Weidmuller GPRS User Manual

IE-GPRS-I/O
Alarm Modem
Weidmüller Interface GmbH & Co. KG
32758 Detmold
Tel.: 0 52 31 / 14-0
Fax: 0 52 31 / 14 20 83
V 2.02 March 2006
Copyright
Weidmüller Interface GmbH & Co. KG. All rights reserved.
All rights are reserved, including those of translation, reprinting, and reproduction of this manual, or parts thereof. No part of this manual may be reproduced, processed, copied, or transmitted in any way whatsoever (photocopy, microfilm, or other method) without the express written permission of Weidmüller Interface GmbH & Co. KG, not even for use as training material, or in using electronic systems. All rights reserved in the case of a patent grant or registration of a utility model or design.
Copyright © 2005 by
Weidmüller Interface GmbH & Co. KG
NOTE
We have checked the contents of this manual for conformity with the hardware and software described. Nevertheless, because deviations cannot be ruled out, we cannot accept any liability for complete conformity. The data in this manual have been checked regularly and any necessary corrections will be included in subsequent editions.
We always welcome suggestions for improvement.
Trademarks
Microsoft and Windows are U.S. registered trademarks of Microsoft Corporation.
All products mentioned herein may be trademarks or registered trademarks of their respective owners.
HEYFRA® is a registered trademark of HEYFRA ELECTRONIC GmbH
Weidmüller® is a registered trademark of Weidmüller Interface GmbH & Co. KG
Handbuch: Manual Datei: handbuch ie-gprs-io en rev1 w-04-2-06.doc 04.04.2006 Revision: 1.0 c04-2/06
Alarm Modem IE-GPRS-I/O
Contents

1 Safety Notes 1-4

1.1 Graduated safety notes 1-4

1.2 Definitions 1-4

1.3 Hazards resulting from use other than as described 1-5

1.4 Hazards resulting from modifications and upgrades 1-5

1.5 Admitted personnel 1-5

1.5.1 Operator 1-6

1.5.2 Start-up engineer 1-6

1.5.3 Service engineer 1-6

1.6 Electrical connections 1-7

1.7 Safety regulations 1-7

1.8 Service and maintenance 1-8

1.9 Waste disposal 1-8

1.10 Liability 1-9

2 Use as Prescribed 2-10

2.1 Range of application 2-10

3 Description of Functions 3-12

3.1 General Description of Functions 3-12

3.2 Functions of the interfaces 3-13

3.2.1 Digital inputs 3-13

3.2.2 Analog inputs 3-14

3.2.3 Digital outputs
3.2.4 Serial interface

3.2.5 Operating modes of the serial interface 3-16

3.2.6 GSM modem 3-17

3.2.7 SIM card 3-17

3.2.8 GSM services 3-17

3-15 3-16

3.3 Settings of the operating system 3-18

3.3.1 (Firmware) update for the operating system 3-18

3.3.2 Resetting to the factory defaults 3-20

3.4 Communication between PC and IE-GPRS-IO 3-21

3.4.1 Diagnosis using a terminal program 3-22

1

3.4.2 Remote servicing 3-24

3.4.3 The "Passive" mode 3-25

3.4.4 The "Transparent" mode 3-25

Contents

4 Configuring the IE-GPRS-IO 4-26

4.1 Configuring the via the RS 232 interface 4-26

4.1.1 Setting up the virtual modem and the long-distance data transmission connection under Windows XP/2000 4-26

4.1.2 Installing the long-distance data transmission connection 4-29

4.2 Making the settings 4-38

4.2.1 General Settings 4-40

4.3 Access to the device 4-42

4.3.1 Device Access 4-42

4.4 Digital inputs and outputs (Digital I/O) 4-45

4.5 Analog inputs ("Analog I") 4-47

4.6 Alarm Message 4-50

4.7 Message Services 4-53

4.8 ISP settings for the Internet access 4-57

4.9 Function control 4-60

4.10 Server 4-62

4.11 COM port 4-64

4.12 Logbook 4-65

4.13 Cost control 4-66

4.14 Troubleshooting 4-68

4.15 Systemtime 4-68

4.16 About 4-69

5 Hardware 5-70

5.1 Installation 5-70

5.1.1 Dimensions 5-70

5.1.2 Installing the top-hat rail 5-71

5.1.3 Wall mounting 5-72

5.2 Installation notes 5-74

5.2.1 Functional earthing 5-74

5.3 Installation guidelines 5-75

2

5.4 Storage and storage temperatures 5-75

5.5 Operating temperature, humidity 5-75

5.6 Status display 5-76

5.6.1 Display "POWER on/off" 5-77

5.6.2 "Status" display 5-77

5.6.3 "Line" display 5-77

5.6.4 "Ports" display 5-78

5.7 Connections / interfaces 5-79

5.7.1 Power supply 5-79

5.7.2 RS232
5.7.3 Inserting the SIM card
Contents
5-80 5-80

6 Technical Data 6-84

7 Standards and Certifications 7-86

7.1 Harmonised standards 7-86

7.2 Certification to DIN EN ISO 9001 7-86

7.3 Approbations 7-86

7.4 CE marking 7-86

8 Symbols Used 8-87

9 Glossary 9-88

3
DANGER

1 Safety Notes

1.1 Graduated safety notes
In this Instruction Manual, safety notes are marked with a symbol and the keyword CAUTION or NOTE at the page margin. Safety notes are printed in bold letters and are marked with an outside border.
1.2 Definitions
The keyword DANGER is used to warn you of a possibly hazardous situation.
Safety Notes
DANGER
ATTENTION
NOTE
DANGER of electric shock is used to warn of a possibly hazardous situation involving electric current.
ATTENTION alerts you to hazards and error sources.
The keyword NOTE is used to draw your attention to an important recommendation to be observed.
1-4
DANGER
1.3 Hazards resulting from use other than as
described
Use other than as prescribed may result in personal injuries to the user or third persons, as well as in material damage to the control system or the product, or in environmental damage. The IE-GPRS-I/O must only be used according to its intended purpose!
1.4 Hazards resulting from modifications and
upgrades
Unauthorised modifications and amendments are not permitted.
Safety Notes
DANGER
DANGER
Such unauthorised modifications or amendments may impair the proper operation of the device, resulting in personal injuries, material damage or environmental impairments and will void all liability on our part null and void.
1.5 Admitted personnel
Only sufficiently qualified and instructed personnel are allowed to operate the IE-GPRS-I/O!
It must only be started up by an electrical expert.
Service and maintenance, as well as troubleshooting, must only be carried out by qualified expert staff.
1-5
1.5.1 Operator
The operator:
is an instructed person
who is authorised to turn on / turn off the equipment
1.5.2 Start-up engineer
The start-up engineer:
is an electrical expert
must be an expert in parameterising the device
who carries out the start-up, observing strict precautions and
carries out the required test
1.5.3 Service engineer
Safety Notes
The service engineer:
is a qualified expert
who services the electrical and mechanical components of the
control system
carries out maintenance work
carries out troubleshooting
1-6
DANGER
1.6 Electrical connections
The IE-GPRS-I/O must be connected to an electrical supply system.
Power supply connection
The IE-GPRS-I/O must only be connected to the electrical supply system by an electrical expert.
The power supply of the IE-GPRS-I/O must be provided exclusively by a power pack which complies with DIN EN 60 742 (VDE 0551).
Make sure that an appropriate fuse is installed in the incoming supply feeder.
For operation of the IE-GPRS-I/O, please refer to the information provided in Chapter
6 Technical Data.
Safety Notes
DANGER
1.7 Safety regulations
The IE-GPRS-I/O possesses a housing.
Electrical hazards
The operation of the IE-GPRS-I/O is only allowed with the housing closed.
The housing prevents:
persons from coming into contact with live parts;
the penetration of humidity and foreign substances, and
the impairment of system functions by electromagnetic interference
The housing cover must not be opened.
1-7
DANGER
1.8 Service and maintenance
Service and maintenance work
Improper service and maintenance may result in loss of life, personal injuries, material damage or environmental impairments.
Service and maintenance work, as well as troubleshooting, must only be carried out by qualified expert personnel.
Before performing service or maintenance work, always switch off the power supply of the Alarm Modem first!
Reinstall all panelling, protective covering and safety devices immediately after completion of service and maintenance work and check their functioning.
Safety Notes
DANGER
DANGER
Spare parts
The use of inappropriate spare parts may result in loss of life, personal injuries, material damage or environmental impairments.
The spare parts must comply with the technical requirements of the manufacturer.
Use only original spare parts from Weidmüller.
1.9 Waste disposal
Electrical waste (components, CRT units, etc.) may harm the environment.
Dispose all electrical devices and materials according to the relevant environmental regulations or entrust an expert company with this job.
1-8
NOTE
1.10 Liability
The contents of the present Instruction Manual are subject to technical modifications, which may result, in particular, from the continuous further development of the products made by Weidmüller. Weidmüller will not assume any liability for printing errors or any other inaccuracies contained in the present Instruction Manual, unless these are serious errors which are evidently known to Weidmüller. In addition, the "General Terms and Conditions for the Supply of Products and Services in the Electrical Industry" shall apply. Irrespective thereof, the relevant national and international standards and regulations will apply in addition to the notices and instructions contained in this Instruction Manual.
Use other than prescribed - exclusion of liability
Weidmüller Interface GmbH & Co. KG will not be liable for damage resulting from use or application of the products not according to the intended purpose or other than as prescribed.
Safety Notes
Use as prescribed or according to the intended purpose also includes the exact knowledge of this Instruction Manual. In particular, the notes and safety notes contained therein must be observed.
If you run the products together with other components, such as safety modules, control systems or sensors, always observe the relevant user information of such devices.
1-9
Use as Prescribed

