Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequência
CFW701
User's Manual
Manual del Usuario
Manual do Usuário
Language: English, Spanish, Portuguese
User's Manual
Series: CFW701
Language: English
Document: 10001393824 / 02
Models: Frame Sizes A...E
Date: 05/2015
Summary of Revisions
The table below describes the revisions made to this manual.
VersionReviewDescription
-R00First edition
-R01General review
-R02
Inclu sion of new fra me s izes m ode ls D a nd E
Update from IP54 to IP55 in frame sizes B and C
ATTENTION!
Parameters P0296 (Rated Line Voltage), P0400 (Rated Motor Voltage) and
P0403 (Rated Motor Frequency), were readjusted at the:
200...240 V / 220 / 230 V (S2, B2 and T2) models: P0296 = 0 (200 / 240 V),
P0400 = 220 V and P0403 = 60 Hz.
380...480 V (T4) models: P0296 = 3 (440 / 460 V), P0400 = 440 V and
P0403 = 60 Hz.
500...600 V (T5) models: P0296 = 6 (550 / 575 V), P0400 = 575 V and
P0403 = 60 Hz.
For different values of line rated voltage and/or motor voltage and frequency,
set these parameters through the STARTUP menu, as presented in the user's
manual section 5.2 START-UP on page 27.
8.2.1 Codes and Standards ...................................................................42
APPENDIX A - DIAGRAMS AND FIGURES ......................................138
APPENDIX B - TECHNICAL SPECIFICATIONS ................................ 148
Safety Instructions
1 SAFETY INSTRUCTIONS
This manual provides information for the proper installation and operation of the CFW701
frequency inverter.
Only trained personnel, with proper qualifications, and familiar with this kind of equipment
and associated machinery shall plan and implement the installation, starting, operation, and
maintenance of this equipment. The personnel shall follow all the safety instructions described in
this manual and/or defined by the local regulations. Failure to comply with the safety instructions
may result in death, serious injury, and equipment damage.
1.1 SAFETY WARNINGS IN THE MANUAL
DANGER!
The procedures recommended in this warning have the purpose of protecting
the user against death, serious injuries and considerable material damage.
DANGER!
Les procédures concernées par cet avertissement sont destinées à protéger
l'utilisateur contre des dangers mortels, des blessures et des détériorations
matérielles importantes.
ATTENTION!
The procedures recommended in this warning have the purpose of avoiding
material damage.
English
NOTE!
The information mentioned in this warning is important for the proper
understanding and good operation of the product.
1.2 SAFETY WARNINGS IN THE PRODUCT
The following symbols are attached to the product, serving as safety notices:
High voltages are present.
Components sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to the protective ground (PE).
CFW701 | 1
Safety Instructions
Connection of the shield to the ground.
English
Hot surface.
1.3 PRELIMINARY RECOMMENDATIONS
DANGER!
Always disconnect the main power supply before touching any electrical
device associated with the inverter. Several components may remain charged
with high voltage and/or in movement (fans), even after the AC power supply
has been disconnected or turned off. Wait at least 10 minutes to guarantee
the fully discharge of capacitors. Always connect the equipment frame to the
ground protection (PE).
DANGER!
Débranchez toujours l'alimentation principale avant d'entrer en contact avec un
appareil électrique associé au variateur. Plusieurs composants peuvent rester
chargés à un potentiel électrique élevé et/ou être en mouvement (ventilateurs),
même après la déconnexion ou la coupure de l'alimentation en courant alternatif.
Attendez au moins 10 minutes que les condensateurs se déchargent
complètement.
Raccordez toujours la masse de l'appareil à une terre protectrice (PE).
Do not perform a withstand voltage test on any part of the inverter!
2 | CFW701
NOTE!
Frequency inver ters may cause interference in other electronic devices. Follow
the recommendations listed in chapter 3 INSTALLATION AND CONNECTION
on page 9, to minimize these effects.
Fully read this manual before installing or operating the inverter.
If needed, please, consult WEG.
General Instructions
2 GENERAL INSTRUCTIONS
2.1 ABOUT THE MANUAL
The purpose of this manual is to provide the basic information needed to install, start-up in
the V/f control mode (scalar), and troubleshoot the most common problems of the CFW701
frequency inverter series.
ATTENTION!
