This supplement must only be used by a qualified heating installer/service technician. Before installing, read all
instructions, including this supplement, the boiler manual and any related documents. Perform steps in the order given.
Failure to comply could result in severe personal injury, death or substantial property damage.
Part Number 550-110-646/0607
Page 2
EG • PEG • EGH Series 4
Please read this page first!
Hazard definitions
The following defined terms are used throughout these instructions to bring attention to the
presence of hazards of various risk levels or to important information concerning the life of
the product.
Indicates presence of hazards that will cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or
property damage.
Indicates special instructions on installation, operation or maintenance that are
important but not related to personal injury or property damage.
Note to the installer
Controls must only be installed by a Weil-McLain distributor or other qualified
installer/service technician in accordance with this Supplement and all applicable
codes and requirements of the authority having jurisdiction. Read this Control
Supplement completely before beginning the installation. If the information
in this Supplement is not followed exactly, a fire, explosion, carbon monoxide
emission or other hazardous conditions can result, causing severe personal injury,
death or substantial property damage.
This system is used on gas-fired boilers without vent dampers as shipped from
the factory. This system is not offered for retrofit. Any attempt to apply the system
components to boilers shipped for use with a different control system will not
be covered under boiler warranty and can cause severe personal injury, death or
substantial property damage.
When calling or writing about the boiler, please have the boiler model number
from the boiler rating label and the CP number from the boiler jacket.
2
Part Number 550-110-646/0607
Page 3
Universal control systems — Control supplement
Table of contents
Hazard definitions and Note to the installer ....................................................................................2
Control installation — EG-30 through EG-75 water boilers without tankless heaters ............ 4-5
Control installation — EG-30 through EG-75 water boilers with tankless heaters .................. 6-7
Control installation — EG and PEG steam boilers with probe-type low water cutoff ............. 8-9
Control installation — EG steam boilers with float-type low water cutoff ............................ 10-11
Control installation — EGH water boilers without tankless heaters ..................................... 12-13
Control installation — EGH water boilers with tankless heaters ........................................... 14-15
Control installation — EGH steam boilers with probe-type low water cut-off ..................... 16-17
Control installation — EGH steam boilers with float-type low water cut-off ....................... 18-19
Replacement parts ...........................................................................................................................32
Part Number 550-110-646/0607
3
Page 4
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
4
Part Number 550-110-646/0607
Page 5
Universal control systems — Control supplement
Control installation
EG-30 through EG-75 water boilers without tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 1 EG-30 through EG-75 water boilers without tankless heaters
1. Mount and wire controls per wiring diagram, page 4, and Figure 1.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
5
Page 6
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
6
Part Number 550-110-646/0607
Page 7
Universal control systems — Control supplement
Control installation continued
EG-30 through EG-75 water boilers with tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 2 EG-30 through EG-75 water boilers with tankless heaters
1. Mount and wire controls per wiring diagram, page 6, and Figure 2.
a. Install combination limit control and relay in tapping. See Boiler Manual
control tapping table. Operating and limit circuit wiring must be 14 gauge
or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
7
Page 8
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
8
Part Number 550-110-646/0607
Page 9
Universal control systems — Control supplement
Control installation continued
EG and PEG steam boilers with probe-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 3 EG and PEG steam boilers with probe-type low water cut-off
1. Mount and wire controls per wiring diagram, page 8, and Figure 3.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
9
Page 10
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
10
Part Number 550-110-646/0607
Page 11
Universal control systems — Control supplement
Control installation continued
EG steam boilers with float-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 4 EG steam boilers with float-type low water cut-off
1. Mount and wire controls per wiring diagram, page 10, and Figure 4.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
Part Number 550-110-646/0607
11
Page 12
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
12
Part Number 550-110-646/0607
Page 13
Universal control systems — Control supplement
Control installation continued
EGH water boilers without tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 5 EGH water boilers without tankless heaters
1. Mount and wire controls per wiring diagram, page 12, and Figure 5.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
13
Page 14
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
14
Part Number 550-110-646/0607
Page 15
Universal control systems — Control supplement
Control installation continued
EGH water boilers with tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 6 EGH water boilers with tankless heaters
1. Mount and wire controls per wiring diagram, page 14, and Figure 6.
a. Install combination limit control and relay in tapping. See Boiler Manual
control tapping table. Operating and limit circuit wiring must be 14 gauge
or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
15
Page 16
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
16
Part Number 550-110-646/0607
Page 17
Universal control systems — Control supplement
Control installation continued
EGH steam boilers with probe-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 7 EGH steam boilers with probe-type low water cut-off
1. Mount and wire controls per wiring diagram, page 16, and Figure 7.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
provided.
