This manual must only be used by a qualified heating installer/service technician. BEFORE
installing, read all instructions in this manual and all other information shipped with the
boiler. Perform steps in the order given. Failure to comply could result in severe personal
injury, death or substantial property damage.
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Using this manual
Homeowner —
Read and follow all information on pages 1 through 7 ONLY.
Service technician —
Read and follow ALL information in the entire manual.
Failure to follow all instructions in proper order can cause severe personal injury, death or
substantial property damage.
When calling or writing about the boiler
Please have boiler model number and series from boiler rating label and CP number(s) from boiler jacket,
burner and controls. On page 28 of this manual is space to list CP number(s).
Packaged and non-packaged boilers
Packaged boilers, available only in sizes 2 through 6, are factory assembled, complete with block, jacket and
controls. Burner is shipped separately.
Non-packaged boilers, available in all sizes, 2 through 9, are shipped with block assembled, with jacket.
Controls, trim and burner shipped separately for field assembly.
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards
of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury,
death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury,
death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal
injury or property damage.
Indicates special instructions on installation, operation or
maintenance that are important but not related to personal injury
or property damage.
2
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
Contents
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Please read before proceeding
Homeowner —
• For homeowner or person responsible for
simple start-up and routine maintenance of
the system
• Instructions on page 1 through page 7 must
be followed to assure proper operation of your
boiler. See page 7 for lists common problems
and possible corrections. In addition, it is your
responsibility to:
• Have boiler and burner installed by a quali-
fied installer.
• Have boiler and burner serviced annually
by a qualified service technician.
• Review and understand start-up and rou-
tine maintenance procedures with qualified service technician.
• Perform routine maintenance as described
on page 5.
Service technician —
• For a qualified service technician who has the
necessary equipment to check the boiler and
system performance, and is responsible for
start-up and service of boiler and system.
• All instructions in this manual must be followed to assure proper operation of this boiler.
• Annually service boiler and burner to assure
proper operation. See page 29 for service
record.
• Review and explain start-up and routine maintenance procedures with homeowner.
Follow instructions below to prevent severe personal
injury, death or substantial property damage:
• To avoid electric shock, disconnect electrical supply to burner
service switch and additional external switches before performing service.
• To avoid severe burns, allow boiler to cool before performing
service.
• Do not block flow of combustion or ventilation air to boiler.
• Boiler must be connected to a flue with sufficient draft at all times
to assure proper operation.
• Do not use this boiler if any part has been under water. Electrical
and mechanical failures may cause electric shock and fire risks.
Immediately call a qualified service technician to inspect chimney
or vent, boiler and burner. Have the boiler flueways cleaned and
have the following replaced:
• all electrical and mechanical controls
• electrical wiring
• oil burner and controls
• insulation and chamber lining
Tips for water systems —
• Check boiler and system piping for leaks. Continual makeup water
will reduce boiler life. Minerals can build up in sections, reducing heat transfer and causing cast iron to overheat, resulting in
section failure.
Failure to maintain recommended pH and repair leaks
can cause section iron corrosion, leading to section
failure and leaks. Do not use petroleum-based sealing
or stop-leak compounds in boiler systems. Damage to
system components can result, causing property damage.
Follow instructions below to prevent
severe personal injury, death or substantial property damage:
• Do not use crankcase drainings or any oil
containing gasoline. See burner manual for
proper fuel oil.
• Do not attempt to start burner when excess
oil has accumulated in combustion chamber,
when unit is full of vapor, or when combustion
chamber is very hot.
• Do not start burner unless collector hood, flue
cap, jacket cap, breeching and burner mounting door are secured in place.
• Never burn garbage or paper in the boiler.
Never leave combustible material around
boiler.
• DO NOT TAMPER WITH UNIT OR CONTROLS. Always follow specific instructions
when starting up boiler or performing routine
maintenance or service.
4
• Boiler water pH 7.0 to 8.5 is recommended. For pH conditions
outside 7.0 to 8.5 range or unusually hard water areas (above 7
grains hardness), consult local water treatment company.
• When using antifreeze:
Use antifreeze especially made for hydronic systems. Inhibited
propylene glycol is recommended.
Do not use automotive, ethylene glycol, undiluted or
petroleum-based antifreeze. Severe personal injury, death
or substantial property damage can result.
50% solution provides protection to about –30°F. Local codes may require back-flow preventer or actual discon-
nect from city water supply.
Determine quantity according to system water content. Boiler
water content is listed on back cover of Boiler Manual.
Percent of solution will affect sizing of heat distribution units,
circulator and expansion tank.
