This manual must only be used by a qualified heating installer/
service technician. Failure to comply could result in severe personal
injury, death or substantial property damage.
Part No. 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
How it works . . .
Control module
①
The GCM control module responds to signals from the room thermostat, air pressure switch, inlet
water sensor and boiler limit circuit to operate the circulators, gas valve, igniter and blower. When
a room thermostat calls for heat, the GCM starts the system circulator and blower.
The GCM runs the blower long enough to purge the boiler flue passages, then turns on the igniter
and lets it warm up.
After a 15-second warmup, the GCM opens the gas valve, turns the igniter off, and checks for
flame. The flame must come on within 4 seconds or the GCM will shut down and try the full cycle
again.
When the room thermostat is satisfied, the GCM turns off the boiler components and waits for the
next heat call.
The GCM indicator lights show normal sequence when the lights are on steady. When a problem
occurs, the GCM flashes combinations of lights which indicate the most likely reason for the
problem.
Transformer
②
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Blower
③
The blower pulls in air and mixes it with gas from the gas valve. The blower forces this mixture into
the burner for combustion inside the boiler chamber.
Air pressure switch
④
The air pressure switch signals the control module, telling the control module whether air is
moving through the blower.
Water temperature limit switch
⑤
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes
above its setting. (The circulators will continue to run as long as there is a call for heat.)
System circulator
⑥
The system circulator circulates water through the external (system) piping. The flow rate of the
circulator is controlled by the GCM, depending on the temperature of the water entering the boiler
sections.
Bypass circulator
⑦
The GCM operates the bypass circulator to mix hot water from the boiler outlet with colder return
water from the system as needed to prevent condensation of flue gases in the boiler.
When the water returning to the boiler is below 130 °F, the GCM regulates the bypass circulator
and system circulator flow rates to raise the return water temperature up to 130 °F before it enters
the boiler sections. By balancing these flow rates, the GCM can protect against condensation even
if return water is as low as 60 °F.
Water temperature sensor
⑧
The water temperature sensor monitors the temperature of the water entering the boiler sections.
The sensor sends this information to the GCM. The GCM determines how much to adjust the
circulator flow rates to provide at least 130 °F entering water.
Part number 550-141-850/06992
Ž Installation • Start-Up • Parts • Maintenance
GOLDGV Water boiler — Series 3
a
supply to system
b
return from system
c
combustio n a ir in le t fittin g
d
flue outlet
e
gas valve (see warning, right)
f
pressure/temperature gauge
g
flueway inspection port cover
h
sensor hose trap
i
manual air vent
j relief valve
85001
Thisboilerusesa
regulated
gasvalve,setforanoutlet
pressure approximatelyw.c..
set the outlet pressure higher than
NOT
negative-pressure-
–0.20"DO
factory setting.
3Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Please read before proceeding
Hazard definitions
Installer
The following defined terms are used throughout this manual to bring
attention to the presence of hazards of various risk levels or to important
information concerning the life of the product.
Indicates presence of hazards that will cause severe
personal injury, death or substantial property damage.
Indicates presence of hazards that can cause severe
personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause
minor personal injury or property damage.
Indicates special instructions on installation, operation
or maintenance that are important but not related to
personal injury or property damage.
Read all instructions before installing. Follow all
instructions in proper order to prevent personal injury
or death.
•Also refer to GV Series 3 Venting supplements.
•Consider piping and installation when determining boiler location.
•Any claims for damage or shortage in shipment must be filed
immediately against the transportation company by the consignee.
User
•This manual is for use only by your qualified heating installer/
service technician
•Please refer to the User’s information manual for your reference.
•We recommend regular service by a qualifed service technician,
at least annually
.
.
Table of contentsSee pages 6 and 7 for Table of contents.
Part number 550-141-850/06994
• Installation • Start-Up • Parts • Maintenance
Please read before proceeding
Failure to adhere to the guidelines on this page can result in severe personal
injury, death or substantial property damage.
When servicing boiler —
•To avoid electric shock, disconnect electrical supply before
performing maintenance.
•To avoid severe burns, allow boiler to cool before performing
maintenance.
Boiler operation —
•Do not block flow of combustion or ventilation air to boiler.
•Should overheating occur or gas supply fail to shut off, do not
turn off or disconnect electrical supply to pump. Instead, shut off the
gas supply
•Do not use this boiler if any part has been under water.
Immediately call a qualified service technician to inspect the boiler and to
replace any part of the control system and any gas control, which has
been under water.
at a location external to the appliance.
Boiler water —
•DO NOT use petroleum-based cleaning or sealing compounds in
boiler system. Water seal deterioration will occur, causing leakage between
sections. This can result in substantial property damage.
•DO NOT use "homemade cures" or "boiler patent medicines".
Serious damage to boiler, personnel and/or property may result.
•Continual fresh makeup water will reduce boiler life. Mineral
build-up in sections reduces heat transfer, overheats cast iron, and causes
section failure. Addition of oxygen and other gases can cause internal
corrosion. Leaks in boiler or piping must be repaired at once to prevent
makeup water.
•Do not add cold water to hot boiler. Thermal shock can cause
sections to crack.
5Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Check for high altitude requirements.
Provide required clearances and accessibility.
Plan vent and combustion air provisions.
Check existing common v ents to be sure the y will work when
old boiler is removed from system.
II.Prepare boilerLeave boiler on its skid until preparation complete.
