Thisaddendumreferstothefollowingchangesthathavebeenmade on the SSW-04
softwarefrom Version4.XXto Version5.XX.
1.Inclusionofthetimeintervalbetweenstartsfunction.
Thisprotectionactslimitingthetimeminimumintervalbetweenstartstoavoidexcessive
startingand stopping according tothe timeadjusted in parameter P36.
- P36: TimeInterval Between Starts(oFF,1...999s). Factory Standard:“oFF”.
OperationbyHMI
(I/O)
Attention:
The SSW controller will not accept a new Start command during the time, adjusted in P36,
elapsedafterStop.Identicallytoserialinterfacecommunication.
Operationbytwo wire digital input
(E.D.1)
Operationbythreewiredigitalinput
(E.D.1and E.D.2)
Attention.:
The SSW controller will not accept a new Start command during the time, adjusted in P36,
elapsedafter Stop.
NOTE!
1)Usethisfunctiononlyif youneed to avoidexcessivestartingandstopping.
5)Duringthe reversalofthe motor direction,thenewstartof the motorwillbeonlyrealized
afterthe timeadjusted in P36elapses.
ADDENDUM TO THE MANUAL 0899.5629 E/5 - SSW-04
Thisaddendumreferstothefollowingchangesthathave been made on theSSW-04 software
from Version3.XX to Version 4.XX
1. AdditionofthefunctionWatch Dog of the Serial Communication.
This protection acts when the serial communicationbetweenthemaster and the Soft-Starter is
interrupted, causing indication and action as set in parameters P63 and P64.
- P63: Watch Dog Time of the Serial Communication(oFF, 1 ... 5s). Factory Standard:“oFF”.
- P64: Action After Watch Dog Time is Elapsed (1,2 and 3). Factory Standard: 1.
1 = Indicates only error E29.
2 =IndicateserrorE29anddisablesthemotorbyramp, if P04 is programmeddifferentfrom “oFF”
and motor is stopped by inertia if equal “oFF”.
3 = Indicates error E29 and cause general disabling of the Soft-Starter. Its cats as emergency.The
motor is stopped by inertia.
NOTE!
Error E29 is reset when the correct serial communicationreturned.
NOTE!
Enable this function only if there is cyclic serial communication with a Master.
Set the watch dog time according to the time between telegrams sent by the master.
2. Change in the setting range of P15 to: off,1 ... 200s.
P11=OFF(CurrentLimitation)
After setting the values above start and stop the Pump.Thencheck the correct direction of rotation,
pump flow andthecurrentof themotor.
After the above step youcanenablethePump Control (P45 = “on”).
4.Additionthe following items 10.2, 10.3 e 10.4 in the accessories chapter.
10.2-RS-485.
Optionallythe SSW-04canoperatein serial interface RS-485 byWeg Interface Module MIW-02.
ModuleTypeWEG Item
NOTE!
Formoredetails see MIW-02 Manual (0899.4430).
10.3-FieldbusNetwork.
OptionallytheSSW-04 can operate in communication network “FieldBus”, by a gateway, Weg Fieldbus
ModuleMFW-01.
10.4- SuperDrive.
ProgrammingsoftwareformicrocomputerPC, forwindows environment.Permitsparameter
programming,commandandmonitoringof the Soft-StarterSSW-04.It edits parameters“on-line”,
directlytotheSoft-Starter or it edits parameters files“off-line”,savinginthe microcomputer.The
communication between Soft-Starter and Microcomputer is by serial interface RS232 (Point to Point)or
RS485(NetworkLine).
ProductWEG Item
SuperDrive417102505
24/04/2001
SOFT-STARTER
SOFT-STARTER
SOFT-STARTER
MANUAL
MANUAL
MANUAL
SSW-04 Series
Software: version 5.XX
0899.5629 E/5
NOTE!
It is very important to check if
the Soft-Starter Software is the
same as the above.
