Weil-McLain 550-141-850-0599 User Manual

GOLDGOLD
GOLD
GOLDGOLD
Water boiler — Series 3
Boiler manual
GVGV
GV
GVGV
• Installation
• Maintenance Parts
This manual must only be used by a qualified heating installer/ service technician. Failure to comply could result in severe personal
injury, death or substantial property damage.
Part No. 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
How it works . . .
Control module
The GCM control module responds to signals from the room thermostat, air pressure switch, inlet water sensor and boiler limit circuit to operate the circulators, gas valve, igniter and blower. When a room thermostat calls for heat, the GCM starts the system circulator and blower.
The GCM runs the blower long enough to purge the boiler flue passages, then turns on the igniter and lets it warm up.
After a 15-second warmup, the GCM opens the gas valve, turns the igniter off, and checks for flame. The flame must come on within 4 seconds or the GCM will shut down and try the full cycle again.
When the room thermostat is satisfied, the GCM turns off the boiler components and waits for the next heat call.
The GCM indicator lights show normal sequence when the lights are on steady. When a problem occurs, the GCM flashes combinations of lights which indicate the most likely reason for the problem.
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Blower
The blower pulls in air and mixes it with gas from the gas valve. The blower forces this mixture into the burner for combustion inside the boiler chamber.
Air pressure switch
The air pressure switch signals the control module, telling the control module whether air is moving through the blower.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting. (The circulators will continue to run as long as there is a call for heat.)
System circulator
The system circulator circulates water through the external (system) piping. The flow rate of the circulator is controlled by the GCM, depending on the temperature of the water entering the boiler sections.
Bypass circulator
The GCM operates the bypass circulator to mix hot water from the boiler outlet with colder return water from the system as needed to prevent condensation of flue gases in the boiler.
When the water returning to the boiler is below 130 °F, the GCM regulates the bypass circulator and system circulator flow rates to raise the return water temperature up to 130 °F before it enters the boiler sections. By balancing these flow rates, the GCM can protect against condensation even if return water is as low as 60 °F.
Water temperature sensor
The water temperature sensor monitors the temperature of the water entering the boiler sections. The sensor sends this information to the GCM. The GCM determines how much to adjust the circulator flow rates to provide at least 130 °F entering water.
Part number 550-141-850/06992
Ž Installation • Start-Up • Parts • Maintenance
GOLD GV Water boiler Series 3
a
supply to system
b
return from system
c
combustio n a ir in le t fittin g
d
flue outlet
e
gas valve (see warning, right)
f
pressure/temperature gauge
g
flueway inspection port cover
h
sensor hose trap
i
manual air vent
j relief valve
85001
Thisboilerusesa
regulated
gasvalve,setforanoutlet
pressure approximately w.c..
set the outlet pressure higher than
NOT
negative-pressure-
–0.20" DO
factory setting.
3Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Please read before proceeding
Hazard definitions
Installer
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
Read all instructions before installing. Follow all
instructions in proper order to prevent personal injury or death.
Also refer to GV Series 3 Venting supplements.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed
immediately against the transportation company by the consignee.
User
This manual is for use only by your qualified heating installer/
service technician
Please refer to the User’s information manual for your reference.
We recommend regular service by a qualifed service technician,
at least annually
.
.
Table of contents See pages 6 and 7 for Table of contents.
Part number 550-141-850/06994
Installation Start-Up Parts Maintenance
Please read before proceeding
Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.
When servicing boiler —
To avoid electric shock, disconnect electrical supply before
performing maintenance.
To avoid severe burns, allow boiler to cool before performing
maintenance.
Boiler operation —
Do not block flow of combustion or ventilation air to boiler.
Should overheating occur or gas supply fail to shut off, do not
turn off or disconnect electrical supply to pump. Instead, shut off the
gas supply
Do not use this boiler if any part has been under water.
Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control, which has been under water.
at a location external to the appliance.
Boiler water —
DO NOT use petroleum-based cleaning or sealing compounds in
boiler system. Water seal deterioration will occur, causing leakage between sections. This can result in substantial property damage.
DO NOT use "homemade cures" or "boiler patent medicines".
Serious damage to boiler, personnel and/or property may result.
Continual fresh makeup water will reduce boiler life. Mineral
build-up in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.
Do not add cold water to hot boiler. Thermal shock can cause
sections to crack.
5Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Contents
Contents Summary Pages
I. Prepare boiler location • Verify code compliance.
Check for high altitude requirements. Provide required clearances and accessibility. Plan vent and combustion air provisions. Check existing common v ents to be sure the y will work when
old boiler is removed from system.
II. Prepare boiler Leave boiler on its skid until preparation complete.
Install vent starter tee. Inspect/replace if necessary the gas/air orifice. Install high altitude kit (over 5,500 feet). Place boiler in position. Hydrostatically test boiler.
III. Water piping Select system type from navigation table on page 26, cover-
ing baseboard systems, radiator systems, radiant heating systems, heat pump systems, snow melt systems and water chiller systems.