Follow antifreeze manufacturer’s instructions. Do not add cold water to hot boiler. Thermal shock can cause
sections to crack.
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Routine maintenance schedule
Beginning
each heating season
Daily
during heating season
Weekly
during heating season
Call a qualified service technician to perform annual service.
Check that boiler area is free from combustible materials, gasoline
and other flammable vapors and liquids.
Check for and remove any obstructions to flow of combustion or
ventilation air to boiler.
Check that breeching is attached between boiler and chimney. If
breeching is loose or damaged, immediately turn off switch on
boiler and call service technician to repair.
Check for oil leaks in oil piping and around burner. If found, im-
mediately call qualified service technician to correct situation.
Check for water leaks in boiler and piping; also check for leaks
around tankless heater plate, if installed. If found, immediately call
service technician to repair.
End
of heating season
Boiler
shutdown
If tankless heater is installed, boiler will continue to operate. Check
for the following:
• All daily and weekly instructions listed on this page must be followed.
• Burner motor may have to be oiled. Some motors are permanently
lubricated and do not need additional oil. Check for oiling instructions on burner or motor.
Do not drain boiler unless exposure to freezing temperatures will
occur.
Always keep manual fuel supply shut off if burner is shut down for
an extended period of time.
• Turn off switch at boiler and any external switch to boiler.
• Close fuel valves.
• Turn off water feed valve.
• Cover burner to protect from dust and dampness.
Part number 550-141-826/1211
5
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
Operation
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
WGO (see Figure 1)
1. If burner does not fire, check for:
• Service switch on boiler or additional switches turned off.
• Fuses or breaker switch tripped.
• Thermostat set below room temperature.
• Fuel valves turned off.
• Not enough oil in tank to supply burner.
Figure 1 WGO Boilers
2. Correct problems found in step #1. If burner does not fire,
press reset button on burner primary control only once.
Repeated presses will deposit oil in combustion chamber.
Burner must never be fired when oil is in combus-
tion chamber. Immediately call qualified service
technician.
3. If burner still does not fire, call qualified service technician.
1 Burner disconnect plug
2 Service switch on boiler
3 Water relief valve
4 Temperature-pressure gauge
5 Circulator
6 Limit control / low water
cut-off
7 Reset button on burner
primary control
8 Burner primary control
6
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Troubleshooting
Homeowners — The problems and corrections below represent common situations that can occur. There may be
others not listed below. It is important always to contact a qualified service technician if you have any questions
about the operation of your boiler or system.
Common ProblemsCommon CausesPossible Corrections
Rapid cycling — burner
turns on and off frequently.
Need to frequently add
makeup water.
Popping or percolating
noise heard in boiler.
Black water condition.
Frequent release of water
through relief valve.
Metal flakes found in
flueway.
Some radiators or
baseboard units do not
heat or are noisy.
Thermostat installed where
Locate thermostat on inner wall away from heat sources or cool drafts.
drafts or heat affect reading.
Heat anticipator in thermostat adjusted incorrectly.
Adjust heat anticipator to match current draw. Refer to boiler wiring
diagram.
Incorrect limit setting.Have qualified service technician increase limit setting to decrease
cycling. Maximum setting 220° F.
Leaks in boiler or piping.Have qualified service technician repair leaks at once to avoid constant
use of makeup water.
Mineral deposits in sections
due to constant use of makeup water, or incorrect pH.
Oxygen corrosion due to
leaks in piping.
Expansion tank sized too
Have qualified service technician de-lime boiler, repair leaks at once
to avoid constant use of makeup water and check pH (between 7.0
and 8.5).
Have qualified service technician repair leaks at once to avoid constant
use of makeup water and check pH (between 7.0 and 8.5).
Have qualified service technician check expansion tank operation.
small or water-logged.
Contaminated combustion
air supply.
Condensation of combustion
Remove sources of hydrocarbons in or near boiler area. (Bleaches,
cleaners, chemicals, sprays, fabric softeners, paint remover, etc.)
Have qualified service technician check boiler operation.
gases.
Air in system.Bleed air from system through air vents in radiators or baseboard units.
Low system pressure.Have qualified service technician check for leaks in boiler or piping
at once.
Domestic water from
tankless heater is hot then
suddenly turns cold.
OR
Domestic water from
tankless heater is always
lukewarm.
Part number 550-141-826/1211
High limit set too low.Have qualified service technician adjust limit to higher setting.
Mineral deposits insulate
Have qualified service technician delime or replace coil.
internal waterways of heater.
Boiler stop-leak compound
has been added to boiler wa-
Have qualified service technician remove and clean coil and drain,
and flush boiler to remove stop-leak.
ter and is insulating outside
of coil.
