11.8.6 Torque Current Limitation ............................................................................................11-2 0
11.8.7 Supervision of Motor Real Speed ................................................................................ 11-2 1
11.8.8 DC Link Regulator .........................................................................................................11-22
11.9 START-UP IN THE VECTOR MODES SENSORLESS .............................................................11- 2 4
12 FUNCTIONS COMMON TO ALL THE CONTROL MODES ............... 12-1
12 .1 R A MPS ......................................................................................................................................... 12-1
19.11 HVAC FUNCTIONS LOGICAL STATUS ................................................................................. 19-38
19.12 VERSION OF THE HVAC APPLICATION ............................................................................... 19-39
Summary
Quick Parameter Reference, Faults and Alarms
QUICK PARAMETER REFERENCE, FAULTS AND ALARMS
Param.Function
P0000 Access to Parameters0 to 9999 0 5-1
P0001 Speed Reference0 to 18000 rpmroREAD16 -1
P0002 Motor Speed0 to 18000 rpmroREAD16 -1
P0003 Motor Current0.0 to 4500.0 AroREAD16-1
P0004 DC Link Voltage (Ud)0 to 2000 VroREAD16-2
P0005 Motor Frequency0.0 to 1020.0 HzroREAD16-2
P0006 VFD Status0 = Ready
P0007 Motor Voltage0 to 2000 VroREAD16-3
P0009 Motor Torque-1000.0 to 1000.0 %roREAD16-3
P0 010 Output Power0.0 to 6553.5 kWroREAD16-4
P0 0 11 Output Cos φ0.00 to 1.00 roREAD, I/O 16-4
P0 012 DI8 to DI1 StatusBit 0 = DI1
P0 013 DO5 to DO1 StatusBit 0 = DO1
P0 014 AO1 Value0.00 to 100.00 %roREAD, I/O 13-6
P0 015 AO2 Value0.00 to 100.00 %roREAD, I/O 13-6
P0 018 AI1 Value-100.00 to 100.00 %roREAD, I/O 13-1
P0 019 AI2 Value-100.00 to 100.00 %roREAD, I/O 13-1
P0020 AI3 Value-100.00 to 100.00 %roREAD, I/O 13-1
P0022 Frequency Input3.0 to 6500.0 HzroREAD, I/O 13-23
P0023 Software Version0.00 to 655.35 roREAD6-1
P0028 Accessories Config.0000h to FFFFh roREAD6-2
P0029 Power Hardware ConfigBit 0 to 5 = Rated Current
P0030 IGBTs Temperature-20.0 to 150.0 °CroREAD15-4
P0034 Internal Air Temp.-20.0 to 150.0 °CroREAD15- 4
P0036 Fan Heatsink Speed0 to 15000 rpmroREAD16-5
P0037 Motor Overload Status0 to 100 %roREAD16-5
P0042 Powered Time0 to 65535 hroREAD16-6
P0043 Enabled Time0.0 to 6553.5 hroREAD16-6
P0044 kWh Output Energy0 to 65535 kWhroREAD16-6
P0045 Enabled Fan Time0 to 65535 hroREAD16-7
P0048 Present Alarm0 to 999 roREAD16 -7
P0049 Present Fault0 to 999 roREAD16-7
P0050 Last Fault0 to 999 roREAD16-8
P0054 Second Fault0 to 999 roREAD16-8
Adjustable
Range
1 = Run
2 = Undervoltage
3 = Fault
4 = Self-Tuning
5 = Configuration
6 = DC-Braking
7 = STO
8 = Fire Mode
9 = Bypass
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Bit 6 and 7 = Rated Voltage
Bit 8 = RFI Filter
Bit 9 = Safety Relay
Bit 10 = (0)24 V/(1)DC Link
Bit 11 = Always 0
Bit 12 = Dyn. Brak. IGBT
Bit 13 = Special
Bit 14 and 15 = Reserved
Factory
Setting
User
Setting
Propr.Groups Pág.
roREAD16-2
roREAD, I/O 13-9
roREAD, I/O 13-14
roREAD6-2
0
CFW701 | 0-1
Quick Parameter Reference, Faults and Alarms
0
Param.Function
Adjustable
Range
Factory
Setting
User
Setting
Propr.Groups Pág.
P0058 Third Fault0 to 999 roREAD16- 8
P0062 Fourth Fault0 to 999 roREAD16-8
P0066 Fifth Fault0 to 999 roREAD16- 8
P0090 Current At Last Fault0.0 to 4500.0 AroREAD16 -8
P0091 DC Link At Last Fault0 to 2000 VroREAD16-8
P0092 Speed At Last Fault0 to 18000 rpmroREAD16-9
P0093 Reference Last Fault0 to 18000 rpmroREAD16 -9
P0094 Frequency Last Fault0.0 to 1020.0 HzroREAD16-9
P0095 Motor Volt. Last Fault0 to 2000 VroREAD16-9
P0096 DIx Status Last FaultBit 0 = DI1
roREAD16 -10
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
P0097 DOx Status Last FaultBit 0 = DO1
roREAD16 -10
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
P010 0 Acceleration Time0.0 to 999.0 s20.0 sBASIC12-1
P0101 Deceleration Time0.0 to 999.0 s20.0 sBASIC12-1
P010 2 Acceleration Time 20.0 to 999.0 s20.0 s12-1
P010 3 Deceleration Time 20.0 to 999.0 s20.0 s12-1
P010 4 Ramp Type0 = Linear
P0121 Keypad Reference0 to 18000 rpm90 rpm12-4
P0122 JOG/JOG + Reference0 to 18000 rpm150 (125) rpm12-4
P0123 JOG - Reference0 to 18000 rpm150 (125) rpmVector12-5
P0132 Max. Overspeed Level0 to 100 %10 %cfg12- 5
P0133 Minimum Speed0 to 18000 rpm90 (75) rpmBASIC12-6
P0134 Maximum Speed0 to 18000 rpm1800 (1500) rpmBASIC12-6
P0135 Max. Output Current0.2 to 2xI
nom-HD
1.5xI
nom-HD
V/f, V VWBASIC9-6
P0136 Manual Torque Boost0 to 9 1 V/fBASIC9-2
P0137 Autom. Torque Boost0.00 to 1.00 0.00 V/f9-2
P0138 Slip Compensation-10.0 to 10.0 %0.0 %V/f9-3
P0139 Output Current Filter0.0 to 16.0 s0.2 sV/f, V VW9-4
P0142 Max. Output Voltage0.0 to 100.0 %10 0.0 %cfg, Adj9-5
P0143 Interm. Output Voltage0.0 to 100.0 %50.0 %cfg, Adj9-5
P0144 3 Hz Output Voltage0.0 to 100.0 %8.0 %cfg, Adj9-5
P0145 Field Weakening Speed0 to 18000 rpm1800 r pmcfg, Adj9-5
P0146 Intermediate Speed0 to 18000 rpm900 rpmcfg, Adj9-5
P0150 V/f DC Regulation Type0 = Ramp Hold
1 = Ramp Accel.
