Weil-McLain CGS 550-110-260-02002 User Manual

GOLD CGs Gas-Fired Water Boiler
How it works . . .
Control module
The control module responds to signals from the room thermostat, air pressure switch and boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and inducer. When room thermostat calls for heat, the control module starts the system circulator and inducer.
The control module runs the inducer long enough to purge the boiler flue passages, then opens the pilot valve and activates pilot ignition spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within 15 seconds, the control module will turn off the gas valve, flash the Flame light, and then enter a 15-second postpurge. The control module will then start a new cycle. This will continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven, the control module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve, operates the inducer for a 15-second postpurge and waits for the next heat call.
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs, the control module flashes combinations of lights to indicate the most likely reason for the problem (see page 43).
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Inducer
The inducer pulls flue gases through the boiler, causing air to be pulled in through the air intake opening. The inducer pushes the flue gases through the vent pipe as well.
Air pressure switch
The air pressure switch signals the control module, telling the control module whether air is moving through the inducer.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting. (The circulator will continue to run as long as there is a call for heat.)
Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and can be mounted on either the boiler supply or return piping. The factory­installed circulator wiring harness provides ample length for either location. NOTE — The control module provides a pump exercising routine. If the boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
Other boiler components:
a supply to system
b return from system
c combustion air inlet
d flue outlet
e gas valve
f pressure/temperature gauge
g relief valve (not visible)
h air vent connection
i flame rollout switch
j air inlet box
k pilot burner and bracket
l stainless steel burners
m cast iron boiler sections
n flue collector
o junction box
2
Part number 550-110-260/0200
GOLD CGs Gas-Fired Water Boiler
Contents
How it works .................................................................. 2–3
Hazard definitions.............................................................. 4
Please read before proceeding ......................................... 5
1. Prepare boiler location ............................................ 6–11
2. Prepare boiler......................................................... 12–13
3. Water piping........................................................... 14–23
4. Venting & combustion air............................................ 24
5. Gas piping .............................................................. 24–25
6. Field wiring................................................................... 26
7. Start-up .................................................................. 27–29
8. Check-out procedure ................................................... 30
9. Operation ............................................................... 31–34
10. Service and maintenance.................................... 35–40
11. Troubleshooting .................................................. 41–51
12. Replacement parts............................................... 52–57
13. Dimensions and ratings ...................................... 58–59
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
4
Part number 550-110-260/0200
Boiler Manual
Please read before proceeding
Installer
Read all instructions before installing.
proper order to prevent personal injury or death.
Also refer to CGs Venting Supplements.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
When calling or writing about the boiler— Please have the boiler model number from the boiler rating label and the CP number from the boiler jacket. You may list the CP number in the space provided on the Installation and service certificate found on page 30.
Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.
When servicing boiler —
To avoid electric shock, disconnect electrical supply before performing maintenance.
To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation —
Do not block flow of combustion or ventilation air to boiler.
Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water.
Boiler water —
Do not use petroleum-based cleaning or sealing compounds in boiler system. Water seal deterioration will occur, causing leakage between sections. This can result in substantial property damage.
Do not use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel and/or property may result.
Follow all instructions in
User
This manual is for use only by your qualified
heating installer/service technician.
Please refer to the User’s Information Manual for your reference.
We recommend regular service by a qualified
service technician, at least annually
Continual fresh makeup water will reduce boiler
life. Mineral buildup in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.
Do not add cold water to hot boiler. Thermal
shock can cause sections to crack.
Glycol — potential fire hazard —
All glycol is flammable when exposed to high temperatures. If glycol is allowed to accumulate in or around the boiler or any other potential ignition source, a fire can develop. In order to prevent potential severe personal injury, death or substantial property damage from fire and/or structural damage:
Never store glycol of any kind near the boiler or
any potential ignition source.
Monitor and inspect the system and boiler
regularly for leakage. Repair any leaks immediately to prevent possible accumulation of glycol.
Never use automotive antifreeze or ethylene
glycol in the system. Using these glycols can lead to hazardous leakage of glycol in the boiler system.
.
Part number 550-110-260/0200
5
GOLD CGs Gas-Fired Water Boiler
1a
Prepare boiler location —
Installations must
follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1 – latest edition.
