Weil-McLain CGs User Manual

Page 1
GOLD CGs
Gas-Fired Water Boiler
Venting Supplement
Vertical Direct Venting
For use with Weil-McLain
Roof or Through-Unused-Chimney Termination Kit
Through-
87300
To install a new vent system follow instructions in:
This Venting Supplement.
CGs Boiler Manual.
Vent pipe manufacturer’s instructions supplied with vent material.
Part Number 550-141-873/0502
Page 2
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
Table of contents
1. Please — read before proceeding.................................3
Hazard definitions .................................................................................... 3
Venting method definitions ..................................................................... 3
To the installer.......................................................................................... 3
2. Determine venting method ..........................................4
Direct exhaust vent methods .................................................................. 4
Direct vent methods................................................................................. 5
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
3. Combustion air supply — eliminate contamination .....6
4. Obtain vent system components .................................7
5. Install vent starter .....................................................10
6. Vertical direct vent — vent termination .................... 11
7. Installation guidelines ............................................... 11
8. Verify vent system length..........................................12
9. Installation — assembly .............................................14
2
Part Number 550-141-873/0502
Page 3
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
1. Please — read before proceeding . . . . .
Hazard definitions
Venting method
definitions
The following terms are used throughout this Venting Supplement to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
Direct vent — Uses outside combustion air with combustion air connector
piping sealed at all joints and seams. Also known as sealed combustion. All CGs flue gas vents are pressurized, requiring careful sealing of all joints. See also
Exhaust: Vertical and Sidewall
Direct exhaust venting — Uses inside combustion air with no combustion
air connector piping. All CGs flue gas vents are pressurized, requiring careful sealing of all joints. Also known as non-direct venting. See
Supplement — Direct Vent: Sidewall & Direct Exhaust: Vertical and Sidewall
CGs Venting Supplement — Direct Vent: Sidewall & Direct
for alternate direct vent method.
CGs Venting
venting supplement for application information.
To the installer
Chimney draft vent — Uses the natural draft provided by a vertical vent
or chimney. (This method cannot be used with CGs boilers.)
Chimney draft venting cannot be used for CGs boilers.
venting materials listed in this Venting Supplement. Existing vertical vents or chimneys may only be used as raceways for routing vent or vent/air piping as described in this supplement or CGs Direct Vent Supplements.
Boiler must be vented and supplied with combustion air as described in this supplement. Failure to do so will result in severe personal injury, death or substantial property damage.
Use only the sealant specified by the vent pipe manufacturer, applied per their instructions. Vent piping must be sealed gas-tight to prevent possibility of flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
Provide combustion and ventilation air openings as described in the CGs Boiler Manual and this supplement. Failure to provide adequate air supply could result in severe personal injury, death or substantial property damage.
Vent system must be constructed only using
Part Number 550-141-873/0502
3
Page 4
GOLD CGs Gas-FGOLD CGs Gas-F
87251
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
2. Determine venting method
To prevent potential of severe personal injury or death, check for areas and products listed on page 6 before installing boiler. If found:
remove products permanently
OR
provide outside combustion air (direct vent
installation).
Figure 1 Typical sidewall direct exhaust
vent installation
Direct exhaust ventingDirect exhaust venting
Direct exhaust venting
Direct exhaust ventingDirect exhaust venting
Use only when openings for inside combustion air can be supplied in accordance with the CGs Boiler manual, this venting supplement and with all applicable codes.
You must direct vent the boiler if the boiler area may contain contaminants as described in this supplement
Two direct exhaust vent options are permitted: sidewall and vertical, per instructions in
Sidewall
Venting Supplement.
Figure 2 Typical vertical direct exhaust
& Direct Exhaust Venting: Vertical or Sidewall
vent installation
CGs Direct Venting:
.
87250
1. Sidewall direct exhaust venting
— using vent manufacturer’s termination fittings listed in this supplement. See Figure 1.
See instructions on pages 6, 7, 8, 9 and 10 – 13.
4
2. Vertical direct exhaust venting
— using penetration through roof or using existing unused chimney or vent as raceway for vent pipe. See Figure 2.
See instructions in
Direct Exhaust: Vertical or Sidewall
Supplement.