2 Use as Prescribed

2.1 Range of application
The Alarm Modem IE-GPRS-I/O is designed to collect messages in industrial plants and building installations. The messages are detected as activated switching contacts and analog limit values. Via a serial protocol, the higher-level plant or system may either receive data or control the data traffic itself.
The communication with the server is performed over a virtual dedicated line via GPRS as a point-to-point, multipoint or multi-drop connection. An Internet exchange server may log the states of the inputs and outputs permanently on the basis of event or time control. The server constitutes a relational database, i.e. external access is possible via SQL queries.
The exchange server is a service provided by Weidmüller.
DANGER
The configurable alarms are issued via SMS, e-mail, voice messaging and/or fax.
The IE-GPRS-I/O implements telecontrol by remote-switching of the outputs via telephone/mobile telephone.
The IE-GPRS-I/O can be teleserviced and remote-configured.
Any errors in configuration, in the execution of any work or operations, as well as inadvertent false operation may impair the proper functioning of the IE-GPRS-I/O, resulting in personal injury, or material or environmental damage. Therefore, only sufficiently qualified personnel are allowed to operate the IE-GPRS-I/O.
Always observe the safety notes!
The IE-GPRS-I/O is intended exclusively for use in machines complying with the scope of application of DIN EN 60204-1:1998-11 (Electrical Equipment of Machines).
2-10
Danger
Use as Prescribed
Do not use the IE-GPRS-I/O in potentially explosive areas!
When connecting the device, observe, in particular, the information provided in the following sections:
1.6 Electrical connections
5 Hardware
6 Technical Data.
2-11
Description of Functions

3 Description of Functions

3.1 General Description of Functions
The IE-GPRS-I/O provides comprehensive configuration possibilities for messaging services.
The IE-GPRS-I/O can be online permanently. It checks and maintains the connection once established. No costs arise, except the fixed monthly charge. Depending on the M2M tariff, a certain data volume for sending messages is also included.
The IE-GPRS-I/O provides the following functions:
Values from a machine/plant can be written to a data logger
(server) on the Internet at regular intervals.
At the same time, the current data can be requested from the data
logger.
No permanently installed fixed-network telephone connection is
required.
Alarms via SMS, fax and/or e-mail
Freely configurable message sequence with 8 target numbers per
input
Worldwide teleservicing and remote-monitoring of the
machine/plant via the serial console ("Transparent" mode)
Wireless and transparent data transfer to a serial interface at the
machine/plant
The IE-GPRS-I/O is protected against attacks from the Internet.
For purposes of security, routing concepts are integrated into the
IE-GPRS-I/O and can be configured via a web browser.
Additional alarm service functions via GSM for reporting via SMS,
fax, e-mail and/or voice in case of faults on the GPRS line.
The IE-GPRS-I/O can be accessed permanently via the GPRS
connection.
Both master and slave functionalities are implemented in the
IE-GPRS-I/O; thus, point-to-point and multipoint operation is possible.
Straightforward configuration via a serial interface using a web
browser; no special configuration software required.
Teleservice and remote configuration via analog modem
connection.
3-12
Description of Functions
Low purchasing costs and cost-effective operation thanks to special
M2M-GPRS tariffs.
3.2 Functions of the interfaces
3.2.1 Digital inputs
Binary inputs for detection of external states as a high or low signal
Electrically isolated and floating in two groups:
Number: 8
Input voltage: 0 … 30 VDC
Input voltage status 0: 0 … 4 V / 0 … 1.2 mA
Input voltage status 1: 10 … 30 V / 1.5 … 4.5 mA
Debouncing can be parameterised
Each input can be assigned event-related texts with system text
blocks.
Equivalent circuit diagram for the digital inputs:
Each input can be assigned event-related texts with system text blocks, see Section 4.6 Alarm Message.
3-13
Description of Functions
3.2.2 Analog inputs
Analog inputs for detection of external states as violation of minimum or maximum limit values or as a percentage deviation; can be used to measure voltage, temperature or current.
Input ranges
Voltage 0 … 10 V
Current 0 … 20 mA
Temperature PT1000
Electrically isolated and floating in two groups:
Number: 4
Scaling and offset factors can be parameterised separately for each
measured value
Debouncing can be parameterised
Each input can be assigned event-related texts with system text
blocks.
Voltage sensor analog input
Current sensor analog input
Temperature sensor analog input
3-14
Description of Functions
3.2.3 Digital outputs
The binary outputs can be used as follows:
Signalling of successful/failed messages, see Section 4.6 Alarm
Message and 4.9 Function control.
Remote-switching via telephone using tone dialling, see below
Switching from another IE-GPRS-I/O of a group via X-Rec, see
Section 4.4 Digital inputs and outputs (Digital I/O) Digital outputs
Operating voltage: 10 … 30 VDC
Output current: max. 400 mA
Number: 4
Danger
Danger
The short-circuit and overload protection of the outputs must be provided by external measures.
Remote-switching:
Call the IE-GPRS-I/O using a telephone or mobile telephone.
Enter the PIN (see Section 4.3 Access to the device).
Press a number for the number of the output: 14
Switching command, key 0 = OFF or 1 = ON.
When remote-switching, be especially cautious and work with special care, as you cannot observe the reaction of the connected plant from a distance. You should only switch an output if you are fully informed as to all effects resulting for the plant. Make absolutely sure that the health and safety of persons is not endangered.
3-15
NOTE
Description of Functions
3.2.4 Serial interface
The serial interface serves for communication with the monitored plant or for communication of the plant with the connected devices via the IE-GPRS-I/O.
The parameterisation and any firmware updating for the IE-GPRS-I/O are performed via the serial interface.
The communication via the serial interface requires a fully connected 1 : 1 cable. Regarding the information required to configure the serial interface, please refer to Section 4.11 COM.
3.2.5 Operating modes of the serial interface
NOTE
1 2 3 4
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF OFF OFF
ON ON
OFF OFF
ON
OFF OFF OFF
Status
Flashin
Lights
DIP switches "Options" on the front panel
LED
OFF Operation as a signalling and GSM/GPRS system
Configuration locally; Connection from the serial
g red
interface to the PC via a modem cable (1 : 1)
Diagnosis at the serial interface using a terminal
green
program
All settings are reset to their defaults when the operating voltage is connected.
Firmware update
To switch the operating mode, the IE-GPRS-I/O must be turned off; after switching the DIP switch, it can be turned back on.
3-16
Description of Functions
3.2.6 GSM modem
The GPRS module realises a virtual dedicated line. With an M2M GPRS tariff of a mobile telephone provider, the only costs in addition to a low fixed monthly charge are the costs for the actual data transfer. No permanently installed fixed-network telephone connection is required. Each IE-GPRS-I/O can be accessed online at any time in the same way as a mobile telephone.
The data transfer is not provided via the exchange of telephone numbers, but via an Internet-based protocol. The data are collected on an exchange server and can be requested there at any time, without the need to establish a direct connection to the IE-GPRS-I/O. The router of the mobile telephone provider need not be configured.
Thanks to the use of non-public IP addresses of the provider, the IE-GPRS-I/O is invisible to the Internet.
Additionally, software is supplied for an exchange server, which, for example, can also be operated after a router.
CAUTION
3.2.7 SIM card
A SIM card is used to set the selected tariff and the possible communication services for the IE-GPRS-I/O. The availability of the services fax, e-mail and voice depends on the chosen tariff and on the enabling of the SIM card used, see SIM card agreement.
Before you insert the SIM card, first turn off the device!
Inserting the SIM card
Use a pointed object to press gently into the hole beneath the SIM card compartment and open the SIM card compartment. Insert the SIM card into the card compartment such that the contact faces are visible.
