120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
SYSTEM
A
B
C
D
CUS
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
A
SYS
N
5
3
678
2
4
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
C
B
D
9
10
11
12
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
VLT
mA
GND
-
13
mA
GND
-
+
+
+
15
16
14
17
18
Full Modulation Sequencing Control
RUNPROGRAM
D
VLT
VLT
mA
mA
GND
-
+
19
mA
GND
-
+
+
+
+
23
20
22
21
DO NOT APPLY ANY VOLTAGE
OUTDOOR
VLT
+
24
25
TO INPUT TERMINALS
SYSTEM
SYSTEM
TEMP
TEMP
PROVE
O
T
T
O
28
26
29
27
O
30
------
SHUTDOWN
/TSTAT
/SETBACK
31
EXTENSION
MODULE
O
32
RS-485
BMC
WARNING
This Weil McLain control is strictly an operating control; it should never be used as a
primary limit or safety control. All equipment must have its own certified limit and safety
controls required by local codes. The installer must verify proper operation and correct any
safety problems prior to the installation of this Weil McLain control.
Program Switch to restrict access to
function changes. This switch is
covered with Wiring Enclosure.
LED indicates the
associated relay status.
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz , 30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CUS
ENCLOSED
ENERGY
MANAGEMENT
PWR
L
1
EQUIPMENT
LISTED
99RA
A
SYS
N
2
5
3
4
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
C
B
678
9
10
11
D
12
SYSTEM
A
B
C
D
A
CUR / VLT
CUR / VLTBCUR / VLTCCUR / VLT
mA
mA
VLT
GND
GND
-
-
+
+
13
+
15
16
14
17
The digital display shows the system status, set point,
lead stage <in brackets>, and status of each stage.
To view and adjust settings, press the appropriate buttons.
Buttons function is presented on
Bottom Row of display.
BMC
Full Modulation Sequencing Control
------
RUNPROGRAM
D
mA
mA
mA
VLT
VLT
GND
GND
-
-
+
19
18
+
+
+
+
23
20
22
21
DO NOT APPLY ANY VOLTAGE
OUTDOOR
TEMP
VLT
T
+
25
24
TO INPUT TERMINALS
SYSTEM
SYSTEM
PROVE
TEMP
O
T
O
26
O
28
30
29
27
SHUTDO
/TSTAT
/SETBACK
31
N
W
EXTENSION
MODULE
RS-485
O
32
120VAC Power
System Output controls
pumps, valves, or other
system components.
Four N.O. Boiler startup relay
outputs. Each is wired in series
with each boiler's limit circuit.
Four modulation outputs can be 0-5V,
0-10V, 1-5V, 2-10V, or 4-20ma. Go to
Startup Menu to determine the type of
output for each stage.
When connecting Outdoor and System
Sensors, no Polarity is observed.
Prove terminals must be connected
for BMC to operate boilers.
Connect Extension panels to
add additional stages using
a 6 pin phone line only (cable
provided with BMC-6X).
3
BMC and BMC-6X Installation and Operation Manual
BMC OVERVIEW
SEQUENCES UP TO 4 FULLY MODULATING STAGES.
The BMC is the perfect control whenever multiple fully modulating stages are required for hydronic heating applications. The BMC
controls the on/off and the modulation of each stage to maintain precise system set point control.
PID TYPE LOGIC
The BMC’s control algorithms allow it to look at the rate of change in the system. If the system temperature is changing quickly, the BMC
will react quickly to adjust the modulating stages’ output. If the system temperature changes slowly, the BMC will make slow and gradual
output adjustments. Therefore, the BMC adapts to specific system requirements and minimizes fluctuations around the set point.
CONTROLS 0-5 V, 0-10 V, 1-5V, 2-10V, OR 4-20 MA MODULATING MOTORS
The BMC is designed to accurately control the output from 0 to 100% of modulation for each of these different types of motors. One
BMC can even control a variety of the above different motors.
ONLY ONE SENSOR
When Set Point sensor type is selected, the BMC requires only one sensor located in the common output header of all stages. However,
when Reset is selected, an additional Outdoor Sensor is required for Outdoor Reset Ratio input.