Part Number 550-110-646/0607
17
Page 18
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
18
Part Number 550-110-646/0607
Page 19
Universal control systems — Control supplement
Control installation continued
EGH steam boilers with float-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply
valve before attempting to work on the
boiler. Failure to comply can cause severe
personal injury, death or substantial property damage.
Figure 8 EGH steam boilers with float-type low water cut-off
1. Mount and wire controls per wiring diagram, page 18, and Figure 8.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
b.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
provided.
Install transformer with plug-in relay receptacle and relay.
Part Number 550-110-646/0607
19
Page 20
EG • PEG • EGH Series 4
Damper installation
If not installing a vent damper, proceed to page 21.
Once damper is installed, boiler will not operate without a
damper installed.
Only dampers listed in the Replacement parts table on page 32
are approved for use on EG-30 through EG-75 Series 4 and
PEG-30 through PEG-65 Series 4 using Universal Control
Systems. Any other vent damper installed could cause severe
personal injury or death.
The following boiler models must have
damper installed:
• EG-30 through EG-65, natural or propane gas.
• PEG-30 through PEG-65, steam, natural gas.
The following boiler models may have damper
installed:
• EG-75 and EGH-85 through EGH-125, natural or propane
gas.
Minimum clearances to combustibles
Provide a minimum of 6” between the vent damper and any combustible
material. (Provide a minimum of 46” between jacket top and combustible
ceiling for EG/PEG, or 24” for EGH.) See EG • PEG • EGH Boiler manual
for complete clearance requirements.
Figure 9 Vent damper assemblies
Figure 10 Vent damper harness plug warning label
Installation
Damper must be installed directly on top of draft hood so
that it serves only that boiler. Do not modify draft hood or
damper, or make another connection between draft hood and
damper or boiler except as noted below. This will void CSA
certification and will not be covered by Weil-McLain warranty. Any changes will cause severe personal injury, death,
or substantial property damage.
1. Install plug (packed in damper carton of 4” through 8” dampers) in
hole in damper blade.
2. Install vent damper horizontally or vertically as shown in vent damper
manufacturer’s instructions. Vent damper must be installed so that it
serves only one boiler and so damper blade indicator is visible to the
user. See Figure 9.
3. Screws or rivets used to secure the vent damper to the draft hood must
not interfere with rotation of the damper blade.
4. Install damper harness between damper actuator and knockout in jacket
top panel. Use strain relief connectors and locknuts to secure both ends
of the damper harness.
Keep wiring harness clear of all hot surfaces.
20
5. Read and apply the harness plug warning label
(Figure 10) so that it is visible after installation.
6. Plug damper harness receptacle into damper harness
plug.
Bypassing (jumpering) vent damper will
cause flue products such as carbon monoxide to escape into the house. This will
cause severe personal injury or death.
After boiler has operated once, if either
end of the harness is disconnected, the
system safety shutdown will occur. The
boiler will not operate until harness is
reconnected.
Effikal or Field Controls damper — Damp-
er hold open switch must be in “Automatic
Operation” position for system to operate
properly.
Part Number 550-110-646/0607
Page 21
Universal control systems — Control supplement
Boilers with
United Technologies
Ignition control
(control load of 0.10 amps is
included in the values at right)
Gas valveWithout
damper
(amps)
With
Effikal
damper
(amps)
With
Johnson
damper
(amps)
Honeywell VR82000.600.700.80
Honeywell VR83000.800.901.00
Robertshaw 7200ER0.500.600.70
Robertshaw 7000ERHC0.800.901.00
White-Rodgers 36E0.400.500.60
White-Rodgers 36C0.700.800.90
Boilers with
Honeywell
Ignition control
(control load of 0.20 amps is
included in the values at right)
Gas valveWithout
damper
(amps)
With
Effikal
damper
(amps)
With
Johnson
damper
(amps)
Honeywell VR82000.700.800.90
Honeywell VR83000.901.001.10
Robertshaw 7200ER0.600.700.80
Robertshaw 7000ERHC0.901.001.10
White-Rodgers 36E0.500.600.70
White-Rodgers 36C0.800.901.00
Checkout procedure
1. See pages 22–26 for “Operating instructions.”
2. Raise room thermostat to call for heat. Damper actuator will slowly open damper.
3. When damper is fully open, main gas valve will open and main burners will ignite.
Damper must be fully open before main burners light. If damper does not fully
open, flue products will escape into house, causing severe personal injury or
death.