Install vent starter tee.
Inspect/replace if necessary the gas/air orifice.
Install high altitude kit (over 5,500 feet).
Place boiler in position.
Hydrostatically test boiler.
III. Water pipingSelect system type from navigation table on page 26, cover-
ing baseboard systems, radiator systems, radiant heating
systems, heat pump systems, snow melt systems and water
chiller systems.
Review boiler connections pages 28 – 29, including instal-
lation of air separator and expansion tank.
Review general system information, page 30.
Obtain any system components needed but not on hand at
the job site.
Install relief valve and discharge piping.
Connect system piping.
Install low water cutoff and additional limit control, if
required.
8 – 15
16 – 25
26 – 36
IV. Venting and combustion airRefer to Vent supplements included with boiler37
V.Gas pipingConnecting gas supply, including need for pipe supports.
Natural gas boilers — gas line sizing (for 0.3" w.c. drop).
Propane boilers — refer to gas supplier.
VI. Field wiringCode compliances.
Wiring must be N.E.C. Class 1.
Thermostat connections.
Junction box installation.
Field wiring diagram.
Part number 550-141-850/06996
38 – 39
40 – 41
• Installation • Start-Up • Parts • Maintenance
Contents
ContentsSummaryPages
VII.Start-up• Determine water treatment needs, if any.
Obtain correct antifreeze if freeze protection required.
Check for gas leaks (ha ve propane odorant verified by supplier).
Fill system and purge air.
Read Operating instructions, section IX, then start boiler.
Check all piping and verify leak-free.
Check gas valve outlet pressure (altitudes over 5,500 feet).
VIII.Check-out procedureComplete checklist and fill out certificate.48 – 49
IX. OperationGCM (control module) indicator lights and sequence of opera-
Checking air pressure switch (page 68).
Servicing tips and precautions — Igniter, gas valve and blower
housing (page 69).
Servicing tips and precautions plus indicator lights and lockout
modes of GCM (control module) (page 70).
Common problems and solutions (pages 72 and 73).
Troubleshooting based on GCM indicator lights (pages 74 – 81).
XII. Replacement partsAccessory bag assembly shipped with boiler (page 83).
Section assembly parts (page 84).
Jacket assembly parts (page 86).
Blower assembly parts (page 88).
Trim assembly parts (page 90).
Interior panel parts (page 92).
XIII.Dimensions and ratingsDimensional drawing and boiler rating table.94 – 95
66 – 81
82 – 93
7Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Ia
Prepare boiler location — overview
Overview of this section
❏ Verify the boiler installation will meet all applicable codes.
❏ If the boiler installation is at high altitude (over 5,500 feet) make sure to
obtain and install the high altitude kit. Obtain the high altitude kit and
review the instructions included. Note the venting restrictions and input
reductions at altitudes over 5,500 feet.
❏ Check the boiler space to be sure minimum clearances and accessibility
are available.
❏ Obtain special venting materials and make sure vent will comply with
instructions.
❏ Direct vent installation (outside air piped to boiler) is optional in most
cases. But, if air contamination is likely, you will have to pipe air to the
boiler
. Note list of contaminants on page 13.
❏ If the GV boiler is replacing a boiler being removed from a combined vent
system
manual to verify vent performance.
that will still serve other appliances, follow the procedure in this
Part number 550-141-850/06998
• Installation • Start-Up • Parts • Maintenance
Prepare boiler location — codes & altitudeIb
Installations must
follow these codes:
High altitude
installations
•Local, state, provincial, and national codes, laws, regulations and ordinances.
•National Fuel Gas Code, ANSI Z223.1- latest edition.
•Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1,
when required.
•National Electrical Code.
•For Canada only: CAN/CGA B149.1 or B149.2 Installation Code and C.S.A. C22.1 Canadian
Electrical Code Part 1 and any local codes.
The GV boiler gas manifold and controls met safe lighting and other performance criteria when
boiler underwent tests specified in ANSI Z21.13 — latest edition.
GV boiler controls automatically reduce input with increasing altitude. See Table 1 for estimated
input at altitude as a percentage of sea level input. Multiply the boiler sea level input by this
percentage to obtain the estimated high altitude input. Note that the length of the venting system
will also have a minor impact on input. Refer to the vent supplement for further information.
No modifications to the boiler should be necessary for installations up to 5,500 feet above sea
level. For higher elevations, the air pressure switch must be changed to a special high altitude
switch. Refer to the high altitude kit instructions, manual Section IId. Note that the gas valve
outlet pressure must be checked (and adjusted if necessary) in accordance with manual Section
VIIf.
Table 1
Estimated GV input at altitude
At altitudes above 5,500 feet, GV boilers can be sidewall vented only when
using direct vent (ducted combustion air). GV boilers can be vertically vented
in any of the configurations shown in the vent supplements. Refer to vent
supplements for more detail.
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Ic
Prepare boiler location — clearances
Clearance options:
Large space
The boiler space must be at least as big as shown in
Figure 1 to qualify as a
•Air openings to a large space can be per manual
Ie.
Section
•The space will probably be large enough for most
service and maintenance to be done in place.
Small space
You can install the boiler in a space smaller than Figure 1,
but no smaller than shown in Figure 2— this is called a
small space installation.