DIGITAL DISPLAY OF ALL SYSTEM SETTINGS
The BMC’s alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to follow
menu system allows users to quickly make changes to any system setting without having to learn any specialized codes or keyboard
commands.
AUTOMATIC ROTATION AMONG STAGES
Rotating the first stage to be activated on a call for output promotes even wear on each stage. The BMC has three modes of rotation:
Manual, Last On, or Time. The Time rotates the lead stage every selected time period from every hour to every 60 days.
OUTDOOR RESET
The BMC has a hydronic outdoor temperature reset function. This allows the BMC to change the set point based on outdoor temperature.
Furthermore, additional settings have been added to fine tune this operation, like Offset, Minimum, and Maximum Water Temperature
and night setback schedule.
STANDBY BOILERS
Each of the BMC stages can be configured as a Standby boiler with an adjustable Standby delay. A boiler can be used as a backup during
extended large demand periods.
SYSTEM OUTPUT
In Set Point mode, this output can be used to activate a system pump, combustion air damper, or perform any other function that is required
when any stage is active. In Outdoor Reset mode, the System Output will activate whenever the outdoor temperature is below the Outdoor
Cutoff setting. A System Prove input checks the status of components activated by the System output before stages can be activated.
STAGING (NORMAL) OR PARALLEL MODULATION
The BMC can stage boilers as needed. That will allow it to increase the modulation on the lead boiler. When the lead boiler reaches
its modulation start point adjustment and does not satisfy the load, the BMC will start the next boiler and so on... Moreover, the BMC
allows for a parallel mode that can modulate several boilers together as a one large boiler. This mode is useful for boilers with lower
water content, which are usually more efficient at lower firing points.
ADD UP TO 16 BOILER STAGE (OPTIONAL)
As a stand-alone, the BMC is designed to control four modulating boilers. However, it has the capability of expanding its control to two
extension panels each with six boiler stages. Thus, the BMC can control a total of up to 16 boiler stages.
4
BMC and BMC-6X Installation and Operation Manual
UNDERSTANDING OPERATION CONCEPT
1:31:21:1.5
The BMC has multiple operating modes that satisfy most hydronic systems. It can change the
System Set Point based on outdoor temperature (Outdoor Reset) or it can modulate its stages
to achieve an adjustable fixed Set Point.
In Outdoor Reset, the BMC controls a hot water heating system to provide a building with
comfortable and even heat levels. The BMC varies the temperature of the circulating heating
water in response to changes in the outdoor temperature. The heating water temperature is
controlled through the modulation of stages.
The BMC also controls the system circulating pump with an adjustable Outdoor Cutoff. When
the outdoor temperature is above Outdoor Cutoff, the pump is off and no heating water is
circulated through the system. When the outdoor temperature drops below the Outdoor Cutoff,
the system pump relay is activated and the heating water circulates through the system. The
temperature of the heating water is controlled by the Reset Ratio, Water Offset, and changes
with Outdoor temperature.
RESET RATIO/OUTDOOR RESET
When a building is being heated, heat escapes through the walls, doors, and windows to
the colder outside air. The colder the outside temperature, the more heat escapes. If you
can input heat into the building at the same rate that it is lost out of the building, then
the building temperatures will remain constant. The Reset Ratio is an adjustment that
lets you achieve this equilibrium between heat input and heat loss.
The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature
: Heating Water Temperature) ratio. This means that for every degree the outdoor
temperature drops, the temperature of the heating water will increase one degree. The
starting point of the curves is adjustable, but comes factory selected at 70
°F Outdoor
Temp. and 100°F Water Temp. For example with a 1.00 (OD):1.00 (SYS) ratio, if the
outdoor temperature is 50°F, this means the temperature has fallen 20° from the starting
point of 70°F. Therefore, the heating water temperature will increase 20° to 120°F.
