRC and LIMIT lights should come on.
Does vent damper operate?
NoYes
• Wait 45 seconds.
Does vent damper operate?
NoYes
• Remove DAMPER plug (
from plug receptacle of control module.
• Place voltmeter leads across the top two pins (1 and 4)
of the DAMPER receptacle.
Does the voltmeter indicate 24 VAC?
NoYes
Are the
• Replace control
module.
• Retest.
TSTAT CIRC
YesNo
Figure 30, Item 6, page 53
• Try reseating plug in
module receptacle and
restart.
• If vent damper still does
not work, replace vent
damper assembly or
actuator.
• Retest.
and
LIMIT
lights on steady?
• Make sure thermostat is
calling for heat. If lights
still don't come on, see
Chart 7.
)
• Wait 5 minutes.
Is
DAMPER
NoYes
• Boiler should be in
normal operating
sequence.
• Observe operation until
thermostat is satisfied.
• Replace vent damper
assembly or actuator.
• Retest.
light flashing?
Does vent damper actuator
indicator show damper is
open?
NoYes
• Remove damper wiring
plug at damper and firmly
reconnect.
• Recheck boiler operation.
• If problem persists,
replace vent damper
assembly or actuator.
56Part Number 550-110-593/1099
Page 57
Boiler Manual
continued
Chart 5 — Spark-ignited pilot — FLAME & POWER lights flashing
— Usually indicates flame sensed when it shouldn't be there —
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Are manual main shutoff valve and gas valve open?
NoYes
• Leave main manual gas valve closed.
• Turn off power to boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Operating instructions in this
manual or on boiler label.
Do
FLAME
• ▲TURN OFF POWER▲
to boiler at service switch
or breaker.
• Open main manual gas
valve.
• Turn on power to boiler
at service switch or
breaker.
• Restart boiler per
operating instructions.
• Perform start-up
procedures in boiler
manual to verify proper
operation.
and
POWER
lights still flash?
YesNo
• Replace control module.
• Retest.
• Allow boiler to continue cycling.
Are
FLAME
• Boiler may now be
operating
normally.
• Perform start-up
procedures in
boiler manual to
verify proper
operation.
No
and
POWER
• Turn off power to the boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Operating instructions in this
manual or on boiler label.
• Look through the pilot inspection port to see if the pilot is
burning.
lights flashing?
Yes
• Replace control
module.
• Retest.
Is pilot burning?
No
• Replace gas valve.
• Retest boiler.
Are
FLAME
• Boiler should now
operate normally.
• Original flashing
FLAME light
caused by gas
valve not
operating
properly.
• See normal
sequence of
operation,
Figure 24,
page 37.
and
No
Yes
POWER
lights flashing?
• Replace control
module.
• Retest.
Yes
Part Number 550-110-593/109957
Page 58
GOLD CGa Gas-Fired Water Boiler
Troubleshooting — spark-ignited pilot boilers11c
Chart 6 — Spark-ignited pilot — FLAME light flashing and POWER light on steady
ALSO — Troubleshooting failure to establish main flame
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Is pilot flame visible through inspection port?• Are main manual shutoff valve and boiler gas valve open?
NoYes
• ▲TURN OFF POWER▲ to boiler at service switch or breaker.
• Open main manual shutoff valve and boiler gas valve (per
Operating instructions in this manual). Wait at least 45
seconds.
• Turn on power at service switch or breaker. Allow boiler to
cycle.
Does
FLAME
NoYes
light flash now?
• Check the voltage across
main gas valve terminals of
the gas valve.
Is 24 VAC present there?
NoYes
• Make sure ground wire
terminal is securely fastened
to control module mounting
screw.
NoYes
• Boiler should be in
• Verify inlet gas pressure at gas
normal operating
sequence.
• Observe operation
until thermostat is
satisfied and blower
has completed its
post-purge cycle.
• ▲TURN OFF POWER▲ to
boiler at service switch or
breaker.
• Remove base access panel
(see Figure 32, page 62 for
location).
• Verify pilot gas line is not
kinked, obstructed or damaged
and is correctly attached to
pilot and gas valve.