3.2.8 GSM services
For the case that the virtual GPRS line is interrupted, alarms can be issued additionally via the GSM network using the configurable services SMS, e-mail, fax and voice messaging.
3-17
Description of Functions
3.3 Settings of the operating system
CAUTION
3.3.1
(Firmware) update for the operating system
The operating system of the IE-GPRS-I/O is subject to continuous further development to adapt it to the technical requirements and customer wishes. Devices which are already in use may thus also require a new operating system. The version of operating system currently installed on your IE-GPRS-I/O can be displayed on the About page of your web browser (see Section 4.16 About) or read out using a terminal program (see Section 3.4.1).
When loading a new operating system, it may be necessary to reset all settings to the factory defaults.
If the IE-GPRS-I/O is reset manually to its factory default settings after installing the operating system, all settings already made are lost; the user name and the password are also reset to the factory defaults. Therefore, you should always document the current settings before you make an update!
After the update, check both all settings and the access protection.
To load the operating system, use a loader.
Files required: gprs-flash.exe Loader
ie-gprs-io-xxxxx.hex Loader file
xxxxx stands for the version number
It is not necessary that both files are in the same directory.
Connect the RS232 of your IE-GPRS-I/O to COM1 or COM2 of
your PC.
Turn off the IE-GPRS-I/O.
Set the DIP switch to 0-0-0-1.
Turn on the IE-GPRS-I/O.
Start gprs-flash.exe.
Set the COMx interface and select the baud rate 115200.
Select the loader file.
Type flash it to start.
3-18
Description of Functions
The loading process will take approx. 5 min.
Once loading is completed successfully, OK is displayed in the
status line.
NOTE
If the Loader does not permit any choice in the COM window, the interfaces may already be occupied either by a driver of installed software or by an application which is currently running.
The version number can also be displayed via the serial interface using a terminal program. You need not enter a user name or the password to display the version number. For communication via the serial interface, see 3.4.1.
3-19
Description of Functions
3.3.2 Resetting to the factory defaults
If you wish to reset the IE-GPRS-I/O to a defined initial state, you can load the factory settings:
Turn off the IE-GPRS-I/O.
Set the DIP switch to 1-1-0-0.
Turn on the IE-GPRS-I/O.
The LEDs 1 … 4 will flash yellow for 5 s.
The LEDs 1 … 4 will go out one after the other.
The status LED flashes red.
The factory settings are now loaded.
Turn off the IE-GPRS-I/O.
Set the DIP switch to 1-0-0-0.
NOTE
Turn on the IE-GPRS-I/O; reparameterise the IE-GPRS-I/O if
necessary.
Turn off the IE-GPRS-I/O.
Set the DIP switch to 0-0-0-0.
Turn on the IE-GPRS-I/O; the IE-GPRS-I/O is now ready for
operation.
Resetting the IE-GPRS-I/O to its factory settings will also reset the password and the IP address!
Default factory settings
Default IP address: 192.168.1.120
User name: admin
Default password: 12345
3-20
NOTE
Description of Functions
3.4 Communication between PC and
IE-GPRS-I/O
The communication is realised via a serial connection. To display the HTML user interface of the IE-GPRS-I/O, Microsoft Internet Explorer, version 5.5 or higher is required. For the relevant information required to configure the IE-GPRS-I/O via the serial interface, please refer to Section 4.1.
To configure the IE-GPRS-I/O using the HTML user interface, it is imperative to know the current Ethernet address of your IE-GPRS-I/O. The factory setting is 192.168.1.120.
In the Windows operating system, set up the IE-GPRS-I/O as a
long-distance data transmission connection ("Dial-Up Networking", see Section 4.1.1 Setting up the virtual modem and the long­distance data transmission connection under Windows XP).
Configure a serial COM interface of your PC for the IE-GPRS-I/O
(see Section 4.1 Configuring the 218HIE-GPRS-I/O via the RS 232 interface).
Establish the connection either by clicking on the previously created
shortcut on the desktop or use Start – Settings - Dial-Up Networking - IE-GPRS-I/O ; IE-GPRS-I/O stands for the name of the connection.
In the Internet explorer, call the start page
http://
After a few seconds, the start page of the parameterisation user
192.168.1.120/index.htm.
interface is displayed.
IE-GPRS-I/O is addressed directly via the long-distance data
The transmission connection and cannot itself communicate with a network connected to the PC. The IP address of the
IE-GPRS-I/O is not visible in the network of the PC. Thus, no attacks are possible against the IE-GPRS-I/O from the network. Furthermore, no address conflicts result with devices with the same network address in the network.
3-21
ATTENTION
Description of Functions
3.4.1 Diagnosis using a terminal program
If Windows HyperTerminal is used, previous activities, which may also have arisen from other communication instances, are displayed outside the visible window but can be viewed in the full­screen mode. You should therefore set the view in the Terminal window in the View menu to Fit to Window Size.
Set and configure the serial interface to be used for the terminal
program:
Disconnect the operating voltage.
Set the DIP switch on the IE-GPRS-I/O to 0-1-0-0.
Either select an existing connection from the saved connections or
create a new connection and select it.
The terminal window remains empty.
Once the connection has been established successfully, the
message Connected is displayed at the lower margin.
Connect the supply voltage.
The status LED lights red; the diagnostic data are transmitted to the
terminal.
Once the status LED lights green, the data transfer is completed,
and the diagnostic data are visible in the terminal window.
To reinitiate the data transfer, disconnect and then reconnect the
supply voltage.
3-22
Diagnosis is also possible in the messaging mode.
Messages:
Description of Functions
Reset Hardware The IE-GPRS-I/O has been restarted.
Mon, 16 Jan … Date, time and time zone of the IE-GPRS-I/O
DI1 … 8 S Normally open contact 1s Debouncing set; the signal must have been present for 1 s.
AI1 … 4 V Analog input set to voltage measurement
1s Debouncing set; the signal must have exceeded or fallen below the level for 1 s.
Network login Shows that you are logged into the network and displays the receive signal level.
3-23
Description of Functions
3.4.2 Remote servicing
It is possible to make all settings for the IE-GPRS-I/O from a remote PC. To do so, you will need an analog modem.
The connection to the IE-GPRS-I/O is again established via "Dial-Up Networking".
In "Properties" of "Dial-Up Networking", set the analog modem as the transfer device.
Enter the number of your IE-GPRS-I/O as the dialling number; the dialling number is indicated in your SIM-card agreement.
After establishing the connection, you can configure your IE-GPRS-I/O as described in Section 4 Configuring the .
Reloading of the operating system is not possible via teleservice!
NOTE
NOTE
If no communication to the IE-GPRS-I/O can be established within 5 min., the connection is cancelled. The connection is also cancelled, if no data have been transferred for 5 min. when the connection is active. Subsequently, the IE-GPRS-I/O must be reselected. Thus, unnecessary connection costs are avoided, as would otherwise result if the connection was not cancelled manually.
3-24
Description of Functions
3.4.3 The "Passive" mode
The "Passive" mode provides a data connection from a remote PC, via a modem and the IE-GPRS-I/O to a device connected to the serial interface of your IE-GPRS-I/O.
Procedure
The PC calls the IE-GPRS-I/O via a modem.
The IE-GPRS-I/O accepts the call and establishes a connection.
On the basis of the first data sent by the PC, the IE-GPRS-I/O
decides whether the data are part of a remote configuration for the IE-GPRS-I/O or whether the data are intended for a downstream device.
If the data are intended for a downstream device, they are passed
to the serial interface. All data sent by the downstream device to the serial interface are sent without changes to the remote computer via the modem connection.
3.4.4 The "Transparent" mode
In the "Transparent" mode, it is possible for the internal GSM/GPRS modem to be controlled by a downstream device.
In this case, the establishing, cancellation and monitoring of the
connection must be controlled by the downstream device.
3-25
Configuration