Each building has different heat loss characteristics. A very well insulated building will
not lose much heat to the outside air, and may need a Reset Ratio of 2.00 (OD):1.00
(SYS) (Outdoor:Water). This means the outdoor temperature would have to drop
2 degrees to increase the water temperature 1 degree. On the other hand, a poorly
insulated building with insufficient radiation may need a Reset Ratio of 1.00 (OD):2.00
(SYS). This means that for each degree the outdoor temperature dropped the water
temperature will increase 2 degrees. The BMC has a full range of Reset Ratios to match
any buildings heat loss characteristics.
A heating curve that relies not only on Outdoor temperature but also on type of radiation
will improve heat comfort. The following are suggested initial settings for different
types of radiation based on average building insulation and heat loss. The contractor
can fine tune these adjustments based on the specific building need.
With a 0° Offset, the
ratio curves begin at
100° Water Temperature.
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
Fan Coils & Air Handlers1.00 (OD) : 1.00 (SYS)20˚F
WARNING
When controlling a non condensing
boiler directly without the use of a
mixing valve, minimum boiler water
temperature must be set to boiler
manufacturer specifications. In that
case, system temperature must not go
below such temperature.
5
BMC and BMC-6X Installation and Operation Manual
MAKE SURE YOU HAVE THE RIGHT CONTROL
If you need the BCP-8W to do additional tasks that either are not listed or do not know how to set them, contact Weil McLain.
INITIAL SETUP
Setting an Initial Program will ease the configuration of the BMC and will give the opportunity to utilize many of the energy saving
features and give more comfortable heat when needed.
The program should consist of the following:
• Selecting the features that your system can utilize,
• Installation: Install the Control, switches and sensors,
• Setting the System Startup,
• Setting the System Settings,
• Setting the Stages
• Adjusting Reset Ratio and Water Offset (In Reset Mode Only)
SELECTING THE SYSTEM FEATURES
The BMC has been designed with Hydronic building heating as the primary purpose. With this in mind, many of the BMC features can
be utilized to ease, enhance and improve your system performance. Some of these features are listed in this section.
OUTDOOR RESET OR SET POINT
• The BMC can control the System Temperature either by adjusting the calculated temperature according to the Outdoor Temperature
(Outdoor Reset) or by maintaining an adjustable Set Point. The earlier relies on an Outdoor Sensor (supplied with the control) and
achieves better fuel savings in addition to better comfort.
NUMBER OF STAGES
• The BMC can be configured to control up to 4 modulating boilers. It can control up to 16 boiler stages using a maximum of two
BMC-6X Panels
MODULATION MODE
• The BMC can stage boilers using one of two methods. Normal Modulation Mode, allows it to increase the modulation of the lead
boiler. When the lead boiler reaches its modulation start point adjustment and does not satisfy the load, the BMC will start the next
boiler and so on. This mode targets boilers that can run more efficient at higher modulation rates.
• The Parallel Modulation Mode can modulate several boilers together as a one large boiler. This mode is useful for boilers that are
more efficient at lower firing points.
MODULATING SIGNAL
• The BMC is designed to accurately control the output from 0 to 100% of modulation for each of these different types of motors. One
BMC can even control a variety of the above different modulation motors.
AUTOMATIC ROTATION AMONG BOILERS
• Rotating the first burner to be activated on a call for output promotes even wear on all burners. The BMC has three modes of rotation:
Manual, Last-ON, or Time automatically rotating every selected time period from every hour to every 60 days.
STANDBY BOILER
• Any boiler can be configured as a Standby boiler. It withholds a specific boiler from being included in the Lead Rotation. However,
the Standby boiler will be fired only as a backup when all other stages combined cannot satisfy the demand and after an adjustable
delay period.
SETBACK OR DAY/NIGHT SCHEDULING
Two Setback modes are available for the BMC:
• The Day/Night Scheduling provides an adjustable time-based schedule for the Setback.
• The Setback mode uses an external signal to switch the operation of the BMC in and out of setback mode.
6
BMC and BMC-6X Installation and Operation Manual
System Run-On
• This feature lets the BMC run the SYS relay for a longer period after the boilers have been turned off. When this relay is used to
control a pump, it helps in dissipating the excess heat from the boilers combustion chamber.
