Weil-McLain CGS 550-110-260-02002 User Manual

Page 1
Page 2
GOLD CGs Gas-Fired Water Boiler
How it works . . .
Control module
The control module responds to signals from the room thermostat, air pressure switch and boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and inducer. When room thermostat calls for heat, the control module starts the system circulator and inducer.
The control module runs the inducer long enough to purge the boiler flue passages, then opens the pilot valve and activates pilot ignition spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within 15 seconds, the control module will turn off the gas valve, flash the Flame light, and then enter a 15-second postpurge. The control module will then start a new cycle. This will continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven, the control module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve, operates the inducer for a 15-second postpurge and waits for the next heat call.
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs, the control module flashes combinations of lights to indicate the most likely reason for the problem (see page 43).
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Inducer
The inducer pulls flue gases through the boiler, causing air to be pulled in through the air intake opening. The inducer pushes the flue gases through the vent pipe as well.
Air pressure switch
The air pressure switch signals the control module, telling the control module whether air is moving through the inducer.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting. (The circulator will continue to run as long as there is a call for heat.)
Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and can be mounted on either the boiler supply or return piping. The factory­installed circulator wiring harness provides ample length for either location. NOTE — The control module provides a pump exercising routine. If the boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
Other boiler components:
a supply to system
b return from system
c combustion air inlet
d flue outlet
e gas valve
f pressure/temperature gauge
g relief valve (not visible)
h air vent connection
i flame rollout switch
j air inlet box
k pilot burner and bracket
l stainless steel burners
m cast iron boiler sections
n flue collector
o junction box
2
Part number 550-110-260/0200
Page 3
Page 4
GOLD CGs Gas-Fired Water Boiler
Contents
How it works .................................................................. 2–3
Hazard definitions.............................................................. 4
Please read before proceeding ......................................... 5
1. Prepare boiler location ............................................ 6–11
2. Prepare boiler......................................................... 12–13
3. Water piping........................................................... 14–23
4. Venting & combustion air............................................ 24
5. Gas piping .............................................................. 24–25
6. Field wiring................................................................... 26
7. Start-up .................................................................. 27–29
8. Check-out procedure ................................................... 30
9. Operation ............................................................... 31–34
10. Service and maintenance.................................... 35–40
11. Troubleshooting .................................................. 41–51
12. Replacement parts............................................... 52–57
13. Dimensions and ratings ...................................... 58–59
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
4
Part number 550-110-260/0200
Page 5
Boiler Manual
Please read before proceeding
Installer
Read all instructions before installing.
proper order to prevent personal injury or death.
Also refer to CGs Venting Supplements.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
When calling or writing about the boiler— Please have the boiler model number from the boiler rating label and the CP number from the boiler jacket. You may list the CP number in the space provided on the Installation and service certificate found on page 30.
Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.
When servicing boiler —
To avoid electric shock, disconnect electrical supply before performing maintenance.
To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation —
Do not block flow of combustion or ventilation air to boiler.
Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water.
Boiler water —
Do not use petroleum-based cleaning or sealing compounds in boiler system. Water seal deterioration will occur, causing leakage between sections. This can result in substantial property damage.
Do not use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel and/or property may result.
Follow all instructions in
User
This manual is for use only by your qualified
heating installer/service technician.
Please refer to the User’s Information Manual for your reference.
We recommend regular service by a qualified
service technician, at least annually
Continual fresh makeup water will reduce boiler
life. Mineral buildup in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.
Do not add cold water to hot boiler. Thermal
shock can cause sections to crack.
Glycol — potential fire hazard —
All glycol is flammable when exposed to high temperatures. If glycol is allowed to accumulate in or around the boiler or any other potential ignition source, a fire can develop. In order to prevent potential severe personal injury, death or substantial property damage from fire and/or structural damage:
Never store glycol of any kind near the boiler or
any potential ignition source.
Monitor and inspect the system and boiler
regularly for leakage. Repair any leaks immediately to prevent possible accumulation of glycol.
Never use automotive antifreeze or ethylene
glycol in the system. Using these glycols can lead to hazardous leakage of glycol in the boiler system.
.
Part number 550-110-260/0200
5
Page 6
GOLD CGs Gas-Fired Water Boiler
1a
Prepare boiler location —
Installations must
follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1 – latest edition.
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
The CGs boiler gas manifold and controls met safe lighting and other performance criteria when boiler underwent tests specified in ANSI Z21.13 — latest edition.
codes & checklist
Before locating the boiler,
check the following:
Check for nearby connection to:
System water piping
Venting connections
Gas supply piping
Electrical power
Check area around boiler. Remove any combustible materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
Boiler must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.
If new boiler will replace existing boiler, check for and correct system problems, such as:
1. System leaks causing oxygen corrosion or section cracks from hard water deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and leak.
6
Part number 550-110-260/0200
Page 7
Boiler Manual
Prepare boiler location — clearances1b
Provide the following clearances:
1. Hot water pipes — at least ½" from combustible materials.
2. Recommended service clearances — See Figure 1.
3. Minimum clearances for tight spaces — See
Figure 2.
Figure 1 Recommended clearances for service
Figure 2 Minimum clearances for tight spaces
Flooring and foundation
Flooring
The CGs boiler is approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
Foundation
Provide a solid brick or minimum 2-inch thick concrete foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
The minimum foundation size is
Boiler model number Width — Inches
CGs-3 15
CGs-4 18
CGs-5 21
CGs-6 24
25" long by:
Part number 550-110-260/0200
Residential garage installation
Precautions
Take the following special precautions when installing the boiler in a residential garage. If the boiler is located in a residential garage, per ANSI Z223.1, paragraph
5.1.9:
Mount the boiler a minimum of 18 inches
above the floor
burner and ignition devices will be no less than 18 inches above the floor.
Locate or protect the boiler so it cannot be damaged by a moving vehicle.
of the garage to assure the
7
Page 8
GOLD CGs Gas-Fired Water Boiler
1c
Prepare boiler location — vent system
Removing from existing vent
Do not install the CGs into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
When removing boiler from existing common vent system:
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common venting
system.
Visually inspect the venting system for proper
b.
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
c.
Test vent system — Insofar as is practical, close
all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning
each appliance
appliance to their previous conditions of use.
Any improper operation of common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 — latest edition. Correct by resizing to approach the minimum size as determined using the appropriate tables in Part 11 of that code. Canadian installations must comply with B149.1 or B149.2 Installation Code.
CGs special vent system
Vent system
The CGs boiler requires a special vent system, designed for pressurized venting. Model CGs-3 is rated ANSI Z21.13 Category IV (pressurized vent, likely to condense in the vent). Models CGs-4, -5 and -6 are rated Z21.13 Category III (pressurized vent).
You may use any of the vent systems covered by the CGs Venting Supplements included in the envelope assembly. The CGs vent starter is a special item, designed only for the CGs boiler, available from each vendor. Do not attempt to connect the vent to the CGs boiler with any other means.
DO NOT mix components from
different systems. The vent system could fail, causing leakage of flue products into the living space.
Vent termination and combustion air supply
The CGs boiler may be vented through the roof or through a side wall. Follow the appropriate vent supplement for the vent system chosen. The maximum vent length depends on boiler size. Refer to the vent supplement to determine acceptable vent length.
Combustion air for the CGs boiler may be from inside or ducted directly to the boiler from outside. For outside air (direct vent installation), two options are available for the flue/air termination. The air supply must
ALWAYS terminate at the same location as the
flue, using either:
1. Vertical direct vent installation. Obtain the Weil- McLain Through-Roof or Through-Unused
Chimney Vertical Direct Venting Venting Supplement, packed
with the kit, and to the vent manufacturer’s instructions for the vent material chosen.
2. Sidewall direct vent installation. Use the Vent/Air
Intake
Refer to
Exhaust Venting: Vertical or Sidewall
Supplement shipped with the boiler.
termination kit and supplement. Refer to
termination kit shipped with the boiler.
CGs Direct Venting: Sidewall & Direct
Venting
8
Part number 550-110-260/0200
Page 9
Boiler Manual
1d
Prepare boiler location — contamination
Air contamination
Please review the following information on potential combustion air contamination problems.
If the boiler is installed in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must pipe combustion air to the boiler air intake. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death or substantial property damage. Do not install CGs boiler in a
room or pool facility, for example, without using ducted outside air. These areas will always
contain contaminants.
Table 1 Corrosive contaminants
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
Permanent wave solutions Swimming pools
Refer to Table 1 for products and areas which may cause contaminated combustion air.
laundry
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers Remodeling areas
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and other similar products
Part number 550-110-260/0200
9
Page 10
GOLD CGs Gas-Fired Water Boiler
Prepare boiler location — air openings1e
CGs combustion air options
Using inside air — direct exhaust vent
The CGs boiler can use inside air if no contaminants are present in the boiler space. If contaminants are likely to be present, install the CGs boiler as a direct vent appliance, using the appropriate vent supplement and the instructions in this manual.
Using outside air — direct vent
Combustion air can be ducted directly from outside to the CGs boiler air intake fitting. This method is defined as combustion). Refer to the appropriate vent supplement and the instructions in this manual. Two options are available: sidewall or vertical direct vent. Each requires a special vent component kit.
direct vent (also referred to as sealed
Sizing air openings
Air openings provide for ventilation (as well as combustion air) to prevent overheating of the boiler controls and boiler space. Air is also needed for other appliances located in the same space.
Figure 3, selecting the appropriate installation
Use conditions. Note that the sizing given in Figure 3 applies only to CGs installations with clearances no
smaller than shown in Figure 1, page 7 of this manual.
For smaller clearances, regardless of how the air openings are arranged, two openings providing free area of 1 square inch per 1,000 Btuh input of all appliances in the space are required.
Air openings must be sized to handle all appliances and air movers (exhaust fans, etc.) using the air supply.
Louver allowance
The free area of openings means the area after
reduction for any installed louvers or grilles
to consider this reduction when sizing the air openings.
. Be sure
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction where:
a. Walls and ceilings exposed to the outside
atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed, and . . .
b. Weather-stripping has been added on openable
windows and doors, and . . .
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and in other openings.
For buildings with such construction, provide air openings into the building from outside, sized per the appropriate case in inside air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative pressure unless all appliances are installed as direct vent. Always provide air openings sized not only to the dimensions required for the firing rate of all appliances, but also to handle the air movement rate of the exhaust fans or air movers using air from the building or space.
Motorized air dampers
Figure 3 if appliances are to use
10
The sizing given in Figure 3 is based on the National Fuel Gas Code, ANSI Z223.1, allowing adequate air opening for gravity-vented gas appliances (Category I). The CGs boiler is rated Category III or IV (pressurized vent), and has different requirements for combustion and ventilation air, reflected by the special sizing instructions given in Figure 3. The air openings recommended in Figure 3 will allow adequate ventilation and combustion air provided the boiler room is not subjected to negative pressure due to exhaust fans or other mechanical ventilation devices. Refer to the National Fuel Gas Code for dealing with other conditions.
If the air openings are fitted with motorized dampers, electrically interlock the damper to:
Prevent the boiler from firing if the damper is not fully open.
Shut the boiler down should the damper close during boiler operation.
To accomplish this interlock, wire an (proving the damper open) in series with the thermostat input to the boiler. The boiler will not start if this contact is open, and will shut down should it open during operation.
Part number 550-110-260/0200
isolated contact
Page 11
Boiler Manual
Figure 3 Sizing air openings for CGs installations
Room Air Openings
Required area of the air openings given in this table are free area — after the correction for louver obstruction. (See below.)Exception
Apply this table only to installations with clearances no smaller than those shown in Figure 1, page 7 of this manual.