0cfg, V/f,
VVW
9-10
P0151 V/f DC Regulation Level 339 to 1000 V800 VV/f, V VW9-10
P0152 DC Link Regul. P Gain0.00 to 9.99 1.50 V/f, V VW9 -11
P0153 Dyn. Braking Level339 to 1000 V748 V14-1
P0156 100 % Speed Overload
Current
P0157 50 % Speed Overload
Current
P0158 5 % Speed Overload Current 0.1 to 1.5xI
0.1 to 1.5xI
0.1 to 1.5xI
nom-ND
nom-ND
nom-ND
1.0 5xI
0.9xI
0.65xI
nom-ND
nom-ND
nom-ND
15- 4
15- 4
15- 4
0-2 | CFW701
Quick Parameter Reference, Faults and Alarms
Param.Function
P0159 Motor Thermal Class0 = Class 5
P0160 Speed Regul. Config.0 = Normal
P0161 Speed Prop. Gain0.0 to 63.9 7.4 Vector11-12
P0162 Speed Integral Gain0.000 to 9.999 0.023 Vector11-12
P0163 LOC Reference Offset-999 to 999 0 Vector11-13
P0164 REM Reference Offset-999 to 999 0 Vector11-13
P0165 Speed Filter0.012 to 1.000 s0.012 sVector11-13
P0166 Speed Diff. Gain0.00 to 7.99 0.00 Vector11-14
P0167 Current Prop. Gain0.00 to 1.99 0.50 Vector11-14
P0168 Current Integral Gain0.000 to 1.999 0.010 Vector11-14
P0169 Max. + Torque Curr.0.0 to 350.0 %125.0 %Vector11-20
P0175 Flux Proport. Gain0.0 to 31.9 2.0 Vector11-14
P0176 Flux Integral Gain0.000 to 9.999 0.020 Vector11-15
P0178 Rated Flux0 to 120 %100 %Vector11-15
P0180 Iq* After I/f0 to 350 %10 %Sless11-16
P0182 Speed for I/f Activ.0 to 90 rpm18 rpmSless11-16
P0183 Current in I/f Mode0 to 9 1 Sless11-16
P0184 DC Link Regul. Mode0 = With losses
P0185 DC Link Regul. Level339 to 1000 V800 VVector11- 2 3
P0186 DC Link Prop. Gain0.0 to 63.9 26.0 Vector11- 2 3
P0187 DC Link Integral Gain0.000 to 9.999 0.010Vector11- 2 3
P0190 Max. Output Voltage0 to 600 V440 VVector11-15
P0200 Password0 = Inactive
P0202 Control Type0 = V/f 60 Hz
P0204 Load/Save Parameters0 = Not Used
P0205 Main Display Parameter Sel. 0 to 1199 2 HMI5-3
P0206 Secondary Display
Parameter Sel.
P0208 Main Display Scale Factor0.1 to 1000.0 %100.0 %HMI5-3
Adjustable
Range
1 = Class 10
2 = Class 15
3 = Class 20
4 = Class 25
5 = Class 30
6 = Class 35
7 = Class 40
8 = Class 45
1 = Saturated
1 = Without losses
2 = Enab/Disab DIx
1 = Active
2 = Change Pass.
1 = V/f 50 Hz
2 = V/f Adjustable
3 = V V W
4 = Sensorless
1 = Not Used
2 = Reset P0045
3 = Reset P0043
4 = Reset P0044
5 = Load 60 Hz
6 = Load 50 Hz
7 = Load User 1
8 = Load User 2
9 = Save User 1
10 = Save User 2
0 to 1199 3HMI5-3
Factory
Setting
1cfg15-5
0cfg, Vector11-12
1cfg, Vector11- 2 2
1 HMI5-2
0cfg9-5
0cfg7-1
User
Setting
Propr.Groups Pág.
0
CFW701 | 0-3
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0209 Main Display Eng. Unit0 = None
P0210 Main Display Decimal Point0 = wxyz
P0 211 Secondary Display Scale
Factor
P0 212 Secondary Display Decimal
Point
P0216 HMI Backlighting0 to 15 15 HMI5-6
Adjustable
Range
1 = V
2 = A
3 = rpm
4 = s
5 = ms
6 = None
7 = m
8 = None
9 = None
10 = %
11 = °C
12 = None
13 = Hz
14 = None
15 = h
16 = W
17 = kW
18 = None
19 = None
20 = min
21 = °F
22 = bar
23 = mbar
24 = psi
25 = Pa
26 = kPa
27 = MPa
28 = mwc
29 = mca
30 = gal
31 = l
32 = in
33 = ft
34 = m³
35 = ft³
36 = gal/s
37 = gal/min
38 = gal/h
39 = l/s
40 = l/min
41 = l/h
42 = m/s
43 = m/min
44 = m/h
45 = ft/s
46 = ft/min
47 = ft/h
48 = m³/s
49 = m³/min
50 = m³/h
51 = ft³/s
52 = ft³/min
53 = ft³/h
54 = As per P0510
55 = As per P0512
56 = As per P0514
57 = As per P0516
1 = wxy.z
2 = wx.yz
3 = w.xyz
4 = As per P0511
5 = As per P0513
6 = As per P0515
7 = As per P0517
0.1 to 1000.0 %100.0 %HMI5-3
See options in P02101HMI5-4
Factory
Setting
3HMI5-5
0HMI5-4
User
Setting
Propr.Groups Pág.
0-4 | CFW701
Quick Parameter Reference, Faults and Alarms
Param.Function
P0217 Zero Speed Disable0 = Inactive
P0218 Zero Speed Dis. Out0 = Ref. or Speed
P0219 Zero Speed Time0 to 999 s0 s12-8
P0220 LOC/REM Selection Src0 = Always LOC
P0221 LOC Reference Sel.0 = HMI
P0222 REM Reference Sel.See options in P02211cfgI/O13-24
P0223 LOC FWD/REV Selection0 = Forward
P0224 LOC Run/Stop Sel.0 = I,O Keys
P0225 LOC JOG Selection0 = Disable
P0226 REM FWD/REV Sel.See options in P02234cfgI/O13-25
P0227 REM Run/Stop Sel.See options in P02241cfgI/O13-25
P0228 REM JOG SelectionSee options in P02252cfgI/O13-26
P0229 Stop Mode Selection0 = Ramp to Stop
P0230 Dead Zone (AIs)0 = Inactive
P0231 AI1 Signal Function0 = Speed Ref.
P0232 AI1 Gain0.000 to 9.999 1.000 I/O13-3
P0233 AI1 Signal Type0 = 0 to 10 V / 20 mA
P0234 AI1 Off set-100.00 to 100.00 %0.00 %I/O13-3
P0235 AI1 Filter0.00 to 16.00 s0 .15 sI/O13-4
P0236 AI2 Signal FunctionSee options in P02318cfgI/O13-2
Adjustable
Range
1 = Active (N* and N)
2 = Active (N*)
1 = Reference
1 = Always REM
2 = LR Key LOC
3 = LR Key REM
4 = DIx
5 = Serial LOC
6 = Serial REM
7 = SoftPLC LOC
8 = SoftPLC REM
1 = AI1
2 = AI2
3 = AI3
4 = Sum AIs > 0
5 = Sum AIs
6 = Serial
7 = SoftPLC
1 = No Ramp Ref.
