Weil-McLain Gold CGa User Manual

Page 1
Page 2
Boiler Manual
Please read before proceeding
Installer
Read all instructions before installing.
proper order to prevent personal injury or death.
Consider piping and installation when determining boiler location.
•Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
When calling or writing about the boiler— Please have the boiler model number from the boiler rating label and the CP number from the boiler jacket. You may list the CP number in the space provided on the Installation and service certificate found on page 33.
Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.
When servicing boiler —
To avoid electric shock, disconnect electrical supply before performing maintenance.
To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation —
Do not block flow of combustion or ventilation air to boiler.
Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water.
Follow all instructions in
User
This manual is for use only by your qualified
heating installer/service technician.
Please refer to the User’s Information Manual for your reference.
We recommend regular service by a qualified
service technician, at least annually
and/or property may result.
Continual fresh makeup water will reduce boiler
life. Mineral buildup in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.
Do not add cold water to hot boiler. Thermal
shock can cause sections to crack.
Glycol — potential fire hazard —
All glycol is flammable when exposed to high temperatures. If glycol is allowed to accumulate in or around the boiler or any other potential ignition source, a fire can develop. In order to prevent potential severe personal injury, death or substantial property damage from fire and/or structural damage:
.
Boiler water —
Do not use petroleum-based cleaning or sealing compounds in boiler system. Water seal deterioration will occur, causing leakage between sections. This can result in substantial property damage.
Do not use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel
Part Number 550-110-593/1099 5
Never store glycol of any kind near the boiler or any potential ignition source.
Monitor and inspect the system and boiler regularly for leakage. Repair any leaks immediately to prevent possible accumulation of glycol.
Never use automotive antifreeze or ethylene glycol in the system. Using these glycols can lead to hazardous leakage of glycol in the boiler system.
Page 3
Page 4
GOLD CGa Gas-Fired Water Boiler
How it works . . .
Control module
The control module (used on spark-ignited pilot boilers) responds to signals from the room thermostat and boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and vent damper. When room thermostat calls for heat, the control module starts the system circulator and activates the vent damper (causing it to drive open).
When the vent damper has opened completely, the control module opens the pilot valve and activates pilot ignition spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within 15 seconds, the control module will turn off the gas valve, flash the Flame light, and immediately start a new cycle. This will continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven, the control module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve and deactivates the vent damper (causing it to close).
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs, the control module flashes combinations of lights to indicate the most likely reason for the problem. See page 52 for details.
Standing pilot boilers (controls not shown) use the pilot thermocouple to prove flame. If the thermocouple is
satisfied, the gas valve and vent damper will open on a call for heat and close afterwards.
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Draft hood
The draft hood provides a minimum draft for the boiler, assuring adequate air for combustion if installed in accordance with manual and not modified in any way.
Spill switch
The spill switch will shut down the boiler (requiring manual reset of the switch reset button) if the vent system becomes blocked.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting. (The circulator will continue to run as long as there is a call for heat.)
Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and can be mounted on either the boiler supply or return piping. The factory-installed circulator wiring harness provides ample length for either location. NOTE — The control module provides a pump exercising routine. If the boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
Vent damper
The vent damper closes during off cycles to reduce heat loss from the house up the vent.
Other boiler components:
a supply to system b return from system c flue outlet d burner manifold e gas valve
f pressure/temperature gauge g relief valve h air vent connection i flame rollout switch j burner orifice
k pilot burner, typical l stainless steel burners m cast iron boiler sections n flue collector o junction box
2 Part Number 550-110-593/1099
Page 5
GOLD CGa Gas-Fired Water Boiler
Contents
Standing pilot Spark-ignited pilot
How it works 2–3
Hazard definitions 4
Please read before proceeding 5
1. Prepare boiler location 6–11
2. Prepare boiler 12–15
3. Water piping 16–25
4. Gas piping 26
5. Field wiring 27
6. Start-up 28–32
7. Check-out procedure 33
8. Operation — standing pilot boilers
9. Operation — spark-ignited pilot boilers 37–43
10. Service and maintenance 44–49
11. Troubleshooting
12. Replacement parts 60–65
13. Dimensions and ratings 66–67
34–36
49–50, 51 49–50, 51–59
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage. Indicates special instructions on installation, operation or maintenance that are important but
not related to personal injury or property damage.
4 Part Number 550-110-593/1099
Page 6
GOLD CGa Gas-Fired Water Boiler
1a
Prepare boiler location —
codes & checklist
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1–latest edition.
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
Before locating the boiler, check the following:
Check for nearby connection to:
System water piping
Venting connections
Gas supply piping
Electrical power
Check area around boiler. Remove any combustible materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
Boiler must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.
If new boiler will replace existing boiler, check for and correct system problems, such as:
1. System leaks causing oxygen corrosion or section cracks from hard water deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and leak.
Figure 1
Minimum clearances (see page 7)
7
6
3
Top view
6 Part Number 550-110-593/1099
2
Fresh air opening
59305
6
35
7
6
Side elevation
Page 7
Boiler Manual
Prepare boiler location — clearances1b
Service clearances
1. Provide the following clearances for cleaning and servicing the boiler and for access to controls and components:
Clearance from: Minimum
Top
(for cleaning flueways)
Front
(for access to controls and components)
Back 7" Left side Right side 7"
(for cleaning and servicing)
35" 18"
24"
2. Provide at least screwdriver clearance to jacket front panel screws for removal of front panel for inspection and minor service. If unable to provide at least screwdriver clearance, install unions and shutoff valves in system so boiler can be moved for servicing.
Small space installations
1. Provide the following clearances to combustible material for small space installations.
(See Figure 1, page 6):
Clearance from combustible materials (closet installations):
Top
(for cleaning flueways)
Front
(provide means of access)
Back 7" Left side Right side 2"
(provide means of access)
Minimum
35" 3"
6"
Flooring and foundation
Flooring
The CGa boiler is approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
Foundation
1. Provide a solid brick or minimum 2-inch thick concrete foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
2. The minimum foundation size is:
Boiler model
CGa-25 25" 12" CGa-3 25" 12" CGa-4 25" 15" CGa-5 25" 18" CGa-6 25" 21" CGa-7 25" 24" CGa-8 25" 27"
Minimum foundation length
Minimum foundation width
Residential garage installation
Take the following special precautions when installing
Hot water pipes must be at least ¹⁄₂" from
2. combustible material.
the boiler in a residential garage. If the boiler is located in a residential garage, per ANSI Z223.1, paragraph
5.1.9:
3. Single-wall vent pipe must be at least 6 inches from combustible material.
Mount the boiler a minimum of
the floor
of the garage to assure the burner and
18 inches above
ignition devices will be no less than 18 inches above
4. Type B double-wall metal vent pipe — refer to vent manufacturer’s recommendation for clearances
to combustible material.
Part Number 550-110-593/1099 7
the floor.
Locate or protect the boiler so it cannot be damaged by a moving vehicle.
Page 8
GOLD CGa Gas-Fired Water Boiler
Prepare boiler location — vent system1c
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe personal injury or death.
Do not alter boiler draft hood or place any obstruction or non-approved vent damper in breeching or vent system. CSA certification will become void. Flue gas spillage and carbon monoxide emissions will occur causing severe personal injury or death.
When removing boiler from existing common vent system:
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a.
Seal any unused openings in the common venting
system.
Visually inspect the venting system for proper
b.
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
c. Test vent system — Insofar as is practical, close all
building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d.
Place in operation the appliance being inspected.
Follow the lighting/operating instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle.
f. After it has been determined that
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
Any improper operation of common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. Correct by resizing to approach the minimum size as determined using the appropriate tables in Part 11 of that code. Canadian installations must comply with B149.1 or B149.2 Installation Code.
each appliance
Chimney or vent requirements
1. Venting must be installed according to Part 7, Venting of Equipment, of National Fuel Gas Code, ANSI Z223.1-latest edition and applicable building codes. Canadian installations must comply with B149.1 or B149.2 Installation Codes.
2. See Ratings table on page 67 for minimum chimney or vent sizes. A chimney or vent
should extend at least 3 feet above the highest
cap
where it passes through a roof of a building
point
and at least 2 feet higher than any portion of a
building within a horizontal distance of 10 feet
A chimney or vent must not extend less than the distances stated above.
3. A lined chimney is preferred and must be used when required by local, state, provincial and national codes, laws, regulations and ordinances. Vitreous tile linings with joints that prevent retention of moisture and linings made of noncorrosive materials are best. Advice for flue connections and chimney linings can be obtained from local gas utility. wall metal vent pipe or single-wall vent pipe may be used as a liner.
4. Cold masonry chimneys, also known as outside chimneys, typically have one or more walls exposed to outside air. When any atmospheric gas-fired boiler with automatic vent damper is vented through this type of chimney, the potential exists for condensation to occur. Condensation can damage a masonry chimney. Weil-McLain recommends the following to prevent possible damage.
a. Line chimney with corrosion-resistant metal
liner such as AL29-4C® single-wall stainless steel or B-vent. Size liner per National Fuel Gas Code ANSI Z223.1-latest edition.
b. Provide drain trap to remove any condensate.
5. Where two or more gas appliances vent into a common chimney or vent, equivalent area should
at least equal to area of vent outlet on largest
be appliance plus 50 percent of vent outlet area on additional appliance.
without a listed
Type B double-
.
8 Part Number 550-110-593/1099
Page 9
Boiler Manual
1d
Prepare boiler location — air contamination
Please review the following information on potential combustion air contamination problems.
To prevent potential of severe personal injury or death, check for products or areas listed below before installing boiler. If any of these contaminants are found:
remove contaminants permanently
— OR —
isolate boiler and provide outside combustion air. See national, provincial or local codes for further information.
Table 1 Corrosive contaminants and likely locations
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
Permanent wave solutions Swimming pools
Refer to contaminated combustion air.
Table 1 for products and areas which may cause
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers Remodeling areas
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and other similar products
Part Number 550-110-593/1099 9
Page 10
GOLD CGa Gas-Fired Water Boiler
MODEL
CGi
Prepare boiler location — air openings1c
Combustion air and ventilation openings must comply with Section 5.3, Air for Combustion and Ventilation, of National Fuel Gas Code ANSI Z223.1-latest edition, or applicable local building codes. Canadian installations must comply with B149.1 or B149.2 Installation Codes.
Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk of severe personal injury, death or substantial property damage caused by flue gas spillage and carbon monoxide emissions.
Air from inside building
(boiler in interior room - Figure 2)
1. Tightly constructed buildings must be provided with openings to outside for combustion and ventilation air. These openings must be sized to handle all fuel burning appliances, exhaust or ventilation fans and fireplaces.
2. When openings to boiler room are taken to interior spaces, provide two permanent openings:
One air opening within 12 inches of floor.
A second opening within 12 inches of ceiling.
Air directly from outside to boiler room
1. Tightly constructed buildings must be provided with combustion and ventilation air openings to boiler room, which are adequate to handle the boiler needs plus the needs of all other fuel burning appliances, exhaust or ventilation fans and fireplaces.
2. When combustion air is supplied to the boiler space
directly through outside walls (Figure 3): Provide
two permanent openings:
One air opening within 12 inches of floor.
A second opening within 12 inches of ceiling. Each opening must provide a minimum free area
of
1 square inch per 4,000 Btuh of input of all
appliances in room plus requirements for any exhaust fans in room.
Each opening must provide a minimum free area
1 square inch per 1,000 Btuh of input of all
of appliances in room plus requirements for any exhaust fans in room. The interior space supplying combustion and ventilation air must have adequate infiltration from outside.
MODEL
CGi
10 Part Number 550-110-593/1099
Page 11
Boiler Manual
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction where:
a. Walls and ceilings exposed to the outside
atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed, and . . .
b. Weather-stripping has been added on openable
windows and doors, and . . .
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and in other openings.
Other
appliances
CGa boiler
0 to 12"
For buildings with such construction, provide air openings into the building from outside, sized per the appropriate case in
Figure 3 if appliances are to use
inside air for combustion and ventilation.
