WEG Electric NEMA LOW VOLTAGE ELECTRIC MOTORS Installation Guide

260.03/122002
INSTALLATION AND MAINTENANCE MANUAL FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
TT
The electric motor is the item of equipment most
TT
widely used by man in his pursuit of progress, as virtually all machines and many renowned inventions depend upon it. By virtue of the prominent role the electric motor plays in the comfort and welfare of mankind, it must be regarded and treated as a prime power unit embodying features that merit special attention, including its installation and maintenance. This means that the electric motor should receive proper attention. Its installation and routine maintenance require specific care to ensure perfect operation and longer life of the unit. THE WEG ELECTRIC MOTOR INST ALLA TION AND MAINTENANCE MANUAL provides the necessary information to properly install, maintain and preserve the most important component of all equipment:
THE ELECTRIC MOTOR!
WEG
Contents
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
1 - Introduction .................................................................. 04
2 - Basic Instructions ........................................................ 05
2.1 Safety Instructions....................................................... 05
2.2 Delivery .................................................................. 05
2.3 Storage .................................................................. 05
2.3.1 Drying the Windings.................................... 06
3 - Installation .................................................................. 07
3.1 Mechanical Aspects.................................................. 07
3.1.1 Foundation ................................................. 07
3.1.2 Types of bases ........................................... 07
3.1.3 Alignment.................................................... 08
3.1.4 Coupling..................................................... 08
3.2 Electrical Aspects...................................................... 16
3.2.1 Feed System .............................................. 16
3.2.2 Starting of Electric Motors ............................ 16
3.2.3 Motor Protection.......................................... 18
3.3 Start-up .................................................................. 18
3.3.1 Preliminary Inspection................................. 18
3.3.2 The First Start-up........................................ 18
3.3.3 Operation ................................................... 18
3.3.4 Stopping ..................................................... 18
4 - Maintenance .................................................................. 23
4.1 Cleanliness.............................................................. 23
4.2 Lubrication............................................................... 23
4.2.1 Periodical Lubrication.................................. 23
4.2.2 Quality and Quantity of Grease.................... 23
4.2.3 Lubricating Instructions................................ 23
4.2.4 Replacement of Bearings ............................ 24
4.3 Air Gap Checking .................................................... 24
4.4 Explosion Proof Motor Repair Steps......................... 24
4.4.1 Objective .................................................... 24
4.4.2 Repair Procedure and Precautions............. 24
4.4.3 Miscellaneous Recommendations................ 25
5 - Malfunctioning .............................................................. 26
5.1 Standard Three-phase Motor Failures ..................... 26
5.1.1 Short Circuits Between Turns...................... 26
5.1.2 Winding Failures ......................................... 26
5.1.3 Rotor Failures............................................. 27
5.1.4 Bearing Failures ......................................... 27
5.1.5 Shaft Fractures ........................................... 27
5.1.6 Unbalanced V-Belt Drives........................... 27
5.1.7 Damage Arising from Poorly Fitted Transmission Parts or
Improper Motor Alignment ........................... 27
5.2 Troubleshooting Chart ............................................. 28
6 - Spare Parts and Component Terminology ................. 29
3
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
1. Introduction
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
TT
This manual covers all the three-phase and
TT
single-phase asynchronous squirrel-cage induction motors, from 140T to 580T frame sizes.
The motors described in this manual are subject to continuous improvement and all information is subject to change without notice. For further details, please consult WEG .
4
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
2. Basic Instructions
2.1 Safety Instructions
All personnel involved with electrical installations, either handling, lifting, operation and maintenance, should be well-informed and up­to-date concerning the safety standards and principles that govern the work and carefully follow them. Before work commences, it is the responsibility of the person in charge to ascertain that these have been duly complied with and to alert his personnel of the inherent hazards of the job in hand. It is recommended that these tasks be undertaken only by qualified personnel and they should be instructed to:
· avoid contact with energized circuits or rotating parts,
· avoid by-passing or rendering inoperative any safeguards or protective devices,
· avoid extended exposure in close proximity to machinery with high noise levels,
· use proper care and procedures in handling, lifting, installing, operating and maintaining the equipment, and
· follow consistently any instructions and product documentation supplied when they do such work.
Before initiating maintenance procedures, be sure that all power sources are disconnected from the motor and accessories to avoid electric shock. Fire fighting equipment and notices concerning first aid should not be lacking at the job site; these should be visible and accessible at all times.
2.2 Delivery
Prior to shipment, motors are factory-tested and balanced. They are packed in boxes or bolted to a wooden base. Upon receipt, we recommend careful handling and a physical examination for damage which may have occurred during transportation. In the event of damage and in order to guaranty insurance coverage, both the nearest WEG sales office and the carrier should be notified without delay.
bearing surfaces thereby removing the protective film that impedes metal-to-metal contact. As a preventive measure against the formation of corrosion by contact, motors should not be stored near machines which cause vibrations, and every 3 month their shafts should be rotated manually.
Insulation resistance fluctuates widely with temperature and humidity variations and the cleanliness of components. When a motor is not immediately put into service it should be protected against moist, high temperatures and impurities, thus avoiding damage to insulation resistance. If the motor has been in storage more than six month or has been subjected to adverse moisture conditions, it is best to check the insulation resistance of the stator winding with a megohmeter. If the resistance is lower than ten megohms the windings should be dried in one of the two following ways:
1) Bake in oven at temperatures not exceeding 194 degrees F until insulation resistance becomes constant.
2) With rotor locked, apply low voltage and gradually increase current through windings until temperature measured with thermometer reaches 194 degrees F . Do not exceed this temperature.
If the motor is stored for an extensive period, the rotor must be periodically rotated. Should the ambient conditions be very humid, a periodical inspection is recommended during storage. It is difficult to prescribe rules for the true insulation resistance value of a machine as resistance varies according to the type, size and rated voltage and the state of the insulation material used, method of construction and the machine’s insulation antecedents. A lot of experience is necessary in order to decide when a machine is ready or not to be put into service. Periodical records are useful in making this decision.
The following guidelines show the approximate values that can be expected of a clean and dry motor, at 40°C test voltage in applied during one minute.
2.3 Storage
Motors should be raised by their eyebolts and never by their shafts. It is important that high rating three-phase motors be raised by their eyebolts. Raising and lowering must be steady and joltless, otherwise bearings may be harmed. When motors are not immediately installed, they should be stored in their normal upright position in a dry even temperature place, free of dust, gases and corrosive atmosphere. Other objects should not be placed on or against them. Motors stored over long periods are subject to loss of insulation resistance and oxidation of bearings.
Bearings and lubricant deserve special attention during prolonged periods of storage. Depending on the length and conditions of storage it may be necessary to regrease or change rusted bearings. The weight of the rotor in an inactive motor tends to expel grease from between the
Insulation resistance Rm is obtained by the formula:
Rm = Vn + 1
Where: Rm - minimum recommended insulation resistance in
M with winding at 40°C Vn - rated machine voltage in kV
In case the test is carried out at a temperature other than 40°C, the value must be corrected to 40°C using an approximated curve of insulation resistance v.s temperature of the winding with the aid of Figure 2.1; it’s possible verify that resistance practically doubles every 10°C that insulating temperature is lowered.
5
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
Example:
Ambient temperature = 50°C Motor winding resistence at 50°C = 1.02 M Correction to 40°C
R
= R
40°C
R
= 1.02 x 1.3
40º C
R
40º C
x K
50°C
= 1.326 M
50°C
The minimum resistence Rm will be:
Rm = Vn + 1 Rm = 0.440 + 1 Rm = 1.440 M
On new motors, lower values are often attained due to solvents present in the insulating varnishes that later evaporate during normal operation. This does not necessarily mean that the motor is not operational, since insulating resistance will increase after a period of service. On motors which have been in service for a period of time much larger values are often attained. A comparison of the values recorded in previous tests on the same motor under similar load, temperature and humidity conditions, serves as a better indication of insulation condition than that of the value derived from a single test. Any substantial or sudden reduction is suspect and the cause determined and corrective action taken. Insulation resistance is usually measured with a MEGGER. In the event that insulation resistance is inferior to the values derived from the above formula, motors should be subjected to a drying process.