Review boiler connections pages 28 – 29, including instal- lation of air separator and expansion tank.
Review general system information, page 30. Obtain any system components needed but not on hand at
the job site. Install relief valve and discharge piping. Connect system piping. Install low water cutoff and additional limit control, if
required.
8 – 15
16 – 25
26 – 36
IV. Venting and combustion air Refer to Vent supplements included with boiler 37
V. Gas piping Connecting gas supply, including need for pipe supports.
Natural gas boilers — gas line sizing (for 0.3" w.c. drop). Propane boilers — refer to gas supplier.
VI. Field wiring Code compliances.
Wiring must be N.E.C. Class 1. Thermostat connections. Junction box installation. Field wiring diagram.
Part number 550-141-850/06996
38 – 39
40 – 41
Installation Start-Up Parts Maintenance
Contents
Contents Summary Pages
VII.Start-up • Determine water treatment needs, if any.
Obtain correct antifreeze if freeze protection required. Check for gas leaks (ha ve propane odorant verified by supplier). Fill system and purge air. Read Operating instructions, section IX, then start boiler. Check all piping and verify leak-free. Check gas valve outlet pressure (altitudes over 5,500 feet).
VIII.Check-out procedure Complete checklist and fill out certificate. 48 – 49
IX. Operation GCM (control module) indicator lights and sequence of opera-
tion. Ladder wiring diagram (page 52). Schematic wiring diagram (page 53). Lighting instruction sheet boiler with Robertshaw 7200DERN
gas valve (page 54). Lighting instruction sheet boiler with White-Rodgers 36E gas
valve (page 55).
X. Service and maintenance Service/maintenance schedule table (page 57).
Detailed instructions for annual start-up and service. Special procedures for condensate drain line check v alve (page
63, if needed) and cleaning boiler heating surfaces (page 64).
42 – 47
50 – 55
56 – 65
XI.Troubleshooting Troubleshooting procedures (page 67).
Checking air pressure switch (page 68). Servicing tips and precautions Igniter, gas valve and blower
housing (page 69). Servicing tips and precautions plus indicator lights and lockout
modes of GCM (control module) (page 70). Common problems and solutions (pages 72 and 73). Troubleshooting based on GCM indicator lights (pages 74 – 81).
XII. Replacement parts Accessory bag assembly shipped with boiler (page 83).
Section assembly parts (page 84). Jacket assembly parts (page 86). Blower assembly parts (page 88). Trim assembly parts (page 90). Interior panel parts (page 92).
XIII.Dimensions and ratings Dimensional drawing and boiler rating table. 94 – 95
66 – 81
82 – 93
7Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Ia
Prepare boiler location overview
Overview of this section
Verify the boiler installation will meet all applicable codes.
If the boiler installation is at high altitude (over 5,500 feet) make sure to
obtain and install the high altitude kit. Obtain the high altitude kit and review the instructions included. Note the venting restrictions and input reductions at altitudes over 5,500 feet.
Check the boiler space to be sure minimum clearances and accessibility
are available.
Obtain special venting materials and make sure vent will comply with
instructions.
Direct vent installation (outside air piped to boiler) is optional in most
cases. But, if air contamination is likely, you will have to pipe air to the
boiler
. Note list of contaminants on page 13.
If the GV boiler is replacing a boiler being removed from a combined vent
system
manual to verify vent performance.
that will still serve other appliances, follow the procedure in this
Part number 550-141-850/06998
Installation Start-Up Parts Maintenance
Prepare boiler location — codes & altitudeIb
Installations must
follow these codes:
High altitude
installations
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1- latest edition.
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1,
when required.
National Electrical Code.
For Canada only: CAN/CGA B149.1 or B149.2 Installation Code and C.S.A. C22.1 Canadian
Electrical Code Part 1 and any local codes.
The GV boiler gas manifold and controls met safe lighting and other performance criteria when boiler underwent tests specified in ANSI Z21.13 latest edition.
GV boiler controls automatically reduce input with increasing altitude. See Table 1 for estimated input at altitude as a percentage of sea level input. Multiply the boiler sea level input by this percentage to obtain the estimated high altitude input. Note that the length of the venting system will also have a minor impact on input. Refer to the vent supplement for further information.
No modifications to the boiler should be necessary for installations up to 5,500 feet above sea level. For higher elevations, the air pressure switch must be changed to a special high altitude switch. Refer to the high altitude kit instructions, manual Section IId. Note that the gas valve outlet pressure must be checked (and adjusted if necessary) in accordance with manual Section
VIIf.
Table 1
Estimated GV input at altitude
At altitudes above 5,500 feet, GV boilers can be sidewall vented only when using direct vent (ducted combustion air). GV boilers can be vertically vented in any of the configurations shown in the vent supplements. Refer to vent supplements for more detail.