4 Configuring the IE-GPRS-IO

To start up your IE-GPRS-I/O, it must be configured first. The individual steps for starting up will be explained in the present chapter.
4.1 Configuring the IE-GPRS-I/O via the RS 232
interface
The IE-GPRS-I/O is connected to a PC via the RS 232 interface "RS232" using a modem cable. The RS232 protocol is used directly. The IE-GPRS-I/O is addressed using Internet Explorer 5.5 or higher.
In the MS Windows operating system, install your IE-GPRS-I/O as a modem for a long-distance data transmission connection.
4.1.1 Setting up the virtual modem and the long-
distance data transmission connection under Windows XP/2000
If the modem and the long-distance data transmission connection are already set up, proceed as described in Section 4.1.2.
Installing a new modem:
Select Start – Settings – Control Panel - Phone and Modem Options and there
"Modems – Add" tab.
4-26
Configuration
The wizard assisting you in setting up a new modem is started:
• ; Select Don't detect my modem. select: I will select
it from a list.
Select your modem from the following window:
(default modem type) -> default modem 33,600bps
NOTE
Select the interface on your PC to which your IE-GPRS-I/O is
connected: COM1 or COM2
If an interface on your PC is not displayed, but is known to exist, it is probably currently occupied by another interface driver, e.g. a CAPI driver.
The installation of your modem is thus completed.
In the next step, the modem properties are set.
4-27
Configuration
Select Start – Settings – Control Panel - Phone and
Modem Options and there select
the new modem:
- "General" tab
Make sure that Use this device (enable) is selected:
"Modem" tab: Select 38400 as the maximum transfer rate.
"Diagnostics" tab: Nothing need be entered here.
"Advanced" tab: Nothing need be entered here.
"Driver" tab: Do not make any changes here.
4-28
Configuration
4.1.2 Installing the long-distance data transmission
connection
Select Start - Settings – Control Panel – New
Connection Wizard;
The wizard assisting you in establishing a new connection is
started.
Select : Connection to the Internet
Select : Connect using dial-up modem
Select the modem you have just installed:
4-29
Configuration
Assign the long-distance data transmission connection a name:
Enter any number:
• ; Add a shortcut to this connection on my desktop
4-30
NOTE
After setting up is completed, the connection to the IE-GPRS-I/O can be called directly by clicking on the shortcut on the desktop. To do so, the Internet Explorer need not be reconfigured.
If no shortcut was created on the desktop, the connection can also be called directly under Start – Settings – Network Connections - IE-GPRS-I/O . "IE-GPRS-I/O" stands for the name selected for the connection.
Call the connection to the IE-GPRS-I/O:
Configuration
Factory setting:
User name:
admin
Password: 12345
; Save this user name and password fort he
following users:
~ Me only
4-31
Configuration
• "General" tab: Make sure that only the previously installed
modem is selected.
Modem configuration:
Maximum speed (bps) 38400
• ; Enable hardware flow control
• ; Enable modem error control
• ; Enable modem compression
• ; Enable modem speaker
4-32
Configuration
• "Dialling Rules" tab:
~ My Location - The once selected location is displayed.
• "Options" tab:
• ; Display progress while connecting
• ; Prompt for name and password, certificate, etc.
Redial attempts: 3
Time between redial attempts: 1 minute
Idle before hanging up: 20 minutes
4-33
"Security" tab:
Configuration
~ Security options Typical
Allow unsecured password
No further checkboxes must be set.
"Network" tab:
Type of dial-up server I am calling:
PPP Windows 95/98/NT4/2000 Internet
4-34
Configuration
• ; Enable LCP extensions
Enable software compression must not be selected.
• ; Internet Protocol (TCP/IP) Properties
4-35
• ; Use default gateway on remote network
PPP link:
Use IP header compression must not be selected.
"DNS" tab
Configuration
~ Append primary and connection specific DNS
suffixes ;Append parend suffixes of the primäry DNS
suffix
• ; Register this connection's addresses in DNS
"WINS" tab
4-36
~ Disable NetBIOS over TCP/IP must be set.
Back to "Properties of IE-GPRS-I/O"
Advanced – Settings tab
Configuration
| "On" must not be set!
- until all windows are closed.
4-37
Configuration
4.2 Making the settings
The configuring tool required is Internet Explorer 5.5 or higher.
Starting configuring
Disconnect the operating voltage.
Set the DIP switch Options on the IE-GPRS-I/O for the
configuring mode to 1-0-0-0 (ON-OFF-OFF-OFF).
Connect the serial interconnecting cable (1 : 1).
Reconnect the operating voltage and wait until the Power LED
lights green and the Status LED flashes red.
Open the long-distance data transmission connection either by
double-clicking on the shortcut IE-GPRS-I/O you have created on the desktop or use Start – Settings - Dial-Up
Networking - IE-GPRS-I/O to establish the connection. IE-GPRS-I/O stands for the name of the connection.
Enter the default user name admin - if not stored.
Enter the default password 12345 - if not stored.
Start the long-distance data transmission connection.
In your browser, type http://192.168.1.120/index.htm.
If you have not changed the default settings, the integrated web server of your IE-GPRS-I/O will be started. The browser will create a dynamic web site from the configuration data of your IE-GPRS-I/O.
It will take a few seconds until the page is displayed.
4-38
ATTENTION
Once the page is open, you can save the address of your IE-GPRS-I/O as a favourite (bookmark) in the Internet Explorer.
Configuration
The appearance and contents of the windows depend on the firmware version installed. The appearance may deviate from the illustration shown here. Furthermore, the screen display is influenced by the browser and its settings. No language selection is possible in the present version.
Function keys in the menus:
Save settings
Before switching to another menu, it is imperative to wait until Finished is displayed in the status line of the browser.
Accept saved settings immediately
Is only important if you make settings via a modem connection. Only settings that have been saved are accepted.
Back to higher-level menu
Restores the factory settings for the menu
concerned. After a reset, the page must be refreshed with so
that the changes become visible.
4-39
4.2.1 General Settings
The general settings apply for the device as a whole.
Configuration
Station number
Dialling number used to call the station; is supplied with your SIM
card when the contract is concluded with the mobile telephone provider.
A number must always be entered.
If you are uncertain, "1" can be left for the time being, and you can
change the number later (also remotely).
This number is transmitted where appropriate, e.g. in the fax
identification.
Max. 30 characters
Station ID
An identifier that identifies the station in question unambiguously.
With some messaging services (fax, e-mail, voice), the identifier is
included in the message.
Letters and digits can be entered, but only the digits are announced
in the voice message, i.e. if "abc12de345" is entered, for example, "12345" is announced.
This field must not be left empty; if no identifier is needed, either
leave or re-enter 0000.
Max. 16 characters.
4-40
Configuration
Quit Pin
4-digit sequence of digits which is used to acknowledge SMS and
voice messages. Acknowledgement must be enabled in the menu Messages with a þ , i.e. acknowledgement of the messages is imperative (see Section
Only digits may be used.
If 0000 is entered, you can use any numeric key of your telephone;
4.6).
in this case, only one key must be pressed.
Always 4 digits.
SIM PIN
4-digit number which is supplied with your SIM card
It is imperative to configure the SIM PIN if the SIM card requires a
PIN.
If you have set your SIM card such that no PIN is required, 0000
must be entered to allow the device to log into the GSM network without SIM PIN.
Make sure that you enter the correct SIM PIN; an incorrect PIN,
however, will not usually block your SIM card (max. 2 attempts are accepted to enter the PIN); but this cannot be guaranteed.
If your SIM PIN is not properly configured, no message can be
triggered and thus no remote access to the device is possible.
Older 5V SIM cards cannot be used.
Always 4 digits.
Redialling
Number of further attempts made by the device when a message is
to be sent if a target number cannot be reached or an error has occurred.
1 automatic redial means max. 2 attempts.
If a message is sent as an SMS with receipt acknowledgement, the
number of automatic redials applies first for the SMS and then once more for the acknowledgement.
The next recipient in the messaging chain is only processed after
the maximum number of automatic redials is reached.
Automatic redialling may also occur if the message has reached the
recipient, but, for example, an error has occurred in the final phase of the message.
0 ... 9
4-41
CAUTION
Configuration
Text Header
Here you can enter a text that can be inserted in the message texts
using the text block #HEAD#.
For example, the name of the plant or the name of the company
can be entered, or a description of the states of the digital I/Os.
Max. 80 characters.
For further fixed text blocks, see Section 4.6 Safety Notes.
4.3 Access to the device
4.3.1 Device Access
These settings control the access to the device.
When making these settings, proceed very carefully; otherwise, access to the device may no longer be possible without undue difficulties. This would pertain both to local and remote access.
4-42
Configuration
User name for PPP
User name used to connect via "Dial-Up Networking, whether
remotely or locally; see "Configuring the long-distance data transmission connection", Section 4.1.1.
Max. 30 characters
Password for PPP choice
User name used to connect via "Dial-Up Networking", whether
remotely or locally, if the device is to be accessed via voice.
Max. 30 characters
Password repetition
Repetition of your password to verify the password for PPP dialling
4-43
ATTENTION
Configuration
Certified dialling numbers
Dialling numbers of fixed/mobile telephones and modems from
which a remote access is to be granted to the device.
8 access numbers are possible.
If no numbers are entered, access is possible from any dialling
number.
The dialling number must have the format +49123456789; no
blanks or special characters are allowed.
If one or several numbers are entered here, access to the device can only be realised from one of these numbers. It should always be tested whether your dialling number is transmitted. If the dialling number is suppressed by the telephone or by the provider, no remote access to the IE-GPRS-I/O is possible from this device.
NO remote access to the device will be possible in case of incorrect settings or incorrect entries for the numbers.
Call accept
~ Data mode
If you use a SIM card that does not possess a data number, it is
nevertheless possible to accept the call in the data mode if this feature is set.
Call acceptance in the "Data" mode, however, requires that the
data mode is enabled for incoming calls for your SIM card by the mobile telephone provider.
~ Voice mode
If the call is accepted in the "Voice" mode, it is possible to accept
the next call in the "Data" mode via telephone using the key 9 provided that you have dialled successfully in the "Voice" mode ­see temporary data mode for GSM devices.
4-44
Configuration