Air
opening
Air
0 to 12"
Part Number 550-110-593/1099 11
opening
Page 12
GOLD CGa Gas-Fired Water Boiler
2a
Prepare boiler — placement and setup
Place boiler/crate near position
1. Leave boiler in crate and on pallet until installation site is ready.
2. Move entire crate and pallet next to selected location.
3. Remove crate.
4. Remove boiler from pallet as follows:
a. Tilt left side of boiler up and place a board
under left legs.
b. Tilt boiler the other way and place a board
under right legs.
c. Slide boiler backwards off pallet and into
position.
5. Check level.
a. Shim legs, if necessary. b. Do not alter legs.
Leave boiler on pallet.
Do not drop boiler or bump jacket on floor or pallet. Damage to boiler can result.
Inspect orifices and burners
1. Remove front jacket door. Remove base access panel (See Figure 32, item 4, page 62).
2. Check for correctly-sized manifold orifices. See
below for sizing. (The orifice size is stamped on
2
the orifice spud barrel.)
Correctly-sized manifold orifices must be used. Failure to do so will result in severe personal injury, death or substantial property damage.
3. Level and straighten burners.
Burners must be properly seated in slots in burner rest with their openings face up. Main burner orifices must inject down center of
Table
4. Reinstall access panel.
Orifice replacement procedure
(when required)
1. Remove access panel.
2. On gas manifold, mark location of main burner with attached pilot assembly.
3. Remove main burner with attached pilot assembly from manifold. Remove all remaining burners.
4. Remove and discard all main burner orifices in gas manifold.
5. Apply a small amount of pipe dope to each of the new orifices and install in the manifold. Make sure the orifices are aligned correctly, not cross-threaded in the manifold tappings.
6. Reinstall main burner with attached pilot assembly at location marked on gas manifold. Reinstall all remaining burners.
7. Follow check-out procedure, section 7, page 33.
burner. Failure to properly seat burners will result in severe personal injury, death or substantial property damage.
Do not operate boiler without access panel secured in place. Failure to comply could cause momentary flame rollout on ignition of main flame, resulting in possible fire or personal injury hazard.
Use only pipe dope compatible with propane gas, even if boiler is to be operated on natural gas. Failure to comply could result in severe personal injury, death or substantial property damage.
Table 2 Manifold orifice sizing
Location Natural gas Propane gas
U. S.
Canada
Note 1:
12 Part Number 550-110-593/1099
For elevations above 2,000 feet, contact your local Weil-McLain sales office for details.
0-2,000 ft over 2,000 ft 0-2,000 ft over 2,000 ft
2.00 mm (Note 1) 1.30 mm (Note 1)
0-2,000 ft 2,000-4,500 0-2,000 ft 2,000-4,500
2.00 mm 1.90 mm 1.30 mm 1.20 mm
Page 13
Boiler Manual
2b
Prepare boiler — pressure test
Perform hydrostatic pressure test
Pressure test boiler before attaching water or gas piping or electrical supply (except as noted below).
Prepare boiler for test
1. Remove the shipping nipple (from CGa supply tapping) and remove the boiler relief valve.
Temporarily plug the relief valve tapping with a ¾"
NPT pipe plug.
2. Remove 1¼" nipple, reducing tee and drain valve from accessory bag. Install in boiler return connection as shown on page 3 or in Figure 34, item
3, page 64. Install circulator on either the return or
supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/ temperature gauge from accessory bag. Pipe to boiler supply connection as shown in (Use pipe dope sparingly.)
4. Connect a hose to boiler drain valve, the other end connected to a fresh water supply. Make sure hose can also be used to drain boiler after test.
5. Connect a nipple and shutoff valve to system supply connection on the 1¼" tee. This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
Figure 34, page 64.
3. When water flows from shutoff valves, close boiler drain valve.
4. Close shutoff valves.
5. Slowly reopen boiler drain valve until test pressure of not more than 45 psi is reached on the pressure/ temperature gauge.
6. Test at no more than 45 psi for no more than 10
minutes.
Do not leave boiler unattended. A
cold water fill could expand and cause excessive pressure, resulting in severe personal injury, death or substantial property damage.
7. Make sure constant gauge pressure has been maintained throughout test. Check for leaks. Repair if found.
Leaks must be repaired at once.
Failure to do so can damage boiler, resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
6. Connect a nipple and shutoff valve to system return connection (at circulator flange if circulator installed on return). This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
Fill and pressure test
1. Open the shutoff valves you installed on supply and return connections.
2. Slowly open boiler drain valve and fresh water supply to fill boiler with water.
Part Number 550-110-593/1099 13
Drain and remove fittings
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever provides best access to drain. Remove hose after draining if used to drain boiler.
3. Remove nipples and valves unless they will remain for use in the system piping.
4. Remove plug from relief valve tapping. See Section 3 to replace relief valve.
Page 14
GOLD CGa Gas-Fired Water Boiler
14 Part Number 550-110-593/1099
Page 15
Boiler Manual
Prepare boiler — vent damper installation
These systems are used on gas-fired boilers with vent dampers as shipped from factory. Boiler will not operate without vent damper installed.
Only vent dampers listed in the Replacement parts list on page 61 are certified for use with CGa boilers. Any other vent damper installed could cause severe personal injury or death.
Damper blade
Standing pilot ignition systems— Refer to vent
manufacturer’s instructions to install plug (shipped with damper) in damper hole. For standing pilot boilers only, install plug with hole.
Spark-ignited pilot systems— Refer to vent manufacturer’s instructions to install plug (shipped with damper) in damper hole. For spark-ignited pilot boilers only,
install plug with no hole in veper
3
/
" diameter hole in vent damper
8
4. Read and apply the harness plug warning label (shown above) so that it is visible after installation.
5. Plug damper harness receptacle into damper harness
Figure 8 Vent damper assemblies
plug.
Bypassing (jumpering) vent damper will cause flue products such as carbon monoxide to escape into the house. This will cause severe personal injury or death.
After boiler has operated once, if either end of harness is disconnected, the system safety shutdown will occur. The boiler will not operate until harness is reconnected.
Effikal damper — Damper hold
open switch must be in Automatic
Operation position for system to
operate properly.
Part Number 550-110-593/1099 15
Page 16
GOLD CGa Gas-Fired Water Boiler
Water piping — general information3a
General piping information
If installation is to comply with ASME or Canadian requirements, an additional high temperature limit is needed. Install control in supply piping between boiler and isolation valve. Set second control to minimum 20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F. See page 34 or 38, for wiring.
A low water cutoff device is required when boiler is installed above radiation level or by certain state or local codes or insurance companies. Use low water cutoff designed for water installations. Electrode probe-type is recommended. Purchase and install in tee in supply piping above boiler.
backflow check valve in cold water supply as required by local codes.
Use
Pressure/temperature gauge
Install pressure/temperature gauge in tee on supply piping (as shown in drawing on page 3). The gauge well is a self-closing valve, allowing removal of the gauge without draining the system.
Relief valve
Install relief valve vertically in ¾" tapping on side of boiler. See Figure 9 or
and the tag attached to the relief valve for manufacturer’s instructions.
10
To avoid water damage or scalding due to relief valve operation:
Discharge line must be connected to relief valve outlet and run to a
safe place of disposal
possibility of severe burns should the valve discharge.
Discharge line must be as short as possible and be the
the valve discharge connection
Discharge line must pitch downward from the valve and terminate at least 6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler,
or in the discharge line. Do not plug or place any obstruction in the discharge line.
Failure to comply with the above guidelines could result in failure of
the relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.
Test the operation of the valve after filling and pressurizing system
by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
. Terminate the discharge line to eliminate
same size as
throughout its entire length.
System water piping
See Figure 9 (diaphragm-type or bladder-type expansion tank) or tank) on page 21, and Table 3 below, for near-boiler and single-zone systems designed for return water at least 130 °F.
See pages 18-19 to complete multiple-zone piping or pages 20-25 to complete piping for radiant heating systems or converted gravity systems.
Refer to page 25 for boilers used with refrigeration systems.
Boiler model To
CGa-25 ¾" ¾"
CGa-3 1" 1" CGa-4 1" 1" CGa-5 1" 1" CGa-6 1¼" 1¼" CGa-7 1¼" 1¼" CGa-8 1½" 1½"
Note: Circulator flange supplied with boiler is same size as
recommended piping above.
Chilled medium, if used, is piped in parallel with heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. Consult I=B=R Installation and Piping Guides.
If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle. Circulation of cold water through the boiler could result in damage to the heat exchanger, causing possible severe personal injury, death or substantial property damage.
Figure 10 (closed-type expansion
system
From
system
Install boiler such that —
16 Part Number 550-110-593/1099
Page 17
Boiler Manual
3b
Water piping — single-zone system
Expansion tank
Diaphragm-type or bladder-type expansion tank — Figure 9
1. Ensure expansion tank size will handle boiler and system water volume and temperature. Tank must be located in boiler return piping as close to boiler as possible, before inlet side of circulator. See tank manufacturer’s instructions for details.
2. Install an automatic air vent as shown.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual section failure can result.
Use Figure 9 or Figure 10 only for single-zone systems designed for return water at least 130 °F. For systems with low return water temperature possible, such as converted gravity systems and radiant heating systems, refer to the special piping suggestions of pages 20-25. Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Figure 9
Diaphragm- or bladder-type expansion tank
Piping to single-zone system using diaphragm-type or bladder-type expansion tank. See Table 3 for piping sizes.
From system
Cold water fill
To DIAPHRAGM expansion tank and fittings
Closed-type expansion tank — Figure 10
1. Ensure expansion tank size will handle boiler and system water volume and temperature. See tank manufacturer’s instructions for details.
2. Connect tank to ½" NPT tapping located behind supply outlet, using ½" NPT piping. Pitch any horizontal piping up towards tank 1 inch per 5 feet of piping.
Figure 10 Closed-type expansion tank
Piping to single-zone system using closed­type expansion tank. See Table 3 for piping sizes.
CLOSED-type expansion tank
Isolation valve
Isolation valve
From system
Cold water fill
Isolation valve
Relief valve
To system
Circulator*
Isolation valve
To system
Relief
Automatic air vent
D
L O G
CGa
Drain valve
Circulator
*Alternate
59306
Part Number 550-110-593/1099 17
location
valve
Circulator
59307
*Alternate
location
Drain valve
Circulator*
D
L O G
CGa
Page 18
GOLD CGa Gas-Fired Water Boiler
Water piping — multiple zones
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 13 or14 on page 21. Alternatively, use the method of either
(system-bypass), because this method does not control radiant system supply temperature.
17
If radiant system tubing has no oxygen barrier, a
Figure 15 or Figure 16 on page 23. Do not use the piping of Figure
heat exchanger must be used.
18 Part Number 550-110-593/1099
Page 19
Boiler Manual
Typical piping — multiple-zone installations
Figure 11
Zoning with circulators — return water 130 °F or higher.
ZONE 2
ZONE 1
1
2
11
Cold
water
6
9
11
fill
12
10
13
CGa
GOLD
Figure 12
Zoning with zone valves — return water 130 °F or higher.
ZONE 2
ZONE 1
Cold
water
1
6
11
9
11
fill
12
6
Alternate circulator location
10
GOLD
CGa
1 2
3
6
1
5
13
59308
1 Boiler isolation (balancing) valves 2 Flow/check valve 3 System or zone circulator 5 Zone valve 6 Drain valve 9 Relief valve 10 Automatic air vent (with diaphragm-type expansion
59309
11 Fill valve 12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 10.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank circulator or air separator.
tank), or connect to tank fitting (closed-type expansion tank).
DO NOT use an automatic air vent
when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
For systems with possible low return-water temperature (such as converted gravity systems, radiant heating systems and heat pump systems), refer to the special piping suggestions of
Figures 13 – 17, as applies. Failure to prevent sustained low return water temperature to the
boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death or substantial property damage.
Part Number 550-110-593/1099 19
Page 20
GOLD CGa Gas-Fired Water Boiler
3d
Primary/secondary
(preferred) bypass
piping method
Temperature gauges
Water piping — low temp systems
Primary/secondary bypass piping is preferred because the flow rate and temperature drop in
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and temperature distribution.