For installations with clearances less than shown in Figure 1, page 7 of this manual, provide 2 openings, each with 1 square inch of free area per 1,000 Btuh of total input of all appliances.
A
Air from Inside
CGs
B
Air
Directly
from
CGs
Outside
12”
Max
12”
Max
Air
opening
Air
opening
12”
Max
opening
opening
12”
Max
Inside
Air
Air
Direct exhaust vent installation
(CGs using room air for combustion)
Other
appliances
CGs CGs
Room
with other appliances
2 Openings — each opening:
1 square inch
free area per
Outside
1,000
Btuh input of
other appliances
shared Room
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
of
plus CGs
2 Openings — each opening:
1 square inch
free area per
Outside
4,000
Btuh input of
other appliances
2 Openings — each opening:
1 square inch
free area per
4,000
of
plus CGs
Direct vent installation
(combustion air piped to CGs)
Combustion
Other
appliances
alone CGs
in room
with other appliances
air piping
CGs
shared
2 Openings —
each opening:
1 square inch
free area per
1,000
Btuh input
CGs
Btuh input of other appliances only (not )
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
Btuh input of other appliances only (not )
CGs
Combustion
air piping
CGs
alone
in room
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
C
Air from
Outside
Through horizontal ducts
CGs
Outside or ventilated attic
D
Air from or
Outside Attic
Lower Opening in Floor or Vertical Duct
CGs
Ventilated
crawl space
26007
Exception to combustion air opening rules:
NO Openings are
needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
Max
Max
12”
12”
Max
Air
opening
Air
opening
12”
Duct
2 Openings — each opening:
Duct
1 square inch
Inside
Duct
free area per
Outside
2,000
other appliances
plus CGs
Btuh input of
2 Openings — each opening:
1 square inch
free area per
Outside
4,000
Or
Btuh input of
other appliances
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
of
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
of
plus CGs
combustion air openings are needed when theboiler (and other appliances) are installed ina space with a volume
NO NO LESS
(1,000's of Btuh) andmultiply this numbertimes 50. (see page 10).
Example:
than 50 cubic feet per 1,000 Btuh of all installed appliances. Sum the total input of all appliances in MBH
Building must not be of Tight construction
For total input of 100 MBH (100,000 Btuh), minimum volume is 50 x 100 = 5,000 cubic feet. At a ceiling
2 Openings — each opening:
1 square inch
free area per
2,000
Btuh input of other appliances only (not )
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input of other appliances only (not )
CGs
height of 8feet, space must have at least 5,000÷8=625square feet (25feet x 25 feet, for instance).
Part number 550-110-260/0200
11
Page 12
GOLD CGs Gas-Fired Water Boiler
Prepare boiler — placement & setup2a
Place boiler/crate near position
1. Leave boiler in crate and on pallet until installation site is ready.
2. Move entire crate and pallet next to selected location.
3. Remove crate.
4. Remove boiler from pallet.
Do not drop boiler or bump jacket on floor or pallet. Damage to boiler can result.
a. Tilt left side of boiler up and place a board
under left legs.
b. Tilt boiler the other way and place a board
under right legs.
c. Slide boiler backward off pallet and into
position.
5. Check level.
a. Shim legs, if necessary.
b. Do not alter legs.
Inspect orifices and burners
1. Remove front jacket door. Remove inlet air box top panel (see Figure 27, item 13, page 54).
death or substantial property damage.
3. Reinstall inlet air box top panel.
Inlet air box top panel must be in position during boiler operation. Failure to do so could result in severe personal injury, death or substantial property damage.
Orifice replacement procedure
(when required)
1. Remove the screws securing the inlet air box top panel.
2. Remove inlet air box top panel and inspect the fiber gasket. Verify the gasket is in good condition and can seal around the complete perimeter of the air box. Replace the gasket if necessary.
3. Using a 7/16" open-end wrench, remove the burner orifices from the manifold.
4. Apply a small amount of pipe dope to each of the new orifices and install in the manifold using a 7/16" open-end wrench. Make sure the orifices are aligned correctly, not cross-threaded in the manifold tappings.
Use only pipe dope compatible with propane gas, even if boiler is to be operated on natural gas. Failure to comply could result in severe personal injury, death or substantial property damage.
12
2. Check for correctly-sized manifold orifices. See
Table 2 for sizing. (The orifice size is stamped on
the orifice spud barrel.)
Correctly-sized manifold orifices must be used. Failure to do so will result in severe personal injury,
Table 2 Manifold orifice sizing
Location Natural gas Propane gas
0-2,000 ft over 2,000 ft 0-2,000 ft over 2,000 ft
U. S.
2.70 mm (Note 1) 1.65 mm (Note 1)
0-2,000 ft 2,000-4,500 0-2,000 ft 2,000-4,500
Canada
2.70 mm #38 1.65 mm #53
Note 1: For elevations above 2,000 feet, contact your local Weil-McLain sales office for details.
5. Carefully replace the inlet air box top panel, making sure the gasket is in place will seal all around the perimeter.
6. Follow the check-out procedure, section to assure the boiler is now operating properly after orifices are replaced.
8 page 30,
Part number 550-110-260/0200
Page 13
Boiler Manual
2b
Prepare boiler — pressure test
Perform hydrostatic pressure test
Pressure test boiler before attaching water or gas piping (except as noted below) or electrical supply.
Prepare boiler for test
1. Remove the shipping nipple (from CGs supply tapping) and remove the boiler relief valve.
Temporarily plug the relief valve tapping with a ¾" NPT pipe plug.
2. Remove 1¼" nipple, reducing tee and drain valve from accessory bag. Install in boiler return connection as shown on page 3 and the return or supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature gauge from accessory bag. Pipe to boiler supply connection as shown on page 3 and Figure 29, page 56. (Use pipe dope sparingly.)
4. Connect a hose to boiler drain valve, the other end connected to a fresh water supply. Make sure hose can also be used to drain boiler after test.
5. Connect a nipple and shutoff valve to system supply connection on the 1¼" tee. This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
6. Connect a nipple and shutoff valve to system return connection (at circulator flange if circulator installed on return). This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
Fill and pressure test
1. Open the shutoff valves you installed on supply and return connections.
2. Slowly open boiler drain valve and fresh water supply to fill boiler with water.
3. When water flows from shutoff valves, close boiler drain valve.
4. Close shutoff valves.
5. Slowly reopen boiler drain valve until test pressure on the pressure/temperature gauge reaches no more than:
45 psig for boilers with 30 psig relief valve.
75 psig
6. Test for no more than 10 minutes at:
45 psig
75 psig
7. Make sure constant gauge pressure has been maintained throughout test. Check for leaks. Repair if found.
for boilers with 50 psig relief valve.
for boilers with 30 psig relief valve. for boilers with 50 psig relief valve.
Do not leave boiler unattended. A cold water fill could expand and cause
excessive pressure, resulting in severe personal injury, death or substantial property damage.
Leaks must be repaired at once. Failure to do so can damage boiler,
resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
Figure 29, page 56. Install circulator on either
Part number 550-110-260/0200
Drain and remove fittings
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever provides best access to drain. Remove hose after draining if used to drain boiler.
3. Remove nipples and valves unless they will remain for use in the system piping.
4. Remove plug from relief valve tapping. See section 3a to replace relief valve.
13
Page 14
GOLD CGs Gas-Fired Water Boiler
Boiler model
number
To
system
From
system
CGs-3 1" 1"
CGs-4 1" 1"
CGs-5 1" 1"
CGs-6 1 ¼" 1 ¼"
Note: Circulator flange supplied with boiler is same size as
recommended piping above.
3a
Water piping —
general information
General piping information
If installation is to comply with ASME or Canadian requirements, an additional piping between boiler and isolation valve. Set second control to minimum 20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F. See section
A low water cutoff device is required when boiler is installed above radiation level or by certain state or local codes or insurance companies. Use low water cutoff designed for water installations. Electrode probe­type is recommended. Purchase and install in tee in supply piping above boiler.
Use backflow check valve in cold water supply as required by local codes.
high temperature limit is needed. Install control in supply
9b, page 32 for wiring.
Pressure/temperature gauge
Install pressure/temperature gauge in tee on supply piping (as shown in drawing on page 3). The gauge well is a self-closing valve, allowing removal of the gauge without draining the system.
Slowly remove pressure/temperature gauge from well. The self-closing valve could leak if clogged with sediment. If water begins to spray, stop removing gauge. Close system fill valve and drain enough water to release system pressure before continuing with gauge removal. Escaping hot water could cause severe personal injury.
Circulator
The circulator is shipped loose (wiring pre-attached to boiler) to allow you to locate it either in the return or supply piping, as desired. See page 3 for a typical installation. Pipe the expansion tank to the suction side of the circulator whenever possible. Install an air separator in the supply piping. Connect the expansion tank to the air separator only if the separator is on the suction side of the circulator. Always install the system fill connection at the same point as the expansion tank connection to the system. Figures 4 and 5 show typical near-boiler piping connections.
System water piping
See Figure 4 (diaphragm-type or bladder-type expansion tank) or tank) on page 15, and and single-zone systems designed for return water at least 130 °F.
See pages 16-17 to complete multiple-zone piping or pages 18-23 to complete piping for radiant heating systems or converted gravity systems.
Refer to page 23 for boilers used with refrigeration systems.
Figure 5 (closed-type expansion
Table 3 below, for near-boiler
Relief valve
Install relief valve vertically in ¾" tapping on side of boiler. See Figure 4
and the tag attached to the relief valve for manufacturer’s instructions.
or 5
To avoid water damage or scalding due to relief valve operation:
Discharge line must be connected to relief valve outlet and
safe place of disposal
possibility of severe burns should the valve discharge.
Discharge line must be as short as possible and be the
the valve discharge connection
Discharge line must least 6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler,
or in the discharge line. Do not plug or place any obstruction in the discharge line.
Failure to comply with the above guidelines could result in failure of
the relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.
Test the operation of the valve after filling and pressurizing system
by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
14
. Terminate the discharge line to eliminate
throughout its entire length.
pitch downward from the valve and terminate at
Table 3 Water pipe size (based on 20 °F rise)
run to a
same size as
Install boiler such that —
Chilled medium, if used, is piped in parallel with heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. Consult I=B=R Installation and Piping Guides.
If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle. Circulation of cold water through the boiler could result in damage to the heat exchanger, causing possible severe personal injury, death or substantial property damage.
Part number 550-110-260/0200
Page 15
Boiler Manual
Water piping — single-zone system3b
Expansion tank
Diaphragm-type or bladder-type expansion tank — Figure 4
1. Ensure expansion tank size will handle boiler and system water volume and temperature. Tank must be located in boiler return piping as close to boiler as possible, before inlet side of circulator. See tank manufacturer’s instructions for details.
2. Install an shown.
automatic air vent in air vent tapping as
Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual section failure can result.
Use Figure 4 or Figure 5 only for single-zone systems designed for return water at least 130 °F. For systems with low return water temperature possible, such as converted gravity systems and radiant heating systems, refer to the special piping suggestions of pages 18-23. Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Closed-type expansion tank — Figure 5
1. Ensure expansion tank size will handle boiler and system water volume and temperature. See tank manufacturer’s instructions for details.
2. Connect tank to ½" NPT tapping located behind supply outlet, using ½" NPT piping. Pitch any horizontal piping up towards tank 1 inch per 5 feet of piping.
Figure 4 Diaphragm- or bladder-type expansion tank
Piping to single-zone system using diaphragm-type or bladder-type expansion tank. See Table 3 for piping sizes.
