Weil-McLain 1194, 1294, 1094, 1394, 1494 Series Manual

...
94
Series 3
Water & steam boilers
for use with Gas, Light Oil, & Gas/Light Oil – Fired Burners
Boiler Manual
• Installation
• Maintenance
• Parts
For additional information, refer to . .
Burner specifi cation and data sheets
(for burners pre-tested with model 94 boilers)
This manual must only be used by a qualifi ed
heating installer/service technician. Read all instructions before installing. Follow all instructions in proper order. Failure to comply could result in severe personal injury, death or substantial property damage.
INSTALLER Consider piping and installation when determining
boiler location.
Any claims for damage or shortage in shipment must be
fi led immediately against the transportation company by the consignee.
USER . . . . This manual is for use only by your qualifi ed heating
installer/service technician. Boiler and burner must be installed by a qualifi ed service technician. We recom­mend regular service by a qualifi ed service technician, at least annually.
Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Read before proceeding
Read before proceeding:
Read all instructions before installing. Fail-
ure to follow all instructions in proper order can cause severe personal injury, death or substantial property damage.
Do not use petroleum-based cleaning or
sealing components in boiler system. Severe damage to system components can result, causing substantial property damage.
Propane boilers only — Your propane
supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade and the gas may no longer have an odor.
Propane gas can accumulate at floor level. Smell near the floor for the gas odorant or any unusual odor. If you suspect a leak, do not attempt to light the burner.
Use caution when attempting to light a propane burner (or pilot burner). This should be done by a qualified service technician, particularly if flame out­ages (or pilot outages) are common.
Hazard Definitions
The terms defined below are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.
Indicates presence of hazards that will
cause severe personal injury, death or
substantial property damage if ignored.
Indicates presence of hazards that can
cause severe
substantial property damage if ignored.
Indicates presence of hazards that will or
can cause minor personal injury, death or
substantial property damage if ignored.
Indicates special instructions on installa-
tion, operation or maintenance that are im­portant but not related to personal injury.
personal injury, death or
Periodically check the odorant level of your gas.
Inspect boiler and system at least yearly to make sure all gas piping is leak-tight.
Consult your propane supplier regard­ing installation of a gas leak detector. There are some products on the market intended for this purpose. Your sup­plier may be able to suggest an appro­priate device.
Controls:
One limit control is supplied with the
boiler. A second limit control must be supplied by the installer (field installed) to comply with current ASME Boiler and Pressure Vessel Code, Section IV.
IMPORTANT
When calling or writing about the boiler, please provide:
• Boiler model number
• Series
• CP number
This information is located on the boiler label/nameplate.
2 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Contents
Before installing boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Set boiler in place . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Assembling the block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Perform hydrostatic pressure test . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Control tapping locations — water boilers . . . . . . . . . . . . . . . . . . . . . . 12
Control tapping locations — steam boilers . . . . . . . . . . . . . . . . . . . . . . 13
Connect water boiler piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connect steam boiler piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Complete block assembly & install jacket . . . . . . . . . . . . . . . . . . . . . . . 20
Pipe tankless heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Install water boiler controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install steam boiler controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Connect breeching and venting systems . . . . . . . . . . . . . . . . . . . . . . . 31
Install fuel piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Make final adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Handling ceramic fiber and fiberglass materials . . . . . . . . . . . . . . . . . . . 36
Maintenance and troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Before installing boiler
Installation must comply with —
1. State, provincial and local plumbing, heating and electrical codes.
2. Regulations of servicing utilities.
3. ASME Section IV, Low Pressure Boiler and Pressure Vessel Code.
4. National Fuel Gas Code, ANSI/NFPA 54, when applicable.
5. National codes where applicable.
Before selecting boiler location
1. Check for nearby connections to: a. Fuel supply. b. Electrical power. c. System water or steam piping. d. Venting systems — see page 31. e. Combustion and ventilation air supply — see page 5.
2. Check area around boiler. Remove any combustible materials, gasoline and other flammable vapors and liquids.
Failure to keep boiler area clear and free of combustible
materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death and substantial property damage.
Provide clearance around boiler
1. Provide minimum clearances to combustible materials:
Boiler top24 inches.
Boiler front48 inches.
Boiler flue9 inches.
Boiler rear9 inches.
Boiler sides6 inches.
Single-wall vent pipe18 inches.
Double-wall vent pipe – refer to vent pipe manufacturer's recom-
mendations for vent pipe clearances.
2. Boiler may be installed on combustible flooring.
3. See page 42 for boiler dimensions.
Flue pipe/breeching clearances take precedence over jacket
clearances. Follow local codes requirements for clearances. Increase clearances if necessary.
