Weidmuller Thermo Signal Conditioners for current User Manual

WAVESERIES Thermo Signal Conditioners for Current and Voltage Output
Type Cat. No.
Screw-type connection WTS4 Thermo Select 8432300000
Tension clamp connection WTS4 Thermo Select 8432310000
15
1 General instructions
The WAVESERIES Thermo signal conditioner should only be installed by qualified staff. The Thermo signal conditioner should only be powered up following professional installation.
2 Application
WAVESERIES Thermo signal conditioners can be used to con­nect to the following thermocouple types: K, J, T, E, N, R, S and B. The temperature range and the type of thermocouple can be set by the DIP switches on the printed circuit board.
Note!! The Thermo signal conditioner only processes signals
Insulated from housing.
16
from fully insulated thermocouples.
3 Mounting and dismounting
Warning!! Mounting and dismounting may only be carried out
when the power supply has be disconnected. Failure to observe will lead to considerable damage!
3.1 Mounting onto TS 35 DIN rails
(s. Fig. 1)
3.2 Pluggable electronic components for range alteration (depending on model)
(s. Fig. 2)
1. Remove connector, (depending on model either screw-type or tension clamp).
2. Press locking clips on both sides of the enclosure.
3. Pull out the circuit board.
Warning!! The circuit board can only be inserted in one
position. The connectors have been coded by the manufac­turer, ensuring that they cannot be reversed.
17
3.3 Pluggable cross-connections for voltage supply
(s. Fig. 3)
A maximum feed through of 2 A is possible. If a signal conditioner is accidently rotated through 180°, the cross-connection cannot be inserted.
3.4 Labelling possibilities
(s. Fig. 4)
WS 10 connector markers can be used to label module.
4 Calibration
Warning!! The power supply must be disconnected, before
Note!! The module calibrates itself, when using the DIP
18
changing the signal conditioner settings using the DIP switches. Failure to observe will lead to considerable damage!
switches on the printed circuit board to set the temperature range.
4.1 Setting the DIP switches
Warning!! The Thermo signal conditioner must be protected
against a direct electrostatic discharge when setting the DIP switches.
Thermocouple types
DIP switch 1
Type 1 2 3 KONONON J OFF ON ON T ON OFF ON E OFF OFF ON N ON ON OFF R OFF ON OFF S ON OFF OFF B OFF OFF OFF
19
Selecting the min. temperature
T
min
4567
0 °C ON ON ON ON
-10 °C ON ON ON OFF
-20 °C ON ON OFF ON
-30 °C ON ON OFF OFF
-40 °C ON OFF ON ON
-50 °C ON OFF ON OFF
-100 °C ON OFF OFF ON
-200 °C OFF ON ON ON +50 °C OFF ON ON OFF
-100 °C OFF ON OFF ON +150 °C OFF ON OFF OFF +200 °C OFF OFF ON ON +250 °C OFF OFF ON OFF +500 °C OFF OFF OFF ON Special range OFF OFF OFF OFF
20
DIP switch 1
Selecting the temperature span
Span 1 2345
DIP switch 2
100 °C ON ON ON ON ON 150 °C ON ON ON ON OFF 200 °C ON ON ON OFF ON 250 °C ON ON ON OFF OFF 300 °C ON ON OFF ON ON 350 °C ON ON OFF ON OFF 400 °C ON ON OFF OFF ON 450 °C ON ON OFF OFF OFF 500 °C ON OFF ON ON ON 550 °C ON OFF ON ON OFF 600 °C ON OFF ON OFF ON 650 °C ON OFF ON OFF OFF 700 °C ON OFF OFF ON ON 750 °C ON OFF OFF ON OFF 800 °C ON OFF OFF OFF ON 850 °C ON OFF OFF OFF OFF 900 °C OFF ON ON ON ON 950 °C OFF ON ON ON OFF 1000 °C OFF ON ON OFF ON
21
1050 °C OFF ON ON OFF OFF 1100 °C OFF ON OFF ON ON 1150 °C OFF ON OFF ON OFF 1200 °C OFF ON OFF OFF ON 1250 °C OFF ON OFF OFF OFF 1300 °C OFF OFF ON ON ON 1350 °C OFF OFF ON ON OFF 1400 °C OFF OFF ON OFF ON 1450 °C OFF OFF ON OFF OFF 1500 °C OFF OFF OFF ON ON 1600 °C OFF OFF OFF ON OFF 1700 °C OFF OFF OFF OFF ON 1800 °C OFF OFF OFF OFF OFF
Warning!! Should a temperature range be selected, that is
22
above the maximum possible range, then the module sets itself to the greatest possible range.