Figures 13 and 14 show suggested bypass arrangements using primary/secondary bypass
piping (preferred) for low temperature systems such as radiant heating systems or converted
gravity systems
The bypass valves (items system return water — set to assure a minimum return water temperature (at least 130 °F) to the boiler. Set the valves as explained below.
Gauge 4a is suggested, but optional on any system. Gauge 4b is optional on converted gravity systems, but required on radiant heating systems —
to display the water temperature being supplied to the radiant tubing.
8 is required on all systems to assure the return water temperature is accurately set for
Gauge a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return water is cold (approximately 60 °F water temperature).
. For alternatives, see pages 22 through 25.
7a and 7b) provide mixing of hot boiler outlet water with cooler
Valve adjustment
(Figure 13 and 14 only)
1. Set the valves while the system is cool, setting for the coldest expected water temperature (usually 60 °F since the system will often drop to room temperature between cycles).
2. Start with valve
3. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads 130 °F when gauge 4a reads 60 °F.
4. Note that valve 7a regulates the amount of hot water from the boiler supply which mixes with return water. Valve 7b regulates the amount of system water flowing through the boiler secondary loop.
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of
temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control. temperature
Weil-McLain representative for suggested piping and control methods. Failure to
to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
Instead, provide controls and piping which can regulate the boiler return water
prevent cold return water temperature to the boiler could cause corrosion damage
7a fully closed and 7b fully open.
regulating the boiler return water
and the system supply temperature (such as provided by an injection
).
at no less than 130 °F regardless of system supply temperature. Contact your
20 Part Number 550-110-593/1099
Page 21
Boiler Manual
Primary/secondary (preferred) piping —
for radiant heating or converted gravity systems
Figure 13
Zoning with circulators
ZONE 2
ZONE 1
1
Cold
water
4a 4b
2
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
Alternate circulator location
10
GOLD
CGa
13
Figure 14
Zoning with zone valves
ZONE 2
ZONE 1
1 2
3
1
Cold
water
1
4a 4b
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
10
13
Alternate circulator location
GOLD
CGa
3
1
5
1
59310
1 Boiler isolation (balancing) valves 2 Flow/check valve 3 System or zone circulator (circulator should cycle
with zone valve and switches, using circulator valve or zone control panel)
4 System temperature gauges 5 Zone valve 6 Drain valve 7 System temperature valves (see instructions to the
left for adjusting valves)
8 Blend temperature gauge 9 Relief valve
59311
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve 12 Diaphragm-type or bladder-type expansion tank, if
used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 10.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.)
Part Number 550-110-593/1099 21
Page 22
GOLD CGa Gas-Fired Water Boiler
3e
Boiler-bypass piping
method
Temperature gauges
Water piping — low temp systems
This piping method is called a boiler-bypass because part of the circulator flow is bypassed around the boiler (through valve 7a). This method reduces the flow rate throughout the boiler, in order to raise the average water temperature in the boiler enough to prevent flue gas condensation. Boiler-bypass piping is effective for some boilers — including the CGa — provided the flow rates are adjusted according to the instructions following.
Figures 15 and16 are alternative piping suggestions for converted gravity (large water content
or steam systems) or be applied. (Figure 17 is another alternative, using system bypass in place of boiler-bypass piping. protect the radiant system from possible high water temperature.)
Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low as possible, helping to equalize the building heat distribution.
Gauge 4a is optional if the bypass valves will be adjusted using cold (or room temperature) return water to the boiler. (When setting the valves without gauge room temperature water — assume the return water temperature to be 60 °F. Set the valves so gauge
Gauge 4b is optional on converted gravity systems, but required on radiant heating systems — to display the water temperature being supplied to the radiant tubing.
Gauge boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is not installed.
Figure 17 however, is not suitable for radiant heating applications because it does not
8 reads at least 120 °F.
8 is required on all systems to assure reliable adjustment of the bypass valves. The
radiant heating system — for use when primary/secondary piping can’t
4a installed — using cold or
Valve adjustment
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads 60 °F higher than gauge enough flow rate and high enough average temperature to prevent condensation even with low system return water temperature.
3. Valve 7a regulates the system flow rate, while valve 7b regulates the boiler flow rate.
4. The boiler-mounted temperature/pressure gauge may be used in place of a separate gauge 8.
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of
temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control temperature
Weil-McLain representative for suggested piping and control methods. Failure to
to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
and the system supply temperature (such as provided by an injection
. Instead, provide controls and piping which can regulate the boiler return water
prevent cold return water temperature to the boiler could cause corrosion damage
4a. A minimum 60 °F temperature rise through the boiler assures a low
regulating the boiler return water
).
at no less than 130 °F regardless of system supply temperature. Contact your
22 Part Number 550-110-593/1099
Page 23
Boiler Manual
Boiler-bypass (alternate) piping —
for radiant heating or converted gravity systems
Figure 15 Boiler-bypass piping
Zoning with circulators
(Alternative to primary/secondary piping Figures 13 and 14)
ZONE 2
ZONE 1
1
4a 4b
2
7b
10
13
8
GOLD
CGa
Cold
water
11
66
7a
9
11
fill
12
Figure 16 Boiler-bypass piping
Zoning with zone valves
(Alternative to primary/secondary piping Figures 13 and 14)
ZONE 2
1
2
3
4a
Cold
water
11
fill
12
3
ZONE 1
Alternate circulator
location
7a
7b
9
10
11
4b
66
8
GOLD
CGa
5
13
59312
1 Boiler isolation (balancing) valves
59313
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type
2 Flow/check valve 3 System or zone circulator 4 System temperature gauges 5 Zone valve 6 Drain valve 7 System temperature valves (see instructions to the left
for adjusting valves)
8 Blend temperature gauge 9 Relief valve
expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve 12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in
13 Air separator and automatic vent, if used (Note that
Figure 10.)
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.)
Part Number 550-110-593/1099 23
Page 24
GOLD CGa Gas-Fired Water Boiler
3f
System-bypass
piping method
Water piping — low temp systems
This piping method is called a system-bypass because part of the circulator flow bypasses the system (through valve 7a). This bypassed hot water from the boiler outlet mixes with cooler system return water temperature in order to provide minimum 130 °F return water to the boiler. Valve 7b will most often be full open, but may need to be slightly closed on some low pressure drop systems in order to cause enough flow through valve 7a.
Figure 17 is an alternative piping method that provides return water temperature control for
boilers installed on
Do not apply the piping of Figure 17 on radiant heating systems. It provides no method of
regulating the water temperature provided to the system and could result in excessive water temperature in the radiant tubing.
System-bypass piping as shown in Figure 17 can be used with either zone valve or circulator zoning. When used with circulator zoning however, the boiler circulator (item piped as shown. It cannot be used as one of the zoning circulators.
Do not apply system-bypass piping if the reduced flow in the system could cause poor heat distribution. That is, system-bypass piping reduces the flow in the system and increases the water temperature supplied to the system. This can cause increased heat from radiators at the beginning of the system and reduced heat from radiators near the end of the system.
converted gravity systems (large water content or steam systems).
3), must be
Valve adjustment
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve least 130 °F at all times.
3. Valve
4. The valve adjustment should be done with the system at the coldest expected temperature
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of
temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control temperature
Weil-McLain representative for suggested piping and control methods.
7a regulates the amount of boiler supply water mixed with return water. Valve 7b
causes a pressure drop in the system needed to balance flow through valve 7a and the system.
(60 °F for converted gravity systems or high mass radiant systems).
and the system supply temperature (such as provided by an injection
. Instead, provide controls and piping which can regulate the boiler return water
at no less than 130 °F regardless of system supply temperature. Contact your
7a while closing valve 7b until the temperature at gauge 8 reads at
regulating the boiler return water
).
Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
24 Part Number 550-110-593/1099
Page 25
Boiler Manual
3f
System-bypass
(alternate)
piping —
for converted gravity (or steam) systems
Cold
water
59314
fill
11
12
8
7a
To systemFrom system
7b
Alternate circulator location
9
10
CGa
GOLD
Figure 17 System-bypass piping
Zoning with zone valve or circulators, return water 130 °F or higher.
(Alternative to boiler-bypass piping Figures 15 and 16)
3 System or zone circulator 7 System temperature valves (see instructions to the left for
adjusting valves)
8 Blend temperature gauge 9 Relief valve 10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion tank). DO NOT closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve 12 Diaphragm-type or bladder-type expansion tank, if used
(For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 10.)
use an automatic air vent when using
3g
Water piping — Refrigeration system
Figure 18 Piping refrigeration systems
System supply
Circulator
System return
59315
Water chiller
Strainer
Check valve
Expansion tank
Balancing valve
Shut-off valve
Boiler
GOLD
CGa
Prevent chilled water from entering boiler
Install boiler so that chilled medium is piped in parallel with the heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. See typical installation of balancing valve and check valve.
If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle.
Figure 18 for
Part Number 550-110-593/1099 25
Page 26
GOLD CGa Gas-Fired Water Boiler
4
Gas piping
Natural Gas:
1. Refer to on rated boiler input (divide by 1,000 to obtain cubic feet per hour). Table 4 is only for gas with specific
gravity 0.60, with a pressure drop through the
gas piping of 0.30" w.c. For additional gas pipe
sizing information, refer to ANSI Z223.1 (or B149.1 or B149.2 for Canadian installations).
2. Inlet pressure required at gas valve inlet:
Maximum: 13" w.c.
Minimum: 5" w.c.
Manifold gas pressure: 3.5" w.c.
3. Install 100% lockup gas pressure regulator in supply line if inlet pressure exceeds 13" w.c. Adjust for 13" w.c. maximum.
Propane Gas:
1. Contact gas supplier to size pipes, tanks and 100% lockup gas pressure regulator.
Table 4 for pipe length and diameter. Base
Table 4 Pipe capacity for 0.60 specific gravity natural gas
Gas pipe
length
(feet)
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 860
40 63 130 245 500 760
50 56 11 5 215 440 670
75 45 93 175 360 545
100 38 79 150 305 460
150 31 64 120 250 380
½" ¾" 1" 1¼" 1½"
Capacity of pipe for pipe size of:
(Capacity in cubic feet gas per hour)
2. Adjust propane supply regulator provided by gas supplier for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
Maximum: 13" w.c.
Minimum: 11" w.c.
Manifold gas pressure: 10" w.c.
Figure 19 Gas supply piping
Manual main shutoff gas valve (when required)
Ground joint union (when required)
Tee
Nipple
Cap
59322
26 Part Number 550-110-593/1099
Page 27
Boiler Manual
5
Field wiring
For your safety, turn off electrical power supply at
service entrance panel before making any electrical connections
Failure to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
If rollout thermal fuse element wire as supplied with boiler must be replaced, type must be used. If other original wiring as supplied with boiler must be replaced, use only type equivalent.
Boiler must be electrically grounded as required by National Electrical Code ANSI/NFPA 70-latest edition.
Electrical installation must comply with:
1. National Electrical Code and any other national, state, provincial or local codes or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.
Wiring connections
Boiler is shipped with controls completely wired, except spill switch and vent damper. Refer to wiring diagrams shown on page 34 for standing pilot ignition boiler or page 38 for spark-ignited pilot boiler.
to avoid possible electric shock hazard.
200 °C wire or equivalent
105 °C wire or
Thermostat
1. Connect thermostat as shown on wiring diagram on boiler.
2. Install on inside wall away from influences of drafts, hot or cold water pipes, lighting fixtures, television, sunrays or fireplaces.
3. If thermostat has a heat anticipator, set heat anticipator in thermostat to match power requirements of equipment connected to it. If connected directly to boiler, set for 0.1 amps plus gas valve current. See information on the wiring diagram shown in
Figure 25b, page 39. For other
devices, refer to manufacturer’s specifications. Wiring diagram on boiler gives setting for control module and gas valve. Also see instructions with thermostat.
Junction box (furnished)
1. Connect 120 VAC power wiring (Figure 20).
2. Fused disconnect or service switch (15 amp. recommended) may be mounted on this box. For those installations with local codes which prohibit installation of fused disconnect or service switch on boiler, install a 2 x 4 cover plate on the boiler junction box and mount the service switch remotely as required by the code.
Wiring multiple zones
Refer to zone valve manufacturer’s literature for wiring and application. A separate transformer is required to power zone valves. Zoning with circulators requires a relay for each circulator.