2.3.1 Drying the windings
This operation should be carried out with maximum care, and only by qualified personnel. The rate of temperature rise should not exceed 5°C per hour and the temperature of the winding should not exceed 105°C. An overly high final temperature as well as a fast temperature increase rate can each generate vapour harmful to the insulation. T emperature should be accurately controlled during the drying process and the insulation resistance measured at regular intervals. During the early stages of the drying process, insulation resistance will decrease as a result of the temperature increase, but the resistance will increase again when the insulation becomes dryer. The drying process should be extended until sucessive measurements of insulation resistance indicate that a constant value above the minimum acceptable value has been attained. It is extremely important that the interior of the motor be well ventilated during the drying operation to ensure that the dampness is really removed. Heat for drying can be obtained from outside sources (an oven), energization of the space heater (optional), or introducing a current through the actual winding of the motor being dried.
Figure 2.1
Winding T emperature (ºC) R
= Rt x K
40 ºC
t 40 ºC
6
3. Installation
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
Electric machines should be installed in order to allow an easy access for inspection and maintenance. Should the surrounding atmosphere be humid, corrosive or contain flammable substances or particles, it is essential to ensure an adequate degree of protection. The installation of motors in environments where there are vapours, gases or dusts, flammable or combustible materials, subject to fire or explosion, should be undertaken according to appropriate and governing codes, such as NEC Art. 500 (National Electrical Code) and UL-674 (Underwriters Laboratories, Inc.) Standards. Under no circumstances can motors be enclosed in boxes or covered with materials which may impede or reduce the free circulation of ventilating air. Machines fitted with external ventilation should be at least 50cm from the wall to permit the passage of air. The opening for the entry and exit of air flow should never be obstructed or reduced by conductors, pipes or other objects. The place of installation should allow for air renewal at a rate of 700 cubic feet per minute for each 75 HP motor capacity .
3.1 Mechanical Aspect s
3.1.1 Foundation
The motor base must be levelled and as far as possible free of vibrations. A concrete foundation is recommended for motors over 100 HP . The choice of base will depend upon the nature of the soil at the place of erection or of the floor capacity in the case of buildings. When dimensioning the motor base, keep in mind that the motor may occasionally be run at a torque above that of the rated full load torque. Based upon Figure 3.1, foundation stresses can be calculated by using the following formula:
Where: F1 and F2 - Lateral stress (Lb)
g - Force of gravity (32.18 ft/s2) G - Weight of motor (Lb) Tmax - Maximum torque (Lb . Ft) A - Obtained from the dimensional drawing of the motor (in)
Sunken bolts or metallic base plates should be used to secure the motor to the base.
3.1.2 Types of Bases
a) Slide Rails
When motor drive is by pulleys the motor should be mounted on slide rails and the lower part of the belt should be pulling. The rail nearest the drive pulley is positioned in such a manner that the adjusting bolt be between the motor and the driven machine. The other rail should be positioned with the bolt in the opposite position, as shown in Figure 3.2. The motor is bolted to the rails and set on the base. The drive pulley is aligned such that its center is on a plane with the center of the driven pulley and the motor shaft and that of the machine be parallel.
The belt should not be overly stretched, see Figure 3.11. After the alignment, the rails are fixed.
F1 = 0.2247 (0.009 x g x G - 213 Tmáx/A)
F2 = 0.2247 (0.009 x g x G + 213 Tmax/A )
Figure 3.1 - Base stresses
Figure 3.2 - Positioning of slide rails for motor alignment
7
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
b) Foundation Studs
Very often, particularly when drive is by flexible coupling the motor is anchored directly to the base with foundation studs. It is recommended that shim plates of approximately 0.8 inches be used between the foundation studs and the feet of the motor for replacement purposes. These shim plates are useful when exchanging one motor for another of larger shaft height due to variations allowed by standard tolerances. Foundation studs should neither be painted nor rusted as both interfere with to the adherence of the concrete, and bring about loosening. After accurate alignment and levelling of the motor, the foundation studs are cemented and their screws tightened to secure the motor.
Thus, simultaneous readings are possible and allow for checking for any parallel (Figure 3.6a) and concentricity deviations (Figure 3.6b) by rotating the shafts one turn. Gauge readings should not exceed 0.02 inches. If the installer is sufficiently skilled, he can obtain alignment with feeler gauges and a steel ruler, providing that the couplings are perfect and centered ­Figure 3.6c.
Figure 3.6a - Deviation from parallel
Figure 3.6b - Deviation from concentricity
Figure 3.3 - Motor mounted on a concrete base with foundation studs
3.1.3 Alignment
The electric motor should be accurately aligned with the driven machine, particularly in cases of direct coupling. An incorrect alignment can cause bearing failure vibrations and even shaft rupture. The best way to ensure correct alignment is to use dial gauges placed on each coupling half, one reading radially and the other exially ­Figure 3.5.
Figure 3.6c - Alignment with a steel ruler
3.1.4 Coupling
a) Direct Coupling
Direct coupling is always preferable due to its lower cost, space economy, no belt slippage and lower accident risk. In the case of speed ratio drives, it is also common to use a direct coupling with a reducer (gear box).
CAUTION: Carefully align the shaft ends using, whenever feasible, a flexible coupling.
Figure 3.5 - Alignment with dial gauges
8
Figure 3.7 - A type of direct coupling
b) Gear Coupling
Poorly aligned gear couplings are the cause of jerking motions which bring about the vibration of the actual drive and vibrations within the motor.
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
Therefore, due care must be given to perfect shaft alignment: exactly parallel in the case of straight gears, and at the correct angle for bevel or helical gears. Perfect gear engagement can be checked by the insertion of a strip of paper on which the teeth marks will be traced after a single rotation.
c) Belt and Pulley Coupling
Belt coupling is most commonly used when a speed ratio is required.
Assembly of Pulleys: T o assemble pulleys on shaft ends with a keyway and threaded end holes the pulley should be inserted halfway up the keyway merely by manual pressure. On shafts without threaded end holes the heating of the pulley to about 80°C is recommended, or alternatively, the devices illustrated in Figure
3.8 may be employed.
Figure 3.8 - Pulley mounting device
RUNNING: To avoid needless radial stresses on the bearings it is imperative that shafts are parallel and the pulleys perfectly aligned. (Figure 3.10).
Figure 3.10 - Correct pulley alignment
Laterally misaligned pulleys, when running, transmit alternating knocks to the rotor and can damage the bearing housing. Belt slippage can be avoided by applying a resin (rosin for example). Belt tension should be sufficient to avoid slippage during operation (Figure 3.11). Pulleys that are too small should be avoided; these cause shaft flexion because belt traction increases in proportion to a decrease in the pulley size. T able 1 determines minimum pulley diameters, and T ables 2 and 3 refer to the maximum stresses acceptable on motor bearings up to frame 580. Beyond frame size 600, an analysis should be requested from the WEG engineering.
Figure 3.8a - Pulley extractor
Hammers should be avoided during the fitting of pulleys and bearings. The fitting of bearings with the aid of hammers leaves blemishes on the bearing races. These initially small flaws increase with usage and can develop to a stage that completely impairs the bearing. The correct positioning of a pulley is shown in Figure 3.9.
Figure 3.9 - Correct positioning of pulley on the shaft
Figure 3.1 1 - Belt tensions
9
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
T able 1 - Minimum pitch diameter of pulleys
Ball bearings
Frame Size X Inches
140 6205-Z 1.7 1.85 2
W 180 6206-Z 3.03 3.23 3.46
180 6307-Z 1.69 1.81 1.93
W 210 6308-Z 2.86 3.00 3.16
210 6308-Z 2.90 3.06 3.22
W 250 6309 C3 4.37 4.54 4.72 4.92
25 0 6309 C3 4.41 4.59 4.77 4.97 280 6311 C3 5.08 5.19 5.47 5.65 32 0 6312 C3 7.44 7.76 7.94 8.18 36 0 6314 C3 8.73 9.00 9.28 9.57
Frame Poles Size X Inches Size X Inches
400
440
500
5008
580
Bearing
II 6314 C3 7.3 7.62 7.94 8.24 - - - - - -
IV-VI-VII 6314 C3 NU 316 4.13 4.31 4.49 4.67 4.85 -
II 6314 C3 1 1.75 12.16 12.61 13.08 - - - - - -
IV-VI-VIII 6319 C3 NU 319 4.02 4.17 4.32 4.47 4.62 4.82
II 6314 C3 23.54 24.34 25.12 25.87 - - - - - -
IV-VI-VIII 6319 C3 NU 319 6.52 6.73 6.95 7.17 7.39 7.67
II 6314 C3 44.66 45.79 46.98 48.23 - - - - - -
IV-VI-VIII 6322 C3 NU 322 8.73 8.95 9.96 11.34 12.87 14.82
II 6314 C3 5 7 5 8 5 9 6 0 - - - - - -
IV-VI-VIII 6322 C3 NU 322 10.72 10.91 11.1 1 11.31 11.50 1 1.76
0.79 1.57 2.36 3.15 3.94 4.72
Ball Bearing Roller Bearing
Bearing Bearing
1.97 3.15 4.33 5.51 1.97 3.15 4.33 5.51 6.69 8.27
Important: 1) Peripheral speeds for solid grey cast iron pulleys FC 200 is V = 1 15 ft/s.