CGs Direct Vent: Sidewall &
Part Number 550-141-873/0502
Venting
Page 5
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
Direct vent methodsDirect vent methods
Direct vent methods
Direct vent methodsDirect vent methods
Combustion air is provided by air piping connecting from the boiler Air intake fitting to the outside.
You must direct vent the boiler (pipe outside air to boiler air intake fitting) if the boiler area may contain contaminants as described in this supplement.
Two direct vent options are permitted:
enting — Venting — V
enting — V
enting — Venting — V
1. Sidewall direct vent
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Figure 4 Typical vertical direct vent
installation
— using Weil-McLain
Kit
. See instructions in
& Direct Exhaust: Vertical or Sidewall
Supplement. Termination kit is included with CGs boiler. See Figure 3.
Vent/Air Intake Termination
CGs Direct Vent: Sidewall
2. Vertical direct vent
— using Weil-McLain
Unused-ChimneyTermination Kit
vertical direct venting are covered in this supplement. See Figure 4.
Figure 3 Typical sidewall direct vent
installation
Through-Roof or Through-
. Instructions for
Venting
Part Number 550-141-873/0502
87203
87205
5
Page 6
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
3. Combustion air supply — eliminate contamination
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
If the boiler is installed in any area likely to cause
contamination
contaminate the air cannot be removed, you must pipe
combustion air to the boiler air intake
combustion air will damage the boiler, resulting in possible severe personal injury, death or substantial property damage. Do not install a CGs boiler in a
laundry room or pool facility
using ducted outside air. These areas will always contain contaminants.
Please review the following information on potential combustion air contamination problems.
Refer to Table 1 for products and areas that may cause contaminated combustion air. These contaminants may cause damage to the vent piping, and must be eliminated
Table 1 Corrosive contaminants
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
, or if products which would
. Contaminated
, for example, without
from the boiler combustion air supply. You may do this by removing the contaminants permanently from the area or piping air directly to the boiler (direct vent) using one of the methods referenced in this supplement and described in the direct vent supplements.
To prevent potential of severe personal injury or death, check for areas and products listed below before installing boiler. If found:
remove products permanently
— OR —
provide outside combustion air
(direct vent installation).
Permanent wave solutions Swimming pools
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and clean­ing solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
6
Remodeling areas
Garages with workshops
Part Number 550-141-873/0502
Page 7
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
4. Obtain vent system components
The following special gas vent systems comply with UL-1738 and ULC­S636 standards and are certified by CSA as the only systems suitable for use with CGs boilers:
• Heat-Fab, Inc. Saf-T Vent
• Flex-L International, Inc. StaR-34
• Z-Flex®, Inc. Z-Vent II
•ProTech Systems FasNSeal™
Use only the vent starter of the same manufacturer as the vent compo­nents. Do not mix components from different systems. The vent system could fail, causing flue gas spillage, resulting in severe personal injury or death.
®
1. The
2. Verify that the vent termination will comply with the requirements
3. You will need to obtain stainless vent pipe and fittings, using only the
4. Use suitable 3" material for combustion air connector piping, such as:
Through-Roof or Through-Unused-Chimney Termination Kit
provides special parts required to route 3-inch stainless vent pipe through 5-inch B-vent. The space between the vents provides the passage for combustion air. See page 9 for parts included with the kit.
listed on page 11. Then verify that the vent and air piping will not exceed the length limits given in section 8 of this supplement before locating boiler or floor/roof penetrations.
vent systems listed in the CGi, CGs & GV Vent Component
Supplement. Also obtain B-vent pipe and fittings for the vertical run
and floor/roof penetrations (See Table 3).
Dryer vent
Galvanized steel
PVC (3" I.D.)
Part Number 550-141-873/0502
7
Page 8
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
4. Obtain vent system components (continued)
Figure 5 Typical installation,
showing component identification
Termination coupling
Elastomer flashing*
5”Type “B” storm ring
5”Type “B” adjustable flashing
Vent pipe
5”Type “B” rain cap with hole in top for vent pipe
For minimum height followType “B” gas vent manufacturer’s instruction
5”Type “B” stack
Fire stop
Fire stop
Single wall stack reducer tee*
Cap with hole for vent pipe
Elastomer flashing*
3” vent pipe:
Heat-Fab Saf-T Vent
®
Z-Flex Z-Vent II Flex-L International StaR-34 ProTech Systems FasNSeal™
* furnished in kit
®
Condensate drain line
Vent starter must be by same manufacturer as the vent pipe.
