This Venting Supplement must only be used by a qualified installer/service
technician. Read these instructions completely before beginning the
installation. Failure to follow all instructions in proper order can cause
severe personal injury, death or substantial property damage.
To install a new vent system follow instructions in:
•This Venting Supplement.
•CGs Boiler Manual.
•Vent pipe manufacturer’s instructions supplied with vent material.
Part Number 550-141-873/0502
Page 2
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
Table of contents
1. Please — read before proceeding.................................3
The following terms are used throughout this Venting Supplement to bring
attention to the presence of hazards of various risk levels or to important
information concerning the life of the product.
Indicates presence of hazards that will cause severe
personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe
personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause
minor personal injury or property damage.
Indicates special instructions on installation, operation
or maintenance that are important but not related to
personal injury or property damage.
Direct vent — Uses outside combustion air with combustion air connector
piping sealed at all joints and seams. Also known as sealed combustion.
All CGs flue gas vents are pressurized, requiring careful sealing of all joints.
See also
Exhaust: Vertical and Sidewall
Direct exhaust venting — Uses inside combustion air with no combustion
air connector piping. All CGs flue gas vents are pressurized, requiring careful
sealing of all joints. Also known as non-direct venting. See
Supplement — Direct Vent: Sidewall & Direct Exhaust: Vertical and
Sidewall
CGs Venting Supplement — Direct Vent: Sidewall & Direct
for alternate direct vent method.
CGs Venting
venting supplement for application information.
To the installer
Chimney draft vent — Uses the natural draft provided by a vertical vent
or chimney. (This method cannot be used with CGs boilers.)
Chimney draft venting cannot be used for CGs
boilers.
venting materials listed in this Venting Supplement.
Existing vertical vents or chimneys may only be used as
raceways for routing vent or vent/air piping as described
in this supplement or CGs Direct Vent Supplements.
Boiler must be vented and supplied with combustion
air as described in this supplement. Failure to do so will
result in severe personal injury, death or substantial
property damage.
Use only the sealant specified by the vent pipe
manufacturer, applied per their instructions. Vent
piping must be sealed gas-tight to prevent possibility
of flue gas spillage and carbon monoxide emissions,
resulting in severe personal injury or death.
Provide combustion and ventilation air openings as
described in the CGs Boiler Manual and this
supplement. Failure to provide adequate air supply
could result in severe personal injury, death or
substantial property damage.
Vent system must be constructed only using
Part Number 550-141-873/0502
3
Page 4
GOLD CGs Gas-FGOLD CGs Gas-F
87251
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
2. Determine venting method
To prevent potential of severe personal injury or death,
check for areas and products listed on page 6 before
installing boiler. If found:
• remove products permanently
—
OR —
• provide outside combustion air (direct vent
installation).
Figure 1 Typical sidewall direct exhaust
vent installation
Direct exhaust ventingDirect exhaust venting
Direct exhaust venting
Direct exhaust ventingDirect exhaust venting
Use only when openings for inside combustion air can
be supplied in accordance with the CGs Boiler manual,
this venting supplement and with all applicable codes.
You must direct vent the boiler if the boiler area may
contain contaminants as described in this supplement
Two direct exhaust vent options are permitted: sidewall
and vertical, per instructions in
Sidewall
Venting Supplement.
Figure 2 Typical vertical direct exhaust
& Direct Exhaust Venting: Vertical or Sidewall
vent installation
CGs Direct Venting:
.
87250
1. Sidewall direct exhaust venting
— using vent manufacturer’s termination fittings
listed in this supplement. See Figure 1.
See instructions on pages 6, 7, 8, 9 and 10 – 13.
4
2. Vertical direct exhaust venting
— using penetration through roof or using existing
unused chimney or vent as raceway for vent pipe.
See Figure 2.
See instructions in
Direct Exhaust: Vertical or Sidewall
Supplement.
CGs Direct Vent: Sidewall &
Part Number 550-141-873/0502
Venting
Page 5
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
Direct vent methodsDirect vent methods
Direct vent methods
Direct vent methodsDirect vent methods
Combustion air is provided by air piping connecting
from the boiler Air intake fitting to the outside.
You must direct vent the boiler (pipe outside air to
boiler air intake fitting) if the boiler area may contain
contaminants as described in this supplement.