2) Use steel pulleys when peripheral speed is higher than 115 ft/s.
3) V-belt speed should not exceed 1 15 ft/s.
T able 2 - Maximum acceptable radial load (Lbf)
Nema 56 Motors Saw Arbor Motors
Radial Force (Lbf) 80 LMS II - 35 5 -
Frame Distance X 80 MMS II - 3 59 -
56A 90 LMS
56B
56D
Poles
II 88 - 59 II 427 -
IV 88 - 59 IV - 555 -
II 88 - 59
IV 86 - 59
II 127 - 70
IV 141 - 70
1 1,18 2 80 S MS I I - 357 -
10
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
T able 3 - Maximum acceptable axial load (Lbf)
IP55 T otally Enclosed Motors - 60Hz
Position / Construction Form
F R A M E
II IV VI VIII II IV VI VIII II IV VI VIII II IV VI VIII
140 103 141 167 187 112 152 185 207 99 132 158 178 105 143 174 198
W 180 108 145 180 202 154 209 255 286 94 130 165 183 141 194 240 269
180 149 207 249 286 269 370 443 500 136 189 229 266 253 352 421 480
W 210 196 264 326 368 329 447 544 610 176 238 297 339 310 421 518 582
210 189 257 315 357 324 443 533 599 160 220 275 310 295 405 493 553
W 250 282 372 443 485 471 620 734 811 240 317 394 414 430 564 685 743
250 273 368 436 485 463 615 727 813 220 310 379 421 410 557 672 749 280 355 480 551 624 621 826 959 1,082 275 388 427 502 540 736 838 961 320 374 498 588 668 703 930 1,091 1,232 266 366 432 511 597 793 937 1,078 360 890 1,181 1,144 1,323 890 1,181 1,375 1,552 745 985 1,144 1,323 745 985 1,144 1,323 400 877 1,148 1,347 1,521 877 1,148 1,347 1,521 705 890 1,060 1,241 705 890 1,060 1,241 440 842 1,303 1,563 1,821 842 1,303 1,563 1,821 568 884 1,109 1,488 568 884 1,109 1,488 500 769 1,250 1,481 1,728 769 1,250 1,481 1,728 355 721 844 1,190 355 721 844 1,109
5008 791 1624 1909 2137 791 1624 1909 2137 728 1548 1808 2029 728 1548 1808 2029
580 679 1,406 1,649 1,865 679 1,406 1,649 1,865 033 474 549 597 033 474 549 597
Open Motors - NEMA 56 Frames - 60Hz
Position / Construction Form
F R A M E
II IV II IV II IV II IV 56 A 68 90 83 112 63 85 79 108 56 B 66 90 81 110 63 83 77 105 56 D 63 88 105 145 59 81 101 138
11
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
The maximum radial load for each frame are determined, by graphs.
INSTRUCTIONS ON HOW TO USE THE GRAPHS
1 - Maximum radial load on shaft. 2 - Maximum radial load on bearings.
Where: X - Half of pulley width (inches)
Fr- Maximum radial load in relation to the diameter and
pulley width.
Example:
Verify whether a 2HP motor , II Pole, 60Hz withstands a radial load of 110Lb, considering a pulley width of 4 inches.
Frame: 145T Fr: 110Lb X: 2 inches
1 - Mark the distance X 2 - Find out line N = 3600 for bearing Based on the above, this bearing withstands a radial load of 130Lb.
12
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
13
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
14
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
Note: For frames 600 and above, consult your engineering
representative.
15
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
3.2 Electrical Aspects
3.2.1 Feed System
Proper electric power supply is very important. The choice of motor feed conductors, whether branch or distribution circuits, should be based on the rated current of the motors as per NFPA-70 Standard article 430. T ables 4, 5 and 6 show minimum conductor gauges sized according to maximum current capacity and maximum voltage drop in relation to the distance from the distribution center to the motor, and to the type of installation (Overhead or in ducts).
To determine the conductor gauge proceed as follows:
a) Determine the current by multiplying the current indicated on the motor nameplate by 1.25 and then locate the resulting value on the corresponding table. If the conductor feeds more than one motor, the value to be sought on the table should be equal 1.25 times the rated current of the largest motor plus the rated current of the other motors. In the case of variable speed motors, the highest value among the rated currents should be considered. When motor operation is intermittent, the conductors should have a current carrying capacity equal or greater, to the product of the motor rated current times the running cycle factor shown on T able
7.
T able 7 - Running cycle factor
Motor Short
Motor short
Duty Classification
Short (operating valves, activating contacts etc)
Intermittent (passenger or freight elevators, tools, pumps, rolling bridges etc)
Cyclic (rolling mills,mining machines etc)
Variable
time rating
5min 15min
1.10
0.85
0.85
1.10
30 at 60min
1.50
1.20
0.85
0.90
0.90 0.95
1.20 1.50
Continuos
-
1.40
1.40
2.00
3.2.2 Starting of Electric Motor
Induction motors can be started by the following methods:
Direct Starting
Whenever possible a three-phase motor with a squirrel cage rotor should be started directly at full supply voltage by means of a contactor (Connection diagram a). This method is called Direct-on­Line (DOL) starting. There are DOL starter assemblies available combining a three-pole contactor, a bimetal relay (overload protection device), and a fuse (short circuit protection on branch circuit). DOL starting is the simplest method, only feasible however , when the locked rotor current (LRC) does not influence the main electric supply lines. Initial locked rotor current (LRC) in induction motors reach values six to eight times the value of the full load current. During starting by the DOL method, starting current can reach these high levels. The main electrical supply should be rated sufficiently, such that during the starting cycle no supply disturbance to others on the power network is caused by the voltage drop in the main supply. This can be achieved under one of the following situations: a) The rated main supply current is high enough for the locked rotor
current not to be proportionally high. b) Motor locked rotor current is low with no effect on the networks. c) The motor is started under no-load conditions with a short starting
cycle and, consequently, a low locked rotor current with a transient
voltage drop tolerable to other consumers.
Starting with a compensating switch (auto-transformer starting)
Should direct on line starting not be possible, either due to restrictions imposed by the power supply authority or due to the installation itself, reduced voltage indirect starting methods can be employed to lower the locked rotor current. The single line connection diagram (C) shows the basic components of a compensating switch featuring a transformer (usually an auto-transformer) with a series of taps corresponding to the different values of the reduced voltage. Only three terminals of the motor are connected to the switch, the other being interconnected as per diagram, for the indicated voltage.
Star-Delta starting
It is fundamental to star-delta starting that the three-phase motor has the necessary numbers of leads for both connections:
b) Locate the rated voltage of the motor and the feed network distance in the upper part of the corresponding table. The point of intersection of the distance column and the line referring to current will indicate the minimum required gauge of the conductor.