2 = Max. Torque Cur
3 = SoftPLC
4 = PTC
5 = Main PID Feedback 1
6 = Main PID Feedback 2
7 = Main PID Feedback 3
8 = External PID 1 Feedback
9 = External PID 2 Feedback
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
4 = -10 to +10 V
Factory
Setting
0cfg12-7
012-7
2cfgI/O13-24
0cfgI/O13-24
2cfgI/O13-25
0cfgI/O13-25
1cfgI/O13-2 6
0cfg13-26
0I/O13-1
5cfgI/O13-2
0cfgI/O13-5
User
Setting
Propr.Groups Pág.
0
CFW701 | 0-5
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0237 AI2 Gain0.000 to 9.999 1.000 I/O13-3
P0238 AI2 Signal TypeSee options in P02330cfgI/O13- 5
P0239 AI2 Offset-100.00 to 100.00 %0.00 %I/O13-3
P0240 AI2 Filter0.00 to 16.00 s0.15 sI/O13-4
P0 241 AI3 Signal FunctionSee options in P02319cfgI/O13-2
P0242 AI3 Gain0.000 to 9.999 1.000 I/O13- 3
P0243 AI3 Signal Type0 = 0 to 20mA
P0244 AI3 Offset-100.00 to 100.00 % 0.00 % I/O13- 3
P0245 AI3 Filter0.00 to 16.00 s0.15 sI/O13-4
P0246 Frequency Input
Configuration
P0 251 AO1 Function0 = Speed Ref.
P0252 AO1 Gain0.000 to 9.999 1.000 I/O13-7
P0253 AO1 Signal Type0 = 0 to 10 V / 20 mA
P0254 AO2 FunctionSee options in P025117I/O13-6
P0255 AO2 Gain0.000 to 9.999 1.000 I/O13-7
P0256 AO2 Signal TypeSee options in P02530cfgI/O13-8
P0263 DI1 Function0 = Not Used
P0264 DI2 FunctionSee options in P02634cfgI/O13 -10
P0265 DI3 FunctionSee options in P02630cfgI/O13 -10
P0266 DI4 FunctionSee options in P026320cfgI/O13 -10
P0267 DI5 FunctionSee options in P026321cfgI/O13 -10
P0268 DI6 FunctionSee options in P026322cfgI/O13 -10
Adjustable
Range
1 = 4 to 20 mA
2 = 20 to 0 mA
3 = 20 to 4 mA
0 = Off
1 = DI3
2 = DI4
1 = Total Ref.
2 = Real Speed
3 = Torque Cur. Ref
4 = Torque Current
5 = Output Current
6 = Active Current
7 = Output Power
8 = Torque Cur. > 0
9 = Motor Torque
10 = SoftPLC
11 = PTC
12 = Motor Ixt
13 = P0696 Value
14 = P0697 Value
15 = Id* Current
16 = External PID 1 Output
17 = External PID 2 Output
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
1 = Run/Stop
2 = General Enable
3 = Fast Stop
4 = FWD/REV
5 = LOC/REM
6 = JOG
7 = SoftPLC
8 = Ramp 2
9 = Speed/Torque
10 = JOG+
11 = JOG12 = No Ext. Alarm
13 = No Ext. Fault
14 = Reset
15 = Disab.FlyStart
16 = DC Link Regul.
17 = Progr. Off
18 = Load User 1
19 = Load User 2
20 = Main PID Aut/Man
21 = External PID 1 Aut/Man
22 = External PID 2 Aut/Man
23 = Bypass Mode
24 = Fire Mode
Factory
Setting
0cfgI/O13-5
0cfg13-23
16I/O13-6
0cfgI/O13-8
1cfgI/O13 -10
User
Setting
Propr.Groups Pág.
0-6 | CFW701
Quick Parameter Reference, Faults and Alarms
Param.Function
P0269 DI7 FunctionSee options in P02630cfgI/O13 -10
P0270 DI8 FunctionSee options in P02630cfgI/O13-10
P0275 DO1 Function (RL1)0 = Not Used
P0276 DO2 Function (RL2)See options in P027524cfgI/O13 -16
P0277 DO3 FunctionSee options in P02750cfgI/O13 -16
P0278 DO4 FunctionSee options in P02750cfgI/O13 -16
P0279 DO5 FunctionSee options in P02750cfgI/O13 -16
P0281 Fx Frequency0.0 to 300.0 Hz4.0 Hz13-21
P0282 Fx Hysteresis0.0 to 15.0 Hz2.0 Hz13-21
P0287 Nx/Ny Hysteresis0 to 900 rpm18 (15) rpm13-21
P0288 Nx Speed0 to 18000 rpm120 (100) rpm13-21
P0289 Ny Speed0 to 18000 rpm1800 (1500) rpm13-21
P0290 Ix Current0 to 2xI
P0291 Zero Speed 0 to 18000 rpm18 (15) rpm13-22
P0292 N = N* Band0 to 18000 rpm18 (15) rpm13-22
P0293 Tx To r q u e0 to 200 %100 %13-22
P0294 Hx Time0 to 6553 h4320 h13-23
Adjustable
Range
1 = N* > Nx
2 = N > Nx
3 = N < Ny
4 = N = N*
5 = Zero Speed
6 = Is > Ix
7 = Is < Ix
8 = Torque > Tx
9 = Torque < Tx
10 = Remote
11 = Run
12 = Ready
13 = No Fault
14 = No F0070
15 = No F0071
16 = No F0006/21/22
17 = No F0051
18 = No F0072
19 = 4-20 mA OK
20 = P0695 Value
21 = Forward
22 = Ride-Through
23 = Pre-Charge OK
24 = Fault
25 = Enabled Time > Hx
26 = SoftPLC
27 = N>Nx/Nt>Nx
28 = F > Fx (1)
29 = F > Fx (2)
30 = STO
31 = No F0160
32 = No Alarm
33 = No Fault/Alarm
34 = Dry Pump Alarm/Fault
35 = Broken Belt Alarm/Fault
36 = Filter Mainten. Alarm/
Fault
37 = Sleep Mode
38 = Not Used
39 = Drive Bypass Contactor
40 = Mains Bypass
Contactor
41 = Fire Mode
42 = Self-Tuning
nom-ND
Factory
Setting
11cfgI/O13 -16
1.0 x I
nom-ND
User
Setting
Propr.Groups Pág.
