Weil-McLain Boiler User Manual

Page 1
EG
PEG
EGH
Gas-Fired Boilers – Series 4
Control supplement – Universal control systems
For additional information, refer to . . .
EG• PEG • EGH Boiler manual
for Natural or Propane gas
This supplement must only be used by a qualified heating installer/service technician. Before installing, read all
instructions, including this supplement, the boiler manual and any related documents. Perform steps in the order given. Failure to comply could result in severe personal injury, death or substantial property damage.
Part Number 550-110-646/0607
Page 2
EG • PEG • EGH Series 4
Please read this page first!
Hazard definitions
The following defined terms are used throughout these instructions to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or
substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or
property damage.
Indicates special instructions on installation, operation or maintenance that are
important but not related to personal injury or property damage.
Note to the installer
Controls must only be installed by a Weil-McLain distributor or other qualified
installer/service technician in accordance with this Supplement and all applicable codes and requirements of the authority having jurisdiction. Read this Control Supplement completely before beginning the installation. If the information in this Supplement is not followed exactly, a fire, explosion, carbon monoxide emission or other hazardous conditions can result, causing severe personal injury, death or substantial property damage.
This system is used on gas-fired boilers without vent dampers as shipped from
the factory. This system is not offered for retrofit. Any attempt to apply the system components to boilers shipped for use with a different control system will not be covered under boiler warranty and can cause severe personal injury, death or substantial property damage.
When calling or writing about the boiler, please have the boiler model number
from the boiler rating label and the CP number from the boiler jacket.
2
Part Number 550-110-646/0607
Page 3
Universal control systems — Control supplement
Table of contents
Hazard definitions and Note to the installer ....................................................................................2
Control installation — EG-30 through EG-75 water boilers without tankless heaters ............ 4-5
Control installation — EG-30 through EG-75 water boilers with tankless heaters .................. 6-7
Control installation — EG and PEG steam boilers with probe-type low water cutoff ............. 8-9
Control installation — EG steam boilers with float-type low water cutoff ............................ 10-11
Control installation — EGH water boilers without tankless heaters ..................................... 12-13
Control installation — EGH water boilers with tankless heaters ........................................... 14-15
Control installation — EGH steam boilers with probe-type low water cut-off ..................... 16-17
Control installation — EGH steam boilers with float-type low water cut-off ....................... 18-19
Damper installation .......................................................................................................................... 20
Checkout procedure ........................................................................................................................21
Operating instructions ............................................................................................................... 22-26
Troubleshooting .......................................................................................................................... 27-31
Replacement parts ...........................................................................................................................32
Part Number 550-110-646/0607
3
Page 4
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
4
Part Number 550-110-646/0607
Page 5
Universal control systems — Control supplement
Control installation
EG-30 through EG-75 water boilers without tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 1 EG-30 through EG-75 water boilers without tankless heaters
1. Mount and wire controls per wiring diagram, page 4, and Figure 1.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
5
Page 6
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
6
Part Number 550-110-646/0607
Page 7
Universal control systems — Control supplement
Control installation continued
EG-30 through EG-75 water boilers with tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 2 EG-30 through EG-75 water boilers with tankless heaters
1. Mount and wire controls per wiring diagram, page 6, and Figure 2.
a. Install combination limit control and relay in tapping. See Boiler Manual
control tapping table. Operating and limit circuit wiring must be 14 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
7
Page 8
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
8
Part Number 550-110-646/0607
Page 9
Universal control systems — Control supplement
Control installation continued
EG and PEG steam boilers with probe-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 3 EG and PEG steam boilers with probe-type low water cut-off
1. Mount and wire controls per wiring diagram, page 8, and Figure 3.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
9
Page 10
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
10
Part Number 550-110-646/0607
Page 11
Universal control systems — Control supplement
Control installation continued
EG steam boilers with float-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 4 EG steam boilers with float-type low water cut-off
1. Mount and wire controls per wiring diagram, page 10, and Figure 4.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
Part Number 550-110-646/0607
11
Page 12
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
12
Part Number 550-110-646/0607
Page 13
Universal control systems — Control supplement
Control installation continued
EGH water boilers without tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 5 EGH water boilers without tankless heaters
1. Mount and wire controls per wiring diagram, page 12, and Figure 5.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
provided.
