CP-SNT 160W 3 Phase
Switchmode Power Supply
The 3 phase CP-SNT 160W is a compact switchmode power supply that continues our tradition of more power from smaller packages.
Requiring just 58.4mm (2.3”) of DIN rail, the CP-SNT 160W has the following features:
• 380-480VAC input 50/60Hz
• multiple output terminals
• input and output plug-socket connectors
• over current protection
• output status LED
• output voltage adjustment
• fault relay output (Form C)
• load sharing
• high outrush (surge) capability
2
Input V oltage
Input Current
Input Protection
Switching Frequency Output
Efficiency @ max. load Maximum Ripple Regulation
Protection
Hold Time
Temperature Range
Humidity
Galvanic Isolation
Wire Size
Dimensions (mm) Weight (kg) Mounting
Special Features
Approvals/Certifications
342 V ac 480Vac 528Vac
0.34A
0.36A
0.43A Yes
5.7A Varistor 100kHz 24Vdc
22.5-28.5Vdc
6.5A 13A 1 sec 10 sec 10,000µF 83% 1% (p-p) max. 3%
0.50% Yes Yes Yes No 15mS 50mS 70mS
-40 to 85 °C
-20 to 50 °C 20 to 90% 20 to 85% 3KV 3KV
1.5KV 500V 26-12AWG 26-12AWG 26-12AWG
5.44 x 2.3 x 7 (138.2 x 58.4 x 177.8)
2.2lbs (.993kg) TS35 or Chassis
Fault Relay Load sharing
Automatic Restart CE, cULus Listed
3 x T2A 250V Thermistor Limited
Full Load Vertical 65°C Non-condensing Non-condensing
Chassis mountable with optional bracket part #7920560000 Form C, 125Vac and 30Vdc @ 1A rating Open loop Unit typically cycles 0.9s ON and 2.5s OFF.
Specifications
992534 0324 24Vdc @ 6.5A - 480Vac Input
Minimum
Typical
Maximum
Minimum Vin
Typical Vin
Maximum Vin
Fuse
Inrush Current
Overvoltage
Voltage Nominal
Voltage Adj. Range
Current nominal
Current Surge
Current Surge Time
Surge Cycle Time
Max. Load Capacitance
Typical Vin Typical Vin
Load (10 -100%)
Line
Short Circuit
Over Voltage
Under V oltage
Over Temperature
Minimum Vin
Typical Vin
Maximum Vin
Storage
Operating
Storage
Operating
Input to Output
Input/Output to Rail
Input to Ground
Output to Ground
Input
Output
I/O
LxWxD
3
Output
Adjustable via trimpot located on front cover, from 22.5 to 28.5Vdc
Surge
13A for 1 second Unit will shutdown if surge exceeds 1 second
Overload
Automatic restart if overloaded. Unit restar ts after approximately 4 seconds.
Contacts rated 30VDC 1A or 125VAC, 1A maximum, Form ‘C’ SPDT. Relay is energized when power supply is operating under normal conditions.
Maximum 2 units can be connected in parallel for load sharing. Derate supplies to 80% capacity (5.2A) when load sharing. Follow these directions for correct operation.
1. Adjust the output voltage of each power supply to the same value before connecting them in parallel (±200mV).
2. Connect wires of the same length from each power supply to terminal blocks.
3. Connect the load(s) at these ter minal blocks.
Output V oltage
Relay Output
Load Sharing
Subject to technical changes · Printed in Canada · 99990309 ·01/2003
4 IL04XXXX000016-
g(earth) terminal should be connected to earth ground for safe operation.
•Outputs of power supplies can be connected in parallel.
•Outputs of power supplies can be connected in series.
•Outputs of power supplies can be connected to produce a bi-polar output.
•Power supply should be mounted allowing for natural air flow through the ventilation holes.
O/P Current
Temperature
6.5A 50°C
4.5A 65°C
O/P Current Temperature
4.6A 50°C
2.5A 65°C
9925340324 T emperature Ratings
CurrentCurrent
Temperature (°C)
Temperature (°C)