4.4 Digital inputs and outputs (Digital I/O)
CAUTION
Active on
High: A message can be triggered if a voltage in the range
12 ... 24 V is present at the input.
Low: A message can be triggered if a voltage of 0 V is present at
the input.
Level change: A message can be triggered if the input voltage
changes from 0 V to 12 ... 24 V or vice versa.
The input voltage must NOT lie within the range of 4 … 10 V. In this voltage range, no reliable status detection is provided.
4-45
Configuration
Debouncing time
The relevant input signal must have been present without
interruption for at least the set debouncing time for a message to be triggered; shorter disturbances cannot trigger a message.
Text for High
A text that can be inserted into the message block using the text
block #VAL# or #DI1#...; thus, it is possible to modify the message text dynamically, depending on the particular event.
Max. 16 characters.
Text for Low
A text that can be inserted into the message block using the text
block #VAL# or #DI1#...; thus, it is possible to modify the message text dynamically, depending on the particular event.
Max. 16 characters.
Report
NOTE
If you wish a message to be triggered via an input, it is imperative that the appropriate input be set by ; .
Digital outputs
Switching time
The digital outputs can be switched by events (see Section 4.6
Alarm Message) "Switch if" and Section 4.9 Function control "Switch if".
Switching time in seconds for which the output remains closed after
an event has occurred and before it reopens automatically
4-46
ATTENTION
ATTENTION
The switching time is not effective when switching the digital outputs remotely via telephone.
X-Rec
Remote-switching by a digital input of another IE-GPRS-I/O in a
group of IE-GPRS-I/Os
Two IE-GPRS-I/Os are included in a group.
; Connects the IE-GPRS-I/O as the receiving device of the group to the digital input of the sending IE-GPRS-I/O.
In all cases, inputs and the outputs with the same number are
connected; linking is only possible for the digital inputs 1 … 4.
Digital outputs that are connected to another IE-GPRS-I/O via X-Rec must not be used for issuing messages (see Section 4.6 Alarm Message, "Switch if" and Section 4.9 Function control "Switch if".
Configuration
4.5 Analog inputs ("Analog I")
4-47
Configuration
Measured unit
Selection of the analog measurement unit: Volt
Ampere Temperature
Measured value
This field displays the measured value of the inputs.
Clicking on the field refreshes the measured values of the two
analog inputs.
Factor
It is possible to scale the measured value with a factor.
In this case, the calculation is performed as follows: (Factor measured value) + offset, i.e. the slope of the measurement characteristic is not changed so that the displayed measured value can be matched to the physical measurement quantity. Example: Assumed 0 … 10 V is to correspond to a water level of 0 … 100 cm, the factor to be set is 10.
Offset
It is possible to shift the measured value using an offset.
In this case, the calculation is performed as follows: (Factor measured value) + offset, i.e. the zero of the measurement characteristic is offset.
Debouncing time
The measured value must have been either higher or lower than
the appropriate limit value for at least the set debouncing time for a message to be triggered.
Display unit
A unit, e.g. "V", which is inserted into the text block #AI1#, #AI2#,
together with the measured value.
Max. 3 characters.
Upper limit value
If the measured value exceeds the upper limit value, a message
can be triggered.
Further messages can only be triggered if the measured value has
fallen below the lower limit value and has then again risen above the upper limit value.
Text for upper limit value
A text that can be inserted into the message text using the text
block #VAL#; thus, it is possible to modify the message text
4-48
Configuration
dynamically, depending on the particular event;
max. 16 characters.
Report
If this field is checked, a message is triggered when the upper limit
value is exceeded.
Lower limit value
If the measured value is lower than the lower limit value, a
message can be triggered.
Further messages can only be triggered if the measured value has
risen above the upper limit value and has then again fallen below the lower limit value.
Text for lower limit value
A text that can be inserted into the message text using the text
block #VAL#; thus, it is possible to modify the message text dynamically, depending on the particular event;
Max. 16 characters.
Report
If this field is checked, a message is triggered when the measured
value falls below the lower limit value.
Signalling when the measured value is lower/greater than a limit value
If the measured value falls below the lower limit value or exceeds
the upper limit value, a message is triggered.
Further messages can only be triggered after the measured value
has fallen below or exceeded the corresponding other limit value.
Change
Signals when a measured value changes.
A message can be triggered if a measured value changes by a
certain amount.
The appropriate change is specified as a percentage and refers to
the measuring range of the input, e.g. voltage 0 ... 10 V; 10 % corresponds to a change of 1 V.
NOTE
If a measured value is monitored for changes, the debouncing time is not considered, meaning that a message is triggered immediately if the measured value changes accordingly.
4-49
4.6 Alarm Message
Configuration
Input
The following events can be selected to trigger a message:
REPORT An error has occurred, e.g. faulty login into the GPRS network DI1 ... DI4 Digital inputs 1 to 8 AI1 … AI2 Analog inputs 1 and 4 EI1 … EI16 Signal inputs, serial, via the TUP protocol
Text
Enter the text you wish to be displayed in the message in the text
field, for example "Fault: Pump".
The maximum length permitted, including all text blocks, is 160
characters.
Longer texts will be truncated.
The following text blocks can be used to create a message text
dynamically:
#HEAD# Inserts the header (menu option "General").
#DATE# Inserts the sending date of the message.
#TIME# Inserts the sending time of the message.
4-50
Configuration
#VAL# Inserts the text for the input belonging to the message,
depending on its value at the time when the message was triggered.
#DI1# ... DI8# Inserts the text for the digital input belonging to the
message, depending on its value at the time when the message was triggered.
#AI1# ... AI4# Inserts the measured value and its unit for the
analog input, depending on its value at the time when the message was triggered.
#ATIME# Time when the message is triggered
#ADATE# Date when the message is triggered
Message Target
To configure the appropriate message sequence:
8 message targets can be defined per input.
The message targets are contacted one after the other until a
message has been sent successfully; this makes sense, for example, with graduated standby services.
NOTE
Enter the appropriate target mobile telephone number for short
messages (SMS).
Enter the appropriate target e-mail address for e-mails, etc.
Service
Select the appropriate transmission method,
e.g. D1 SMS = Send SMS via the D1 network / E-mail = Send e-
mail to the specified address, etc. ...
The messaging service must correspond to the target! For example, you cannot sent an SMS to an e-mail address.
; ACKN
If acknowledgement is possible for this messaging service (menu
option "Messaging services"), this feature can be activated here.
; ALW
Message targets that are always to be informed irrespective of the
message sequence.
4-51
Configuration
The message targets form a message sequence.
The message sequence is interrupted if a target of this sequence was informed successfully, including acknowledgement.
If a message target is to be informed in any case, irrespective of
its position in the message sequence, the message targets must be marked additionally with "ALW".
- Example: Shift schedule in a sequence of 3 and additionally a fax to the exchange centre, which is always to be sent. -
Message targets that are marked with an "I" have no influence on
the message sequence, i.e. even if such a message target was informed successfully, the message sequence is not quit.
Weekday
The relevant message is only sent on the marked days of the week;
thus, a simple shift schedule can be realised.
from - to
The message is sent during the time "from - to".
NOTE
If the time period passes midnight, the message is still sent even if
the second day of the week is not marked, for example, from = 07:00 p.m. to = 08:00 a.m. Mon Tue is marked. If the input is now triggered on Wednesday at 07:50 a.m., the message is sent even though Wed is not marked.
Switch if
Here you can specify that one of the digital outputs can be
switched:
If no message target was informed successfully.
If one message target was informed successfully.
If all message targets were informed successfully.
Message targets marked with "ALW" are ignored.
Save your settings before switching to a different input!
4-52
4.7 Message Services
Configuration
List box "Messaging services"
D1 SMS
D2 SMS (Vodafone)
E+ SMS
FAX
E-mail
VOICE
Use the NEW button to create a new messaging service.
An unambiguous name must be specified.
Name
The name of the messaging service can be changed.
Max. 8 characters (no letters with accents).
Protocol
Transfer protocol
Max. 8 characters
Text length
Maximum length of the message text
Max. 160 characters; for pagers only 80 characters permitted.
If the field is empty, no check is performed to determine whether a
message text has actually been configured (e.g. for voice messages).
1 ... 160
4-53
Configuration
Country code
A prefix placed in front of the actual target number of the recipient
for this messaging service.
Leading zeros in the number of the recipient are omitted,
for example, country code = 0049 target number = 0171 1234567; in this case, the message is sent to 0049171 1234567.
It is recommended to use the syntax 0049, 0041... .
The country prefix can also be entered directly in the target number
of the recipient (menu option "Messages").
Max. 8 characters
Country code SMSC
A prefix placed in front of the actual SMSC dialling number for this
messaging service.
Leading zeros in the number of the recipient are omitted,
for example, country prefix SMSC = 0049 SMSC dialling number = 01770610000; in this case, the short message is sent to 0049
01770610000.
It is recommended to use the syntax +49, +41... .
Max. 8 characters
Phone number SMSC
Various messaging services require that an SMSC (Short Message
Service Centre) is involved; this centre is used, for example, to send the SMS.
This dialling number is provider-dependent.
An incorrect SMSC may be the cause for an SMS not reaching the
recipient.
Max. 30 characters
Init String
Additional information which can be transmitted in addition to the
relevant messaging protocol.
Max. 30 characters
Receipt if possible
With various messaging services, an additional acknowledgement
call is possible, with others not (e.g. fax, e-mail).
yes/no
4-54
NOTE
Configuration
The messaging service "E-mail" requires an e-mail account, see Section 4.9.
If you select E-mail, a link is displayed to another menu option where you can make further settings required for this messaging service.
Further settings
ISP
For selecting an Internet service provider which has been set up
under IPS settings, see Section
4.8.
Host name
A name that identifies the device; can be selected freely.
Sender's e-mail address