From system
Isolation valve
Relief valve
Cold water fill
To DIAPHRAGM expansion tank and fittings
Isolation valve
To system
Circulator*
Automatic air vent
Figure 5 Closed-type expansion tank
Piping to single-zone system using closed­type expansion tank. See Table 3 for piping sizes.
CLOSED-type expansion tank
From system
Isolation valve
Relief valve
Cold water fill
Isolation valve
To system
Circulator*
Circulator
26010
Part number 550-110-260/0200
Drain valve
*Alternate
location
Circulator
26011
Drain valve
*Alternate
location
15
Page 16
GOLD CGs Gas-Fired Water Boiler
Water piping — multiple zones3c
Piping multiple zones
Zoning with
circulators, return
temp over 130 °F
Zoning with zone
valves, return temp
over 130 °F
Piping for radiant
heating systems or
converted gravity
systems
Follow instructions on pages 14 and 15 to install near-boiler or single-zone piping. (Also refer to applicable.)
See
1. Size each circulator to individual circuit requirements.
2. Do not install circulator on boiler (except for primary/secondary piping).
3. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
4. Install and wire a separate relay for each zone circulator.
1. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
2. Provide a separate 24-volt transformer to power the zone valves. Size the transformer to
Converted gravity (or steam) systems
Whenever possible, use the primary/secondary piping shown in Figures 8 or 9 on page 19. This piping design allows changing boiler flow rate without affecting primary circuit flow rate.
If
11
the reduced flow rate in the heating system will not cause heat distribution problems.
Piping for radiant heating systems or converted gravity systems, below, if
Figure 6 or Figure 7 to complete installation.
handle the total rated load of all connected zone valves.
Figures 8 or 9 cannot be used, use the boiler-bypass piping shown in Figure 10 or Figure
on page 21. You can also use the piping shown in Figure 12 on page 23 (system-bypass), if
16
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 8 or 9 on page 19. Alternatively, use the method of either
12
(system-bypass), because this method does not control radiant system supply temperature.
If radiant system tubing has no oxygen barrier, a heat exchanger must be used.
Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
Do not apply the methods in this manual if the system is equipped with an outdoor reset control
temperature at no less than 130 °F regardless of system supply temperature. Contact your Weil-McLain representative for suggested piping and control methods. Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
. Instead, provide controls and piping which can regulate the boiler return water
Figure 10 or Figure 11 on page 21. Do not use the piping of Figure
Part number 550-110-260/0200
Page 17
Boiler Manual
typical piping — multiple-zone installations
Figure 6
Zoning with circulators — return water 130 °F or higher.
ZONE 2
ZONE 1
1
2
11
13
10
Cold
water
6
9
11
fill
12
Figure 7
Zoning with zone valves — return water 130 °F or higher.
ZONE 2
ZONE 1
1 2
3
6
Cold
water
1
6
11
9
11
fill
12
6
Alternate circulator location
10
1
5
13
26012
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator
5 Zone valve
6 Drain valve
9 Relief valve
10 Automatic air vent (with diaphragm-type
expansion tank), or connect to tank fitting (closed­type expansion tank).
DO NOT use an automatic
For systems with possible low return-water temperature (such as converted gravity systems, radiant heating systems and heat pump systems), refer to the special piping suggestions of
Figures 8 - 12, as applies. Failure to prevent sustained low return water temperature to the
boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death or substantial property damage.
Part number 550-110-260/0200
26013
air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank circulator or air separator.
17
Page 18
GOLD CGs Gas-Fired Water Boiler
Water piping — low temp systems3d
Primary/secondary
(preferred) bypass
piping method
Temperature gauges
Valve adjustment
(Figure 12 and 13 only)
Primary/secondary bypass piping is preferred because the flow rate and temperature drop in
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and temperature distribution.
Figures 8 and 9 show suggested bypass arrangements using primary/secondary bypass piping
(preferred) for low temperature systems such as radiant heating systems or converted gravity
systems
The bypass valves (items system return water — set to assure a minimum return water temperature (at least 130 °F) to the boiler. Set the valves as explained below.
Gauge 4a is suggested, but optional on any system.
Gauge — to display the water temperature being supplied to the radiant tubing.
Gauge a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return water is cold (approximately 60 °F water temperature).
1. Set the valves while the system is cool, setting for the coldest expected water temperature
2. Start with valve 7a fully closed and 7b fully open.
3. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads
4. Note that valve
. For alternatives, see pages 20 through 23.
7a and 7b) provide mixing of hot boiler outlet water with cooler
4b is optional on converted gravity systems, but required on radiant heating systems
8 is required on all systems to assure the return water temperature is accurately set for
(usually 60 °F since the system will often drop to room temperature between cycles).
130 °F when gauge 4a reads 60 °F.
7a regulates the amount of hot water from the boiler supply which mixes
with return water. Valve 7b regulates the amount of system water flowing through the boiler secondary loop.
18
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset control water temperature at no less than 130 °F
your Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
and the system supply temperature (such as provided by an injection
).
system supply temperature is relatively constant.
. Instead, provide controls and piping which can regulate the boiler return
regardless of system supply temperature. Contact
Part number 550-110-260/0200
Page 19
Boiler Manual
primary/secondary (preferred) bypass piping —
for radiant heating or converted gravity systems
Figure 8
Zoning with circulators
ZONE 2
ZONE 1
1
Cold
water
4a 4b
2
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
Alternate circulator location
10
13
Figure 9
Zoning with zone valves
ZONE 2
ZONE 1
1
2
3
1
Cold
water
1
4a 4b
66
8
11
fill
12
12"
MAX.
1
7a
9
7b
10
13
Alternate circulator location
3
1
5
1
26014
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator
4 System temperature gauges
5 Zone valve
6 Drain valve
7 System temperature valves (see instructions to the
left for adjusting valves)
8 Blend temperature gauge
9 Relief valve
26015
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion tank).
DO NOT use an automatic air vent when using
closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank, if
used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.)
Part number 550-110-260/0200
19
Page 20
GOLD CGs Gas-Fired Water Boiler
Water piping — low temp systems3e
Boiler-bypass piping
method
Temperature gauges
Valve adjustment
This piping method is called a boiler-bypass because part of the circulator flow is bypassed around the boiler (through valve 7a). This method reduces the flow rate throughout the boiler, in order to raise the average water temperature in the boiler enough to prevent flue gas condensation. Boiler-bypass piping is effective for some boilers — including the CGs — provided the flow rates are adjusted according to the instructions following.
Figures 10 and 11 are alternative piping suggestions for converted gravity (large water content
or steam systems) or radiant heating system — for use when primary/secondary piping can’t be applied. (Figure 12 is another alternative, using system bypass in place of boiler­bypass piping. Figure 12 however, is not suitable for radiant heating applications because it does not protect the radiant system from possible high water temperature.)
Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low as possible, helping to equalize the building heat distribution.
Gauge 4a is optional if the bypass valves will be adjusted using cold (or room temperature) return water to the boiler. (When setting the valves without gauge 4a installed — using cold or room temperature water — assume the return water temperature to be 60 °F. Set the valves so gauge 8 reads at least 120 °F.
4b is optional on converted gravity systems, but required on radiant heating systems
Gauge — to display the water temperature being supplied to the radiant tubing.
Gauge
8 is required on all systems to assure reliable adjustment of the bypass valves. The
boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is not installed.
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve 60 °F higher than gauge 4a. A minimum 60 °F temperature rise through the boiler assures a low enough flow rate and high enough average temperature to prevent condensation even with low system return water temperature.
3. Valve 7a regulates the system flow rate, while valve 7b regulates the boiler flow rate.
4. The boiler-mounted temperature/pressure gauge may be used in place of a separate gauge 8.
7a while closing valve 7b until the temperature at gauge 8 reads
20
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset control water temperature
your Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
and the system supply temperature (such as provided by an injection
).
system supply temperature is relatively constant.
. Instead, provide controls and piping which can regulate the boiler return
at no less than 130 °F regardless of system supply temperature. Contact
Part number 550-110-260/0200
Page 21
Boiler Manual
boiler-bypass (alternate) piping —
for radiant heating or converted gravity systems
Figure 10 Boiler-bypass piping
Zoning with circulators
(Alternative to primary/secondary piping Figures 8 and 9)
ZONE 2
ZONE 1
1
4a 4b
2
13
8
7b
10
Cold
water
fill
11
66
7a
11
12
9
Figure 11 Boiler-bypass piping
Zoning with zone valves
(Alternative to primary/secondary piping Figures 8 and 9)
ZONE 2
ZONE 1
1 2
3
Alternate circulator
location
7a
7b
9
Cold
water
4a
11
fill
12
3
4b
66
8
10
11
5
13
26016
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator
4 System temperature gauges
5 Zone valve
6 Drain valve
7 System temperature valves (see instructions to the left
for adjusting valves)
8 Blend temperature gauge
9 Relief valve
Part number 550-110-260/0200
26017
10 Automatic air vent (with diaphragm-type
expansion tank), or connect to tank fitting (closed­type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.)
21
Page 22
GOLD CGs Gas-Fired Water Boiler
Water piping — low temp systems3f
System-bypass
piping method
Valve adjustment
This piping method is called a system-bypass because part of the circulator flow bypasses the system (through valve cooler system return water temperature in order to provide minimum 130 °F return water to the boiler. Valve low pressure drop systems in order to cause enough flow through valve
Figure 12 is an alternative piping method that provides return water temperature control for
boilers installed on
Do not apply the piping of Figure 12 on radiant heating systems. It provides no method
regulating the water temperature provided to the system and could result in excessive water temperature in the radiant tubing.
System-bypass piping as shown in Figure 12 can be used with either zone valve or circulator zoning. When used with circulator zoning however, the boiler circulator (item piped as shown. It cannot be used as one of the zoning circulators.
Do not apply system-bypass piping if the reduced flow in the system could cause poor heat distribution. That is, system-bypass piping reduces the flow in the system and increases the water temperature supplied to the system. This can cause increased heat from radiators at the beginning of the system and reduced heat from radiators near the end of the system.
1. Start with valve 7a fully closed and 7b fully open.
2. Gradually open valve least 130 °F at all times.
7b will most often be full open, but may need to be slightly closed on some
converted gravity systems (large water content or steam systems).
7a). This bypassed hot water from the boiler outlet mixes with
7a.
3), must be
7a while closing valve 7b until the temperature at gauge 8 reads at
3. Valve 7a regulates the amount of boiler supply water mixed with return water. Valve 7b causes a pressure drop in the system needed to balance flow through valve 7a and the system.
4. The valve adjustment should be done with the system at the coldest expected temperature (60 °F for converted gravity systems or high mass radiant systems).
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset control water temperature
your Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
and the system supply temperature (such as provided by an injection
).
system supply temperature is relatively constant.
. Instead, provide controls and piping which can regulate the boiler return
at no less than 130 °F regardless of system supply temperature. Contact
22
Part number 550-110-260/0200
Page 23
Boiler Manual
3f
system-bypass (alternate) piping —
for converted gravity (or steam) systems
Cold
water
26018
fill
11
12
8
7a
To systemFrom system
7b
Alternate circulator location
9
10
Figure 12 System-bypass piping
Zoning with zone valve or circulators, return water 130 °F or higher.
(Alternative to boiler-bypass piping Figures 10 and 11)
3 System or zone circulator
7 System temperature valves (see instructions to the left for
adjusting valves)
8 Blend temperature gauge
9 Relief valve
10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank, if used
(For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5.)
Water piping — refrigeration system3g
Figure 13 Piping refrigeration systems
System supply
Circulator
System return
26019
Part number 550-110-260/0200
Water chiller
Strainer
Check valve
Balancing valve
Expansion tank
Shut-off valve
Boiler
Prevent chilled water from entering boiler
Install boiler so that chilled medium is piped in parallel with the heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. See for typical installation of balancing valve and check valve.