13-22
0
CFW701 | 0-7
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0295 ND/HD VFD Rated Curr.0 = 2 A / 2 A
P0296 Line Rated Voltage0 = 200 / 240 V
P0297 Switching Frequency0 = 1.25 kHz
P0298 Application0 = Normal Duty
P0299 DC-Braking Start Time0.0 to 15.0 s0.0 sV/f, V V W,
P0300 DC-Braking Stop Time0.0 to 15.0 s0.0 sV/f, V V W,
P0301 DC-Braking Speed0 to 450 rpm30 rpmV/f, VV W,
P0302 DC-Braking Voltage0.0 to 10.0 %2.0 %V/f, V VW12-18
P0303 Skip Speed 10 to 18000 rpm600 rpm12-19
Adjustable
Range
1 = 3.6 A / 3.6 A
2 = 5 A / 5 A
3 = 6 A / 5 A
4 = 7 A / 5.5 A
5 = 7 A / 7 A
6 = 10 A / 8 A
7 = 10 A / 10 A
8 = 13 A / 11 A
9 = 13.5 A / 11 A
10 = 16 A / 13 A
11 = 17 A / 13.5 A
12 = 24 A / 19 A
13 = 24 A / 20 A
14 = 28 A / 24 A
15 = 31 A / 25 A
16 = 33.5 A / 28 A
17 = 38 A / 33 A
18 = 45 A / 36 A
19 = 45 A / 38 A
20 = 54 A / 45 A
21 = 58.5 A / 47 A
22 = 70 A / 56 A
23 = 70.5 A / 61 A
24 = 86 A / 70 A
25 = 88 A / 73 A
26 = 105 A / 86 A
27 = 105 A / 88 A
28 = 142 A / 115 A
29 = 180 A / 142 A
30 = 211 A / 180 A
31 = 2.9 A / 2.7 A
32 = 4.2 A / 3.8 A
33 = 7 A / 6.5 A
34 = 10 A / 9 A
35 = 12 A / 10 A
36 = 17 A / 17 A
37 = 22 A / 19 A
38 = 27 A / 22 A
39 = 32 A / 27 A
40 = 44 A / 36 A
41 = 53 A / 44 A
42 = 63 A / 53 A
43 = 80 A / 66 A
44 = 107 A / 90 A
45 = 125 A / 107 A
46 = 150 A / 122 A
1 = 380 V
2 = 400 / 415 V
3 = 440 / 460 V
4 = 480 V
5 = 500 / 525 V
6 = 550 / 575 V
7 = 600 V
1 = 2.5 kHz
2 = 5.0 kHz
3 = 10.0 kHz
4 = 2.0 kHz
1 = Heavy Duty
Factory
Setting
According to
inverter model
According to
inverter model
0cfg6-8
User
Setting
Propr.Groups Pág.
roREAD6-6
cfg6-7
cfg6-7
Sless
Sless
Sless
12-16
12-16
12-18
0-8 | CFW701
Quick Parameter Reference, Faults and Alarms
Param.Function
P0304 Skip Speed 20 to 18000 rpm900 rpm12-19
P0305 Skip Speed 30 to 18000 rpm120 0 r pm12-19
P0306 Skip Band0 to 750 rpm0 rpm12-19
P0308 Serial Address1 to 247 1 NET17-1
P0310 Serial Baud Rate0 = 9600 bits/s
P0 311 Serial Bytes Config.0 = 8 bits, no, 1
P0 312 Serial Protocol2 = Modbus RTU
P0 313 Comm. Error Action0 = Off
P0 314 Serial Watchdog0.0 to 999.0 s0.0 sNET17-1
P0316 Serial Interf. Status0 = Off
P0317 Oriented Start-up0 = No
P0 318 Copy Function MMF0 = Off
P0320 FlyStart/Ride-Through0 = Off
P0321 DC Link Power Loss178 to 770 V505 VVector12-14
P0322 DC Link Ride-Through178 to 770 V490 VVector12-14
P0323 DC Link Power Back178 to 770 V535 VVector12-14
P0325 Ride-Through P Gain0.0 to 63.9 22.8 Vector12-15
P0326 Ride-Through I Gain0.000 to 9.999 0.12 8 Vector12-15
P0327 F.S. I/f Current Ramp0.000 to 1.000 s0.070 sSless12-10
P0328 Flying Start Filter0.000 to 1.000 s0.085 sSless12-10
P0329 Frequency Ramp F. S.2.0 to 50.0 20.0Sless12-10
P0331 Voltage Ramp0.2 to 60.0 s2.0 sV/f, V VW12-12
P0332 Dead Time0.1 to 10.0 s1.0 sV/f, V VW12-12
P0340 Auto-reset Time0 to 255 s0 s15- 8
P0 3 41 AIPTC Configuration0 = Off
1 = Ramp Stop
2 = General Disab.
3 = Go to LOC
4 = LOC Keep Enab.
5 = Cause Fault
1 = On
2 = Watchdog Error
1 = Yes
1 = VFD → MMF
2 = MMF → VFD
3 = Sync VFD → MMF
4 = Format MMF
5 = Copy SoftPLC Program.
6 = SoftPLC Program Save
1 = Flying Start
2 = FS/RT
3 = Ride-Through
1 = Fault/Alarm
2 = Fault
3 = Alarm
1 = On
1 = Decel.
1 = Fault/Alarm
2 = Fault
3 = Alarm
Factory
Setting
1NET17-1
1NET17-1
2NET17-1
1NET17-2
0cfgSTARTUP7-2
0cfg7- 2
0cfg12- 8
0cfgI/O15-8
1cfg15-9
1cfg, V/f,
1cfg15-9
User
Setting
Propr.Groups Pág.
roNET17-1
VVW
9-6
0
CFW701 | 0-9
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0350 IGBTs Overload Conf.0 = F, w/ SF rd.
P0 3 51 Motor Overtemp. Conf.0 = Off
P0352 Fan Control Config.0 = HS-OFF, Int-OFF
P0353 IGBTs/Air Overtemp. Cfg0 = HS-F/A, Air-F/A
P0354 Fan Speed Config.0 = Inactive
P0355 F0185 Fault Config.0 = Off
P0356 Dead Time Compens.0 = Off
P0357 Line Phase Loss Time0 to 60 s3 s15-14
P0360 Speed Hysteresis 0.0 to 100.0 %10.0 %Vector11-21
P0361 Time with Speed Different
from Reference
P0372 DC-Braking Curr. Sless0.0 to 90.0 %40.0 %Sless12 -18
P0397 Slip Compens. Regen.0 = Off
P0398 Motor Service Factor1.00 to 1.50 1.00 cfgMOTOR11-7
P0399 Motor Rated Eff.50.0 to 99.9 %67. 0 %cfg, V VWMOTOR10-3
P0400 Motor Rated Voltage0 to 600 V440 VcfgMOTOR11- 8
P0401 Motor Rated Current0 to 1.3xI
P0402 Motor Rated Speed0 to 18000 rpm1750 (1458) rpmcfgMOTOR11- 8
P0403 Motor Rated Frequency0 to 300 Hz60 (50) HzcfgMOTOR11- 9
Adjustable
Range
1 = F/A, w/ SF rd.
2 = F, no SF rd.
3 = F/A, no SF rd.