•Air openings to a small space must provide at least 1
square inch free area for every 1,000 Btuh of boiler
input (at least 75 sq. in. for GV-3, 105 sq. in. for GV-
4, 140 sq. in. for GV-5 or 175 sq. in. for GV-6). The air
opening free area must be at least this size even if the
boiler uses outside air.
•Air openings have to be within 6 inches of the floor
and 6 inches of the ceiling of the space to prevent
overheating of boiler internal components.
•Provide at least screwdriver clearance to jacket front
panel screws for removal of front panel for inspection
and minor service.
•The boiler cannot be serviced in place. Pipe the
boiler with unions and isolation valves so it can be
slid out of the space and serviced in an adjacent area.
The space has to be equipped with a door so boiler
can be accessed, unpiped and removed.
•No other appliance or air handler can be installed in
the same space or share its air supply.
large space.
Install the boiler so control system
components are protected from
dripping or spraying water or
rain
during operation. Allowing
these components to become wet
could cause a boiler failure, resulting
in severe personal injury, death or
substantial property damage.
Figure 1
Large space — minimum clearances between
boiler and walls or obstructions as below; see
Section Ie for minimum combustion/ventilation
air opening sizing.
TOP VIEW
Wal l
36"
Wal l
min
Wall or obstruction
FRONT VIEW
Ceiling
Wal l
36"
min
Floor
min
Boiler
front
36"
min
36"
min
Boiler
front
6"
6"
min
Wal l
85006a
Wal l
6"
min
Part number 550-141-850/069910
• Installation • Start-Up • Parts • Maintenance
Figure 2
Small space— installation with less clearance
than Figure 1 – BUT – no less than below; air
openings for combustion/ventilation must be
as shown below even for direct vent system.
TOP VIEW
Wal l
Access
DOOR
with fresh air
openings
4"
min
Wal l
Area adjacent to access door must be accessible
and must allow for removal of the GV boiler for service.
No other appliance or air mover (exhaust fan, etc.)
may be mounted in the same space.
10"
min
Boiler
top
Front
1" min
1"
min
Flooring and foundation
Flooring
The GV boiler is approved for installation on combustible
flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death
or substantial property damage.
Foundation
Provide a solid brick or minimum 2-inch thick concrete
Wal l
foundation pad if any of the following is true:
•floor can become flooded.
•the boiler mounting area is not level.
•high profile condensate pump is used.
(Foundation thickness will depend on height
of condensate pump inlet.) Refer to separate
Weil-McLain supplement for details.
The minimum foundation size is 16" wide by:
•30¾" long for GV-3 or GV-4.
•37¾" long for GV-5 or GV-6.
SIDE VIEW
Ceiling
6" max
6" max
(2) Fresh air openings —
Each with at least 1 sq. inch per 1,000 Btuh
of boiler input
Access door
4"
min
Floor
85006b
1"
min
Boiler
side
Front
1"
min
Residential garage installation
Precautions
Wal l
Take the following special precautions when installing
the boiler in a residential garage. If the boiler is located in
a residential garage, per ANSI Z223.1, paragraph 5.1.9:
•Mount the boiler a minimum of 18 inches
above the floor
of the garage to assure the
burner and ignition devices will be no less than
18 inches above the floor.
•Locate or protect the boiler so it cannot be
damaged by a moving vehicle.
11Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Id
Prepare boiler location — vent system
Removing from existing vent
Failure to follow all instructions
following can result in flue gas
spillage and carbon monoxide
emissions, causing severe personal
injury or death.
When removing a boiler
from an existing common vent system:
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining connected
to the common venting system are not in operation.
a. Seal any unused openings in the common
venting system.
b. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
c. Test vent system— Insofar as is practical, close
all building doors and windows and all doors between
the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the
common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after
5 minutes of main burner operation. Use the flame
of a match or candle, or smoke from a cigarette,
cigar, or pipe.
f. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers, and
any other gas-burning appliance to their previous
conditions of use.
Any improper operation of common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1 — latest edition.
Correct by resizing to approach the minimum size as
determined using the appropriate tables in Part 11 of
that code. Canadian installations must comply with CAN/
CGA B149.1 or B149.2 Installation Code.
GV special vent system
Vent system
The GV boiler requires a special vent system, designed
for pressurized venting with likelihood of condensation
in the vent. This is referred to as ANSI Z21 Class IV,
Condensing
You may use any of the vent systems covered by the GV
venting supplements included in the instruction manual
envelope. The GV vent starter tee is a special item designed
only for the GV boiler, available from each vendor. Do
not attempt to connect the vent to the GV boiler with any
other means.
Vent termination and
combustion air supply
The GV boiler may be vented through the roof or through
a side wall. Follow the appropriate vent supplement for
the vent system chosen. The maximum vent length
depends on boiler size. Refer to the vent supplement to
verify vent length will be acceptable.
Combustion air for the GV boiler may be from inside or
ducted directly to the boiler from outside. For outside air
(direct vent installation), two options are available for
the flue/air termination. The air supply must ALWAYS
terminate at the same location as the flue, using either:
1. Vertical direct vent installation. Obtain the Through-
roof or through-unused chimney kit and
supplement. Find additional information in the vent
supplement for the venting material chosen.
2. Sidewall vent/air termination. This requires the Weil-
McLain GV vent/air intake termination kit. Refer
to the instructions packed with the kit and the vent
supplement for the venting material chosen.
Installations above 5,500 feet altitude must be
direct vent if sidewall vented.