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
The CGs boiler gas manifold and controls met safe lighting and other performance criteria when boiler underwent tests specified in ANSI Z21.13 — latest edition.
codes & checklist
Before locating the boiler,
check the following:
Check for nearby connection to:
System water piping
Venting connections
Gas supply piping
Electrical power
Check area around boiler. Remove any combustible materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
Boiler must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.
If new boiler will replace existing boiler, check for and correct system problems, such as:
1. System leaks causing oxygen corrosion or section cracks from hard water deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and leak.
6
Part number 550-110-260/0200
Boiler Manual
Prepare boiler location — clearances1b
Provide the following clearances:
1. Hot water pipes — at least ½" from combustible materials.
2. Recommended service clearances — See Figure 1.
3. Minimum clearances for tight spaces — See
Figure 2.
Figure 1 Recommended clearances for service
Figure 2 Minimum clearances for tight spaces
Flooring and foundation
Flooring
The CGs boiler is approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
Foundation
Provide a solid brick or minimum 2-inch thick concrete foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
The minimum foundation size is
Boiler model number Width — Inches
CGs-3 15
CGs-4 18
CGs-5 21
CGs-6 24
25" long by:
Part number 550-110-260/0200
Residential garage installation
Precautions
Take the following special precautions when installing the boiler in a residential garage. If the boiler is located in a residential garage, per ANSI Z223.1, paragraph
5.1.9:
Mount the boiler a minimum of 18 inches
above the floor
burner and ignition devices will be no less than 18 inches above the floor.
Locate or protect the boiler so it cannot be damaged by a moving vehicle.
of the garage to assure the
7
GOLD CGs Gas-Fired Water Boiler
1c
Prepare boiler location — vent system
Removing from existing vent
Do not install the CGs into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
When removing boiler from existing common vent system:
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common venting
system.
Visually inspect the venting system for proper
b.
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
c.
Test vent system — Insofar as is practical, close
all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning
each appliance
appliance to their previous conditions of use.
Any improper operation of common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 — latest edition. Correct by resizing to approach the minimum size as determined using the appropriate tables in Part 11 of that code. Canadian installations must comply with B149.1 or B149.2 Installation Code.
CGs special vent system
Vent system
The CGs boiler requires a special vent system, designed for pressurized venting. Model CGs-3 is rated ANSI Z21.13 Category IV (pressurized vent, likely to condense in the vent). Models CGs-4, -5 and -6 are rated Z21.13 Category III (pressurized vent).
You may use any of the vent systems covered by the CGs Venting Supplements included in the envelope assembly. The CGs vent starter is a special item, designed only for the CGs boiler, available from each vendor. Do not attempt to connect the vent to the CGs boiler with any other means.
DO NOT mix components from
different systems. The vent system could fail, causing leakage of flue products into the living space.
Vent termination and combustion air supply
The CGs boiler may be vented through the roof or through a side wall. Follow the appropriate vent supplement for the vent system chosen. The maximum vent length depends on boiler size. Refer to the vent supplement to determine acceptable vent length.
Combustion air for the CGs boiler may be from inside or ducted directly to the boiler from outside. For outside air (direct vent installation), two options are available for the flue/air termination. The air supply must
ALWAYS terminate at the same location as the
flue, using either:
1. Vertical direct vent installation. Obtain the Weil- McLain Through-Roof or Through-Unused
Chimney Vertical Direct Venting Venting Supplement, packed
with the kit, and to the vent manufacturer’s instructions for the vent material chosen.
2. Sidewall direct vent installation. Use the Vent/Air
Intake
Refer to
Exhaust Venting: Vertical or Sidewall
Supplement shipped with the boiler.
termination kit and supplement. Refer to
termination kit shipped with the boiler.
CGs Direct Venting: Sidewall & Direct
Venting
8
Part number 550-110-260/0200
Boiler Manual
1d
Prepare boiler location — contamination
Air contamination
Please review the following information on potential combustion air contamination problems.
If the boiler is installed in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must pipe combustion air to the boiler air intake. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death or substantial property damage. Do not install CGs boiler in a
room or pool facility, for example, without using ducted outside air. These areas will always
contain contaminants.