Altitude
(feet)
1,000 97 2,000 93 3,000 90 4,000 87 5,000 83 5,500 82 6,000 80 7,000 77 8,000 74 9,000 72
10,000 69
% Sea level input
9Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Ic
Prepare boiler location clearances
Clearance options:
Large space
The boiler space must be at least as big as shown in Figure 1 to qualify as a
Air openings to a large space can be per manual
Ie.
Section
The space will probably be large enough for most service and maintenance to be done in place.
Small space
You can install the boiler in a space smaller than Figure 1, but no smaller than shown in Figure 2 this is called a
small space installation.
Air openings to a small space must provide at least 1 square inch free area for every 1,000 Btuh of boiler input (at least 75 sq. in. for GV-3, 105 sq. in. for GV-
4, 140 sq. in. for GV-5 or 175 sq. in. for GV-6). The air opening free area must be at least this size even if the boiler uses outside air.
Air openings have to be within 6 inches of the floor and 6 inches of the ceiling of the space to prevent overheating of boiler internal components.
Provide at least screwdriver clearance to jacket front panel screws for removal of front panel for inspection and minor service.
The boiler cannot be serviced in place. Pipe the boiler with unions and isolation valves so it can be slid out of the space and serviced in an adjacent area. The space has to be equipped with a door so boiler can be accessed, unpiped and removed.
No other appliance or air handler can be installed in the same space or share its air supply.
large space.
Install the boiler so control system components are protected from
dripping or spraying water or rain
during operation. Allowing these components to become wet could cause a boiler failure, resulting in severe personal injury, death or substantial property damage.
Figure 1
Large space — minimum clearances between boiler and walls or obstructions as below; see Section Ie for minimum combustion/ventilation air opening sizing.
TOP VIEW
Wal l
36"
Wal l
min
Wall or obstruction
FRONT VIEW
Ceiling
Wal l
36"
min
Floor
min
Boiler
front
36"
min
36"
min
Boiler
front
6"
6"
min
Wal l
85006a
Wal l
6"
min
Part number 550-141-850/069910
Installation Start-Up Parts Maintenance
Figure 2
Small space — installation with less clearance than Figure 1 – BUT – no less than below; air
openings for combustion/ventilation must be as shown below even for direct vent system.
TOP VIEW
Wal l
Access
DOOR
with fresh air
openings
4"
min
Wal l
Area adjacent to access door must be accessible and must allow for removal of the GV boiler for service.
No other appliance or air mover (exhaust fan, etc.) may be mounted in the same space.
10"
min
Boiler
top
Front
1" min
1"
min
Flooring and foundation
Flooring
The GV boiler is approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
Foundation
Provide a solid brick or minimum 2-inch thick concrete
Wal l
foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
high profile condensate pump is used.
(Foundation thickness will depend on height of condensate pump inlet.) Refer to separate Weil-McLain supplement for details.
The minimum foundation size is 16" wide by:
30¾" long for GV-3 or GV-4.
37¾" long for GV-5 or GV-6.
SIDE VIEW
Ceiling
6" max
6" max
(2) Fresh air openings
Each with at least 1 sq. inch per 1,000 Btuh of boiler input
Access door
4"
min
Floor
85006b
1"
min
Boiler
side
Front
1"
min
Residential garage installation
Precautions
Wal l
Take the following special precautions when installing the boiler in a residential garage. If the boiler is located in a residential garage, per ANSI Z223.1, paragraph 5.1.9:
Mount the boiler a minimum of 18 inches
above the floor
of the garage to assure the burner and ignition devices will be no less than 18 inches above the floor.
Locate or protect the boiler so it cannot be
damaged by a moving vehicle.
11Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Id
Prepare boiler location vent system
Removing from existing vent
Failure to follow all instructions following can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
When removing a boiler from an existing common vent system:
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common
venting system.
b. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
c. Test vent system Insofar as is practical, close
all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
Any improper operation of common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 latest edition.
Correct by resizing to approach the minimum size as determined using the appropriate tables in Part 11 of that code. Canadian installations must comply with CAN/ CGA B149.1 or B149.2 Installation Code.
GV special vent system
Vent system
The GV boiler requires a special vent system, designed for pressurized venting with likelihood of condensation in the vent. This is referred to as ANSI Z21 Class IV,
Condensing
You may use any of the vent systems covered by the GV venting supplements included in the instruction manual envelope. The GV vent starter tee is a special item designed only for the GV boiler, available from each vendor. Do not attempt to connect the vent to the GV boiler with any other means.
Vent termination and combustion air supply
The GV boiler may be vented through the roof or through a side wall. Follow the appropriate vent supplement for the vent system chosen. The maximum vent length depends on boiler size. Refer to the vent supplement to verify vent length will be acceptable.
Combustion air for the GV boiler may be from inside or ducted directly to the boiler from outside. For outside air (direct vent installation), two options are available for the flue/air termination. The air supply must ALWAYS terminate at the same location as the flue, using either:
1. Vertical direct vent installation. Obtain the Through-
roof or through-unused chimney kit and
supplement. Find additional information in the vent supplement for the venting material chosen.