5” type “B” support
5” type “B” draft hood connector
Air intake pipe – 3” pvc, standard 3” galvanized or aluminum single wall pipe, or 3” flexible dryer vent
CGs boiler
87303
8
Part Number 550-141-873/0502
Page 9
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
Figure 6 Parts provided in kit Table 2 Parts provided in kit
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Item Description Qty
1 Tee —
galvanized 5" x 5" x 3"
2 Vent clamp 5
3 Bottom cap —
3
1
2
4
6
8
Table 3 Parts below are required for installation and are provided by installer (not included in kit)
7
5
87302
galvanized with 4 ½" hole
4 Vent support 1
5 Elastomer grippers 11
6 Screws — sheet metal
type A, #10 x 1¼"
7 Screws — sheet metal
type A, #10 x ½"
8 Elastomer flashing 2
1
1
11
3
Description Quantity
Rain cap, galvanized, 5" 1 Adjustable flashing, type B, 5" 1 Fire stop for each floor or attic penetration 1 Storm ring, type B, 5" 1 Support, type B, 5" 1 Draft hood connector, type B, 5" 1 Adequate B-Vent with clamp rings for combustion air run (less than 30 feet) -­Adequate 3" vent material for vent run and elbows from one of the following (See Note):
• Heat-Fab, Inc. — Saf-T Vent
• Flex-L International, Inc. — StaR-34 • Z-Flex Adequate sealant specified by vent pipe manufacturer’s instructions -­Adequate 3" PVC, galvanized or dryer vent (for combustion air supply piping between tee and boiler) -- Note: Do not mix types of vent material. CSA certification will be void.
Part Number 550-141-873/0502
®
• ProTech Systems — FasNSeal™
®
, Inc. — Z-Vent II
--
9
Page 10
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
5. Install vent starter
1. Select a vent pipe manufacturer and obtain all vent components needed, based on boiler location and venting method.
2. You must use the vent starter made by the vent pipe manufacturer. See separate CGi, CGs & GV Vent
Component Supplement
, for part numbers of each
component, listed by vent manufacturer.
Use only the vent starter of the same manufacturer as the vent compo­nents. Do not mix components from different systems. The vent system could fail, causing flue gas spillage, resulting in severe personal injury or death.
Band clamp
Band clamp strap
screw
FasNSeal™ starter
Band clamp screw
Figure 7
FasNSeal™ vent starter
3. Follow all applicable national, state, local or provincial codes when venting the CGs boiler.
4. Connect vent starter to blower housing outlet as shown in the
Figures 7 through 10, below.
a. Do not mix components from different vent
manufacturers.
b. Maintain minimum 2" clearance from
combustible materials to vent pipe.
c. Seal with sealant specified by vent pipe
manufacturer, using ³⁄₈" bead (not required for FasNSeal™).
d. Tighten strap at band clamp screw until strap is
snug around blower housing.
Tighten position
Feed
Band clamp strap
position
Z-Vent II starter
Band clamp screw
³⁄₈ " Bead of sealant
Band clamp strap
Blower housing outlet
87211
Saf-T Vent starter
Band clamp screw
³⁄₈ " Bead of sealant
Blower housing outlet
87208
Z-Vent II vent starter
®
Figure 9
Saf-T Vent® vent starter
StaR-34 vent starter
Figure 8
Figure 10
Band clamp strap
Blower housing outlet
87210
StaR-34 starter
Band clamp screw
3/8" Bead of sealant
Blower housing outlet
87209
10
Part Number 550-141-873/0502
Page 11
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
6. Vertical direct vent — vent termination
Follow instructions on this page when determining vent location to avoid possibility of severe personal injury, death or substantial property damage.
1. Locate the boiler and vent penetration through the roof so all requirements on this page will be met. Also follow vent manufacturer’s instructions.