Table 1 Corrosive contaminants
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
Permanent wave solutions Swimming pools
Refer to Table 1 for products and areas which may cause contaminated combustion air.
laundry
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers Remodeling areas
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and other similar products
Part number 550-110-260/0200
9
GOLD CGs Gas-Fired Water Boiler
Prepare boiler location — air openings1e
CGs combustion air options
Using inside air — direct exhaust vent
The CGs boiler can use inside air if no contaminants are present in the boiler space. If contaminants are likely to be present, install the CGs boiler as a direct vent appliance, using the appropriate vent supplement and the instructions in this manual.
Using outside air — direct vent
Combustion air can be ducted directly from outside to the CGs boiler air intake fitting. This method is defined as combustion). Refer to the appropriate vent supplement and the instructions in this manual. Two options are available: sidewall or vertical direct vent. Each requires a special vent component kit.
direct vent (also referred to as sealed
Sizing air openings
Air openings provide for ventilation (as well as combustion air) to prevent overheating of the boiler controls and boiler space. Air is also needed for other appliances located in the same space.
Figure 3, selecting the appropriate installation
Use conditions. Note that the sizing given in Figure 3 applies only to CGs installations with clearances no
smaller than shown in Figure 1, page 7 of this manual.
For smaller clearances, regardless of how the air openings are arranged, two openings providing free area of 1 square inch per 1,000 Btuh input of all appliances in the space are required.
Air openings must be sized to handle all appliances and air movers (exhaust fans, etc.) using the air supply.
Louver allowance
The free area of openings means the area after
reduction for any installed louvers or grilles
to consider this reduction when sizing the air openings.
. Be sure
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction where:
a. Walls and ceilings exposed to the outside
atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed, and . . .
b. Weather-stripping has been added on openable
windows and doors, and . . .
c. Caulking or sealants are applied to areas such as
joints around windows and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and in other openings.
For buildings with such construction, provide air openings into the building from outside, sized per the appropriate case in inside air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative pressure unless all appliances are installed as direct vent. Always provide air openings sized not only to the dimensions required for the firing rate of all appliances, but also to handle the air movement rate of the exhaust fans or air movers using air from the building or space.
Motorized air dampers
Figure 3 if appliances are to use
10
The sizing given in Figure 3 is based on the National Fuel Gas Code, ANSI Z223.1, allowing adequate air opening for gravity-vented gas appliances (Category I). The CGs boiler is rated Category III or IV (pressurized vent), and has different requirements for combustion and ventilation air, reflected by the special sizing instructions given in Figure 3. The air openings recommended in Figure 3 will allow adequate ventilation and combustion air provided the boiler room is not subjected to negative pressure due to exhaust fans or other mechanical ventilation devices. Refer to the National Fuel Gas Code for dealing with other conditions.
If the air openings are fitted with motorized dampers, electrically interlock the damper to:
Prevent the boiler from firing if the damper is not fully open.
Shut the boiler down should the damper close during boiler operation.
To accomplish this interlock, wire an (proving the damper open) in series with the thermostat input to the boiler. The boiler will not start if this contact is open, and will shut down should it open during operation.
Part number 550-110-260/0200
isolated contact
Boiler Manual
Figure 3 Sizing air openings for CGs installations
Room Air Openings
Required area of the air openings given in this table are free area — after the correction for louver obstruction. (See below.)Exception
Apply this table only to installations with clearances no smaller than those shown in Figure 1, page 7 of this manual.
For installations with clearances less than shown in Figure 1, page 7 of this manual, provide 2 openings, each with 1 square inch of free area per 1,000 Btuh of total input of all appliances.