4. Provide minimum clearances for servicing:
Right side — for cleaning and for tankless heater insertion/re-
moval — 44 inches.
Rear — for breeching — 50 inches.
• Allow sufficient space on remaining sides for cleaning, servicing
and burner installation. See burner literature for length and recom­mended service clearances.
Lay a foundation, if needed
1. Floor construction and condition must be suitable for weight of boiler when filled with water. See page 42 for approximate boiler operating weight.
2. A level concrete or brick foundation, constructed per Figure 1 and Figure 2 is required when: a. A floor could possibly become flooded. b. Non-level conditions exist. c. Boiler must be raised for burner clearance.
Figure 1 Boiler foundation, when required —
always use steel strips as shown for proper draw-up and alignment of
sections
Figure 2 Boiler foundation (see Figure 1)
(boiler sections flush with one end of foundation, 4 inches from the other end)
Boiler model
number
894
994
1094
1194
1294
1394
1494
1594
1694
1794
1894
1994
2094
2194
2294
2394
2494
2594
Height,
H
(inches)
Gun-type burner: 2 inches min.
Horizontal rotary or air atomizing burner: 7 inches min.
Consult burner manufacturer for required clearances if burner is not supplied by Weil-McLain.
Length,
(inches)
55
61
67
73
79
85
91
97
103
109
115
121
127
133
139
145
151
157
L1
4 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Before installing boiler
(continued)
Combustion and ventilation air openings
Adequate combustion and ventilation air must be
provided to assure proper combustion and prevent possibility of flue gas leakage and carbon monoxide emissions, causing severe personal injury or death.
Do not install an exhaust fan in boiler room. Incor-
rect burner operation can result.
When combustion and ventilation air enters
through side wall openings, ensure that the open­ings comply with the requirements of Figure 3 and Figure 4.
Opening sizes must comply with state, provincial or
local codes. In the absence of local requirements, use the National Fuel Gas Code, ANSI/NFPA 54). The following information is taken from ANSI/NFPA 54. For details and information not addressed below, refer to the standard.
Figure 3 Combustion and ventilation air
openings — Boiler room below grade
Figure 4 Combustion and ventilation air
openings — Boiler room partially or completely above grade
Combustion air openings to inside
Required volume of interior spaces
ANSI/NFPA 54 allows combustion air to be supplied through openings to interior spaces if the volume of the connected interior spaces
meets the minimum volume required by the standard.
The minimum volume of interior spaces can be taken as 50 cubic feet per 1,000 Btuh of all appliances in the spaces, or the minimum volume can be calculated using the formulas given in ANSI/NFPA 54. Excep­tion: If the air infiltration rate for the spaces is known to be less than
0.40 air changes per hour, the minimum volume must be calculated as specified in the standard.
Inside air opening sizes and locations
For spaces that provide the minimum volume required by ANSI/ NFPA 54, the air openings must be sized per the following:
Combining spaces on the same story — Each opening shall have
a minimum free area of 1 in2 ⁄1000 Btuh (2200 mm2 /kW) of the total input rating of all appliances in the space but not less than 100 in2 (0.06 m2). One opening shall commence within 12 inches (300 mm) of the top, and one opening shall commence within 12 inches (300 mm) of the bottom, of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (80 mm).
Combining spaces in different stories — The volumes of spaces
in different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in2 ⁄1000 Btuh (4400 mm2 /kW) of total input rating of all appliances.
Combustion air openings to outside
Outdoor combustion air can be taken through per­manent openings (TWO or ONE), as described in the following. The minimum dimension of air openings shall not be less than 3 inches (80 mm).
Outside openings: TWO permanent openings method
Two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclo­sure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that
5Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Before installing boiler
freely communicate with the outdoors, as follows:
• Where directly communicating with the outdoors or
where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of
2
⁄4000 Btuh (550 mm2/kW) of total input rating of
1 in all appliances in the enclosure.
• Where communicating with the outdoors through hori-
zontal ducts, each opening shall have a minimum free area of 1 in rating of all appliances in the enclosure.
Outside openings: ONE permanent opening method
One permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
2
(1) 1 in of all appliances located in the enclosure, and . . .
(2) Not less than the sum of the areas of all vent connectors in the space.
⁄3000 Btu/hr (700 mm2 per kW) of the total input rating
2
⁄2000Btuh (1100 mm2 /kW) of total input
(continued)
Combustion air — combination indoor and outdoor openings
ANSI/NFPA 54 allows combustion air to be taken from a com­bination of openings to outside and to interior spaces. Follow all requirements of the standard to determine the minimum volume of interior spaces and to calculate minimum sizes of openings.
