WEG Electric UBW Series Catalog Page

Page 1
UBW Family – UL489 Molded Case
Circuit Breakers
The UBW line offers the quality, realiablity and uncompromising protection
that you have come to expect from WEG
Page 2
Molded Case Circuit Breakers– UBW Series
The WEG UBW Series of Molded Case Circuit Breakers are designed to provide short circuit and thermal protection for industrial electrical equipment. Increased frame sizes and amperages cover more applications than ever before!!
Product Range
15 to 2500 A
35, 65, or 100 KAIC
@ 480V
Features
Broad product offering up to 2500 Amps
Multiple SCCR Ratings up to 100 KAIC
Optional Maintenance Mode for Superior Arc
Flash Protection (1200 & 2500A Frames)
Field or Factory Installed Options
Optional Multi-Conductor Load Side Lugs
WEG UBW Molded Case Circuit Breakers
Rotary
Operators
Flange
Page 3
Molded Case Circuit Breakers– UBW Series
UBW225 (15-225A) UBW250 (250A) UBW400 (300-400A) UBW600 (500-600A)
Fixed Thermal / Fixed
Magnetic Trip
Lugs Included
UBW800 (800A)
Fixed Thermal / Adjustable
Magnetic Trip
Lugs Included
Product Line Overview – Controls
Fixed Thermal / Adjustable
Magnetic Trip
Lugs Included
UBW1200 (800-1200A)
Electronic Trip
Order Lugs Separately
Fixed Thermal / Adjustable
Magnetic Trip
Lugs Included
UBW2500 (1200-2500A)
Electronic Trip
Order Lugs Separately
Fixed Thermal / Adjustable
Magnetic Trip
Lugs Included
Page 4
Maintenance Mode
Optional on the UBW1200 and UBW2500 frame Molded Case Circuit Breakers
When enabled arc flash energy is reduced allowing for less PPE (Personal Protective Equipment)
Utilizes dedicated Arc Flash Circuit within the trip unit
Shifts instantaneous trip curve to the left (2.5 – 4.0 times trip rating)
Faster Trip Response / Less Let
through Current!!
Lower your PPE Category and work
comfortably!!
Product Line Overview – Controls
Page 5
Accessories
Auxiliary Alarm Aux/Alarm Shunt Trip Undervoltage
Module
Options for All Frame Sizes Multiple Voltages for Each Frame Size
Lock On/Off Padlocks Direct Mount Handles Extension Handles
Product Line Overview – Controls
Page 6
ACW Breakers
Description at 480vac
New UBW Breaker
Comments
ACW125P-FTU15-3
35ka 15amp
UBW225N-FTU15-3A
Fixed Thermal & Magnetic
ACW125P-FTU20-3
35ka 20amp
UBW225N-FTU20-3A
Fixed Thermal & Magnetic
ACW125P-FTU30-3
35ka 30amp
UBW225N-FTU30-3A
Fixed Thermal & Magnetic
ACW125P-FTU40-3
35ka 40amp
UBW225N-FTU40-3A
Fixed Thermal & Magnetic
ACW125P-FTU50-3
35ka 50amp
UBW225N-FTU50-3A
Fixed Thermal & Magnetic
ACW125P-FTU60-3
35ka 60amp
UBW225N-FTU60-3A
Fixed Thermal & Magnetic
ACW125P-FTU80-3
35ka 80amp
UBW225N-FTU80-3A
Fixed Thermal & Magnetic
ACW125P-FTU100-3
35ka 100amp
UBW225N-FTU100-3A
Fixed Thermal & Magnetic
ACW125P-FTU125-3
35ka 115amp
UBW225N-FTU125-3A
Fixed Thermal & Magnetic
ACW250P-FTU160-3
35ka 160amp
UBW225N-FTU150-3A
New UBW 150 Amp
ACW250P-FTU200-3
35ka 200amp
UBW225N-FTU200-3A
Fixed Thermal & Magnetic
ACW250P-FTU250-3
35ka 250amp
UBW250N-FTU250-3A
Fixed Thermal & Adjustable Magnetic
ACW400P-FTU300-3
35ka 300amp
UBW400N-FTU300-3A
Fixed Thermal & Adjustable Magnetic
ACW400P-FTU400-3
35ka 400amp
UBW400N-FTU400-3A
Fixed Thermal & Adjustable Magnetic
ACW800P-FTU500-3
35ka 500amp
UBW600N-FTU500-3A
Fixed Thermal & Adjustable Magnetic
ACW800P-FTU600-3
35ka 600amp
UBW600N-FTU600-3A
Fixed Thermal & Adjustable Magnetic
ACW800P-FTU800-3
35ka 800amp
UBW800S-FTU800-3A
New UBW 50KA
ACW125W-FTU15-3
65ka 15amp
UBW225H-FTU15-3A
Fixed Thermal & Magnetic
ACW125W-FTU20-3
65ka 20amp
UBW225H-FTU20-3A
Fixed Thermal & Magnetic
ACW125W-FTU30-3
65ka 30amp
UBW225H-FTU30-3A
Fixed Thermal & Magnetic
ACW125W-FTU40-3
65ka 40amp
UBW225H-FTU40-3A
Fixed Thermal & Magnetic
ACW125W-FTU50-3
65ka 50amp
UBW225H-FTU50-3A
Fixed Thermal & Magnetic
ACW125W-FTU60-3
65ka 60amp
UBW225H-FTU60-3A
Fixed Thermal & Magnetic
ACW125W-FTU80-3
65ka 80amp
UBW225H-FTU80-3A
Fixed Thermal & Magnetic
ACW125W-FTU100-3
65ka 100amp
UBW225H-FTU100-3A
Fixed Thermal & Magnetic
ACW125W-FTU125-3
65ka 115amp
UBW225H-FTU125-3A
Fixed Thermal & Magnetic
ACW250W-FTU160-3
65ka 160amp
UBW225H-FTU150-3A
New UBW 150 Amp
ACW250W-FTU200-3
65ka 200amp
UBW225H-FTU200-3A
Fixed Thermal & Magnetic
ACW250W-FTU250-3
65ka 250amp
UBW250H-FTU250-3A
Fixed Thermal & Adjustable Magnetic
ACW400W-FTU300-3
65ka 300amp
UBW400H-FTU300-3A
Fixed Thermal & Adjustable Magnetic
ACW400W-FTU400-3
65ka 400amp
UBW400H-FTU400-3A
Fixed Thermal & Adjustable Magnetic
ACW800W-FTU500-3
65ka 500amp
UBW600H-FTU500-3A
Fixed Thermal & Adjustable Magnetic
ACW800W-FTU600-3
65ka 600amp
UBW600H-FTU600-3A
Fixed Thermal & Adjustable Magnetic
ACW800W-FTU800-3
65ka 800amp
UBW800S-FTU800-3A
New UBW 50KA
ACW to UBW Cross Reference
Product Line Overview – Controls
Page 7
FAQ
Why a breaker instead of fuses?
A breaker minimize downtime, can be switched on
immediately after a fault is cleared
Can the UBW line replace the ACW line?
For protection purposes yes, on the physical side there
is a slight difference in the size and mounting dimensions
Do all the frame sizes have various KA ratings?
Yes but check which is available for each frame
Can the options be installed in the field?
Yes with the exception of the 225 frame units
Can you reverse feed UBWs? – Yes
Are UBWs DC rated? – No
Are the UBWs 100% breakers?– No
Product Line Overview – Controls
Loading...