Weidmuller G118 User Manual

Weidmuller Ltd. 10 Spy Court Markham, ON L3R 5H6 Tel: (905)475-1507 Fax: (905)475-5855
Weidmuller Inc. 821 Southlake Blvd. Richmond, VA 23236 U.S.A. Tel: (804)794-2877 Fax: (804)794-0252
ISO 9001 Registered
Electronic Interface Modules
G118 Ultra SlimPak®
RTD Input, Field Configurable Limit Alarm
• field configurable via DIP switches for different input­output combinations
• provides relay contact closure(s) at a preset RTD/resistance input level
• field configurable input ranges for platinum, nickel and copper RTDs
• setpoints programmable HI or LO and failsafe or non­failsafe
• LED trip and input indicators
• flexible power supply accepts 9 to 30Vdc
• ASIC technology for high reliability
• CSA approved, UL recognized, CE marked
Description
Diagnostic LEDs
Output
Operation
Dynamic Deadband
The Ultra SlimPak G118 is a DIN rail mount, RTD input limit alarm with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. There are up to eight temperature ranges available for each RTD type to ensure accuracy and maximize setpoint resolution. The G118 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe operation. Also included are adjustable deadbands (1% to 5% of full scale input) for each setpoint and a flexible DC power supply which accepts any voltage between 9 and 30Vdc.
The G118 is equipped with three front panel LEDs. The first is a dual function LED labeled IN (input). This green LED indicates line power and input signal status. Active DC power is indicated by an illuminated LED. If this LED is off, check DC power and wiring connection. If the input signal is more than 110% of full scale, the LED will flash at 8 Hz. Below -10%, the flash rate is 4 Hz. Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.
The G118 is equipped with two SPDT (form C) relays, rated at 120Vac or 28Vdc at 5 amperes. Each of these relays is independently controlled by the field configurable setpoint and deadband.
The field configurable G118 limit alarm setpoints can be configured for HI or LO, failsafe or non­failsafe operation. Each of the setpoints has a respective HI or LO dead-band. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the LO deadband (see Figure 1). For proper deadband operation the HI setpoint must always be set above the LO setpoint. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.
LSI circuitry in the G118 prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This effectively results in a "dynamic deadband" - based on time- in addition to the normal deadband.
Figure 1
Note: resistance values for Pt500(M) and Pt1000(M) are 5 and 10 times the resistance value of Pt100(M), respectively
Relay
Tabele 1: RTD input type switch settings (SW2 - 1 through 6)
Tabele 2: Setpoint function switch settings (SW1 - 5 through 8)
Table 3 Input range switch settings (SW-1 through 4)
Conta cts
(optional)
Figure 2: DC Inductive Loads
Relay
Conta cts
Figure 3: AC Inductive Loads
Power
+
-
Load
Diode
47 ohm
0.1uF
1/2W
Film
Power
Load
MOV
47 ohm
0.1uF
1/2W
Film
Unless otherwise specified, the factory presets the Model G118 as follows: Input: Platinum (100M) Range: 0 to 250°C Output: Dual, SPDT Trip: A:HI, B:LO Failsafe: No Deadband: A, B: 1.0% The DC power input accepts any DC source between 9 and 30V; typically a 12V or 24Vdc source is used. For other I/O ranges, refer to Tables 1 through 3 and reconfigure switches SW1 and SW2 for the desired input type, range and function.
Do not attempt to change any switch settings with power ap-plied. Severe damage will result!
Input
1. With DC power off, position input switches 1 through 6 on "SW2" for RTD type (see Table 1).
2. Set position 1 through position 4 of input range switch "SW1" for the desired RTD type and input temperature range (Table 3).
3. Set position 5 and 6 of input range switch "SW1" to ON for a HI trip setpoint or OFF for a LO trip setpoint (Figure 4).
4. Set position 7 of input range switch "SW1" to ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon power failure).
1. After configuring the DIP switches, connect the input to a calibrated RTD source or a resistance decade box and apply power. See wiring diagram. NOTE: To maximize thermal stability, final calibration should be performed in the operating installation, allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.