Mechanical Combustion Air Supply
Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft3/minute per 1000 Btuh (0.034 m3/ min per kW) for all appliances located within the space.
• Where exhaust fans are installed in the building, addi­tional air shall be provided to replace the exhausted air.
• Each of the appliances served shall be interlocked to the mechanical air supply system to prevent main burner operation where the mechanical air supply system is not in operation.
• Where combustion air is provided by the building’s me­chanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air.
Louvers, Grilles, and Screens.
The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening.
Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size opening required to provide the free area specified.
Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25 percent free area, and metal louvers and grilles will have 75 percent free area.
Non-motorized louvers and grilles shall be fixed in the open position.
Minimum screen mesh size
Screens shall not be smaller than ¼ inch mesh.
Motorized louvers
Motorized louvers shall be interlocked with the appliance so they
Engineered Installations
Engineered combustion air installations shall provide an ad­equate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.
6 Part No. 550-110-275/1018
are proven in the full open position prior to main burner ignition and during main burner operation. Means shall be proved to prevent the main burner from igniting should the louver fail to open during burner startup, and to shut down the main burner if the louvers close during burner operation.
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Set boiler in place
Ensure the equipment and cables used for lifting are
designed to handle the load. See Figure 5 for approximate weights of model 94 section assemblies. Failure to comply can result in severe personal injury, death or substantial property damage.
The boiler contains ceramic fiber and fiberglass materials.
Use care when handling these materials per instructions on "Handling ceramic fiber and fiberglass materials," page 36 of this manual. Failure to comply could result in severe personal injury.
For packaged boiler or assembled block assembly:
1. Packaged boilers only — Remove top jacket panels. Set aside until after boiler is piped.
2. Remove lag screws from shipping rails.
3. Remove boiler from skid. Cables are already attached to block as­sembly. See Figure 5 for lifting weight.
• Using crane – attach free end of cables to eye of crane.
• Using hoist – attach free end of cables to hoist. Raise boiler
off skid. Use pipe rollers under steel skid angles to roll boiler.
4. Place ¼" x 3" steel plates on floor or foundation, spaced 51 inches apart, as shown in Figure 1, page 4.
5. Place boiler in final position. Place boiler on foundation (if used) as shown in Figure 1, page 4.
6. Level boiler. Shim under legs if necessary.
7. Cut off cables.
Cables are not intended for long-term usage. Cables may
corrode inside boiler, weakening their lifting strength. Failure to remove cables can result in severe personal injury, death or substantial property damage.
8. Inspect block assembly for disjointed sections.
a. Check inside section assembly for any light passing through
unsealed areas. b. Mark all unsealed areas. c. At unsealed areas, check for:
• Damaged gaskets.
• Sealing rope not in place.
• Loose bolts or nuts.
d. Correct all conditions and repeat step b. If unsealed areas still
exist, contact your Weil-McLain distributor or sales office
before continuing installation.
9. Check gas-tight seal of flue collector hood and cleanout plates.
Do not raise or move assembled sections
using a jack or forklift. This could cause the sections to shift, resulting in leaks.
Figure 5
Section assembly lifting weights
Boiler model
number
894 8600
994 9500
1094 10300
1194 11200
1294 12000
1394 12800
1494 13700
1594 14500
1694 15400
1794 16200
1894 17100
1994 17900
2094 18700
2194 19800
2294 20600
2394 21500
Approximate
lifting
weight
(pounds)
Minimum
sling length —
(from crane hook to
boiler lifting lugs)
3' 6"
3' 6"
4' 0"
4' 6"
5' 0"
5' 0"
5' 0"
5' 0"
5' 0"
5' 0"
5' 0"
5' 6"
5' 6"
7' 6"
7' 6"
7' 6"
Gas tight seal must be maintained to prevent possible flue
gas leakage and carbon monoxide emissions, resulting in severe personal injury or death.
10. Proceed to "Perform hydrostatic pressure test," page 11.
2494 22400
2594 23200
8' 0"
8' 0"
7Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Assembling the block
Sections are top heavy. Unbolted sections may fall if not
supported, resulting in severe personal injury or death.
Prepare the back section first
1. Place ¼" x 3" steel plates on the floor or foundation, spaced 51 inches apart, as shown in Figure 1, page 4.
2. Apply
1
8" continuous bead of sealing rope adhesive in sealing rope
grooves around section perimeter and around flueways — see Figure 6.
Do not get any adhesive on the machined port surfaces.