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
13
Page 14
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
14
Part Number 550-110-646/0607
Page 15
Universal control systems — Control supplement
Control installation continued
EGH water boilers with tankless heaters
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 6 EGH water boilers with tankless heaters
1. Mount and wire controls per wiring diagram, page 14, and Figure 6.
a. Install combination limit control and relay in tapping. See Boiler Manual
control tapping table. Operating and limit circuit wiring must be 14 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
Part Number 550-110-646/0607
15
Page 16
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
16
Part Number 550-110-646/0607
Page 17
Universal control systems — Control supplement
Control installation continued
EGH steam boilers with probe-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 7 EGH steam boilers with probe-type low water cut-off
1. Mount and wire controls per wiring diagram, page 16, and Figure 7.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
b.
Install transformer with plug-in relay receptacle and relay.
c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
provided.
Part Number 550-110-646/0607
17
Page 18
EG • PEG • EGH Series 4 — Universal control systems — Control Supplement
18
Part Number 550-110-646/0607
Page 19
Universal control systems — Control supplement
Control installation continued
EGH steam boilers with float-type low water cut-off
For your safety, turn off electrical power
supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial prop­erty damage.
Figure 8 EGH steam boilers with float-type low water cut-off
1. Mount and wire controls per wiring diagram, page 18, and Figure 8.
a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws
b. c. Operating and limit circuit wiring must be 18 gauge or heavier.
2. Bring supply wiring to boiler. Must be 14 gauge or heavier.
3. Proceed to page 20.
provided.
Install transformer with plug-in relay receptacle and relay.
Part Number 550-110-646/0607
19
Page 20
EG • PEG • EGH Series 4
Damper installation
If not installing a vent damper, proceed to page 21.
Once damper is installed, boiler will not operate without a
damper installed.
Only dampers listed in the Replacement parts table on page 32
are approved for use on EG-30 through EG-75 Series 4 and PEG-30 through PEG-65 Series 4 using Universal Control Systems. Any other vent damper installed could cause severe personal injury or death.
The following boiler models must have damper installed:
• EG-30 through EG-65, natural or propane gas.
PEG-30 through PEG-65, steam, natural gas.
The following boiler models may have damper installed:
EG-75 and EGH-85 through EGH-125, natural or propane gas.
Minimum clearances to combustibles
Provide a minimum of 6” between the vent damper and any combustible material. (Provide a minimum of 46” between jacket top and combustible ceiling for EG/PEG, or 24” for EGH.) See EG • PEG • EGH Boiler manual for complete clearance requirements.
Figure 9 Vent damper assemblies
Figure 10 Vent damper harness plug warning label
Installation
Damper must be installed directly on top of draft hood so
that it serves only that boiler. Do not modify draft hood or damper, or make another connection between draft hood and damper or boiler except as noted below. This will void CSA certification and will not be covered by Weil-McLain war­ranty. Any changes will cause severe personal injury, death, or substantial property damage.
1. Install plug (packed in damper carton of 4” through 8” dampers) in
hole in damper blade.
2. Install vent damper horizontally or vertically as shown in vent damper
manufacturer’s instructions. Vent damper must be installed so that it serves only one boiler and so damper blade indicator is visible to the user. See Figure 9.
3. Screws or rivets used to secure the vent damper to the draft hood must
not interfere with rotation of the damper blade.
4. Install damper harness between damper actuator and knockout in jacket
top panel. Use strain relief connectors and locknuts to secure both ends of the damper harness.
Keep wiring harness clear of all hot surfaces.