Two direct vent options are permitted:
enting — Venting — V
enting — V
enting — Venting — V
1. Sidewall direct vent
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Figure 4 Typical vertical direct vent
installation
— using Weil-McLain
Kit
. See instructions in
& Direct Exhaust: Vertical or Sidewall
Supplement. Termination kit is included with CGs
boiler. See Figure 3.
Vent/Air Intake Termination
CGs Direct Vent: Sidewall
2. Vertical direct vent
— using Weil-McLain
Unused-ChimneyTermination Kit
vertical direct venting are covered in this
supplement. See Figure 4.
Figure 3 Typical sidewall direct vent
installation
Through-Roof or Through-
. Instructions for
Venting
Part Number 550-141-873/0502
87203
87205
5
Page 6
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
3. Combustion air supply —
eliminate contamination
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
If the boiler is installed in any area likely to cause
contamination
contaminate the air cannot be removed, you must pipe
combustion air to the boiler air intake
combustion air will damage the boiler, resulting in
possible severe personal injury, death or substantial
property damage. Do not install a CGs boiler in a
laundry room or pool facility
using ducted outside air. These areas will always contain
contaminants.
Please review the following information on potential
combustion air contamination problems.
Refer to Table 1 for products and areas that may cause
contaminated combustion air. These contaminants may
cause damage to the vent piping, and must be eliminated
Table 1Corrosive contaminants
Products to avoidAreas likely to have contaminants
Spray cans containing chloro/fluorocarbonsDry cleaning/laundry areas and establishments
, or if products which would
. Contaminated
, for example, without
from the boiler combustion air supply. You may do this
by removing the contaminants permanently from the
area or piping air directly to the boiler (direct vent) using
one of the methods referenced in this supplement and
described in the direct vent supplements.
To prevent potential of severe
personal injury or death, check for
areas and products listed below
before installing boiler. If found:
Chlorine-based swimming pool chemicalsBeauty shops
Calcium chloride used for thawingRefrigeration repair shops
Sodium chloride used for water softeningPhoto processing plants
Refrigerant leaksAuto body shops
Paint or varnish removersPlastic manufacturing plants
Hydrochloric acid/muriatic acidFurniture refinishing areas and establishments
Cements and gluesNew building construction
Antistatic fabric softeners used in clothes
dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Adhesives used to fasten building products and
other similar products
6
Remodeling areas
Garages with workshops
Part Number 550-141-873/0502
Page 7
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
4. Obtain vent system components
The following special gas vent systems comply with UL-1738 and ULCS636 standards and are certified by CSA as the only systems suitable for
use with CGs boilers:
• Heat-Fab, Inc. Saf-T Vent
• Flex-L International, Inc. StaR-34
• Z-Flex®, Inc. Z-Vent II
•ProTech Systems FasNSeal™
Use only the vent starter of the same manufacturer as the vent components. Do not mix components from different systems. The vent system
could fail, causing flue gas spillage, resulting in severe personal injury or
death.
®
1. The
2. Verify that the vent termination will comply with the requirements
3. You will need to obtain stainless vent pipe and fittings, using only the
4. Use suitable 3" material for combustion air connector piping, such as:
Through-Roof or Through-Unused-Chimney Termination Kit
provides special parts required to route 3-inch stainless vent pipe
through 5-inch B-vent. The space between the vents provides the
passage for combustion air. See page 9 for parts included with the kit.
listed on page 11. Then verify that the vent and air piping will not
exceed the length limits given in section 8 of this supplement before
locating boiler or floor/roof penetrations.
vent systems listed in the CGi, CGs & GV Vent Component
Supplement. Also obtain B-vent pipe and fittings for the vertical run
and floor/roof penetrations (See Table 3).
•Dryer vent
•Galvanized steel
•PVC (3" I.D.)
Part Number 550-141-873/0502
7
Page 8
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
4. Obtain vent system components (continued)
Figure 5Typical installation,
showing component
identification
Termination coupling
Elastomer
flashing*
5”Type “B”
storm ring
5”Type “B”
adjustable
flashing
Vent pipe
5”Type “B” rain cap with
hole in top for vent pipe
For minimum height
followType “B” gas
vent manufacturer’s
instruction
5”Type “B” stack
Fire stop
Fire stop
Single wall stack
reducer tee*
Cap with hole
for vent pipe
Elastomer
flashing*
3” vent pipe:
Heat-Fab Saf-T Vent
®
Z-Flex Z-Vent II
Flex-L International StaR-34
ProTech Systems FasNSeal™
* furnished in kit
®
Condensate drain line
Vent starter must be
by same manufacturer
as the vent pipe.
