Weigel A1U 2.2, V1U 2.2 Product Manual

Page 1
Product Guide 800.U.001.01
Transducers
x
y
=
P/Q
=
f
=
=
=
=
=
=
=
=
RS232 RS485
RS232 RS485
RS232
RS485
for AC Current or AC Voltage:
A1U / V1U 2.2 – also self-powered: AU / VU 2.0
for Active or Reactive Power
in single phase systems: EW / EB 2.2 in balanced or unbalanced load 3āĆāphase systems: DGW / VGW / DUW / VUW / DGB / VGB / DUB / VUB 2.2
Programmable Multi-Functional Transducer: MMU 3.0for Frequency: FU 2.2
for Phase Angle (cos
ϕ): CU 2.2
for DC Current or DC Voltage: AUD / VUD 2.2for RMS Current or RMS Voltage: AUE / VUE 2.2for Temperature: PTU 2.0Isolation Transducers for Standard Signals: TUA 2.2
also self-powered: TUP 2.0
Standard Signal Interface Converter: MU-RS232/485RS232-RS485 Converter: AP-RS232/485
SMD and microprocessor controlled technology
Accuracy: class 0.5
Mounting on DIN-rail 35 mm
Case width: 22.5 mm each module
Auxiliary supply AC 115/230 V (50/60 Hz), DC 24 V
or wide range supply
Page 2
General Data
Transducers
=
x
Application
Transducers convert power current and voltage quantities or proccess control inputs into proportional load independent DC current or voltage outputs.
for measuring AC current or AC voltage,
active or reactive power, frequency, phase angle (ϕ ) / power factor (cos ϕ ), DC current or DC voltage, standard signals, temperature
Technical Data
case details projecting case clamping to DIN mounting rail
(to DIN EN 50 022 – 35)
material of case ABS/PC black
self - extinguishing to UL rating 94 V–0 terminals screw - terminals wire cross - section 4 mm
2
max.
enclosure code IP 40 case
IP 20 terminals dielectric test 3.7 kV measuring circuits and power supply
to output class of protection II excess voltage CAT II
category pollution level 2 climatic suitability climatic class 3 acc. to VDE/VDI 3540 sheet 2 operating temperature –10 ... +55
o
C
range storage temperature –25 ... +65oC
range relative humidity 75% annual average, non- condensing
Outputs
current output
output current I
A
load independent DC current 0 ... 20 mA
or optionally 0 ... 10 mA, 0 ... 5 mA,
4 ... 20 mA (”live zero”), –20 ... 0 ... 20 mA
(bipolar output only with wide range supply) load range R
A
0 ... 10 V / I
AN
current limitation to approx.120% of full–scale value,
other ratings on request
voltage output
output voltage U
A
load independent DC voltage 0 ... 10 V or
optionally 2 ...10 V (”live zero”), –10 ... 0 ... 10 V
(bipolar output only with wide range supply) load R
A
4 kW load error 0.1% based on 50% load change residual ripple 1%
rms
response time approx. 500 ms idling voltage 15 V (Ratings do not apply completely to self - powered transducers.)
Auxiliary Supply
auxiliary voltage UHN230 V AC (195 ... 253 V), 48 ... 62 Hz
optional 115 V AC (98 ... 126 V), 48 .. 62 Hz
24 V DC (20 ... 72 V) wide range supply 20 ... 100 V DC resp. 20 ... 70 V AC
90 ... 357 V DC resp. 65 ... 253 V AC galvanic isolation between input, output and auxiliary supply circuits
Short Form Data
Transducers for AC Current or AC Voltage
A1U 2.2 V1U 2.2
=
J/U
Inputs
input quantity sinusoidal AC current or
sinusoidal AC voltage
frequency range 48 ... 62 Hz or
16
2
/3 Hz, 100 Hz, other ratings on request power consumption 0.4 VA operating voltage 600 V max.
measuring ranges A1U 2.2 V1U 2.2
rated current I
EN
rated voltage U
EN
in the range 0 ... 200 mA up to 5 A 0 ... 60 mV up to 600 V
(also for use on transformer)
current input voltage input
measuring range 0 ... I
EN
0 ... U
EN
modulation range 1.2 I
EN
1.2 U
EN
permissible 1.2 I
EN
continuously 1.2 U
EN
continuously
overload limit 10 I
EN
1 s max. 2 UEN 1 s max.