A
Air from Inside
CGs
B
Air
Directly
from
CGs
Outside
12”
Max
12”
Max
Air
opening
Air
opening
12”
Max
opening
opening
12”
Max
Inside
Air
Air
Direct exhaust vent installation
(CGs using room air for combustion)
Other
appliances
CGs CGs
Room
with other appliances
2 Openings — each opening:
1 square inch
free area per
Outside
1,000
Btuh input of
other appliances
shared Room
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
of
plus CGs
2 Openings — each opening:
1 square inch
free area per
Outside
4,000
Btuh input of
other appliances
2 Openings — each opening:
1 square inch
free area per
4,000
of
plus CGs
Direct vent installation
(combustion air piped to CGs)
Combustion
Other
appliances
alone CGs
in room
with other appliances
air piping
CGs
shared
2 Openings —
each opening:
1 square inch
free area per
1,000
Btuh input
CGs
Btuh input of other appliances only (not )
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
Btuh input of other appliances only (not )
CGs
Combustion
air piping
CGs
alone
in room
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
C
Air from
Outside
Through horizontal ducts
CGs
Outside or ventilated attic
D
Air from or
Outside Attic
Lower Opening in Floor or Vertical Duct
CGs
Ventilated
crawl space
26007
Exception to combustion air opening rules:
NO Openings are
needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
NO Openings are needed, provided:
Clearance around boiler is
NO LESS
than shown in Figure 1, page 7 of this manual.
Max
Max
12”
12”
Max
Air
opening
Air
opening
12”
Duct
2 Openings — each opening:
Duct
1 square inch
Inside
Duct
free area per
Outside
2,000
other appliances
plus CGs
Btuh input of
2 Openings — each opening:
1 square inch
free area per
Outside
4,000
Or
Btuh input of
other appliances
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
of
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input
CGs
of
plus CGs
combustion air openings are needed when theboiler (and other appliances) are installed ina space with a volume
NO NO LESS
(1,000's of Btuh) andmultiply this numbertimes 50. (see page 10).
Example:
than 50 cubic feet per 1,000 Btuh of all installed appliances. Sum the total input of all appliances in MBH
Building must not be of Tight construction
For total input of 100 MBH (100,000 Btuh), minimum volume is 50 x 100 = 5,000 cubic feet. At a ceiling
2 Openings — each opening:
1 square inch
free area per
2,000
Btuh input of other appliances only (not )
CGs
2 Openings — each opening:
1 square inch
free area per
4,000
Btuh input of other appliances only (not )
CGs
height of 8feet, space must have at least 5,000÷8=625square feet (25feet x 25 feet, for instance).
Part number 550-110-260/0200
11
GOLD CGs Gas-Fired Water Boiler
Prepare boiler — placement & setup2a
Place boiler/crate near position
1. Leave boiler in crate and on pallet until installation site is ready.
2. Move entire crate and pallet next to selected location.
3. Remove crate.
4. Remove boiler from pallet.
Do not drop boiler or bump jacket on floor or pallet. Damage to boiler can result.
a. Tilt left side of boiler up and place a board
under left legs.
b. Tilt boiler the other way and place a board
under right legs.
c. Slide boiler backward off pallet and into
position.
5. Check level.
a. Shim legs, if necessary.
b. Do not alter legs.
Inspect orifices and burners
1. Remove front jacket door. Remove inlet air box top panel (see Figure 27, item 13, page 54).
death or substantial property damage.
3. Reinstall inlet air box top panel.
Inlet air box top panel must be in position during boiler operation. Failure to do so could result in severe personal injury, death or substantial property damage.
Orifice replacement procedure
(when required)
1. Remove the screws securing the inlet air box top panel.
2. Remove inlet air box top panel and inspect the fiber gasket. Verify the gasket is in good condition and can seal around the complete perimeter of the air box. Replace the gasket if necessary.
3. Using a 7/16" open-end wrench, remove the burner orifices from the manifold.
4. Apply a small amount of pipe dope to each of the new orifices and install in the manifold using a 7/16" open-end wrench. Make sure the orifices are aligned correctly, not cross-threaded in the manifold tappings.
Use only pipe dope compatible with propane gas, even if boiler is to be operated on natural gas. Failure to comply could result in severe personal injury, death or substantial property damage.
12
2. Check for correctly-sized manifold orifices. See
Table 2 for sizing. (The orifice size is stamped on
the orifice spud barrel.)
Correctly-sized manifold orifices must be used. Failure to do so will result in severe personal injury,
Table 2 Manifold orifice sizing
Location Natural gas Propane gas
0-2,000 ft over 2,000 ft 0-2,000 ft over 2,000 ft
U. S.
2.70 mm (Note 1) 1.65 mm (Note 1)
0-2,000 ft 2,000-4,500 0-2,000 ft 2,000-4,500
Canada
2.70 mm #38 1.65 mm #53
Note 1: For elevations above 2,000 feet, contact your local Weil-McLain sales office for details.