5” type “B” support
5” type “B” draft hood connector
Air intake pipe – 3” pvc,
standard 3” galvanized
or aluminum single
wall pipe, or 3” flexible
dryer vent
CGs boiler
87303
8
Part Number 550-141-873/0502
Page 9
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
Figure 6 Parts provided in kitTable 2 Parts provided in kit
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Item DescriptionQty
1Tee —
galvanized 5" x 5" x 3"
2Vent clamp5
3Bottom cap —
3
1
2
4
6
8
Table 3 Parts below are required for installation and are provided by installer (not included in kit)
7
5
87302
galvanized with 4 ½" hole
4Vent support1
5Elastomer grippers11
6Screws — sheet metal
type A, #10 x 1¼"
7Screws — sheet metal
type A, #10 x ½"
8Elastomer flashing2
1
1
11
3
DescriptionQuantity
Rain cap, galvanized, 5"1
Adjustable flashing, type B, 5"1
Fire stop for each floor or attic penetration1
Storm ring, type B, 5"1
Support, type B, 5"1
Draft hood connector, type B, 5"1
Adequate B-Vent with clamp rings for combustion air run (less than 30 feet)-Adequate 3" vent material for vent run and elbows from one of the following (See Note):
• Heat-Fab, Inc. — Saf-T Vent
• Flex-L International, Inc. — StaR-34• Z-Flex
Adequate sealant specified by vent pipe manufacturer’s instructions-Adequate 3" PVC, galvanized or dryer vent (for combustion air supply piping between tee and boiler)--
Note: Do not mix types of vent material. CSA certification will be void.
Part Number 550-141-873/0502
®
• ProTech Systems — FasNSeal™
®
, Inc. — Z-Vent II
--
9
Page 10
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
5. Install vent starter
1. Select a vent pipe manufacturer and obtain all vent
components needed, based on boiler location and
venting method.
2. You must use the vent starter made by the vent pipe
manufacturer. See separate CGi, CGs & GV Vent
Component Supplement
, for part numbers of each
component, listed by vent manufacturer.
Use only the vent starter of the same
manufacturer as the vent components. Do not mix components from
different systems. The vent system
could fail, causing flue gas spillage,
resulting in severe personal injury or
death.
Band clamp
Band clamp
strap
screw
FasNSeal™
starter
Band clamp
screw
Figure 7
FasNSeal™ vent starter
3. Follow all applicable national, state, local or
provincial codes when venting the CGs boiler.
4. Connect vent starter to blower housing outlet as
shown in the
Figures 7 through 10, below.
a. Do not mix components from different vent
manufacturers.
b. Maintain minimum 2" clearance from
combustible materials to vent pipe.
c. Seal with sealant specified by vent pipe
manufacturer, using ³⁄₈" bead (not required for
FasNSeal™).
d. Tighten strap at band clamp screw until strap is
snug around blower housing.
Tighten
position
Feed
Band clamp
strap
position
Z-Vent II
starter
Band clamp
screw
³⁄₈ " Bead
of sealant
Band clamp
strap
Blower
housing
outlet
87211
Saf-T Vent
starter
Band clamp
screw
³⁄₈ " Bead of
sealant
Blower
housing
outlet
87208
Z-Vent II vent starter
®
Figure 9
Saf-T Vent® vent starter
StaR-34 vent starter
Figure 8
Figure 10
Band clamp
strap
Blower
housing
outlet
87210
StaR-34
starter
Band clamp
screw
3/8" Bead
of sealant
Blower
housing
outlet
87209
10
Part Number 550-141-873/0502
Page 11
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
6. Vertical direct vent — vent termination
Follow instructions on this page
when determining vent location to
avoid possibility of severe personal
injury, death or substantial property
damage.
1. Locate the boiler and vent penetration through the
roof so all requirements on this page will be met.
Also follow vent manufacturer’s instructions.
2. Gases will form white plume in winter. Plume could
obstruct window view of nearby windows in multistory buildings.
3. Prevailing winds could cause freezing of condensate
and water/ice buildup on vent termination, building,
plants or roof. Ice buildup on vent termination can
cause boiler shutdown and building freezeup.