20
5. Read and apply the harness plug warning label (Figure 10) so that it is visible after installation.
6. Plug damper harness receptacle into damper harness plug.
Bypassing (jumpering) vent damper will
cause flue products such as carbon mon­oxide to escape into the house. This will cause severe personal injury or death.
After boiler has operated once, if either
end of the harness is disconnected, the system safety shutdown will occur. The boiler will not operate until harness is reconnected.
Effikal or Field Controls damper — Damp-
er hold open switch must be in “Automatic Operation” position for system to operate properly.
Part Number 550-110-646/0607
Page 21
Universal control systems — Control supplement
Boilers with United Technologies Ignition control
(control load of 0.10 amps is included in the values at right)
Gas valve Without
damper
(amps)
With
Effikal
damper
(amps)
With
Johnson
damper
(amps)
Honeywell VR8200 0.60 0.70 0.80
Honeywell VR8300 0.80 0.90 1.00
Robertshaw 7200ER 0.50 0.60 0.70
Robertshaw 7000ERHC 0.80 0.90 1.00
White-Rodgers 36E 0.40 0.50 0.60
White-Rodgers 36C 0.70 0.80 0.90
Boilers with Honeywell Ignition control
(control load of 0.20 amps is included in the values at right)
Gas valve Without
damper
(amps)
With
Effikal
damper
(amps)
With
Johnson
damper
(amps)
Honeywell VR8200 0.70 0.80 0.90
Honeywell VR8300 0.90 1.00 1.10
Robertshaw 7200ER 0.60 0.70 0.80
Robertshaw 7000ERHC 0.90 1.00 1.10
White-Rodgers 36E 0.50 0.60 0.70
White-Rodgers 36C 0.80 0.90 1.00
Checkout procedure
1. See pages 22–26 for “Operating instructions.”
2. Raise room thermostat to call for heat. Damper actuator will slowly open damper.
3. When damper is fully open, main gas valve will open and main burners will ignite.
Damper must be fully open before main burners light. If damper does not fully
open, flue products will escape into house, causing severe personal injury or death.
4. Lower thermostat setting. Main burner flames will go out, then damper will close.
5. Repeat steps 1 through 3 several times to verify operation.
6. Return thermostat to normal setting.
Room thermostat anticipator settings
Water without tankless heater — 0.40 amps
Water with tankless heater — 0.20 amps
Steam — Select based on gas valve and damper. See table below.
Part Number 550-110-646/0607
21
Page 22
EG • PEG • EGH Series 4
Operating instructions – EG and PEG with
Honeywell VR8204/VR8304 gas valve
22
Part Number 550-110-646/0607
Page 23
Universal control systems — Control supplement
Operating instructions – EG/PEG-30 through EG/PEG-50 with
White-Rodgers 36E gas valve
Part Number 550-110-646/0607
23
Page 24
EG • PEG • EGH Series 4
Operating instructions – EG/PEG-30 through EG/PEG-50 with
Robertshaw 7200 gas valve
24
Part Number 550-110-646/0607
Page 25
Universal control systems — Control supplement
Operating instructions – EG/PEG-55, EG/PEG-65, EG-75 with
White-Rodgers 36C gas valve
Part Number 550-110-646/0607
25
Page 26
EG • PEG • EGH Series 4
Operating instructions – EGH with
Robertshaw 7000DERHC gas valve
26
Part Number 550-110-646/0607
Page 27
Universal control systems — Control supplement
Troubleshooting
Burner access panel must be in posi-
tion during boiler operation to prevent momentary flame rollout on ignition of main flame. Severe personal injury or substantial property damage will result.
Never jumper (bypass) any device ex-
cept for momentary testing as outlined in Troubleshooting Charts. Substantial property damage and/or severe personal injury could occur.
Label all wires prior to disconnection
when servicing controls. Wiring errors can cause improper and dangerous opera­tion.
Verify proper operation after servicing. See
vent damper manufacturer’s instructions packed with vent damper for additional information. Failure to comply could result in severe personal injury, death or substantial property damage.