INSTALLATION
Each of the BMC or BMC-6X consists of three primary enclosure components.
• The Enclosure Display Module: contains the display, buttons, LEDs and electric wiring terminals. It has two screws to hold it
to the base. A program configuration switch, used to adjust BMC settings, is placed above the terminals. This switch is enclosed
with the enclosure wiring cover for security. Wiring terminals are of the plug-in type to ease installation and removal.
• The Enclosure Base: contains the holes to mount and hold the control against the wall or any flat surface. All other enclosure
components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the
bottom to easy installation.
• The Enclosure Wiring Cover: seals the wires from the external environment. It has two screws to hold it the base and a hole to
secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been
provided.
Enclosure Display Module
MOUNTING THE ENCLOSURE
• Select a location near the equipment to be controlled.
• The surface should be flat and sufficiently wide and strong to hold the BMC
or BMC-6X.
• Keep the control away from extreme heat, cold, or humidity. Ambient
operating temperature is from 20 to 120°F.
• Remove the Enclosure Wiring Cover from the control enclosure by
removing the two bottom screws.
• Remove the Enclosure Display Module by removing the middle screws.
• Screw the Enclosure Base to the surface through the upper and lower
mounting holes on the back of the enclosure.
• Replace the Enclosure Display Module and replace the middle screws.
• Do not replace the enclosure wiring cover until all wiring is done.
• When purchasing a padlock for the enclosure, the maximum shank diameter
should not exceed ¼"
• Put the Heating System sensor approximately 10' feet past the last boiler on
the common supply header but before any major takeoffs.
• The sensor must be located where it sees the output of all the boiler stages. If
a boiler is piped so that the sensor does not see its output, the BMC will not
sequence the boilers correctly.
• Only use a Standard Brass Tube sensor (389-900-230).
• The sensor wires can be extended up to 500' using a shielded 2-conductor
cable (Belden #8760 or equivalent). Do not ground the shield at the sensor
but at the panel using one of the terminals marked with an “O”.
• Do not run sensor wires in conduit with line voltage wiring.
IMMERSION HEATING SYSTEM SENSOR (HSS) INSTALLATION
• Install a 3/8"ID 1/2"NPT immersion well (592-300-023 or equivalent).
• Insert the sensor probe of the supplied sensor into the well.
STRAP-ON HEATING SYSTEM SENSOR (HSS) INSTALLATION
• Strap the sensor to the pipe using metal clamps. Do not over tighten the
clamp.
• Strap pipe insulation around the sensor and pipe.
Immersion Heating System Sensor
Immersion Well
3/8" ID 1/2" NPT
Shield
Heating System
Sensor
Strap-On Heating System Sensor
Common Supply Pipe
Pipe Insulation
Shield
Common Supply Pipe
Sensor Probe
Sensor Probe
ALERT
If the HSS can not sense the correct
heating system water temperature being
supplied to the building, the BMC will not
provide comfortable heat levels. Be sure
the HSS is located on a main supply pipe
which can not easily be isolated from the
system.
OUTDOOR SENSOR INSTALLATION
• Only use the Weil McLain sensor included with the unit (389-900-229).
• Locate the sensor in the shade on the north side of the building. The sensor
should never be in direct sunlight.
• Be sure the location is away from doors, windows, exhaust fans, vents, or
other possible heat sources.
• The sensor should be mounted approximately 10' feet above ground level.
• Adhere the Outdoor Label provided to the back of the sensor base.
• Use the Enclosure Base bottom knockout for the conduit. Use the locknut to
hold the conduit and enclosure base together. Screw the cover to the base.
• If screws are used to affix the enclosure to the wall, make sure to seal around
the sensor and wall except from the bottom.
• The sensor wires can be extended up to 500' using shielded 2-conductor cable
(#18/2). Do not ground the shield at the sensor but at the control using the
terminal marked with an “O”.
• Do not run sensor wires in conduit with line voltage wiring.