P0407 Motor Rated Power Fac0.50 to 0.99 0.68 cfg, V/f,
VVW
P0408 Run Self-Tuning0 = No
1 = No Rotation
2 = Run for I
m
0cfg, VV W,
Vector
P0409 Stator Resistance0.000 to 9.999 Ω0.000 Ωcfg, V VW,
MOTOR10-4
19-7
MOTOR 11-17
MOTOR 11-18
Vector
P0 410 Magnetization Current0 to 1.25xI
nom-ND
I
nom-ND
MOTOR 11-18
P0 411 Leakage Inductance0.00 to 99.99 mH0.00 mHcfg, Vector MOTOR 11-19
P0 412 Tr Time Constant0.000 to 9.999 s0.000 sVectorMOTOR 11-19
P0 413 Tm Time Constant0.00 to 99.99 s0.00 sVectorMOTOR 11- 2 0
0
CFW701 | 0-11
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0 510 Ind. Eng. Unit 10 = None
P0 511 Ind. Decimal Point 10 = wxyz
P0 512 Ind. Eng. Unit 2See options in P051011HMI5-9
P0 513 Ind. Decimal Point 20 = wxyz
P0 514 Ind. Eng. Unit 3See options in P051010HMI5 -11
P0 515 Ind. Decimal Point 30 = wxyz
P0 516 Ind. Eng. Unit 4See options in P051013HMI5-13
Adjustable
Range
1 = V
2 = A
3 = rpm
4 = s
5 = ms
6 = None
7 = m
8 = None
9 = None
10 = %
11 = °C
12 = None
13 = Hz
14 = None
15 = h
16 = W
17 = kW
18 = None
19 = None
20 = min
21 = °F
22 = bar
23 = mbar
24 = psi
25 = Pa
26 = kPa
27 = MPa
28 = mwc
29 = mca
30 = gal
31 = l
32 = in
33 = ft
34 = m³
35 = ft³
36 = gal/s
37 = gal/min
38 = gal/h
39 = l/s
40 = l/min
41 = l/h
42 = m/s
43 = m/min
44 = m/h
45 = ft/s
46 = ft/min
47 = ft/h
48 = m³/s
49 = m³/min
50 = m³/h
51 = ft³/s
52 = ft³/min
53 = ft³/h
1 = wxy.z
2 = wx.yz
3 = w.xyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
Factory
Setting
22HMI5-7
1HMI5-8
1HMI5 -10
1HMI5 -12
User
Setting
Propr.Groups Pág.
0-12 | CFW701
Quick Parameter Reference, Faults and Alarms
Param.Function
P0517 Ind. Decimal Point 40 = wxyz
P0579 Reference to Fire Mode0 to 18000 rpm1800 (1500) rpmHVAC19-2
P0580 Fire Mode Configuration0 = Disabled
P0581 Fire Mode PID Setpoint-32768 to 32767 0 HVAC19-3
P0582 Auto-reset Configuration0 = Limited
P0583 Bypass Mode Configuration 0 = Off
P0584 Bypass Contactor Time0.00 to 300.00 s0.30 sHVAC19-7
P0585 Short Cycle Protection
Config.
P0586 Minimum RUN Time0.00 to 650.00 s5.00 sHVAC19-9
P0587 Minimum STOP Time0.00 to 650.00 s5.00 sHVAC19-9
P0588 Maximum Torque Level 0 to 85 %0 %cfg, V/fHVAC19- 8
P0589 Energy Saving Min. Mag.40 to 80 %40 %cfg, V/fHVAC19-8
P0590 Energy Saving Min. Speed0 to 18000 rpm600 (525) rpmcfg, V/fHVAC19-8
P0591 Energy Saving Histeresis0 to 30 %10 %cfg, V/fHVAC19-8
P0680 Logical StatusBit 0 = Not Used
P0681 Speed in 13 bits-32768 to 32767 roREAD,
P0682 Serial Control WordBit 0 = Ramp Enable
P0683 Serial Speed Ref.-32768 to 32767 roREAD,
P0695 DOx ValueBit 0 = DO1
P0696 AOx Value 1-32768 to 32767 0 NET17-2
P0697 AOx Value 2-32768 to 32767 0 NET17- 2
P0760 BACnet Dev Inst High0 to 419 0 NET17-1
P0761 BACnet Dev Inst Low0 to 9999 0 NET17-1
P0762 Max. Number of Master0 to 127 127 NET17-1
P0763 MS/TP Max. Info Frame1 to 65535 1 NET17-1
Bit 1 = Run Command
Bit 2 = Fire Mode
Bit 3 = Bypass
Bit 4 = Quick Stop ON
Bit 5 = 2nd Ramp
Bit 6 = Config. Mode
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Forward
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Subvoltage
Bit 14 = Not Used
Bit 15 = Fault
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2nd Ramp
Bit 6 = Quick Stop
Bit 7 = Fault Reset
Bit 8 to 12 = Reserved
Bit 13 = Internal PID
Bit 14 = External PID 1
Bit 15 = External PID 2
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Factory
Setting
1HMI5 -14
0cfgHVAC19-3
0cfgHVAC19-3
0cfgHVAC19-6
0cfgHVAC19-9
Bit 4NET17-2
User
Setting
Propr.Groups Pág.
roRE AD,
NET
NET
roRE AD,
NET
NET
17-2
17-2
17-1
17-2
17-1
17-2
0
CFW701 | 0-13
Quick Parameter Reference, Faults and Alarms
0
Param.Function
P0764 I-AM Msg Transmition0 = Power Up
P0765 Token RX Qtde0 to 65535 roREAD,
P1000 SoftPLC Status0 = No Application
P1001 SoftPLC Command0 = Stop Application
P1002 Scan Cycle Time0.0 to 999.9 msroRE AD,
P1003 SoftPLC Appl. Sel.0 = User
P1010 Version of the HVAC
Application
P10 11 Main PID Aut. Setpoint-32768 to 32767 0 HVAC19 -14
P1012 SoftPLC Parameter 3-32768 to 32767 0 HVAC18-2
P1013 SoftPLC Parameter 4-32768 to 32767 0 HVAC18-2
P1014 Main PID Man. Setpoint0.0 to 100.0 %0.0 %HVAC19-14
P1015 Main PID Process Variable-32768 to 32767 roRE AD,
P1016 MainPID Output0.0 to 100.0 %roRE AD,
P1017 MainPID Act. Control0 = Disable PID
P1018 Main PID Operation Mode0 = AlwaysAutomatic
P1019 Main PID Sampling Time0.10 to 60.00 s0 .1 0 sHVAC19 -16
P1020 Main PIDP. Gain0.000 to 32.767 1.000 HVAC19 -17
P1021 Main PIDI. Gain0.000 to 32.767 0.430 HVAC19 -17
P102 2 Main PIDD. Gain0.000 to 32.767 0.000 HVAC19 -17
P1023 Main PID Output Min. Value 0.0 to 100.0 %0.0 %HVAC19 -17
P1024 Main PID Output Max. Value 0.0 to 100.0 %100.0 %HVAC19 -18
P1025 SoftPLC Parameter 16-32768 to 32767 0 HVAC18-2
P1026 Main PID Feedback Conf.0 = Sum Feed. 1, 2 and 3
P1027 Main PID Min. Feedback-32768 to 32767 0 HVAC19-18
P1028 Main PID Max. Feedback-32768 to 32767 1000 H VAC19-19
P102 9 SoftPLC Parameter 20-32768 to 32767 0 HVAC18-2
P1030 Main PID Fdbck Alarms
Conf.