Figure 20
Field wiring connections —
service switch and
thermostat (or end switch)
provided by installer
Part Number 550-110-593/1099 27
Service
(not provided)
Field wiring
Factory wiring
120 VAC Hot Neutral
switch
Black White Green
Junction box,
boiler left side
Ground
Thermostat
or end switch
(not provided)
Ground screw Wire nuts
Black Black
Thermostat leads, through jacket left side
59323
Service
switch
(not provided)
Thermostat
or end switch
(not provided)
Page 28
GOLD CGa Gas-Fired Water Boiler
Start-up — preparation6a
Check for gas leaks
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Do not proceed with start-up if there is any indication of a gas leak. Repair any leak at once.
Propane boilers only — Your propane supplier mixes an odorant with the propane to make
its presence detectable. In some instances, the odorant can fade and the gas may no longer have an odor.
Propane gas can accumulate at floor level. Smell near the floor for the gas odorant or any unusual odor. If you suspect a leak, do not attempt to light the pilot.
Use caution when attempting to light the propane pilot. This should be done by a qualified service technician, particularly if pilot outages are common.
Periodically check the odorant level of your gas.
Inspect boiler and system at least yearly to make sure all gas piping is leak-tight.
Consult your propane supplier regarding installation of a gas leak detector. There are some products on the market intended for this purpose. Your supplier may be able to suggest an appropriate device.
Determine if water treatment is needed
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
Verify water chemistry
Consult local water treatment companies for unusually hard water areas (above 7 grains hardness) or low pH water conditions (below 7.0). Boiler water pH of 7.0 to 8.5 is recommended.
Freeze protection (when used)
Use antifreeze made especially for hydronic systems. Inhibited propylene glycol is recommended. Do not use ethylene glycol, automotive or undiluted antifreeze. Severe personal injury or
death can result.
1. Determine antifreeze quantity according to system water content. Boiler water content is
listed on page 67. Remember to include expansion tank water content.
2. Follow antifreeze manufacturer's instructions.
3. A 50% solution of propylene glycol/water provides maximum protection to about -30 °F.
4. Local codes may require
5. When using antifreeze in a system with automatic fill, install a water meter to monitor
water makeup. Glycol will leak before the water begins to leak, causing glycol level to drop. Added water will dilute the antifreeze, reducing the freeze protection level.
back flow preventer or actual disconnect from city water supply.
28 Part Number 550-110-593/1099
Page 29
Boiler Manual
Fill the system with water
1. Close manual and automatic air vents and boiler drain cock.
2. Fill to correct system pressure. Correct pressure will vary with each application. Typical cold water fill pressure for a residential system is 12 psi.
3. Purge air from system:
a. Connect a hose to the purge valve (see drain valves, item 6, in suggested piping diagrams
on pages 17 through 23, water can drain and be seen.
b. Close the boiler or system isolation valve between the purge valve and fill connection
to the system.
c. Close zone isolation valves. d. Open quick-fill valve on cold water makeup line. e. Open purge valve. f. One zone at a time, open the isolation valves. Allow water to run through the zone,
pushing out the air. Run until no noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve and remove the hose. Open all isolation
valves. Watch that system pressure rises to correct cold-fill pressure.
h. After the system has operated for a while, eliminate any residual air by using the manual
air vents located throughout the system.
i. If purge valves are not installed in system, open manual air vents in system one at a
time, beginning with lowest floor. Close vent when water squirts out. Repeat with remaining vents.
Figure 9 through Figure 16). Route hose to an area where
4. Open automatic air vent (diaphragm-type or bladder-type expansion tank systems only) one turn.
5. Open other vents:
a. Starting on the lowest floor, open air vents one at a time until water squirts out. b. Repeat with remaining vents.
6. Refill to correct pressure.
Inspect system water piping
After filling the boiler and system with water, inspect all piping throughout the system for leaks. If found, repair immediately. Repeat this inspection after the boiler has been started and the system has heated up.
Leaks must be repaired at once. Failure to do so can damage the boiler, resulting in substantial
property damage. Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage
to boiler will occur, resulting in substantial property damage.
Part Number 550-110-593/1099 29
Page 30
GOLD CGa Gas-Fired Water Boiler
Start-up — preparation continued6a
Inspect base insulation
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 68 of this manual. Failure to comply could result in severe personal injury.
Failure to replace damaged insulation or reposition insulation can result
in a fire hazard, causing severe personal injury, death or substantial property damage.
Check to make sure insulation is secure against all four sides of the base. If insulation is damaged or displaced,
do not operate boiler. Replace or reposition insulation.
Start-up — operate boiler6b
DO NOT proceed with boiler operation unless boiler and system have been
filled with water and all instructions and procedures of previous manual sections have been completed. Failure to do so could result in severe personal injury, death or substantial property damage. Before starting the boiler . . .
Read manual procedure (see Table 5, below).
Verify the boiler and system are full of water.
Verify the completed.
Table 5 Lighting/Operating instruction location guide
Models Standing pilot Gas Page Spark-ignited pilot Gas Page
Honeywell VR8200/VR8300
CGa-25
to
CGa-6
Robertshaw 7200 Natural 36
CGa-7
Honeywell VR8200/VR8300
to
CGa-8
Robertshaw 7200 Natural 36 White-Rodgers 36C Natural 43
Section 8/9 and the Lighting/Operating instruction
Start-up preparation procedures of Section 6 have been
Natural or Propane
Natural or Propane
35 Honeywell VR8204/VR8304 Natural 40
Robertshaw 7200 Natural 41
White-Rodgers 36E Natural 42
35 Honeywell VR8204/VR8304 Natural 40
30 Part Number 550-110-593/1099
Page 31
Boiler Manual
Start-up — operate boiler continued6b
Start the boiler
Follow the Lighting/Operating Instructions from
Section 8 or 9 to start the boiler. Remove boiler
jacket door and note the gas valve manufacturer and model number. Use only the lighting/operating instruction which applies to this gas valve (see Table
Check system and boiler
Eliminate all system leaks. Continual fresh makeup
water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
If you discover evidence of any gas leak, shut down the boiler at once. Find the leak source with bubble test and repair immediately. Do not start boiler again until corrected. Failure to comply could result in severe personal injury, death or substantial property damage.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.
1. Check system piping for leaks. If found, shut down boiler and repair immediately.
5, page 30). (The lighting instruction label on the
boiler provides the same information.)
See Section 6c, below, if boiler fails to start.
2. Vent air from system using manual vents. Air in the system will interfere with circulation and cause heat distribution problems and noise.
3. Inspect vent system thoroughly for signs of deterioration from corrosion, physical damage or sagging. Verify that masonry chimney liners are in good condition, with no obstructions, and there are no openings into the chimney.
Check around the boiler for gas odor following the
4. procedure of section 6a, page 28 of this manual.
5. Verify operation per section 6d, page 32. Perform check-out procedure in section 7, page 33, and fill in the Installation and service certificate.
Start-up — if boiler doesn’t start . . .6c
Check for:
1. Loose connections, blown fuse or service switch off?
2. High limit switch set below boiler water tempera­ture?
3. Thermostat set below room temperature?
Part Number 550-110-593/1099 31
4. Gas not turned on at meter or boiler?
5. Incoming gas pressure less than: 5" w.c. for natural gas? 11" w.c. for propane gas?
6. If none of the above corrects the problem, refer to
Troubleshooting, section 11, page 49 of this manual.
Page 32
GOLD CGa Gas-Fired Water Boiler
Start-up — verify operation6d
The boiler model suffix will be “SPD”. For spark-ignited pilot boilers (suffix “ operation and lighting/operating information.
PID”), see Section 8 or 9 for
Figure 21 Typical pilot burner flame
Figure 22 Typical main burner flame
32 Part Number 550-110-593/1099
Page 33
Boiler Manual
Check-out procedure — checklist7
Boiler and heat distribution units filled with water? Automatic air vent, if used, open one full turn? Air purged from system? Air purged from gas piping? Piping checked for leaks? Correctly sized manifold orifices installed? Refer to Table 2,
page 12 to check size and fuel type.
Correctly sized manifold orifices must be used. Failure to do so will cause severe personal injury, death or substantial property damage.
Followed lighting/operating instructions on boiler or in
manual section start-up?
Proper burner flame observed? Refer to Check burner flame,
manual section 6d, page 32.
Test limit control — While burners are operating, move
indicator on limit control below actual boiler water temperature. Burners should go off while circulator continues to operate. Raise setting on limit control above boiler water temperature and burners should reignite.
Test additional field-installed controls — If boiler has a low
water cutoff, additional high limit or other controls, test for operation as outlined by manufacturer. Burners should be operating and should go off when controls are tested. When controls are restored, burners should reignite.
Botton on spill switch pushed in? Test ignition system safety device:
a.
Standing pilot — Turn gas cock knob to PILOT
position and extinguish pilot flame. Pilot gas flow should stop in less than 3 minutes. Put system back into operation (see section 6, pages 28-32).
b. Spark-ignited pilot — Connect manometer to outlet
side of gas valve. Start boiler, allowing for normal start­up cycle to occur and main burners to ignite. With main burners on, manually shut off gas supply at manual main shutoff gas valve. Burners should go off.
8, page 34 or section 9, page 37 for proper
Open manual main shutoff gas valve. Manometer should confirm there is no gas flow. Pilot will relight, flame sensing element will sense pilot flame and main burners reignite.
Set limit control(s) to system temperature requirements.
Adjust balancing valves and controls to provide design temperature to system.
For multiple zones, adjust flow so it is about the same in
each zone.
Verify thermostat heat anticipator (if available) set properly?
Refer to
Thermostat(s).
Cycle boiler with thermostat — Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to lowest setting and verify boiler goes off.
Measure natural gas input:
a. Operate boiler 10 minutes. b. Turn off other appliances. c. At natural gas meter, measure time (in seconds)
d. Calculate gas input:
e. Btuh calculated should approximate input rating on
Check manifold gas pressure by connecting manometer to
downstream test tapping on main gas valve. Manifold pressure for natural gas should be 3.5" w.c. and for propane gas should be 10" w.c.
Observe several operating cycles for proper operation. Set room thermostat to desired room temperature. Fill in Installation and service certificate below? Review all instructions shipped with this boiler with owner
or maintenance person. Return instructions to envelope and give to owner or place in pocket inside front panel in boiler.
Field wiring, manual section 5, page 27,
required to use one cubic foot of gas.
3600 x 1000
number of seconds from step c
boiler rating label.
= Btuh
Installation and service certificate
Boiler model __________________ Series __________ CP number ___________ Date installed _______________
Installation instructions have been followed.
Measured Btuh input ____________
Installer ________________________ ________________________________ ______________________________ (company) (address) (phone)
Part Number 550-110-593/1099 33
Check out sequence has been performed.Above information is certified to be correct.Information received and left with owner/maintenance person
_____________________________________
(installer’s signature)
Page 34
GOLD CGa Gas-Fired Water Boiler
Operation — standing pilot boilers8a
Figure 23 Wiring diagram — Standing pilot system
SCHEMATIC WIRING DIAGRAM
ADDITIONAL
LIMITS
(NOTE 6)
EQUIPMENT
GROUND (NOTE 7)
SERVICE SWITCH
(BY OTHERS)
H
N
Y
W
CIRCULATOR
NOTES:
1. ALL WIRING MUST BE INSTALLED IN ACCORDANCE WITH: A. U.S.A. - NATIONAL ELECTRICAL CODE AND ANY OTHER NATIONAL, STATE OR LOCAL
CODE REQUIREMENTS.
B. CANADA - C.S.A. C22.1 CANADIAN ELECTRICAL CODE PART 1 AND ANY OTHER
2. ALL CONTACTS SHOWN WITHOUT POWER APPLIED-OFF SHELF CONDITION.
3. IF ORIGINAL ROLLOUT TFE WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED,
4. REFER TO CONTROL COMPONENT INSTRUCTIONS PACKED WITH BOILER FOR APPLICATION INFORMATION.
5. THERMOSTAT - FOR SINGLE ZONE SYSTEMS, THERMOSTAT ANTICIPATOR SETTING IS 0.40 AMPS.
6. L.W.C.O., ADDITIONAL HIGH LIMIT, ETC., WIRED IN SERIES.
7. DENOTES FIELD INSTALLED CHASSIS GROUND.
o
TYPE 200 C WIRE OR ITS EQUIVALENT MUST BE USED. IF OTHER ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, TYPE 105 C OR ITS EQUIVALENT MUST BE USED.