• Verify pilot ignition electrode,
electrode ceramic and spark
lead wire from control are in
good condition. Spark gap
should be approximately 1/8".
• Correct any above problems,
replacing pilot if burner or
wiring is damaged.
• Reinstall base access panel to
operate boiler for retest after
any changes or corrections.
• If none of the above corrects
problem, then replace the
control module, reinstall base
access panel, and retest.
valve:
Natural gas — 5.0" w.c. min/14.0"
w.c. max
Propane — 11.0" w.c. min/14.0"
w.c. max
Is gas present at gas valve inlet and
within above range?
Yes
• Contact gas supplier to correct
pressure or gas supply.
• ▲TURN OFF POWER▲ to boiler
at service switch or breaker.
• Remove base access panel (see
Figure 32, page 62 for location).
• Verify pilot burner is securely
attached to pilot bracket, bracket is
securely attached to cross tie, and
there is no corrosion on the parts
which would affect the ground path
for flame sense.
• Verify that pilot flame rod, flame rod
ceramic and lead wire from control
module to flame rod are in good
condition.
• Correct any above problems,
replacing pilot if burner or wiring is
damaged.
No
• If the wiring from the
control module to gas
valve is intact, replace the
control module.
• Retest.
• Verify inlet gas pressure at gas valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and within above range?
No
• ▲TURN OFF POWER▲ to boiler at service switch or breaker.
• Check flame signal — Detach sense lead from igntion control
(
Figure 30, item 8, page 53
• Connect negative lead of MICROAMMETER to control sense
terminal (
MICROAMMETER to sense wire.
• DISCONNECT red wire connected to man gas valve terminal of
the gas valve.
• Turn on power to boiler and allow to cycle. As soon as pilot is
burning, the MICROAMMETER should read at least 1.0
microamp.
• If none of the previous steps
(including replacing pilot)
corrects problem, then replace
the control module, reinstall
base access panel and retest.
Figure 30, item 8, page 53
Is flame signal at least 1.0 microamp?
NoYes
• Check the voltage across
main gas valve terminals of
the gas valve.
Is 24 VAC present there?
NoYes
Yes
).
). Connect positive lead of
• If the wiring from the
control module to gas
valve is intact, replace the
control module and retest.
58Part Number 550-110-593/1099
Page 59
Boiler Manual
continued
Chart 7 — Spark-ignited pilot — Insufficient heat or no heat (POWER light on steady)
Electrical shock hazard — Wherever you see ▲TURN OFF POWER▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Has it been at least 5 minutes since setting thermostat to
call for heat? If not, wait 5 minutes. Is system heating?
• Is thermostat set to call for heat? Remove thermostat
wires at boiler and check continuity across the two wires.
If circuit isn't closed, check external thermostat (zone
valve, relay, etc.) wiring. Correct problems and retry.
• Reconnect external thermostat wiring at boiler.
Is thermostat circuit closed (continuity across wires)?
NoYes
• Boiler is in standby.
Are all red lights off?
NoYes
Wait 30 seconds.
Are all red lights off?
NoYes
Replace control
module. Retest.
• If you have sufficient heat — boiler should be in normal
operating sequence. (See normal sequence of
operation, Figure 24, page 37.)
• If you have less than sufficient heat —
• Set thermostat to call for
heat and recheck
operation.
Is vent or combustion air piping free of blockage?
NoYes
• Correct conditions and
recheck operation.
• See Figure 24, page 37
for normal sequence of
operation.
• Wait for boiler water to cool to temperature 20 to 30 ˚F
lower than temperature set on limit switch.
Contact your Weil-McLain
sales representative.
Are limit switch contacts closed?
NoYes
• Boiler water temperature exceeded
setting on limit switch with thermostat
• Replace
limit switch.
• Retest.
calling for heat. Boiler is OK.
sequence of operation,
• Also check setting on limit switch (should
be above 140˚F.).
(See normal
Figure 24
, p. 37.)
Is boiler System circulator operating?