Incorrect mixing valve setting
Have qualified service technician adjust mixing valve setting.
for tankless heater.
Domestic flow rate too high. Have qualified service technician install flow check valve set to rating
of tankless heater.
Incorrect setting on tankless
heater control.
Have qualified service technician raise tankless control setting. Adjust
differential on tankless control to lower setting.
7
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Before installing boiler
Homeowner — STOP! The procedures and information on this and following pages are intended only for a quali-
fied service technician who has the necessary equipment to inspect and adjust boiler and burner. A homeowner
should never attempt these procedures. The service technician must also read pages 1 through 7 before proceeding.
Installations must comply with
• United States
• State and local plumbing, heating and electrical codes.
• National codes where applicable.
• Canada
•Canadian Standards Association, CSA B139, Installation Code for Oil-
Burning Equipment.
• CSA C22.1 Canadian Electrical Code Part One.
• Applicable local or provincial codes.
Before selecting boiler location
Check for nearby connections to:
• System water piping.
• Chimney. See page 16. Boiler can be top or back vented.
• Combustion and ventilation air supply. See page 9.
• Oil supply. See page 26for oil line routing.
• Electrical power.
• Check area around boiler. Remove any combustible materials, gasoline
and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors
can result in severe personal injury, death or substantial property damage.
Figure 2 Recommended service clearances
Provide clearances around boiler
(see Figure 2)
Jacket cap must be in place on boiler to
avoid requiring an 9" minimum clearance
from back or top of boiler to combustible
material.
• MINIMUM clearances from vent pipe to
combustible material
• 6 inches — Type “L” double-wall vent*
• 9 inches — Single-wall vent*
Flue pipe clearances must take precedence
over jacket clearances.
• Recommended SERVICE clearances
• 24 inches — Front and top
• 6 inches — Left side, back and right side
• 12 inches — Right side for burner door
swing radius
• Special close clearances (alcove, closet, under counters, etc.) — see Appendix, page 32.
Walls
B
A
A
A
Top View
A Provide 6" minimum clearance for service, provide 12"
minimum clearance for burner door swing.
B Minimum clearance from vent pipe to combustible mate-
rial: 6" for type “L” double-wall vent, 9" for single-wall
vent.
8
24"
B
Wall
Left side
B
24"
Part number 550-141-826/1211
Ceiling
Floor
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Before installing boiler (continued)
Provide air for combustion and
ventilation
Do not install exhaust fan in boiler room.
Adequate combustion and ventilation air:
• Assures proper combustion.
• Reduces risk of severe personal injury or death from
possible flue gas leakage and carbon monoxide
emissions.
Older buildings with single-pane windows, minimal
weather-stripping and no vapor barrier often provide
enough natural infiltration and ventilation without
dedicated openings.
New construction or remodeled buildings are most
often built tighter. Windows and doors are weatherstripped, vapor barriers are used and openings in
walls are caulked. As a result, such tight construction
is unlikely to allow proper natural air infiltration and
ventilation.
Follow state, provincial or local codes when sizing
adequate combustion and ventilation air openings. In
absence of codes, use the following guidelines when
boiler is in a confined room (defined by NFPA 31 as
as less than 7200 cubic feet per 1 GPH input of all appliances in area. A room 8 ft. high x 33.5 ft. x 33.5 ft.
is 7200 cu. ft.).
Permanent Openings
Provide two permanent openings, one within 12 inches
of ceiling, one within 12 inches of floor. Minimum
height or length dimension of each rectangular opening
should be at least 3 inches.
Inside air
When inside air is used, each opening must freely
connect with areas having adequate infiltration from
outside. Each opening should be at least 140 sq. in. per
1 GPH input (1 sq. in. per 1000 Btu input) of all fuelburning appliances plus requirements for any equipment that can pull air from room (including clothes
dryer and fireplace).
Outside air
When outside air is used, connect each opening directly
or by ducts to the outdoors or to crawl or attic space
that freely connects with outdoors. Size per below:
• Through outside wall or vertical ducts — at least
35 sq. in. per 1 GPH input (1 sq. in. per 4000 Btu
input) of all fuel-burning appliances plus requirements for equipment that can pull air from room
(including clothes dryer and fireplace).
• Through horizontal ducts — at least 70 sq. in. per 1
GPH boiler input (1 sq. in. per 2000 Btu input) of all
fuel-burning appliances plus requirements for any
equipment that can pull air from room (including
clothes dryer and fireplace).
Where ducts are used, they should have same crosssectional area as free area of openings to which they
connect. Compensate for louver, grille or screen blockage when calculating free air openings. Refer to their
manufacturer’s instructions for details. If unknown,
use:
• Wood louvers, which provide 20-25% free air.