2. Setpoint Calibration: Before adjusting the setpoint, adjust deadband pot to its minimum (20 turns counter clockwise). With the desired trip RTD resistance input applied, adjust setpoint pot until the relay trips. For HI trip calibration, start with the set-point pot above the desired trip (20 turns clockwise). For LO trip calibration, start with the setpoint pot below the desired trip (20 turns counter clockwise).
3. Deadband Calibration: Set dead-band pot to its minimum (20 turns counter clockwise). Adjust the setpoint pot to desired trip. Adjust RTD resistance input until relay trips. Re-adjust deadband pots to 5% (20 turns clockwise). Set RTD resistance input to desired deadband position. Slowly adjust deadband (counter clockwise) until relay untrips.
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 and 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1HF pulse film capacitor (foil polypropylene recommended) of sufficient voltage, and a 47M, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV>DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
Configuration
WARNING:
Calibration
Relay Protection and EMI Suppression
Figure 4 G118 input range/function selection (SW1) Factory default settings
Not Used
3
Not Used
Rated data Input
Range
Maximum ratings Field device excitation Other input specification Other input specification
Output
Range Load Burnout level Zero / Span adjustment Protection Other output specification Other output specification
Supply
Range Consumption Other supply specification
General
Accuracy Linearity Temperature coefficient (drift) Transmission frequency Response time. 90% span
Other general specification Status LED Isolation (# of ports) Operating / Storage temperature Housing (mounting) Dimensions (Lx W x H) Wire range (conductor size) Insulation stripping length Tightening torque Approvals
Ordering data
Ultra SlimPak Heat sink (width) Shunt resistor
RTD temperature sensor, 3 wire
-200 to 850°C for Pt100/Pt500/Pt1000, -200 to 260°C for Cu10/Cu100
-80 to 320°C for Ni120, -200 to 240°C for NiFe604, DIP switch selectable ±5Vdc <2mA for Pt100, Pt500, Pt1000, Ni120, Cu100 or NiFe604; <10mA for Cu10 leadwire resistance: 40% of base sensor resistance or 100M (whichever is less), maximum per lead. leadwire effect: less than 1% of selected span over entire leadwire resistance range. 2 form C relays (2 SPDT), one set point per relay, gold flash/silver alloy 2 set points independently adjustable over 100% of the selected input span, HI or LO, failsafe or non-failsafe maximum 5A at 120Vac, 2A at 240Vac, 5A at 28Vdc (resistive load), minimum 10HA at 10mV
deadband adjustable from 1% to 5% of span external relay contact protection required for inductive load switching Electrical life: 105operations at rated load Mechanical life: 107operations no load DC voltage 9 to 30Vdc, inverter isolated
1.5W typ., 2.5W max. (300mA inrush at 9Vdc).
0.2% of full scale
±0.05% of full scale/°C, max.
<250mS in normal mode, dynamic deadband: relay status will change when proper setpoint/process condition exists for 100mS
input green (>110% of input: 8Hz, <-10% of input: 4Hz), 2 setpoint red (ON: tripped, OFF: safe) 1800V (3 port) between contacts, input and power
-15°C to 55°C / -25°C to 75°C EG12 (TS32 and TS35) 90mm x 17.7mm x 112.7mm max. 22-12AWG (0.5-4.0mm2) 7mm
0.4-0.8Nm CSA (file LR-42272), UL (file E99775), CE marked (EMC dir. 89/336/EEC, LV dir. 73/23/EEC)
Cat. No. G118 (factory calibration: 0-250ºC (Pt 100), A-HI/B-LO, non-failsafe) HS01-A (1.6mm) (conditionally required depending on installation, see heat sink data)
Note: G118-000X where X is the revision level. For 2 wire sensors: connect RTN and - externally
Specifications subject to change without notice. 99990014 - 8/98 Printed in Canada
RTD
RTD Return
RTD Input (+)
RTD Input (+) RTD Return
TS32 RAIL
TS35 RAIL
Loading...