5. Carefully replace the inlet air box top panel, making sure the gasket is in place will seal all around the perimeter.
6. Follow the check-out procedure, section to assure the boiler is now operating properly after orifices are replaced.
8 page 30,
Part number 550-110-260/0200
Boiler Manual
2b
Prepare boiler — pressure test
Perform hydrostatic pressure test
Pressure test boiler before attaching water or gas piping (except as noted below) or electrical supply.
Prepare boiler for test
1. Remove the shipping nipple (from CGs supply tapping) and remove the boiler relief valve.
Temporarily plug the relief valve tapping with a ¾" NPT pipe plug.
2. Remove 1¼" nipple, reducing tee and drain valve from accessory bag. Install in boiler return connection as shown on page 3 and the return or supply.
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature gauge from accessory bag. Pipe to boiler supply connection as shown on page 3 and Figure 29, page 56. (Use pipe dope sparingly.)
4. Connect a hose to boiler drain valve, the other end connected to a fresh water supply. Make sure hose can also be used to drain boiler after test.
5. Connect a nipple and shutoff valve to system supply connection on the 1¼" tee. This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
6. Connect a nipple and shutoff valve to system return connection (at circulator flange if circulator installed on return). This valve will be used to bleed air during the fill. (Valve and nipple are not included with boiler.)
Fill and pressure test
1. Open the shutoff valves you installed on supply and return connections.
2. Slowly open boiler drain valve and fresh water supply to fill boiler with water.
3. When water flows from shutoff valves, close boiler drain valve.
4. Close shutoff valves.
5. Slowly reopen boiler drain valve until test pressure on the pressure/temperature gauge reaches no more than:
45 psig for boilers with 30 psig relief valve.
75 psig
6. Test for no more than 10 minutes at:
45 psig
75 psig
7. Make sure constant gauge pressure has been maintained throughout test. Check for leaks. Repair if found.
for boilers with 50 psig relief valve.
for boilers with 30 psig relief valve. for boilers with 50 psig relief valve.
Do not leave boiler unattended. A cold water fill could expand and cause
excessive pressure, resulting in severe personal injury, death or substantial property damage.
Leaks must be repaired at once. Failure to do so can damage boiler,
resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
Figure 29, page 56. Install circulator on either
Part number 550-110-260/0200
Drain and remove fittings
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever provides best access to drain. Remove hose after draining if used to drain boiler.
3. Remove nipples and valves unless they will remain for use in the system piping.
4. Remove plug from relief valve tapping. See section 3a to replace relief valve.
13
GOLD CGs Gas-Fired Water Boiler
Boiler model
number
To
system
From
system
CGs-3 1" 1"
CGs-4 1" 1"
CGs-5 1" 1"
CGs-6 1 ¼" 1 ¼"
Note: Circulator flange supplied with boiler is same size as
recommended piping above.
3a
Water piping —
general information
General piping information
If installation is to comply with ASME or Canadian requirements, an additional piping between boiler and isolation valve. Set second control to minimum 20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F. See section
A low water cutoff device is required when boiler is installed above radiation level or by certain state or local codes or insurance companies. Use low water cutoff designed for water installations. Electrode probe­type is recommended. Purchase and install in tee in supply piping above boiler.
Use backflow check valve in cold water supply as required by local codes.
high temperature limit is needed. Install control in supply
9b, page 32 for wiring.
Pressure/temperature gauge
Install pressure/temperature gauge in tee on supply piping (as shown in drawing on page 3). The gauge well is a self-closing valve, allowing removal of the gauge without draining the system.
Slowly remove pressure/temperature gauge from well. The self-closing valve could leak if clogged with sediment. If water begins to spray, stop removing gauge. Close system fill valve and drain enough water to release system pressure before continuing with gauge removal. Escaping hot water could cause severe personal injury.