Place sealing rope in grooves
1. Place 5⁄8" coated and uncoated sealing rope in the rope grooves as shown in Figure 6.
2. See WARNING below — place coated rope and uncoated rope as described.
3. Around curves, grasp rope at 1" intervals and push together.
stretch the rope
.
Do not
Figure 6 Sealing rope installation
The boiler is supplied with TWO types of section sealing
rope — uncoated and coated with a narrow uncoated strip.
Use the uncoated rope only on the flueways as shown in
Figure 6.
Use the coated rope around the perimeter and around the
upper nipple port as shown in Figure 6. The uncoated side of the rope must be pressed into the adhesive as shown in order to obtain a proper adhesion.
DO NOT pre-cut rope for sections. Cut rope as each section
is placed.
A gas-tight seal must be maintained to prevent possibility
of flue gas leakage and carbon monoxide emissions, causing severe personal injury or death.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system com­ponents can result, causing substantial property damage.
Install nipple port sealing rings
1. Remove any grit from port machined surfaces with clean rag.
2. Place 9" and 6" sealing rings in appropriate port openings as shown in Figure 6, page 8. If sealing ring slips out of groove, stretch ring gently for several seconds, then reposition in groove.
3. Apply a continuous bead of silicone sealant no larger than entire outside edge of the outer machined surface of the port. See Fig­ure 7. Do not apply silicone sealant on, next to or under sealing ring.
1
16" around
8 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Assembling the block
Silicone sealant applied as specified above
prevents unburned oil vapors from coming in contact with sealing ring. Vapor con­tact can damage rings, resulting in severe damage to boiler and substantial property damage.
Raise the rear section upright
1. Hoist the back section upright.
2. Move rear section into position on the steel rails. The section should be 4 inches from the end of the founda­tion (if used) as shown in Figure 1, page 4.
3. Block under the flueway outlet to hold the rear section upright in plumb position.
The back section must be plumb before in-
stalling other sections to ensure the block will assemble correctly.
4. The blocking under the flueway can be removed later, after several intermediate sections have been attached and the assembly is stable.
5. Install intermediate sections and front section as de­scribed on the following.
(continued)
Figure 7 Applying silicone sealant around outsides of sealing
rings (shown on 94 intermediate section upper nipple port)
Install intermediate sections
1. Remove and discard 3⁄8" diameter shipping tie rods.
2. Remove grit from port machined surfaces with clean rag. Also remove grit from tapped holes in all sections.
Do not use petroleum-based cleaning or
sealing compounds in boiler system. Severe damage to system components can result, causing substantial property damage.
3. Position intermediate section so aligning lugs fit into sockets of next section. See Figure 8.
4. Draw sections together until metal-to-metal contact is made around machined port openings (see Figure 8):
a. Oil threads on (4)
and nut on end to be tightened. Use nut only on other end.
b. Uniformly draw sections together, starting at
washer/nut end.
Important — Leave an equal amount of thread
on each end of the draw rod. This is needed to allow securing the jacket support brackets in place. The draw rods must not extend past the face of the front or back section, or they will interfere with the jacket.
c. Draw rods should be torqued to a range of 100 to
120 ft-lbs. Do not back off draw rods.
d. Metal-to-metal contact will be achieved around port
openings. See Figure 8. If gap occurs, it should be no greater than .032". Check with feeler gauge.
5
8" x 11" draw rods. Install washer
Figure 8 Sealing ring installation and port alignment, typical
Weil-McLain cast iron section nipple port
9Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Assembling the block
e. If, for any reason, the gap around machined port open-
ing exceeds .032", check for rope extending from rope
(continued)
6. Check each section for proper sealing rope position before proceeding to next section.
grooves, dirt on port openings or sockets, or misaligned lugs. If corrections are made and gap still exists, contact your Weil-McLain distributor or sales office before con­tinuing installation.
Failure to position sealing rope properly can
cause boiler to not seal gas-tight. Gas tight seal prevents possible flue gas leakage and carbon monoxide emissions, resulting in severe personal
After erecting first intermediate section, check
injury or death.
both sections for plumb. Repeat the check as each additional section is installed. Failure to plumb sec­tions can cause misaligned piping and breeching,
7. Install remaining intermediate sections and front section using the same procedure.
possibly resulting in property damage.
5. Repeat steps 1-5 for all remaining sections. NOTE — use x 10" draw rods between intermediates. When used, install TI (tankless intermediate) and SI (supply intermediate) sections in the positions shown in Figure 9, page 10.
5
If using tankless heater (TI) sections
8"
• Install tankless heaters and gaskets or heater cover plates and gaskets.