EMCS - FOR EMCS CONNECTION IN PLACE OF THERMOSTAT, REFER TO
BK
BK
Y
G
BK
W
WIRE NUT
NATIONAL, PROVINCIAL OR LOCAL CODE REQUIREMENTS.
FOR MULTIPLE ZONE SYSTEMS USING ZONE VALVES OR CIRCULATORS, REFER TO COMPONENT MANUFACTURER’S INSTRUCTIONS FOR APPLICATION WIRING AND THERMOSTAT ANTICIPATOR SETTING.
EMCS INSTALLATION/OPERATING MANUAL.
G
C
BK
Y
ELECTRICAL SHOCK HAZARD, CAN CAUSE SEVERE INJURY OR DEATH. DISCONNECT POWER BEFORE INSTALLING AND/OR SERVICING.
SPILL
SWITCH
BK BK
THERMOSTAT
OR EMCS
(NOTE 5)
BK
W
R
TRANSFORMER 120/24 V.A.C.
PLUG-IN DPST RELAY
JUNCTION BOX
LIMIT
CONTROL
ROLLOUT
TFE
THERMO-
COUPLE
o
Y
Y
G
BK
BL
DAMPER
CONNECTOR
GAS
VALV E
PILOT
CGa
CABLE
TO
DAMPER
25 thru 8
H
R C
BL
Y
LADDER WIRING DIAGRAM
120 V.A.C.
SERVICE SWITCH
(BY OTHERS)
CR2
THERMOSTAT
OR EMCS
(NOTE 5)
CR1
ADDITIONAL
LIMITS
(NOTE 6)
SPILL
SWITCH
LOW VOLTAGE FIELD HIGH VOLTAGE FIELD LOW VOLTAGE FACTORY HIGH VOLTAGE FACTORY THERMOCOUPLE
Standing Pilot
Natural Or Propane Gas
Forced Hot Water
G
LIMIT
CONTROL
PRIMARY
24 V.A.C.
1
ROLLOUT
Weil-McLain
PART NUMBER
CIRCULATOR
RELAY COIL
CR
CABLE
TO
DAMPER
536
2
4
6315
FUSE
TFE
2
4
DAMPER
CONNECTOR
A United Dominion Company
500 Blaine St.
Michigan City, IN 46360-2388
550-225-009/0999
N
EQUIPMENT
GROUND (NOTE 7)
34 Part Number 550-110-593/1099
Page 35
Boiler Manual
Lighting instructions — CGa-25 to CGa-88b
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot, which must be lighted
by hand. When lighting the pilot, follow these instructions exactly.
B. Before LIGHTING, smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
C. Use only your hand to push down the reset button or turn the gas
D. Do not use this appliance if any part has been under water.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. Turn gas control knob clockwise
7. When equipped with vent damper, verify damper blade is in full open position.
8. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas,
go to the next step.
Effikal vent damper Model RVGP,
Johnson Controls vent damper
to OFF.
control knob. Never use tools. If the knob or reset button will not operate by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
9. Remove access panel located above burners.
10. Find pilot — follow metal tube from gas control. The pilot is between two burners behind the access panel.
11. Turn gas control knob counterclockwise to PILOT.
12. Push in red reset button and hold. Immediately light the pilot with a match. Continue to hold reset button in for about one (1) minute after the pilot is lit.
13. Release reset button. Pilot should remain lit. If pilot goes out, repeat steps 6 through 13.
If reset button stays depressed after release, stop and
immediately call your service technician or gas supplier.
If the pilot will not stay lit after several tries, turn the
gas control knob clockwise service technician or gas supplier.
14. Replace access panel.
15. Turn gas control knob counterclockwise
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service switch in
18. Set thermostat to desired setting.
19. Replace front panel.
Automatic Operation position.
to OFF and call your
to ON.
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
Part Number 550-110-593/1099 35
3. Remove front panel.
4. Turn gas control knob clockwise
5. Replace front panel.
to OFF.
Page 36
GOLD CGa Gas-Fired Water Boiler
Lighting instructions — CGa-25 to CGa-88b
Standing pilot Gas valve manufacturer Robertshaw
• Natural gas
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot, which must be lighted
by hand. When lighting the pilot, follow these instructions exactly.
B. Before LIGHTING, smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
C. Use only your hand to depress the selector arm. Never use tools. If the
D. Do not use this appliance if any part has been under water.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. Depress and move selector arm left
7. When equipped with vent damper, verify damper blade is in full open position.
Position indicator
(shown in
position)OFF
59332
8. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above. If you don't smell gas,
go to the next step.
Johnson Controls vent damper
to OFF.
Selector arm
Gas valve model(s) 7200
selector arm will not move by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
9. Remove access panel located above burners.
10. Find pilot — follow metal tube from gas control. The pilot is between two burners behind the access panel.
11. Move selector arm on gas control right to SET position.
12. Hold selector arm in the pilot with a match. Continue to hold selector arm to
SET for about one-half (¹⁄₂) minute after the pilot is lit.
13. Release selector arm. If pilot does not remain lit, repeat steps 6 through 13.
If the pilot will not stay lit after several tries, move
selector arm left to OFF and call your service technician or gas supplier.
14. Replace access panel.
15. Turn selector arm left to ON.
16. Turn on all electric power to the appliance.
17. When equipped with Effikal vent damper, place service switch in Automatic Operation position.
18. Set thermostat to desired setting.
19. Replace front panel.
SET position and immediately light
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
36 Part Number 550-110-593/1099
3. Remove front panel.
4. Depress and move selector arm left
5. Replace front panel.
to OFF.
Page 37
Boiler Manual
Operation — spark-ignited pilot boilers9a
Follow all procedures given in this manual and operating instructions when operating the boiler. Failure to do so could result in severe personal injury, death or substantial property damage.
1. Standby: With no call for heat, the vent damper and circulator are deenergized. No gas flows to pilot or main gas valve.
2.
Call for heat (thermostat circuit closes):
a. Vent damper and circulator energized if pilot status
acceptable. Vent damper drives open. When vent damper end switch makes circuit, ignition control begins pilot ignition attempt.
b. Ignition control checks for false flame signal: If
ignition control senses pilot signal when no pilot gas should be present, control will lockout, requiring reset procedure as given in
Figure 24.
3. Pilot ignition: Control module sparks the pilot and opens pilot valve in main gas valve. a. If pilot does light and control module senses flame
current, spark generator is turned off and main valve opens.
b. If pilot does not light within 15 seconds, pilot valve
is closed and spark generator is turned off. Control module waits 5 minutes, then attempts to ignite pilot again. This cycle will continue indefinitely if pilot ignition control does not sense pilot flame.
Main burner operation:
4. a. Control module monitors pilot flame current. If
signal is lost, main valve closes, spark generator activates and sequence returns to step 4.
b. If power is interrupted, control system shuts off
pilot and main gas valves and restarts at step 1 when power is restored.
c. In the event the limit control shuts down the boiler
— The control module closes the main gas valve, but keeps the circulator operating and the vent damper open.
5.
Thermostat satisfied (thermostat circuit opens) —
Pilot and main gas valves are closed — Vent damper is deenergized, and cycles to closed position. Circulator is shut off.
6. Boiler is now in the standby mode.
7. Thermostat anticipator setting: Set thermostat heat anticipator as instructed in
Figure 25b, page 39.
Figure 24 Ignition control module sequence of operation — status light indications
Steps
(Following step 7,cycle goes back to step 1.)
Call for
heat?
POWER TSTAT
CIRC
LIMIT
DAMPER
FLAME
Timing
1. Standby
Waiting for call for heat·
2. Call for heat
· Circulator on
3. Limit circuit
· Limit controls closed
4. Damper circuit
· Damper proven open
5. Pilot flame proven *
· Gas valve open
· Pilot remains on
· Boiler producing heat
6. Limit cycle
· Limit circuit open
· Gas valve closed
7. Flame outage *
· Flame out
· Boiler recycles
8. Thermostat satisfied
· Circulator off
9. Circulator exercise routine
· Circulator turns on for 30 seconds if boiler not operated for 30 days
* If pilot flame is not proven in 15 seconds, control module will flash the FLAME light, but will continue indefinitely with attempts to light the pilot burner.
The control module will not lockout on a failure to establish flame. It will lockout if line voltage polarity is reversed, stray voltage is sensed on thermostat line, or if flame is sensed when it shouldn’t be there. The boiler will reset after these lockouts if any of the following occurs:
• 1 hour waiting period • Opening and closing of thermostat circuit • Removal of 120 VAC power for at least 45 seconds.
NO
YES
YES
YES
YES
YES
YES
NO
NO
or
= "ON"
= "OFF"
15 sec
15 sec
30 sec
59340
Part Number 550-110-593/1099 37
Page 38
GOLD CGa Gas-Fired Water Boiler
Operation — spark-ignited pilot system continued9a
Figure 25a Schematic wiring diagram — Spark-ignited pilot system
White
Red
Plug-in connectors
O FF
O N
38 Part Number 550-110-593/1099
Page 39
Boiler Manual
Figure 25b Ladder wiring diagram — Spark-ignited pilot system
Electrical shock hazard — can cause severe injury or death. Disconnect power before installing or servicing.
Legend for ladder wiring diagram
120 VAC field wiring
Low voltage field wiring
120 VAC factory wiring
Low voltage factory wiring
High voltage spark ignition wiring
Ground connectors
Table G: Gas valve terminals and anticipator settings
PV PV
P 3
Anticipator
amps
0.6
0.8
0.55
0.7
Gas valve
Honeywell VR8204 Honeywell VR8304 Robertshaw 7200 White-Rodgers 36C
* Terminals 2–4 are factory-jumpered on the
White-Rodgers 36C gas valve.
"A" "B" "C"
MV/PV MV/PV
2–4 *
MV
MV
M
C
1
SERVICE
SWITCH
HIGH
VOLTAGE
PILOT
IGNITION
ELECTRODE
120 VAC
CONTROL
MODULE
120 VAC
SECTION
CIRCULATOR
120 VAC
24 VAC
POWER
G
GndNeutralHot
24VAC CONSTANT
1. All wiring must be installed in accordance with: A. U.S.A. — N.E.C.And any other national, state,
or local code requirements.
THERMOSTAT
TSTAT/CIRC
R
B. Canada — C.S.A. C22.1 C.E.C.Part 1 and any other national, provincial, or local code require­ments.
2. Pilot lead wires are not field replaceable. Replace pi­lot assembly if necessary.
3. If any of the original wire as supplied with the ap­pliance must be replaced,use minimum 105 °C wire or equivalent. Exception — wires to a rollout TFE must be 200 °C or equivalent.
4. Thermostat anticipator setting (single zone) — see Table G for anticipator setting, depending on which gas valve is installed in boiler.
ROLLOUT
TFE
Additional
limits
(note 7)
TEMPERATURE
LIMIT SWITCH
WATER
SPILL
SWITCH
LIMIT
R
CONTROL MODULE
LOW VOLTAGE
SECTION
5. For multiple zoning, use either zone valves or circulators. Refer to the component manufac­turer's instructions and this manual for applica­tion and wiring suggestions.
6. Refer to control component instructions packed with the boiler for application information.
7. Wire any additional limit controls (low water cut­off, additional high limit, etc.) in series with boiler limit control as shown.
Part Number 550-110-593/1099 39
DAMPER END SWITCH
(INTERNAL TO DAMPER)
PILOT
FLAME
59347a
SENSOR
HIGH
VOLTAGE
DAMPER
R
FLAME
R
VENT
DAMPER
24VAC CALL FOR HEAT
PILOT GAS
VALVE
"C"
"A"
"B"
MAIN GAS
VALVE
See Table G
Page 40
GOLD CGa Gas-Fired Water Boiler
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to turn the gas control knob. Never use tools. If
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which automatically lights the pilot. by hand.
