Weidmuller G128 User Manual

Page 1
Weidmuller Ltd. 10 Spy Court Markham, ON L3R 5H6 Tel: (905)475-1507 Fax: (905)475-5855
Weidmuller Inc. 821 Southlake Blvd. Richmond, VA 23236 U.S.A. Tel: (804)794-2877 Fax: (804)794-0252
ISO 9001 Registered
Electronic Interface Modules
G128 Ultra SlimPak®
Thermocouple Input, Field Configurable Limit Alarm
• field configurable via DIP switches for different input­output combinations
• provides relay contact closure(s) at a preset temperature input level
• field configurable input ranges for J, K, T, R, S, E and B type thermocouples
• setpoints programmable HI or LO and failsafe or non­failsafe
• LED trip and input indicators
• 9 to 30Vdc powered
• CSA approved, UL recognized, CE marked
Page 2
Description
Diagnostic LEDs
Output
Operation
Dynamic Deadband
The Ultra SlimPak G128 is a DIN rail mount, thermocouple input limit alarm with input terminal cold junction compensation (cjc), dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. There are up to six temperature ranges available for each thermocouple type to ensure accuracy and maximize setpoint resolution. A bipolar input switch is provided for temperature ranges below 0°C. The G128 is configurable as a single or dual setpoint alarm, with HI or LO trips, upscale or downscale thermocouple burnout detection and failsafe or non-failsafe operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint and a flexible DC power supply which accepts any voltage between 9 and 30Vdc.
The G128 is equipped with three front panel LEDs. The first is a dual function LED labeled INPUT. This green LED indicates DC power and input signal status. Active DC power is indicated by an illuminated LED. If this LED is off, check line power and wiring connection. If the input signal is more than 110% of the full scale range, the LED will flash at 8 Hz. Below 0%, the flash rate is 4 Hz. Two red LED's indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.
The G128 is equipped with two SPDT (form C) relays, rated at 120Vac or 28Vdc at 5 amperes. Each of these relays is independently controlled by the field configurable set point and deadband.
The field configurable G128 limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has a respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the low deadband (see Figure 1). For proper deadband operation, the HI setpoint must always be set above the LO setpoint. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.
LSI circuitry in the G128 prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This effectively results in a "dynamic deadband" - based on time- in addition to the normal deadband.
Table 1 G128 input range selector - switch settings
Key: n ON
Figure 1
+
Load
Relay
Conta cts
Diode
(optio nal)
Figure 2: DC Inductive Loads
Relay
Conta cts
Figure 3: AC Inductive Loads
47 ohm
1/2W
47 ohm
1/2W
Load
MOV
0.1uF
0.1uF
Film
Film
Power
Power
-
Page 3
Unless otherwise specified, the factory presets the Model G128 as follows: Input: J Type Range: 0 to 350°C Output: Dual, SPDT Trip: A: HI, B: LO Failsafe: No Deadband: A, B: 0.25% The DC power input accepts any DC source between 9 and 30V, typically a 12V or 24Vdc source is used. For other I/O ranges, refer to Table 1 and reconfigure switches SW1 and SW2 for the desired input type, range and function.
Do not attempt to change any switch settings with power ap-plied. Severe damage will result!
1. With DC power off, position switch SW1-1, 2, 3 and SW2-1 through 6 for the desired input range (Table 1).
2. Set positions 4 and 5 of function switch "SW1" to ON for a HI trip setpoint or OFF for a LO trip setpoint (Figure 4).
3. Set position 6 of function switch "SW1" to ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon power failure).
4. Set positions 7 and 8 of function switch "SW1" to upscale or down-scale burn-out.
1. After configuring the DIP switches, connect the input to a calibrated TC source and apply power. Refer to the terminal wiring diagram. NOTE: to maximize thermal stability, final calibration should be performed in the operation installation, allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.
2. Setpoint: set deadband at its minimum (20 turns counter clockwise) before adjusting the setpoint. With the desired trip thermocouple millivolt input applied, adjust setpoint until the relay trips. For HI trip calibration, start with the setpoint above the desired trip (20 turns clockwise). For LO trip calibration, start below the desired trip (full counter clockwise).
3. Deadband: Set deadband to its minimum (20 turns counter clockwise). Set the setpoint to desired trip. Adjust thermocouple millivolt input until relay trips. Readjust deadband to 5% (20 turns clockwise). Set voltage/current input to desired deadband position. Slowly adjust deadband until relay untrips.
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 and 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1HF pulse film capacitor (foil polypropylene recommended) of sufficient voltage, and a 47M, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV>DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
Configuration
WARNING:
Calibration
Relay Protection and EMI Suppression
Figure 4: G128 input range/function selection (SW1) Factory default settings
Page 4
Rated data Input
Range
Impedance
Maximum ratings / type of protection
Other input specification Other input specification
Output
Range Load Zero / Span adjustment Protection Other output specification Other output specification
Supply
Range Consumption
General
Accuracy Temperature coefficient (drift) Transmission frequency Response time. 90% span
Other general specification Status LED Isolation (# of ports) Operating / Storage temperature Housing (mounting) Dimensions (L x W x H) Wire range (conductor size) Insulation stripping length Tightening torque Approvals
Ordering data
Ultra SlimPak Heat sink (width) Shunt resistor
Thermocouple temperature sensor Thermocouple Type Temperature Range Thermocouple Type Temperature Range
B 0...1820ºC R 0...1760ºC E -270...1000ºC S 0...1750ºC J -210...760ºC T -270...390ºC
K -270...1372ºC DIP switch selectable 1 Meg M min. ±10Vdc input bias current: <1.5HA
2 form C relays (2 SPDT), one set point per relay, gold flash / silver alloy contacts 2 set points independently adjustable over 100% of the selected input span, HI or LO, failsafe or non-failsafe maximum 5A at 120Vac, 2A at 240Vac, 5A at 28Vdc (resistive load), minimum 10HA at 10mV deadband adjustable from 0.25% to 5% of span external relay contact protection required for inductive load switching Electrical life: 105operations at rated load Mechanical life: 107operations no load DC voltage 9 to 30Vdc, inverter isolated
1.5W typ., 2.5W max. (300mA inrush at 9Vdc)
0.2% for temp. >0°C, 0.3% for temp. <0°C ±0.05% of full scale/°C, max.
<250mS in normal mode, dynamic deadband: relay status will change when proper setpoint/process condition exists for 100mS
input green (>110% of input: 8Hz, <-10% of input: 4Hz), 2 setpoint red (ON: tripped, OFF: safe) 1800V (3 port) between contacts, input and power 0°C to 55°C / -15°C to 70°C EG12 (TS32 and TS35) 90mm x 17.7mm x 112.7mm max. 22-12AWG (0.5-4.0mm2) 7mm
0.4-0.8Nm CSA (file LR-42272), UL (file E99775), CE marked (EMC dir. 89/336/EEC, LV dir. 73/23/EEC)
Cat. No. G128 (factory calibration: 0 to 350ºC (J-type,), A-HI/B-LO, non-failsafe) HS01-A (1.6mm) (conditionally required depending on installation, see heat sink data)
Note: G128-000X where X is the revision level
Specifications subject to change without notice. 99990009 - 8/98 Printed in Canada