Seal around
sensor and wall
Mounting
Outdoor Sensor
screws
location
Outdoor
drip-hole
Outdoor
Sensor
snap-in
location
Shield
not connected
Outdoor Label
on back of Sensor
Conduit
WARNING
The BMC is an operating control only. All boilers must have all
safety and limit controls required by code. It is the responsibility
of the installer to verify that all the safety and limits are working
properly before the BMC is installed.
ALERT
Determining the proper location for the Outdoor Sensor is very important. The BMC will base the heat on the
outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice,
its reading will be different from the actual Outdoor temperature (OD).
8
BMC and BMC-6X Installation and Operation Manual
e
O
W
9
R
WIRING
WIRING THE POWER (TERMINALS 1, 2)
• Bring the 120VAC 60Hz power wires through the bottom Knockout of the enclosure.
• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
• Connect the hot line to terminal marked L.
• Connect the neutral line to the terminal marked N.
• Weil McLain recommends installing a surge suppressor on the power source to the BMC.
WARNING
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Weil McLain recommends installing a surge suppressor on the power source to the BMC.
WARNING
Connect the shield at the control terminal end and cut the shield wire at the sensor end.
WIRING THE SENSORS
SYSTEM SENSOR WIRING (TERMINALS 27, 28)
• A BMC must be connected to a temperature sensor located in the common header.
• The BMC is designed to be connected to a 389-900-230 temperature sensor for immersion in a 3/8ID
well (592-300-023 or equivalent). Contact the factory for additional temperature sensor options.
• Temperature sensor wires can be extended up to 500’ by splicing shielded
2-conductor cable (Belden #8760 or equivalent (#18/2)).
• Temperature sensors have no polarity. Connect the two wires from the
sensor to the BMC terminals marked SYSTEM TEMP 27, 28.
• Connect the sensor shield to the circled terminal 28 with one of the sensor wires.
OUTDOOR SENSOR WIRING (TERMINALS 25, 26)
• When Outdoor Reset is selected, the BMC will vary the system Set Point based on outdoor temperature.
• Whether in Set Point or Outdoor Reset modes, the outdoor sensor can be used as an Outdoor Cutoff. The BMC
will disable all boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature. This
feature will automatically be activated when an outdoor sensor is connected.
• For an outdoor sensor use a Weil McLain outdoor sensor (389-900-229).
• The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent
(#18/2)).
• Temperature sensors have no polarity. Connect the wires from the outdoor sensor to the BMC terminals marked
OUTDOOR TEMP - 25, 26.
• Connect the shield to the circled terminal 26 with one of the sensor wires.
PWR
L
1
120VAC
Power Sourc
SYSTEM
OUTDOOR
TEMP
TEMP
T
T
O
26
25
27
OUTDOOR
TEMP
T
O
26
25
27
Outdoor Sensor
N
2
Line
Neutral
PR
/DH
O
28
29
Sensor Shiled
System Sensor
SYSTEM
P
TEMP
/D
T
O
28
2
Sensor Shiled
SHUTDOWN
M
WIRING THE SHUTDOWN, TSTAT, OR SETBACK (TERMINALS 31, 32)
• The Shutdown will be available when selected as the Shutdown/Tstat/Setback mode from the Startup menu. See
page 15. This will provide the user with a customizable Day/Night Schedule. See page 21.
PROVE
/SETBACK
P
/DHW
O
O
8
O
30
32
29
31
• The Shutdown feature can be used whenever it is desirable to turn off the BMC stage outputs from a remote
location or another controller (i.e. EMS input).
• The Tstat option, when selected from the Shutdown/Tstat/Setback startup menu, provide the capability of
controlling the operation of the BMC based on a thermostat input.
• The thermostat will provide the BMC with a call for heat by shorting terminals 31 and 32.
• When the Shutdown input is enabled by closing the dry contact, or when the Tstat input is disabled by opening
the dry-contact, all active boilers will immediately modulate down to low for the Soft-Off period, then turn off.
Shutdown,
T-Stat, or
Setback Signal
• The System Output relay will remain active until the System Delay is over and then it will turn off.
• When Setback is selected in the Startup, a BMS/EMS or external clock can provide a Setback signal using these input terminals.