If boiler is connected to heating
MODEL
CGs
coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle.
Figure 13
23
Page 24
GOLD CGs Gas-Fired Water Boiler
26020
Manual main shutoff gas valve (when required)
Ground joint union (when required)
Nipple
Tee
Cap
Venting and combustion air4
Install vent piping and air piping (if used) per appropriate Venting
Supplement included in boiler
envelope assembly.
Refer to Venting Supplements and to manual section 1 regarding requirements for:
vent system
combustion air openings
combustion air quality
CGs Boiler must be vented and supplied with
combustion and ventilation air
Weil-McLain CGs Venting Supplements packed in envelope assembly with boiler. Failure to do so will cause severe personal injury or death.
Use direct vent (sealed combustion) if combustion
air quality cannot be assured to be free of contaminants. Refer to page 9 for a list of potential
contaminants and locations likely to contain them. Operating the boiler with contaminated air will damage the boiler sections and vent, resulting in possible boiler failure or leakage of flue products, causing severe personal injury, death or substantial property damage.
as described in
Gas piping5
Connecting gas supply piping to boiler
1. Remove jacket front panel and refer to to pipe gas to boiler.
a. Install drip leg at inlet of gas connection to
boiler. Where local utility requires drip leg to be extended to the floor, use appropriate length of pipe between cap and tee.
b. Install ground joint union for servicing, when
required.
c. Install manual shutoff valve in gas supply
piping outside boiler jacket when required by local codes or utility requirements.
d. In Canada — When using manual main shutoff
valve, it must be identified by the installer.
Figure 14
Figure 14 Gas supply piping
24
Part number 550-110-260/0200
Page 25
Boiler Manual
Gas piping continued5
Support piping with hangers, not by boiler or its
2. accessories.
3. Purge all air from gas supply piping.
4. Before placing boiler in operation,
and its gas connection for leaks.
a. Close manual main shutoff valve during any
pressure testing at less than 13" w.c.
b. Disconnect boiler and gas valve from gas
supply piping
during any pressure testing
greater than 13" w.c.
Do not check for gas leaks with an open flame
Failure to use bubble test or check for gas leaks can cause severe personal injury, death or substantial property damage.
check boiler
— use bubble test.
Natural Gas:
1. Refer to Table 4 for pipe length and diameter. Base on rated boiler input (divide by 1,000 to obtain cubic feet per hour). Table 4 is only for gas with
specific gravity 0.60, with a pressure drop through the gas piping of 0.30" w.c.
For additional gas pipe sizing information, refer to ANSI Z223.1 (or B149.1 or B149.2 for Canadian installations).
2. Inlet pressure required at gas valve inlet:
• Maximum: 13" w.c.
• Minimum: 5" w.c.
• Manifold gas pressure: 3.5" w.c.
3. Install 100% lockup gas pressure regulator in supply line
if inlet pressure exceeds 13" w.c.
Adjust for 13" w.c. maximum.
Propane Gas:
1. Contact gas supplier to size pipes, tanks and 100%
5. Use pipe dope compatible with propane gases. Apply sparingly only to male threads of pipe joints so that pipe dope does not block gas flow.
Failure to apply pipe dope as
detailed above can result in severe personal injury, death or substantial property damage.
lockup gas pressure regulator.
2. Adjust propane supply regulator provided by gas supplier for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
• Maximum: 13" w.c.
• Minimum: 11" w.c.
• Manifold gas pressure: 10" w.c.
Table 4 Pipe capacity for 0.60 specific gravity natural gas
Gas pipe
length
(feet)
10 132 278 520 1050 1600
20 92 190 350 730 1100
30 73 152 285 590 860
40 63 130 245 500 760
½" ¾" 1" 1¼" 1½"
Capacity of pipe for pipe size of:
(Capacity in cubic feet gas per hour)
Part number 550-110-260/0200
50 56 115 215 440 670
75 45 93 175 360 545
100 38 79 150 305 460
150 31 64 120 250 380
25
Page 26
GOLD CGs Gas-Fired Water Boiler
Field wiring6
For your safety, turn off electrical
power supply at service entrance panel before making any electrical connections
to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler must be replaced, use only type 105 °C wire or equivalent.
Boiler must be electrically
grounded
as required by National Electrical Code ANSI/NFPA 70 – latest edition.
Electrical installation must comply with:
1. National Electrical Code and
any other national, state, provincial or local codes or regulations.
2. In Canada, CSA C22.1
Canadian Electrical Code Part 1, and any local codes.
Wiring connections
Boiler is shipped with controls completely wired.
Thermostat
1. Connect thermostat as shown on wiring diagram on boiler.
Install on inside wall away from influences of
2.
drafts, hot or cold water pipes, lighting fixtures, television, sunrays, or fireplaces.
3. If thermostat has a heat anticipator, set heat anticipator in thermostat to match power requirements of equipment connected to it. If connected directly to boiler, set for 0.4 amps. For other devices, refer to manufacturer’s specifications. Wiring diagram on boiler gives setting for control module and gas valve. Also see instructions with thermostat.
Junction Box (furnished)
1. Connect 120 VAC power wiring as shown in
Figure 15.
2. Fused disconnect or service switch (15 amp. recommended) may be mounted on this box. For those installations with local codes which prohibit installation of fused disconnect or service switch on boiler, install a 2 x 4 cover plate on the boiler junction box and mount the service switch remotely as required by the code.
Figure 15
Field wiring connections —
service switch and thermostat
(or end switch) provided by
installer
The CGs control module is polarity-sensitive. The hot and neutral wires must be connected to the correct leads. A flashing POWER light usually indicates reversed polarity of 120 VAC lead wires.
26
Service
switch
(not provided)
Field wiring
Factory wiring
120 VAC Hot Neutral
Black White Green
Junction box,
boiler left side
Ground
Thermostat
or end switch
(not provided)
Ground screw Wire nuts
Black Black
Thermostat leads, through jacket left side
26021
Part number 550-110-260/0200
Service
switch
(not provided)
Thermostat
or end switch
(not provided)
Page 27
Boiler Manual
Start-up — preparation7a
Determine if water treatment is needed
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
Verify water chemistry
Consult local water treatment companies for unusually hard water areas (above 7 grains hardness) or low pH water conditions (below 7.0). Boiler water pH of 7.0 to 8.5 is recommended.
Freeze protection (when used)
Use antifreeze made especially for hydronic systems. Inhibited propylene glycol is recommended.
Do not use ethylene glycol,
automotive or undiluted antifreeze
or death can result.
1. Determine water content. Boiler water content is listed on page 59. Remember to include expansion tank water content.
2. Follow antifreeze manufacturer's instructions.
3. A 50% solution of propylene glycol/water provides maximum protection to about -30 °F.
4. Local codes may require back flow preventer or actual disconnect from city water supply.
5. When using antifreeze in a system with automatic fill, install a water meter to monitor water makeup. Glycol will leak before the water begins to leak, causing glycol level to drop. Added water will dilute the antifreeze, reducing the freeze protection level.
antifreeze quantity according to system
. Severe personal injury
Check for gas leaks
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Do not proceed with start-up if there is any indication of a gas leak. Repair any leak at once.
Propane boilers only — Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before start-up (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
Fill the system with water
1. Close manual and automatic air vents and boiler drain cock.
2. Fill to correct system pressure. Correct pressure will vary with each application. Typical cold water fill pressure for a residential system is 12 psi.
3.
Purge air from system:
a. Connect a hose to the purge valve (see drain
valves, item
on pages 17 through 21, Figure 6 through
Figure 11). Route hose to an area where water
can drain and be seen.
b. Close the boiler or system isolation valve
between the purge valve and fill connection to the system.
c. Close zone isolation valves.
d. Open quick-fill valve on cold water makeup
line.
e. Open purge valve.
f. One zone at a time, open the isolation valves.
Allow water to run through the zone, pushing out the air. Run until no noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve
and remove the hose. Open all isolation valves. Watch that system pressure rises to correct cold-fill pressure.
h. After the system has operated for a while,
eliminate any residual air by using the manual air vents located throughout the system.
i. If purge valves are not installed in system, open
manual air vents in system one at a time, beginning with lowest floor. Close vent when water squirts out. Repeat with remaining vents.
4. Open
5. Open other vents:
6. Refill to correct pressure.
automatic air vent (diaphragm-type or
bladder-type expansion tank systems only) one turn.
a. Starting on the lowest floor, open air vents one
at a time until water squirts out.
b. Repeat with remaining vents.
6, in suggested piping diagrams
Part number 550-110-260/0200
27
Page 28
GOLD CGs Gas-Fired Water Boiler
Start-up — preparation continued7a
Inspect system water piping
After filling the boiler and system with water, inspect all piping throughout the system for leaks. If found, repair immediately. Repeat this inspection after the boiler has been started and the system has heated up.
Leaks must be repaired at once.
Failure to do so can damage the boiler, resulting in substantial property damage.
Do not use petroleum-based
cleaning or sealing compounds
boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
Inspect base insulation
Check to make sure insulation is
secure
base. If insulation is damaged or displaced, do not operate boiler. Replace or reposition insulation.
Failure to replace damaged
insulation or reposition insulation can result in a fire hazard, causing severe personal injury, death or substantial property damage.
The boiler contains ceramic fiber and fiberglass materials. Use care
in
when handling these materials per instructions on manual. Failure to comply could result in severe personal injury.
against all four sides of the
page 60 of this
Start-up — operate boiler7b
Final check before starting boiler
Read manual section 9 including the Lighting
instructions
Verify the boiler and system are
Verify the Start-up preparation procedures of section 7a have been completed.
Start the boiler
Follow the Lighting instructions from section 9c to start the boiler.
See section 7c if boiler fails to start.
Check system and boiler
procedure (Figure 21, page 34).
full of water.
Do not use petroleum-based
cleaning or sealing compounds
boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
in
Eliminate all system leaks.
Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
1. Check system piping for leaks. If found, shut down boiler and repair immediately.
Vent air from system using manual vents. Air in
2. the system will interfere with circulation and cause heat distribution problems and noise.
3.
Inspect vent system thoroughly for signs of
deterioration from corrosion, physical damage or sagging. In addition — Check for gas-tight seal at every connection and seam.
Venting system must be sealed gas-tight
and carbon monoxide emissions which will result in severe personal injury or death.
to prevent flue gas spillage
28
Part number 550-110-260/0200
Page 29
Boiler Manual
26024
Transparent
blue flame
Inner flame
Start-up — operate boiler continued7b
4. Check around the boiler for gas odor following the procedure of section
If you discover evidence of any gas leak, shut down the boiler at once. Find the leak source with bubble test and repair immediately. Do not start boiler again until corrected. Failure to comply could result in severe personal injury, death or substantial property damage.
7a of this manual.
Check burner flames
View pilot and main flames through the inspection port in the Air inlet box front cover.
Pilot burner flame
Proper pilot flame characteristics (see Figure 16):
1. Blue flame.
2. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.
Improper pilot flame characteristics:
1. Overfired — Large flame lifting or blowing past pilot flame sensor.
2. Underfired — Small flame. Inner cone not engulfing pilot flame sensor.
3. Lack of primary air — Yellow flame tip.
4. Incorrectly heated pilot flame sensor.
Figure 16 Typical pilot burner flame
Spark electrode
Pilot flame sensor
Figure 17 Typical main burner flame
Inner
cone
26023
Main burner flame
Proper main burner flame characteristics
(see
Figure 17):
1. Yellow-orange streaks may appear (caused by dust).
Improper main burner flame characteristics:
1. Overfired — Large flames.
2. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on flames (sooting will occur).