The operation of this equipment requires installation instructions and
detailed operation provided in the user's manual, programming manual and
communication manuals. The user's manual and the parameters quick reference
are supplied in a hard copy together with the inverter. The user guides are
also provided in a hard copy along with the accessories. The other manuals
are included on the CD supplied with the inverter or can be downloaded from
the WEG website at - www.weg.net. The CD should always be kept with the
equipment. A printed copy of the files available on the CD can be ordered
through your local WEG representative.
Some of the figures and tables are available in the appendixes. The APPENDIX A - DIAGRAMS AND
FIGURES on page 138 shows the figures and the APPENDIX B - TECHNICAL SPECIFICATIONS
on page 148 shows the technical specifications. The information is available in three languages.
Please refer to the following technical manuals for further information:
CFW701 Programming Manual.
English
Modbus Communication Manual.
BACnet Communication Manual.
2.2 ABOUT THE CFW701
The CFW701 frequency inverter is a high performance product designed for speed and torque
control of threephase induction motors. The main characteristic of this product is the “Vectrue”
technology, which has the following advantages:
Scalar control (V/f), VVW, or vector control programmable in the same product.
The vector control may be programmed as “sensorless” (which means standard motors
without using encoders).
The “sensorless” control allows high torque and fast response, even in very low speeds or at
the starting.
“Optimal Braking” function for the vector control, allowing the controlled braking of the motor
and avoiding external braking resistor for some applications.
“Self-Tuning” feature for vector control. It allows the automatic adjustment of the regulators
and control parameters from the identification (also automatic) of the motor parameters and
load.
The main components of the CFW701 can be viewed in Figure A.1 on page 138.
CFW701 | 3
General Instructions
English
C3 RFI filter
= DC bus connection
= Braking resistor
DC+DC-BR
(*)
connection
Mains power
supply
PC
WPS software
WLP software
Keypad
(remote)
Digital inputs
DI1 to DI8
Analog
inputs
AI1 to AI3
R/L1/L
S/L2/N
T/L 3
PE
RS-485
Three-phase
rectifier
Pre-
charge
DC link chokes
DC link capacitor bank
CFW701...DB... inver ters)
Braking IGBT (available in
POWER
CONTROL
Control power supply and interfaces
between power and control
Keypad
CC701
Control
board
with a
32 bits
"RISC"
CPU
RFI filter
transistors
Accessories
COMM 1
(Slot 3 - green)
Inverter
with
IGBT
Feedback:
- voltage
- current
U/T1
V/T2
W/T3
Motor
PE
PTC
protection
input
4 | CFW701
FLASH
memor y
module
(Slot 5)
= Keypad (HMI)
(*) The capacitor to the ground of the C3 RFI filter (it is possible to meet the
requirements of category C2 with this filter on frame size A models) must be
disconnected for IT net works and grounded delta power supplies. Please
refer to item 3.2.3.1 Input Connections on page 14.
Figure 2.1: Block diagram for the CFW701
Analog
outputs
AO1 and AO2
Digital outputs
DO1 (RL1) and
DO2 (RL2)
Digital outputs
DO3 to DO5
General Instructions
2.3 IDENTIFICATION
Table 2.1: Identification of the CFW701 inverters
Product
and
Series
Eg.: CFW701 A03P6T4DB20C3DSY1W1-----
CFW701
Available options
Notes:
(1) The options available for each model are shown in Table 2.2 on page 6.
(2) This option is not available for 200...240 V and 380...480 V models of frame size D inverters (the standard product is
Ne ma1).
(3) This option is not available for frame size A inverters with N1 (Nema1 enclosure) or IP21 options.
(4) It is possible to meet the requirements of catego ry C2 with this fi lter on frame size A models. For fur ther details, see Table
B.6 on page 163.
(5) Only applicable to models with degree of protection IP55, option N12.
Model Identification
Rated
Output
Current
(4)
(2)
Number
of Power
Phases
Rated
Volta ge
Frame
Size
Refer to Table 2.2 on p age 6.
NB = withou t dynamic braki ng (valid only for
frame size E inverters and 50 0...60 0 V models
of frame si ze D).
DB = with dy namic braking.Blank = standard.
20 = IP20
21 = IP21 (not availa ble for frame size E inverter s).Blank = not available.
N1 = Nema1 enclos ure (UL Type 1) (protection de gree
accordi ng to IEC: IP21 for frame size s A, B and C and IP20
for frame s izes D and E).