3
• Use
8" x 3⁄4"studs, washers and nuts.
Figure 9 Section arrangement (location of TI and SI sections, numbered from REAR to FRONT of block assembly)
Boiler
W = water S = steam
# of coils ——
894 W or S 5 5, 7 3, 5, 7
994 W or S 6 6, 8 2, 4, 6 2, 4, 6, 8 — 1094 W or S 4 2, 4 2, 4, 7 2, 4, 7, 9 — 1194 W or S 4 2, 4 2, 4, 8 2, 4, 8, 10 — 1294 W or S 4 2, 4 2, 4, 9 2, 4, 9, 11 2, 4, 7, 9, 11 — 1394 W or S 5 3, 5 3, 5, 10 3, 5, 10, 12 3, 5, 8, 10, 12 — 1494 W or S 6 4, 6 2, 4, 6 4, 6, 11, 13 2, 4, 6, 11, 13 2, 4, 6, 9, 11, 13 — 1594 W or S 6 4, 6 2, 4, 6 4, 6, 12, 14 2, 4, 6, 12, 14 2, 4, 6, 10, 12, 14 — 1694 W or S 6 4, 6 2, 4, 6 4, 6, 13, 15 2, 4, 6, 13, 15 2, 4, 6, 9, 11, 13 2, 4, 6, 9, 11, 13, 15 — 1794 W or S 7 5, 7 3, 5, 7 5, 7, 14, 16 3, 5, 7, 14, 16 3, 5, 7, 10, 12, 14 3, 5, 7, 10, 12, 14, 16 — 1894 W or S 8 6, 8 2, 4, 6 2, 4, 6, 8 2, 4, 6, 8, 15 2, 4, 6, 8, 15, 17 2, 4, 6, 8, 11, 13, 15 2, 4, 6, 8, 11, 13, 15, 17 — 1994 W or S 6 4, 6 2, 4, 6 4, 6, 9, 11 2, 4, 6, 9, 11 2, 4, 6, 9, 11, 16 2, 4, 6, 9, 11, 16, 18 2, 4, 6, 9, 11, 14, 16, 18 — 2094 W or S 6 4, 6 2, 4, 6 4, 6, 10, 12 2, 4, 6, 10, 12 2, 4, 6, 10, 12, 17 2, 4, 6, 10, 12, 17, 19 2, 4, 6, 10, 12, 15, 17, 19
If the boiler was ordered with tankless coils, the heaters must be located on the right hand side of the boiler. It is important to position the TI sections (where used) in the exact location in the boiler section assembly as shown above so the heater knockout openings in the jacket side panels will accommodate the heaters. If the TI sections and internal water heaters are not positioned in the boiler section assembly as shown above, the installer must cut openings in the jacket side panels to accommodate the heaters.
>
12 3 4 5 6 7 8
2194 W 6 4, 6 2, 4, 6 2, 4, 6, 9 2, 4, 6, 9, 11 2, 4, 6, 9, 11, 13 2, 4, 6, 9, 11, 13, 16 18, 20 2294 W 6 4, 6 2, 4, 6 2, 4, 6, 10 2, 4, 6, 10, 12 2, 4, 6, 10, 12, 14 2, 4, 6, 10, 12, 14, 17 19, 21 2394 W 6 4, 6 2, 4, 6 2, 4, 6, 9 2, 4, 6, 9, 11 2, 4, 6, 9, 11, 13 2, 4, 6, 9, 11, 13, 15 2, 4, 6, 9, 11, 13, 15, 18 20, 22 2494 W 8 6, 8 2, 4, 6 2, 4, 6, 8 2, 4, 6, 8, 12 2, 4, 6, 8, 12, 14 2, 4, 6, 8, 12, 14, 16 2, 4, 6, 8, 12, 14, 16, 19 21, 23 2594 W 8 6, 8 2, 4, 6 2, 4, 6, 8 2, 4, 6, 8, 11 2, 4, 6, 8, 11, 13 2, 4, 6, 8, 11, 13, 15 2, 4, 6, 8, 11, 13, 15, 17 22, 24
2194 S 2 2, 9 2, 9, 11 2, 9, 11, 13 2, 9, 11, 13, 20 4, 6, 16, 18 2294 S 2 2, 10 2, 10, 12 2, 10, 12, 14 2, 10, 12, 14, 21 4, 6, 17, 19 2394 S 2 2, 9 2, 9, 11 2, 9, 11, 13 2, 9, 11, 13, 15 2, 9, 11, 13, 15, 22 4, 6, 18, 20 2494 S 8 2, 8 2, 8, 12 2, 8, 12, 14 2, 8, 12, 14, 16 2, 8, 12, 14, 16, 23 4, 6, 19, 21 2594 S 8 2, 8 2, 8, 11 2, 8, 11, 13 2, 8, 11, 13, 15 2, 8, 11, 13, 15, 17 2, 8, 11, 13, 15, 17, 24 4, 6, 20, 22
[numbering from REAR to FRONT, beginning with rear section as section number 1]
Placement of special intermediate sections (TI and SI)
TI sections
with tankless coil openings
SI sections
with supply
tappings
10 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Perform hydrostatic pressure test