Example:
Size the conductors for a 15 HP , three-phase, 230V , 42A, motor located 200 feet from the main supply with cables laid in conduits.
a) Current to be located: 1.25 x 42A = 52.5A b) Closest value on table 6:55A c) Minimum gauge: 6 A WG
16
6 leads for Y/ or 12 leads for YY/∆∆
All the connections for the various voltages are made through terminals in the terminal box in accordance with the wiring diagram that accompanies the motor. This diagram may be shown on the nameplate or in the terminal box. The star-delta connection is usually used only in low-voltage motors due to normally available control and protection devices. In this method of starting the locked rotor current is approximately 30% of the original LRC. The locked rotor torque is reduced proportionally as well. For this reason, it is very important before deciding to use
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
T able 4 - Wire and cable gauges for single-phase motor installation (voltage drop < 5%) (in conduits)
Supply Voltage Distance of motor from distribution centre (feet)
115 34 51 69 85 102 137 171 205 240 273 308 342 428 514 230 69 102 138 170 204 274 342 410 480 546 616 684 856 1028 460 138 204 276 340 408 548 684 820 960 1092 1232 1368 1712 2056 575 170 250 338 420 501 670 840 1010 1181 1342 1515 1680 2105 2530
Current ( A) Cable gauge (conductor)
5 14141414141414121212121010 8 10 14 14 14 14 12 12 10 10 10 8 8 8 6 6 15 12 12 12 12 12 10 8 8 6 6 6 6 4 2 20 121212101088666444 2 30 10101088666442221/0 40 8888664422221/02/0 55 6666644221/01/01/01/02/0 70 444442221/01/02/02/02/02/0 95 2222221/01/01/02/03/03/04/0250M
T able 5 - Wire and cable gauges for three-phase motor installation - aerial conductors with 25cm spacing (voltage drop < 5%)
Supply Voltage Distance of motor from distribution centre (feet)
115 51 69 85 102 137 171 205 240 273 308 342 428 514 685 230 102 138 170 204 274 342 410 480 546 616 684 856 1028 1370 460 204 276 340 408 547 684 820 960 1092 1232 1368 1712 2056 2740 575 250 338 420 501 670 840 1010 1181 1342 1515 1680 2105 2530 3350
Current ( A) Cable gauge (conductor)
15 14 14 14 12 12 10 10 10 8 8 8 6 6 4 20 14 14 12 12 10 10 8 8 8 6 6 4 4 2 30 14121088866444221/0 40 1210108864442221/02/0 55 1010886442221/02/03/0--
70 886642221/01/02/03/0---­100 6644221/02/03/04/04/0-----­130 44421/01/02/04/0---------- -­175 2 2 2 1/0 2/0 3/0 -- -- -- -- -- -- -- -­225 1/0 1/0 1/0 2/0 3/0 -- -- -- -- -- -- -- -- -­275 2/0 2/0 2/0 4/0 -- -- -- -- -- -- -- -- -- -­320 3/0 3/0 3/0 4/0 -- -- -- -- -- -- -- -- -- --
T able 6 - Wire and cable gauges for three-phase motor installation (voltage drop < 5%) (in conduits)
Supply Voltage Distance of motor from distribution centre (feet)
115 85 102 120 137 171 205 240 273 308 342 428 514 230 170 204 240 274 342 410 480 546 616 684 856 1028 460 340 408 480 548 684 820 960 1092 1232 1368 1712 2056 575 420 501 590 670 840 1010 1181 1342 1515 1680 2105 2530
Current ( A) Cable gauge (conductor)
15 12121210108 886664 20 1210101088 666644 30 1088866 644422 40 886664 442221/0 55 6 6 6 4 4 4 2 2 2 1/0 1/0 1/0 70 4 4 4 4 2 2 2 1/0 1/0 1/0 2/0 2/0 95 2 2 2 2 2 1/0 1/0 1/0 1/0 2/0 3/0 4/0
125 1/0 1/0 1/0 1/0 1/0 1/0 2/0 2/0 3/0 3/0 4/0 250M 145 2/0 2/0 2/0 2/0 2/0 2/0 2/0 3/0 3/0 4/0 250M 300M 165 3/0 3/0 3/0 3/0 3/0 3/0 3/0 3/0 4/0 4/0 250M 350M 195 4/0 4/0 4/0 4/0 4/0 4/0 4/0 4/0 250M 250M 300M 350M 215 250M 250M 250M 250M 250M 250M 250M 250M 250M 300M 350M 400M 240 300M 300M 300M 300M 300M 300M 300M 300M 300M 300M 400M 500M 265 350M 350M 350M 350M 350M 350M 350M 350M 350M 350M 500M 500M 280 400M 400M 400M 400M 400M 400M 400M 400M 400M 400M 400M -­320 500M 500M 500M 500M 500M 500M 500M 500M 500M 500M 500M --
Note: The above indicated values are orientative. For guaranteed values, contact the Local Power Company.
17
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
star-delta starting to verify if the reduced locked rotor torque in “STAR” connection is enough to accelerate the load.
3.2.3 Motor Protection
Motor circuits have, in principle, two types of protection: motor overload, locked rotor and protection of branch circuit from short circuits. Motors in continuous use should be protected from overloading by means of a device incorporated into the motor, or by an independent device, usually a fixed or adjustable thermal relay equal or less than to the value derived from multiplying the rated feed current at full load by:
- 1.25 for motors with a service factor equal or superior to 1.15 or;
- 1.15 for motors with service factor equal to 1.0. Some motors are optionally fitted with overheating protective detectors
(in the event of overload, locked rotor, low voltage, inadequate motor ventilation) such as a thermostat (thermal probe), thermistor (PTC), RTD type resistance which dispense with independent devices.
THERMOSTA T (THERMAL PROBE): Bimetallic thermal detectors with normally closed silver contacts. These open at pre-determined temperatures. Thermostats are series connected directly to the contactor coil circuit by two conductors.
THERMISTORS: Semi-conductor heat detectors positive temperature coeficient (PTC) that sharply change their resistance upon reaching a set temperature. Thermistors, depending upon the type, are series or parallel-connected to a control unit that cuts out the motor feed, or actuates an alarm system, in response to the thermistors reaction.
RESISTANCE TEMPERATURE DETECT ORS (RTD) - PT 100:The resistance type heat detector (RTD) is a resistance element usually manufactured of copper or platinum. The RTD operates on the principle that the electrical resistance of a metallic conductor varies linearly with the temperature. The detector terminals are connected to a control panel, usually fitted with a temperature gauge, a test resistance and a terminal changeover switch.
Subject to the desired degree of safety and the client’s specification, three (one per phase) or six (two per phase) protective devices can be fitted to a motor for the alarm stems, circuit breaker or combined alarm and circuit breaker, with two leads from the terminal box to the alarm or circuit breaker system and four for the combined system (alarm and circuit breaker). T able 9 compares the two methods of protection.
3.3 Start-up
3.3.1 Preliminary Inspection
Before starting a motor for the first time, it will be necessary to:
c) Ascertain that voltage and frequency correspond to those indicated
on the nameplate. Motor performance will be satisfactory with main supply voltage fluctuation within ten per cent of the value indicated on the nameplate or a frequency fluctuation within five per cent or, yet, with a combined voltage and frequency variance within ten per cent;
d) Check that connections are in accordance with the connection
diagram shown on the nameplate and be sure that all terminal screws and nuts are tight;
e) Check the motor for proper grounding. Providing that there are no
specifications calling for ground-insulated installation, the motor must be grounded in accordance with prevalent standard for grounding electrical machines. The screw identified by the symbol
should be used for this purpose. This screw is generally to be found in the terminal box or on one foot of the frame;
f) Check that motor leads connecting with the mains, as well as the
control wires and the overload protection device, are in accordance with Nema Standards;
g) If the motor has been stored in a damp place, or has been stopped
for some time, measure the insulating resistance as recommended under the item covering storage instructions;
h) Start the motor uncoupled to ascertain that it is turning in the desired
direction. To reverse the rotation of a three-phase motor , invert two terminal leads of the mains supply. High voltage motors bearing an arrow on the frame indicating rotation direction can only turn in the direction shown.
3.3.2 The First Start-up
Three-Phase Motor with Cage Rotor:
After careful examination of the motor, follow the normal sequence of starting operations listed in the control instructions for the initial start­up.
3.3.3 Operation
Drive the motor coupled to the load for a period of at least one hour while watching for abnormal noises or signs of overheating. Compare the line current with the value shown on the nameplate. Under continuous running conditions without load fluctuations this should not exceed the rated current times the service factor, also shown on the nameplate. All measuring and control instruments and apparatus should be continuously checked for anomalies, and any irregularities corrected.
a) Remove all locking devices and blocks used in transit and check
that the motor rotates freely;
b) Check that the motor is firmly secured and that coupling elements
are correctly mounted and aligned.;
18
3.3.4 Stopping
Warning:
To touch any moving part of a running motor, even though
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
disconnected, is a danger to life and limb.
Three-phase motor with cage rotor:
Open the stator circuit switch. With the motor at a complete stop, reset the auto-transformer, if any, to the “start” position.