The e-mail address that belongs to the e-mail account (access) of
the IPS, see above.
4-55
Configuration
SMTP server/IP
Server via which the e-mail is to be sent
This server is bound to the e-mail account.
Either a server name or an IP address can be specified; syntax:
aaa.bbb.ccc.ddd, for example 213.165.64.20 These data are provided by your e-mail provider.
This server can be compared with the posting box used to send
conventional letters.
Authentication
Most e-mail providers require an authentication to send e-mails via
an SMTP server.
Selection:
none
No authentication is required, or the authentication is provided via the senders and often via the recipient's e-mail address (see Section 4.6 Alarm Message).
In other words: Only e-mails with certain addresses can be sent.
SMTP after POP
An authentication procedure which is supported by many e-mail providers.
Before sending an e-mail, the user must access his e-mail inbox (see below) using his password and his user name. Subsequently, he is left a defined time window of, for example, 15 minutes, within which he may send e-mails via SMTP. Thus, the successful POP authentication serves as an authentication for sending via SMTP.
SMTP AUTH
An authentication method which is supported by many e-mail providers.
With a user name and password, a user is entitled, for example, to send e-mails via the above-specified SMTP server.
4-56
Configuration
POP Server IP
Inbox server of your e-mail account
This server can be compared with the letter box for receiving
conventional letters.
User ID
The user name or, for example, the customer number of your e-
mail account.
Password
The password that is used for access to the inbox or for the SMTP
authentication.
Password confirmation
A confirmation (input repetition) of your password to avoid incorrect
inputs.
4.8 ISP settings for the Internet access
The provider supported by the Weidmüller is Vodafone.
4-57
Configuration
An e-mail is always sent via the Internet. To this end, an Internet Service Provider must be configured through which access to the
Internet is possible from a mobile wireless device.
There are call-by-call providers allowing this access; furthermore, all mobile service providers offer their own Internet access (see your Mobile Service Agreement).
ISP1
Connection
GPRS or GSM
For functions that are permanently online, no GSM should be used
(excessive costs)
Provider
Vodafone (the name for the provider can be selected freely)
It should be visible whether GSM or GPRS is used.
Max. 30 characters
Call number
The number at which the provider is to be reached.
Max. 50 characters.
Access Point
Required for connection to the GPRS network.
For Vodafone: www.vodafone.de
Max. 50 characters.
Init
Additional initialisation commands (AT commands)
Could be necessary for GPRS, but is generally not required
(for Germany and Switzerland not necessary to date)
Max. 50 characters.
User name
The name with which the user is to be logged into the ISP.
Max. 30 characters
Password
The password which is to be used when logging into the ISP.
Max. 30 characters
4-58
Configuration
DNS1
Optional DNS (Domain Name Server)
Syntax: e.g. 217.237.151.97
Normally, no entry is necessary, since the settings are transferred
by the ISP.
Even if a DNS is received by the ISP, it is not this entry which is
used, but that of the ISP.
DNS2
Optional DNS (Domain Name Server)
Notification: e.g. 217.237.151.97
Normally, no entry is necessary, since the settings are transferred
by the ISP.
Even if a DNS is received by the ISP, it is not this entry which is
used, but that of the ISP.
Two ISPs can be configured, e.g. one for GPRS and one for GSM.
Thus, if GRPS is not available, it is nevertheless possible to send an e-mail as an error message.
ISP2
ISP2 is the backup connection for ISP1. Status messages via e-mail are sent via IPS1 and GPRS by default. In case of failure of this connection, an error message, e.g. via e-mail, is sent via the connection configured under ISP2. Thus, alternative sending is possible via GSM.
4-59
Configuration
4.9 Function control
The IE-GPRS-I/O can issue a cyclic message (sign of life) as a function monitoring signal.
Text
Enter the text you wish to be displayed in the message in the text
field, for example " Fault: Pump1".
The maximum length permitted, including all text blocks, is
160 characters. Longer texts are truncated.
It is possible to use text blocks to create a message text dynamically, see Section 4.6 Alarm Message.
Target
Two targets can be specified.
Enter the appropriate target mobile telephone number for short
messages (SMS).
Enter the appropriate target e-mail address for e-mails, etc.
Sun - Sat
Enter the day of the week, time 00:00 and interval 0 min here.
The message is sent on the weekday set and at the time set.
If an interval > 0 has been set, a message is issued at the
interval as specified in minutes. This process ends at midnight of the set weekday.
4-60
Configuration
; ACKN
If acknowledgement is possible for this messaging service (menu option "Messaging services"), this feature can be activated here.
; ALW
The message targets form a message sequence, in other words:
If a target of this sequence was informed successfully (including acknowledgement), the message sequence is cancelled.
If, however, a message target is to be informed in all cases, this
target can be marked under "ALW".
Message targets that are marked with "I" have no influence on
the message sequence. In other words: Even if such a message target was informed successfully, this does not end the message sequence.
Switch if … Message was successful
Here you can specify that one of the two digital outputs is to be switched if:
No message target was informed successfully.
One message target was informed successfully. All message target were performed successfully.
Message targets marked with an "I" are ignored.
4-61
Configuration
4.10 Server
The Internet exchange server is operated with further partners on behalf of Weidmüller. The server is a relational database which can be accessed externally via SQL queries. The server itself need not be configured externally by the customer. To be able to use the server, only the following settings are required:
Interconnection between two or several IE-GPRS-I/Os to one another can only be provided via the exchange server. The exchange server performs the data transfer from one IE-GPRS-I/O to the other IE-GPRS-I/O or within a group of several IE-GPRS-I/Os.
All IE-GPRS-I/Os log into the exchange server with a password, a code and a group. Several IE-GPRS-I/Os of a group can communicate with each other; the communicate with each other.
IE-GPRS-I/Os may be master, slave or master/slave.
A master sends data to all slaves and master/slaves of a group, not to other masters. The master receives data from all slaves and master/slaves of a group, but not from other masters.
A slave sends data to all masters and master/slaves of a group, not to other slaves. The master receives data from all masters and master/slaves of a group, but not from other slaves.
IE-GPRS-I/Os of different groups, however, cannot
ISP
Internet service provider via which the IE-GPRS-I/O establishes
connection to the exchange server
GPRS should be set as the service used (see 4.8 ISP settings for
the Internet access).
4-62
Configuration
Server
Server name
Can be resolved via DNS or
Server IP address
If both are entered, an attempt is made first to reach the server via
its server name.
ID
Each IE-GPRS-I/O must contain an unambiguous name for
identification within a group. Observe use of uppercase/lowercase letters!
Password
Password for identification
Observe use of uppercase/lowercase letters!
Group
Communication group to which the IE-GPRS-I/O is to belong.
Observe use of uppercase/lowercase letters!
4-63
Configuration
Mode
Master:
Master IE-GPRS-I/O talks -> all slaves listen
Slave:
Slave IE-GPRS-I/O talks -> only the master listens
Master/slave:
Listens to everybody
Connect automatically
If Connect automatically is enabled, the IE-GPRS-I/O
attempts to establish the connection to the exchange server automatically after a reset.
Send all input states
Time interval at which the IE-GPRS-I/O sends its input status to the
exchange server
0 means that the input status is sent not cyclically.
4.11 COM port
Settings for the serial interface for the data traffic with connected devices. The serial interface is only activated in the DIP switch position
1-0-0-0 in the "Configuring" mode; in the "Diagnostic" mode 0-1-0­0, it is set to 38,400 Baud as a fixed transfer rate.
See Section 3.4 Communication between PC and IE-GPRS-I/O.
4-64
Configuration
4.12 Logbook
The IE-GPRS-I/O manages a logbook where important events, messages etc. are entered.
Max. 255 entries are possible. If this number is exceeded, the oldest entries are overwritten. The entries can be viewed and deleted under the menu option "Logbook". Normally, the log file need not be reset.
The entries are displayed in the form "Weekday", "Date", "Time", "Event" and "Error code".
4-65
Configuration
4.13 Cost control
The IE-GPRS-I/O monitors the data volume for GPRS connections and the online time for GSM connections.
To this end, you must enter the specifications from your mobile subscriber agreement in the menu Cost control.
Rounding error
Each time a connection is established to the GPRS network, the
provider debits a certain data volume from you at a flat rate. The amount of this value depends on the appropriate mobile subscriber agreement. It is recommended to use ALWAYS a tariff model with a rounding error as low as possible.
Reset to
Date on which the counters are reset to 00:00 o'clock
4-66
Limit value
Byte counter
The following limit values can be set for two graduated report messages.
Example:
If a volume tariff of 10 MB/month was agreed with the mobile
service provider, with byte counter1 = 5 MB, a report message is issued when half of this volume has been used, and with byte counter2 = 8 MB again at 80 %. The setting is made in the menu "Messages", see Section
Online time
Due to technical reasons, the counter can only provide a rough overview (guide value) of the actually used volume.
Example:
Necessary repetitions when sending data which cannot be
protocolled by the
IE-GPRS-I/O
4.6 Alarm Message.
Configuration
CAUTION
Different protocol overheads when sending
Counter
Current counts
The displayed values apply with reservation and serve only as guide values to provide an overview. No guarantee can be given for the correctness of the above­mentioned counter values, as the invoicing procedures of the individual providers may differ.
The invoices of the provider are binding.
4-67
4.14 Troubleshooting
4.15 Systemtime
Configuration
When the IE-GPRS-I/O starts an Internet connection (e.g. for sending an e-mail), it can match its system clock with a time server (SNTP server) on the Internet.
Summer time
Summer/winter time is observed when setting the clock.
4-68
SNTP server
IP address or host name of the time server
Default setting: Time server 1 of PTB in Braunschweig
Time zone in which the IE-GPRS-I/O is located (Germany +1)
If "Set clock" is set, the time match is performed when the Internet
connection is first established.
The internal clock is backed up for approx. 75 hours. If the IE-GPRS-I/O remains without operating voltage for longer, the clock must be reset via the time server.
Configuration
ATTENTION
4.16 About
Homepage of the manufacturer
Ver: Version number of the operating system
4-69