2. Sidewall vent/air termination. This requires the Weil-
McLain GV vent/air intake termination kit. Refer to the instructions packed with the kit and the vent supplement for the venting material chosen.
Installations above 5,500 feet altitude must be direct vent if sidewall vented.
.
DO NOT mix components from
different systems. The vent system could fail, causing leakage of flue products into the living space, causing severe personal injury or death.
Part number 550-141-850/069912
Installation Start-Up Parts Maintenance
Ie
Prepare boiler location contamination
Air contamination
Please review the following information on potential combustion air contamination problems.
If the boiler is installed in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must pipe combustion air to the boiler air intake. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death or substantial property damage. Do not install GV boiler in a
room or pool facility, for example
contain contaminants.
Table 2 Corrosive contaminants
Products to avoid Areas likely to have contaminants
Spray cans containing chloro/fluorocarbons Dry cleaning/laundry areas and establishments
Permanent wave solutions Swimming pools
Refer to Table 2 for products and areas which may cause contaminated combustion air.
, without using ducted outside air. These areas will always
laundry
Chlorinated waxes/cleaners Metal fabrication plants
Chlorine-based swimming pool chemicals Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water softening Photo processing plants
Refrigerant leaks Auto body shops
Paint or varnish removers Plastic manufacturing plants
Hydrochloric acid/muriatic acid Furniture refinishing areas and establishments
Cements and glues New building construction
Antistatic fabric softeners used in clothes dryers Remodeling areas
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and other similar products
13Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
If
Prepare boiler location air openings
GV combustion air options
Using inside air — non-direct vent
The GV boiler can use inside air if no contaminants are present in the boiler space.
Using outside air — direct vent
Combustion air can be ducted directly from outside to the GV boiler air intake fitting. The installation is defined as direct vent (also referred to as sealed combustion).
Sizing air openings
Air openings to the GV boiler space are always required, regardless whether combustion air is taken from inside or outside. These air openings provide for ventilation (as
well as combustion air) to prevent overheating of the boiler controls and boiler space. Air is also needed for other appliances located in the same space.
Use Figure 3, cases a through d, depending on how the air is supplied and whether the space contains only the GV or other appliances as well. The air opening sizing of Figure 3 is based on ANSI Z223.1, National Fuel Gas Code, intended for natural draft appliances. The GV boiler is not natural draft, so its requirements differ.
Single air opening option
A single air opening within 12 inches of the ceiling may be used where the GV boiler is installed in a large space (clearances per Figure 1) with other appliances.
The other appliances must all be installed with at least 1 inch clearance from the sides and back, and 6 inches from the front. The GV boiler must have minimum clearances as shown in Figure 1.
The single air opening may be connected from outside to the appliance space by any of the methods of Figure 3.
The free area of the opening must also be at least equal to the combined area of all appliance vent connectors OR sized per the following, whichever result is larger:
GV direct vent large shared space single air opening
Size the single air opening for 1 square inch of free opening for each 3,000 Btuh of all appliances other than the GV. No additional air opening is needed for the GV.
GV inside air large shared space single air opening
Size the air opening for 1 square inch of free opening for each 3,000 Btuh of all appliances, including the GV.
Air openings must be sized to handle all appliances and air movers (exhaust fans, etc.) using the air supply.
Louver allowance
The free area of openings means the area after reduction for any installed louvers or grilles. Be sure to consider this reduction when sizing the air openings.
GV with other appliances
If the GV boiler is installed in a large space (clearances per Figure 1) providing air for a water heater or other gas appliance, size the air openings as follows:
GV direct vent large shared space
Provide two openings per Figure 3, based only on the size of the other appliances and air movers. No additional air opening area is required for the GV boiler.
GV inside air large shared space
If the GV combustion air comes from the inside space, size two air openings for the total of all appliances and air movers, including the GV boiler. Use the formula from the appropriate case in Figure 3.
GV without other appliances
If the GV boiler is installed in a space by itself, with no other appliance or air mover using air from the space, and with clearances around the boiler no less than those shown in Figure 1 for large space installations:
GV direct vent large space alone
Air is needed only for ventilation. Size the air openings for any of the cases of Figure 3 for a free area of at least:
1 square inch per 8,000 Btuh of GV input
for each of the two openings. (If a single opening within 12 inches of the ceiling is used, size the opening for 1 square inch of free area for each 3,000 Btuh of GV input.)
GV inside air large space alone
Size the air openings for any of the cases of Figure 3 for a free area of at least:
1 square inch per 4,000 Btuh of GV input
for each of the two openings. (If a single opening within 12 inches of the ceiling is used, size the opening for 1 square inch of free area for each 3,000 Btuh of GV input.)
Part number 550-141-850/069914
Installation Start-Up Parts Maintenance
Air
Air
Air
Air
opening
Add air openings
to outside if
building is tight
construction.