P1031 M. PID Fdbck Alarm Low V.-32768 to 32767 50 HVAC19 -20
P1032 M. PID Fdbck Alarm Low T.0.00 to 650.00 s5.00 sHVAC19-20
P1033 M. PID Fdbck Alarm High V. -32768 to 32767 900 H VAC19 -20
P1034 M. PID Fdbck Alarm Hig T.0.00 to 650.00 s5.00 sHVAC19-21
P1035 SoftPLC Parameter 26-32768 to 327670 HVAC18-2
P1036 Sleep Mode Speed0 to 18000 350 HVAC19 -21
P1037 Sleep Mode Time0.00 to 650.00 s5.00 sHVAC19-22
P1038 Wake Up Main Deviation0.0 to 100.0 %5.0 %HVAC19-22
P1039 Wake Up Main Time0.00 to 650.00 s10.0 0 sHVAC19 -22
P1040 HVAC Fun. Log. Status0000h to FFFFhroRE AD,
P10 41 SoftPLC Parameter 32-32768 to 32767 0 HVAC18-2
P1086 Ext. PID 2 Sampling Time0.10 to 60.00 s0.10 sHVAC19-3 4
P1087 Ext. PID 2 P. Gain0.000 to 32.767 1.000 HVAC19 - 34
P1088 Ext. PID 2 I. Gain0.000 to 32.767 0.430 HVAC19 -34
P1089 Ext. PID 2 D. Gain0.000 to 32.767 0.000 HVAC19-35
P1090 Ext. PID 2 Output Min. Value 0.0 to 100.0 %0.0 %HVAC19-35
P1091 Ext. PID 2 Output Max. Value 0.0 to 100.0 %100.0 %HVAC19-35
P1092 SoftPLC Parameter 83-32768 to 32767 0 HVAC18-2
P1093 Ext. PID 2 Min. Feedback-32768 to 32767 0 HVAC19-35
P1094 Ext. PID 2 Max. Feedback-32768 to 32767 1000 HVAC19- 36
P1095 Ext. PID 2 Fdbck Alarms
Conf.
P1096 Ext. PID 2 Fdbck Alarm
Lo w V.
P1097 Ext. PID 2 Fdbck Alarm
Low T.
P1098 Ext. PID 2 Fdbck Alarm
High V.
P1099 Ext. PID 2 Fdbck Alarm
Hig T.
Adjustable
Range
1 = Direct Mode
2 = Reverse Mode
1 = Always Manual
2 = A/M DI w/o bumpless
3 = A/M Net w/o bumpless
4 = A/M DI w/ bumpless
5 = A/M Net w/ bumpless
0 = Disable
1 = Enable Alarm
2 = Enable Fault
-32768 to 32767 2 HVAC19-37
0.00 to 650.00 s5.00 sHVAC19 -37
-32768 to 32767 900 HVAC19-37
0.00 to 650.00 s5.00 sHVAC19-38
Factory
Setting
0cfgHVAC19-32
0HVAC19-3 3
0HVAC19-3 6
User
Setting
Propr.Groups Pág.
Notes:
ro = Read-only parameter
rw = Reading/writing parameter
cfg = Configuration parameter, it can be changed only with stopped motor
V/f = Parameter available in V/f mode
Adj = Parameter available only in adjustable V/f mode
VVW = Parameter available in VV W mode
Vector = Parameter available in vector mode
Sless = Parameter available only in sensorless mode
0-16 | CFW701
Quick Parameter Reference, Faults and Alarms
Fault/AlarmDescriptionPossible Causes
F0006:
Input Voltage Imbalance
or Phase Loss
The mains voltage imbalance is too high or phase
loss at the supply line has occurred.
Note:
A Phase Loss at the inverter input. The input voltage imbalance is > 5 %.
- This fault may not occur if the load at the motor
shaft is too low or nonexistent.
P0357 sets the time for the trip, and P0357 = 0
disables this fault.
F0 021:
DC Link Undervoltage
A DC link undervoltage condition has occurred. The input voltage is too low and the DC link voltage
dropped below the minimum permitted value (monitor
the P0004 parameter value):
Ud < 223 V - 200 / 240 V three-phase input voltage;
Ud < 170 V - 200 / 240 V single-phase input voltage
(CFW701XXXXS2 or CFW701XXXXB2 models)
(P0296 = 0);
Ud < 385 V - 380 V input voltage (P0296 = 1);
Ud < 405 V - 400 / 415 V input voltage (P0296 = 2);
Ud < 446 V - 440 / 460 V input voltage (P0296 = 3);
Ud < 487 V - 480 V input voltage (P0296 = 4);
Ud < 530 V - input voltage 500 / 525 V (P0296 = 5);
Ud < 580 V - input voltage 550 / 575 V (P0296 = 6);
Ud < 605 V - input voltage 600 V (P0296 = 7).
Phase loss at the inverter input. Pre-charge circuit failure. Parameter P0296 was set to a value higher than the
power supply rated voltage.
F0022:
DC Link Overvoltage
A DC link overvoltage condition has occurred. Too high input voltage, resulting in a DC link voltage higher
than the maximum permitted value:
Ud > 400 V - 220 / 230 V models (P0296 = 0);
Ud > 800 V - 380 / 480 V models (P0296 = 1, 2, 3, or 4);
Ud > 1000 V - 500 / 600 V models (P0296 = 5, 6 or 7).
The inertia of the driven-load is too high or the
deceleration time is too short.
The parameter P0151, P0153 or P0185 setting is too high.
A0046:
High Load at the Motor
A0 047:
IGBT Overload Alarm
It is the motor overload alarm.
Note:
It can be disabled by setting P0348 = 0 or 2.
It is the IGBT overload alarm.
Note:
The settings of P0156, P0157 and P0158 are too low for
the used motor.
There is excessive load at the motor shaft. The inverter output current is too high.
It can be disabled by setting P0350 = 0 or 2.
F0048:
It is the IGBT overload fault. The inverter output current is too high.
IGBT Overload Fault
A0050:
IGBT High Temperature
F0 051:
IGBT Overtemperature
F0070:
Overcurrent/
Short-circuit
F0 071:
Output Overcurrent
F0072:
Motor Overload
F0 0 74:
Ground Fault
The NTC temperature sensors located in the
IGBTs detected a high temperature alarm.
Note:
It can be disabled by setting P0353 = 2 or 3.
High surrounding air temperature (>50 °C (122 °F)) and
high output current.
Blocked or defective fan. Very dirty heatsink.
The NTC temperature sensors located in the
IGBTs detected a high temperature fault.
An overcurrent or a short-circuit at the output,
at the DC link or at the braking resistor, has
occurred.
Short-circuit between two motor phases. Short-circuit between the dynamic braking resistor
connection cables.
Shorted IGBT modules.
An output overcurrent has occurred. Excessive load inertia or too short acceleration ramp.
P0135, or P0169 and P0170 settings are too high.
The motor overload protection has tripped.
Note:
It can be disabled by setting P0348 = 0 or 3.
A ground fault occurred either in the cable
between the inverter and the motor or in the
motor itself.
The settings of P0156, P0157 and P0158 are too low for
the used motor.
There is excessive load at the motor shaft.
Short-circuit to the ground in one or more output phases. Motor cable capacitance is too large, resulting in current
peaks at the output.
Note:
It can be disabled by setting P0343 = 0.
F0078:
Motor Overtemperature
Fault related to the PTC temperature sensor
installed in the motor.
Note:
- It can be disabled by setting P0351 = 0 or 3.
- An analog input and an analog output must be
set for the PTC function.
Excessive load at the motor shaft. Severe duty cycle (too many starts / stops per minute). Too high surrounding air temperature. Loose connection or short-circuit (resistance < 100 Ω) in
the wiring connected to the motor thermistors.
Not installed motor thermistors. Blocked motor shaft.
Auto-Diagnosis Fault. Defect in the inverter internal circuitry.
Firmware incompatible with an accessory.
External alarm monitored through a digital input.
Note:
A digital input (DI1 to DI8) programmed for “No external
alarm” is open.
It is necessary to program a digital input for “No
external alarm”.