SUMMARY
SUMMARY
QUICK PARAMETER
REFERENCES, ERROR
MESSAGES AND STATUS
MESSAGES
Apparent power indication supplied to the
load (KVA)
Load power factor
Soft-Starter output
voltage indication % UN
Heatsink Temperature
(ºC)
Indication of motor
Thermal Protection
Status
Last hardware error
Second hardware error
Third hardware error
0.0...999.9A
0.0...999.9kW
0.0...999.9kVA
0.00...0.99
0...100% UN
10...110ºC
0...250%
1...8
1...8
1...8
51
51
51
51
51
51
51
52
52
52
P99
Fourth hardware error
1...8
52
11
QUICK PARAMETER REFERENCES,
ERROR MESSAGES AND STATUS MESSAGES
2.Error Messages
Display
E01
E02
E03
E04
E05
E06
E07
E08
E24
E2X
Meaning
Phase failure or thyristor fault or motor not connected
At the end of time of the programmed acceleration time, the voltage does
not reach 100% UN due to the current limit.
Overtemperature at the thyristors and in the heatsink
Motor overload
Undercurrent (applicable to pumps)
Immediate overcurrent
Phase rotation
External fault
Programming error
Serial communication error
3.Soft-Starter Status
Display
rdy
PuP
EEP
On
OFF
Soft-Starter is ready to be enabled
Loading pump control parameters
Loading "Default" values
Function enabled
Function disabled
Definition
12
1
SAFETY NOTICE
This Manual contains all necessary information for the correct installation and operation
of the SSW-04 Soft-Starter.
This Manual has been written for qualified personnel with suitable training or technical
qualifications to operate this type of equipment.
1.1 SAFETY NOTICES
IN THE MANUAL
1.2 SAFETY NOTICES
ON THE PRODUCT
The following Safety Notices will be used in this Manual:
DANGER!
If the recommended Safety Instructions are not strictly
observed, it can lead to serious or fatal injuries of personnel
and/or equipment damage.
ATTENTION!
Failure to observe the recommended Safety Procedures can
lead to material damage.
NOTE!
The content of this Manual supplies important information
for the correct understanding of operation and proper
performance of the equipment.
The followingsymbols maybe attachedto the product,serving
as Safety Notice:
High Voltages
1.3 PRELIMINARY
RECOMMENDATIONS
Components are sensitive to electrostatic discharge. Do not
touch them without following proper grounding procedures.
Mandatory connection to ground protection (PE)
Shield connection to ground
DANGER!
Onlyqualifiedpersonnelshouldplanorimplement theinstallation,
startup, operation and maintenance of this equipment.
13
1
SAFETY NOTICE
Personnel must review this entire Manual before attempting
to install, operate or troubleshoot the SSW-04. These personnel
mustfollow all safety instructions included in this Manual and/
or defined by local regulations.
Failure to comply with these instructions may result in
personnel injury and/or equipment damage.
NOTE!
In this Manual, qualified personnel are defined as peoplethat
are trained to:
1.Install, ground, power up and operate the SSW-04
according to this manual and the local required safety
procedures;
2.Use of safetyequipment according tothelocalregulations;
3.Administer Cardio Pulmonary Resuscitation (CPR) and
First Aid.
DANGER!
Always disconnect the supply voltage before touching any
electrical component inside the Soft-Starter.
Many components are charged with high voltages, even after
the incoming AC power supply has been disconnected or
switched OFF. Wait at least 3 minutes for the total discharge
of the power capacitors.
Always connect the frame of the equipment to the ground
(PE) at the suitable connection point.
ATTENTION!
All electronic boards have components that are sensitive to
electrostatic discharges. Never touch any of the electrical
components or connectors without following proper
grounding procedures. If necessary to do so, touch the
properly grounded metallic frame or use a suitable ground
strap.
Do not apply High Voltage (High Pot) Test on the Soft-Starter!
If this test is necessary, contact the Manufacturer.
14
NOTE!
Read this entire Manual carefully and completely before
installing or operating the SSW-04.
2
INTRODUCTION
2.1 - ABOUT THIS
MANUAL
This Manual describes how to install, start-up, operate and
identify the problems of the SSW-04 Soft-Starters series.
Should you require any training or further info, please contact
WEG.
This Manual is divided into 9 Chapters, providing information
to the user on how to receive, install, start-up and operate
the SSW-04:
This Manual provides information for the correct use of the
SSW-04. The SSW-04 is very flexible and allows for the
operation in many different modes as described in this manual.
2.2 VERSION OF
SOFTWARE
As the SSW-04 can be applied in several ways, it is impossible
to describe here all of the application possibilities. WEG does
not accept any responsibility when the SSW-04 is not used
according to this Manual.
No part of this Manual may be reproduced in any form,
without the written permission of WEG.
It is important to note the Software Version installed in the
Version SSW-04, since it defines the functions and the
programming parameters of the Soft-Starter.