• Metal louvers or grilles, which provide 60-75%
free air.
Lock louvers in open position or interlock with equipment to prove open before boiler operation.
Foundation
Lay a foundation, if needed. Boiler may be installed
on non-carpeted combustible flooring. Solid concrete
blocks can be used to create a pad.
For residential garage installation, install boiler so
burner is at least 18 inches above floor to avoid contact
with gasoline fumes.
A level concrete or masonry foundation is required
when:
• Floor could possibly become flooded.
• Non-level conditions exist.
Table 1 Boiler foundation sizes
Boiler
model
WGO-2
WGO-3
WGO-4
WGO-5
WGO-6
WGO-7
WGO-8
WGO-9
Length
inches
14222
17222
17222
20222
23222
26222
29222
32222
Width
inches
Installation instructions:
Packaged boiler — Continued on page 10
Non-packaged boiler — Continued on page 12
Min.
height
inches
Part number 550-141-826/1211
9
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — packaged boilers only
Place boiler
1. Remove circulator strapped to pallet.
Circulator will be damaged if not removed before boiler is
lifted from pallet.
2. Remove boiler from pallet.
Do not drop boiler or bump jacket on floor or pallet. Damage
to boiler can result.
Smaller sized boilers may be top heavy. Use caution when
handling to avoid minor personal injury or property damage.
3. Boiler is shipped for back flue outlet. To change to top flue outlet (see
Figure 3, page 11):
a. Remove jacket cap on top of boiler.
b. Loosen two screws holding flue cap strap to collector hood. Remove
strap and flue cap from opening. Re-tighten screws.
c. Check rope placement inside flue cap.
(Read
d. Loosen two screws on back flue outlet. Set flue cap on outlet. Install
e. Snap jacket cap in back outlet opening.
4. Check level. Shim legs, if needed.
5. Check for secure placement of insulation on target wall, chamber floor
and burner door.
6. Visually check:
a. Flue collector hood seal.
b. Burner mounting door seal.
under step #6 below).
strap by engaging slots in screws. Tighten screws. Make sure cap is
securely installed.
Jacket cap must be in place on boiler to avoid requiring an 18”
minimum clearance from back or top of boiler to combustible
material.
Obtain gas-tight seal to prevent possible flue gas leakage
and carbon monoxide emissions, which can lead to severe
personal injury or death.
Perform hydrostatic pressure test
1. Remove relief valve installed in boiler.
2. Install air vent in “N” tapping on top boiler.
3. Plug supply and return tappings.
4. Drain valve is already factory-installed.
5. Fill boiler. Vent all air. Pressure test boiler at 1½
times working pressure.
Do not leave boiler unattended. Cold
water fill can expand and damage cast
iron, resulting in severe personal injury,
death or substantial property damage.
6. Check for maintained gauge pressure for more
than 10 minutes. Visually check for leaks if gauge
pressure drops.
7. Drain boiler. Repair leaks if found.
Do not use petroleum-based sealing
compounds to repair leaks. Damage to
system components can result, causing
property damage.
8. Retest boiler after repairing leaks.
9. Remove air vent and plugs. Reinstall relief valve.
10
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — packaged boilers only (continued)
Figure 3 Change from back flue outlet to top flue outlet (optional)
Part number 550-141-826/1211
Instructions for packaged boilers continued on page 15.
11
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — non-packaged boilers only
Fiberglass wool and ceramic fiber ma-
terials are possible cancer hazards. See
warning on page 31.
Place boiler
Non-Packaged WGO-2 through 6 —
position on site
Smaller sized boilers may be top heavy.
Use caution when handling to avoid minor personal injury or property damage.
Boiler is shipped for back flue outlet. To change to top
flue outlet (see Figure 3):
1. Loosen two screws holding flue cap strap to collector hood. Remove strap and flue cap from opening.
Re-tighten screws.
2. Check rope placement inside flue cap.
(Read
3. Loosen two screws on back flue outlet. Set flue cap
on outlet. Install strap by engaging slots in screws.
Tighten screws. Make sure cap is securely installed.
under Step #3 on page 13.)
Non-Packaged WGO-7, 8 & 9 — split the assembled
block for easier handling (see Figure 4, page 13)
1. Open burner mounting door and, using utility knife, slit floor insulation at joint to be separated.
2. Remove 5½" draw rod and the longest draw rod from each side. Pull
block apart. Save draw rods, nuts, washers and sealing rings for reassembly.
3. Move divided block to location.
4. Clean port openings with clean rag.
Do not use petroleum-based compounds to clean openings.