Table 9 - Comparison between motor protection system
Current-based Protection
protection with
Causes of probe
overheating Fuse and thermistor
Fuse only thermal in motor
protector
1. Overload with 1.2 times rated current
2. Duty cycles S1 to S8 IEC 34, EB 120
Caption: unprotected
partially protected totally protected
3. Brakings, reversals and frequent starts
4. Operating with more than 15 starts p/hour
5. Locked rotor
6. Fault on one phase
7. Execessive voltage fluctuation
8. Frequency fluctuation
on main supply
9. Excessive ambient temperature
10. External heating caused by bearings, belts, pulleys etc.
11. Obstructed ventilation
19
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
CONNECTION DIAGRAMS
a) Direct starting
POWER NETWORK
b) Star-Delta starting
POWER NETWOR
c) Auto-transformer starting
POWER NETWORK
20
T able 1 1 - Bearing specifications by type of motor
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
NEMA Bearings
Frames Front (D.E.) Rear (O.D.E.)
B48 and C48 6203 Z 6202 Z
56 and A56 6203 Z 6202 Z
B56 and C56 6203 Z 6202 Z
D56 and 6204 Z 6202 Z /
F56H/G56H 6203 Z
143 T 6205 ZZ 6204 ZZ 145 T 6205 ZZ 6204 ZZ 182 T 6307 ZZ 6206 ZZ
184 T 6307 ZZ 6206 ZZ W 182 T 6206 ZZ 6205 ZZ W 184 T 6206 ZZ 6205 ZZ
213 T 6308 ZZ 6207 ZZ
215 T 6308 ZZ 6207 ZZ W 213 T 6308 ZZ 6207 ZZ W 215 T 6308 ZZ 6207 ZZ
254 T 6309-C3 6209 Z-C3
256 T 6309-C3 6209 Z-C3 W 254 T 6309-C3 6209 Z-C3 W 256 T 6309-C3 6209 Z-C3
284 T and TS 631 1-C3 621 1 Z-C3 286 T and TS 631 1-C3 621 1 Z-C3 324 T and TS 6312-C3 6212 Z-C3 326 T and TS 6312-C3 6212 Z-C3 364 T and TS 6314-C3 6314-C3 365 T and TS 6314-C3 6314-C3
404 T NU 316-C3 6314-C3
404 TS 6314-C3 6314-C3
405 T NU 316-C3 6314-C3
405 TS 6314-C3 6414-C3
444 T NU 319-C3 6316-C3
444 TS 6314-C3 6314-C3
445 T NU 319-C3 6316-C3
445 TS 6314-C3 6314-C3
447 T NU 319-C3 6316-C3
447 TS 6314-C3 6314-C3
449 T NU 322-C3 6319-C3
449 TS 6314-C3 6314-C3
504 T NU 319-C3 6316-C3
504 TS 6314-C3 6314-C3
505 T NU 319-C3 6316-C3
505 TS 6314-C3 6314-C3
5008 T NU 322-C3 6319-C3
5008TS 6314-C3 6314-C3
586 T NU 322-C3 6319-C3
586 TS 6314-C3 6314-C3
587 T NU 322-C3 6319-C3
587 TS 6314-C3 6314-C3
Saw Arbor Bearings
motor Mounting
frame Front (D.E.) Rear (O.D.E.)
80 S M S 6307 ZZ 6207 ZZ
80 M M S 6307 ZZ 6207 ZZ
80 L MS 6307 ZZ 6207 ZZ 90 L MS 6308 ZZ 6208 ZZ
Mounting
Open drip proof motors
ALL FORMS
T otally enclosed fan cooled motors
ALL FORMS
B3
ODP Motors Bearings
Nema-T Mounting
frames Front (D.E.) Rear (O.D.E.)
E143/5T 6205 ZZ 6204 ZZ F143/5T 6205 ZZ 6204 ZZ
182 T 6206 ZZ 6205 ZZ 184 T 6202 ZZ 6205 ZZ
213/5T 6208 ZZ 6206 ZZ
254 T 6309 Z-C3 6209 Z-C3 256 T 6309 Z-C3 6209 Z-C3 284 T 6311 Z-C3 6211 Z-C3
284 TS 6311 Z-C3 6211 Z-C3
286 T 6311 Z-C3 6211 Z-C3
286 TS 6311 Z-C3 6211 Z-C3
324 T 6312 Z-C3 6212 Z-C3
324 TS 6312 Z-C3 6212 Z-C3
326 T 6312 Z-C3 6212 Z-C3
326 TS 6312 Z-C3 6212 Z-C3
364 T 6314 C3 6314 C3
364 TS 6314 C3 6314 C3
365 T 6314 C3 6314 C3
365 TS 6314 C3 6314 C3
404 T NU 316 C3 6314 C3
404 TS 6314 C3 6314 C3
405 T NU 316 C3 6314 C3
405 TS 6314 C3 6314 C3
444 T NU 319 C3 6316 C3
444 TS 6314 C3 6314 C3
445 T NU 319 C3 6316 C3
445 TS 6314 C3 6314 C3
IEC Bearings
frame Front (D.E.) Rear (O.D.E.)
63 6201 ZZ 6201 ZZ 71 6203 ZZ 6202 ZZ 80 6204 ZZ 6203 ZZ
90 S - L 6205 ZZ 6204 ZZ
100 L 6206 ZZ 6205 ZZ
112 M 6307 ZZ 6206 ZZ 132 S - M 6308 ZZ 6207 ZZ 160 M - L 6309-C3 6209 Z-C3 180 M - L B3 6311-C3 6211 Z-C3 200 M - L 6312-C3 6212 Z-C3
225 S/M 6314-C3 6314-C3 250 S/M 6314-C3 6314-C3 280 S/M 6314-C3 6314-C3
315 S/M 6314-C3 6314-C3
355 M/L 6314-C3 6314-C3
HORIZONTAL MOUNTING ONLY
Mounting
T otally enclosed fan cooled motors
6316-C3 6316-C3
6319-C3 6316-C3
NU 322-C3 6319-C3
21
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
T able 12 – Bearing lubrication intervals and amount of grease
BALL BEARINGS - Series 62/63
Relubrication intervals (running hours – horizontal position)
II pole IV pole VI pole VIII pole X pole XII pole
Serie 62
Bearing 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz (g)
6209 18400 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 9 6211 14200 16500 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 11 6212 12100 14400 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 13
Serie 63
Bearing 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz (g)
6309 15700 18100 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 13 6311 11500 13700 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 18 6312 9800 11900 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 21 6314 3600 4500 9700 11600 14200 16400 17300 19700 19700 20000 20000 20000 27 6316 - - 8500 10400 12800 14900 15900 18700 18700 20000 20000 20000 34 6319 - - 7000 9000 11000 13000 14000 17400 17400 18600 18600 20000 45 6322 - - 5100 7200 9200 10800 11800 15100 15100 15500 15500 19300 60
Amount of
grease
Table 13 – Bearing lubrication intervals and amount of grease
BALL BEARINGS - Series NU3
Relubrication intervals (running hours – horizontal position)
II pole IV pole VI pole VIII pole X pole XII pole
Bearing 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz 50Hz (g) NU 309 9800 13300 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000 13 NU 311 6400 9200 19100 20000 20000 20000 20000 20000 20000 20000 20000 20000 18 NU 312 5100 7600 17200 20000 20000 20000 20000 20000 20000 20000 20000 20000 21 NU 314 1600 2500 7100 8900 11000 13100 15100 16900 16900 19300 19300 20000 27 NU 316 - - 6000 7600 9500 11600 13800 15500 15500 17800 17800 20000 34 NU 319 - - 4700 6000 7600 9800 12200 13700 13700 15700 15700 20000 45 NU 322 - - 3300 4400 5900 7800 10700 11500 11500 13400 13400 17300 60 NU 324 - - 2400 3500 5000 6600 10000 10200 10200 12100 12100 15000 72
Notes:
• The ZZ bearings from 6201 to 6307 do not require relubrication as its life time is about 20,000 hours.
• Tables 1 and 2 are intended for the lubrication period under bearing temperature of 70oC (for bearings up to 6312 and NU 312) and temperature of 85oC (for bearings 6314 and NU 314 and larger).
• For each 15oC of temperature rise, the relubrication period is reduced by half.
• The relubrication periods given above are for those cases applying Polyrex® EM grease.
• When motors are used on the vertical position, their relubrication interval is reduced by half if compared to horizontal position motors.
Compatibility of Polyrex® EM grease with other types of grease:
Containing polyurea thickener and mineral oil, the Polyrex® EM grease is compatible with other types of grease that contain:
• Lithium base or complex of lithium or polyurea and highly refined mineral oil.
• Inhibitor additive against corrosion, rust and anti-oxidant additive.