4. Locate or guard vent termination to prevent
condensate from damaging exterior surfaces.
5. Locate the vent termination well away from trees,
shrubs, and decorative items.
6. Locate or guard vent to prevent accidental contact
by people or pets.
7. Do not terminate vent in window well, stairwell,
alcove, courtyard, or other recessed areas.
8. Do not wrap or insulate vent pipe or fittings.
9. Do not connect:
•Any other appliance to vent pipe.
•Multiple boilers to a common vent pipe.
10. Canadian installations — See B149.1 or B149.2
Installation Code. Terminate vent no less than 6 feet
from another combustion air inlet, 3 feet from any
other building opening, and 3 feet from any gas
service regulator.
11. The vent must terminate:
•more than 1 foot below or to side of all doors
or windows.
•more than 1 foot above grade or anticipated
snow line.
•3 feet above any forced air intake within 10
feet.
12. Vent must also terminate:
•at least 6 feet away from adjacent walls.
•no closer than 5 feet below roof overhang.
•at least 4 feet horizontally (and in no case above
or below unless a 4 foot horizontal distance is
maintained) from electric meters, gas meters,
regulators, relief valves, and other equipment.
13. Site conditions may dictate greater clearances.
Do not terminate the vent adjacent
to a wall or below any building
extension such as eaves, parapets,
balconies or decks. Failure to
comply could result in severe
personal injury, death or substantial
property damage.
14. Multiple boilers may be vented with vent
terminations at the same height. Space
terminations to provide a minimum of 1 foot
between pipes for U.S. installations. For Canadian
installations, provide clearances required by
B149.1 or B149.2 Installation Code.
7. Installation guidelines
1. Codes— Install vent and combustion air piping in
compliance with all applicable national, state, local
or provincial codes.
2. Do not connect:
•Any other appliance to combustion air or vent
piping.
•Any other appliance into or through chimney
when using existing chimney as raceway.
•Multiple boilers into common vent.
3. Vent length limits — Position boiler as close as
possible to vertical vent/air run. Do not exceed vent
length limits given in Section 8 of this supplement.
B-vent limit is 30 feet. Vent or air max. lengths are:
•CGs-3 & CGs-4: Max 55 equivalent feet
•CGs-5 & CGs-6: Max 45 equivalent feet
Part Number 550-141-873/0502
4. Materials and construction —
•Seal all B-vent combustion air joints with
•Construct vent joints per vent manufacturer’s
•Use only one of the approved vent systems listed
5. Install boiler per CGs Boiler Manual.
approved silicone sealant (Dow Corning 700™
or 732™, General Electric 108 or 800, or sealant
specified by vent pipe manufacturer. B-vent
sections must be straight — no elbows
instructions, including use of their specified
sealant. Vent pipe routed inside B-vent must
also be fitted with vent clamps with elastomer
grippers, installed per section 9 of this
supplement.
in Table 2. Do not mix types of vent material.
CSA certification will be void.
.
11
Page 12
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
8. Verify vent system length
The vent or air piping must be no longer than the
maximum value given in
tables that the maximum length of connector piping
(vent or air piping between boiler and B-vent tee
connection) depends on the number of elbows and the
length of the B-vent section. The reason for this is that
each 90-degree vent or air pipe elbow cause the same
pressure drop as 7 feet of straight pipe.
Tables 4 and 5. Note in the
Vent/air piping length verification
procedure:
Step 1 — Determine dimensions of vent/air pipe
needed for planned location
Measure or calculate the vent/air pipe lengths required
for the planned location of the boiler and floor/roof
penetrations. See Figure 11 for a typical layout.
•How long will the vertical B-vent section have to be?
Round up to the nearest 5 feet (for example, if B-vent
length needs to be 12 feet, round this amount up to the
nearest 5 feet — use 15 feet for your B-vent length).
(This is dimension L in Figure 11.)
•How many elbows will be needed in the vent connector
piping (from boiler to B-vent tee)?
•How many feet of vent piping will be needed for the
connector runs?
(This would be the sum of dimensions C & D in Fig. 11.)
•How many elbows will be needed in the air connector
piping (from boiler to B-vent tee)?
•How many feet of air piping will be needed for the
connector runs?
(This would be the sum of dimensions A & B in Fig. 11.)