Install boiler connections
894 – 1294 W
1. Secure supply elbow and gasket to front section and supply outlet cover plate and gasket to back section.
• Use
• Thread flat end of stud into section.
2. Secure 6" NPT return opening counter flange and gasket to back section using ¾" x 2" cap screws and washers.
1394 – 2094 W
1. Secure supply elbow and gasket to front section.
2. Use
3. Thread flat end of stud into section.
4. Secure supply outlet cover plate and gasket to back section.
5. Use
6. Secure 8" pipe with standard 8" flange (not furnished) and gasket (furnished) to back section. Use ¾" x 2" cap screws and washers (furnished).
2194 — 2594 W
1. Secure outlet cover plate with 3 holes (¾" tapping on top) and gasket to front section.
2. Secure outlet cover plate with 2 holes and gasket to back section.
3. Use
4. Secure 10" supply outlets and gaskets on top of "SI" sections.
• Supply outlet should have 1¼" tapping facing front.
• Use
5. Secure 10" flanged return adapter and gasket to back section using ¾" x 2" hex head cap screws and washers.
894 S
1. Secure supply elbow and outlet gasket to front section and supply outlet cover plate and gasket to back section.
• Use
2. Secure 6" return opening counter flange and gasket to back section. Use ¾" x 2" cap screws and washers.
994 — 2094 S
1. Secure supply elbows and outlet gaskets to front and back sections.
• Use
• Thread flat end of stud into section.
2. Secure 6" NPT return opening counter flange and gasket to back section. Use ¾" x 2" cap screws and washers.
2194 — 2594 S
1. Secure outlet cover plates and gaskets to front and back sections.
• The ¾" tappings in plates should be at top.
• Use
5
8" x 3" studs, nuts, and washers.
5
8" x 3" studs, nuts, and washers.
5
8" x 1¾" bolts.
5
8" x 1¾" bolts.
5
8" x 3" studs, nuts, and washers.
5
8" x 1¾" bolts.
5
8" x 3" studs, nuts and washers.
5
8" x 1¾" bolts.
2. Secure 10" supply outlets and gaskets on top of "SI" sections.
• Supply outlet installed close to boiler front should have 1¼" tapping facing front.
• Use
5
8" x 3" studs, nuts, and washers.
3. Secure 6" NPT return opening counter flange and gasket to back section using ¾" x 2" hex head cap screws and washers.
Prepare boiler and test:
1. See Figure 10 (water boilers) or Figure 11 (steam boilers) for tapping locations.
2. Install water pressure gauge — can handle test pressure — see step 8 for required test pres­sure. Gauge range should be at least 1.5 times the test pres­sure. Install the pressure test gauge in the tapping specified in Figure 10 (water boilers) or Figure 11 (steam boilers).
3. Install an air vent in an upper tapping.
4. On front section: Install 3" close nipples and caps in washout tappings.
5. On rear section: Install drain valve (furnished by installer) in one of the washout tappings. (Verify drain valve size per Figure 15, page 15.) Install 2" x 2 other washout tapping.
6. Plug or use blind flanges on remaining tappings.
Do not pressure test with any control installed.
Damage to control can occur due to overpressure.
7. Fill the boiler with water. Vent all air.
8. Pressure test at least 10 minutes at a pressure not less than the following:
a.
Steam boiler: Between 45 and 55 psig.
b.
Water boiler: 1½ times maximum allowable working pressure
(MAWP) stamped on the boiler nameplate,
located on boiler jacket front panel.
Do not exceed above test pressures by more than
10 psig.
Do not leave boiler unattended. Cold water fill
could expand and cause excessive pressure, result­ing in severe personal injury, death or substantial property damage.
9. Check for maintained gauge pressure and leaks. Repair if found.
Leaks must be repaired at once. Failure to do so
can damage boiler, resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to system components can result, causing substantial property damage.