.
DO NOT mix components from
different systems. The vent system
could fail, causing leakage of flue
products into the living space, causing
severe personal injury or death.
Part number 550-141-850/069912
• Installation • Start-Up • Parts • Maintenance
Ie
Prepare boiler location — contamination
Air contamination
Please review the following information on potential
combustion air contamination problems.
If the boiler is installed in any area likely to cause contamination, or if products which
would contaminate the air cannot be removed, you must pipe combustion air to the boiler
air intake. Contaminated combustion air will damage the boiler, resulting in possible severe
personal injury, death or substantial property damage. Do not install GV boiler in a
room or pool facility, for example
contain contaminants.
Table 2Corrosive contaminants
Products to avoidAreas likely to have contaminants
Spray cans containing chloro/fluorocarbonsDry cleaning/laundry areas and establishments
Permanent wave solutionsSwimming pools
Refer to Table 2 for products and areas which may cause
contaminated combustion air.
, without using ducted outside air. These areas will always
Chlorine-based swimming pool chemicalsBeauty shops
Calcium chloride used for thawingRefrigeration repair shops
Sodium chloride used for water softeningPhoto processing plants
Refrigerant leaksAuto body shops
Paint or varnish removersPlastic manufacturing plants
Hydrochloric acid/muriatic acidFurniture refinishing areas and establishments
Cements and gluesNew building construction
Antistatic fabric softeners used in clothes dryersRemodeling areas
Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
Garages with workshops
Adhesives used to fasten building products and
other similar products
13Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
If
Prepare boiler location — air openings
GV combustion air options
Using inside air — non-direct vent
The GV boiler can use inside air if no contaminants are
present in the boiler space.
Using outside air — direct vent
Combustion air can be ducted directly from outside to
the GV boiler air intake fitting. The installation is defined
as direct vent (also referred to as sealed combustion).
Sizing air openings
Air openings to the GV boiler space are always required,
regardless whether combustion air is taken from inside or
outside. These air openings provide for ventilation (as
well as combustion air) to prevent overheating of the
boiler controls and boiler space. Air is also needed for
other appliances located in the same space.
Use Figure 3, cases a through d, depending on how the
air is supplied and whether the space contains only the
GV or other appliances as well. The air opening sizing of
Figure 3 is based on ANSI Z223.1, National Fuel Gas
Code, intended for natural draft appliances. The GV boiler
is not natural draft, so its requirements differ.
Single air opening option
A single air opening within 12 inches of the ceiling may be
used where the GV boiler is installed in a large space
(clearances per Figure 1) with other appliances.
The other appliances must all be installed with at least 1
inch clearance from the sides and back, and 6 inches from
the front. The GV boiler must have minimum clearances
as shown in Figure 1.
The single air opening may be connected from outside to
the appliance space by any of the methods of Figure 3.
The free area of the opening must also be at least equal to
the combined area of all appliance vent connectors OR
sized per the following, whichever result is larger:
GV direct vent — large shared space —
single air opening
Size the single air opening for 1 square inch of free opening
for each 3,000 Btuh of all appliances other than the GV.
No additional air opening is needed for the GV.
GV inside air — large shared space —
single air opening
Size the air opening for 1 square inch of free opening for
each 3,000 Btuh of all appliances, including the GV.
Air openings must be sized to handle
all appliances and air movers
(exhaust fans, etc.) using the air
supply.
Louver allowance
The free area of openings means the area after reduction
for any installed louvers or grilles. Be sure to consider
this reduction when sizing the air openings.
GV with other appliances
If the GV boiler is installed in a large space (clearances per
Figure 1) providing air for a water heater or other gas
appliance, size the air openings as follows:
GV direct vent — large shared space
Provide two openings per Figure 3, based only on the size
of the other appliances and air movers. No additional airopening area is required for the GV boiler.
GV inside air — large shared space
If the GV combustion air comes from the inside space,
size two air openings for the total of all appliances and air
movers, including the GV boiler. Use the formula from
the appropriate case in Figure 3.
GV without other appliances
If the GV boiler is installed in a space by itself, with no
other appliance or air mover using air from the space,
and with clearances around the boiler no less than those
shown in Figure 1 for large space installations:
GV direct vent — large space — alone
Air is needed only for ventilation. Size the air openings
for any of the cases of Figure 3 for a free area of at least:
1 square inch per 8,000 Btuh of GV input
for each of the two openings. (If a single opening within
12 inches of the ceiling is used, size the opening for 1
square inch of free area for each 3,000 Btuh of GV input.)
GV inside air — large space — alone
Size the air openings for any of the cases of Figure 3 for a
free area of at least:
1 square inch per 4,000 Btuh of GV input
for each of the two openings. (If a single opening within
12 inches of the ceiling is used, size the opening for 1
square inch of free area for each 3,000 Btuh of GV input.)
Part number 550-141-850/069914
• Installation • Start-Up • Parts • Maintenance
Air
Air
Air
Air
opening
Add air openings
to outside if
building is tight
construction.