Notes:
• Although Polyrex® EM is compatible with types of grease given above, we do no recommended to mix it with any other greases.
• If you intend to use a type of grease different than those recommended above , first contact WEG.
• On applications (with high or low temperatures, speed variation, etc), the type of grease and relubrification interval are given on an
additional nameplate attached to the motor.
Amount of
grease
22
4. Maintenance
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
A well-designed maintenance program for electric motors can be summed up as: periodical inspection of insulation levels, temperature rise, wear, bearing lubrication and the occasional checking of fan air flow. Inspection cycles depend upon the type of motor and the conditions under which it operates.
4.1 Cleanliness
Motors should be kept clean, free of dust, debris and oil. Soft brushes or clean cotton rags should be used for cleaning. A jet of compressed air should be used to remove non-abrasive dust from the fan cover and any accumulated grime from the fan and cooling fins. Oil or damp impregnated impurities can be removed with rags soaked in a suitable solvent. T erminal boxes fitted to motors with IP55 protection should be cleaned; their terminals should be free of oxidation, in perfect mechanical condition, and all unused space dust-free. Motors with IPW 55 protection are recommended for use under unfavourable ambient conditions.
4.2 Lubrication
Proper lubrication extends bearing life.
Lubrication Maintenance Includes:
a) Attention to the overall state of the bearings; b) Cleaning and lubrication; c) Critical inspection of the bearings.
Motor noise should be measured at regular intervals of one to four months. A well-tuned ear is perfectly capable of distinguishing unusual noises, even with rudimentary tools such as a screw driver, etc., without recourse to sophisticated listening aids or stethescopes that are available on the market. A uniform hum is a sign that a bearing is running perfectly . Bearing temperature control is also part of routine maintenance. Constant temperature control is possible with the aid of external thermometers or by embedded thermal elements. WEG motors are normally equipped with grease lubricated ball or roller bearings. Bearings should be lubricated to avoid metallic contact of the moving parts, and also for protection against corrosion and wear. Lubricant properties deteriorate in the course of time and mechanical operation: furthermore, all lubricants are subject to contamination under working conditions. For this reason lubricants must be renewed and any lubricant consumed needs replacing from time to time.
4.2.1 Periodical Lubrication
WEG motors are supplied with sufficient grease for a long running period. Lubrication intervals, the amount of grease and the type of bearing used in frames 140T to 580T are to be found in Tables 11, 12 and 13. Lubrication intervals depend upon the size of the motor, speed, working conditions and the type of grease used.
4.2.2 Quality and Quantity of Grease
Correct lubrication is important!
Grease must be applied correctly and in sufficient quantity as both insufficient or excessive greasing are harmful. Excessive greasing causes overheating brought about by the greater resistance encountered by the rotating parts and, in particular, by the compacting of the lubricant and its eventual loss of lubricating qualities. This can cause seepage with the grease penetrating the motor and dripping on the coils.
GREASES FOR MOTOR BEARINGS
For operating temperatures from -30 to 170oC
Type
Polyrex® EM
Supplier
Esso
4.2.3 Lubricating Instructions
a) Frame 140T to 210T motors
Frame 140T to 210T size motors are not fitted with grease nipples. Lubrication is carried out during periodical overhauls when the motor is taken apart.
Cleaning and Lubrication of Bearings
With the motor dismantled and without extracting the bearings from the shaft, all existing grease should be removed and the bearings cleaned with Diesel oil, kerosene or other solvent, until thoroughly clean. Refill the spaces between the balls or rollers and the bearing cages with grease immediately after washing. Never rotate bearings in their dry state after washing. For inspection purposes apply a few drops of machine oil. During these operations maximum care and cleanliness is recommended to avoid the penetration of any impurities or dust that could harm the bearings. Clean all external parts prior to reassembly .
b) Frame 360T to 580T Motors Motors above 360T frame size are fitted with regreasable bearing system. The lubrication system from this frame size upwards was designed to allow the removal of all grease from the bearing races through a bleeder outlet which at the same time impedes the entry of dust or other contaminants harmful to the bearing. This outlet also prevents injury to the bearings from the well-known problem of over-greasing.
23
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
It is advisable to lubricate while the motor is running, to allow the renewal of grease in the bearing case. Should this procedure not be possible because of rotating parts in the proximity of the nipple (pulleys, coupling sleeves, etc.) that are hazardous to the operator the following procedure should be followed:
- Inject about half the estimated amount of grease and run the motor at full speed for approximately a minute; switch off the motor and inject the remaining grease. The injection of all the grease with the motor at rest could cause penetration of a portion of the lubricant through the internal seal of the bearing case and hence into the motor.
Providing suitable tooling is employed, disassembly of a bearing is not difficult. The extractor grips should be applied to the sidewall of the inner ring to be stripped, or to an adjacent part. To ensure perfect functioning and to prevent injury to the bearing parts, it is essential that the assembly be undertaken under conditions of complete cleanliness and by competent personnel. New bearings should not be removed from their packages until the moment of assembly. Prior to fitting a new bearing, ascertain that the shaft has no rough edges or signs of hammering.
Figure 4.1 - Bearings and lubrication system
Nipples must be clean prior to introduction of grease to avoid entry of any alien bodies into the bearing. For lubricating use only a manual grease gun.
Bearing Lubrication Steps
1.Cleanse the area around the grease nipples with clean cotton fabric.
2.With the motor running, add grease with a manual grease gun until the lubricant commences to be expelled from the bleeder outlet, or until the quantity of grease recommended in T ables 12 or 13 has been applied.
3.Allow the motor to run long enough to eject all excess grease.
4.2.4 Replacement of Bearings
The opening of a motor to replace a bearing should only be carried out by qualified personnel. Damage to the core after the removal of the bearing cover can be avoided by filling the gap between the rotor and the stator with stiff paper of a proper thickness.
Figure 4.2 - A bearing extractor
During assembly bearings cannot be subjected to direct blows. The aid used to press or strike the bearing should be applied to the inner ring.
4.3 Air Gap Checking (Large Rating Open Motors)
Upon the completion of any work on the bearings check the gap measurement between the stator and the rotor using the appropriate gazes. The gap variation at any two vertically opposite points must be less than 10% of the average gap measurement.
4.4 Explosion Proof Motor Repair Steps
4.4.1 Objective
In view of the heavy liability associated with burning of motors of this type, this product has been designed and manufactured to high technical standards, under rigid controls. In addition, in many areas it is required that explosion proof motors ONLY be repaired by licensed personnel or in licensed facilities authorized to do this type of work. The following general procedures, safeguards, and guidelines must be followed in order to ensure repaired explosion proof motors operate as intended.
4.4.2 Repair Procedure and Precautions
Dismantle the damaged motor with appropriate tools without hammering and/or pitting machined surfaces such as enclosure joints, fastening
24
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
holes, and all joints in general. The position of the fan cover should be suitably marked prior to removal so as to facilitate reassembly later on. Examine the motor’s general condition and, if necessary, disassemble all parts and clean them with kerosene. Under no circumstances should scrapers, emery papers or tools be used that could affect the dimensions of any part during cleaning. Protect all machined parts against oxidation by applying a coating of vaseline or oil immediately after cleaning.
STRIPPING OF WINDINGS
This step requires great care to avoid knocking and/or denting of enclosure joints and, when removing the sealing compound from the terminal box, damage or cracking of the frame.
IMPREGNATION
Protect all frame threads by inserting corresponding bolts, and the joint between terminal box and frame, by coating it with a non-adhesive varnish (ISO 287 - ISOLASIL). Protective varnish on machined parts should be removed soon after treating with impregnating varnish. This operation should be carried out manually without using tools.
ASSEMBLY
Inspect all parts for defects, such as cracks, joint incrustations, damaged threads and other potential problems. Assemble using a rubber headed mallet and a bronze bushing after ascertaining that all parts are perfectly fitted. Bolts should be positioned with corresponding spring washers and evenly tightened.
Upon reassembling explosion proof motors IPW55 the substitution of all seals is mandatory.
Should any doubts arise, consult WEG.
TESTING
Rotate the shaft by hand while examining for any drag problems on covers or fastening rings. Carry out running tests as for standard motors.
