Electronic Interface Modules
G108 Ultra SlimPak®
DC Input, Field Configurable Limit Alarm
n field configurable via DIP switches for
different input-output combinations
n provides relay contact closure(s) at a preset
DC input level
n field configurable input ranges 10mV to 200V,
1mA to 100mA
n setpoints programmable HI or LO and failsafe
or non failsafe
n LED trip and input indicators n 24Vdc transducer excitation n 9 to 30Vdc powered n CSA approved, UL recognized, CE marked
Page 2
Description
Diagnostic LEDs
Output
Operation
Dynamic Deadband
The Ultra SlimPak G108 is a DIN rail mount, DC voltage or current input, limit alarm with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. Input voltage spans from 10mV to 200V and input current spans from 1mA to 100mA can be field configured. Bipolar inputs are also accepted. The G108 is configurable as a single or dual setpoint alarm, HI or LO trips and failsafe or non-failsafe operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint, a 24Vdc voltage source (isolated from line power) for transducer excitation, and a flexible DC power supply which accepts any voltage between 9 and 30Vdc.
The G108 is equipped with three front panel LEDs. The green LED is a dual function LED labelled INPUT. This LED indicates line power and input signal status. Active DC power is indicated by an illuminated LED. If this LED is off, check DC power and wiring connection. If the input signal is above 110% full scale, the LED will flash at approximately 8Hz. Below 0%, the flash rate is 4Hz. Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.
The G108 is equipped with two SPDT (form C) relays, rated at 120Vac or 28Vdc at 5 amperes. Each of these relays is independently controlled by the field configurable setpoint and deadband.
The field configurable G108 limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the low deadband (see Figure 1). For proper deadband operation, the HI setpoint must always be set above the LO setpoint. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.
LSI circuitry in the G108 prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This effectively results in a “dynamic deadband” based on time in addition to the normal deadband.
+
Figure 1
Table 1: G108 Input range switch settings (SW1, 1 through 4) KEY z = ON
(optional)
47 ohm
1/2W
47 ohm
1/2W
Load
Load
Diode
MOV
0.1uF
0.1uF Film
Film
Relay
Conta cts
Figure 2: DC Inductive Loads
Relay
Conta cts
Figure 3: AC Inductive Loads
Power
Power
-
Page 3
Unless otherwise specified the factory presets the G108 as follows: Input: Current Range: 0-20mA Output: Dual, SPDT Trip: A:HI, B:LO Failsafe: No Deadband: A, B: 0.25% The DC power input accepts any DC source between 9 and 30V, typically a 12V or 24Vdc source is used. For other I/O ranges, refer to table 1 and Figure 4. Reconfigure switches SW1 for the desired input type, range and function.
Do not attempt to change any settings with power applied. Severe damage will result!
1. With DC power off, position 9 and 10 of SW1 for current or voltage (see Table 1).
2. Set position 1 through position 4 of input range switch “SW1” for the desired input range (see Table 1).
3. Set position 5 of input range switch “SW1" to ON for unipolar (e.g. zero based, 0-20mA) range or OFF for bipolar (e.g. -100% offset, -20 to 20mA) range (see Figure 4).
4. Set position 6 and 7 of input range switch “SW1" to ON for a HI trip setpoint or OFF for a LO trip setpoint (see Figure 4).
5. Set position 8 of input range switch “SW1" to ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon power failure).
1. After configuring the DIP switches, connect the input to a calibrated DC source and apply power. Refer to the terminal wiring diagram.
Note: to maximize thermal stability final calibration should be performed in the operating installation, allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.
2. Setpoint: set deadband at its minimum (fully Counter Clockwise) before adjusting the setpoint. With the desired trip voltage or current input applied, adjust setpoint until the relay trips. For HI trip calibration, start with the setpoint above the desired trip. For LO trip calibration, start below the desired trip.
3. Deadband: Set deadband to its minimum (fully counter clockwise). Set the setpoint to desired trip. Adjust voltage/current input until relay trips. Readjust deadband to 5% (fully Clockwise). Set voltage/current input signal to desired deadband position. Slowly adjust deadband until relay untrips.
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 and 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1HF pulse film capacitor (foil polypropylene recommended) of sufficient voltage and a 47M, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
Configuration
WARNING:
Calibration
Relay Protection and EMI Suppression
Figure 4 G108 Input range/ function selection (SW1), factory default settings
Page 4
Rated data Input
Range Impedance Maximum ratings/type of protection Field device excitation Other input specification Other input specification
Output
Range Load Burnout level Zero / Span adjustment
Protection Other output specification Other output specification
Supply
Range Consumption Other supply specification
General
Accuracy Linearity Temperature coefficient (drift) Transmission frequency Response time. 90% span
Other general specification Status LED Isolation (# of ports) Operating / Storage temperature Housing (mounting) Dimensions (Length x Width x Height) Wire range (conductor size) Insulation stripping length Tightening torque Approvals
Ordering data
Ultra SlimPak Heat sink (width) Shunt resistor
DC current or voltage ±1mA to ±100mA or ±10mVdc to ±200Vdc, DIP switch selectable 20M for current, >100kM for voltage 170mA, 60Vdc for current, 200Vrms for voltage / self resetting fuse 24Vdc @ 20mA typical
2 form C relays (2 SPDT), one set point per relay, gold flash / silver alloy contacts 2 set points independently adjustable over 100% of the selected input span, HI or LO, failsafe or non-failsafe maximum 5A at 120Vac, 2A at 240Vac, 5A at 24Vdc (resistive load), minimum 10HA at 10mV
deadband adjustable from 0.25% to 5% of span (span >50mV or >5mA) and from 1% to 5% of span (span <50mV or <5mA) external relay contact protection required for inductive load switching Electrical life: 105operations at rated load Mechanical life: 107operations no load DC voltage 9 to 30Vdc, inverter isolated
1.5W typ., 2.5W max. (300mA inrush at 9Vdc)
0.1% of full scale (span >50mV or >5mA), 0.2% of full scale (span <50mV or <5mA)
±0.05% of full scale/°C, max.
<250mS in normal mode, dynamic deadband: relay status will change when proper setpoint/process condition exists for 100mS
input green (>110% of input: 8Hz, <0% of input: 4Hz), 2 setpoint red (ON: tripped, OFF: safe) 1800V (3 port) between contacts, input and power 0°C to 55°C / -25°C to 70°C EG12 (TS32 and TS35) 90mm x 17.7mm x 112.7mm max. 22-12AWG (0.5-4.0mm2) 7mm
0.4-0.8Nm CSA (file LR-42272), UL (file E99775), CE marked (EMC dir. 89/336/EEC, LV dir. 73/23/EEC: input <75Vdc only)
Cat.No. G108 (factory calibration: 0...20mA, A-HI/B-LO, non-failsafe) HS01-A (1.6mm) (conditionally required depending on installation, see heat sink data) C006 (0.1M, 1%, 5W for use with external DC current source)
Note: G108-000X where X is the revision level
Specifications subject to change without notice. 99990010 - 8/98 Printed in Canada