4. Lower thermostat setting. Main burner flames will go out, then damper will close.
5. Repeat steps 1 through 3 several times to verify operation.
6. Return thermostat to normal setting.
Room thermostat anticipator settings
Water without tankless heater — 0.40 amps
Water with tankless heater — 0.20 amps
Steam — Select based on gas valve and damper. See table below.
Part Number 550-110-646/0607
21
Page 22
EG • PEG • EGH Series 4
Operating instructions –EG and PEG with
Honeywell VR8204/VR8304 gas valve
22
Part Number 550-110-646/0607
Page 23
Universal control systems — Control supplement
Operating instructions –EG/PEG-30 through EG/PEG-50 with
White-Rodgers 36E gas valve
Part Number 550-110-646/0607
23
Page 24
EG • PEG • EGH Series 4
Operating instructions –EG/PEG-30 through EG/PEG-50 with
Robertshaw 7200 gas valve
24
Part Number 550-110-646/0607
Page 25
Universal control systems — Control supplement
Operating instructions –EG/PEG-55, EG/PEG-65, EG-75 with
White-Rodgers 36C gas valve
Part Number 550-110-646/0607
25
Page 26
EG • PEG • EGH Series 4
Operating instructions –EGH with
Robertshaw 7000DERHC gas valve
26
Part Number 550-110-646/0607
Page 27
Universal control systems — Control supplement
Troubleshooting
Burner access panel must be in posi-
tion during boiler operation to prevent
momentary flame rollout on ignition of
main flame. Severe personal injury or
substantial property damage will result.
Never jumper (bypass) any device ex-
cept for momentary testing as outlined
in Troubleshooting Charts. Substantial
property damage and/or severe personal
injury could occur.
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous operation.
Verify proper operation after servicing. See
vent damper manufacturer’s instructions
packed with vent damper for additional
information. Failure to comply could
result in severe personal injury, death or
substantial property damage.
Before troubleshooting
1. Have a voltmeter that can check 120 VAC, 24 VAC,
and a continuity tester.
2. Check for 120 VAC (minimum 102 to maximum
132) to boiler.
3. Make sure thermostat is calling for heat and contacts
(including appropriate zone controls) are closed.
Check for 24VAC between thermostat wire nuts and
ground.
In event of vent damper failure:
Effikal or Field Controls vent damper
If troubleshooting chart recommends replacing actuator and actuator is
not immediately available, damper blade can be fixed in an open position
to allow boiler operation. Manually turning blade can cause actuator
damage
actuator malfunction.
1. Move damper service switch to Hold Damper Open position. Apply call
2. If step 1 does not open damper, manually rotate damper blade to open
3. Do not leave vent damper permanently in this position. Replace actua-
Johnson Controls vent damper
If troubleshooting chart recommends replacing actuator and actuator is
not immediately available, damper blade can be fixed in an open position
to allow boiler operation. Follow these instructions only in case of no heat
or damper actuator malfunction. See Figure 11.
1. Turn off power to boiler.
2. Refer to vent damper manufacturer’s instructions for procedure to fix
3. Turn on power to boiler.
4. Using wrench or pliers on flat shaft section, manually rotate damper
5. Do not leave vent damper permanently in this position. Replace
. Follow these instructions only in case of no heat or damper
for heat to boiler. Damper blade should then rotate to open position
and boiler will fire.
position using wrench or pliers on flat shaft between damper and actuator. Boiler will fire. Verify that damper service switch is in Hold Damper
Open position (Figure 11).
tor immediately. If vent damper is left in open position, boiler will not
operate at published efficiencies.
Failure to turn off power to boiler can result in severe personal
injury, death or substantial property damage.
vent damper in open position.
blade until green light turns on. Boiler will fire (Figure 11).
actuator immediately. If vent damper is left in open position, boiler will
not operate at published efficiencies.