Circulator
The circulator is shipped loose (wiring pre-attached to boiler) to allow you to locate it either in the return or supply piping, as desired. See page 3 for a typical installation. Pipe the expansion tank to the suction side of the circulator whenever possible. Install an air separator in the supply piping. Connect the expansion tank to the air separator only if the separator is on the suction side of the circulator. Always install the system fill connection at the same point as the expansion tank connection to the system. Figures 4 and 5 show typical near-boiler piping connections.
System water piping
See Figure 4 (diaphragm-type or bladder-type expansion tank) or tank) on page 15, and and single-zone systems designed for return water at least 130 °F.
See pages 16-17 to complete multiple-zone piping or pages 18-23 to complete piping for radiant heating systems or converted gravity systems.
Refer to page 23 for boilers used with refrigeration systems.
Figure 5 (closed-type expansion
Table 3 below, for near-boiler
Relief valve
Install relief valve vertically in ¾" tapping on side of boiler. See Figure 4
and the tag attached to the relief valve for manufacturer’s instructions.
or 5
To avoid water damage or scalding due to relief valve operation:
Discharge line must be connected to relief valve outlet and
safe place of disposal
possibility of severe burns should the valve discharge.
Discharge line must be as short as possible and be the
the valve discharge connection
Discharge line must least 6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler,
or in the discharge line. Do not plug or place any obstruction in the discharge line.
Failure to comply with the above guidelines could result in failure of
the relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.
Test the operation of the valve after filling and pressurizing system
by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
14
. Terminate the discharge line to eliminate
throughout its entire length.
pitch downward from the valve and terminate at
Table 3 Water pipe size (based on 20 °F rise)
run to a
same size as
Install boiler such that —
Chilled medium, if used, is piped in parallel with heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. Consult I=B=R Installation and Piping Guides.
If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle. Circulation of cold water through the boiler could result in damage to the heat exchanger, causing possible severe personal injury, death or substantial property damage.
Part number 550-110-260/0200
Boiler Manual
Water piping — single-zone system3b
Expansion tank
Diaphragm-type or bladder-type expansion tank — Figure 4
1. Ensure expansion tank size will handle boiler and system water volume and temperature. Tank must be located in boiler return piping as close to boiler as possible, before inlet side of circulator. See tank manufacturer’s instructions for details.
2. Install an shown.
automatic air vent in air vent tapping as
Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual section failure can result.
Use Figure 4 or Figure 5 only for single-zone systems designed for return water at least 130 °F. For systems with low return water temperature possible, such as converted gravity systems and radiant heating systems, refer to the special piping suggestions of pages 18-23. Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Closed-type expansion tank — Figure 5
1. Ensure expansion tank size will handle boiler and system water volume and temperature. See tank manufacturer’s instructions for details.
2. Connect tank to ½" NPT tapping located behind supply outlet, using ½" NPT piping. Pitch any horizontal piping up towards tank 1 inch per 5 feet of piping.
Figure 4 Diaphragm- or bladder-type expansion tank
Piping to single-zone system using diaphragm-type or bladder-type expansion tank. See Table 3 for piping sizes.
From system
Isolation valve
Relief valve
Cold water fill
To DIAPHRAGM expansion tank and fittings
Isolation valve
To system
Circulator*
Automatic air vent
Figure 5 Closed-type expansion tank
Piping to single-zone system using closed­type expansion tank. See Table 3 for piping sizes.
CLOSED-type expansion tank
From system
Isolation valve
Relief valve
Cold water fill
Isolation valve
To system
Circulator*
Circulator
26010
Part number 550-110-260/0200
Drain valve
*Alternate
location
Circulator
26011
Drain valve
*Alternate
location
15
GOLD CGs Gas-Fired Water Boiler
Water piping — multiple zones3c
Piping multiple zones
Zoning with
circulators, return
temp over 130 °F
Zoning with zone
valves, return temp
over 130 °F
Piping for radiant
heating systems or
converted gravity
systems
Follow instructions on pages 14 and 15 to install near-boiler or single-zone piping. (Also refer to applicable.)
See
1. Size each circulator to individual circuit requirements.
2. Do not install circulator on boiler (except for primary/secondary piping).
3. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
4. Install and wire a separate relay for each zone circulator.
1. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.