Other Ratings
outputs refer to General Data accuracy class 0.5 (±0.5% of end value) auxiliary voltage refer to General Data dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.12 kg
for detailed information refer to Data Sheet No. 061.## prices refer to Price Sheet No. 061.##
Page 3
Short Form Data
Transducers for AC Current or AC Voltage,
Self-Powered AU2.0 VU 2.0
=
J/U
Inputs
input quantity sinusoidal AC current (AU 2.0)
sinusoidal AC voltage (VU 2.0)
frequency range 48 ... 62 Hz power consumption voltage transformer < 3 VA
current transformer 5A < 4 VA
current transformer 1A < 2 VA
operating voltage 600 V max.
measuring ranges AU 2.0 VU 2.0
rated current I
EN
rated voltage U
EN
1 A *), 1.2 A, 57.7 V, 63.5 V,
5 A *), 6 A 100 V *), 110 V *),
150 V, 250 V, 400 V,
other rating on request 500 V, 600 V
*) also for use on transducer
measuring range 0 ... I
EN
0 ... U
EN
modulation range 1.2 I
EN
1.2 U
EN
overload limit 1.5 I
EN
continuously 1.2 U
EN
continuously
10 I
EN
1 s max. 2 UEN 1 s max.
Outputs
current output
output current I
A
load independent DC current
rated current IAN0 ... 20 mA load range R
A
0 ... 500 W
load error 0.4% based on 50% load change idling voltage 20 V
accuracy class 0.5 (±0.5% of end value)
Other Ratings
auxiliary voltage none required dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.35 kg
for detailed information refer to Data Sheet No. 045.## prices refer to Price Sheet No. 045.##
Short Form Data
Transducers for Active and Reactive Power
EW 2.2 EB 2.2 DGW 2.2 VGW 2.2 DUW 2.2 VUW 2.2 DGB 2.2 VGB 2.2 DUB 2.2 VUB 2.2
=
P/Q
with mP
Inputs
input quantity sinusoidal AC current / voltage measuring unit P
E
active or reactive power type active / reactive power single-phase AC system EW 2.2 EB 2.2
3 - phase 3 - wire system balanced load DGW 2.2 DGB 2.2 3 - phase 4 - wire system balanced load VGW 2.2 VGB 2.2 3 - phase 3 - wire system unbalanced load DUW 2.2 DUB 2.2 3 - phase 4 - wire system unbalanced load VUW 2.2 VUB 2.2
measuring range 0 ... P
N
or –PN ... 0 ... P
N
PN= (0.3 ... 1.5).P
S
PS = U.I (single-phase AC system)
P
S
= 3.U.I (3 - phase systems) rated input voltage UEN ranging from 50 V to 600 V rated input current IEN1 A or 5 A (also for use on transformer)
or ranging from 0.5 to 5 A
modulation range 1.2 U
EN
and 1.2 I
EN
overload limits 1.2 UEN, 1.2 I
EN
continuously
2 U
EN
, 10 IEN 1 s max. frequency range 48 ... 62 Hz power consumption <1 mA each voltage circuit
0.1 VA each current circuit for I
EN
= 1 A
1.6 VA each current circuit for IEN = 5 A
Other Ratings
outputs refer to General Data accuracy class 0.5 (±0.5% of end value) auxiliary voltage refer to General Data dimensions WxHxL 45 mm x 80 mm x 115 mm weight approx. EW/B 2.2
DGW/B 2.2 DUW/B 2.2 VGW/B 2.2 VUW/B 2.2
0.27 kg 0.29 kg 0.31 kg
for detailed information refer to Data Sheet No. 062.## prices refer to Price Sheet No. 062.##
Page 4
Short Form Data
Transducer for Frequency
FU 2.2
=
f
with mP
Inputs
input quantity AC voltage measuring unit frequency f
E
f
Emin
14 Hz
f
Emax
500 Hz
measuring ranges f
Emin
... fN ... f
Emax
Df class 45 ... 50 ... 55 Hz 10 Hz 0,2 48 ... 50 ... 52 Hz 4 Hz 0,3 55 ... 60 ... 65 Hz 10 Hz 0,2 58 ... 60 ... 62 Hz 4 Hz 0,5
360 ...400 ... 440 Hz 80 Hz 0,2 380 ...400 ... 420 Hz 40 Hz 0,2
other ratings on request (Df = f
Emax–fEmin
)
rated input voltage U
EN
100 V, 110 V, 115 V, 120 V, 230 V, 240 V, 380 V
,
400 V, 415 V
,
440 V
overload limit 1.2 U
EN
continuously
2 U
EN
1 s max.