Air
opening
Air
opening
Air
opening
Air (direct vent)
(optional)
Air (direct vent)
(optional)
Air (direct vent)
(optional)
0 to 12"
0 to 12"
12"
0 to 12"
0 to 12"
Flue
Flue
Flue
Other
appliances
Other
appliances
Other
appliances
Other
appliances
GV
GV
Air
Air (direct vent)
(optional)
Flue
GV
GV
Outside
Outside or ventilated attic
Air
opening
Air
opening
0 to 12"
0 to 12"
Outside
Ventilated
crawl space
— or —
a
d
b
c
Each opening free area =
1 sq. inch per 4,000 Btuh
Each opening free area =
1 sq. inch per 2,000 Btuh
Each opening free area =
1 sq. inch per 1,000 Btuh
Each opening free area =
1 sq. inch per 4,000 Btuh
85005
GV in small space (less than Fig. 1) — alone
For all vent/air situations, whether air is taken from inside or outside, provide
two openings, each with minimum free area of:
1 square inch per 1,000 Btuh of GV input.
The openings must be within 6 inches of the ceiling and 6 inches of the floor
as shown in Figure 2 for small space installations.
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction where:
a. Walls and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of 1 perm or less with openings gasketed,
and . . .
b. Weatherstripping has been added on openable windows and doors, and
. . .
c. Caulking or sealants are applied to areas such as joints around windows
and door frames, between sole plates and floors, between wall-ceiling
joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and in other openings.
For buildings with such construction, provide air openings into the building
from outside, sized per the appropriate case in Figure 3 if appliances are to
use inside air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative
pressure, even if the appliance(s) are installed as direct
vent. Always provide air openings sized not only to the
dimensions required for the firing rate of all appliances,
but also to handle the air movement rate of the exhaust
fans or air movers using air from the building or space.
Motorized air dampers
If the air openings are fitted with motorized dampers,
electrically interlock the damper to:
•Prevent the boiler from firing if the damper is not
fully open.
•Shut the boiler down should the damper close during
boiler operation.
To accomplish this interlock, wire an isolated contact
(proving the damper open) in series with the thermostat
input to the boiler. The boiler will not start if this contact
is open, and will shut down should it open during
operation.
Figure 3
Air openings:
GV in space
with other
appliances
a —
Air from inside
building
b —
Air directly
from outside
c —
Air through
vertical ducts
(or inlet air
from ventilated
crawl space)
d —
Air through
horizontal
ducts
15Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IIa
Overview of this
section
Prepare boiler — vent starter tee & drainIIb
Prepare boiler — overview
❏ Leave the boiler on its skid until installation site is ready and boiler prep is
complete per this section.
❏ Install vent starter tee and condensate drain line.
❏ Inspect gas/air orifice plate to verify model size and gas markings agree
with boiler and application. Install propane gas/air orifice for propane
installations.
❏ Install high altitude kit for altitudes more than 5500 feet above sea level.
❏ Place boiler in position and install jacket rear panel.
❏ Plug openings and hydrostatically test boiler. Remove plugs.
Install vent starter
tee and condensate
drain hose
Use only the vent starter tee of the same manufacturer as the
vent components
systems. The vent system could fail, causing flue gas spillage, resulting in
severe personal injury or death.
Install vent starter tee as shown in Figure 4.
1. Remove jacket access panel (item 1). You can rotate the plate out of the way, leaving the air
hose connected to the air intake fitting, or loosen the hose clamp (item 2) and pull the air hose
off of the fitting as shown in Figure 4.
2. Remove the hex nuts (item 5) from the vent starter tee studs at the boiler vent connection.
3. Remove the vent starter tee gasket (item 4) from the studs.
4. Clean the surface of the boiler flue connection to assure a good seal. Use emery cloth if
necessary to remove any accumulated rust.
5. Place the vent starter tee gasket (item 4) over the studs.
6. Slide the holes in the vent starter tee flange (item 3) over the studs.
7. Apply the (4) hex nuts (item 5), align the vent starter tee (item 3) and tighten the nuts
uniformly.
Install condensate trap hose as shown in Figure 4.
1. Loosen and slide a spring hose clamp (item 8) over each end of the condensate drain hose
(item 6).
2. Loosen the clamp and slide one end of the hose over the CPVC drain elbow (item 7). Slide
clamp into position and release.
3. Attach and clamp the other end of the hose to the drain connection on the bottom of the vent
starter tee (item 3).
to be used. Do not mix components from different
Replace jacket access panel (item 1), reconnecting the air hose to the air intake fitting if necessary.
Part number 550-141-850/069916
• Installation • Start-Up • Parts • Maintenance
IIb
Figure 4Install vent starter tee and
Prepare boiler — vent starter tee & drain (cont.)
condensate drain hose before
placing boiler.
Screw hole
and notch, located
in base rail under
vent outlet
Base rail
Insert CPVC elbow
into bracket. Then
attach bracket to
base rail with screw
as shown at left.
10-32 x 3/8"
85002
Vent starter tee — not included
with boiler. See information
below.
The vent starter tee is NOT supplied with the boiler. Obtain this
part as a separate purchase from your Weil-McLain wholesaler.
The vent starter tee shown is for Saf-TVent®. Use only the vent tee
made for the vent system you are using. DO NOT mix different
brands of vent system components. The vent system could fail to
operate properly, causing leakage of flue products into the living
space, resulting in severe personal injury or death.
17Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IIc
Check for correct
orifice plate and
replace if necessary
Prepare boiler — orifice plate
The correct orifice plate must be used. Failure to do so will result in severe
personal injury, death or substantial property damage.