Start-up — if boiler doesn’t start . . .7c
Check for:
1. Loose connections, blown fuse or service switch
off?
Part number 550-110-260/0200
2. High limit switch set below boiler water
temperature?
3. Thermostat set below room temperature?
4. Gas not turned on at meter or boiler?
5. Incoming gas pressure less than: 5" w.c. for natural gas?
11" w.c. for propane gas?
If none of the above corrects the problem, refer to
Troubleshooting, section 11 of this manual.
29
Page 30
GOLD CGs Gas-Fired Water Boiler
Check-out procedure — checklist8
Boiler and heat distribution units filled with water?
Automatic air vent, if used, open one full turn?
Air purged from system?
Air purged from gas piping? Piping checked for leaks?
Correctly sized manifold orifices installed? Refer to manual
section 2a to check size and fuel type.
Correctly sized manifold orifices must be used. Failure to do so will cause severe personal injury, death or substantial property damage.
Followed operating instructions on boiler or in manual
section 9 for proper start-up?
Proper burner flame observed? Refer to
, manual section 7b.
flame
Test limit control — While burners are operating, move
indicator on limit control below actual boiler water temperature. Burners should go off while circulator continues to operate. Raise setting on limit control above boiler water temperature and burners should reignite.
Test additional field-installed controls — If boiler has a
low water cutoff, additional high limit or other controls, test for operation as outlined by manufacturer. Burners should be operating and should go off when controls are tested. When controls are restored, burners should reignite.
Test ignition system safety device:
a. Connect manometer to outlet side of gas valve. b. Start boiler, allowing for normal start-up cycle to occur
and main burners to ignite.
c. With main burners on, manually shut off gas supply
at manual main shutoff gas valve. Burners should go off.
d. Open manual main shutoff gas valve. Manometer
should confirm there is no gas flow.
Check burner
e. Pilot will relight, flame sensing element will sense pilot
flame and main burners will reignite.
Set limit control(s) to system temperature requirements.
Adjust balancing valves and controls to provide design temperature to system.
For multiple zones, adjust flow so it is about the same in
each zone.
Verify thermostat heat anticipator (if available) set properly?
Refer to Field wiring, manual section 6a, Thermostat(s).
Cycle boiler with thermostat — Raise to highest setting
and verify boiler goes through normal start-up cycle. Lower to lowest setting and verify boiler goes off.
Measure natural gas input:
a. Operate boiler 10 minutes. b. Turn off other appliances. c. At natural gas meter, measure time (in seconds)
required to use one cubic foot of gas.
d. Calculate gas input:
3600 x 1000
number of seconds from step c
e. Btuh calculated should approximate input rating on
boiler rating label.
Check manifold gas pressure by connecting manometer to
downstream test tapping on main gas valve. Manifold pressure for natural gas should be 3.5" w.c. and for propane gas should be 10" w.c.
Observe several operating cycles for proper operation.
Set room thermostat to desired room temperature.
Fill in Installation and service certificate below?
Review all instructions shipped with this boiler with owner
or maintenance person. Return instructions to envelope and give to owner or place in pocket inside front panel in boiler.
= Btuh
Installation and service certificate
Boiler model __________________ Series __________ CP number ___________ Date installed _______________
Installation instructions have been followed.
Measured Btuh input ____________
Installer ________________________ ________________________________ ______________________________ (company) (address) (phone)
30
Check out sequence has been performed.Above information is certified to be correct.Information received and left with owner/maintenance person
_____________________________________
(installer’s signature)
Part number 550-110-260/0200
Page 31
Boiler Manual
Operation — sequence9a
1.
Read Lighting instructions on page 34. This
information is also located on a label on the inside of the boiler jacket door panel.
2. Raise room thermostat to call for heat.
3. Inducer and circulator energize. After pressure switch proves proper airflow, control module initiates 30-second prepurge.
4. Control module sparks the pilot and opens pilot valve in main gas valve.
a. If pilot does not light within 15 seconds, pilot
valve is closed and spark generator is turned off. Control module initiates a 15-second postpurge, then starts a new cycle.
b. If pilot does light and control module senses
flame current, spark generator is turned off and main valve opens.
5. During
a. Control module monitors pilot flame current.
main burner operation:
If signal is lost, main valve closes, spark
generator activates and sequence returns to step 4.
b. If power is interrupted, control system shuts
off
pilot and main gas valves and restarts at step
1 when power is restored.
6. In the event the
boiler
— The control module closes the pilot and
limit control shuts down the
main gas valves, but keeps the inducer operating for 15-second postpurge.
— The circulator continues to operate.
7.
Lower room thermostat setting to stop call for heat.
Thermostat is satisfied — Pilot and main gas valves are closed — Inducer operates for 15-second postpurge — Circulator is shut off.
8. Boiler is now in the off cycle.
9. Repeat steps 1 through 6 several times to verify operation.
10. Return the thermostat to normal setting.
11. Set thermostat heat anticipator setting to 0.4 amps, adjusted for gas valve and control current.
Figure 18 Control module sequence of operation — status light indications
Steps
(Following step 8, cycle goes back to step 1.)
1. Standby
Waiting for call for heat·
2. Call for heat
· Circulator on
· Blower on
3. Limit circuit
· Limit controls closed
· Block switch contacts closed
4. Pressure circuit
· Pressure switch contacts closed
· Prepurge for 30 seconds
5. Pilot flame proven *
· Gas valve open
· Pilot remains on
· Boiler producing heat
6. Limit cycle
· Limit circuit open
· Gas valve closed
7. Flame outage *
· Flame out
· Boiler recycles
8. Thermostat satisfied
· Circulator off
· Blower postpurge
9. Circulator exercise routine
· Circulator turns on for 30 seconds if boiler not operated for 30 days
* If pilot flame is not proven in 15 seconds, control module will flash the FLAME light, but will continue indefinitely with attempts to light the pilot burner.
The control module will not lockout on a failure to establish flame. It will lockout if line voltage polarity is reversed,stray voltage is sensed on thermostat line, pressure switch sticks closed or fails to make within 5 minutes or if flame is sensed when it shouldn’t be there. The boiler will reset after these lockouts if any of the following occurs:
• 1 hour waiting period • Opening and closing of thermostat circuit • Removal of 120 VAC power for at least 45 seconds.
Call for
heat?
NO
YES
YES
YES
YES
YES
YES
NO
NO
POWER TSTAT
CIRC
or
LIMIT
= "ON"
PRESS
SWITCH
FLAME
= "OFF"
Timing
35 sec
15 sec
15 sec
30 sec
26030
Part number 550-110-260/0200
31
Page 32
GOLD CGs Gas-Fired Water Boiler
Operation — wiring diagrams9b
Figure 19 Schematic wiring diagram
32
Part number 550-110-260/0200
Page 33
Boiler Manual
Figure 20 Ladder wiring diagram
Electrical shock hazard — can cause severe injury or death. Disconnect power before installing or servicing.
All contacts are shown without power applied.
Legend for ladder wiring diagram
120 VAC field wiring
Low voltage field wiring
120 VAC factory wiring
Low voltage factory wiring
High voltage spark ignition wiring
Ground connectors
Table G: Gas valve terminals and anticipator settings
PV PV
Anticipator
amps
0.6
0.8 3 3
0.64
0.7
Gas valve
Honeywell VR8204 Honeywell VR8304 White-Rodgers 36E White-Rodgers 36C
* Terminals 2–4 are factory-jumpered on the
White-Rodgers 36C gas valve.
"A" "B" "C"
MV/PV MV/PV
2–4 *
MV
MV
2
1 1
SERVICE
SWITCH
HIGH
VOLTAGE
PILOT
IGNITION
ELECTRODE
GndNeutralHot
120 VAC
INDUCER MOTOR
CONTROL
MODULE
120 VAC
SECTION
CIRCULATOR
120 VAC
24 VAC
1. All wiring must be installed in accordance with: A. U.S.A. — N.E.C. And any other national, state,
or local code requirements. B. Canada — C.S.A. C22.1 C.E.C. Part 1 and any
other national, provincial, or local code require­ments.
2. Pilot lead wires are not field replaceable. Replace pi­lot assembly if necessary.
3. If any of the original wire as supplied with the ap­pliance must be replaced, use minimum 105 °C wire or equivalent. Exception — wires to a rollout TFE must be 200 °C or equivalent.
4. Thermostat anticipator setting (single zone) — see Table G for anticipator setting, depending on which gas valve is installed in boiler.
5. For multiple zoning, use either zone valves or circulators. Refer to the component manufac­turer's instructions and this manual for applica­tion and wiring suggestions.
6. Refer to control component instructions packed with the boiler for application information.
7. Wire any additional limit controls (low water cut­off, additional high limit, etc.) in series with boiler limit control as shown.
Part number 550-110-260/0200
THERMOSTAT
ROLLOUT
TFE
Additional
limits (note 7)
AIR PRESSURE
SWITCH
71033
WATER TEMP
LIMIT SWITCH
PILOT
FLAME
SENSOR
HIGH
VOLTAGE
Power
G
Tstat–Circ
R
Limit
R
Press switch
R
Flame
R
Control module
low voltage
section
PILOT GAS
VALVE
"C"
"A"
"B"
MAIN GAS
VALVE
See Table G
33
Page 34
GOLD CGs Gas-Fired Water Boiler
Operation — lighting instructions9c
Figure 21 Lighting instructions
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
B. Before OPERATING, smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
C. Use only your hand to turn the gas control knob. Never use
tools. If the knob will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electrical power to the appliance.
4. Remove jacket front panel.
5. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
6. Turn Gas control knob clockwise to OFF.
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.
8. Turn Gas control knob counterclockwise to ON.
9. Turn on all electric power to the appliance.
10. Set thermostat to desired setting.
11. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" below and call your service technician or gas supplier.
12. Replace jacket front panel.
26070
White-Rodgers 36C Gas valve
Position indicator
(shown in "ON" position)
White-Rodgers 36E Gas valve
Position indicator
(shown in "ON" position)
Honeywell VR8204 or VR8304 Gas valve
Position indicator
(shown in "ON" position)
Gas control knob
Gas control knob
Gas control knob
TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove jacket front panel.
4. Turn Gas control knob clockwise to OFF. Do not force.
5. Replace jacket front panel.
34
Part number 550-110-260/0200
Page 35
Boiler Manual
Service and maintenance — schedule10a
Table 5 Service and maintenance schedules
Service technician
(see following pages for instructions)
Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system (and air piping)
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners, base and inlet air box
• Condensate drain system
UP
-
Service:
• Inducer motor
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
NNNUAL START
A
Check/test:
Owner maintenance
(see CGs User’s Information Manual for instructions)
• Check boiler area
Daily
Monthly
Periodically
Every 6 months
• Check air openings
• Check boiler pressure/ temperature gauge
• Check boiler interior piping
• Check venting system
• Check air vents
• Check boiler relief valve
• Check condensate drain system
• Check automatic air vents (if used)
• Test low water cutoff (if used)
• Clean vent termination/air intake screens
• Oil inducer motor
• Operate relief valve
Part number 550-110-260/0200
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
Review:
• Review with owner
Follow the Service and maintenance procedures given throughout this manual and in
component literature shipped with the boiler. Failure to perform the service and maintenance
could result in damage to the boiler or system. Failure to follow the directions in this manual
and component literature could result in severe personal injury, death or substantial property
damage.
End of season • Shut down procedure
35
Page 36
GOLD CGs Gas-Fired Water Boiler
Service & maintenance — annual start-up10b
The boiler should be inspected and started annually, at the beginning of the heating season, only by a qualified
service technician
the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
. In addition, the maintenance and care of the boiler designated in Table 5 and explained on
Inspect . . . . . . . . . .