2. Gases will form white plume in winter. Plume could obstruct window view of nearby windows in multi­story buildings.
3. Prevailing winds could cause freezing of condensate and water/ice buildup on vent termination, building, plants or roof. Ice buildup on vent termination can cause boiler shutdown and building freezeup.
4. Locate or guard vent termination to prevent condensate from damaging exterior surfaces.
5. Locate the vent termination well away from trees, shrubs, and decorative items.
6. Locate or guard vent to prevent accidental contact by people or pets.
7. Do not terminate vent in window well, stairwell, alcove, courtyard, or other recessed areas.
8. Do not wrap or insulate vent pipe or fittings.
9. Do not connect:
Any other appliance to vent pipe.
Multiple boilers to a common vent pipe.
10. Canadian installations — See B149.1 or B149.2 Installation Code. Terminate vent no less than 6 feet from another combustion air inlet, 3 feet from any other building opening, and 3 feet from any gas service regulator.
11. The vent must terminate:
more than 1 foot below or to side of all doors or windows.
more than 1 foot above grade or anticipated snow line.
3 feet above any forced air intake within 10 feet.
12. Vent must also terminate:
at least 6 feet away from adjacent walls.
no closer than 5 feet below roof overhang.
at least 4 feet horizontally (and in no case above or below unless a 4 foot horizontal distance is maintained) from electric meters, gas meters, regulators, relief valves, and other equipment.
13. Site conditions may dictate greater clearances. Do not terminate the vent adjacent
to a wall or below any building extension such as eaves, parapets, balconies or decks. Failure to comply could result in severe personal injury, death or substantial property damage.
14. Multiple boilers may be vented with vent
terminations at the same height. Space terminations to provide a minimum of 1 foot between pipes for U.S. installations. For Canadian installations, provide clearances required by B149.1 or B149.2 Installation Code.
7. Installation guidelines
1. Codes — Install vent and combustion air piping in
compliance with all applicable national, state, local or provincial codes.
2. Do not connect:
Any other appliance to combustion air or vent piping.
Any other appliance into or through chimney when using existing chimney as raceway.
Multiple boilers into common vent.
3. Vent length limits — Position boiler as close as
possible to vertical vent/air run. Do not exceed vent length limits given in Section 8 of this supplement. B-vent limit is 30 feet. Vent or air max. lengths are:
CGs-3 & CGs-4: Max 55 equivalent feet
CGs-5 & CGs-6: Max 45 equivalent feet
Part Number 550-141-873/0502
4. Materials and construction
Seal all B-vent combustion air joints with
Construct vent joints per vent manufacturer’s
Use only one of the approved vent systems listed
5. Install boiler per CGs Boiler Manual.
approved silicone sealant (Dow Corning 700™ or 732™, General Electric 108 or 800, or sealant specified by vent pipe manufacturer. B-vent
sections must be straight — no elbows
instructions, including use of their specified sealant. Vent pipe routed inside B-vent must also be fitted with vent clamps with elastomer grippers, installed per section 9 of this supplement.
in Table 2. Do not mix types of vent material. CSA certification will be void.
.
11
Page 12
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
8. Verify vent system length
The vent or air piping must be no longer than the maximum value given in tables that the maximum length of connector piping (vent or air piping between boiler and B-vent tee connection) depends on the number of elbows and the length of the B-vent section. The reason for this is that each 90-degree vent or air pipe elbow cause the same pressure drop as 7 feet of straight pipe.
Tables 4 and 5. Note in the
Vent/air piping length verification procedure:
Step 1 — Determine dimensions of vent/air pipe needed for planned location
Measure or calculate the vent/air pipe lengths required for the planned location of the boiler and floor/roof penetrations. See Figure 11 for a typical layout.
How long will the vertical B-vent section have to be? Round up to the nearest 5 feet (for example, if B-vent length needs to be 12 feet, round this amount up to the nearest 5 feet — use 15 feet for your B-vent length). (This is dimension L in Figure 11.)
How many elbows will be needed in the vent connector piping (from boiler to B-vent tee)?
How many feet of vent piping will be needed for the connector runs? (This would be the sum of dimensions C & D in Fig. 11.)