N12 = IP55 (only for 200...240 V and 3 80...4 80 V models of
frame sizes B, C, D and E).
C3 = accord ing to category 3 (C3) of IEC 61800-3, wi th built-in C3 RFI
fil ter.
Braking
(1)
Enclosure
Conducted
(1)
Emission
Level
(1)
Safet y
Discon.
Switc h
Blank = not
available
DS = with
discon.
switch
External
Stop
Control
(5)
(3)
Volta ge
W1 = 24 Vdc power supply,
indepe ndent of the control
voltage.
Blank = not available.
Y1 = with STO function (Safe Torqu e Off)
accordi ng to EN 954-1/ ISO 13849-1,
category 3.
Special
Special
Hardware
Software
Versi on
Versi on
Blank =
standard.
Sx =
special
software.
Hxx or K xx = special
hardware.
English
CFW701 | 5
General Instructions
Table 2.2: Options available for each model according to the frame size, power supply, rated current and
voltage of the inverter
Available Options for the Remaining Identification
Braking
DB
NB or DB 20, N1 o r N12
DB20, 21 or N1
NB or DB
Frame
Size
A
A
B
C
D
E
A
B
C
D
E
B
C
D
E
Rated Output
Curre nt for ND
Overload
06P0 = 6.0 A
07P0 = 7.0 A
10P0 = 10 A
07P0 = 7.0 A
10P0 = 10 A
13P0 = 13 A
16P0 = 16 A
24P0 = 24 A
28P0 = 28 A
33P5 = 33.5 A
45P0 = 45 A
54P0 = 54 A
70P0 = 70 A
86P0 = 8 6 A
0105 = 105 A
0142 = 142 A
02 11 = 211 A
03P6 = 3.6 A
05P0 = 5.0 A
07P0 = 7.0 A
10P0 = 10 A
13P5 = 13.5 A
17P0 = 17 A
24P0 = 24 A
31P0 = 31 A
38P0 = 3 8 A
45P0 = 45 A
58P5 = 58.5 A
70P5 = 70.5 A
88P0 = 8 8 A
0105 = 105 A
0142 = 142 A
0180 = 180 A
02 11 = 211 A
02P9 = 2.9 A
04P2 = 4.2 A
07P0 = 7.0 A
10P0 = 10 A
12P0 = 12 A
17P0 = 17 A
22P0 = 22 A
27P0 = 27 A
32P0 = 32 A
44P0 = 44 A
22P0 = 22 A
27P0 = 27 A
32P0 = 32 A
44P0 = 44 A
53P0 = 53 A
63P0 = 63 A
80P0 = 80 A
0107 = 107 A
0125 = 125 A
0150 = 150 A
Number of
Power Phases
S = Single-phase2 = 200…240 VDB20, 21 or N1
T = three-phase
T = three-phase4 = 380...480 V
T = three-phase5 = 500...600 V
Rated Voltage
2 = 200…240 VDB
2 = 220 / 230 VNB or DB 20, N1 or N120180 = 180 A
English
Codes o f the Inverte rs
(standard product is shown in bold)
Enclosure
(protection
degree)
20, 21or N1
20, 21, N1
21, N1 o r N12
20, 21 or N1Blank
20, 21, N1
21, N1 o r N12
20, 21 or N1
20 or N1
or N 12
or N 12
Disconnecting
Switch
Blank
Blank or DS
Blank o r DS
Blank or DS
Blank o r DS
BlankC3
Conducted Emission
Level
C3
C3
6 | CFW701
General Instructions
2.4 LIST OF AVAILABLE MODELS
The available inverter models are listed in Table B.1 on page 148, Table B.2 on page 149
and Table B.3 on page 150.
2.5 IDENTIFICATION LABELS
There are two nameplates on the CFW701: one complete nameplate is affixed to the side of the
inverter and a simplified one is located under the keypad. Please refer to Figure A.2 on page
139 to verify the position of these labels on the product. The nameplate under the keypad
allows the identification of the most important characteristics of the inverter even if they are
mounted side-by-side. When there is more than one inverter it is necessary to be careful not to
exchange the inverter covers (front cover in case of inverters frame sizes A, B or C and control
rack cover for inverters frame sizes D and E) because there are individual information labels
under the keypad of each inverter.