Reported problems
Inspect any problems reported by owner and correct before proceeding.
Boiler area
1. Verify that boiler area is free of any combustible
materials
liquids.
2. Verify that boiler area (and air intake) is free of any of the manual. If any of these are present in the boiler intake air vicinity, they must be removed. If they cannot be removed, install combustion air piping to the boiler in accordance with the appropriate venting supplement.
, gasoline and other flammable vapors and
contaminants listed on page 9 of this
Air openings
1. Verify that combustion and ventilation air openings to the boiler room and/or building are open and
unobstructed. Check operation and wiring of
automatic combustion air dampers, if used.
2. Verify that boiler vent discharge and air intake are
clean and free of obstructions.
Flue gas vent system (and air piping)
1. Visually inspect entire flue gas venting system (and air piping, if installed) for blockage, deterioration or leakage. Repair any joints that show signs of leakage in accordance with vent manufacturer’s instructions. When air is ducted to boiler, verify that air inlet hose is connected and properly sealed.
Failure to inspect for the above
conditions and have them repaired can result in severe personal injury or death.
Pilot and main burner flames
1. Visually inspect pilot burner and main burner flames as directed under manual.
Start-up, section 7 of this
Water piping
1. Check the boiler interior piping and all system piping for signs of leaks.
2. Repair any leaks before proceeding.
36
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 60 of this manual. Failure to comply could result in severe personal injury.
Part number 550-110-260/0200
Page 37
Boiler Manual
Inspect . . . . . . . . . .
Eliminate all system or boiler leaks. Continual fresh
makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure. Leaking water may also cause severe property damage.
Do not use petroleum-based cleaning or sealing
compounds
will occur, resulting in substantial property damage.
Electrical shock hazard — Turn off power to the boiler
before any service operation
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Boiler heating surfaces
1. Disconnect the vent pipe at the boiler inducer outlet connection after turning off power to the boiler.
2. Use a bright light to inspect the flue pipe interior and inducer interior.
3. Inspect the boiler vent outlet area and heating surfaces by looking through the opening.
4. If the vent pipe or inducer interior show evidence of soot, follow Cleaning boiler heating surfaces in this manual section to remove the flue collector and clean the boiler if necessary after close inspection of boiler heating surfaces. If there is evidence of rusty scale deposits, check the water piping and control system to make sure the boiler return water temperature is properly maintained (per this manual).
5. Reconnect vent to inducer outlet and replace all boiler components before returning to service.
in boiler system. Severe damage to boiler
on the boiler except as
6. Check inside and around boiler for evidence of any leaks from the boiler. If found, locate source of leaks and repair.
Burners, base and inlet air box
1. After turning off power to the boiler, remove the inlet air box top panel (Figure 27, item 13, page 54).
2. Inspect gasket (item 14). Replace if necessary.
3. Inspect burners and all other components in the inlet air box and boiler base.
4. If burners must be cleaned, first remove item 4,
Figure 27, page 54. Access the burner assembly by
first removing burner baffle, item 4. Then remove the screws securing the burner tray to the manifold. Slide the burner tray out. Then brush and vacuum the burners thoroughly, making sure all ports are free of debris.
5. Inspect the slotted jacket cooling openings in the bottom left and rear of the base pan ( item 1, page 54).
6. Inspect the base insulation. Pay attention to the
WARNING on page 36 regarding working with
insulation materials. Verify that the insulation is intact and secure against all four sides of the base.
If insulation is damaged or displaced, do not operate the boiler. Replace or reposition insulation as necessary. Failure to replace damaged insulation can result in a fire hazard, causing severe personal injury, death or substantial property damage.
Figure 27,
Condensate drain system
1. Inspect condensate drain fittings and tubing. Verify that condensate can flow freely to drain.
Service . . . . . . . . . .
Inducer motor
1. With boiler power OFF, place a few drops of S.A.E. 20 motor oil in each of the two oil cups.
Part number 550-110-260/0200
Use only S.A.E. 20 motor oil to lubricate the inducer motor. Do not use universal household oils. Motor could be damaged, resulting in possible severe property damage.
Oiled bearing circulators
1. The circulator shipped with the CGs boiler is water-lubricated. No oiling is required.
2. Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.
37
Page 38
GOLD CGs Gas-Fired Water Boiler
Service & maint. — annual start-up continued10b
Start-up . . . . . . . . .
1. Start the boiler, following the instructions in manual section 7.
4. Check gas piping, per manual Sections 5 and 7, verifying no indications of leakage and all piping and connections are in good condition.
2. Verify cold fill pressure is correct and that fill system is working properly.
3. Verify
antifreeze level (if used) is at the right
concentration and that inhibitor level is correct.
Check/test . . . . . . .
Gas piping
1. Sniff near floor and around boiler area for any indication of a gas leak.
2. Test gas piping using bubble test, per section 5 of this manual, if there is any indication of a leak.
Cold fill and operating pressures
1. While the system is cold, note the pressure reading on the boiler pressure/temperature gauge. Verify that cold fill pressure is correct.
Watch the pressure as the boiler and system heat
2. up to ensure pressure rise is normal. Too high a rise would indicate a waterlogged or undersized expansion tank.
5. Read the Lighting instructions (Figure 21 of this manual or on boiler label) applying to the boiler.
6. Start the boiler following the Lighting instructions and manual section 7.
2. Inspect and test additional limit controls or low water cutoffs installed on system.
Figure 22 Automatic air vent, typical
A
B
26031
38
Air vents and air elimination
1. Inspect automatic air vents (if used). Also inspect air separators to ensure they are operational.
2. The cap must be unscrewed one turn to allow air to escape.
3. See Figure 22. If the air vent is leaking, remove cap
A and briefly push valve B and then release to clean
the valve seat.
4. Replace cap A by twisting all the way onto valve B and then unscrewing one turn.
Limit controls and cutoffs
1. Inspect and test the boiler limit control. Verify operation by turning control set point below boiler temperature. Boiler should cycle off. Return dial to original setting.
Expansion tank
1. Expansion tanks provide space for water to move in an out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See section suggested best location of expansion tanks and air eliminators.
Open-type — located above highest radiator or
baseboard unit, usually in the attic or closet. Has a gauge glass and overflow pipe to a drain.
Closed-type — welded gas tight and located above
boiler. Tank is partially filled with water, leaving an air cushion for expansion.
Make sure this type of tank is fitted with a tank , such as the B & G Tank-Trol or Taco
fitting
Taco-Trol. This fitting reduces gravity
3 of this manual for
Part number 550-110-260/0200
Page 39
Boiler Manual
Check/test . . . . . . .
circulation of air-saturated tank water back to the system and prevents the air from bubbling up through the water as it returns from the system.
Do not use automatic air vents in systems
with closed-type tanks.
from the system instead of returning to the tank. Eventually, the tank will waterlog and no longer control pressurization. The boiler relief valve will weep frequently.
Diaphragm- or bladder-type — welded gas tight
with a rubber membrane to separate the tank pressurizing air and the water. May be located at any point in the system, but most often found near the boiler.
Systems with this type of expansion tank require at least one automatic air vent, preferably located on top of an air eliminator, as shown in examples in manual section 3.
2. If relief valve has tended to weep frequently, the expansion tank may be waterlogged or undersized.
Closed-type tank — tank is most likely
waterlogged. Install a tank fitting if not already installed. Then check fill level per fitting manufacturer’s instructions. If fill level is correct, check tank size against manufacturer’s instructions. Replace with a larger tank if necessary.
Diaphragm- or bladder-type — first, check tank
size to be sure it is large enough for the system. If size is too small, add additional tank(s) as necessary to provide sufficient expansion. If tank size is large enough, remove tank from system and check charge pressure (usually 12 psig for residential applications). If tank won’t hold pressure, membrane has been damaged. Replace tank.
The air will escape
discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency — not by the owner. Failure to reinspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death or substantial property damage.
Following installation, the valve
lever must be operated AT LEAST
ONCE A YEAR to ensure that waterways are clear.
Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down boiler until a new relief valve has been installed.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
Figure 23 Relief valve, typical
Boiler relief valve
1. Inspect the relief valve and lift the lever to verify flow as in the following warnings, excerpted from a relief valve manufacturer’s warning label. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read manual section 3a before proceeding further.
EVERY THREE YEARS
contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and
Part number 550-110-260/0200
Safety relief valves should be
reinspected AT LEAST ONCE
, by a licensed plumbing
26032
39
Page 40
GOLD CGs Gas-Fired Water Boiler
Service & maint. — annual start-up10b
Review with owner . . . . . . . .
1. Review the User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the User’s
Information Manual
3. Remind the owner of the need to call in a licensed contractor should the boiler or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
(and in this manual as well).
Cleaning boiler heating surfaces
1. Shut down boiler:
Follow “To Turn Off Gas to Appliance” instructions on boiler and Lighting
instructions
Do not drain boiler unless it will be exposed to freezing temperatures. If using antifreeze in system, do not drain.
2. Follow shutdown procedure.
3. Remove venting system connection to boiler.
4. Remove top jacket panel. Turn back insulation.
5. Remove collector box/transition assembly. Clean sealant from assembly and sections.
6. Remove radiation plates hanging between sections.
7. Remove burners from base. Brush and vacuum burners to remove all dust and lint. Verify that all burner ports are free of debris.
8. Place newspapers in base of boiler to collect soot.
9. Clean between sections with wire flue brush.
10. Remove newspaper and soot. Vacuum or brush base and surrounding area.
11. Reinstall radiation plates.
12. Replace collector box/transition assembly. Seal with sealant. Obtain gas-tight seal to prevent flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
13. Replace insulation and jacket top panel.
14. Start up boiler following section Excessive sooting indicates improper gas combustion. If found check for proper combustion and make any necessary adjustments.
.
7 of this manual and the boiler Lighting instructions.
40
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 60 of this manual. Failure to comply could result in severe personal injury.
Part number 550-110-260/0200
Page 41
Boiler Manual
Troubleshooting — procedure11a
Before troubleshooting:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Never jumper (bypass) rollout thermal fuse element or any other device except for momentary testing as outlined in personal injury, death or substantial property damage can result.
1. Have the following items:
a. Voltmeter that can check 120 VAC and 24 VAC.
Troubleshooting Charts. Severe
b. Microammeter with a minimum scale range of 0-25.
c. Continuity checker.
d. Inclined manometer with 0 – 2" w.c. range.
2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to boiler.
3. Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.
Check the following:
1. Wire connectors to control module are securely plugged in at module and originating control.
2. Air pressure switch hoses are properly and securely plugged in and are not damaged.
3. Gas pressures:
a. With boiler off — 13" w.c. maximum natural or propane gas
pressure upstream of gas valve.
b. With boiler on:
Part number 550-110-260/0200
5" w.c. natural gas pressure or 11" w.c. propane gas pressure upstream of gas valve.
3 ½" w.c. natural gas pressure or 10" w.c. propane gas pressure downstream tapping on gas valve — Can be adjusted by regulator on gas valve.
VERIFY PROPER OPERATION AFTER SERVICING.
41
Page 42
GOLD CGs Gas-Fired Water Boiler
Troubleshooting — air pressure switch11b
Make sure boiler water temperature is 100 °F or cooler before starting procedure to obtain appropriate readings.
Check pressure switch setting
1. See Figure 24 and Table 6.
2. Remove both air pressure switch hoses from air pressure switch.
3. Install tees and tubing as shown in inclined manometer.
4. Turn off gas valve and set thermostat to call for heat. Inducer will run but burners will not ignite.
5. Check for 24 VAC between both air pressure switch terminals and ground.
6. If manometer reading is above the setpoint of the switch (see
Table 6), but there is not 24 VAC
between both air pressure switch terminals and ground — replace air pressure switch.