10. Drain boiler and remove air vent, boiler drain and gauge.
11. Remove plugs from tappings that will be used for controls and accessories.
for test only. Be sure gauge
1
2" nipple and cap in the
11Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Control tapping locations — water boilers
Figure 10 Model 94 water boiler control tappings
Item # Function Size
(Inches
NPT)
PRESSURE TEST GAUGE — REMOVE AFTER
J1
HYDROSTATIC TEST
J1 Temperature control or limit
J2 & J5
M3 Probe-type low water cutoff
M1 + M2
M3 + M4
P1 or R1 Temperature control or limit
S1 P/T gauge or temperature gauge
T1 or T2
U1 & U2
V1 Temperature control or limit
PLUG these tappings — not used on water boilers
Float-type low water cutoff or LWCO/feeder
combination
Temperature control or limit — or —
Air vent piping to compression tank
Pressure relief valve(s):
894–2094: Install relief valve in one tapping and plug the other tapping 2194–2594: Install a relief valve in each tapping (2 relief valves required on these boilers)
½
½
½
1
1
3
¾
2
4
W1 or W2
X1 or X2
Y1 & Y2
Z1 or Z2
Z3 or Z4
Temperature control or limit — or —
P/T gauge or temperature gauge
Temperature control or limit — or —
Air vent piping to compression tank
PLUG this tapping — unless needed for a control
Cleanout tappings — Front section — Install 2" NPT
close nipple and 2" NPT cap in each cleanout tapping
Cleanout or drain tappings — Rear section — Install drain valve in one tapping; install 2" NPT x 2½" length nipple and 2" NPT cap in the other
Low limit control (when using tankless heaters) — locate in control tapping on one of the tankless heaters
Controls and fi ttings must not
obstruct cleanout openings or prevent required access to the boiler or components.
¾
3
8
2
2
12 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Control tapping locations — steam boilers
Figure 11 Model 94 steam boiler control tappings
Item # Function Size
PRESSURE TEST GAUGE — REMOVE AFTER
J1
HYDROSTATIC TEST
J1 + J5
M3
M1 + M2
M3 + M4
P1 Skim tapping
P2 Steam pressure relief valve
R1 Skim tapping
R2 Steam pressure relief valve
S1
S2 Pressure controls (limit, operating, etc.)
T1 or T2 Pressure controls (limit, operating, etc.)
T3 or T4
U1 or U2
V1 or V2
W1 or W2
W3 or W4 Pressure controls (limit, operating, etc.)
X1 & X2
X3 & X4
Y1 & Y2 Try cocks
Z1 or Z2
Z3 or Z4
Gauge glass
J2
PLUG this tapping — not used
PLUG this tapping — not used
Float-type low water cutoff, LWCO/pump control or
LWCO/feeder combination
Steam pressure gauge — or —
Pressure controls (limit, operating, etc.)
Steam pressure gauge — or —
Pressure controls (limit, operating, etc.)
Steam pressure relief valve — Install relief valve in
one tapping and plug the other
Steam pressure relief valve — or —
Skim tapping
Steam pressure gauge — or —
Pressure controls (limit, operating, etc.)
PLUG these tappings — not used
PLUG these tappings — not used
Cleanout tappings — Front section — Install 2" NPT
close nipple and 2" NPT cap in each cleanout tapping
Cleanout or drain tappings — Rear section — Install drain valve in one tapping; install 2" NPT x 2½" length nipple and 2" NPT cap in the other
Low limit temperature control (when using tankless
heaters) — locate in control tapping on one of the tankless heaters
(Inches
NPT)
½
½
½
1
1
3
3
4
4
¾
¾
2
4
¾
¾
3
8
2
2
Controls and fi ttings must not
obstruct cleanout openings or prevent required access to the boiler or components.
13Part No. 550-110-275/1018
Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Connect water boiler piping
General water piping information
1. System water supply and return piping should be installed and piping connections attached to boiler before erecting jacket or installing controls.
2. Do not pipe in through supply and out through return. This creates reverse water flow through boiler that must not be used.
3. When installing in a system in which return water temperature can drop below 140°F, apply the by-pass piping with by-pass pump as shown in Figure 16, page 15.
4. When three-way valves are used for temperature modulation, install slow-opening valves to minimize the potential of boiler thermal shock.
Install piping
Install piping as shown in Figure 12, page 14 and Figure 16, page 15 (if applicable) for single boilers. For multiple boilers, see Fig­ure 17, page 15.
Improperly piped systems or undersized piping can
contribute to erratic boiler operation and possible boiler or system damage.
1. Connect supply and return piping: a. Size according to tables below.
• For
• For
known flow rates or higher flow rate (less than 20°F
temperature rise) through boiler, see Figure 13.
unknown flow rates, size piping per Figure 15, page 15,
using 20°F temperature rise through boiler.