2. Provide a separate 24-volt transformer to power the zone valves. Size the transformer to
Converted gravity (or steam) systems
Whenever possible, use the primary/secondary piping shown in Figures 8 or 9 on page 19. This piping design allows changing boiler flow rate without affecting primary circuit flow rate.
If
11
the reduced flow rate in the heating system will not cause heat distribution problems.
Piping for radiant heating systems or converted gravity systems, below, if
Figure 6 or Figure 7 to complete installation.
handle the total rated load of all connected zone valves.
Figures 8 or 9 cannot be used, use the boiler-bypass piping shown in Figure 10 or Figure
on page 21. You can also use the piping shown in Figure 12 on page 23 (system-bypass), if
16
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 8 or 9 on page 19. Alternatively, use the method of either
12
(system-bypass), because this method does not control radiant system supply temperature.
If radiant system tubing has no oxygen barrier, a heat exchanger must be used.
Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
Do not apply the methods in this manual if the system is equipped with an outdoor reset control
temperature at no less than 130 °F regardless of system supply temperature. Contact your Weil-McLain representative for suggested piping and control methods. Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
. Instead, provide controls and piping which can regulate the boiler return water
Figure 10 or Figure 11 on page 21. Do not use the piping of Figure
Part number 550-110-260/0200
Boiler Manual
typical piping — multiple-zone installations
Figure 6
Zoning with circulators — return water 130 °F or higher.
ZONE 2
ZONE 1
1
2
11
13
10
Cold
water
6
9
11
fill
12
Figure 7
Zoning with zone valves — return water 130 °F or higher.
ZONE 2
ZONE 1
1 2
3
6
Cold
water
1
6
11
9
11
fill
12
6
Alternate circulator location
10
1
5
13
26012
1 Boiler isolation (balancing) valves
2 Flow/check valve
3 System or zone circulator
5 Zone valve
6 Drain valve
9 Relief valve
10 Automatic air vent (with diaphragm-type
expansion tank), or connect to tank fitting (closed­type expansion tank).
DO NOT use an automatic
For systems with possible low return-water temperature (such as converted gravity systems, radiant heating systems and heat pump systems), refer to the special piping suggestions of
Figures 8 - 12, as applies. Failure to prevent sustained low return water temperature to the
boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death or substantial property damage.
Part number 550-110-260/0200
26013
air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank.
11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5.)
13 Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion tank, regardless of location of expansion tank circulator or air separator.
17
GOLD CGs Gas-Fired Water Boiler
Water piping — low temp systems3d
Primary/secondary
(preferred) bypass
piping method
Temperature gauges
Valve adjustment
(Figure 12 and 13 only)
Primary/secondary bypass piping is preferred because the flow rate and temperature drop in
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and temperature distribution.
Figures 8 and 9 show suggested bypass arrangements using primary/secondary bypass piping
(preferred) for low temperature systems such as radiant heating systems or converted gravity
systems
The bypass valves (items system return water — set to assure a minimum return water temperature (at least 130 °F) to the boiler. Set the valves as explained below.
Gauge 4a is suggested, but optional on any system.
Gauge — to display the water temperature being supplied to the radiant tubing.
Gauge a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return water is cold (approximately 60 °F water temperature).
1. Set the valves while the system is cool, setting for the coldest expected water temperature
2. Start with valve 7a fully closed and 7b fully open.
3. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads
4. Note that valve
. For alternatives, see pages 20 through 23.
7a and 7b) provide mixing of hot boiler outlet water with cooler
4b is optional on converted gravity systems, but required on radiant heating systems
8 is required on all systems to assure the return water temperature is accurately set for
(usually 60 °F since the system will often drop to room temperature between cycles).
130 °F when gauge 4a reads 60 °F.
7a regulates the amount of hot water from the boiler supply which mixes
with return water. Valve 7b regulates the amount of system water flowing through the boiler secondary loop.
18
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature pumping control
Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset control water temperature at no less than 130 °F
your Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.
and the system supply temperature (such as provided by an injection
).
system supply temperature is relatively constant.
. Instead, provide controls and piping which can regulate the boiler return
regardless of system supply temperature. Contact
Part number 550-110-260/0200
Loading...
+ 42 hidden pages