current consumption 1 mA
Other Ratings
outputs refer to General Data accuracy refer to measuring ranges auxiliary voltage refer to General Data dimensions WxHxL 45 mm x 80 mm x 115 mm weight approx. 0.22 kg
for detailed information refer to Data Sheet No. 064.## prices refer to Price Sheet No. 064.##
Short Form Data
Transducer for Phase Angle (cos )
CU 2.2
=
with mP
Inputs
input quantity sinusoidal AC current / voltage measuring unit phase angle ϕ (power factor) in
E single -phase AC system or D 3 -phase 3 -wire balanced load system
measuring ranges
-37° ... 0 ... 37° corresponds to cos ϕ : cap 0.8 ... 1 ... 0.8 ind
-60° ... 0 ... 60° corresponds to cos ϕ : cap 0.5 ... 1 ... 0.5 ind
optional to be specified ranging from
-85° ... 0 ... 85° corresponds cos ϕ : cap 0.087 ... 1 ... 0.087 ind rated input voltage U
EN
ranging from 50 V to 600 V
rated input current IEN1 A or 5 A (also for use on transformer)
or ranging from 0.5 to 5 A
modulation range 1.2 U
EN
and 1.5 I
EN
overload limits 1.2 UEN, 1.6 I
EN
continuously
2 U
EN
, 10 IEN 1 s max. frequency range 48 ... 62 Hz power consumption <1 mA each voltage circuit
0.1 VA each current circuit for I
EN
= 1 A
1.6 VA each current circuit for I
EN
= 5 A
Other Ratings
outputs refer to General Data accuracy class 0.5 (±0.5% of end value) auxiliary voltage refer to General Data dimensions WxHxL 45 mm x 80 mm x 115 mm weight approx. 0.27 kg
for detailed information refer to Data Sheet No. 063.## prices refer to Price Sheet No. 063.##
Page 5
Short Form Data
Programmable Multi-Functional Trans­ducer for AC Currents, AC Voltages and Powers
MMU 3.0
=
RS232 RS485
with mP
Inputs
input quantities AC current and AC voltage
in single phase or 3 phase system
voltages L1, L2, L3 (3 terminals), N (1 terminal) 600V (inter -connected) or optional N/120V (also for N/100V or N/110V)
currents I1, I2, I3 (6 terminals)
N/5 A or optional N/1.2 A (also for N/1 A)
Measuring Quantity
Total L1 L2 L3
voltage (U) U U
1
U
2
U
3
current (I) I I
1
I
2
I
3
active power (P) P P
1
P
2
P
3
reactive power (Q) Q Q
1
Q
2
Q
3
apparent power (S) S S
1
S
2
S
3
active factor (PF) PF PF
1
PF
2
PF
3
reactive factor (QF) QF QF
1
QF
2
QF
3
phase angle (PH) PH PH
1
PH
2
PH
3
frequency (f) F
Depending on power system, not all these values van be measured.