NoYes
• Remove CIRCULATOR harness plug from
CIRCULATOR plug receptacle (
7, page 53
control module receptacle.
). Check with voltmeter across pins of
Figure 30, Item
Does voltmeter show 120 VAC across pins?
NoYes
• Replace control
module.
• Retest.
• Wait 5 minutes.
NoYes
• Check limit switch
contacts with continuity
checker.
• Repair/replace
• Repair/replace
Is
FLAME
Is
LIMIT
circulator. Retest.
wiring. Retest.
light on?
light on?
• Replace control module.
• Retest.
Are limit switch contacts
closed?
NoYes
Check spill switch and
rollout switch continuity —
are switches closed?
NoYes
• Reset spill switch, or replace
rollout switch.
If rollout thermal fuse element or
spill switch has opened, determine
cause and correct condition.
Failure to do so will cause severe
personal injury, death or
substantial property damage.
• Check any other
limit controls wired
into the limit
circuit. If all are
OK, then replace
control module.
Trim assembly .................................................... 64
Gas control assembly — standing pilot .............. 65
Gas control assembly — spark-ignited pilot....... 65
Replacement parts must be purchased through a local Weil-McLain
distributor. When ordering, specify boiler model and size and include
description and part number of replacement part. Results from using
modified or other manufactured parts will not be covered by warranty and
may damage boiler or impair operation.
Weil-McLain part numbers are found in Weil-McLain Boilers and Controls
Repair Parts Lists.
The boiler contains ceramic fiber and fiberglass materials. Use care when
handling these materials per instructions on page 68 of this manual. Failure
to comply could result in severe personal injury.
60Part Number 550-110-593/1099
Page 61
Page 62
Page 63
Page 64
Page 65
Page 66
GOLDCGa Gas-Fired Water Boiler
Dimensions13a
Figure 36Dimensional drawing —ALL DIMENSIONS IN INCHES
CGa-2552,00044,00052,00044,00046,80039,00038,0001.581.583.384.04"I.D. x 20’
CGa-370,00059,00070,00059,00063,00053,00051,0001.581.683.784.04"I.D. x 20’
CGa-4105,00088,000 105,00088,00094,50079,00077,0002.181.783.784.05"I.D. x 20’
CGa-5140,000117,000 140,000 117,000 126,000 105,000 102,0002.781.883.783.56"I.D. x 20’
CGa-6175,000146,000 175,000 146,000 157,500 131,000 127,0003.381.983.683.26"I.D. x 20’
Input
(Btuh)
DOE
Heating
capacity
(Btuh)
0–2,000 feet
altitude
Input
(Btuh)
Output
(Btuh)
2,000–4,500 feet
altitude
Input
(Btuh)
Output
(Btuh)
Net
I=B=R
ratings
(Btuh)
Boiler
water
content
(gallons)
DOE
Seasonal efficiency
(% A.F.U.E)
SPDNSPDLPIDN
Chimney
and
breeching
size
CGa-7210,000175,000 210,000 175,000 189,000 157,000 152,0003.882.083.683.07"I.D. x 20’
CGa-8245,000204,000 245,000 204,000 220,500 183,000 177,0004.482.183.682.77"I.D. x 20’
Notes
1.See Table 7 for available pilot systems. The suffix shown
in the table is added to the boiler model number. (Not
available for millivolt systems.)
2. Based on standard test procedures prescribed by the
United States Department of Energy.
3. Net I=B=R ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of
1.15. An additional allowance should be made for unusual
piping and pickup loads.
Table 7Ignition system model suffixes
Pilot ignition systemNatural gasPropane gas
Standing pilotSPDNSPDL
Spark-ignited pilotPIDNNot available
Install CGa boilers for residential radiant panel systems, converted gravity heating systems or other low water
temperature applications per instructions in this manual to avoid damage due to condensation.
CGa boilers are CSA design certified for installation on combustible flooring.
CGa boilers are ASME rated for 50 psig working pressure.
Part Number 550-110-593/109967
Page 68
GOLD CGa Gas-Fired Water Boiler — Boiler Manual
68
Part Number 550-110-593/1099
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.