CFW701 model
Manufacturing dateWEG part number
Serial number
(a) Nameplate located under the keypad
CFW701 model
WEG part number
Inverter net weight
Input rated data (voltage,
number of phases, rated
currents for operation with
ND and HD overload cycles,
and frequency)
Current specifications
for operation with normal
overload cycle (ND)
Current specifications
for operation with heavy
overload cycle (HD)
(b) Nameplate affixed to the side of the inverter
Figure 2.2: (a) and (b) Nameplates
Manufacturing date
Serial number
Maximum ambient
temperature (without
derating) for ND overload
with open spaces for
ventilation around the
inverter (refer to the
dimensions A, B, C and
D in Figure B.3 on page
171)
Output rated data
(voltage, number of
phases, rated currents for
operation with ND and HD
overload cycles, overload
currents for 1 min and 3 s,
and frequency range)
The maximum output
frequency depends on the
settings of the motor rated
frequency, control mode
and inverter switching
frequency. For fur ther
details, see Table 8.1 on
page 40.
English
2.6 RECEIVING AND STORAGE
The CFW701 comes packaged in a cardboard box up to frame size C inverter models. The
bigger models are packed in wooden box. There is an identification label affixed to the outside
of this package, the same one that is affixed to the side of the CFW701 inverter.
CFW701 | 7
General Instructions
Follow the steps below to open the packaging of models larger than frame size C:
1. Put the shipping container over a flat and stable area with the assistance of another two
people.
English
2. Open the wood crate.
3. Remove all the packing material (the cardboard or styrofoam protection) before removing
the inverter.
Check the following items once the inverter is delivered:
Verify that the CFW701 nameplate corresponds to the model number on your purchase order.
Inspect the CFW701 for external damage during transportation.
Report any damage immediately to the carrier that delivered your CFW701 inverter.
If CFW701 is to be stored for some time before use, be sure that it is stored in a clean and dry
location that conforms to the storage temperature specification (between -25 °C and 60 °C
(-13 °F and 140 °F)). Cover the inverter to prevent dust accumulation inside it.
ATTENTION!
Capacitor reforming is required if drives are stored for long periods of time
without power. Refer to section 6.4 PREVENTIVE MAINTENANCE on page 32.
8 | CFW701
3 INSTALLATION AND CONNECTION
3.1 MECHANICAL INSTALLATION
3.1.1 Installation Environment
Installation and Connection
Avoid installing the inverter in an area with:
Direct exposure to sunlight, rain, high humidity, or sea-air.
Inflammable or corrosive gases or liquids.
Excessive vibration.
Dust, metallic particles, and oil mist.
Environment conditions for the operation of the inverter:
Inverter surrounding temperature: from -10 ºC up to Ta according to the Table B.4 on page
152.
For temperatures around the inverter greater than Ta and smaller than 60 °C (140 °F) (frame
sizes A, B, C and D), 40 °C (104 °F) (models with degree of protection IP55) and 55 °C (133 °F)
(frame size E), it is necessary to apply current reduction of 2 % for every degree Celsius (or
1.11 % each °F) up to Ta.
Humidity: from 5 % to 95 % non-condensing.
Altitude: up to 1000 m (3.300 ft) - standard conditions (no derating required).
From 1000 m to 4000 m (3.300 ft to 13.200 ft) - current derating of 1 % each 100 m (or 0.3 %
each 100 ft) above 1000 m (3.300 ft) altitude.
From 2000 m to 4000 m (6.600 ft to 13.200 ft) above sea level - maximum voltage reduction
(240 V for 200...240 V models, 230 V for 220...230 V models, 480 V for 380...480 V models
and 600 V for 500 ...600 V models) of 1.1 % for each 100 m (330 ft) above 2000 m (6.600 ft).
English
Pollution degree: 2 (according to EN50178 and UL508C) with non-conductive pollution.
Condensation shall not originate conduction through the accumulated residues.
3.1. 2 Mounting Considerations
External dimensions, fixing holes position and net weight of the inverter are presented at Figure
B.2 on page 169 and Figure B.3 on page 171. Please refer to Figure B.4 on page 172 to
Figure B.10 on page 178 for more details of each inverter frame size.
Install the inverter upright on a flat surface. First place the screws on the surface where the
drive is going to be installed, install the drive and then tighten the screws.
Frame size E inverters with N1 option (CFW701E...N1...):
After fixing the inverter, install the upper Nema 1 kit on the inverter using the two M8 screws
provided with the product.
