5. Mounting instructions
The device is designed for mounting onto 35 mm DIN mounting rails. To
guarantee convection cooling the following amount of space must be kept
free: 100 mm above and below the device, 20 mm at the sides. Do not
cover ventilation openings.
6. Dimensions and tightening torques.
7. Miscellaneous
We constantly endeavour to improve our products in line with our policy
on customer satisfaction. We would be pleased to receive your requests
and ideas.
Please read this information carefully before installing the product.
This information should be retained for future reference.
1. General notes
Warning! Power supplies must be installed by qualified
personnel only.
Non observance of valid rules and regulations can lead to
damage to property and physical injury, or even death.
2. Connections
Input: L, N ~ 100...240 V, 50/60 Hz, PE.
Back-up fuse: cable protection
according to regulation
min. 10 A C
Output: Voltage: = 24 V, +/- 1 % (factory set)
Max. current: 3 A 8708660000
5 A 8708670000
10 A 8708680000
Voltage indication: LED green
3. Parallel connection
When connecting the same type in parallel, the output voltages are to be
set to ± 50 mV of one another.
The + and – output lines are to be connected with litz conductors of the
same length and connected according to the circuit diagram.
Use diodes with appropriate current load-carrying capacity and ensure
sufficient cooling.
4. Approvals and markings
% EN 60950
UL 508.
These devices correspond to the European EMC and Low Voltage
Directives and are suitable for use in both industrial estates and residential
areas. The EU Declarations of Conformity are held available for the
responsible authorities in accordance with Article 10 of the above
mentioned EU guidelines at: Weidmüller Interface GmbH & Co. KG
Dimensions A B C
70 Watt 55,5 125 108
120 Watt 65,5 125 129
250 Watt 125,5 125 133
tightening torques cable diameter
70, 120, 250 Watt 0,4 - 0,5 Nm max. 4 mm
2
,
AWG 10