INTRODUCTION
The WEG GPH series of Combination Soft Starters provides a complete system to start, run and
monitor the operation of your AC motor. This Quick Start Guide provides key information to start-up
and operate the GPH Combination Soft Starter. For more complete information on the Soft
Starter, please refer to the SSW04 Instruction Manual (5 – 30HP @ 230V and 10 – 75HP @ 460V)
or SSW03 Instruction Manual (50 – 150HP @ 230V and 100 – 300HP @ 460V) and the Wiring
Diagrams that are provided.
Before beginning the installation of the GPH, please review the documentation that has been shipped
in an envelope inside the GPH enclosure. If you contact the machine manufacturer, distributor, or
WEG Motors and Drives about this equipment, please refer to the following part numbers to help you
identify the exact product that you are using.
Model No. _________________ HP ______ Job No. _________________Serial No. ___________
The GPH series Combination Soft Starter is comprised of a WEG SSW-04 or SSW03 Soft Starter
(HP dependent), Circuit Breaker, Bypass Contactor with motor overload relay, Control Power
Transformer, Start and Stop Pushbuttons, Run and Trip Pilot Lights, control logic, Motor output
terminal block and optional remote Keypad.
INSTALLATION
Connect the incoming AC power to the Circuit Breaker (CB-101) located in the top right side of the
enclosure panel. The operator handle must be in the OFF position to open the front door of the
enclosure. Connect the ground wire to the ground terminal block (GND-101) located next to the
circuit breaker. Connect the motor cables to the output terminal block (TB-107) located on the lower
right side of the enclosure panel.
SET-UP
To simplify installation for the typical application, several parameters have already been set. As noted
on the label on the inside of the enclosure door, P22 and P23 are set for the current rating of the Soft
Starter and the input voltage, respectively. P21 is set based on NEC motor FLA by HP. P43 (ON) is
set for Bypass operation and P61 (OFF) for Starting and Stopping the unit via the terminal inputs
(Start/Stop PB) instead of the keypad. P53 (4) allows “three wire” start/stop via the Start and Stop
Pushbuttons on the enclosure door. The Start and Stop keys on the keypad are disabled.
The motor overload relay, mounted inside the enclosure, must be adjusted to the FLA (Full Load
Amperage) rating of the motor. The relay has been factory set in the position closest to the NEC
standard for that HP setting. Check the motor nameplate for the FLA rating, and adjust the setting if
your motor is different. For example, on a 50HP, 460 VAC motor, the typical FLA would be 60 Amps.
With a small screwdriver, adjust the rotary dial to the FLA of the motor being used. If not adjusted
properly, the motor overload relay will not function properly. When tripped, it results in an E08
External Fault trip on the Soft Start. There are four positions of the reset function. Default is M
(Manual) or H (Hand) depending on the HP of the GPH. This requires the overload to be manually
reset if tripped by pushing in the Trip tab. The overloads can be set to A (Auto) for automatic reset
after the overload cools down. The other two positions are either M-O or A-O (Auto-R and Hand-R).
When in the O or R position, the overload can be manually tripped when pressed. To change
positions, press in the tab before rotating to the new position.
Minimal set-up changes may be required to customize the GPH Combination Starter to meet the
specific needs of your application. These will be explained on the following page.
NOTE: To allow the changing of any parameter value, P00 must be changed to “ON”. 4/03