F0 091:
External Fault
External fault monitored through a digital input.
Note:
A digital input (DI1 to DI8) programmed for “No external
fault” is open.
It is necessary to program a digital input for “No
external fault”.
A0098:
Activate General Enable
F0099:
Invalid Current Offset
A0110 :
High Motor Temperature
General Enable signal is missing during the
self-tuning.
The current measurement circuit is presenting an
abnormal value for null current.
Fault detected through PTC type temperature
sensors installed in the motor.
Note:
- It can be disabled by setting P0351 = 0 or 2.
- An analog input and an analog output must be
The digital input programmed for “General Enable” is
open.
Defect in the inverter internal circuitry.
Excessive load at the motor shaft. Severe duty cycle (too many starts / stops per minute). Too high surrounding air temperature. Not installed motor thermistors. Blocked motor shaft.
set for the PTC function.
A0128:
Serial Communication
Timeout
It indicates that the inverter stopped receiving
valid telegrams during a certain period.
Note:
Check the wiring and the ground installation. Make sure that the inverter has sent a new message
within the time interval set at P0314.
It can be disabled by setting P0314 = 0.0 s
F0150:
Motor Overspeed
Overspeed fault.
It trips when the actual speed exceeds the value
(100 % + P0132)
of
P0134 x
100%
for more than 20 ms.
Wrong settings of P0161 and/or P0162. Problem with a hoist-type load.
Check the connection of the FLASH memory module.
This alarm indicates that the internal air
temperature is too high.
Note:
It can be disabled by setting P0353 = 1 or 3.
High surrounding air temperature (>50 °C (122 °F)) and
high output current.
Defective internal fan (if existent). High temperature (> 45 ºC) inside the cabinet.
It indicates internal air overtemperature fault. High surrounding air temperature (>50 °C (122 °F)) and
high output current.
Defective internal fan (if existent).
The temperature sensors located in the IGBTs or
Surrounding air temperature ≤ -30 °C (-22 °F).
in the rectifier detected a low temperature, below
-30 °C ( -22 °F), fault.
There was a problem during the initialization,
during the parameter table loading routine. Some
The control was switched off very fast while a parameter
was being modified.
recent parameter modifications may have been
lost.
There was a problem during the initialization,
during the parameter table loading routine. All
Firmware updating fault. Defective control board.
the parameters were lost and the factory settings
were loaded.
Incompatible HMI HMI of another product being used.
Safety stop relay fault. One of the relays is defective or it does not have +24 V
applied to its coil.
It indicates that the AI1 current (4-20 mA or
20-4 mA) reference is out of the 4 to 20 mA range.
Broken AI1 cable. Bad contact at the connection of the signal to the
terminal strip.
It indicates that the AI2 current (4-20 mA or
20-4 mA) reference is out of the 4 to 20 mA range.
Broken AI2 cable. Bad contact at the connection of the signal to the
terminal strip.
It indicates that the AI3 current (4-20 mA or
20-4 mA) reference is out of the 4 to 20 mA range.
Broken AI3 cable. Bad contact at the connection of the signal to the
terminal strip.
Difference between speed reference and effective
Inverter in torque current limitation.
speed greater than the setting in P0360.
Quick Parameter Reference, Faults and Alarms
Fault/AlarmDescriptionPossible Causes
F016 9:
Speed Error too High
A0 170:
Safety Stop
A0 177:
Fan Replacement
F0 179:
Heatsink Fan Speed
Fault
F018 2:
Pulse Feedback Fault
F018 3:
IGBT Overload +
Temperature
F018 5:
Pre-Charge Contactor
Fault
A0210:
Drive in Bypass mode
A0211:
Drive in Fire Mode
F0228:
Serial Communication
Timeout
A0702:
Disabled Inverter
A0704:
Two Enabled
Movements
A0706:
Reference not
Programmed for
SoftPLC
F0711:
Fault in the Execution of
the SoftPLC
A0750:
Programming AIx for
Main PID Controller
Feedback
A0752:
Programming DIx for
Main PID Controller
Automatic/Manual
Selection
A0754:
Programming Local
Reference (P0221) for
SoftPLC
A0756:
Programming Remote
Reference (P0222) for
SoftPLC
A0758:
Programming Indirect
Engineering Unit 4
(P0516) for Hz or rpm
Difference between speed reference and effective
speed greater than the setting in P0360 for longer
than P0361.
The Safety Stop function is active. The CFW701 went to the STO state.
Fan replacement alarm (P0045 > 50000 hours).
Note:
This function can be disabled by setting
P0354 = 0.
This fault indicates a problem with the heatsink fan.
Note:
This function can be disabled by setting
P0354 = 0.
It indicates a fault in the output pulses feedback. Defect in the inverter internal circuitr y.
Overtemperature related to the IGBT overload
protection.
It indicates a fault at the pre-charge contactor. Defective pre-charge contactor.
Indicates that the drive is in Bypass mode. The digital input programmed for activating the Bypass
Indicates that the drive is in Fire Mode.The digital input programmed for activating the Fire Mode
Refer to the RS-232 / RS-485 Serial Communication Manual.
Refer to the SoftPLC Manual.
Fault in the execution of the SoftPLC. Incompatible applicative.
It indicates to the user there is not analog input
programmed for Main PID controller feedback.
It indicates to the user there is not digital input
programmed for Main PID controller
Automatic/Manual selection.
It indicates to the user that the origin of the speed
reference in the Local situation is not programmed
for SoftPLC .
It indicates to the user that the origin of the
speed reference in the Remote situation is not
programmed for SoftPLC.
It indicates to the user that the engineering unit
parameters for motor speed is not programmed
for Hz or rpm.
Inverter in torque current limitation for too long.
The heatsink fan maximum number of operating hours
has been reached.
Dirt on the blades and in the bearings of the fan. Defective fan. Defective fan power supply connection.
Too high inverter surrounding temperature. Operation with frequencies < 10 Hz with overload.
Open command fuse. Phase loss at the L1/R or L2/S input. P0355 = 1 (incorrect setting for mechanical models “E”
powered by the DC Link. For these models should be
set P0355 = 0).
mode is active.
is active.
Fault during upload of the applicative.
Parameter P0231 or P0236 or P0241 is not programmed
in 5, 6 or 7.
Parameter P0263 or P0264 or P0265 or P0266 or P0267
or P0268 or P0269 or P0270 is not programmed in 20.
Main PID controller is enabled (P1017 in 1 or 2) and
CFW701 frequency inverter run the motor in Local
situation and parameter P0221 is not programmed in 7.
Main PID controller is enabled (P1017 in 1 or 2) and
CFW701 frequency inverter run the motor in Remote
situation and parameter P0222 is not programmed in 7.
Parameter P0516 is not programmed in 13 (Hz) or 3 (rpm).