This Manual refers to the Software version indicated on the
inside cover. For example, the Version 1.XX applies to versions
1.00 to 1.99, where “X” is a variable that will change due to
minor software revisions. The operation of the SSW-04 with
these software revisions are still covered by this version of
the Manual.
The Software Version can be read in the Parameter P71.
15
2
INTRODUCTION
2.3 - ABBREVIATIONS
USED
2.4 - ABOUT THE
SSW-04
HMI- Human machine interface (keypad + display)
HMI-3P - Keypad + Display interface - Linked via parallel
cable
RLX- Relay output No X
DIX- Digital input No X
IN- Soft-Starter nominal output current
UN- Rated mains voltage
LED- Light Emitting Diode
The SSW-04 series is a totally microprocessor controlled SoftStarter series which controls the starting current of threephase induction motors. In this way mechanical inmpacts on
the load and current peaks on the supply network are
prevented.
2.4.1 - Introduction
This series includes models from 16 to 85A, being supplied
from 220V, 230V, 240V, 380V, 400V, 415V, 440V, 460V, 480V,
525V or 575V. (The available types are listed in Section 8).
The models up to 45A are with natural cooling and isolated
heatsink (thyristor-thyristor modules). The models from 60A
and 85A have forced cooling and isolated heatsink (ThyristorThyristor Modules).
The electronic control circuit uses a 16 bit microprocessor with
high performance, allowing settings and displaying by means
of the interface (keypad + display) of all needed parameters.
Depending on the power, this series (SSW-04) has 2 different
construction forms, as shown in Figure 2.1.
16
2
INTRODUCTION
WidthDepthHeight
MECRatedLPHWeight
Currentmmmmmmkg
(in)(in)(in)(lb)
16A
130A1401992755.2
45A(5.51)(7.83)(10.83) (11.46)
SIDE VIEW
2
60A1402832759.0
85A(5.51)(11.06) (10.83) (19.84)
FRONT VIEW
Figure 2.1 - Construction forms
17
2
INTRODUCTION
2.4.2 - Simplified Block Diagram of the SSW-04
CT
LINE
3~
DIGITAL
INPUT
CT
ELECTRONIC
CONTROL BOARD
CCS4.0X
RELAY OUTPUT
RL1, RL2,RL3
Figure 2.2 - Simplified Block Diagram of the SSW-04
In the power stage, the line voltage is controlled by means of
6 SCR’s that allow the variation of the conduction angle of
the voltage supplied to the motor.
For the internal supply of the electronics, a switched source is
used with several voltages, fed independently of the power
supply.
The control board contains the circuits responsible for the
control, monitoring and protection of the power components.
This board also contains the control and signalling circuit to
be used by the user according to its application as a relay
output.
All parameters or controls for the operation of the Soft-Starter
can be displayed or changed through the HMI.
18
2
INTRODUCTION
2.4.3 - Description of the control board - CCS 4.00 or CCS 4.01
Firing connection of the thyristors
Communication
Selection
Connector for
HMI-3P
Supply
transformer
Connection
ground
Internal fan
connector
Power on LED
Fault LED
Current
transformers Input
Heatsink Thermistor Input
Microcontroller
with software
version label
Input for serial
RS232
Relays
Supply and fan connector
Figure. 2.3 - Layout of the electronic control board CCS 4.00 or CCS4.01
Supply Fuse
User Connector
19
2
INTRODUCTION
2.5 - PRODUCT
IDENTIFICATION
SERIAL NUMBER
SOFT-STARTER MODEL
INPUT DATA
OUTPUTDATA/MAXIMUM CURRENT RATINGFOR
CONTINUOUSDUTY
ELECTRONIC/FAN DATA
FABRICATION DATE
WEGITEM
Soft-Starter Type
SSW-04.
2.6 - RECEIVING
+
Voltage of the electronics
Three-phase supply voltage (220 - 440, 460 - 575).
Rated output current (A)
Max. Cont.: It's the maximum current that the Soft-Starter
can have in continuous duty. For this current the Soft-Starter
can only have 1 start per hour.
EXTERN HMI
HMI-3P.1: HMI with LEDs, 1 m (3.28ft) cable
HMI-3P.2: HMI with LEDs, 2 m (6.56ft) cable
HMI-3P.3: HMI with LEDs, 3 m (9.84ft) cable
The SSW-04 is supplied in cardboard boxes.