5 Hardware

5.1 Installation
This chapter provides all relevant information on the dimensions.
5.1.1 Dimensions
The diagram below shows the dimensions of the IE-GPRS-I/O:
Hardware
Dimensions [mm]
Height 156 plus space for connectors and lines of the
inputs and outputs above and beneath the device
Width 44
Depth 140 plus space for connectors and lines for the
power supply, for the serial interface connector and for the aerial/aerial connector
5-70
NOTE
5.1.2 Installing the top-hat rail
The IE-GPRS-I/O can be fastened on a top-hat rail which complies with the standard EN 50022:
1
35
7,5
This top-hat rail must be fastened on the control cubicle wall such that a conductive connection is provided.
Observe the instructions of the manufacturer with reference to fastening.
Hardware
NOTE
Installation
Pull the top-hat rail downwards, at the same time pushing the device back onto the top-hat rail.
Removal
The top-hat rail adapter is offered in two variants, resulting in the different direction of movement when unhooking from the top-hat rail. Therefore, before unhooking, check whether the IE-GPRS-I/O is to be moved upwards or downwards against the retaining spring.
To remove the device, unhook it by pushing it firmly upwards or downwards, and then remove it forwards from the top-hat rail.
5-71
Hardware
5.1.3 Wall mounting
There are two mounting plates intended for mounting of the device on the wall. The mounting plates are fastened with screws on the rear side of the housing and must be mounted as shown in the illustration. The top-hat rail adapter must be removed if you mount the device on the wall.
Mounting using a top-hat rail Mounting on the wall
5-72
When mounting a top-hat rail adapter on the rear of the housing, it is imperative to observe the correct position of the retaining spring:
Hardware
NOTE
Plastic variant: Retaining spring at the bottom
Aluminium variant: Retaining spring at the top
CAUTION: Incorrect mounting will reduce the retaining force of the top-hat rail adapters.
Only use the original screws of the top-hat rail; longer screws will damage the electronics of your IE-GPRS-I/O. The screws to be used are M3 x 8 round head for adapters with plastic insert and M3 x 4 countersunk head for aluminium adapters.
5-73
Hardware
5.2 Installation notes
Make sure that at least 35 mm of space is left above the module.
A space of 35 mm must be provided beneath the module for routing of the cables for the interfaces and for the power supply.
5.2.1 Functional earthing
For functional earthing, connect the "Functional earthing" terminal on the housing of the IE-GPRS-I/O to the equipotential bonding of the control cabinet.
The connection "Functional earth" serves for purely operational functions (modem function).
Make sure that the cross-section of the interconnecting line does not exceed 4 mm2.
5-74
Hardware
5.3 Installation guidelines
The specified maximum operating temperature pertains to the air temperature beneath the IE-GPRS-I/O (air inlet).
Observe a sufficient distance to devices emitting strong electromagnetic radiation (such as frequency converters, transformers, motor controllers, etc.). The clearance between these devices and the IE-GPRS-I/O should be as large as possible. If necessary install a shielding of partition walls (MU metal).
Do not plug or remove the devices during operation!
Before removing a IE-GPRS-I/O, also remove the relevant plugs and connectors.
Do not connect or remove the connectors if the supply lines are still live (all-pole disconnection).
5.4 Storage and storage temperatures
The following values will apply for storing:
Storage temperature: -10 ... +70 °C
Humidity: 30 ... 95 % (not condensing)
5.5 Operating temperature, humidity
The following values will apply for operation:
Operating temperature with vertical mounting position: -10 ... +55 °C
Humidity: 30 ... 95 % (not condensing)
5-75
Hardware
5.6 Status display
Three LEDs are located on the front panel of the IE-GPRS-I/O to display the operating status. To display the status of the port, 12 further LEDs are installed on the upperside/underside of the device to display the states of the digital inputs/outputs.
Status of the GPRS/GSM communication
Voltage level at the
digital inputs/outputs
Mode selector switch
Operating state of the IE-GPRS-I/O
Status of the operating voltage
5-76
5.6.1 Display "POWER on/off"
LED Description
OFF The supply voltage is turned off.
Lights red
Lights green The supply voltage is turned on.
Insufficient power supply
IE-GPRS-I/O is not ready for operation.
The
5.6.2 "Status" display
LED Description
OFF -
Lights red During the phase of initialisation of the IE-GPRS-I/O
Lights green IE-GPRS-I/O in the standby mode
Flashes quickly green Flashes slowly green Flashes quickly red
Flashes slowly red Flashes quickly red
Connection to the exchange server established
Message is just being issued
Error while signalling (if DIP1 OFF)
In the "Programming" mode (DIP1 ON), but long-distance data transmission connection not yet established In the "Programming" mode (DIP1 ON) and long-distance data transmission connection established
Hardware
5.6.3 "Line" display
"Line" LED Description
OFF offline
Lights green GSM module is ON Flashes slowly green Flashes quickly green
GSM module is logged into the GSM network (SIM PIN OK)
Call detected, call accepted
5-77
5.6.4 "Ports" display
LED 1 … 4 Digital inputs DI1 ... DI4
OFF Digital input DIx not active
Lights green Digital input DIx active, but debouncing time not yet expired
Flashes slowly green Flashes quickly green
LED 1 … 4 Resetting to the factory settings
Flash together green for 5 s Go out one after the other
All OFF Factory settings set
LEDs 5 ... 6 Digital outputs DO1, DO2
Debouncing time expired; digital input DIx has tripped
The digital input DIx is being processed
Waiting time until resetting to factory settings
Resetting to the factory settings
Hardware
OFF Digital output DOx OFF
Lights green Digital output DOx ON
LEDs 7 … 10 Digital inputs DI5 ... DI8
OFF Digital input DIx not active
Lights green Digital input DIx active, but debouncing time not yet expired
Flashes slowly green Flashes quickly green
LEDs 11 … 12 Digital outputs DO3 ... DO4
OFF Digital output DOx OFF
Lights green Digital output DOx ON
Debouncing time expired; digital input DIx has tripped
The digital input DIx is being processed
5-78
Hardware
5.7 Connections / interfaces
The connection for the power supply, the serial interface RS232, the connection for the external aerial and the slot for the telephone card are located on the front panel of the IE-GPRS-I/O:
Aerial connection for the FME connector
Plug-in SIM card
RS232 interface Sub-D female socket connector
Power supply
5.7.1 Power supply
The IE-GPRS-I/O can be supplied either with +10 … 36 VDC or with 8 … 24 VAC. The power consumption is approx. 5 W.
5-79
DANGER
Power supply connection
The Alarm Modem IE-GPRS-I/O must only be connected to the electrical supply system by an electrical expert.
The power supply of the Alarm Modem IE-GPRS-I/O must be provided exclusively by a power pack which complies with DIN EN 60 742 (VDE 0551).
Hardware
CAUTION
Make sure that an appropriate fuse is installed in the incoming supply feeder.
5.7.2 RS232
The RS232 interface is intended for the connection of a PC or a notebook with which the start-up and parameterisation may be carried out on the spot (see Section 4).
5.7.3 Inserting the SIM card
A SIM card is used to set the selected tariff and the possible communication services for the IE-GPRS-IO.
Before you insert the SIM card, first turn off the device!
Use a pointed object to press gently into the hole beneath the SIM card compartment and open the SIM card compartment. Insert the SIM card into the card compartment such that the contact faces are visible.
5-80
Pin assignment of the terminals on the device underside
GND Digital earth signal digital in 1 … 4 GND
1 DI1 0 ... 30 V DC signal digital in 1
2 DI2 0 ... 30 V DC signal digital in 2
3 DI3 0 ... 30 V DC signal digital in 3
4 DI4 0 ... 30 V DC signal digital in 4
GND Signal digital GND digital in 1 … 4 GND
5 DO1.1 0 ... 30 V DC signal digital out 1
5 DO1.2 0 ... 30 V DC signal digital out 1
6 DO2.1 0 ... 30 V DC signal digital out 2
6 DO2.2 0 ... 30 V DC signal digital out 2
DIP 0-0-x-x
DIP 1-0-x-x AI1 PT1000 (minus)
DIP 0-1-x-x 0 ... 20 mA signal analog in 1 Current
GND GND2 Signal analog earth analog in 1 … 2 GND
DIP x-x-0-0
DIP x-x-1-0 AI2 PT1000 (minus)
DIP x-x-0-1 0 ... 20 mA signal analog in 2 Current
0 ... 30 V DC signal (minus)
0 ... 30 V DC signal (minus)
analog in 1 Voltage
analog in 1 Temperature
analog in 2 Voltage
analog in 2 Temperature
Hardware
5-81
Pin assignment of the terminal on the device upperside
GND GND3 Digital earth signal digital in 5 … 8 GND
7 DI5 0 ... 30 V DC signal digital in 5
8 DI6 0 ... 30 V DC signal digital in 6
9 DI7 0 ... 30 V DC signal digital in 7
10 DI8 0 ... 30 V DC signal digital in 8
GND GND3 Signal digital GND digital in 5 … 8 GND
11 DO3.1 0 ... 30 V DC signal digital out 3
11 DO3.2 0 ... 30 V DC signal digital out 3
12 DO4.1 0 ... 30 V DC signal digital out 4
12 DO4.2 0 ... 30 V DC signal digital out 4
DIP 0-0-x-x
DIP 1-0-x-x AI3 PT1000 (minus)
DIP 0-1-x-x 0 ... 20 mA signal analog in 3 Current
GND GND4 Signal analog earth analog in 3 … 4 GND
DIP x-x-0-0
DIP x-x-1-0 AI4 PT1000 (minus)
DIP x-x-0-1 0 ... 20 mA signal analog in 6 Current
0 ... 30 V DC signal (minus)
0 ... 30 V DC signal (minus)
analog in 3 Voltage
analog in 3 Temperature
analog in 4 Voltage
analog in 5 Temperature
Hardware
5-82
g
g
g
g
Settings of the analog inputs
Hardware
1 2 3 4
OFF OFF
ON
OFF
ON
OFF
1 2 3 4
OFF OFF
ON OFF
ON OFF
1 2 3 4
OFF OFF
ON
OFF
ON
OFF
1 2 3 4
OFF OFF
ON OFF
ON
OFF
AI1 - Analo
input 1
Connection of voltage sensors 0 … 10 V
Connection of current sensors 0 … 20 mA
Connection of resistance thermometers PT1000
AI1 - Analo
input 2
Connection of voltage sensors 0 … 10 V
Connection of current sensors 0 … 20 mA
Connection of resistance thermometers PT1000
AI1 - Analo
input 3
Connection of voltage sensors 0 … 10 V
Connection of current sensors 0 … 20 mA
Connection of resistance thermometers PT1000
AI1 - Analo
input 4
Connection of voltage sensors 0 … 10 V
Connection of current sensors 0 … 20 mA
Connection of resistance thermometers PT1000
5-83