0
CFW701 | 0-19
Quick Parameter Reference, Faults and Alarms
0
Fault/AlarmDescriptionPossible Causes
A0760:
Low Level for Main PID
Controller Feedback
F0761:
Low Level for Main PID
Controller Feedback
A0762:
High Level for Main PID
Controller Feedback
F0763:
High Level for Main PID
Controller Feedback
A0764:
CFW701 in Sleep Mode
A0766:
Dry Pump Detected
F0 767:
Dry Pump Detected
A0768:
Broken Belt Detected
F0769:
Broken Belt Detected
A0770:
Filter Maintenance
F0771:
Filter Maintenance
A0780:
Programming AIx for
External PID Controller 1
Feedback
A0782:
Programming DIx for
External PID Controller
1 Automatic/Manual
Selection
A0784:
Programming AOx for
External PID Controller 1
Output
A0786:
Low Level for External PID
Controller 1 Feedback
F0787:
Low Level for External PID
Controller 1 Feedback
A0788:
High Level for External PID
Controller 1 Feedback
It indicates to the user that the Main PID controller
feedback is low.
It indicates to the user that the Main PID controller
feedback is low.
It indicates to the user that the Main PID controller
feedback is high.
It indicates to the user that the Main PID controller
feedback is high.
It indicates to the user that the CFW701 frequency
inverter is in Sleep mode.
It indicates to the user that the dry pump
condition was detected for the pump driven by
CFW701 frequency inverter.
It indicates to the user that the dry pump
condition was detected for the pump driven by
CFW701 frequency inverter.
It indicates to the user that the broken belt
condition was detected for the motor driven by
CFW701 frequency inverter.
It indicates to the user that the broken belt
condition was detected for the motor driven by
CFW701 frequency inverter.
It indicates to the user that the need to change
the filter system.
It indicates to the user that the need to change
the filter system.
It indicates to the user there is not analog input
programmed for External PID controller 1
feedback.
It indicates to the user there is not digital input
programmed for External PID controller 1
Automatic/Manual selection.
It indicates to the user there is not analog output
programmed for External PID controller 1 output.
It indicates to the user that the External PID
controller 1 feedback is low.
It indicates to the user that the External PID
controller 1 feedback is low.
It indicates to the user that the External PID
controller 1 feedback is high.
Parameter P1030 is programmed in 1 and the Main PID
controller feedback value is remaining below the value
programmed in P1031 for the time programmed in P1032.
Parameter P1030 is programmed in 2 and the Main PID
controller feedback value is remaining below the value
programmed in P1031 for the time programmed in P1032.
Parameter P1030 is programmed in 1 and the Main PID
controller feedback value is remaining above the value
programmed in P1033 for the time programmed in P1034.
Parameter P1030 is programmed in 2 and the Main PID
controller feedback value is remaining above the value
programmed in P1033 for the time programmed in P1034.
Main PID controller is enabled and in Automatic mode
and the motor speed is remaining below the speed value
programmed in P1036 for the time programmed in P1037.
Parameter P1042 is programmed in 1 and the pump
driven by CFW701 frequency inverter is running faster
than speed programmed in P1043 and the motor torque
is remaining below the torque value programmed in
P1044 for the time programmed in P1045.
Parameter P1042 is programmed in 2 and the pump
driven by CFW701 frequency inverter is running faster
than speed programmed in P1043 and the motor torque
is remaining below the torque value programmed in
P1044 for the time programmed in P1045.
Parameter P1046 is programmed in 1 and the motor
driven by CFW701 frequency inverter is running faster
than speed programmed in P1047 and the motor torque
is remaining below the torque value programmed in
P1048 for the time programmed in P1049.
Parameter P1046 is programmed in 2 and the motor
driven by CFW701 frequency inverter is running faster
than speed programmed in P1047 and the motor torque
is remaining below the torque value programmed in
P1048 for the time programmed in P1049.
Parameter P1050 is programmed in 1 and the operation
time of motor driven by CFW701 frequency inverter
displayed in P1052 is greater than the time programmed
in P10 51.
Parameter P1050 is programmed in 2 and the operation
time of motor driven by CFW701 frequency inverter
displayed in P1052 is greater than the time programmed
in P10 51.
Parameter P0231 or P0236 or P0241 is not programmed
in 8.
Parameter P0263 or P0264 or P0265 or P0266 or P0267
or P0268 or P0269 or P0270 is not programmed in 21.
Parameter P0251 or P0254 is not programmed in 16.
Parameter P1075 is programmed in 1 and the External PID
controller 1 feedback value is remaining below the value
programmed in P1076 for the time programmed in P1077.
Parameter P1075 is programmed in 2 and the External PID
controller 1 Feedback value is remaining below the value
programmed in P1076 for the time programmed in P1077.
Parameter P1075 is programmed in 1 and the External PID
controller 1 feedback value is remaining above the value
programmed in P1078 for the time programmed in P1079.
0-20 | CFW701
Quick Parameter Reference, Faults and Alarms
Fault/AlarmDescriptionPossible Causes
F0789:
High Level for External PID
Controller 1 Feedback
A0790:
Programming AIx for
External PID Controller 2
Feedback
A0792:
Programming DIx for
External PID Controller
2 Automatic/Manual
Selection
A0794:
Programming AOx for
External PID Controller 2
Output
A0796:
Low Level for External PID
Controller 2 Feedback
F0 797:
Low Level for External PID
Controller 2 Feedback
A0798:
High Level for External PID
Controller 2 Feedback
F0799:
High Level for External PID
Controller 2 Feedback
It indicates to the user that the External PID
controller 1 feedback is high.
It indicates to the user there is not analog
input programmed for External PID controller 2
feedback.
It indicates to the user there is not digital input
programmed for External PID controller 2
Automatic/Manual selection.
It indicates to the user there is not analog output
programmed for External PID controller 2 output.
It indicates to the user that the External PID
controller 2 feedback is low.
It indicates to the user that the External PID
controller 2 feedback is low.
It indicates to the user that the External PID
controller 2 feedback is high.
It indicates to the user that the External PID
controller 2 feedback is high.
Parameter P1075 is programmed in 2 and the External PID
controller 1 feedback value is remaining above the value
programmed in P1078 for the time programmed in P1079.
Parameter P0231 or P0236 or P0241 is not programmed
in 9.
Parameter P0263 or P0264 or P0265 or P0266 or P0267
or P0268 or P0269 or P0270 is not programmed in 22.
Parameter P0251 or P0254 is not programmed in 17.
Parameter P1095 is programmed in 1 and the External PID
controller 2 feedback value is remaining below the value
programmed in P1096 for the time programmed in P1097.
Parameter P1095 is programmed in 2 and the External PID
controller 2 feedback value is remaining below the value
programmed in P1096 for the time programmed in P1097.
Parameter P1095 is programmed in 1 and the External PID
controller 2 feedback value is remaining above the value
programmed in P1098 for the time programmed in P1099.
Parameter P1095 is programmed in 2 and the External PID
controller 2 feedback value is remaining above the value
programmed in P1098 for the time programmed in P1099.
0
Notes:
(1) Very long motor cables, with more than 100 m (328.08 ft), presents a high parasitic capacitance to the ground.
The circulation of a leakage current through this capacitance may cause the activation of the ground fault circuit,
and consequently an F0074 trip immediately after the inverter enabling.
POSSIBLE SOLUTION:
To reduce the switching frequency (P0297).
ATTENTION!
A bad contact in the HMI cable, or electric noise in the installation, can cause a failure in the
communication between the HMI and the control board. In such case, the operation through the HMI
becomes impossible and the HMI indicates the following message on the display:
CFW701 | 0-21
Quick Parameter Reference, Faults and Alarms
0
0-22 | CFW701
Loading...
+ 207 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.