MOUNTING THE TERMINAL BOX
Prior to fitting the terminal box all cable outlets on the frame should be sealed with a sealing compound (Ist layer) and an Epoxy resin (ISO
340) mixed with ground quartz (2nd layer) in the following proportions: 340A resin 50 parts
340B resin 50 parts Ground quartz 100 parts
Drying time for this mixture is two hours during which the frame should not be handled and cable outlets should be upwards. When dry, see that the outlets and areas around the cables are perfectly sealed. Mount the terminal box and paint the motor.
4.4.3 Miscellaneous Recommendations
Any damaged parts (cracks, pittings in machined surfaces,
defective threads) must be replaced and under no circumstances should attempts be made to recover them.
25
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
5. Malfunctioning
Most malfunctions affecting the normal running of electric motors can be prevented by maintenance and the appropriate precautions. While ventilation, cleanliness and careful maintenance are the main factors ensuring long motor life, a further essential factor is the prompt attention to any malfunctioning as signalled by vibrations, shaft knock, declining insulation resistance, smoke or fire, sparking or unusual slip ring or brush wear, sudden changes of bearing temperatures. When failures of an electric or mechanical nature arise, the first step to be taken is to stop the motor and subsequent examination of all mechanical and electrical parts of the installation. In the event of fire, the installation should be isolated from the mains supply, which is normally done by turning of f the respective switches. In the event of fire within the motor itself, steps should be taken to restrain and suffocate it by covering the ventilation vents. To extinguish a fire, dry chemical or C0 used - never water.
extinguishers should be
2
5.1 Standard Three-Phase Motor Failures
Owing to the widespread usage of asynchronous three-phase motors in industry which are more often repaired in the plant workshops, there follows a summary of possible failures and their probable causes, detection and repairs. Motors are generally designed to Class B or F insulation and for ambient temperatures up to 40°C. Most winding defects arise when temperature limits, due to current overload, are surpassed throughout the winding or even in only portions thereof. These defects are identified by the darkening or carbonizing of wire insulation.
5.1.1 Short Circuits Between Turns
A short circuit between turns can be a consequent of two coinciding insulation defects, or the result of defects arising simultaneously on two adjacent wires. As wires are randomly tested, even the best quality wires can have weak spots. Weak spots can, on occasion, tolerate a voltage surge of 30% at the time of testing for shorting between turns, and later fail due to humidity, dust or vibration. Depending on the intensity of the short, a magnetic hum becomes audible. In some cases, the three-phase current imbalance can be so insignificant that the motor protective device fails to react. A short circuit between turns, and phases to ground due to insulation failure is rare, and even so, it nearly always occurs during the early stages of operation.
5.1.2 Winding Failures a) One burnt winding phase
This failure arises when a motor runs wired in delta and current fails in one main conductor. Current rises from 2 to 2.5 times in the remaining winding with a simultaneous marked fall in speed. If the motor stops, the current will increase from 3.5 to 4 times its rated value. In most instances, this defect is due to the absence of a protective switch, or else the switch has been set too high.
b) Two burnt winding phases
This failure arises when current fails in one main conductor and the motor winding is star-connected. 0ne of the winding phases remains currentless while the others absorb the full voltage and carry an excessive current. The slip almost doubles.
c) Three burnt winding phases
Probable cause 1
Motor only protected by fuses; an overload on the motor will be the cause of the trouble. Consequently, progressive carbonizing of the wires and insulation culminate in a short circuit between turns, or a short against the frame occurs. A protective switch placed before the motor would easily solve this problem.
Probable cause 2
Motor incorrectly connected. For example: A motor with windings designed for 230/400V is connected through a star-delta switch to 400V connection. The absorted current will be so high that the winding will burn out in a few seconds if the fuses or a wrongly set protective switch fail to react promptly.
Probable cause 3
The star-delta switch is not commutated and the motor continues to run for a time connected to the star under overload conditions. As it only develops 1/3 of its torque, the motor cannot reach rated speed. The increased slip results in higher ohmic losses arising from the Joule effect. As the stator current, consistent with the load, may not exceed the rated value for the delta connection, the protective switch will not react. Consequent to increased winding and rotor losses the motor will overheat and the winding burn out.
Probable cause 4
Failures from this cause arise from thermal overload, due to too many starts under intermittent operation or to an overly long starting cycle. The perfect functioning of motor operating under these conditions is only assured when the following values are heeded: a) number of starts per hour; b) starting with or without load; c) mechanical brake or current inversion; d) acceleration of rotating masses connected to motor shaft; e) load torque vs. speed during acceleration and braking.
The continuous effort exerted by the rotor during intermittent starting brings about heavier losses which provoke overheating. Under certain circumstances with the motor idle there is a possibility that the stator winding is subjected to damage as a result of the
26
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
heating of the motor. In such a case, a slip ring motor is recommended as a large portion of the heat (due to rotor losses) is dissipated in the rheostat.
5.1.3 Rotor Failures
If a motor running under load conditions produces a noise of varying intensity and decreasing frequency while the load is increased, the reason, in most cases, will be an unsymmetrical rotor winding. In squirrel-cage motors the cause will nearly always be a break in one or more of the rotor bars; simultaneously, periodical stator current fluctuations may be recorded. As a rule, this defect appears only in molded or die cast aluminum cages. Failures due to spot heating in one or another of the bars in the rotor stack are identified by the blue coloration at the affected points. Should there be failures in various contiguous bars, vibrations and shuddering can occur as if due to an unbalance, and are often interpreted as such. When the rotor stack acquires a blue or violet coloration, it is a sign of overloading. This can be caused by overly high slip, by too many starts or overlong starting cycles. This failure can also arise from insufficient main voltage.
5.1.4 Bearing Failures
Bearing damage is a result of overloading brought about by an overly taut belt or axial impacts and stresses. Underestimating the distance between the drive pulley and the driven pulley is a common occurrence. The arc of contact of the belt on the drive pulley thus becomes inadmissibly small and thereby belt tension is insufficient for torque transmission. In spite of this it is quite usual to increase belt tension in order to attain sufficient drive. Admittably, this is feasible with the latest belt types reinforced by synthetic materials. However, this practice fails to consider the load on the bearing and the result is bearing failure within a short time. Additionally there is the possibility of the shaft being subjected to unacceptably high loads when the motor is fitted with a pulley that is too wide.
Any used, and consequently stretched belts retained on the drive, especially those closest to the motor, while new and unstretched belts are placed on the same drive turning farther from the bearing, can augment shaft stress.
5.1.7 Damage Arising from Poorly Fitted Transmission Parts or Improper Motor Alignment
Damage to bearing and fracture in shafts often ensue from inadequate fitting of pulleys, couplings or pinions. There parts “knock” when rotating. The defect is recognized by the scratches that appear on the shaft or the eventual scalelike flaking of the shaft end. Keyways with edges pitted by loosely fitted keys can also bring about shaft failures. Poorly aligned couplings cause knocks and radial and axial shaking to shaft and bearings. Within a short while these malpractices cause the deterioration of the bearings and the enlargement of the bearing cover bracket located on the drive end side. Shaft fracture can occur in more serious cases.
5.1.5 Shaft Fractures
Although bearings traditionally constitute the weaker part, and the shafts are designed with wide safety margins, it is not beyond the realm of possibility that a shaft may fracture by fatigue from bending stress brought about by excessive belt tension. In most cases, fractures occur right behind the drive end bearing. As a consequence of alternating bending stress induced by a rotating shaft, fractures travel inwards from the outside of the shaft until the point of rupture is reached when resistance of the remaining shaft cross-section no longer suffices. Avoid additional drilling the shaft (fastening screw holes) as such operations tend to cause stress concentration.
5.1.6 Unbalanced V-Belt Drives
The substitution of only one of a number of other parallel belts on a drive is frequently the cause of shaft fractures, as well as being malpractice.
27
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
5.2 Troubleshooting chart
FAILURE PROBABLE CAUSE CORRECTIVE MEASURES
Motor fails to start No voltage supply Check feed connections to control system and from this to motor .
Low voltage supply Check voltage supply and ascertain that voltage remains within 10% of the rated voltage shown on the motor nameplate.
Wrong control connections Compare connections with the wiring diagram on the motor nameplate.
Loose connection at some Tighten all connections.
terminal lug
Overload Try to start motor under no-load conditions. If it starts, there may be an overload condition or a blocking of the starting mechanism. Reduce load to rated load level and increase torque.
High noise level • Unbalance Vibrations can be eliminated by balancing rotor. If load is
coupled directly to motor shaft, the load can be unbalanced.
Distorted shaft Shaft key bent; check rotor balance and eccentricity .
Incorrect alignment Check motor aligment with machine running.