The outside of the packing container has a nameplate that is
the identical to that on the SSW-04. Please check if the SSW04 is the one you ordered.
Options : + I with remote HMI
1- 110/120 V
{
2- 220/230 V
20
Open the box, remove the foam and then remove the SSW-04.
SSW-04 nameplate data matches the purchase order;
The equipment has not been damaged during transport.
If any problem is detected, contact the carrier immediately.
If the SSW-04 is not to be installed immediately, store it in a
clean and dry room (Storage temperatures between - 25°C
and 60°C). Cover it to prevent dust, dirt or other contamination
of the drive.
3
INSTALLATION
3.1 - MECHANICAL
INSTALLATION
3.1.1 - Environment
The location of the SSW-04 installation is a determinaning
factor for obtaining a good performance and a normal useful
life of its components.
Regarding the installation of the Soft-Starter we make the
following recommendations:
Avoid directexposureto sunlight, rain, high moistureandsea air.
Avoid exposure to gases or explosive or corrosive liquids;
Avoid exposure to excessive vibration, dust, oil or any
(conductive particles or materials).
Environmental Conditions:
Temperature: 32...104º F (0 ... 40º C) - nominal conditions.
104...131º F (40 ... 55º C) - see table 8.2.
Relative Air Humidity: 5% to 90%, non-condensing.
Maximum Altitude: 3,300 ft(1000m) - nominal conditions.
3,300 ... 13,200 ft (1000 ... 4000m) - with 10% current
reduction for each 3,300 ft (1000m) above 3,300 ft(1000m).
Pollution Degree: 2 (according to EN50178 and UL508)
(It is not allowed to have water,
condensation or conductive dust/
particles in the air)
NOTE!
When Soft-Starter is installed in panels or closed metallic boxes, adequate cooling is required to ensure that the
temperature around the Soft-Starter will not exceed the
maximum allowed temperature. See Dissipated Power in
Section 8.2.
Please meet the minimum recommended panel dimensions
and its cooling requirements:
AC input disconnect: providean AC input disconnectingswitch
to switch OFF input power to the Soft-Starter.
This device shall disconnect the Soft-Starter from the AC input
supply when required (e.g. during maintenance services).
DANGER!
The AC input disconnect cannot be used as an emergency
stop device.
DANGER!
Be sure that the AC input power is disconnected before
making any terminal connection.
DANGER!
The information below will be a guide to achieve a proper
installation. Follow also all applicable local standards for
electrical installations.
ATTENTION!
Provide at least 10 in (0.25m) spacing between low voltage
wiring and the Soft-Starter, line or load reactors, AC input
power, and AC motor cables.
Figure 3.3 -
Power and Grounding Connections
23
3
INSTALLATION
The line voltage must be compatible with the rated voltage
of the Soft-Starter.
For installation use the cable cross sections and the fuses
recommended in Table 3.1, maximum torque as indicated in
table 3.2
Power factor correction capacitors most never be installed
on the Soft-Starter output.
The Soft-Starters must be grounded. For this purpose use
a cable with a cross section as indicated in Table 3.1.
Connect it to a specific grounding bar or to the general
grounding point (resistance10 ohms).
Do not share the grounding wiring with other equipment
which operate at high currents (for instance, high voltage
motors, welding machines, etc.).
If several Soft-Starters are used together, see Figure 3.4.
SSW-04 ISSW-04 IISSW-04 ISSW-04 IISSW-04 n
Grounding bar intern to the panel
Figure 3.4 -
Do not use the neutral conductor for grounding purpose.
The Soft-Starter is fitted with electronic protection
against motor overloads. This protection must be set
according to the specific motor.
When several motors are connected to the same SoftStarter, use individual overload relays for each motor.
Grounding connection for more than one
Soft-Starter
24
If a isolating switch or a contactor is inserted in the motor supply, do not operate them with running motor or
when the Soft-Starter is enabled.
3
INSTALLATION
Table 3.1 - Recommended Cables/Fuses - Use 75ºC Copper Wire Only
RatedPowerGroundingUltra fast actingI2t of
current ofWiringWiringFuse for SCR'sSCR
the SSW-04mm² (AWG)mm² (AWG)protection(A²s)
16A
30A
45A
60A
85A
2.5mm2(12)
6mm2(8)
8mm2(8)
16mm2(4)
25mm2(3)
6mm2(8)
6mm2(8)
6mm2(8)
8mm2(8)
10mm2(6)
The cross sections indicated in Table 3.1 are orientative values
only. For correct cables dimensioning consider the installation
condition and the maximum allowable voltage drop.