Output 6 7 0 ... 10 V ON OFF 0 ... 20 mA OFF OFF 4 ... 20 mA OFF ON
DIP switch 2
Filter 8
DIP switch 2
OFF OFF ON ON
5 Electrical connection
(s. Fig. 5)
6 Dimensions
(s. Fig. 6)
23
7 Notes on CE labelling of WAVESERIES modules
WAVESERIES modules, that carry CE-labelling, fulfil the requirements of the EU-Guidelines 89/336/EU “electromagnetic compatibility” and the therein listed harmonised European Norms (EN). The declarations of conformity are, in accordance with the above­mentioned EU-Guideline, Article 10, held at the following address for the relevant authorities:
8 Technical data Input
Thermocouple according to IEC 584 (fully insulated) Thermocouple types K, J, T, E, N, R, S, B adjustable by
Selecting the min. temperature adjustable by DIP switches Selecting the temperature span adjustable by DIP switches
24
Weidmüller Interface GmbH & Co. Postfach 3030 D-32720 Detmold
DIP switches
Accuracy (at 23 °C ambient temperature) Type K -200 ... -150 °C ±5 K +0.1 K from span
-150 ... 1200 °C ±3 K +0.1 K from span
1200 ... 1372 °C ±4 K +0.1 K from span
Type J -200 ... -150 °C ±4 K +0.1 K from span
-150 ... 1200 °C ±3 K +0.1 K from span
Type T -200 ... -150 °C ±5 K +0.1 K from span
-150 ... 400 °C ±3 K +0.1 K from span
Type E -200 ... -150 °C ±4 K +0.1 K from span
-150 ... 1000 °C ±3 K +0.1 K from span
Type N -200 ... -150 °C ±6 K +0.1 K from span
-150 ... 1300 °C ±3 K +0.1 K from span
Type R -50 ... 200 °C ±10 K +0.1 K from span
-200 ... 1760 °C ±6 K +0.1 K from span
Type S -50 ... 200 °C ±10 K +0.1 K from span
Type B 50 ... 250 °C ±25 K +0.1 K from span
Temperature coefficient ± (200 ppm from span + 0.075 K) / K
200 ... 1760 °C ±6 K +0.1 K from span
250 ... 500 °C ±10 K +0.1 K from span 500 ... 1820 °C ±6 K +0.1 K from span
25
Step response time max. 1.1 s
- with active filter function: max. 6 s
Open-circuit recognition output signal > 10 V or > 20 mA,
LED blinking Sensor current for open-circuit recognition typ. 0.25 µA
Output
Output signal adjustable using DIP switches Turning on the filter function adjustable using DIP switches Output offset voltage max. 0.05 V Load resistance 1 k Output offset current max. 100 µA Load resistance 500
Connection data
Connection BLZ/SL Insulating stripping length 8 ± 0.5 mm Solid core 0.5 ... 2.5 mm Flexible core 0.5 ... 2.5 mm With ferrules 0.5 ... 1.5 mm
2 2 2
26
EMC specification according to EN 55011, class B,
group 1
according to EN 50081-1
according to EN 50082-2
General
Current consumption
- by current output 28 mA ... 33 mA ... 38 mA
I
= 20 mA
out
- by voltage output 18 mA ... 23 mA ... 28 mA
U
= 10 V
out
Voltage supply 19.2 Vdc ... 24 Vdc ... 28.8 Vdc Cross-connection, upper 24 V, max. 2 A Cross-connection, lower 0 V, max. 2 A Operating temperature 0 ... +55 °C Storage temperature -20 ... +85 °C
Approvals CE, CSA, UL
27
9 Accessories
Cross-connection ZQV 2,5N/2 black 1718080000 Cross-connection ZQV 2,5N/2 red 1717900000 Cross-connection ZQV 2,5N/2 blue 1717990000 Cross-connection ZQV 2,5N/2 yellow 1693800000
Terminal connector, 2-pole for screw-type connection BLZ 5,08/2
- orange 1526460000
- black 1526410000 Terminal connector, 2-pole for tension clamp connection BLZ 5,08/2
- orange 1707460000
- black 1707700000
Connector markers WS 10/5 Multicard for plotter labelling 1635010000 WS 10/5 blank 1060860000
In the interest of protecting the environment, return any spare operating instructions to your local stockist for re-use. Printed on chlorine-free bleached paper.
28
Loading...