• The signal must be a dry contact only. No voltage can be placed across the SHUTDOWN/TSTAT/SETBACK terminals.
• Bring the two wires from the dry contact to the terminals marked SHUTDOWN/TSTAT/SETBACK- 31,32.
9
BMC and BMC-6X Installation and Operation Manual
2
W
K
O
W
K
1
WIRING THE PROVE (TERMINALS 29, 30)
• The Prove feature is provided to check system component operation and must be selected in the Startup Menu.
See page 15.
• A typical use of this feature is to check for pump flow before firing any boiler.
• If the PROVE input is open on a call, the BMC will enable only the System Output. All boiler outputs will be
off when the PROVE input is open.
• A factory-installed jumper provides the System Prove signal. Do not remove the jumper unless it will be
replaced by a System Prove signal or use the terminals for DHW call.
• Bring the two wires from the dry contact to the terminals marked PROVE - 29, 30. No voltage can be placed
across the PROVE terminals
WARNING
The PROVE input cannot be used as a safety limit. All equipment must have its own
certified limit and safety controls as required by local codes. If Prove is selected in the
startup menu, no boiler stage will start unless Prove terminals are shorted. DO NOT
remove the PROVE jumper supplied unless replacing it with a Prove signal.
WIRING THE DOMESTIC HOT WATER CALL DHW (TERMINALS 29, 30)
• DHW can be used to raise system Set Point to 200°F or Maximum Water temperature, whichever is lower.
DHW with or without Priority must be selected in the Startup Menu. See page 15.
• DHW Call terminals are dry contact N.O. terminals.
• Wire an aquastat or other controls to provide closure on the DHW Call terminals.
• Remove the jumper on the DHW terminals for proper operation.
OOR
MP
26
DOOR
MP
O
O
26
SYSTEM
TEMP
T
27
SYSTEM
TEMP
T
27
28
28
PROVE
/DHW
O
O
30
29
Prove Signal
PROVE
/DHW
O
O
29
DHW Signal
SHUTDO
/SETBAC
31
SHUTDO
/SETBAC
31
O
3
3230
WIRING THE SYSTEM OUTPUT (TERMINALS 3, 4)
System Output Operation in Set Point Mode
• The SYS output relay will energize when the outdoor temperature drops below the Outdoor Cutoff or whenever
a boiler output is active. If no outdoor sensor is connected and the last boiler relay has de-energized, the SYS
relay will remain energized for a period set by the System Run-On. See page 20.
• No boilers will be activated until the prove input is shorted. If a Prove is not required, the factory-installed
jumper should remain connected.
• A typical use of the SYS output is to activate a system pump starter. The pump can run whenever there is a call
for heat. When heat is no longer required, the pump will stay active for an adjustable Pump Run-On delay.
System Output Operation in Reset Mode
• The SYS output relay will energize whenever the outdoor temperature is below the Outdoor Cutoff.
• The SYS will remain constantly energized while the outdoor temperature is below the Outdoor Cutoff.
• When the outdoor temperature rises 2°F above the Outdoor Cutoff, the SYS output will remain energized for
the period set by the System Run-On. See page 20.
• The SYS output has one Normally Open (N.O.) relay contact rated for (1/8HP).
• The N.O. contacts are dry contacts only. They do not source any voltage.
• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
• Each N.O. contact is capable of switching 6A resistive at 120VAC.
WIRING THE BOILERS
WIRING THE BOILER OUTPUTS (A TERMINALS 5, 6), (B TERMINALS 7, 8), ...
• Each boiler output (A through D) has one Normally Open (N.O.) relay contact.
• The N.O. contacts are dry contacts only. They do not source any voltage.
• Each N.O. contact is capable of switching 1Amp inductive (1/8HP), or 6A resistive at 120VAC.
• Total output of all boilers, including the SYS, must not exceed 15A.
• Wire the N.O. relay contacts in series with the unit’s limit circuit.
• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
• Note that some boilers may not require the use of these outputs.
SYS
3
L
N
System Pump
or Pump Starter
B
A
5
678
Boiler
Boiler Enable
Output
A
5
6
4
C
9
10
1
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.