The recommended fuse connected at the input side must be
a ultra rapid type (UR) with I2t smaller than 75% of the value
indicated in Table 3.1 (I2t of the SCR).
When a short circuit occurs the ultra rapid fuse protects the
SCR.
Normal fuses can also be used, in that case the installation is
protected against short circuit, but the SCR isn't protected.
Recommended torque on the power terminals:
Table 3.2 - Maximum torque
Soft-Starter
Type
Grounding wiring
Nm(Lb.in)
50A
80A
125A
160A
200A
1,150
8,000
15,000
15,000
125,000
Power wiring
Nm(Lb.in)
16A
30A
45A
60A
85A
It is Recommended to use motors with load above 30%
rated motor load.
1.2 - 1.4
(10.6-12.3)
5.0
(43.9)
1.2 - 1.4
(10.6 - 12.3)
2.5 - 3.0
(21.8 - 26.1)
NOTE!
The rated motor current shall not be less than 30% of the softstarter rated current, in order that the overload protection
works properly.
The SSW-04 is suitablefor use on a circuit capable of delivering
not more than X Arms (see below) symmetrical amperes, Y
volts maximum, when protected by Ultra-fast Semiconductor
Fuses.
25
3
INSTALLATION
3.2.2 - Location of the
power/
grounding/fans
connection
Type
16 - 45A
460 - 575V
60 - 85A
460 - 575V
16 - 60A
220 - 440V
85A
220 - 440V
XY
5,000
10,000
5,000
10,000
575
575
440
440
26
Figure 3.5- Location of the power/grounding connection
3
INSTALLATION
3.2.3 - Signal and
Control
Connections
The signal (digital inputs/outputs by relay) are performed
through the following connectors of the Control Board
CCS4.0X (see location in Figure 2.3).
X2 : Digital input and output by relay
X1 : Electronics and Fan supply
XC2 : connection to HMI-3P
X3 : connection to serial communication
NOTE!
Soft-starters types 60A and 85A the fan current pass also
through the connector X1. Thus the total current is:
274.5mA for 110Vac or 140mA for 220Vac.
27
3
INSTALLATION
3.2.3.1 - Description of the X2 Connector
DI1
DI2
DI3
DI4
Vac
Vac
Vac
28
Figure 3.6 - Description of the X2 (CCS4.00 or CCS4.01 connector)
3
INSTALLATION
When installing the signal and control wiring, please note
the following:
Cable cross-section: 0.5...1.5mm2;
Relays, contactors, solenoid valves or breaking coils
installed near to Soft-Starters can generate interferences in
the control circuit. To eliminate this , you must install
RC supressors connected in parallel with the coils of these
devices, when fed by alternate current and free wheel
diodes when fed by direct current.
When an extern HMI is used, the connection cable to the
Soft-Starter should be passed through the slot at the bottom
of the Soft-Starter. This cable must be laid separate from the
other cables existing in the installation, maintaining a
distance of 100mm (3.94in) each other.
3.2.4 - FAN
CONNECTIONS
Max. recommended torque in the terminals X2 and X1:
Maximum 0.4 Nm or 3.5lb.in.
The control wiring (X2:1...5) must be laid separate from
the power wiring.
The fan connections must be done through X1:1 and X1:2
connector according to the voltage defined by the SoftStarter code:
Ex.: SSW-04. 60/220-440/
Electronic / fan voltage:
1 = 110Vac
2 = 220Vac
29
3
INSTALLATION
3.2.5 - Combination
drive "A" Operation
by HMI-3P
With the factory standard programming, you can operate
the Soft-Starter with the minimum connection shown in Figure 3.7.
This operation mode is recommended for users who
operate the Soft-Starter by first time, as initial training
form.
30
Figure 3.7 -
Minimum connections for operation through HMI
Note: It's necessary to use normal fuses or breaker to protect
the installation. Ultra-Rapid fuses are not necessary for
the SSW-04 operation, but they are recommended for
SCR protection.
The transformer "T" is optional and must be utilized
when the line voltage is different than the electronics
and fan voltage.
The isolation contactor "K1" is optional, and is not
necessary for the SSW-04 operation. However due to
protection and safety reasons it's recommended. In case
Loading...
+ 73 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.