7. Turn gas control knob clockwise
Open position indicated on damper assembly.
Do not try to light the pilot
to OFF.
the knob will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
8. When equipped with vent damper, verify damper blade is in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Turn gas control knob counterclockwise
11. Turn on all electric power to the appliance.
12. When equipped with switch in Automatic Operation position.
13. Set thermostat to desired setting.
Effikal vent damper, place service
STOP! Follow
to ON.
14. If the appliance will not operate, follow the instructions To
Turn Off Gas To The Appliance
technician or gas supplier.
15. Replace front panel.
and call your service
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove front panel.
40 Part Number 550-110-593/1099
4. Turn gas control knob clockwise to OFF. Do not force.
5. Replace front panel.
Page 41
Boiler Manual
Operating instructions — CGa-25 to CGa-69b
Spark pilot Gas valve manufacturer Robertshaw
• Natural gas
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to depress or move the selector arm. Never use
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which automatically lights the pilot. by hand.
7. Depress and move selector arm to OFF. Note: Selector arm cannot be moved to OFF unless selector arm is depressed slightly. Do not force.
Position indicator
(shown in
Open position indicated on damper assembly.
Do not try to light the pilot
Selector arm
position)OFF
Gas valve model(s) 7200
tools. If the selector arm will not depress or move by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
8. When equipped with vent damper, verify damper blade is in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Move selector arm to
11. Turn on all electric power to the appliance.
12. When equipped with Effikal vent damper, place service switch in Automatic Operation position.
13. Set thermostat to desired setting.
14. If the appliance will not operate, follow the instructions To
Turn Off Gas To The Appliance
technician or gas supplier.
ON.
and call your service
STOP! Follow
59332
15. Replace front panel.
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove front panel.
Part Number 550-110-593/1099 41
4. Depress and move selector arm to
5. Replace front panel.
OFF. Do not force.
Page 42
GOLD CGa Gas-Fired Water Boiler
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot.
Do not try to
C. Use only your hand to turn the gas control knob. Never use tools. If
light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the
OPERATING, smell all around the
D. Do not use this appliance if any part has been under water. floor because some gas is heavier than air and will settle on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to Open position indicated on damper assembly.
6. This appliance is equipped with an ignition device which automatically lights the pilot. by hand.
7. Turn gas control knob clockwise to OFF.
Do not try to light the pilot
the knob will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
8. When equipped with vent damper, verify damper blade is in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
STOP! Follow
go to the next step.
10. Turn gas control knob counterclockwise
to ON.
11. Turn on all electric power to the appliance.
12. When equipped with
Effikal vent damper, place service
switch in Automatic Operation position.
13. Set thermostat to desired setting.
Position indicator
(shown in
position)ON
59333
Gas control knob
14. If the appliance will not operate, follow the instructions
Turn Off Gas To The Appliance
and call your service
technician or gas supplier.
15. Replace front panel.
To
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
4. Turn gas control knob clockwise force.
5. Replace front panel.
3. Remove front panel.
42 Part Number 550-110-593/1099
to OFF. Do not
Page 43
Boiler Manual
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. light the pilot by hand.
B. Before
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
OPERATING, smell all around the
Do not try to
WHAT TO DO IF YOU SMELL GAS
C. Use only your hand to depress or turn the gas control knob. Never
D. Do not use this appliance if any part has been under water.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.
4. Turn off all electrical power to the appliance.
5. When equipped with Johnson Controls vent damper
Model M35, manually rotate damper blade in direction of
arrow to
6. This appliance is equipped with an ignition device which automatically lights the pilot. by hand.
7. Depress gas control knob slightly and turn clockwise to OFF. Note: Knob cannot be turned to OFF unless knob is depressed slightly. Do not force.
Open position indicated on damper assembly.
Do not try to light the pilot
use tools. If the knob will not depress or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
8. When equipped with vent damper, verify damper blade is in full open position.
9. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
"B" in the safety information above. If you don't smell gas,
go to the next step.
10. Turn gas control knob counterclockwise
11. Turn on all electric power to the appliance.
12. When equipped with switch in Automatic Operation position.
13. Set thermostat to desired setting.
Effikal vent damper, place service
STOP! Follow
to ON.
14. If the appliance will not operate, follow the instructions
Turn Off Gas To The Appliance
technician or gas supplier.
15. Replace front panel.
and call your service
To
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove front panel.
Part Number 550-110-593/1099 43
4. Depress gas control knob slightly and turn clockwise to OFF. Do not force.
5. Replace front panel.
Page 44
GOLD CGa Gas-Fired Water Boiler
Service and maintenance — schedule10a
Table 6 Service and maintenance schedules (service technician and user)
Service technician
(see following pages for instructions)
Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners and base
Service:
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
Check/test:
ANNNUAL START-UP
• Gas piping
Owner maintenance
(see CGa User’s Information Manual for instructions)
• Check boiler area
Daily
Monthly
Periodically • Test low water cutoff (if used)
Every 6 months • Operate relief valve
• Check air openings
• Check boiler pressure/ temperature gauge
• Check boiler interior piping
• Check venting system
• Check air vents
• Check boiler relief valve
• Check automatic air vents (if used)
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
End of season • Shut down procedure
Review:
• Review with owner
Follow the Service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death or substantial property damage.
44 Part Number 550-110-593/1099
Page 45
Boiler Manual
Service & maintenance — annual start-up10b
The boiler should be inspected and started annually, at the beginning of the heating season, only by a qualified
service technician
following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
. In addition, the maintenance and care of the boiler designated in Table 6 and explained on the
Inspect . . . . . . . . . .
Reported problems
Inspect any problems reported by owner and correct before proceeding.
Boiler area
1. Verify that boiler area is free of any combustible
materials
liquids.
2. Verify that boiler area (and air intake) is free of any of the contaminants listed in Table 1 on page 9 of this manual. If any of these are present in the boiler intake air vicinity, they must be removed. If they cannot be removed, install combustion air piping to the boiler in accordance with national, provincial or local codes.
Air openings
1. Verify that combustion and ventilation air openings to the boiler room and/or building are open and
unobstructed. Check operation and wiring of
automatic combustion air dampers, if used.
, gasoline and other flammable vapors and
2. Verify that boiler vent discharge and air intake are
clean and free of obstructions.
Flue gas vent system
1. Visually inspect entire flue gas venting system for blockage, deterioration or leakage. Repair any joints that show signs of leakage in accordance with vent manufacturer’s instructions.
2. Verify that masonry chimneys are lined, lining is in good condition, and there are not openings into the chimney.
Failure to inspect for the above
conditions and have them repaired can result in severe personal injury or death.
Pilot and main burner flames
1. Visually inspect pilot burner and main burner flames as directed under section 6d, page 32 of this manual.
Water piping
1. Check the boiler interior piping and all system piping for signs of leaks.
2. Repair any leaks before proceeding.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 68 of this manual. Failure to comply could result in severe personal injury.
Part Number 550-110-593/1099 45
Page 46
GOLD CGa Gas-Fired Water Boiler
Service & maint. — annual start-up continued10b
Inspect . . . . . . . . . .
Electrical shock hazard — Turn off power to the boiler
before any service operation
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Do not use petroleum-based cleaning or sealing
compounds
will occur, resulting in substantial property damage.
Eliminate all system or boiler leaks. Continual fresh
makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure. Leaking water may also cause severe property damage.
in boiler system. Severe damage to boiler
Boiler heating surfaces
1. Disconnect the vent pipe at the boiler draft hood and remove draft hood after turning off power to the boiler.
2. Use a bright light to inspect the boiler flue collector and heating surfaces.
3. If the vent pipe or boiler interior surfaces show evidence of soot, follow
surfaces
collector and clean the boiler if necessary after closer inspection of boiler heating surfaces.
4. If there is evidence of rusty scale deposits on boiler surfaces, check the water piping and control system to make sure the boiler return water temperature is properly maintained (per this manual).
5. Reconnect vent and draft hood. Replace all boiler
in this manual section. Remove the flue
on the boiler except as
Cleaning boiler heating
components before returning to service.
6. Check inside and around boiler for evidence of any leaks from the boiler. If found, locate source of leaks and repair.
Burners and base
1. After turning off power to the boiler, remove the jacket door and base access panel (Figure 32, item 4, page 62).
2. Inspect burners and all other components in the boiler base.
3. If burners must be cleaned, raise rear of each burner to release from support slot, slide forward and remove. Then brush and vacuum the burners thoroughly, making sure all ports are free of debris. Carefully replace all burners, making sure burner with pilot bracket is replaced in its original position and all burners are upright (ports up).
4. Inspect the base insulation.
a. Pay attention to the WARNINGS on page 68
regarding working with insulation materials.
b. Verify that the insulation is intact and secure
against all four sides of the base.
If insulation is damaged or displaced, do not operate the boiler. Replace or reposition insulation as necessary. Failure to replace damaged insulation can result in a fire hazard, causing severe personal injury, death or substantial property damage.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 68 of this manual. Failure to comply could result in severe personal injury.
Service . . . . . . . . . .
Oiled-bearing circulators
1. The circulator shipped with the CGa boiler is water­lubricated. No oiling is required.
46 Part Number 550-110-593/1099
2. Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.
Page 47
Boiler Manual
59342
A
B
Start-up . . . . . . . . .
1. Perform start-up procedures section 6, pages 28-32, including procedure to verify operation of burners and vent damper on page 32.
2. Verify cold fill pressure is correct and that fill system is working properly.
3. Verify antifreeze level (if used) is at the right concentration and that inhibitor level is correct.
Check/test . . . . . . .
Gas piping
1. Sniff near floor and around boiler area for any indication of a gas leak.
2. Test gas piping using bubble test, per section 4, page 26 of this manual, if there is any indication of a leak.
Cold fill and operating pressures
1. While the system is cold, note the pressure reading on the boiler pressure/temperature gauge. Verify that cold fill pressure is correct.
4. Check gas piping, per manual sections 4 and 6, verifying no indications of leakage and all piping and connections are in good condition.
5. Read the Lighting or Operating instructions (manual section 8 or 9) applying to the boiler.
6. Start the boiler following the Lighting or Operating
instructions
temperature. Boiler should cycle off. Return dial to original setting.
2. Inspect and test additional limit controls or low water cutoffs installed on system.
Figure 26 Automatic air vent, typical
(manual section 8 or 9).
2.
Watch the pressure as the boiler and system heat
up to ensure pressure rise is normal. Too high a rise would indicate a waterlogged or undersized expansion tank.
Air vents and air elimination
1. Inspect automatic air vents (if used). Also inspect air separators to ensure they are operational.
2. The cap must be unscrewed one turn to allow air to escape.
3. See Figure 26. If the air vent is leaking, remove cap
A and briefly push valve B and then release to clean
the valve seat.
4. Replace cap and then unscrewing one turn.
A by twisting all the way onto valve B
Limit controls and cutoffs
1. Inspect and test the boiler limit control. Verify operation by turning control set point below boiler
Part Number 550-110-593/1099 47
Expansion tank
1. Expansion tanks provide space for water to move in an out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See section 3, page 16 of this manual for suggested best location of expansion tanks and air eliminators.
Open-type — located above highest radiator or
baseboard unit, usually in the attic or closet. Has a gauge glass and overflow pipe to a drain.
Closed-type — welded gas tight and located above
boiler. Tank is partially filled with water, leaving an air cushion for expansion.
Make sure this type of tank is fitted with a tank , such as the B & G Tank-Trol or Taco
fitting
Taco-Trol. This fitting reduces gravity
Page 48
GOLD CGa Gas-Fired Water Boiler
Service & maint. — annual start-up continued10b
Check/test . . . . . . .
circulation of air-saturated tank water back to the system and prevents the air from bubbling up through the water as it returns from the system.
Do not use automatic air vents in systems with closed-type tanks.
from the system instead of returning to the tank. Eventually, the tank will waterlog and no longer control pressurization. The boiler relief valve will weep frequently.
Diaphragm- or bladder-type — welded gas tight
with a rubber membrane to separate the tank pressurizing air and the water. May be located at any point in the system, but most often found near the boiler.
Systems with this type of expansion tank require at least one automatic air vent, preferably located on top of an air eliminator, as shown in examples in manual section pages 16-25.