Figure 12 Water boiler piping, typical
Flow at higher rates than shown in the tables in this
manual for given pipe sizes can damage the boiler, caus­ing substantial property damage.
b. Locate circulator in supply piping. c. For return piping, use full diameter pipe for 10 times that
diameter before making any reduction. For example, a 4-inch return should not be reduced any closer to boiler return tap­ping than 40 inches.
d. Install system blow-off (drain) valve in lowest part of return
piping close to boiler. ASME minimum size requirements are given in Figure 15, page 15.
2. Install expansion tank: a.
Closed type – connect to 1
1
4" tapping T1, T2 or X2 (see Figure 10, page 12). Use 1" NPT piping. Any horizontal pip­ing must pitch up toward tank at least 1 inch per each 5 feet of piping.
b.
Diaphragm type – Refer to tank manufacturer's literature for
location. Install automatic air vent in 1
1
4" tapping T1, T2 or
X2 (see Figure 10, page 12).
c. Connect cold water fill to expansion tank piping. Figure 12
shows typical piping when using a closed type tank. Connect to the same location as the expansion tank connects to the system when using a diaphragm type tank.
d. Also shown are recommended valves and water meter, when
used. Water meter will detect added make-up water, indicating leaks in system.
Figure 13 Recommended minimum pipe sizes for
known flow rates
Water flow
rate, GPM
up to 77
78 – 132
133 – 208
209 – 300
301 – 520
521 – 820
Note 1 High temperature rise through boiler is per missible when boiler
Supply pipe sizeAReturn pipe size
3" 3"
4" 4"
5" 5"
6" 6"
8" 8"
10" 10"
piping connections are sized per this table. Intermittent flow at high velocities may damage any boiler.
(note 1)
B
14 Part No. 550-110-275/1018
Boiler manual: • Installation • Start-Up • Maintenance • Parts
Connect water boiler piping
Figure 14 Recommended minimum pipe sizes when flow rate is
994 – 1294
1394 – 2094
2194 – 2594
Note 1 Pipe sizes are based on a 20°F temperature rise through the boiler. For
Figure 15 ASME drain valve size
not known (see Figure 12, page 14)
Boiler model
894
applications with higher flow rates (lower temperature rise), determine the flow rate and use Figure 13, page 14 to size the piping. DO NOT use flow rates in excess of 520 GPM through 894–2094 or 820 GPM through 2194–2594.
Boiler model
894 – 994
1094 – 2194
2294 – 2594
Supply pipe size
A
5" 5"
6" 6"
8" 8"
10" 10"
Minimum drain/blow-off
(note 1)
Return pipe size
B
valve size
1¼"
1½"
2"
(continued)
Figure 16 By-pass piping for return water less
than 140°F
By-pass circulator sizing:
1. Size system circulator as required. Determine GPM and head requirements.
2. Provide a by-pass circulator for EACH boiler. The flow rate for each by-pass circulator will be:
Flow = ¼ x (System circulator GPM) ÷ (# of boilers)
3. All circulators must run at the same time.
4. Example: For a 1,000,000 Btuh single boiler, with system temperature drop of 20°F:
• System GPM = 1,000,000 ÷ 20 ÷ 500 = 100 GPM
• By-pass GPM = ¼ x 100 GPM = 25 GPM
• Determine by-pass circuit head loss for pipe size
and fittings used.
5. In most applications, a standard booster pump should be adequate.
Piping multiple boilers
1. See Figure 16. (Expansion tanks, relief valves and other accessories are required, but omitted from the illustration for simplicity.)
2. The boiler piping circuits are referred to as the secondary circuits in the following.
3. The legend for Figure 16 and boiler pump sizing recommenda­tions follow:
A Size boiler pump GPM based on the following:
a. Temp rise = High limit temp – Return water temp
b. GPM =
c. Calculate only secondary (boiler) piping circuit resistance. Al-
low for head loss through the boiler equal to three 90 degree elbows of secondary pipe size.
d. Operate each boiler and its pump with a Weil-McLain boiler
control panel.
e. Size secondary (boiler) circuit piping using the flow rate ranges
given in Figure 15.
B Primary pump GPM and head calculation should not include
secondary boiler circuits. Primary pump can operate continuously during heating season.
C Connection to primary circuit — Space 12" maximum or as close
as practical.
D Check valve.
E Hand valve.
Boiler Gross Output, Btuh
Temperature rise x 500
Figure 17 Multiple water boiler piping
15Part No. 550-110-275/1018
Loading...
+ 33 hidden pages