How many elbows will be needed in the air connector piping (from boiler to B-vent tee)?
How many feet of air piping will be needed for the connector runs? (This would be the sum of dimensions A & B in Fig. 11.)
Step 4 — Replan boiler location & piping if piping length of vent or air is too long
See if boiler can be moved closer to vertical vent/air piping.
See if you can reduce the number of elbows required vent piping must have 2 elbows minimum in order to provide horizontal piping to install condensate drain tee.
Example verification (
Step 1 — Vent/air piping required per plan
As an example, consider an installation of a CGs-5 boiler, where the boiler and vent/air locations would require:
Boiler model = CGs-5.
B-vent length (L) = 20 feet.
Vent connector piping requires 2 elbows.
Vent connector piping length (D + C) = 16 feet.
Air connector piping requires 1 elbow.
Air connector piping length (B + A) = 17 feet.
Step 2 — Verify vent piping
Enter Table 5 at the row for B-vent length of 20
feet.
Move to the 2-elbow column.
Read a maximum connector pipe length of 18 feet.
Conclusion — Vent piping is within limits because vent connector piping would only be 16 feet (less than the maximum of 18 feet).
Figure 11Figure 11
Figure 11):
Figure 11Figure 11
12
Step 2 — Verify that vent connector piping is within allowable limits
Use Table 4 or 5, depending on boiler model to be used. Find the row with the B-vent length the installation requires. Move across to the column with the number of vent elbows needed for the installation. This number is the maximum allowable vent connector piping length.
Step 3 — Verify that air connector piping is within allowable limits
Use Table 4 or 5, depending on boiler model to be used. Find the row with the B-vent length the installation requires. Move across to the column with the number of air pipe elbows needed for the installation. This number is the maximum allowable air pipe connector piping length.
Step 3 — Verify air piping
Enter Table 5 at the row for B-vent length of 20
feet.
Move to the 1-elbow column.
Read a maximum connector pipe length of 25 feet.
Conclusion — Air piping is within limits because air connector piping would only be 17 feet (less than the maximum of 25 feet).
Step 4 — Replanning
No replanning needed. Vent and air piping lengths are within limits.
Part Number 550-141-873/0502
Page 13
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
Maximum connector pipe length, vent or air:
Combustion air connector pipe
Vent connector pipe
CGs-3 and CGs-4
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Figure 11 Typical vent/air pipingTable 4 CGs-3 and CGs-4
“B-Vent”
length
(feet)
L
5 504336292215 8
10 45 38 31 24 17 10 3
15 40 33 26 19 12 5 --
20 35 28 21 14 7 -- --
25 30 23 16 9 2 -- --
30 25 18 11 4 -- -- --
Note: Combustion air connector pipe length = A + B
Vent connector pipe length = C + D
Total number of elbows
1 2 3 4 5 6 7
Max. length from boiler to “B-Vent”
Table 5 CGs-5 and CGs-6
Maximum connector pipe length, vent or air:
Combustion air connector pipe
Vent connector pipe
CGs-5 and CGs-6
L
L = B-vent length
A + B
C + D
A
= Combustion air
connector piping length
= Vent connector piping length
Elbow
“B-Vent”
length
(feet)
L
540332619125--
10 35 28 21 14 7 -- --
15 30 23 16 9 2 -- --
20 25 18 11 4 -- -- --
25 20 13 6 -- -- -- --
30 15 8 1 -- -- -- --
Note: Combustion air connector pipe length = A + B
Vent connector pipe length = C + D
Part Number 550-141-873/0502
Total number of elbows
1 2 3 4 5 6 7
Max. length from boiler to “B-Vent”
D
Vent piping
Condensate drain line
Elbows
87304
C
B
Combustion air piping
13
Page 14
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
9. Installation — assembly
Step 1
Step 2
Assemble B-vent piping
1. Install 5" type B support, B-vent combustion air run, flashing, fire stops and storm collar per manufacturer’s instructions. Apply approved sealant to each B-vent joint. See Figure 12.
2. Install type B draft hood connector to bottom of combustion air run. Seal with approved sealant.
Prepare & insert vertical vent
1. From top or bottom of combustion air run, install
vent piping
Top of vent piping must extend 3" above top of rain cap. See Figure 5, page 8.