Natural gas:
For natural gas installations, inspect the silver gas/air orifice plate marking. It must be
the same as the boiler size. If the orifice plate is stamped with another size, obtain the correct plate
from your wholesaler. The boiler size is stamped where the “X” is shown in the plate stamping,
Figure 5b.
Propane:Propane:
Propane:
Propane:Propane:
For propane installations, replace the silver gas/air orifice plate with the red/white
, per following instructions. Ensure the red/white plate boiler size is correct for the GV
plate
boiler being installed. The boiler size is stamped where the “X” is shown in the plate stamping,
Figure 5b.
Also fill out the propane label in the conversion kit and attach to the left side of the jacket, above
the gas inlet opening, as shown in Figure 5a.
Plate installation
Access the bottom of the blower housing as shown in Figure 5a.
To inspect the plate only, read the marking on the plate edge. It must read the same as the
boiler size and fuel.
Figure 5a
Check for correct orifice plate
and replace if necessary.
Leave boiler on its back, on
the skid, until inspection/
replacement is completed.
To replace the plate, using a manual screwdriver or nut driver, see Figure 5b:
1. Loosen screws 1 and 2 two full turns.
2. Remove screws 3 and 4.
3. Pull the gas/air orifice plate forward to remove it.
4. Slide in the new plate as shown in Figure 5b. The red side of a propane plate must go
next to the blower housing
5. Replace screws 3 and 4. Tighten all four screws securely and uniformly. DO NOT overtighten.
DO NOT exceed 40 inch-pounds torque.
6. Bend down plate label tab at score mark as shown in lower right corner of Figure 5b.
as shown.
Remove jacket front panel to access the bottom
side of theblowerhousing.
Complete the propane conversion label included
with the conversion kit. Install label on jacket left
side, as shown.
85004a
Leave the boiler on its back, on the skid as
shown, until you have checked the gas/air orifice
plate and replaceitif necessary.
Part number 550-141-850/069918
• Installation • Start-Up • Parts • Maintenance
Bottom side of boiler front section
Figure 5bChecking and replacing gas/air orifice plate. For propane
installations, replace silver plate with red/white propane plate.
DO NOT use electric or
pneumatic screwdrivers
remove or tighten the gas/air boss
screws. Hand-tighten only, using
manual screwdriver. Should the
torque exceed 40 inch-pounds, the
threaded holes could strip out, causing
to
an inadequate seal of the orifice plate.
Failure to properly seal the plate to
the housing could result in a gas leak,
causing severe personal injury, death
or substantial property damage.
White side (propane plate)
Warning label side (natural gas)
(Install with this side
toward air inlet hose)
Gas/air manifold
Bottom side of boiler front section
GVX PROP
GVX PROP
GVX PROP
Propane — red sideNatural — plain side
Install plate with red side (propane) or plain side
(natural).againstthe blower housing
GVX PROP
GVX PROP
GVX PROP
Orifice plate after bending along
score mark. This makes the plate
identification readable after
installation.
85004b
19Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IId
Prepare boiler — high altitude kit
When requiredWhen required
When required
Obtain high altitude
Install high altitude
air pressure switch
When requiredWhen required
kit
For installations at altitude more than 5,500 feet
above sea level
switch is required. In addition, the gas valve outlet
pressure setting must be checked, and adjusted if
necessary, per the instructions in manual Section VIIf,
altitude over 5,500 feet.
Obtain the GV high altitude kit from your local WeilMcLain distributor. This kit includes the high altitude air
pressure switch and a special tool needed for accessing
the adjusting screw on some gas valves. The kit also
includes tubing fittings as described in manual.
1. See Figure 5c (switch shown with wires removed).
2. Remove the two (RED) control wires from the air
pressure switch spade terminals.
, a special high altitude air pressure
Check gas valve
outlet pressure
3. Remove the factory-installed air pressure switch
(loosen top screw and remove bottom screw holding
switch to jacket interior panel).
4. Install the high altitude air pressure switch in the same
location.
5. Carefully replace the hoses on the new switch, with
the red hose on the hose barb closest to the interior
panel, as shown in Figure 5c. The white hose goes
on the outer hose barb.
6. Replace the two (RED) control wires on the new
pressure switch spade terminals.
After following the start-up procedures of manual Section
VII, follow the procedures of Section VIIf to measure gas
valve outlet pressure and adjust if necessary.
Failure to check gas valve
outlet pressure
necessary, could result in severe
personal injury, death or substantial
property damage. Carefully follow
the guidelines given in this manual.
and adjust, if
Part number 550-141-850/069920
• Installation • Start-Up • Parts • Maintenance
— altitudes above 5,500 feet ONLY
Figure 5cAir pressure switch mounting and sensor hoses
Jacket left
side panel
White
hose
Red
hose
Interior panel
Boiler top
(2) 10-32 x 3/8"
Phillips/hex screws
85052
21Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IIe
Prepare boiler — place in position
Position boiler
After installing vent starter tee, inspecting (replacing if
necessary) the gas/air orifice and installing the high
altitude kit (if required), move the boiler near its position.
Figure 6 shows the boiler with the front and top panels
replaced. These panels may be left off if desired until the
installation has been completed.
Refer to Figure 6 for placement sequence:
Wearing heavy gloves, carefully rotate the boiler
➀➀
➀
➀➀
over onto its base rail legs.
Clip the shipping strap securing the skid to the
➁➁
➁
➁➁
boiler block assembly. Remove the skid and strap.