2. If relief valve has tended to weep frequently, the expansion tank may be waterlogged or undersized.
The air will escape
3,
Closed-type tank — tank is most likely
waterlogged. Install a tank fitting if not already installed. Then check fill level per fitting manufacturer’s instructions. If fill level is correct, check tank size against manufacturer’s instructions. Replace with a larger tank if necessary.
Diaphragm- or bladder-type — first, check tank
size to be sure it is large enough for the system. If size is too small, add additional tank(s) as necessary
Figure 27 Relief valve, typical
59343
48 Part Number 550-110-593/1099
Page 49
Boiler Manual
Review with owner . . . . . . . .
1. Review the owner.
2. Emphasize the need to perform the maintenance schedule specified in the
Manual
3. Remind the owner of the need to call in a licensed
User’s Information Manual with the
User’s Information
(and in this manual as well).
contractor should the boiler or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
Cleaning boiler heating surfaces
1. Shut down boiler:
Follow “ instructions on boiler and Lighting or
Operating instructions
Do not drain boiler unless it will be exposed to freezing temperatures. If using antifreeze in system, do not drain.
2. Follow shutdown procedure.
3. Remove venting system connection to boiler.
4. Remove top jacket panel. Turn back insulation.
5. Remove flue collector. Clean sealant from assembly and sections.
6. Remove radiation plates hanging between sections.
7. Remove burners from base. Brush and vacuum burners to remove all dust and lint. Verify that all burner ports are free of debris.
8. Place newspapers in base of boiler to collect soot.
9. Clean between sections with wire flue brush.
10. Remove newspaper and soot. Vacuum or brush base
To Turn Off Gas to Appliance
.
and surrounding area.
11. Reinstall radiation plates.
12. Replace collector box/transition assembly. Seal with sealant. Obtain gas-tight seal to prevent flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
13. Replace insulation and jacket top panel.
14. Start up boiler following section this manual and the boiler Lighting or Operating
instructions
gas combustion. If found, check for proper combustion and make any necessary adjustments.
. Excessive sooting indicates improper
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 68 of this manual. Failure to comply could result in severe personal injury.
6, pages 28-32 of
Troubleshooting — procedure11a
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Never jumper (bypass) rollout thermal fuse element or any other device except for momentary testing as outlined in Troubleshooting Charts. Severe personal injury, death or substantial property damage can result.
Burner access panel must be in position during boiler operation to prevent momentary flame rollout on ignition of main flame. Severe personal injury or substantial property damage will result.
See pages 50 through 59 for additional troubleshooting information.
Part Number 550-110-593/1099 49
Before troubleshooting:
1. Have the following items:
a. Voltmeter that can check 120 VAC and 24
VA C .
b. Microammeter with a minimum scale range
of 0-25. c. Continuity checker. d. U-tube manometer.
2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to boiler.
3. Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.
Page 50
GOLD CGa Gas-Fired Water Boiler
50 Part Number 550-110-593/1099
Page 51
Boiler Manual
Damper harness Continuity Table
6 Pin Molex Pin Number
4 Pin Molex Pin Number
Pin side of connectors
1 2 3 4 5 6
1 3 4
N/C
2
N/C
59341
Troubleshooting — standing pilot boilers11b
Chart 1 — Standing pilot Boiler will not fire
Secure connections.
Is damper harness securely plugged in at both ends?
No Yes
Check for loose wire connections or bad relay on transformer.
Check for open thermostat, LWCO, high limit, spill switch or rollout thermal fuse element contacts or check for loose wire connections.
If LWCO, spill switch or rollout thermal fuse element contacts are open, determine cause and correct condition. Failure to do so will cause severe personal injury, death or substantial property damage.
Check/repair out of round stack section. Does vent damper rotate open?
No Yes
Replace actuator. Retest.
Open thermostat contacts for 30 seconds. Vent damper will rotate to closed position. Close thermostat contacts. Vent damper will rotate to open position. Is 24VAC present across gas valve terminals?
No
Yes
Is 24VAC present across transformer terminals C & Y?
No Yes
Is 24VAC present across transformer terminal C and yellow wire on vent damper connector?
No Yes
Is vent damper rotated open?
No
Is 24VAC present across gas valve terminals?
No Yes
Is main flame on now?
No Yes
Is gas valve cock turned to ON position?
No
Yes
Retest
Yes
Part Number 550-110-593/1099 51
Check continuity of each wire in damper harness. Does continuity exist for each wire? See Table below.
No
Replace damper wiring harness. Retest.
Replace gas valve. Retest.
Remove damper harness from damper harness plug. TEMPORARILY install jumper between terminal 2 and terminal 5 on damper plug in boiler wiring harness. See figure, right. Does boiler fire?
No Yes
Yes
Replace damper actuator. Retest.
Turn gas valve cock to ON position. Retest.
Replace gas valve. Retest
Page 52
GOLD CGa Gas-Fired Water Boiler
Troubleshooting spark-ignited pilot boilers11c
The information on this page and pages 53 through 59 apply only to spark-ignited pilot CGa boilers. These boilers are equipped with an ignition control module that has indicator lights to show control status. Charts through 7, pages 54-59, help you identify problems based on indicator light conditions.
Make sure ground wiring is installed per wiring diagram. Good grounding is extremely important for proper operation.
Solder or water splatter between plugs and circuit
board can cause improper operation of control module. Place a shield over the boiler internal controls and components during installation. Failure to comply could result in severe personal injury, death or substantial property damage.
Figure 29 CGa Ignition control module
Control indicator lights — lockout modes
See Charts 2 through 7, pages 54-59 in this section, for
2
detailed troubleshooting procedures. To reset control after a lockout, turn off power at the 120 VAC service switch or turn down all thermostats. Wait 45 seconds. Then restore power or call for heat.
POWER light flashing alone
Usually indicates reversed polarity of 120 VAC power wires.
POWER and TSTAT CIRC lights flashing
Usually indicates stray voltage on external thermostat circuit wires (usually due to miswired 3-wire zone valve).
POWER
Usually indicates vent damper failed to open within 5 minutes.
POWER
Usually indicates false flame sense or flame sensed when it shouldn’t be there.
and DAMPER lights flashing
and FLAME lights flashing
Control indicator lights — non-lockout modes
FLAME light flashing alone
Usually indicates pilot flame was not established within 15 seconds from application of spark. Control will flash light, but will continue to cycle indefinitely until flame is established or problem is corrected.
DAMPER light flashing alone
Usually indicates damper opened during run cycle. Boiler will not lockout, but won’t heat unless problem is corrected.
Troubleshooting the control module
See Figure 30, page 53, for location of harness plug
59346
52 Part Number 550-110-593/1099
receptacles and plugs on the control module.
Page 53
Boiler Manual
Figure 30 Control module connections
High voltage to pilot spark electrode
Blue wire to gas valve PV
Indicator lights
Red wire to gas valve MV
24 VAC control
circuits
FLAME
DAMPER
LIMIT
TSTAT CIRC
POWER
Black
White
120 VAC H
120 VAC N
120 VAC to
transformer
Black wires to
thermostat circuit
White wire to
gas valve MV/PV
Yellow wires to limit control
and rollout switch
123
4
Connector plug in vent damper
SJO cable
to J-box
24 VAC Common
Green
24 VAC call for heat
Green
120 VAC H
Entrance ground
Chassis ground
120 VAC N
Black
Green
Green
White
120 VAC IN
Red
24 VAC
24 VAC from transformer
(Constant)
24 VAC
4
1
Black
From end switch
2
5
6
24 VAC to
vent damper
Red
Jumpered to pin "4"
3
Green
Brown
High voltage to spark electrode
120 VAC to transformer
120 VAC IN
24 VAC control circuits
24 VAC from transformer
120 VAC H
120 VAC N
Yellow
White
120 VAC to circulator
24 VAC vent damper connections
120 VAC to circulator
59345
Sense wire to flame sensor
Flame sense wire to pilot
Part Number 550-110-593/1099 53
Page 54
GOLD CGa Gas-Fired Water Boiler
Troubleshooting spark-ignited pilot boilers11c
Chart 2 — Spark-ignited pilot Troubleshooting POWER light status
— Usually indicates reversed 120 VAC polarity if POWER light flashes by itself —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
Is POWER light off?
No Yes
Is POWER light...
Flashing
alone
TSTAT CIRC
light flashing
DAMPER
light flashing
FLAME
light flashing
For insufficient heat or no heat problem, go to
Chart 7 if POWER light is on steady, with no other
light flashing.
Flashing with
another light
Chart
3
Chart
4
Chart
5
On steady
(not flashing)
Chart
6
Make sure service switch or circuit breaker is on or fuses are good.
Remove 120 VAC IN plug (Figure 30, Item 3, page
53) on control module.
Using voltmeter, check across top and bottom pins of 120 VAC IN plug.
Does voltmeter indicate 120 VAC?
No Yes
Problem is with incoming electricity. Have licensed electrician repair circuit.
Reconnect 120 VAC IN plug.
Remove 120 VAC transformer PRIMARY plug (Figure 30, Item 2, page 53) on control module.
Using voltmeter, check across top and bottom pins of PRIMARY receptacle.
Does voltmeter indicate 120 VAC?
No Yes
Usually indicates polarity on incoming 120 VAC power line is wrong.
TURN OFF POWER at service switch or breaker, then reverse the HOT and NEUTRAL wires entering the boiler in the J-box.
Restore POWER at service switch or breaker.
Is POWER light flashing now?
No Yes
Have system checked by a licensed electricain. If problem persists, call your
Boiler should now operate normally.
local Weil-McLain sales representative.
Replace control module. Retest.
Reinstall 120 VAC transformer PRIMARY plug.
Remove 24 VAC transformer plug (Figure 30, Item 5, page 53) on control module.
Using voltmeter, check across pins of receptacle.
Does voltmeter indicate 120 VAC?
No Yes
Replace transformer. Retest.
Replace control module. Retest.
54 Part Number 550-110-593/1099
Page 55
Boiler Manual
continued
Chart 3 — Spark-ignited pilot TSTAT CIRC & POWER lights flashing
— Usually indicates 48 VAC on thermostat circuit (stray voltage) —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Disconnect the two external wires connected to the boiler thermostat leads (two black low voltage leads in J-box).
• Connect a voltmeter across these two incoming wires. Close each thermostat, zone valve and relay in the external circuit one at a time and check the voltmeter reading across the wires.
• There should NEVER be a voltage reading.
Did you find a voltage across the two external thermostat circuit wires?
• Leave external boiler thermostat connection wires disconnected from boiler.
• Troubleshoot the external thermostat circuit until you find the source of the stray voltage. (Pay close attention to the wiring connections to 3-wire zone valves.)
• Correct the problem and repeat the voltmeter test above, verifying there is no longer a voltage reading under any condition in the external thermostat circuit.
• If a voltage does occur under any condition, check and correct the external wiring. (This is a common problem when using 3-wire zone valves.)
• Once the external thermostat circuit wiring is checked and corrected if necessary, reconnect the external thermostat circuit wires to the boiler thermostat wires and allow the boiler to cycle.
NoYes
• If no voltage is found under any condition of the external thermostat circuit, connect the two boiler thermostat connection leads together (or jumper the boiler aquastat T-T terminals).
• Turn off power to the boiler for 1 minute.
• Turn on power and allow boiler to cycle.
Do the
TSTAT
No Yes
and
POWER
lights still flash?
• Boiler should now operate per the normal sequence of operation shown in Figure 24, page 37.
Part Number 550-110-593/1099 55
• Replace control module.
• Retest.
Page 56
GOLD CGa Gas-Fired Water Boiler
Troubleshooting spark-ignited pilot boilers11c
Chart 4 — Spark-ignited pilot DAMPER light flashing
— If POWER light is flashing: Usually indicates vent damper failed to prove open within 5 minutes — — If POWER light is steady: Usually indicates vent damper closed during run cycle —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open. The TSTAT CIRC and LIMIT lights should come on.
Does vent damper operate?
No Yes
• Wait 45 seconds.
Does vent damper operate?
No Yes
• Remove DAMPER plug ( from plug receptacle of control module.