10 V measuring input
INP (±10 V)
Other Ratings
analog output 1 voltage & current synchronous
(2 terminals each) refer to General Data
interfaces RS 232 (SUB–D jack), RS 485 (2 terminals)
digital output contactāĆāfree via opto coupler
1, 2, or 3 additional analog outputs (galvanically isolated) and up to 8 additional digital outputs (galvanically isolated) are optional
accuracy class 0.5 (±0.5% of end value) auxiliary voltage wide range supply refer to General Data dimensions basic version: 3 modules in single - phase
resp. 4 modules in three - phase systems, optional outputs: additional 1 to 3 modules
each module WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.6 kg (basic version)
for detailed information refer to Data Sheet No. 055.## prices refer to Price Sheet No. 055.##
Short Form Data
Transducers for
Active Power and
Reactive Power
DUW 2.1 DUB 2.1 VUW 2.1 VUB 2.1
=
P/Q
Inputs
input rating sinusoidal AC current and
sinusoidal AC voltage
input quantity P
E
active or reactive power
type active / reactive power 3 - phase 3 - wire system unbalanced load DUW 2.1 DUB 2.1
3 - phase 4 - wire system unbalanced load VUW 2.1 VUB 2.1 measuring range 0 ... P
N
or –PN ... 0 ... P
N
PN= (0.3 ... 1.5).P
S
PS = 3.U.I
rated input voltage U
EN
65 V, 100 V, 110 V, 240 V, 400 V, 415 V, 440 V,
500 V, 600 V or deviating from standard inputs
ranging from 0 ... (60 V ... U
EN
... 600 V)
rated input current I
EN
N/1 A, N/5 A or deviating from standard inputs
ranging from 0 ... (0,5 A ... I
EN
... 5 A)
modulation range 1.2 U
EN
and 1.2 I
EN
overload limits 1.2 UEN, 1.2 I
EN
continuously
2 U
EN
, 10 IEN 1 s max.
frequency range 50 Hz (48 ... 52 Hz) or
162/3 Hz, 60 Hz, 100 Hz, others on request
power consumption <1 mA each voltage circuit
0.1 VA each current circuit for IEN = 1 A
1.6 VA each current circuit for IEN = 5 A
Other Ratings
outputs refer to General Data accuracy class 0.5 (±0.5% of end value) auxiliary voltage refer to General Data dimensions WxHxL 45 mm x 80 mm x 115 mm weight DUW/DUB 2.1 VUW/VUB 2.1
approx. 0.29 kg approx. 0.31 kg
for detailed information refer to Data Sheet No. 051.## prices refer to Price Sheet No. 051.##
Page 6
Short Form Data
Transducers for DC Current/Voltage, RMS Current/Voltage,
Isolating Transducers AUD2.2 VUD 2.2 AUE 2.2
VUE 2.2 TUA 2.2
=
J/U
Inputs
current input voltage input
measuring range 0 ... I
EN
0 ... U
EN
modulation range 1.2 I
EN
1.2 U
EN
overload limit 1.2 IEN continuously 1.2 U
EN
continuously
10 I
EN
max. 1 s 2 UEN max. 1 s
power consumption 0.4 VA
model
input quantities rated input value
AUD 2.2 DC current
IEN = 200 mA – 5 A
VUD 2.2 DC voltage UEN = 60 mV – 600 V
AUE 2.2
nonāĆāsinusoidal AC current (true RMS value) *)
IEN = 200 mA – 5 A
VUE 2.2
nonāĆāsinusoidal AC voltage (true RMS value) *)
UEN = 60 mV – 600 V
TUA 2.2 DC standard signals IEN = 20 mA
U
EN
= 60 mV, 10 V
*) also for use on transformer
AUE/VUE 2.2:
frequency range 48 ... 62 Hz or
16
2
/3 Hz, 100 Hz, other ratings on request
crest factor 4 (peak value / rms value)
Other Ratings
outputs refer to General Data
as an option selectable from standard output ratings
via jumpers located behind front panel
accuracy class 0.5 (±0.5% of end value) class 0.2 (±0,2% of end value) only for DC models on request
auxiliary voltage refer to General Data dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.12 kg
for detailed information refer to Data Sheet No. 061.## prices refer to Price Sheet No. 061.##
Short Form Data
Isolating Transducer for Standard Signals, Self-Powered
TUP 2.0
=
=
Single or Dual Channel
Inputs
input quantity IEDC current rated input IEN20 mA
current measuring range 0 ... I
EN
modulation range 1.2 I
EN
overload limit 2 IEN max. continuously
max. input voltage 16 V permissible
power consumption 2.4 V based on 20 mA
Outputs
current output
output current IAload independent DC current rated current I
AN
0 ... 20 mA load range RA0 ... 500 W (rated load 250 W) load error 0.1% based on 50% load change residual ripple 30 mV
ss
idling voltage 25 V response time 0.05 s based on R
A max
Input and output are galvanically isolated.
