www.weg.net
Controls
Manual Motor Protectors - MPW100 Technical Data
Power Contact Ratings
TYPE MPW100-3-U075 MPW100-3-U090 MPW100-3-U100
Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 /
Current Setting Range [A] 55 - 75 70 - 90 80 - 100
Rated Thermal Current Ith [A] 75 90 100.00
Rated Insulation Voltage Ui
Acc. IEC; VDE 0660 [V] 690
Acc. UL; CSA [V] 600
Rated Operating Voltage Ue
Acc. IEC; VDE 0660 [V] 690
Acc. UL; CSA [V] 600
Rated Impulse Voltage Uimp
Acc. IEC60947-1 [kV] 6
Rated Operating Frequency [Hz] 50/60
Overvoltage Category III
Pollution Degree 3
Utilization Category
IEC 60947-2 (Motor Protector) A
IEC 60947-4-1 (Motor Starter) AC-3
Lifespan
Mechanical [ops.] 50,000
Electrical (Ie max.) [ops.] 25,000
Switching Rate (motor starts) AC-3 [ops/hr] 15
Ambient Temperature
Storage [oC (oF)] -50 to +80 (-58 to +176)
Operating [oC (oF)] -20 to +60 (-4 to +140)
Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)
Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30
Altitude
Up to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page 244)
Degree of protection IP20
Resistance to Shock
Acc. IEC 60068-2-27 [g] 15
Resistance to Vibration IEC 68-2
Protection against direct contact
Acc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proof
Phase Failure Sensitivity Protection Yes
Overload Protection Characteristics x Iu [A] 0.6 - 1
Magnetic Release x Iu [A] 13
Overload Trip Class 10
Total Power Loss Pv
At rated load operating temperature [W] 10 10 10
Weight [kg] 1.20
[lb] 3.00
Type of Terminal Flat Type
Screw Driver Allen #4
Terminal Capacity
Solid [mm2] Refer to table on page 243
Stranded [mm2]
Solid or Stranded [AWG]
Tightening Torque [N.m (lb.in)] 4.0 - 4.6 (35 - 55)
Mounting Position Any Position
60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102
CONTROLS
WEG Automation - Products and Solutions
233
www.weg.net
Controls
Manual Motor Protectors - MPW100 Technical Data
Power Contact Ratings
TYPE MPW100-3-U075 MPW100-3-U090 MPW100-3-U100
UL/CSA DATA
Rated Operational Current Ie [A] 75 90 100
Magnetic Release Current [A] 975 1170 1300
Max. Short Circuit Current
480V [kA] 50
600V [kA] 10
Motor Load, 1-phase
115V [HP] 5 71/2 10
230V [HP] 15 20 20
Motor Load, 3-phase
200V [HP] 20 25 30
230V [HP] 25 30 30
460V [HP] 50 60 75
575V [HP] 60 75 100
Max. Rated Current of Protection Device for Group Installation
Fuse or MCCB [A]
IEC DATA
Rated Operational Current Ie [A] 75 90 100
Magnetic Release Current [A] 975 1170 1300
Back-Up Fuses
gL/gG 220/240V [A] - - -
380/400V [A] - - -
415/440V [A] 200 200 200
500V [A] 160 160 160
660/690V [A] 125 160 160
Ultimate Short Circuit Breaking Capacity
Icu 220/240V [kA] 100 100 100
380/400V [kA] 75 75 75
415/440V [kA] 50 50 50
500V [kA] 12 12 12
660/690V [kA] 6 6 6
Rated Service Short Circuit Breaking Capacity
Ics 220/240V [kA] 100 100 100
380/400V [kA] 50 50 50
CONTROLS
415/440V [kA] 38 38 38
500V [kA] 9 9 9
660/690V [kA] 6 6 6
234 1-800-ASK-4WEG
Data is subject to change without notice.