Attach the jacket rear panel as shown using (4)
➂➂
➂
➂➂
#10 x ¾" screws provided in the accessory bag.
Boiler is heavy and contains some
sheet metal parts which may have
sharp edges. Wear gloves when
handling and take proper precautions
when moving. Failure to do so will
result in severe personal injury, death
or substantial property damage.
Part number 550-141-850/069922
• Installation • Start-Up • Parts • Maintenance
Figure 6Rotating boiler into position, removing skid and installing jacket rear panel
Carefully rotate
boiler onto base
rail legs as shown
ROTATE
ROTATE
Install jacket
rear panel
with (4) screws,
#10 x 3/8"
Clip shipping
strap
85003
23Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IIf
Prepare boiler — pressure test
Perform hydrostatic pressure
test
Pressure test boiler before attaching water or gas piping
(except as noted below) or electrical supply.
Prepare boiler for test (Fig. 7)
Connect a hose from water supply to fill and drain
➀➀
➀
➀➀
boiler for hydrostatic test. Hose is not included with
boiler.
Connect hose to boiler drain valve. Make sure hose
➁➁
➁
➁➁
can also be used to drain boiler after test.
Remove 1" nipple, 1" tee, bushing and pressure/
➂➂
➂
➂➂
temperature gauge from accessory bag. Pipe to boiler
supply connection as shown. Use pipe dope sparingly.
Connect a nipple and shutoff valve to system supply
➃➃
➃
➃➃
connection on the 1" tee. This valve will be used to
bleed air during the fill. Valve and nipple are not
included with boiler.
Connect a nipple and shutoff valve to system return
➄➄
➄
➄➄
connection at circulator flange. This valve will be used
to bleed air during the fill. Valve and nipple are not
included with boiler.
Install a ¾" pipe plug in the relief valve opening, top
➅➅
➅
➅➅
of the rear boiler section, as shown. Plug is not
included with boiler.
5. Slowly reopen drain valve (item 2) until test pressure
of not more than 45 psi is reached on the pressure
gauge.
6. Test at no more than 45 psi for no more than 10
minutes.
Do not leave boiler unattended.
A cold water fill could expand and
cause excessive pressure, resulting in
severe personal injury, death or
substantial property damage.
7. Make sure constant gauge pressure has been
maintained throughout test. Check for leaks. Repair
if found.
Leaks must be repaired at once.
Failure to do so can damage boiler,
resulting in substantial property
damage.
Do not use petroleum-based
cleaning or sealing compounds in
boiler system. Severe damage to
boiler will occur, resulting in
substantial property damage.
Drain and remove fittings
Fill and pressure test
1. Connect fill water supply through drain valve (item
2).
2. Fill boiler with water (be sure bleed valves at 4 and 5
are open).
3. When water flows from bleed valves, shut off water
at drain valve.
4. Close bleed valves.
1. Disconnect fill water hose from water source.
2. Drain boiler at drain valve or out hose, whichever
provides best access to drain. Close drain valve and
remove hose after draining.
3. Remove nipples and valves at 4 and 5 unless they
will remain for use in the system piping.
4. Remove plug (item 6) from relief valve tapping.
Part number 550-141-850/069924
• Installation • Start-Up • Parts • Maintenance
Figure 7Piping connections for hydrostatic test
85007
To fill/drain
25Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
For heating system with . . .See pages 27 – 30 and . . .
Baseboard, finned tube or cast iron
31
Radiators, cast iron
32
Radiant floor, wall or ceiling —
single zone
(note 1)
33
Radiant floor, wall or ceiling —
multiple zones
34
Heat pump (note 1)
33
Snow melt plus space heating
35
Control valve (note 2)
34
Water chiller
36
Note 1: Install a temperature limit control in the supply piping to protect the system.
Note 2: Apply these piping designs for outdoor reset or any system requiring automatic
supply temperature regulation.
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
Water piping — overviewIIIa
Overview of this
section
❏ Select suggested piping from the following table, based on the type of
system in which you are installing the GV boiler.
❏ Review boiler connections, pages 28 – 29 — information on supply and
return connections at boiler and key system components (air separator
and expansion tank).
❏ Review page 30, information applying to all systems.
❏ Obtain any system components needed but not on hand or available at
jobsite.
❏ Install boiler relief valve and pipe discharge to a safe location per guidelines
in this section.
❏ Install system piping and boiler connections.
❏ Install additional limit control (if required for code compliance) and low
water cutoff
if required.
Part number 550-141-850/069926
• Installation • Start-Up • Parts • Maintenance
IIIb
Install relief valve
Water piping — relief valve
Refer to Figure 8 for location of the relief valve on the boiler.
Install the relief with the spindle vertical in the ¾" tapping on top left of the back section, as
shown.
To avoid water damage or scalding due to valve operation, a metal discharge
line must be connected to relief valve outlet and run to a safe place of
disposal
should the valve discharge.
Discharge line must be as short as possible and be the same size as the
valve discharge connection throughout its entire length.
Discharge line must pitch downward from the valve and terminate at least
6" above the floor drain where any discharge will be clearly visible.
The discharge line shall terminate plain, not threaded, and must be
rigid metallic pipe of material suitable for temperatures of 375 °F or greater.
Do not pipe the discharge to any place where freezing could occur.
No shutoff valve shall be installed between the relief valve and boiler, or in
the discharge line. Do not plug or place any obstruction in the discharge line.