Step 4 — Replan boiler location & piping if piping
length of vent or air is too long
See if boiler can be moved closer to vertical vent/air
piping.
See if you can reduce the number of elbows required
vent piping must have 2 elbows minimum in order to
provide horizontal piping to install condensate drain
tee.
Example verification (
Step 1 — Vent/air piping required per plan
As an example, consider an installation of a CGs-5
boiler, where the boiler and vent/air locations would
require:
•Boiler model = CGs-5.
•B-vent length (L) = 20 feet.
•Vent connector piping requires 2 elbows.
•Vent connector piping length (D + C) = 16 feet.
•Air connector piping requires 1 elbow.
•Air connector piping length (B + A) = 17 feet.
Step 2 — Verify vent piping
•Enter Table 5 at the row for B-vent length of 20
feet.
•Move to the 2-elbow column.
•Read a maximum connector pipe length of 18 feet.
Conclusion — Vent piping is within limits because
vent connector piping would only be 16 feet (less than
the maximum of 18 feet).
Figure 11Figure 11
Figure 11):
Figure 11Figure 11
12
Step 2 — Verify that vent connector piping is within
allowable limits
Use Table 4 or 5, depending on boiler model to be used.
Find the row with the B-vent length the installation
requires. Move across to the column with the number
of vent elbows needed for the installation. This number
is the maximum allowable vent connector piping length.
Step 3 — Verify that air connector piping is within
allowable limits
Use Table 4 or 5, depending on boiler model to be used.
Find the row with the B-vent length the installation
requires. Move across to the column with the number
of air pipe elbows needed for the installation. This
number is the maximum allowable air pipe connector
piping length.
Step 3 — Verify air piping
•Enter Table 5 at the row for B-vent length of 20
feet.
•Move to the 1-elbow column.
•Read a maximum connector pipe length of 25 feet.
Conclusion — Air piping is within limits because air
connector piping would only be 17 feet (less than the
maximum of 25 feet).
Step 4 — Replanning
No replanning needed. Vent and air piping lengths are
within limits.
Part Number 550-141-873/0502
Page 13
VV
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
Maximum connector pipe length, vent or air:
•Combustion air connector pipe
•Vent connector pipe
CGs-3 and CGs-4
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Figure 11 Typical vent/air pipingTable 4 CGs-3 and CGs-4
“B-Vent”
length
(feet)
L
5504336292215 8
104538312417103
1540332619125--
20352821147----
2530231692----
302518114------
Note: Combustion air connector pipe length = A + B
Vent connector pipe length = C + D
Total number of elbows
1234567
Max. length from boiler to “B-Vent”
Table 5 CGs-5 and CGs-6
Maximum connector pipe length, vent or air:
•Combustion air connector pipe
•Vent connector pipe
CGs-5 and CGs-6
L
L = B-vent length
A + B
C + D
A
= Combustion air
connector piping length
= Vent connector piping length
Elbow
“B-Vent”
length
(feet)
L
540332619125--
10352821147----
1530231692----
202518114------
2520136--------
301581--------
Note: Combustion air connector pipe length = A + B
Vent connector pipe length = C + D
Part Number 550-141-873/0502
Total number of elbows
1234567
Max. length from boiler to “B-Vent”
D
Vent piping
Condensate
drain line
Elbows
87304
C
B
Combustion air piping
13
Page 14
GOLD CGs Gas-FGOLD CGs Gas-F
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
9. Installation — assembly
Step 1
Step 2
Assemble B-vent piping
1. Install 5" type B support, B-vent combustion air run,
flashing, fire stops and storm collar per
manufacturer’s instructions. Apply approved sealant
to each B-vent joint. See Figure 12.
2. Install type B draft hood connector to bottom of
combustion air run. Seal with approved sealant.
Prepare & insert vertical vent
1. From top or bottom of combustion air run, install
vent piping
•Top of vent piping must extend 3" above
top of rain cap. See Figure 5, page 8.
•Bottom of vent piping must extend 18"
below draft hood connector.
2. At each vent joint:
a. Follow vent pipe manufacturer’s instructions to
assemble and seal joints. Sealant recommended
by vent pipe manufacturer must be used as
indicated in their instructions.
b. Apply 2 self-adhesive elastomer grippers to vent
clamp. Grippers must be positioned on clamp
as shown in Figure 13. Bend out 2 ears on vent
clamp.
