CSW SERIES – TECHNICAL DATA
CSW Series
FRACTIONAL HP
PURPOSE
GENERAL
EFFICIENCY
NEMA PREMIUM
CRUSHER® DUTYIEC
TRU-METRIC™
PUMP
MOTORS
DEFINITE
PURPOSE
ADD-ON™
MODIFICATIONS
Standards IEC/EN 60947-5-1, VDE 0660, NFC63140, UL 508, UL 50, CENELEC EN50007
Rated insulation voltage 660 Vac / Vdc
Degree of protection IP66 (IEC/EN 60529)
Degree of protection - Terminals IP2X (IEC/EN 60529)
UL ratings Type 1, 2, 3, 3R, 35, 4, 4X, 5,12, 12K e 13
Electrical ratings
Conventional thermal current Ith = 10A (IEC 947-5-1)
Utilization category AC-15 (V) (A)
24 10
48 10
60 10
110 6
230 3
400 2
500 1,5
600 1,2
Utilization category DC-13 (V) (A)
24 2,5
48 1,4
60 1
110 0,55
230 0,27
400 0,2
600 0,1
UL / CSA ratings AC / Heavy Duty (A600)
DC / Standard Duty (Q600)
Contacts resistance ≤ 25mΩ (IEC/EN 60255)
Short circuit protection 16A gL/gG fuse or MPW25-10
Electrical shock protection Class II
Rated impulse voltage 2,5 kV (IEC 947-5-1)
Terminal capacity 1 or 2 x (0.5 - 2.5mm2) / 1 or 2 x 14-20AWG
Temperature range -25ºC to 70ºC (77ºF to 158ºF)
Shock resitance No damage or disassembling at 100g for all devices
According to MIL 202 B
method 202A ≤ ½ sinusoid 11ms
Vibration resistance 16g with frequency range from 40 to 500Hz
IEC/EN 6068-2-6 and max shifting 0,75mm (peak-to-peak)
Mechanical endurance
Pushbuttons 3 x 10
Selector Switches 1 x 10
Emergency-Stop 3 x 10
6
6
5
Maximum number of contacts AF3 Flange AF5 Flange
Pushbuttons (BF) Max. 6 Max. 10
Selector Switches Max. 4 Max. 8
Pushbuttons (BC, BFI, BSI, BCI, BEG, BEY) Max. 4 Max. 8
MOTOR
DRIVES &
CONTROLS
CONTROLS
TECHNICAL DATA
SOFT STARTERS
BIDL Block Ratings
Rated operational voltage 0,85 ~1,10 x V
Rated current 20 mA
Rated impulse voltage 2,5 kV (IEC 947-5-1)
Temperature range - 25 to 70°C (-73ºF to 158ºF)
Life 100.000 h
Luminosity Red: 70 mcd
Yellow: 115 mcd
White: 275 mcd
Blue: 64 mcd
Green: 150 mcd
D-60
07
05