. Terminate the discharge line to eliminate possibility of severe burns
Figure 8
Install and pipe relief valve
Failure to comply with the above guidelines could result in failure of the
relief valve to operate, resulting in possibility of severe personal injury, death
or substantial property damage.
Test the operation of the valve after filling and pressurizing system by
lifting the lever. Make sure the valve discharges freely. If the valve fails to
operate correctly, replace it with a new relief valve.
1 Jacket plug for unused relief valve jacket
opening.
2 Jackets are provided with two relief valve
openings because each jacket size is used
for two boiler sizes. Cover the unused
opening with the plug provided.
3 Boiler relief valve (from accessory bag)
4 ¾" x 3" nipple, provided in accessory bag
5 ¾" relief valve tapping in back section
6 Connect minimum ¾" discharge piping
to relief valve.
See WARNING above.
85008
27Part number 550-141-850/0699
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manual
GOLD GV Water boiler series 3 — manualGOLD GV Water boiler series 3 — manual
IIIc
Water piping — boiler connections
Supply & return connections
Always connect supply and return connections to the
boiler as shown in Figure 9. (Note in the following and in
the suggested piping drawings in this manual that the
expansion tank and air separator location will depend on
the system piping.)
Air separator
Install an air separator in the piping as shown. For
single-zone systems, install the air separator in the return
piping as shown in Figure 9. This allows mounting the
automatic air vent and expansion tank off of the separator.
Expansion tank
Figures 9 and 10 show typical installation of the
expansion tank when the boiler is connected to a zonevalve zoned baseboard system (see Figure 10). Always
locate the air separator and expansion tank as shown in
the suggested piping drawings, Figures 10 through 16.
Ensure that the expansion tank size will handle boiler and
system water volume and temperature. See tank
manufacturer’s instructions and ratings for details.
Additional tanks may be added to the system if needed to
handle the expansion. These tanks may be installed by
connecting to tees in the system piping.
Undersized expansion tanks
cause system water to be lost from
the relief valve and makeup water to
be added through the fill valve.
Eventual section failure can result.
Always locate the cold water fill
connection
Never locate this elsewhere in the
system.
Diaphragm- or bladder-type tank:
Refer to Figure 9 for suggested piping when using a
diaphragm- or bladder-type expansion tank.
at the expansion tank.
Install an automatic air vent on top of the air separator,
per separator manufacturer’s instructions.
Closed-type expansion tank:
Figure 10 shows suggested piping when using a closedtype expansion tank, in which the air is directly in contact
with tank water.
Connect piping (½" or ¾") from the air separator top
outlet to the tank fitting. Slope any horizontal piping a
minimum of 1 inch per 5 feet of horizontal pipe.
Always use a tank fitting, such as the B&G Tanktrol or
Ta co Taco-Trol (shown). The fitting reduces gravity flow
of water in the piping to the tank, avoids air bubbling
through the tank water, and provides the proper fill height
in the tank.
Operating pressure of system, after
temperature expansion above cold fill
pressure, should not exceed 24 PSIG
to avoid weeping of relief valve.
Correct all leaks in the system or
tank piping. Leaks allow air to escape
from the system and will cause waterlogging of the tank. This will result in
water loss through the boiler relief
valve due to over-pressurization.
NEVER use an automatic air vent in
a system equipped with a closed-type
expansion tank. The air removed
from the system will cause waterlogging of the expansion tank.
Closed-type expansion tank —
Follow tank manufacturer’s
instructions for filling the tank.
Typical tank sizing provides for
approximately 12 PSIG when the
tank is filled to the normal level and
system water is cold. Note that boiler
relief valve is set for 30 PSIG.
Operating pressure of system, after
temperature expansion above cold fill
pressure, should not exceed 24 PSIG
to avoid weeping of relief valve.
Diaphragm- or bladder-type
expansion tank
pressure
pressure. Always check pressure and
charge tank with tank removed fromsystem to be sure reading is accurate.
Boiler relief valve is set for 30 PSIG.
with the tank air charge
— Control fill
Backflow preventer
Where required by codes, install a backflow preventer
in the cold water fill line, as shown in suggested piping
diagrams on following pages. Install a check valve if a
backflow preventer is not installed.
Part number 550-141-850/069928
• Installation • Start-Up • Parts • Maintenance
Figure 9Piping to single-zone system using diaphragm- or bladder-type
expansion tank. Boiler connections are 1" NPT (supply from 1" tee,
return to 1" system circulator flange).
1 Relief valve discharge piping — see page 27
2 Boiler isolation valves
3 Fill valve
4 Air separator
5 Automatic air vent
6 Backflow preventer or check valve
7 System supply piping
8 System return piping
9 Diaphragm-type expansion tank —
always locate as shown in the suggested
piping drawings, Figures 10 through 16
Figure 10Piping closed-
type expansion
tank
To cold fill
To cold fill
Locate the air separator as shown in the suggested piping
diagram, Figures 11 through 16 on the following pages.
Pipe diaphragm- or bladder-type expansion tanks to the
bottom of the separator.
always locate as shown in the
suggested piping drawings,
Figures 10 through 16
85010
13 Tank fitting
Pipe closed-type (air in contact with water) tanks to the
top of the air separator. Always connect the fill line to the
expansion tank location, as shown above and in the
suggested piping.
29Part number 550-141-850/0699
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.