.
Figure 12 Sealing B-vent joints
87305
Figure 13Apply elastomer strips to vent clamps
87306
Figure 14 Install vent clamps on vent piping
14
c. Fasten clamp around vent pipe with 2 – 1¹⁄₄"
screws in top and bottom holes, about every 5
feet. See Figure 14. Tighten screws until clamp
does not turn or slide around vent piping.
87307
Part Number 550-141-873/0502
Page 15
VV
Draft hood
connector
Vent
support
87308
5” x 5” x 3”
Te e
Elastomer
flashing
Draft hood
connector
Bottom cap
87309
ertical Direct Vertical Direct V
V
ertical Direct V
VV
ertical Direct Vertical Direct V
enting — Venting — V
enting — V
enting — Venting — V
enting Supplemententing Supplement
enting Supplement
enting Supplemententing Supplement
Step 3
Step 4
Install vent support
1. Apply 1 elastomer gripper to vent support.
2. Intall vent support around vent piping just below
draft hood connector as shown in Figure 15. Fasten
support around vent piping with 1 – 1 ¹⁄₄" screw.
3. Tighten screw until support does not turn or slide
around vent piping.
Install 5" x 5" x 3" tee
1. Slide tee over vent piping and attach uncrimped end
to bottom of draft hood connector:
a. Drill 3 holes in tee for ¹⁄₄" sheet metal screws.
Do not allow drill to
penetrate vent pipe. Drill
holes carefully in tee and use
1
only
/
" screws to fasten tee
4
to draft hood connector.
Failure to do so can damage
vent pipe, causing severe
personal injury or substantial
property damage.
b. Seal all seams and screws with approved sealant.
Figure 15 Install vent support
Figure 16 Install tee
2. Secure bottom cap to tee with duct tape. Slide
elastomer flashing up around vent pipe and tuck
lip into cap’s bottom opening. Seal with approved
sealant.
Follow vent pipe manufacturer's instructions to
assemble and seal joints. Sealant recommended by vent
pipe manufacturer must be used as indicated in their
instructions. Vent and combustion air connector piping
must be sealed gas-tight to prevent possibility of flue
gas spillage and carbon monoxide emissions, resulting
in severe personal injury or death.
Part Number 550-141-873/0502
15
Page 16
GOLD CGs Gas-FGOLD CGs Gas-F
Vent pipe
Elastomer
flashing
Rain cap
87310
GOLD CGs Gas-F
GOLD CGs Gas-FGOLD CGs Gas-F
ired Wired W
ired W
ired Wired W
ater Boilerater Boiler
ater Boiler
ater Boilerater Boiler
9. Installation — assemblycontinued
Step 5Install rain cap
1. On roof, cut 4 ¹⁄₂" hole in top of rain cap and
install cap over protruding vent pipe. Slide
elastomer flashing down around vent pipe
and tuck lip into cap’s top opening.
2. Connect termination coupling to vent pipe
using vent pipe manufacturer’s specified
sealant.
Step 6
Finish installation
1. Complete vent piping to boiler, making sure to follow vent pipe manufacturer’s instructions and Weil-McLain
vent manufacturers special gas vent system vent and combustion air venting supplements.
2. Use any of the following to install combustion air connector piping from tee to boiler, making sure to seal all
joints and seams:
a. 3" Flexible dryer vent — A piece of 3" galvanized is required at each end to adapt. Seal all pipe joints and
seams between pipe and dryer vent with approved sealant.
b. Galvanized or aluminum single wall pipe — Seal all joints and seams using approved sealant.
c. 3" PVC — Seal all joints using PVC cement.
Figure 17 Install rain cap
16
3. Condensate drain line — A condensate drain fitting is always required for through-roof vents. Follow vent
manufacturer’s instructions to install condensate drain line.
Use only silicone tubing rated for at least 400°F for the first 18" of condensate drain line, then
other non-metallic tubing may be used. Using any other material could cause flue gas leakage,
potentially resulting in severe personal injury, death or substantial property damage.
4.Multiple boilers may be vented with vent terminations at the same height. Space terminations to provide a
minimum of 1 fott between pipes for U.S. installations. For Canadian installations, provide clearances required
by B149.1 or B149.2 Installation Code.
Part Number 550-141-873/0502
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.