6 Technical Data

Type Designation
Alarm Modem IE-GPRS-I/O Art. no. 8850060000
Design
Material of the housing Aluminium Colour RAL 9005 deep black matt Degree of protection - housing IP20 Degree of protection - terminals IP20
Protection against hazardous shock currents
Mechanical Data
Dimensions (H x W x D) 155 x 45 x 137 mm
Fastening on the top-hat rails to DIN 50 022 Connection technique
- Connections of the Power supply
- Connections of the digital inputs
- Connections of the digital outputs
- Connections of the digital inputs and outputs
- RS232
- Aerial connection Conductor cross-sections of the power supply connections
Safety extra-low voltage + protective separation
Plug connector with self-disengaging screw terminals 2 plug connectors, 6-pin, with self-disengaging screw terminals 4 plug connectors, 2-pin, with self-disengaging screw terminals 2 plug connectors, 3-pin, with self-disengaging screw terminals Socket, Sub-D type GSM900/1800 MHz FME connector min. 0.5 mm² max. 2.5 mm²
Technical Data
Environmental Conditions Ambient temperature -
operation Ambient temperature - storage -10 ... +70 °C
Relative humidity - operation min. 30 % / max. 90 % (not condensing) Relative humidity - storage min. 30 % / max. 90 % (not condensing)
-10 ... +55 °C
6-84
Technical Data
Electrical Data
The power supply of the
Power supply
Rated operating voltage 10 … 36 VDC / 8 … 24 VAC Rated operating capacity 5 W Fuse, external T2A Rated frequency 50 Hz ... 60 Hz Redundancy Redundant power supply
Inputs/outputs Digital inputs
- Input voltage range
Digital outputs
- Output voltage range
Analog inputs
- Input voltage range
- Input current range
- Temperature
RS232 EIA RS-232-C/CCITT V.24 to 38.4 Kbit/s
Wireless GSM/GPRS 900/1,800MHz
General specifications Error messages Via GSM if configured
provided exclusively by a power pack which complies with DIN EN 60742 or VDE 0551.
12/24 VDC 0 … 30 V DC against GND of the same connector Insulation voltage 500 V 12/24 VDC 0 … 30 V DC against GND of the same connector Insulation voltage 500 V
0 … 10 V Max. 30 V, input resistance 180 kOhm Insulation voltage 500 V 0 … 20 mA Max. 100 mA, input resistance 100 kOhm Insulation voltage 500 V PT1000 Insulation voltage 500 V
1 DCD Received Line Signal - Data Carrier Detect 2 RxD Received Data 3 TxD Transmitted Data 4 DTR Data Terminal Ready 5 GND Signal Ground/Common Return 6 DSR Data Set Ready 7 RTS Request to Send 8 CTS Clear to Send 9 RING Ring Indicator
Asynchronous, full/half-duplex or simplex
IE-GPRS-I/O must be
6-85
Standards and Certifications

7 Standards and Certifications

7.1 Harmonised standards
EN 50081-1 Noise emission for residential, commercial and light­industrial environment
EN 61000-6-2 Noise immunity for the industrial environment
7.2 Certification to DIN EN ISO 9001
The Weidmüller Interface GmbH & Co. KG is certified to ISO 9001.
7.3 Approbations
7.4 CE marking
EU Low-Voltage Directive
EC Certificate of Conformity on request
7-86

8 Symbols Used

Connection for the functional earthing
Mains transformer
d.c. power supply source
Symbols Used
Battery (emergency power)
8-87
Glossary

9 Glossary

This chapter provides a list of all abbreviations and special terms used in this Manual with their meanings.
A
AT commands
The term 'AT commands' is used for the commands that were originally used by the company Hayes and thus have become quasi-standard for configuring and parameterising modems.
B
C
D
DNS
The Domain Name System (DNS) is one of the most important services on the Internet. The DNS is a distributed database that manages the name space on the Internet. Generally, the DNS is used to convert names to addresses (forward lookup). This is comparable with a telephone book that resolves the names of the subscribers into their telephone numbers. For example, you can remember the domain name www.wikipedia.de very easily, whereas the related IP address 207.142.131.236 is not so easy to remember.
DHCP
Dynamic Host Configuration Protocol. An IEFT (Internet Engineering Task Force) protocol. The Dynamic Host Configuration Protocol is the function used by the DHCP client to fetch a TCP/IP address from a central computer (DHCP server). The DHCP server assigns the client this IP address from a defined address range dynamically. In other words: The client is always assigned a new, but unambiguous IP address so that DHCP can supply, for example, mobile PCs, with IP addresses.
Download
Download is a technical term from the field of IT. During a download, the data are requested from a remote station (e.g. network computer, Internet) and transferred to the computer. The download is thus the opposite to the upload.
9-88
Dynamic IP
IP address, is assigned to the client from a defined address range dynamically, e.g. via a DHCP server.
E
F
Fixed IP
Fixed IP addresses are assigned statically to the client by the appropriate Internet provider.
G
GSM
The Global System for Mobile Communications (GSM) is a fully digital mobile communication network standard that is used mainly for telephony, but also for line-switched and packet-switched data transfer and for short messages (SMS).
Glossary
GPRS
GRPS is an extension of the GSM mobile telecommunication standard - a packet-oriented data transfer which - at least for advertising purposes - is often also called 2.5G (two point fifth generation). This naming is effectively a reference to UMTS (3G). Unlike than the line-switched data service HSCSD, GPRS is packet-oriented. In other words: While still at the sender, the data are converted into individual packets, transferred as such and recompiled with the recipient.
H
I
IPCP
IP Control Protocol. A network control protocol that - among other services - serves for negotiating of a compression algorithm and for transfer of a dynamic IP address (RFC1332).
ISP Internet Service Provider
IP
The Internet Protocol (IP) (also called Internet protocol) is a network protocol widely used in computer networks. It is an (or indeed the) implementation of the Internet layer of the CP/IP model.
J
K
L
LED Light Emitting Diode
9-89
M
N
O
P
Private IP
Private IP addresses or private networks are IP addresses/subnets that can be used for any purpose and by everybody. However, they are not routed on the Internet.
POP3
Address of the Internet service provider for fetching e-mails
PPP
Point to Point Protocol. Universal point-to-point protocol that includes various forms of connection, a dynamic understanding on options, authentication functions and also functions for establishing and cancelling connections and their monitoring.
Glossary
ACKN
R
S
SMS
Short Message Service (SMS) is a telecommunication service for the transferring of text messages which was originally developed for GSM mobile communication and is now also available in the wireline network. Further developments of SMS exist under the names Enhanced Message Service (EMS) and Multimedia Messaging Service (MMS).
SMTP
Address of the Internet service provider for sending e-mails
SNMP Simple Network Management Protocol
9-90
T
TCP
The Transmission Control Protocol (TCP) is a reliable, connection­oriented transfer protocol in computer networks. It is part of the TCP/IP protocol family. TCP provides a virtual channel between two computers (more exactly: the end points (sockets) of two applications on these computers). Data can be transferred on this channel in both directions. In the most cases, TCP is based on the IP protocol.
U
UDP
The User Datagram Protocol (UDP) is a minimum network protocol without connection. It is part of the transport layer of the TCP/IP protocol family and is - in contrast to TCP - not designed for reliability. UDP has the main objective to extend the connection to the end system established by the IP layer by a user interface (ports). The quality of the underlying services, in particular, the reliability of the transfer, however, is not increased by the UDP.
Glossary
Upload
Upload is a technical term from the field of IT. During an upload, data are transferred from a computer to a remote station (e.g. network computer, Internet). The upload is thus the opposite to the download.
V
VPN
A Virtual Private Network (VPN) is a computer network that uses a public network (for example, the Internet) to transfer private data. Subscribers to a VPN can exchange data in the same way as in an internal LAN. The connection of the networks is provided by a tunnel between VPN client and VPN server. In the most cases, the tunnel is secured, but an unsecured clear-text tunnel is also a VPN. IP VPNs use the Internet for transferring IP packets independently of the transmission network, which - in contrast to direct remote access to an internal network (direct dialling, for example, via ISDN, GSM...) - provides significantly more flexibility and is more cost­effective.
9-91
9-92
Loading...