Uneven air gap Check shaft for warping or bearing wear.
Dirt in the air gap Dismantle motor and remove dirt or dust with jet of dry air.
Extraneous matter stuck between Dismantle motor and clean. Remove trash or debris from
fan and motor casing motor vicinity.
Loose motor foundation Tighten all foundation studs. If necessary, realign motor .
Worn bearings Check lubrication. Replace bearing if noise is excessive
and continuous.
Overheating of bearings • Excessive grease Remove grease bleeder plug and run motor until excess
grease is expelled.
Excessive axial or radial strain on belt Reduce belt tension.
Deformed shaft Have shaft straightened and check rotor balance.
Rough bearing surface Replace bearings before they damage shaft.
Loose or poorly fitted motor end Check end shields for close fit and tightness around circumference.
shields
Lack of grease Add grease to bearing.
Hardened grease cause locking of Replace bearings.
balls
Foreign material in grease Flush out housings and relubricate.
Intense bearing vibration Unbalanced rotor Balance rotor statically and dynamically.
Dirty or worn bearing If bearing rings are in perfect condition, clean and
relubricate the bearing, otherwise, replace bearing.
Bearing rings too tight on shaft Before altering shaft or housing dimensions, it is advisable
and/or bearing housing to ascertain that bearing dimensions correspond to
manufacturer’s specifications.
Extraneous solid particles in Take bearing apart and clean. Reassemble only if rotating
bearing and support surfaces are unharmed.
Overheating of motor Obstructed cooling system Clean and dry motor; inspect air vents and windings periodically.
Overload Check application, measuring voltage and current under
normal running conditions.
Incorrect voltages and frequecies Compare values on motor nameplate with those of mains supply. Also check voltage at motor terminals under full load.
Frequent inversions Exchange motor for another that meets needs.
Rotor dragging on stator Check bearing wear and shaft curvature.
Unbalanced electrical load Check for unbalanced voltages or operation under
(burnt fuse, incorrect control) single-phase condition.
28
6. Spare Parts and Component Terminology
THREE-PHASE MOTORS IP55 NEMA
Frames 140T - W180T - 180T - 210T and W210T
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
Part Nr. Description
1 Terminal box cover 2 Terminal box cover fixing bolt 3 Terminal box cover gasket 4 Terminal box fixing bolt 5 Terminal box fixing washer 6 Terminal box grounding lug 7 Terminal box 8 Frame grounding lug
9 Terminal box o’ring gasket 10 Fan cover 11 Fan cover fixing bolt 12 Fan
Part Nr. Description
13 V’Ring 14 Non-drive end endshield fixing bolt 15 Non-drive end endshield washer 16 Non-drive endshield 17 Spring washer 18 Non-drive bearing 19 Fan fixing pin 20 Wound stator 21 Rotor / shaft assembly 22 Nameplate fixing rivet 23 Nameplate 24 Frame
THREE-PHASE MOTORS IP55 NEMA
Frames 250T - W250T - 280T and 320T
Part Nr. Description
25 Shaft key 26 Drive end bearing 27 Drive endshield 28 Drive endshield washer 29 Drive end endshield fixing bolt 33 V’Ring 31 Drain plug
Part Nr. Description
1 Terminal box cover
2 Terminal box cover fixing bolt
3 Terminal box cover gasket
4 Terminal box fixing bolt
5 Terminal box fixing washer
6 Terminal box grounding lug
7 Terminal box
8 Frame grounding lug
9 Terminal box o’ring gasket 10 Fan cover 11 Fan cover washer 12 Fan cover fixing bolt 13 Fan 14 Non-drive end bearing cap bolt 15 V’Ring
Part Nr. Description
16 Non-drive end endshield fixing
bolt 17 Non-drive end bearing cap washer 18 Non-drive end grease nipple 19 Non-drive end grease nipple cover 20 Non-drive end endshield washer 21 Non-drive endshield 22 Spring washer 23 Non-drive end bearing 24 Non-drive end bearing cap 25 Fan fixing pin 26 Wound stator 27 Rotor and shaft 28 Eyebolt 29 Nameplate fixing rivet
Part Nr. Description
30 Nameplate 31 Frame 32 Shaft key 33 Drive end bearing cap 34 Drive end bearing 35 Drive andshield 36 Drive end grease nipple cover 37 Drive endshield washer 38 Drive end endshield fixing bolt 39 Drive end bearing cap washer 40 V’Ring 41 Drive end bearing cap fixing bolt 42 Drain plug 43 Non-drive and grease relief 44 Drive end grease relief
29
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
THREE-PHASE MOTORS IP55 NEMA T
Frames 360T - 400T - 440T - 500T and 580T
Part Nr. Description
1 Terminal box cover 2 Terminal box cover fixing bolt 3 Terminal box cover washer 4 Terminal box cover gasket 5 Terminal box fixing bolt 6 Terminal box fixing washer 7 Terminal box grounding lug 8 Terminal box 9 Frame grounding lug
10 Terminal box o’ring gasket
11 Nameplate fixing rivet 12 Nameplate 13 Eyebolt 14 Fan cover 15 Fan cover washer 16 Fan cover fixing bolt 17 Fan fixing ring
30
Part Nr. Description
18 Fan 19 Non-drive end bearing cap bolt 20 V’Ring 21 Non-drive end bearing cap washer 22 Non-drive end endshield fixing
bolt 23 Non-drive end endshield washer 24 Non-drive end grease nipple 25 Non-drive end grease nipple cover 26 Non-drive enshield 27 Bearing cap 28 Non-drive bearing 29 Internal non-drive end bearing cap 30 Fan fixing key 31 Wound stator 32 Rotor / shaft assembly 33 Frame
Part Nr. Description
34 Shaft key 35 Internal drive end bearing cap 36 Drive end bearing 37 Drive endshield 38 Drive end grease nipple cover 39 Drive endshield washer 40 Pre-load spring 41 Drive end endshield fixing bolt 42 External drive end bearing cap 43 Drive end bearing cap washer 44 V’Ring 45 Drive end bearing cap fixing bolt 46 Drain plug 47 External non-drive end bearing
cap 48 Non drive end grease relief 49 Non-drive end grease relief
INSTALLATION AND MAINTENANCE MANUAL
FOR NEMA LOW VOLTAGE ELECTRIC MOTORS
THREE-PHASE MOTORS NEMA 56
Frames A56 - B56 - D56 - F56H and G56H
Part Nr. Description
1 Sticker 2 Terminal box cover fixing bolt 3 Terminal box cover 4 Grounding lug 5 Through bolt fastening nut 6 Non-drive endshield 7 Spring washer
Frames B48 - C48 - C56 - A56 - B56 - D56 - F56H - G56H
Part Nr. Description
8 Non-drive end bearing
9 Wound stator 10 Rotor / shaft assembly 11 Frame 12 Through bolt 13 Shaft key
SINGLE-PHASE MOTORS NEMA 56
Part Nr. Description
14 Fan 15 Drive end bearing fastening
washer 16 Drive end bearing 17 Drive endshield
Part Nr. Description
1 Sticker 2 Capacitor cover fixing bolt 3 Terminal box cover fixing bolt 4 Terminal box cover 5 Grounding lug 6 Through bolt fastening nut 7 Non-drive endshield 8 Spring washer 9 Non-drive and bearing
10 Non-drive and bearing fastening
washer
11 Stationary switch
Note: For F56H and G56H frame motors: 1) Part nr. 2 = 3 pieces; 2) Part nr. 15 and 16 = 2 pieces
Part Nr. Description
12 Stationary switch fastening bolt 13 Centrifugal switch 14 Rubber ring for lead passing hole
to capacitor 15 Capacitor cover 16 Capacitor 17 Wound stator 18 Rotor / shaft assembly 19 Frame 20 Through bolt 21 Shaft key 22 Fan
Part Nr. Description
23 Drive end bearing fastening
washer 24 Drive end bearing 25 Drive endshield 26 Overload thermal protector fixing
ring 27 Overload thermal protector
31
INSTALLA TION AND MAINTENANCE MANUAL FOR NEMA LOW VOL T AGE ELECTRIC MOTORS
NOTES:
32
WEG EXPORTADORA S.A.
Av . Prefeito Waldemar Grubba, 3000
89256-900 - Jaraguá do Sul - SC - Brazil
Phone: +55 (47) 372-4002 - Fax: +55(47) 372-4060
www .weg.com.br
Loading...