Air
opening
Air
opening
Air
opening
Air (direct vent)
(optional)
Air (direct vent)
(optional)
Air (direct vent)
(optional)
0 to 12"
0 to 12"
12"
0 to 12"
0 to 12"
Flue
Flue
Flue
Other
appliances
Other
appliances
Other
appliances
Other
appliances
GV
GV
Air
Air (direct vent)
(optional)
Flue
GV
GV
Outside
Outside or ventilated attic
Air
opening
Air
opening
0 to 12"
0 to 12"
Outside
Ventilated
crawl space
or
a
d
b
c
Each opening free area = 1 sq. inch per 4,000 Btuh
Each opening free area = 1 sq. inch per 2,000 Btuh
Each opening free area = 1 sq. inch per 1,000 Btuh
Each opening free area = 1 sq. inch per 4,000 Btuh
85005
GV in small space (less than Fig. 1) alone
For all vent/air situations, whether air is taken from inside or outside, provide two openings, each with minimum free area of:
1 square inch per 1,000 Btuh of GV input.
The openings must be within 6 inches of the ceiling and 6 inches of the floor as shown in Figure 2 for small space installations.
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction where: a. Walls and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of 1 perm or less with openings gasketed, and . . .
b. Weatherstripping has been added on openable windows and doors, and
. . .
c. Caulking or sealants are applied to areas such as joints around windows
and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and in other openings.
For buildings with such construction, provide air openings into the building from outside, sized per the appropriate case in Figure 3 if appliances are to
use inside air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative pressure, even if the appliance(s) are installed as direct vent. Always provide air openings sized not only to the dimensions required for the firing rate of all appliances, but also to handle the air movement rate of the exhaust fans or air movers using air from the building or space.
Motorized air dampers
If the air openings are fitted with motorized dampers, electrically interlock the damper to:
Prevent the boiler from firing if the damper is not fully open.
Shut the boiler down should the damper close during boiler operation.
To accomplish this interlock, wire an isolated contact (proving the damper open) in series with the thermostat input to the boiler. The boiler will not start if this contact is open, and will shut down should it open during operation.
Figure 3
Air openings:
GV in space with other appliances
a
Air from inside building
b
Air directly from outside
c
Air through vertical ducts (or inlet air from ventilated crawl space)
d
Air through horizontal ducts
15Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IIa
Overview of this
section
Prepare boiler vent starter tee & drainIIb
Prepare boiler overview
Leave the boiler on its skid until installation site is ready and boiler prep is
complete per this section.
Install vent starter tee and condensate drain line.Inspect gas/air orifice plate to verify model size and gas markings agree
with boiler and application. Install propane gas/air orifice for propane installations.
Install high altitude kit for altitudes more than 5500 feet above sea level.Place boiler in position and install jacket rear panel.Plug openings and hydrostatically test boiler. Remove plugs.
Install vent starter
tee and condensate
drain hose
Use only the vent starter tee of the same manufacturer as the
vent components
systems. The vent system could fail, causing flue gas spillage, resulting in severe personal injury or death.
Install vent starter tee as shown in Figure 4.
1. Remove jacket access panel (item 1). You can rotate the plate out of the way, leaving the air hose connected to the air intake fitting, or loosen the hose clamp (item 2) and pull the air hose off of the fitting as shown in Figure 4.
2. Remove the hex nuts (item 5) from the vent starter tee studs at the boiler vent connection.
3. Remove the vent starter tee gasket (item 4) from the studs.
4. Clean the surface of the boiler flue connection to assure a good seal. Use emery cloth if necessary to remove any accumulated rust.
5. Place the vent starter tee gasket (item 4) over the studs.
6. Slide the holes in the vent starter tee flange (item 3) over the studs.
7. Apply the (4) hex nuts (item 5), align the vent starter tee (item 3) and tighten the nuts uniformly.
Install condensate trap hose as shown in Figure 4.
1. Loosen and slide a spring hose clamp (item 8) over each end of the condensate drain hose (item 6).
2. Loosen the clamp and slide one end of the hose over the CPVC drain elbow (item 7). Slide clamp into position and release.
3. Attach and clamp the other end of the hose to the drain connection on the bottom of the vent starter tee (item 3).
to be used. Do not mix components from different
Replace jacket access panel (item 1), reconnecting the air hose to the air intake fitting if necessary.
Part number 550-141-850/069916
Installation Start-Up Parts Maintenance
IIb
Figure 4 Install vent starter tee and
Prepare boiler vent starter tee & drain (cont.)
condensate drain hose before placing boiler.
Screw hole
and notch, located
in base rail under
vent outlet
Base rail
Insert CPVC elbow into bracket. Then attach bracket to base rail with screw as shown at left.
10-32 x 3/8"
85002
Vent starter tee — not included with boiler. See information below.
The vent starter tee is NOT supplied with the boiler. Obtain this part as a separate purchase from your Weil-McLain wholesaler.
The vent starter tee shown is for Saf-TVent®. Use only the vent tee made for the vent system you are using. DO NOT mix different brands of vent system components. The vent system could fail to operate properly, causing leakage of flue products into the living space, resulting in severe personal injury or death.
17Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IIc
Check for correct
orifice plate and
replace if necessary
Prepare boiler orifice plate
The correct orifice plate must be used. Failure to do so will result in severe personal injury, death or substantial property damage.
Natural gas:
For natural gas installations, inspect the silver gas/air orifice plate marking. It must be the same as the boiler size. If the orifice plate is stamped with another size, obtain the correct plate from your wholesaler. The boiler size is stamped where the “X” is shown in the plate stamping, Figure 5b.
Propane:Propane:
Propane:
Propane:Propane:
For propane installations, replace the silver gas/air orifice plate with the red/white
, per following instructions. Ensure the red/white plate boiler size is correct for the GV
plate
boiler being installed. The boiler size is stamped where the “X” is shown in the plate stamping, Figure 5b.
Also fill out the propane label in the conversion kit and attach to the left side of the jacket, above the gas inlet opening, as shown in Figure 5a.
Plate installation
Access the bottom of the blower housing as shown in Figure 5a.
To inspect the plate only, read the marking on the plate edge. It must read the same as the boiler size and fuel.
Figure 5a
Check for correct orifice plate
and replace if necessary.
Leave boiler on its back, on
the skid, until inspection/
replacement is completed.
To replace the plate, using a manual screwdriver or nut driver, see Figure 5b:
1. Loosen screws 1 and 2 two full turns.
2. Remove screws 3 and 4.
3. Pull the gas/air orifice plate forward to remove it.
4. Slide in the new plate as shown in Figure 5b. The red side of a propane plate must go
next to the blower housing
5. Replace screws 3 and 4. Tighten all four screws securely and uniformly. DO NOT overtighten.
DO NOT exceed 40 inch-pounds torque.
6. Bend down plate label tab at score mark as shown in lower right corner of Figure 5b.
as shown.
Remove jacket front panel to access the bottom side of theblowerhousing.
Complete the propane conversion label included with the conversion kit. Install label on jacket left side, as shown.
85004a
Leave the boiler on its back, on the skid as shown, until you have checked the gas/air orifice plate and replaceitif necessary.
Part number 550-141-850/069918
Installation Start-Up Parts Maintenance
Bottom side of boiler front section
Figure 5b Checking and replacing gas/air orifice plate. For propane
installations, replace silver plate with red/white propane plate.
DO NOT use electric or pneumatic screwdrivers
remove or tighten the gas/air boss screws. Hand-tighten only, using manual screwdriver. Should the torque exceed 40 inch-pounds, the
threaded holes could strip out, causing
to
an inadequate seal of the orifice plate. Failure to properly seal the plate to the housing could result in a gas leak, causing severe personal injury, death or substantial property damage.
White side (propane plate)
Warning label side (natural gas)
(Install with this side
toward air inlet hose)
Gas/air manifold
Bottom side of boiler front section
GVX PROP
GVX PROP
GVX PROP
Propane red side Natural plain side Install plate with red side (propane) or plain side
(natural) .againstthe blower housing
GVX PROP
GVX PROP
GVX PROP
Orifice plate after bending along score mark. This makes the plate identification readable after installation.
85004b
19Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IId
Prepare boiler high altitude kit
When requiredWhen required
When required
Obtain high altitude
Install high altitude
air pressure switch
When requiredWhen required
kit
For installations at altitude more than 5,500 feet
above sea level
switch is required. In addition, the gas valve outlet pressure setting must be checked, and adjusted if necessary, per the instructions in manual Section VIIf,
altitude over 5,500 feet.
Obtain the GV high altitude kit from your local Weil­McLain distributor. This kit includes the high altitude air pressure switch and a special tool needed for accessing the adjusting screw on some gas valves. The kit also includes tubing fittings as described in manual.
1. See Figure 5c (switch shown with wires removed).
2. Remove the two (RED) control wires from the air pressure switch spade terminals.
, a special high altitude air pressure
Check gas valve
outlet pressure
3. Remove the factory-installed air pressure switch (loosen top screw and remove bottom screw holding switch to jacket interior panel).
4. Install the high altitude air pressure switch in the same location.
5. Carefully replace the hoses on the new switch, with the red hose on the hose barb closest to the interior panel, as shown in Figure 5c. The white hose goes on the outer hose barb.
6. Replace the two (RED) control wires on the new pressure switch spade terminals.
After following the start-up procedures of manual Section
VII, follow the procedures of Section VIIf to measure gas
valve outlet pressure and adjust if necessary.
Failure to check gas valve outlet pressure
necessary, could result in severe personal injury, death or substantial property damage. Carefully follow the guidelines given in this manual.
and adjust, if
Part number 550-141-850/069920
Installation Start-Up Parts Maintenance
altitudes above 5,500 feet ONLY
Figure 5c Air pressure switch mounting and sensor hoses
Jacket left side panel
White
hose
Red
hose
Interior panel
Boiler top
(2) 10-32 x 3/8" Phillips/hex screws
85052
21Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IIe
Prepare boiler place in position
Position boiler
After installing vent starter tee, inspecting (replacing if necessary) the gas/air orifice and installing the high altitude kit (if required), move the boiler near its position.