Before troubleshooting
1. Have a voltmeter that can check 120 VAC, 24 VAC, and a continuity tester.
2. Check for 120 VAC (minimum 102 to maximum
132) to boiler.
3. Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24VAC between thermostat wire nuts and ground.
In event of vent damper failure:
Effikal or Field Controls vent damper
If troubleshooting chart recommends replacing actuator and actuator is not immediately available, damper blade can be fixed in an open position to allow boiler operation. Manually turning blade can cause actuator
damage
actuator malfunction.
1. Move damper service switch to Hold Damper Open position. Apply call
2. If step 1 does not open damper, manually rotate damper blade to open
3. Do not leave vent damper permanently in this position. Replace actua-
Johnson Controls vent damper
If troubleshooting chart recommends replacing actuator and actuator is not immediately available, damper blade can be fixed in an open position to allow boiler operation. Follow these instructions only in case of no heat or damper actuator malfunction. See Figure 11.
1. Turn off power to boiler.
2. Refer to vent damper manufacturer’s instructions for procedure to fix
3. Turn on power to boiler.
4. Using wrench or pliers on flat shaft section, manually rotate damper
5. Do not leave vent damper permanently in this position. Replace
. Follow these instructions only in case of no heat or damper
for heat to boiler. Damper blade should then rotate to open position and boiler will fire.
position using wrench or pliers on flat shaft between damper and actua­tor. Boiler will fire. Verify that damper service switch is in Hold Damper Open position (Figure 11).
tor immediately. If vent damper is left in open position, boiler will not operate at published efficiencies.
Failure to turn off power to boiler can result in severe personal
injury, death or substantial property damage.
vent damper in open position.
blade until green light turns on. Boiler will fire (Figure 11).
actuator immediately. If vent damper is left in open position, boiler will not operate at published efficiencies.
Part Number 550-110-646/0607
Figure 11 Manually opening vent damper
27
Page 28
EG • PEG • EGH Series 4
Troubleshooting continued
CHART 1: NO SPARK — System does not work — Without vent damper
VISUALLY CHECK - is ground wire connected from “GND (Burner)” to ignition control mounting screw; and ground wire connected from transformer Terminal “C” to case ground?
Correct by making connections.
N
Is 24VAC present across Terminals 24V & 24V(GND)?
No Yes
o Y
es
Is the vent damper plug in place?
No Yes
Check for open thermostat or circulator relay (where used) or check for loose wire con­nections, defective spill switch or rollout thermal fuse element, or open LWCO or limit contacts.
If LWCO, spill switch or rollout
thermal fuse element contacts are open, determine cause and correct con­dition. Failure to do so will cause severe per­sonal injury, death, or substantial property damage.
Replace ignition control.
Securely connect, then turn ON supply voltage and re-test.
Replace pilot assembly.
Replace damper plug and retest.
Open thermostat contacts for 15 seconds. Close thermo­stat contacts - is 24 VAC across terminals PV & MV/PV?
No Yes
Turn OFF supply voltage.
Check spark wire. Is it securely connected to spark transformer?
No Y
Is condition of spark wire good (not cut, brittle, burned, or cracked)?
No Y
es
es
Is spark gap 0.125” and located in pilot gas steam?
No Yes
Replace pilot assembly, turn ON supply voltage, operate system several complete heat cycles.
28
Is spark electrode ceramic cracked?
No Yes
Replace pilot assembly, turn ON supply voltage, operate system several complete heat cycles.
Replace ignition control.
Part Number 550-110-646/0607
Page 29
Universal control systems — Control supplement
Troubleshooting continued
CHART 2: NO SPARK — System does not work — With vent damper
Is damper harness securely plugged in at both ends?
Secure connections.
Check for loose wire connections or bad relay on transformer.
No Y
Is 24VAC present across terminals C and Y on transformer?
No Y
es
es
Check for open thermostat or circ. relay (where used) or check for loose wire connections, defective spill switch or rollout thermal fuse element, or open LWCO or high limit contacts.