Damage to system components can result, causing property
damage.
5. Place rings in port openings. If ring slips out of groove, stretch ring
gently for several seconds, then place in groove.
6. Position sections so aligning lugs fit into sockets of next section. Make
sure sealing rope is in good condition and in position.
7. Oil threads on draw rods. Install washer and nut on end to be tightened.
Use nut only on other end.
8. With wrench at washer/nut end, uniformly tighten nuts starting with
5½" rod at large port, 5½" rod at small port, bottom long rod and
finally top long rod.
9. Torque on both 5½" rods and bottom long rod should be 50-60 ft. lbs;
long top rod should be 20-25 ft. lbs. Do not back-off nuts.
10. Metal-to-metal contact should be made around port openings. If gap
does exist, it should be less than .020". Check with feeler gauge.
11. If gap around port openings exceeds .020", check for dirt on port
openings, sockets or misaligned lugs. If corrections are made and gap
still exists, contact your Weil-McLain distributor or sales office before
continuing installation.
12
Part number 550-141-826/1211
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — non-packaged boilers only (continued)
1. Thread tinnerman clip on screw so that clip fits snugly in
notch of hold-down lug. Screw must not turn.
2. Remove paper on sealing rope. Starting at back section near
flue collar, position sealing rope around top of block with
adhesive side to sections. Do not stretch rope. Make sure rope
ends meet. Trim excess rope.
3. Position flue collector hood on top of boiler sections and
over screws and clips as shown in Figure 4.
Figure 4 Change from back flue outlet to top flue outlet (optional)
Tinnerman
(see Figure 4)
leakage and carbon monoxide emissions, leading
to severe personal injury or death.
Nut
Washer
clip
Screw
Hold-down
lug
Sealing
rope in
groove
inside cap
4. Install washers and nuts. Tighten nuts until collector hood
makes contact with tinnerman clip.
5. Flue Cap
• Back flue outlet boiler — Position flue cap and strap over
opening in flue collector hood. Make sure rope in cap is
in place and in good condition. Tighten strap to hood
with screws provided.
• Top flue outlet boiler — Position flue cap and strap over
opening in back section. Make sure rope in cap is in place
and in good condition. Tighten strap to boiler with screws
provided in section. Install remaining screws in holes in
flue collector hood.
6. Check level. Shim legs, if needed.
Flue
collector
hood
Sealing
rope with
adhesive
tape
Part number 550-141-826/1211
Flue
cap
Flue cap
strap
Separate
block here
for easier
handling
13
GOLD
WGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — non-packaged boilers only (continued)
Perform hydrostatic pressure test
1. See Figure 5 and Control Tapping table to install:
a. Boiler drain.
b. Water pressure gauge (test only). Be sure gauge can
handle test pressure.
c. Air vent in upper “N” tapping.
d. Plugs in remaining tappings.
2. Fill boiler. Vent all air. Pressure test boiler at 1 times working pressure. For boilers split and reassembled, test between
75 and 85 psig.
Do not leave boiler unattended. Cold water fill
could expand and damage cast iron, resulting in
severe personal injury, death or substantial property damage.
3. Check for maintained gauge pressure for more than 10 minutes. Visually check for leaks if gauge pressure drops.
4. Drain boiler. Repair leaks if found.
Do not use petroleum-based compounds to repair
leaks. Damage to system components can result,
causing property damage.
5. Re-test boiler after repairing leaks.
6. Remove pressure gauge, air vent and plugs from tappings
used for controls.
7. Visually check:
a. Sealing rope placement.
b. Metal-to-metal contact around port openings.
c. Flue collector hood seal.
d. Burner mounting door seal.
Obtain gas-tight seal to prevent possible flue gas
leakage and carbon monoxide emissions, which
can lead to severe personal injury or death.
Install jacket
(sizes 7 through 9 only)
Before installing jacket, remove burner mounting door. See jacket
instructions for details.
Install boiler controls
See Control Tapping Table and Figure 5 and Figure 6, page 15
to install controls.
1. Install limit control. If not furnished, use high limit with
maximum 220°F setting.
2. Affix CP number label(s) on jacket front panel.
Table 2 Control tappings
LocationSizeFunction
B11½"Return piping
B21½"
C1½"Supply piping
E3¼"
H¾"Drain valve
L¾"High limit control
N½"
R1¾"Relief valve
Alternate return piping for
A/B WGO
Pressure-temperature
gauge
Air vent or expansion
tank piping
Figure 5 Control tapping locations
R1
N
E3
B1
Front section
H
C
L
B2
Back section
14
Part number 550-141-826/1211
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.