Figure 24 Manometer connections
Suction
Pressure
Figure 24 to
Table 6 Pressure switch setpoint
(for elevations above 2,000 ft, contact your local Weil-McLain sales office for details.)
Boiler model number Inches W.C.
CGs-3 1.79"
CGs-4 1.48"
CGs-5 1.22"
CGs-6 0.95"
Troubleshooting air pressure reading
1. If manometer reading is lower than the setpoint of the switch (see causes:
blockage in hoses
obstruction in inducer housing outlet
loose inducer wheel on motor shaft
inducer motor not in proper rpm
inducer back plate not sealed properly
blockage in block assembly
blockage in flue pipe or termination
incorrect pressure switch
Table 6) — check for possible
42
White
Side panel
Inclined tube manometer
Red
White
White
Red
Interior panel
Red
Flue collector
Rear panel
Return to normal operation
When pressure reading is correct and air pressure switch is operating properly — remove tees and reinstall hoses to air pressure switch.
The boiler will not operate correctly unless pressure switch hoses are correctly located. The red hose connects from the right side (negative) hose barb to the flue collector. The white hose connects from the left side (positive) hose barb of the switch to the connector box (between flue collector and
26035
inducer) as shown in Figure 24.
Part number 550-110-260/0200
Page 43
Boiler Manual
Troubleshooting — control module11c
Make sure ground wiring is installed per wiring diagram. Good grounding is extremely important for proper operation.
Solder or water splatter between
plugs and circuit board can cause improper operation of control module. Place a shield over the boiler internal controls and components during installation. Failure to comply could result in severe personal injury, death or substantial property damage.
Control indicator lights — lockout modes
See Charts 1 through 7 in this section for detailed troubleshooting procedures.
To reset control after a lockout, turn off power at the 120 VAC service switch or turn down all thermostats. Wait 45 seconds. Then restore power or call for heat.
POWER light flashing alone
Usually indicates reversed polarity of 120 VAC power wires.
POWER and TSTAT CIRC lights flashing
Usually indicates stray voltage on external thermostat circuit wires (usually due to miswired 3-wire zone valve).
POWER and PRESS SWITCH lights flashing
Usually indicates pressure switch is closed when it should not be, or pressure switch failed to close within 5 minutes of inducer starting.
POWER
and FLAME lights flashing
26036
Control indicator lights — non-lockout modes
FLAME light flashing alone
Usually indicates pilot flame was not established within 15 seconds from application of spark. Control will flash light, but will continue to cycle indefinitely until flame is established or problem is corrected.
PRESS SWITCH
Usually indicates pressure switch opened during the run cycle.
Troubleshooting the control module
light flashing alone
Usually indicates false flame sense or flame sensed when it shouldn’t be there.
Part number 550-110-260/0200
See Figure 25 for location of harness plug receptacles and plugs on the control module.
43
Page 44
GOLD CGs Gas-Fired Water Boiler
Troubleshooting — control module continued11c
Figure 25 Control module connections
High voltage to pilot spark electrode
Blue wire to gas valve PV
Red wires to pressure switch
Indicator lights
Red wire to gas valve MV
24 VAC control
circuits
FLAME
PRESS SWITCH
LIMIT
TSTAT CIRC
POWER
Black
White
120 VAC H
120 VAC N
120 VAC to
transformer
Black wires to
thermostat circuit
White wire to
gas valve MV/PV
Yellow wires to limit control
and rollout switch
SJO cable
to J-box
120 VAC H
120 VAC H
Entrance ground
Chassis ground
120 VAC N
24 VAC from transformer
Black
Black
Green
Green
White
120 VAC IN
Red
24 VAC
120 VAC to
inducer motor
Brown
Ground
Green
120 VAC N
White
44
26037
High voltage to spark electrode
120 VAC to transformer
120 VAC IN
24 VAC control circuits
24 VAC from transformer
120 VAC to inducer motor
120 VAC to circulator
Sense wire to flame sensor
120 VAC H
120 VAC N
Flame sense wire to pilot
Yellow
White
120 VAC to circulator
Part number 550-110-260/0200
Page 45
Boiler Manual
Troubleshooting — control module lights11d
CHART 1 — Troubleshooting POWER light status
— Usually indicates reversed 120 VAC polarity if POWER light flashes by itself —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
Is POWER light off?
No Yes
Is POWER light...
Flashing
alone
TSTAT CIRC
light flashing
PRESS SWITCH
light flashing
FLAME
light flashing
For insufficient heat or no heat problem, go to
Chart 7 if POWER light is on steady, with no other
light flashing.
Flashing with
another light
Chart 2
Chart 3
Chart 4
On steady
(not flashing)
Chart 5
Chart 6
• Make sure service switch or circuit breaker is on or fuses are good.
Remove 120 VAC IN plug (
44) on control module.
• Using voltmeter, check across top and bottom pins of 120 VAC IN plug.
Does voltmeter indicate 120 VAC?
No Yes
Problem is with incoming electricity. Have licensed electrician repair circuit.
• Reconnect 120 VAC IN plug.
Remove 120 VAC transformer PRIMARY plug (
25, item 2,
• Using voltmeter, check across top and bottom pins of PRIMARY receptacle.
page 44) on control module.
Does voltmeter indicate 120 VAC?
No Yes
Figure 25, item 3
, page
Figure
• Usually indicates polarity on incoming 120 VAC power line is wrong.
TURN OFF POWER at service switch or breaker, then reverse the HOT and NEUTRAL wires entering the boiler in the J-box.
• Restore POWER at service switch or breaker.
Is POWER light flashing now?
No Yes
Have system checked by a licensed electrician. If problem persists, call your
Boiler should now operate normally.
Part number 550-110-260/0200
local Weil-McLain sales representative.
Replace control module. Retest.
• Reinstall 120 VAC transformer PRIMARY plug. Remove 24 VAC transformer plug (
• page 44) on control module.
• Using voltmeter, check across pins of receptacle.
Does voltmeter indicate 24 VAC?
No Yes
Replace transformer. Retest.
Replace control module. Retest.
Figure 25, item 5,
45
Page 46
GOLD CGs Gas-Fired Water Boiler
Troubleshooting — control module lights11d
CHART 2 — TSTAT CIRC & POWER lights flashing
— Usually indicates 48 VAC on thermostat circuit (stray voltage) —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Disconnect the two external wires connected to the boiler thermostat leads (two black low voltage leads in J-box).
• Connect a voltmeter across these two incoming wires. Close each thermostat, zone valve and relay in the external circuit one at a time and check the voltmeter reading across the wires.
• There should NEVER be a voltage reading.
Did you find a voltage across the two external thermostat circuit wires?
• Leave external boiler thermostat connection wires disconnected from boiler.
• Troubleshoot the external thermostat circuit until you find the source of the stray voltage. (Pay close attention to the wiring connections to 3-wire zone valves.)
• Correct the problem and repeat the voltmeter test above, verifying there is no longer a voltage reading under any condition in the external thermostat circuit.
• If a voltage does occur under any condition, check and correct the external wiring. (This is a common problem when using 3-wire zone valves.)
• Once the external thermostat circuit wiring is checked and corrected if necessary, reconnect the external thermostat circuit wires to the boiler thermostat wires and allow the boiler to cycle.
NoYes
• If no voltage is found under any condition of the external thermostat circuit, connect the two boiler thermostat connection leads together (or jumper the boiler aquastat T-T terminals).
• Turn off power to the boiler for 1 minute.
• Turn on power and allow boiler to cycle.
Do the
TSTAT
No Yes
and
POWER
lights still flash?
• Boiler should now operate per the normal sequence of operation shown in Figure 18, page 31.
46
• Replace control module.
• Retest.
Part number 550-110-260/0200
Page 47
Boiler Manual
continued
CHART 3 — PRESS SWITCH & POWER lights flashing
— Usually indicates pressure switch stuck closed or failed to make within 5 minutes —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open.
Does inducer motor operate?
No Yes
• Wait 45 seconds.
Does inducer motor operate?
No Yes
• Remove INDUCER plug ( from plug receptacle of control module.
• Place voltmeter leads across the 120 VAC N and 120 VAC H pins of the INDUCER receptacle (left column center and right column bottom pins).
Does the voltmeter indicate 120 VAC?
No Yes
• Remove one of the wires connected to the pressure switch.
• Check continuity across the switch terminals.
Does the ohmmeter indicate the switch is closed?
No Yes
Figure 25, Item 6, page 44
• Try reseating plug in module receptacle and restart.
• If inducer still does not work, replace inducer assembly.
• Retest.
)
• Wait 5 minutes.
Is
PRESS SWITCH
No Yes
• Boiler should be in normal operating sequence.
• Observe operation until thermostat is satisfied and inducer has completed its post-purge cycle.
light flashing?
Are vent or combustion air
passages blocked?
No Yes
• Replace control module.
• Retest.
Part number 550-110-260/0200
• Check air pressure switch per manual Section 11.
• Replace if necessary.
• Retest.
• Clear passages and recycle boiler.
• Recheck boiler operation.
47
Page 48
GOLD CGs Gas-Fired Water Boiler
Troubleshooting — control module lights11d
CHART 4 — FLAME & POWER lights flashing
— Usually indicates flame sensed when it shouldn't be there —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
Are manual main shutoff valve and gas valve open?
No Yes
• Leave main manual gas valve closed.
• Turn off power to boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Lighting instructions in this manual (Figure 21, page 34).
Do
FLAME
TURN OFF POWER to boiler at service switch or breaker.
• Open main manual gas valve.
• Turn on power to boiler at service switch or breaker.
• Restart boiler per lighting instructions.
• Perform start-up procedures in boiler manual to verify proper operation.
and
POWER
lights still flash?
YesNo
• Replace control module.
• Retest.
• Allow boiler to continue cycling.
Are FLAME & POWER lights flashing?
No
• Boiler may now be operating normally.
• Perform start-up procedures in boiler manual to verify proper operation.
• Turn off power to the boiler at service switch or breaker.
• Wait at least 45 seconds.
• Turn on power to boiler.
• Restart boiler, following Lighting instructions in this manual (Figure 21, page 34).
• Look through the pilot inspection port (in front of air inlet box) to see if the pilot is burning during the prepurge period (first 30 seconds of operation).
Yes
• Replace control module.
• Retest.
Is pilot burning during prepurge period?
No
• Replace gas valve.
• Retest boiler.
Are FLAME and POWER lights flashing?
No
• Boiler should now operate normally.
• Original flashing FLAME light caused by gas valve not operating properly.
• See normal sequence of operation, Figure 18, page 31.
Yes
Yes
• Replace control module.
• Retest.
48
Part number 550-110-260/0200
Page 49
Boiler Manual
continued
CHART 5 — FLAME light flashing and POWER light on steady
ALSO — Troubleshooting failure to establish main flame
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
No Yes
TURN OFF POWER to boiler at service switch or breaker.
• Open main manual shutoff valve and boiler gas valve (per Lighting instructions in this manual). Wait at least 45 seconds.
• Turn on power at service switch or breaker. Allow boiler to cycle.
• Boiler should be in normal operating sequence.
• Observe operation until thermostat is satisfied and blower has completed its post-purge cycle.
TURN OFF POWER to boiler at service switch or breaker.
• Remove air inlet box top (see Figure 27, page 54 for location).
• Verify pilot gas line is not kinked, obstructed or damaged and is correctly attached to pilot and gas valve.
• Verify pilot ignition electrode, electrode ceramic and spark lead wire from control are in good condition. Spark gap should be approximately 1/8".