Part Number 550-110-646/0607
Figure 11 Manually opening vent damper
27
Page 28
EG • PEG • EGH Series 4
Troubleshooting continued
CHART 1: NO SPARK — System does not work — Without vent damper
VISUALLY CHECK - is ground wire connected from
“GND (Burner)” to ignition control mounting screw;
and ground wire connected from transformer
Terminal “C” to case ground?
Correct by making connections.
N
Is 24VAC present across Terminals 24V & 24V(GND)?
No Yes
o Y
es
Is the vent damper
plug in place?
NoYes
Check for open thermostat or circulator relay
(where used) or check for loose wire connections, defective spill switch or rollout
thermal fuse element, or open LWCO or limit
contacts.
If LWCO, spill switch or rollout
thermal fuse element contacts
are open, determine cause and correct condition. Failure to do so will cause severe personal injury, death, or substantial property
damage.
Replace ignition control.
Securely connect, then turn ON supply voltage and re-test.
Replace pilot assembly.
Replace damper
plug and retest.
Open thermostat contacts for 15 seconds. Close thermostat contacts - is 24 VAC across terminals PV & MV/PV?
No Yes
Turn OFF supply voltage.
Check spark wire. Is it securely connected
to spark transformer?
No Y
Is condition of spark wire good (not cut,
brittle, burned, or cracked)?
No Y
es
es
Is spark gap 0.125” and located in pilot gas steam?
No Yes
Replace pilot assembly, turn ON supply
voltage, operate system several complete
heat cycles.
28
Is spark electrode ceramic cracked?
No Yes
Replace pilot assembly, turn ON supply
voltage, operate system several complete
heat cycles.
Replace ignition control.
Part Number 550-110-646/0607
Page 29
Universal control systems — Control supplement
Troubleshooting continued
CHART 2: NO SPARK — System does not work — With vent damper
Is damper harness securely plugged in at both
ends?
Secure connections.
Check for loose wire connections
or bad relay on transformer.
No Y
Is 24VAC present across terminals C and Y on
transformer?
No Y
es
es
Check for open thermostat or circ. relay (where used) or check for
loose wire connections, defective spill switch or rollout thermal fuse
element, or open LWCO or high limit contacts.
If LWCO, spill switch or rollout thermal fuse element
condition. Failure to do so will cause severe personal injury, death,
or substantial property damage.
Is 24VAC present across terminals PV
and MV/PV?
No Y
Check continuity of each wire in wiring
harness to damper. Does continuity exist
for each wire?
N
Replace damper
wiring harness.
contacts are open, determine cause and correct
Check for out of round stack section.
Does motor rotate open?
Replace actuator.
o Y
Remove damper harness from boiler
wiring harness. TEMPORARILY install
jumper between terminal 2 and
terminal 5 on damper plug in boiler
wiring harness. See Figure 14. Does
boiler fire?
N
Replace ignition control.
o Y
es
es
Replace actuator.
No Y
Open thermostat contacts for 30
seconds. Damper will rotate to closed
position. Close thermostat contacts.
Damper will rotate to open position.
es
Is spark present now?
Yes No
Is 24VAC present across terminal C and yellow wire
between damper connector and rollout thermal fuse
element?
N
es
Re-test.
Securely connect and
turn ON supply voltage.
Re-test.
Replace pilot assembly.
Is spark gap 0.125” and
located in pilot gas stream?
No Y
o Y
Is damper rotated open?
No Yes
Is 24VAC present at Terminals
PV and MV/PV?
No Y
Turn OFF supply voltage.
Check spark wire. Is it securely
connected to ignition control?
No Y
Is condition of spark
wire good (not brittle,
burned, or cracked)?
N
Is spark electrode ceramic
cracked?
No Y
es
Replace pilot assembly.
es
es
o Y
es
es
es
14253
FIGURE 14
Part Number 550-110-646/0607
Replace pilot assembly.
6
Replace ignition
control.
Turn ON supply voltage
and operate system
several complete cycles.
29
Page 30
EG • PEG • EGH Series 4
Troubleshooting continued
CHART 3: PILOT LIGHTS — Main valve will not come on — With or without vent damper
Does spark stay on for more than a few seconds after pilot is established?