Figure 6 shows the boiler with the front and top panels replaced. These panels may be left off if desired until the installation has been completed.
Refer to Figure 6 for placement sequence:
Wearing heavy gloves, carefully rotate the boiler
over onto its base rail legs.
Clip the shipping strap securing the skid to the
boiler block assembly. Remove the skid and strap.
Attach the jacket rear panel as shown using (4)
#10 x ¾" screws provided in the accessory bag.
Boiler is heavy and contains some
sheet metal parts which may have
sharp edges. Wear gloves when
handling and take proper precautions when moving. Failure to do so will result in severe personal injury, death or substantial property damage.
Part number 550-141-850/069922
Installation Start-Up Parts Maintenance
Figure 6 Rotating boiler into position, removing skid and installing jacket rear panel
Carefully rotate boiler onto base rail legs as shown
ROTATE
ROTATE
Install jacket rear panel with (4) screws, #10 x 3/8"
Clip shipping strap
85003
23Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IIf
Prepare boiler pressure test
Perform hydrostatic pressure test
Pressure test boiler before attaching water or gas piping (except as noted below) or electrical supply.
Prepare boiler for test (Fig. 7)
Connect a hose from water supply to fill and drain
boiler for hydrostatic test. Hose is not included with boiler.
Connect hose to boiler drain valve. Make sure hose
can also be used to drain boiler after test.
Remove 1" nipple, 1" tee, bushing and pressure/
temperature gauge from accessory bag. Pipe to boiler supply connection as shown. Use pipe dope sparingly.
Connect a nipple and shutoff valve to system supply
connection on the 1" tee. This valve will be used to bleed air during the fill. Valve and nipple are not included with boiler.
Connect a nipple and shutoff valve to system return
connection at circulator flange. This valve will be used to bleed air during the fill. Valve and nipple are not included with boiler.
Install a ¾" pipe plug in the relief valve opening, top
of the rear boiler section, as shown. Plug is not included with boiler.
5. Slowly reopen drain valve (item 2) until test pressure of not more than 45 psi is reached on the pressure gauge.
6. Test at no more than 45 psi for no more than 10 minutes.
Do not leave boiler unattended.
A cold water fill could expand and cause excessive pressure, resulting in severe personal injury, death or substantial property damage.
7. Make sure constant gauge pressure has been maintained throughout test. Check for leaks. Repair if found.
Leaks must be repaired at once.
Failure to do so can damage boiler, resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing compounds in boiler system. Severe damage to boiler will occur, resulting in substantial property damage.
Drain and remove fittings
Fill and pressure test
1. Connect fill water supply through drain valve (item
2).
2. Fill boiler with water (be sure bleed valves at 4 and 5
are open).
3. When water flows from bleed valves, shut off water at drain valve.
4. Close bleed valves.
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever provides best access to drain. Close drain valve and remove hose after draining.
3. Remove nipples and valves at 4 and 5 unless they will remain for use in the system piping.
4. Remove plug (item 6) from relief valve tapping.
Part number 550-141-850/069924
Installation Start-Up Parts Maintenance
Figure 7 Piping connections for hydrostatic test
85007
To fill/drain
25Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
For heating system with . . . See pages 27 – 30 and . . .
Baseboard, finned tube or cast iron
31
Radiators, cast iron
32
Radiant floor, wall or ceiling
single zone
(note 1)
33
Radiant floor, wall or ceiling
multiple zones
34
Heat pump (note 1)
33
Snow melt plus space heating
35
Control valve (note 2)
34
Water chiller
36
Note 1: Install a temperature limit control in the supply piping to protect the system. Note 2: Apply these piping designs for outdoor reset or any system requiring automatic
supply temperature regulation.
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
Water piping overviewIIIa
Overview of this
section
Select suggested piping from the following table, based on the type of
system in which you are installing the GV boiler.
Review boiler connections, pages 28 – 29 information on supply and
return connections at boiler and key system components (air separator and expansion tank).
Review page 30, information applying to all systems.
Obtain any system components needed but not on hand or available at
jobsite.
Install boiler relief valve and pipe discharge to a safe location per guidelines
in this section.
Install system piping and boiler connections.
Install additional limit control (if required for code compliance) and low
water cutoff
if required.
Part number 550-141-850/069926
Installation Start-Up Parts Maintenance
IIIb
Install relief valve
Water piping relief valve
Refer to Figure 8 for location of the relief valve on the boiler.
Install the relief with the spindle vertical in the ¾" tapping on top left of the back section, as shown.
To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to relief valve outlet and run to a safe place of
disposal
should the valve discharge.
Discharge line must be as short as possible and be the same size as the
valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least 6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, and must be rigid metallic pipe of material suitable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler, or in
the discharge line. Do not plug or place any obstruction in the discharge line.