Other Ratings
accuracy class 0.2 (±0.2% of end value) auxiliary voltage none required dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.12 kg dual channnel unit on request
for detailed information refer to Data Sheet No. 049.## prices refer to Price Sheet No. 049.##
Page 7
Short Form Data
Standard Signal Interface Converter
MU­RS232/485
=
RS232 RS485
with mP
Inputs
input quantity IEDC current or
UEDC voltage
rated input input resistance
current I
EN
20 mA 50 W
voltage U
EN
10 V / 1 V 1 MW / 100 kW
measuring range current input voltage input
0 ... I
EN
0 ... U
EN
“live zero” option
modulation range, 1.2 I
EN
1.2 U
EN
admissible overload limit
continuously 1.2 I
EN
1.2 U
EN
1 s max. 2 I
EN
2 U
EN
Interfaces
type RS 232 (V.24) and
RS 485 (SCPI commands) Baud-rate 19200 Baud as an option: switching output 8 ... 40 V DC / 10 ... 30 mA
open collector insulation voltage 1 kV switching output for voltages up to 230 V AC/DC
MOS FET and currents up to 100 mA
insulation voltage 3 kV
Other Ratings
accuracy ±0.1% and ±1 count
(for 0 ... IEN resp. 0 ... UEN )
auxiliary voltage refer to General Data dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.12 kg
for detailed information refer to Data Sheet No. 052.## prices refer to Price Sheet No. 052.##
Short Form Data
RS232-RS485 Converter
AP­RS232/485
RS232
RS485
Function
The converter is directly plugged to a 9 -contact serial interface of a PC. It converts the RS232 signals of the PC into standardized RS485 signals. This conversion enables to simultaneously connect several devices by a 2 - wire junction to one interface and to inquire one after another.
The device is protocol - transparent, i.e. the RS485 signals are trans­lated 1:1 into the signals of the RS232 interface.
Depending on the 2 - wire junction of the RS485, a half- duplex opera­tion only will be possible. This means, only one device may send in the network at a time. By that a simultaneous operation of sending and receiving will not be possible.
Ratings
case details metalized thermoplastic case terminals SUB - D 9 contact (RS232 interface on the PC)
screw - terminals 2 contacts, wire - cross section 4 mm
2
max.
(RS485 interface)
auxiliary supply power adapter prim. AC 230 V, ±10%, 50 Hz,
sec. DC 9 V / 250 mA included with supply
dimensions 73 mm x 34 mm x 12 mm weight approx. 50 g
RS 485
RS 232
120 W
120 W
MUāĆāRS232/485
~
=
U
H
for detailed information refer to Data Sheet No. 054.## prices refer to Price Sheet No. 054.##
Page 8
=
Short Form Data
Transducers for Temperature (Pt 100)
PTU 2.0 L
Inputs
input quantity temperature (for RTD Pt 100)
Initial Temperature T
E1
Spans DT
– 200 °C 100 K – 150 °C 150 K – 100 °C 200 K – 50 °C 300 K
0 °C 400 K + 50 °C 500 K +100 °C 600 K +150 °C 700 K (for T
E1
100°C only)
+200 °C 800 K (for T
E1
0°C only)
900 K (for T
E1
–100°C only)
1000 K (for T
E1
= –200°C only)
or deviating from standard values in the range of 100 ... 1000 K measuring range T
E1
... TE2 = TE1 + DT input potential–free differential input connection 2–, 3– or 4–wire system
Outputs
current output
output current I
A
load independent DC current
rated current I
AN
4 ... 20 mA load range RA0 ... 500 W (based on 20 mA) load error 0.1% based on 50% load change residual ripple 1%
rms
of IAN with load R
AN
idling voltage 16 V response time 1 s based on R
A max
Other Ratings
accuracy ±0.5% referred to the span DT auxiliary voltage refer to General Data dimensions WxHxL 22.5 mm x 80 mm x 115 mm weight approx. 0.12 kg
for detailed information refer to Data Sheet No. 050.## prices refer to Price Sheet No. 050.##
WEIGEL - MESSGERÄTE GmbH
P.O.B.Ă720ā154 S DĆ90241 Nürnberg S Telephone: 0911ā/ā4ā23ā47Ćā0 Erlenstraße 14 S DĆ90441 Nürnberg S Fax: 0911ā/ā4ā23ā47Ćā39 Internet: http://www.weigel-messgeraete.de e-mail: vertrieb@weigel-messgeraete.de
– specifications subject to change without notice; date of issue 02/06 –