1 General instructions
The WAVESERIES Thermo signal conditioner should only be
installed by qualified staff. The Thermo signal conditioner should
only be powered up following professional installation.
2 Application
WAVESERIES Thermo signal conditioners can be used to connect to the following thermocouple types: K, J, T, E, N, R, S and
B. The temperature range and the type of thermocouple can be
set by the DIP switches on the printed circuit board.
Note!! The Thermo signal conditioner only processes signals
Insulated from housing.
16
from fully insulated thermocouples.
3 Mounting and dismounting
Warning!! Mounting and dismounting may only be carried out
when the power supply has be disconnected. Failure
to observe will lead to considerable damage!
3.1 Mounting onto TS 35 DIN rails
(s. Fig. 1)
3.2 Pluggable electronic components for range alteration
(depending on model)
(s. Fig. 2)
1. Remove connector, (depending on model either screw-type
or tension clamp).
2. Press locking clips on both sides of the enclosure.
3. Pull out the circuit board.
Warning!! The circuit board can only be inserted in one
position.
The connectors have been coded by the manufacturer, ensuring that they cannot be reversed.
17
3.3 Pluggable cross-connections for voltage supply
(s. Fig. 3)
A maximum feed through of 2 A is possible.
If a signal conditioner is accidently rotated through 180°, the
cross-connection cannot be inserted.
3.4 Labelling possibilities
(s. Fig. 4)
WS 10 connector markers can be used to label module.
4 Calibration
Warning!! The power supply must be disconnected, before
Note!! The module calibrates itself, when using the DIP
18
changing the signal conditioner settings using the
DIP switches.
Failure to observe will lead to considerable damage!
switches on the printed circuit board to set the
temperature range.
4.1 Setting the DIP switches
Warning!! The Thermo signal conditioner must be protected
against a direct electrostatic discharge when setting
the DIP switches.
Thermocouple types
DIP switch 1
Type 1 2 3
KONONON
J OFF ON ON
T ON OFF ON
E OFF OFF ON
N ON ON OFF
R OFF ON OFF
S ON OFF OFF
B OFF OFF OFF
19