. Terminate the discharge line to eliminate possibility of severe burns
Figure 8
Install and pipe relief valve
Failure to comply with the above guidelines could result in failure of the
relief valve to operate, resulting in possibility of severe personal injury, death or substantial property damage.
Test the operation of the valve after filling and pressurizing system by
lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.
1 Jacket plug for unused relief valve jacket
opening.
2 Jackets are provided with two relief valve
openings because each jacket size is used for two boiler sizes. Cover the unused opening with the plug provided.
3 Boiler relief valve (from accessory bag)
4 ¾" x 3" nipple, provided in accessory bag
5 ¾" relief valve tapping in back section
6 Connect minimum ¾" discharge piping
to relief valve. See WARNING above.
85008
27Part number 550-141-850/0699
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
IIIc
Water piping boiler connections
Supply & return connections
Always connect supply and return connections to the boiler as shown in Figure 9. (Note in the following and in the suggested piping drawings in this manual that the expansion tank and air separator location will depend on the system piping.)
Air separator
Install an air separator in the piping as shown. For single-zone systems, install the air separator in the return piping as shown in Figure 9. This allows mounting the automatic air vent and expansion tank off of the separator.
Expansion tank
Figures 9 and 10 show typical installation of the expansion tank when the boiler is connected to a zone­valve zoned baseboard system (see Figure 10). Always locate the air separator and expansion tank as shown in the suggested piping drawings, Figures 10 through 16.
Ensure that the expansion tank size will handle boiler and system water volume and temperature. See tank manufacturers instructions and ratings for details. Additional tanks may be added to the system if needed to handle the expansion. These tanks may be installed by connecting to tees in the system piping.
Undersized expansion tanks
cause system water to be lost from the relief valve and makeup water to be added through the fill valve. Eventual section failure can result.
Always locate the cold water fill
connection
Never locate this elsewhere in the system.
Diaphragm- or bladder-type tank:
Refer to Figure 9 for suggested piping when using a diaphragm- or bladder-type expansion tank.
at the expansion tank.
Install an automatic air vent on top of the air separator, per separator manufacturers instructions.
Closed-type expansion tank:
Figure 10 shows suggested piping when using a closed­type expansion tank, in which the air is directly in contact with tank water.
Connect piping (½" or ¾") from the air separator top outlet to the tank fitting. Slope any horizontal piping a minimum of 1 inch per 5 feet of horizontal pipe.
Always use a tank fitting, such as the B&G Tanktrol or Ta co Taco-Trol (shown). The fitting reduces gravity flow of water in the piping to the tank, avoids air bubbling through the tank water, and provides the proper fill height in the tank.
Operating pressure of system, after temperature expansion above cold fill pressure, should not exceed 24 PSIG to avoid weeping of relief valve.
Correct all leaks in the system or
tank piping. Leaks allow air to escape from the system and will cause water­logging of the tank. This will result in water loss through the boiler relief valve due to over-pressurization.
NEVER use an automatic air vent in
a system equipped with a closed-type expansion tank. The air removed from the system will cause water­logging of the expansion tank.
Closed-type expansion tank
Follow tank manufacturer’s instructions for filling the tank. Typical tank sizing provides for approximately 12 PSIG when the tank is filled to the normal level and system water is cold. Note that boiler relief valve is set for 30 PSIG. Operating pressure of system, after temperature expansion above cold fill pressure, should not exceed 24 PSIG to avoid weeping of relief valve.
Diaphragm- or bladder-type expansion tank pressure
pressure. Always check pressure and charge tank with tank removed from system to be sure reading is accurate. Boiler relief valve is set for 30 PSIG.
with the tank air charge
Control fill
Backflow preventer
Where required by codes, install a backflow preventer in the cold water fill line, as shown in suggested piping diagrams on following pages. Install a check valve if a backflow preventer is not installed.
Part number 550-141-850/069928
Installation Start-Up Parts Maintenance
Figure 9 Piping to single-zone system using diaphragm- or bladder-type
expansion tank. Boiler connections are 1" NPT (supply from 1" tee, return to 1" system circulator flange).
1 Relief valve discharge piping see page 27 2 Boiler isolation valves 3 Fill valve 4 Air separator 5 Automatic air vent
6 Backflow preventer or check valve 7 System supply piping 8 System return piping 9 Diaphragm-type expansion tank
always locate as shown in the suggested piping drawings, Figures 10 through 16
Figure 10 Piping closed-
type expansion tank
To cold fill
To cold fill
Locate the air separator as shown in the suggested piping diagram, Figures 11 through 16 on the following pages. Pipe diaphragm- or bladder-type expansion tanks to the bottom of the separator.
85011
10 Pressure reducing valve 11 Quick-fill bypass valve 12 Closed-type expansion tank
always locate as shown in the suggested piping drawings, Figures 10 through 16
85010
13 Tank fitting
Pipe closed-type (air in contact with water) tanks to the top of the air separator. Always connect the fill line to the expansion tank location, as shown above and in the suggested piping.
29Part number 550-141-850/0699
Loading...
+ 67 hidden pages