Bottom of vent piping must extend 18"
below draft hood connector.
2. At each vent joint:
a. Follow vent pipe manufacturer’s instructions to
assemble and seal joints. Sealant recommended by vent pipe manufacturer must be used as indicated in their instructions.
b. Apply 2 self-adhesive elastomer grippers to vent
clamp. Grippers must be positioned on clamp as shown in Figure 13. Bend out 2 ears on vent clamp.
.
Figure 12 Sealing B-vent joints
87305
Figure 13 Apply elastomer strips to vent clamps
87306
Figure 14 Install vent clamps on vent piping
14
c. Fasten clamp around vent pipe with 2 – 1¹⁄₄"
screws in top and bottom holes, about every 5 feet. See Figure 14. Tighten screws until clamp does not turn or slide around vent piping.
87307
Part Number 550-141-873/0502
Page 15
VV
Draft hood connector
Vent support
87308
5” x 5” x 3” Te e
Elastomer flashing
Draft hood connector
Bottom cap
87309
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Step 3
Step 4
Install vent support
1. Apply 1 elastomer gripper to vent support.
2. Intall vent support around vent piping just below draft hood connector as shown in Figure 15. Fasten support around vent piping with 1 – 1 ¹⁄₄" screw.
3. Tighten screw until support does not turn or slide around vent piping.
Install 5" x 5" x 3" tee
1. Slide tee over vent piping and attach uncrimped end to bottom of draft hood connector:
a. Drill 3 holes in tee for ¹⁄₄" sheet metal screws.
Do not allow drill to penetrate vent pipe. Drill
holes carefully in tee and use
1
only
/
" screws to fasten tee
4
to draft hood connector. Failure to do so can damage vent pipe, causing severe personal injury or substantial property damage.
b. Seal all seams and screws with approved sealant.
Figure 15 Install vent support
Figure 16 Install tee
2. Secure bottom cap to tee with duct tape. Slide elastomer flashing up around vent pipe and tuck lip into cap’s bottom opening. Seal with approved sealant.
Follow vent pipe manufacturer's instructions to assemble and seal joints. Sealant recommended by vent pipe manufacturer must be used as indicated in their instructions. Vent and combustion air connector piping must be sealed gas-tight to prevent possibility of flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or death.
Part Number 550-141-873/0502
15
Page 16
GOLD CGs Gas-FGOLD CGs Gas-F
Vent pipe
Elastomer flashing
Rain cap
87310
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
9. Installation — assembly continued
Step 5 Install rain cap
1. On roof, cut 4 ¹⁄₂" hole in top of rain cap and install cap over protruding vent pipe. Slide elastomer flashing down around vent pipe and tuck lip into cap’s top opening.
2. Connect termination coupling to vent pipe using vent pipe manufacturer’s specified sealant.
Step 6
Finish installation
1. Complete vent piping to boiler, making sure to follow vent pipe manufacturer’s instructions and Weil-McLain vent manufacturers special gas vent system vent and combustion air venting supplements.
2. Use any of the following to install combustion air connector piping from tee to boiler, making sure to seal all joints and seams:
a. 3" Flexible dryer vent — A piece of 3" galvanized is required at each end to adapt. Seal all pipe joints and
seams between pipe and dryer vent with approved sealant. b. Galvanized or aluminum single wall pipe — Seal all joints and seams using approved sealant. c. 3" PVC — Seal all joints using PVC cement.
Figure 17 Install rain cap
16
3. Condensate drain line — A condensate drain fitting is always required for through-roof vents. Follow vent
manufacturer’s instructions to install condensate drain line.
Use only silicone tubing rated for at least 400°F for the first 18" of condensate drain line, then other non-metallic tubing may be used. Using any other material could cause flue gas leakage, potentially resulting in severe personal injury, death or substantial property damage.
4. Multiple boilers may be vented with vent terminations at the same height. Space terminations to provide a minimum of 1 fott between pipes for U.S. installations. For Canadian installations, provide clearances required by B149.1 or B149.2 Installation Code.
Part Number 550-141-873/0502
Loading...