NoYes
Replace
ignition control.
Contact gas
supplier to
correct pressure.
Correct wiring.
Is 24VAC between terminals MV and
PV on ignition control?
NoYes
Check inlet gas pressure. Is pressure:
at least 5.0 inches w.c.?
•
not more than 14.0 inches w.c.?
•
NoYes
Is main valve wiring secure at
terminals?
NoYes
Replace gas
valve.
Replace pilot
assembly.
Does system have proper flame signal?
Make sure sense wire is not wrapped around any pipes or
accessories.
Is sense wire securely attached to sense terminal and pilot
assembly?
NoYes
Correct.
Is sense wire or sensing probe
shorted out to a metal surface?
NoYes
Correct.
Check sense wire continuity.
Check condition of insulation.
Both OK?
NoYes
Is sensing probe ceramic
cracked?
NoYes
Replace pilot
assembly.
Set up microammeter to measure output current in flame
sensor circuit as follows:
etach sense lead from ignition control. Attach
a. D
negative lead from microammeter to sense terminal on
ignition control.
ttach positive lead to sense wire from pilot assembly.
b. A
c. Disconnect main valve lead from terminal “MV” on
ignition control.
NoYes
Replace ignition control.
30
nergize the system. Spark should ignite the pilot. As
d. E
soon as pilot is burning, the microammeter should read
at least 1.0 microamp for Honeywell S8620C control,
or 0.1 microamp for United Technologies 1003-611A
control.
. I
s flame current signal less than the minimum specified
e
in step “d” above?
Check for proper gas pressure.
•
Clean pilot assembly.
•
Tighten mechanical and electrical connections.
•
Check for proper system grounding.
•
See procedure to check grounding on next page.
•
Part Number 550-110-646/0607
Page 31
Universal control systems — Control supplement
Troubleshooting continued
CHART 3 (continued): Procedure to check system grounding
Pilot assembly and ignition control must share common ground
with main burner. Nuisance shutdowns are often caused by
poor or erratic ground.
Check for good metal-to-metal contact between pilot burner
•
bracket and main burner, and between main burner and
burner rest.
Check ground lead from “GND (Burner)” terminal on ignition
•
control to ignition control mounting screw, and from “C”
on transformer to transformer case ground. Make sure
connections are clean and tight. If wire is damaged or
deteriorated, replace with No. 18 gauge moisture-resistant,
thermoplastic-insulated wire with 105°C minimum rating.
CHART 4: PILOT LIGHTS — Main valve will not come on — With or without vent damper
Are pilot valve connections correct and securely fastened?
NoYes
Connect securely to terminals PV and
MV/PV on ignition control.
Is manual hand valve open?
Open manual hand valve.
Contact gas supplier to correct gas pressure.
Is inlet gas pressure at least 5.0” w.c. and no more than 14.0” w.c.?
NoYes
Is gas present at pilot burner assembly?
NoYes
on the ignition control. Use a match
taped to a long screwdriver or pilot
lighter rod to manually light the pilot.
Does the pilot light?
To check for gas at pilot —
Remove the wire to “MV”
NoYes
Make sure gas cock is in “ON” position and
pilot line is not kinked or obstructed. Check
for clean pilot orifice. If OK, replace the gas
valve.
Part Number 550-110-646/0607
Replace pilot assembly.
Is spark gap 0.125” and located in pilot
gas stream?
NoYes
Block any draft around the boiler.
•
Check for clean pilot orifice.
•
31
Page 32
EG • PEG • EGH Series 4
Replacement parts
Only dampers listed below are approved for use on EG, PEG and EGH Series 4 boilers. Any other damper installed can
EG-30 through -75 water
EG-35 through -75 water with tankless heater
EG-30 through -75 steam, float LWCO
EG-30 through -75, PEG-30 through -65 steam, probe LWCO
EGH water without tankless heater
EGH water with tankless heater
EGH steam, float LWCO
EGH steam, probe LWCO
½” x ½”, sizes 30 through 50Honeywell VR8204A2001
¾” x ¾”, sizes 55 through 75Honeywell VR8304P4348
¾” x 1”, sizes 85 through 95Robertshaw 7000DERHC-S7C511-044-286
1” x 1”, sizes 105 through 125Robertshaw 7000DERHC-S7C511-044-287