If LWCO, spill switch or rollout thermal fuse element
condition. Failure to do so will cause severe personal injury, death, or substantial property damage.
Is 24VAC present across terminals PV and MV/PV?
No Y
Check continuity of each wire in wiring harness to damper. Does continuity exist for each wire?
N
Replace damper wiring harness.
contacts are open, determine cause and correct
Check for out of round stack section. Does motor rotate open?
Replace actuator.
o Y
Remove damper harness from boiler wiring harness. TEMPORARILY install jumper between terminal 2 and terminal 5 on damper plug in boiler wiring harness. See Figure 14. Does boiler fire?
N
Replace ignition control.
o Y
es
es
Replace actuator.
No Y
Open thermostat contacts for 30 seconds. Damper will rotate to closed position. Close thermostat contacts. Damper will rotate to open position.
es
Is spark present now?
Yes No
Is 24VAC present across terminal C and yellow wire between damper connector and rollout thermal fuse element?
N
es
Re-test.
Securely connect and turn ON supply voltage. Re-test.
Replace pilot assembly.
Is spark gap 0.125 and located in pilot gas stream?
No Y
o Y
Is damper rotated open?
No Yes
Is 24VAC present at Terminals PV and MV/PV?
No Y
Turn OFF supply voltage.
Check spark wire. Is it securely connected to ignition control?
No Y
Is condition of spark wire good (not brittle, burned, or cracked)?
N
Is spark electrode ceramic cracked?
No Y
es
Replace pilot assembly.
es
es
o Y
es
es
es
14253
FIGURE 14
Part Number 550-110-646/0607
Replace pilot assembly.
6
Replace ignition control.
Turn ON supply voltage and operate system several complete cycles.
29
Page 30
EG • PEG • EGH Series 4
Troubleshooting continued
CHART 3: PILOT LIGHTS — Main valve will not come on — With or without vent damper
Does spark stay on for more than a few seconds after pilot is established?
No Yes
Replace ignition control.
Contact gas supplier to correct pressure.
Correct wiring.
Is 24VAC between terminals MV and PV on ignition control?
No Yes
Check inlet gas pressure. Is pressure:
at least 5.0 inches w.c.?
• not more than 14.0 inches w.c.?
No Yes
Is main valve wiring secure at terminals?
No Yes
Replace gas valve.
Replace pilot assembly.
Does system have proper flame signal?
Make sure sense wire is not wrapped around any pipes or accessories.
Is sense wire securely attached to sense terminal and pilot assembly?
No Yes
Correct.
Is sense wire or sensing probe shorted out to a metal surface?
No Yes
Correct.
Check sense wire continuity. Check condition of insulation. Both OK?
No Yes
Is sensing probe ceramic cracked?
No Yes
Replace pilot assembly.
Set up microammeter to measure output current in flame sensor circuit as follows:
etach sense lead from ignition control. Attach
a. D
negative lead from microammeter to sense terminal on ignition control.
ttach positive lead to sense wire from pilot assembly.
b. A c. Disconnect main valve lead from terminal “MV” on
ignition control.
No Yes
Replace ignition control.
30
nergize the system. Spark should ignite the pilot. As
d. E
soon as pilot is burning, the microammeter should read at least 1.0 microamp for Honeywell S8620C control, or 0.1 microamp for United Technologies 1003-611A control.
. I
s flame current signal less than the minimum specified
e
in step “d” above?
Check for proper gas pressure.
• Clean pilot assembly.
• Tighten mechanical and electrical connections.
• Check for proper system grounding.
• See procedure to check grounding on next page.
Part Number 550-110-646/0607
Page 31
Universal control systems — Control supplement
Troubleshooting continued
CHART 3 (continued): Procedure to check system grounding
Pilot assembly and ignition control must share common ground with main burner. Nuisance shutdowns are often caused by poor or erratic ground.
Check for good metal-to-metal contact between pilot burner
• bracket and main burner, and between main burner and burner rest.