• Correct any above problems, replacing pilot if burner or wiring is damaged.
• Reinstall air box top to operate boiler for retest after any changes or corrections.
• If none of the above corrects problem, then replace the control module, reinstall air box top, and retest.
Does
FLAME
No Yes
light flash now?
• Verify inlet gas pressure at gas valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and
within above range?
Yes
• Contact gas supplier to correct pressure or gas supply.
TURN OFF POWER to boiler at service switch or breaker.
• Remove air inlet box cover (see Figure 27, page 54 for location).
• Verify pilot burner is securely attached to pilot bracket, bracket is securely attached to cross tie, and there is no corrosion on the parts which would affect the ground path for flame sense.
• Verify that pilot flame rod, flame rod ceramic and lead wire from control module to flame rod are in good condition.
• Correct any above problems, replacing pilot if burner or wiring is damaged.
No
• Is pilot flame visible through inspection port?• Are main manual shutoff valve and boiler gas valve open?
No Yes
• Check the voltage across terminals "C" and "A" of the gas valve (see Table G, page 33).
Is 24 VAC present there?
NoYes
• If the wiring from the control module to gas valve is intact, replace the control module.
• Retest.
• Verify inlet gas pressure at gas valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
• Make sure ground wire terminal is securely fastened to control module mounting screw.
• Check the voltage across terminals "B" and "A" (see Table G, page 33) of the gas valve.
Is 24 VAC present there?
No Yes
Is gas present at gas valve inlet and within above range?
No
TURN OFF POWER to boiler at service switch or breaker.
• Check flame signal — Detach sense lead from igntion control
Figure 25, item 8, page 44
(
• Connect negative lead of MICROAMMETER to control sense terminal ( MICROAMMETER to sense wire.
• DISCONNECT red wire connected to terminal "B" (see Table G, page 33) of the gas valve.
• Turn on power to boiler and allow to cycle. As soon as pilot is burning, the MICROAMMETER should read at least 1.0 microamp.
Figure 25, item 8, page 44
).
). Connect positive lead of
Yes
Is flame signal at least 1.0 microamp?
No Yes
• If none of the previous steps (including replacing pilot) corrects problem, then replace the control module, reinstall air box cover and retest.
• If the wiring from the control module to gas valve is intact, replace the control module and retest.
Part number 550-110-260/0200
49
Page 50
GOLD CGs Gas-Fired Water Boiler
Troubleshooting — control module lights11d
CHART 6 — PRESS SWITCH light flashing and POWER light on steady
— Usually indicates pressure switch opened during run cycle —
— May also be caused by wind gusts in excess of 31 mph for non-direct vent sidewall-vented boilers —
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open.
Does blower motor operate?
No Yes
• Remove INDUCER plug ( from plug receptacle of control module.
• Place voltmeter leads across the 120 VAC N and 120 VAC H pins of the INDUCER receptacle (left column center and right column bottom pins).
Does the voltmeter indicate 120 VAC?
No Yes
• Remove one of the wires connected to the pressure switch.
• Check continuity across the switch terminals.
Does the ohmmeter indicate the switch is closed?
No Yes
• Inspect and check wire harness from control module to pressure switch.
• Reseat connector in control module receptacle.
• If harness is intact and properly seated, but problem persists, replace control module.
• Retest.
Figure 25, Item 6, page 44
• Replace inducer assembly.
• Retest.
• Check air pressure switch per manual Section 11.
• Replace if necessary. Retest.
)
• Wait 5 minutes.
Is
PRESS SWITCH
No Yes
• Boiler should be in normal operating sequence.
• Observe operation until thermostat is satisfied and inducer has completed its post­purge cycle.
Are vent or combustion air passages blocked?
No Yes
• Clear passages and recycle
• Recheck boiler operation.
light flashing?
boiler.
50
Part number 550-110-260/0200
Page 51
continued
Boiler Manual
CHART 7 — Insufficient heat or no heat to system (POWER light on steady)
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.
• Has it been at least 5 minutes since setting thermostat to call for heat? If not, wait 5 minutes. Is system heating?
• Is thermostat set to call for heat? Remove thermostat wires at boiler and check continuity across the two wires. If circuit isn't closed, check external thermostat (zone valve, relay, etc.) wiring. Correct problems and retry.
• Reconnect external thermostat wiring at boiler.
Is thermostat circuit closed (continuity across wires)?
No Yes
• Boiler is in standby.
Are all red lights off?
No Yes
Wait 30 seconds. Are all red lights off?
No Yes
Replace control module. Retest.
• If you have sufficient heat — boiler should be in normal operating sequence. (See normal sequence of operation, Figure 18.)
• If you have less than sufficient heat —
• Set thermostat to call for heat and recheck operation.
• Verify Sequence of operation, Figure 18, page 31.
Is vent or combustion air piping free of blockage?
No Yes
• Correct conditions and recheck operation.
• See Figure 18, page 31 for normal sequence of operation.
• Wait for boiler water to cool to temperature 20 to 30 ˚F lower than temperature set on limit switch.
Contact your Weil-McLain sales representative.
Are limit switch contacts closed?
No Yes
• Boiler water temperature exceeded setting on limit switch with thermostat
• Replace limit switch.
• Retest.
calling for heat. Boiler is OK. (See normal sequence of operation, Figure 18, p. 31.)
• Also check setting on limit switch (should be above 140˚F.).
Is boiler System circulator operating?
No Yes
• Remove CIRCULATOR harness plug from CIRCULATOR plug receptacle (
7, page 44
control module receptacle.
). Check with voltmeter across pins of
Figure 25, Item
Does voltmeter show 120 VAC across pins?
No Yes
• Replace control module.
• Retest.
• Wait 5 minutes.
No Yes
• Check limit switch contacts with continuity checker.
• Repair/replace
• Repair/replace
Is
FLAME
Is
LIMIT
circulator. Retest.
wiring. Retest.
light on?
light on?
• Replace control module.
• Retest.
Are limit switch contacts
closed?
No Yes
Check rollout switch
continuity — is switch
closed?
No Yes
• Replace rollout switch.
If rollout thermal fuse element has opened, determine cause and correct condition. Failure to do so will cause severe personal injury, death or substantial property damage.
• Check any other limit controls wired into the limit circuit. If all are OK, then replace control module.
• Retest.
NoYes
Part number 550-110-260/0200
51
Page 52
GOLD CGs Gas-Fired Water Boiler
Replacement parts12a
Section assembly................................................ 53
Base assembly .................................................... 54
Jacket assembly ................................................. 55
Trim assembly ..................................................... 56
Gas control assembly ......................................... 57
Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part number of replacement part. Results from using modified or other manufactured parts will not be covered by warranty and may damage boiler or impair operation.
Weil-McLain part numbers are found in Weil-McLain Boilers and
Controls Repair Parts Lists
.
52
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 60 of this manual. Failure to comply could result in severe personal injury.
Part number 550-110-260/0200
Page 53
Page 54
Page 55
Page 56
Page 57
Page 58
GOLD CGs Gas-Fired Water Boiler
Dimensions13a
Figure 31 Dimensional drawing
Supply piping ( )
Return piping ( )
Relief valve, ¾" NPT
½" NPT to expansion tank/air vent
3" Diameter vent
A LL DIMENSIONS IN INCHES
13¹⁄₄
note 1
note 1
NOTE 2
19
28³⁄₈
11¹⁄₈
3¹⁄₄
NOTE 2
2¹⁄₄
A
T OP VIEW
2³⁄₈
MODEL
CGi
3"/3½" Dia. air pipe connection
Gas supply piping
Drain valve
Gas supply entrance (right or left side)
Pressure/temperature gauge
Boiler supply and return tappings are both 1¼" NPT.
Note 1:
See , page 14 for recommended system sup-
Table 3
ply and returnpiping sizes.
Boiler circulator is shipped loose. Circulator may be
Note 2:
mounted on either boiler supply or return piping. Circulator flange provided with boiler is same size as recommended pipe sizein ,page 14.Table3
4³⁄₄4³⁄₄
19
13¹¹₁₆
9
Gas
Note 3
W
F RONT
Gas
manifold size
Note 3
(inches NPT)
“A”
Air inlet
pipe center
(inches)
26060
12
23¹⁄₄
Boiler model number
Supply
tapping
(inches NPT)
1⁵⁄₈
Return
tapping
(inches NPT)
connection size
(inches NPT)
CGs-3 ½ ½ 13
CGs-4 ½ ½ 8 16
CGs-5 ½ ½ 19
CGs-6 ½ ½ 11 22
Note 3: Gas piping from meter to boiler to be sized per local utility requirements.
58
Part number 550-110-260/0200
R IGHT SIDEL EFT SIDE
“W”
Jacket
width
(inches)
Page 59
Boiler Manual
13b
Ratings
DOE
Table 7 Boiler ratings
Boiler model number
(Note 1) (Note 2) (Note 3) (Note 5) (Note 4)
CGs-3
(Note 5)
CGs-4 85,000 100,000 85,000 90,000 76,500 74,000 2.1 84.6 3"
DOE
Heating
capacity
(Btuh)
57,000 67,000 57,300 60,300 51,600 50,000 1.5 85.3 3"
0-2,000 feet 2,000-4,500 feet Net
Input
(Btuh)
Output
(Btuh)
Input
(Btuh)
Output
(Btuh)
I=B=R
ratings
(Btuh)
Boiler water
content
(gallons)
DOE
Seasonal
efficiency
(% AFUE)
(Note 5)
Vent
size
CGs-5 112,000 133,000 112,400 119,000 100,600 97,000 2.7 84.0 3"
CGs-6 140,000 167,000 140,300 150,300 126,300 122,000 3.3 83.4 3"
Notes
1. Add “PIN” for natural gas boiler - “PIL” for propane gas
boiler.
2. Based on standard test procedures prescribed by the United States Department of Energy.
3. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15. An additional allowance should be
made for unusual piping and pickup loads.
4. CGs boilers require special venting, consistent with Category III or IV boiler. Use only the vent materials and methods specified in CGs vent supplements. CGs boilers may be direct-vented (using 3" diameter air piping) as specified in the direct vent supplements.
5. As an Energy Star Partner, Weil-McLain has determined that the CGs-3 meets the Energy Star guidelines for energy efficiency.
CGs boilers for residential radiant panel systems, converted gravity heating systems or other low water temperature applications should be installed with balancing valves and bypass piping equal to the supply and return size to avoid excessive flue gas condensation due to lower operating water temperatures. For alternate piping, contact your Weil-McLain sales office. CSA design certified for installation on combustible flooring. Tested for 50 psi working pressure.
Part number 550-110-260/0200
59
Page 60
GOLD CGs Gas-Fired Water Boiler — Boiler Manual
Handling ceramic fiber and fiberglass materials
REMOVAL OF COMBUSTION CHAMBER LINING OR BASE PANELS
The combustion chamber lining or base insulation panels in this product contain ceramic fiber materials. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).":
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this web site.
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining or base insulation to prevent airborne dust.
Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag for
disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately
Breathing: Fresh air.
REMOVAL OF FIBERGLASS WOOL — OR —
INSTALLATION OF FIBERGLASS WOOL, COMBUSTION CHAMBER LINING OR BASE PANELS:
This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber lining or base panels in gas fired products. Airborne fibers from these materials have been listed by the State of California as a possible cause of cancer through inhalation.
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for fiberglass wool at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this web site.
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Operations such as sawing, blowing, tear out, and spraying may generate airborne fiber concentration requiring additional protection.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately
Breathing: Fresh air.
60
Weil-McLain
500 Blaine Street
Michigan City, IN 46360-2388
http://www.weil-mclain.com
Part Number 550-110-260/0200
Loading...