• Place voltmeter leads across the top two pins (1 and 4) of the DAMPER receptacle.
Does the voltmeter indicate 24 VAC?
No Yes
Are the
• Replace control module.
• Retest.
TSTAT CIRC
Yes No
Figure 30, Item 6, page 53
• Try reseating plug in module receptacle and restart.
• If vent damper still does not work, replace vent damper assembly or actuator.
• Retest.
and
LIMIT
lights on steady?
• Make sure thermostat is calling for heat. If lights still don't come on, see Chart 7.
)
• Wait 5 minutes.
Is
DAMPER
No Yes
• Boiler should be in normal operating sequence.
• Observe operation until thermostat is satisfied.
• Replace vent damper assembly or actuator.
• Retest.
light flashing?
Does vent damper actuator
indicator show damper is
open?
No Yes
• Remove damper wiring plug at damper and firmly reconnect.
• Recheck boiler operation.
• If problem persists, replace vent damper assembly or actuator.
56 Part Number 550-110-593/1099
Page 57
Boiler Manual
continued
Chart 5 — Spark-ignited pilot FLAME & POWER lights flashing
— Usually indicates flame sensed when it shouldn't be there —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
Are manual main shutoff valve and gas valve open?
No Yes
• Leave main manual gas valve closed.
• Turn off power to boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Operating instructions in this manual or on boiler label.
Do
FLAME
TURN OFF POWER to boiler at service switch or breaker.
• Open main manual gas valve.
• Turn on power to boiler at service switch or breaker.
• Restart boiler per operating instructions.
• Perform start-up procedures in boiler manual to verify proper operation.
and
POWER
lights still flash?
YesNo
• Replace control module.
• Retest.
• Allow boiler to continue cycling.
Are
FLAME
• Boiler may now be operating normally.
• Perform start-up procedures in boiler manual to verify proper operation.
No
and
POWER
• Turn off power to the boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Operating instructions in this manual or on boiler label.
• Look through the pilot inspection port to see if the pilot is burning.
lights flashing?
Yes
• Replace control module.
• Retest.
Is pilot burning?
No
• Replace gas valve.
• Retest boiler.
Are
FLAME
• Boiler should now operate normally.
• Original flashing FLAME light caused by gas valve not operating properly.
• See normal sequence of operation, Figure 24, page 37.
and
No
Yes
POWER
lights flashing?
• Replace control module.
• Retest.
Yes
Part Number 550-110-593/1099 57
Page 58
GOLD CGa Gas-Fired Water Boiler
Troubleshooting spark-ignited pilot boilers11c
Chart 6 — Spark-ignited pilot FLAME light flashing and POWER light on steady
ALSO — Troubleshooting failure to establish main flame
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Is pilot flame visible through inspection port?• Are main manual shutoff valve and boiler gas valve open?
No Yes
TURN OFF POWER to boiler at service switch or breaker.
• Open main manual shutoff valve and boiler gas valve (per Operating instructions in this manual). Wait at least 45 seconds.
• Turn on power at service switch or breaker. Allow boiler to cycle.
Does
FLAME
No Yes
light flash now?
• Check the voltage across main gas valve terminals of the gas valve.
Is 24 VAC present there?
No Yes
• Make sure ground wire terminal is securely fastened to control module mounting screw.
NoYes
• Boiler should be in
• Verify inlet gas pressure at gas
normal operating sequence.
• Observe operation until thermostat is satisfied and blower has completed its post-purge cycle.
TURN OFF POWER to boiler at service switch or breaker.
• Remove base access panel (see Figure 32, page 62 for location).
• Verify pilot gas line is not kinked, obstructed or damaged and is correctly attached to pilot and gas valve.
• Verify pilot ignition electrode, electrode ceramic and spark lead wire from control are in good condition. Spark gap should be approximately 1/8".
• Correct any above problems, replacing pilot if burner or wiring is damaged.
• Reinstall base access panel to operate boiler for retest after any changes or corrections.
• If none of the above corrects problem, then replace the control module, reinstall base access panel, and retest.
valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and
within above range?
Yes
• Contact gas supplier to correct pressure or gas supply.
TURN OFF POWER to boiler at service switch or breaker.
• Remove base access panel (see Figure 32, page 62 for location).
• Verify pilot burner is securely attached to pilot bracket, bracket is securely attached to cross tie, and there is no corrosion on the parts which would affect the ground path for flame sense.
• Verify that pilot flame rod, flame rod ceramic and lead wire from control module to flame rod are in good condition.
• Correct any above problems, replacing pilot if burner or wiring is damaged.
No
• If the wiring from the control module to gas valve is intact, replace the control module.
• Retest.
• Verify inlet gas pressure at gas valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and within above range?
No
TURN OFF POWER to boiler at service switch or breaker.
• Check flame signal — Detach sense lead from igntion control (
Figure 30, item 8, page 53
• Connect negative lead of MICROAMMETER to control sense terminal ( MICROAMMETER to sense wire.
• DISCONNECT red wire connected to man gas valve terminal of the gas valve.
• Turn on power to boiler and allow to cycle. As soon as pilot is burning, the MICROAMMETER should read at least 1.0 microamp.
• If none of the previous steps (including replacing pilot) corrects problem, then replace the control module, reinstall base access panel and retest.
Figure 30, item 8, page 53
Is flame signal at least 1.0 microamp?
No Yes
• Check the voltage across main gas valve terminals of the gas valve.
Is 24 VAC present there?
No Yes
Yes
).
). Connect positive lead of
• If the wiring from the control module to gas valve is intact, replace the control module and retest.
58 Part Number 550-110-593/1099
Page 59
Boiler Manual
continued
Chart 7 — Spark-ignited pilot Insufficient heat or no heat (POWER light on steady)
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Has it been at least 5 minutes since setting thermostat to call for heat? If not, wait 5 minutes. Is system heating?
• Is thermostat set to call for heat? Remove thermostat wires at boiler and check continuity across the two wires. If circuit isn't closed, check external thermostat (zone valve, relay, etc.) wiring. Correct problems and retry.
• Reconnect external thermostat wiring at boiler.
Is thermostat circuit closed (continuity across wires)?
No Yes
• Boiler is in standby.
Are all red lights off?
No Yes
Wait 30 seconds. Are all red lights off?
No Yes
Replace control module. Retest.
• If you have sufficient heat — boiler should be in normal operating sequence. (See normal sequence of operation, Figure 24, page 37.)
• If you have less than sufficient heat —
• Set thermostat to call for heat and recheck operation.
• Verify Sequence of operation, Figure 24, page 37.
Is vent or combustion air piping free of blockage?
No Yes
• Correct conditions and recheck operation.
• See Figure 24, page 37 for normal sequence of operation.
• Wait for boiler water to cool to temperature 20 to 30 ˚F lower than temperature set on limit switch.
Contact your Weil-McLain sales representative.
Are limit switch contacts closed?
No Yes
• Boiler water temperature exceeded setting on limit switch with thermostat
• Replace limit switch.
• Retest.
calling for heat. Boiler is OK. sequence of operation,
• Also check setting on limit switch (should be above 140˚F.).
(See normal
Figure 24
, p. 37.)
Is boiler System circulator operating?
No Yes
• Remove CIRCULATOR harness plug from CIRCULATOR plug receptacle (
7, page 53
control module receptacle.
). Check with voltmeter across pins of
Figure 30, Item
Does voltmeter show 120 VAC across pins?
No Yes
• Replace control module.
• Retest.
• Wait 5 minutes.
No Yes
• Check limit switch contacts with continuity checker.
• Repair/replace
• Repair/replace
Is
FLAME
Is
LIMIT
circulator. Retest.
wiring. Retest.
light on?
light on?
• Replace control module.
• Retest.
Are limit switch contacts
closed?
No Yes
Check spill switch and
rollout switch continuity —
are switches closed?
No Yes
• Reset spill switch, or replace rollout switch.
If rollout thermal fuse element or spill switch has opened, determine cause and correct condition. Failure to do so will cause severe personal injury, death or substantial property damage.
• Check any other limit controls wired into the limit circuit. If all are OK, then replace control module.
• Retest.
NoYes
Part Number 550-110-593/1099 59
Page 60
GOLD CGa Gas-Fired Water Boiler
Replacement parts12a
Section assembly ............................................... 61
Base assembly .................................................... 62
Jacket assembly ................................................. 63
Trim assembly .................................................... 64
Gas control assembly — standing pilot .............. 65
Gas control assembly — spark-ignited pilot....... 65
Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part number of replacement part. Results from using modified or other manufactured parts will not be covered by warranty and may damage boiler or impair operation.
Weil-McLain part numbers are found in Weil-McLain Boilers and Controls
Repair Parts Lists.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 68 of this manual. Failure to comply could result in severe personal injury.
60 Part Number 550-110-593/1099
Page 61
Page 62
Page 63
Page 64
Page 65
Page 66
GOLD CGa Gas-Fired Water Boiler
Dimensions13a
Figure 36 Dimensional drawing — ALL DIMENSIONS IN INCHES
6¹⁄₄
T OP VIEW
A
Boiler supply and return tappings are both 1¼" NPT.
Note 1:
See , page 16 for recommended system sup-
Table 3
ply and returnpiping sizes.
Boiler circulator is shipped loose. Circulator may be
Note 2:
mounted on either boiler supply or return piping. Circulator flange provided with boiler is same size as recommended pipe sizein ,page 16.Table3
D
13¹⁄₄
12
23¹⁄₄
NOTE 2
19
13¹¹₁₆
1⁵⁄₈
28³⁄₈
NOTE 2
2³⁄₈
4³⁄₄4³⁄₄
MODEL
CGi
H
19
9
W
F RONT
R IGHT SIDEL EFT SIDE
66 Part Number 550-110-593/1099
Page 67
Boiler Manual
Ratings13b
DOE
Boiler model
number
(Note 1) (Note 2) (Note 3)
CGa-25 52,000 44,000 52,000 44,000 46,800 39,000 38,000 1.5 81.5 83.3 84.0 4"I.D. x 20’
CGa-3 70,000 59,000 70,000 59,000 63,000 53,000 51,000 1.5 81.6 83.7 84.0 4"I.D. x 20’
CGa-4 105,000 88,000 105,000 88,000 94,500 79,000 77,000 2.1 81.7 83.7 84.0 5"I.D. x 20’
CGa-5 140,000 117,000 140,000 117,000 126,000 105,000 102,000 2.7 81.8 83.7 83.5 6"I.D. x 20’
CGa-6 175,000 146,000 175,000 146,000 157,500 131,000 127,000 3.3 81.9 83.6 83.2 6"I.D. x 20’
Input
(Btuh)
DOE
Heating
capacity
(Btuh)
0–2,000 feet
altitude
Input
(Btuh)
Output
(Btuh)
2,000–4,500 feet
altitude
Input
(Btuh)
Output
(Btuh)
Net
I=B=R
ratings
(Btuh)
Boiler water
content
(gallons)
DOE
Seasonal efficiency
(% A.F.U.E)
SPDN SPDL PIDN
Chimney
and
breeching
size
CGa-7 210,000 175,000 210,000 175,000 189,000 157,000 152,000 3.8 82.0 83.6 83.0 7"I.D. x 20’
CGa-8 245,000 204,000 245,000 204,000 220,500 183,000 177,000 4.4 82.1 83.6 82.7 7"I.D. x 20’
Notes
1.See Table 7 for available pilot systems. The suffix shown
in the table is added to the boiler model number. (Not available for millivolt systems.)
2. Based on standard test procedures prescribed by the United States Department of Energy.
3. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of
1.15. An additional allowance should be made for unusual piping and pickup loads.
Table 7 Ignition system model suffixes
Pilot ignition system Natural gas Propane gas
Standing pilot SPDN SPDL
Spark-ignited pilot PIDN Not available
Install CGa boilers for residential radiant panel systems, converted gravity heating systems or other low water temperature applications per instructions in this manual to avoid damage due to condensation.
CGa boilers are CSA design certified for installation on combustible flooring. CGa boilers are ASME rated for 50 psig working pressure.
Part Number 550-110-593/1099 67
Page 68
GOLD CGa Gas-Fired Water Boiler — Boiler Manual
68
Part Number 550-110-593/1099
Loading...