Check ground lead from “GND (Burner)” terminal on ignition
• control to ignition control mounting screw, and from “C” on transformer to transformer case ground. Make sure connections are clean and tight. If wire is damaged or deteriorated, replace with No. 18 gauge moisture-resistant, thermoplastic-insulated wire with 105°C minimum rating.
CHART 4: PILOT LIGHTS — Main valve will not come on — With or without vent damper
Are pilot valve connections correct and securely fastened?
No Yes
Connect securely to terminals PV and MV/PV on ignition control.
Is manual hand valve open?
Open manual hand valve.
Contact gas supplier to correct gas pressure.
Is inlet gas pressure at least 5.0” w.c. and no more than 14.0” w.c.?
No Yes
Is gas present at pilot burner assembly?
No Yes
on the ignition control. Use a match taped to a long screwdriver or pilot lighter rod to manually light the pilot. Does the pilot light?
To check for gas at pilot — Remove the wire to “MV”
No Yes
Make sure gas cock is in “ON” position and pilot line is not kinked or obstructed. Check for clean pilot orifice. If OK, replace the gas valve.
Part Number 550-110-646/0607
Replace pilot assembly.
Is spark gap 0.125” and located in pilot gas stream?
No Yes
Block any draft around the boiler.
Check for clean pilot orifice.
31
Page 32
EG • PEG • EGH Series 4
Replacement parts
Only dampers listed below are approved for use on EG, PEG and EGH Series 4 boilers. Any other damper installed can
cause severe personal injury or death.
Description Manufacturer /
Mfr’s part number
Damper assembly
Damper actuator Effikal RVGP
Damper harness Weil-McLain 591-391-795
UCS Ignition control Honeywell S8620C1003
Boiler wiring harness (in envelope assembly)
Pilot burner assembly Precision Speed Equipment
Gas valve, natural gas
5” — EG-30, EG-35, PEG-30, PEG-35 Effikal RVGP-KS-5BKF
Johnson Q35GD-2
6” — EG-40, EG-45, PEG-40, PEG-45 Effikal RVGP-KS-6BKF
Field Controls 02722701
Johnson Q35GF-2
7” — EG-50, EG-55, PEG-50, PEG-55 Effikal RVGP-KS-7BKF
Field Controls 02723101
Johnson Q35GH-2
8” — EG-65, EG-75, PEG-65 Effikal RVGP-KS-8BKF
Johnson Q35GK-2
9” — EGH-85 Effikal RVGP-KS-9BKF
Johnson Q35GM-2
10” — EGH-95, EGH-105 Effikal RVGP-KS-10BKF
Johnson Q35GP-2
12” — EGH-115, EGH-125 Effikal RVGP-KS-10BKF
Johnson Q35GR-2
Johnson M35BE-1C
United Technologies 1003-611A
EG-30 through -75 water EG-35 through -75 water with tankless heater EG-30 through -75 steam, float LWCO EG-30 through -75, PEG-30 through -65 steam, probe LWCO EGH water without tankless heater EGH water with tankless heater EGH steam, float LWCO EGH steam, probe LWCO
½” x ½”, sizes 30 through 50 Honeywell VR8204A2001
¾” x ¾”, sizes 55 through 75 Honeywell VR8304P4348
¾” x 1”, sizes 85 through 95 Robertshaw 7000DERHC-S7C 511-044-286
1” x 1”, sizes 105 through 125 Robertshaw 7000DERHC-S7C 511-044-287
Weil-McLain 540-130-959
PSE-NA16
White-Rodgers 36E36-266
Robertshaw 7200IPER
White-Rodgers 36C74-474
Weil-McLain part number
381-800-475
381-800-476
381-800-477
381-800-478
381-800-445
381-800-446
381-800-447
510-512-337 510-312-255
511-330-097
540-130-960 540-130-961 540-130-962 540-130-966 540-130-969 540-130-967 540-130-968
511-330-218
511-044-381
511-044-382
32
Part Number 550-110-646/0607
Loading...