CFW701 | 9
Installation and Connection
Let the minimum clearances specified in Figure B.3 on page 171 in order to allow air circulation
for cooling. It is possible to assembly frame sizes A, B and C inverters with IP20 protection
degree (CF W701… 20…) side by side without lateral spacing, i.e., with the D distance presented
English
in Figure B.3 on page 171 equal to zero.
Do not install heat sensitive components right above the inverter.
ATTENTION!
When arranging two or more inverters vertically, respect the minimum
clearance A + B (Figure B.3 on page 171) and provide an air deflecting
plate so that the heat rising up from the bottom inverter does not affect the
top inverter.
Provide conduit for physical separation of the signal, control, and power
conductors (refer to section 3.2 ELECTRICAL INSTALLATION on page 10).
Please refer to Figure B.3 on page 171 for surface and flange mounting data. The inverter
dissipated power at rated condition for surface and flange mounting is presented in Table B.4
on page 152. Remove the drive mounting brackets for flange mounting. The protection degree
of the inverter outside the panel is IP55 for flange mounting. It is necessary to provide proper
seal for the opening where the inverter is installed to ensure the protection degree of the panel.
Example: sealing with silicone.
Please refer to Figure A.4 on page 141 for more details on the access to the control and
power terminals.
3.2 ELECTRICAL INSTALLATION
10 | CFW701
DANGER!
The following information is merely a guide for proper installation. Comply
with applicable local regulations for electrical installations.
Make sure the AC power supply is disconnected before starting the
installation.
DANGER!
Les informations suivantes constituent uniquement un guide pour une
installation correcte. Respectez les réglementations locales en vigueur pour
les installations électriques.
Vérifiez que l'alimentation secteur CA est débranchée avant de commencer
l'installation.
Installation and Connection
3.2 .1 Identification of the Power and Grounding Terminals
R/L1 S/L2 T/L3DC-DC+ U/ T1 V/ T2 W/T3BR
GroundGround
(a) Frame sizes A, B and C
R/L1 S/L2 T/L3DC-DC+ U/ T1 V/ T2 W/T3BR
R/L1, S/L2, T/L3: AC power supply.
DC-: this is the negative potential
terminal in the DC bus circuit.
BR: braking resistor connection.
DC+: this is the positive potential
terminal in the DC bus circuit.
U/T1, V/T2, W/T3: motor
connection.
English
Ground
(b) Frame sizes B and C with degree of protection IP55
R/L1 S/L2 T/ L3DC-DC+U/T1 V/T2 W/ T3
Ground
(c) Frame size D
Ground
BR
Ground
CFW701 | 11
Installation and Connection
R/L1 S/L2 T/L3DC-DC+ U/ T1 V/ T2 W/T3BR
English
(d) Frame size D with degree of protection IP55
GroundGround
R/L1, S/L2, T/L3: AC power supply.
U/T1, V/T2, W/T3: motor
connection.
DC+: this is the positive potential
terminal in the DC bus circuit.
BR: braking resistor connection.
DC-: this is the negative potential
terminal in the DC bus circuit.
12 | CFW701
Ground
(4xM8, 4xM5)
(e) Frame size E
R/L1 S/L2 T/L3DC-DC+ U/ T1 V/ T2 W/T3BR
GroundGround
(f) Frame size E with degree of protection IP55
Figure 3.1: (a) to (f) Power terminals and grounding points – frame sizes A to E
Installation and Connection
English
3.2.2 Power / Grounding Wiring and Fuses
ATTENTION!
Use proper cable lugs for the power and grounding connection cables.
Refer to Table B.1 on page 148, Table B.2 on page 149 and Table B.3 on page 150 for
the recommended wiring and fuses and Table B.5 on page 160 for the specifications of the
power terminals.
NOTE!
The gauges values presented in Table B.1 on page 148, Table B.2 on page
149 and Table B.3 on page 150 are for reference only. Installation conditions
and the maximum permitted voltage drop shall be considered for the proper
wiring sizing.
Input fuses
The fuses to be used at the input must be HS (High-Speed) type with I
value indicated in the Table B.1 on page 148, Table B.2 on page 149 and Table B.3 on
page 150 (consider extinction current value in cold situation (it is not the fusion value)), to
protect the inverter diode rectifiers and input wiring.
2
t equal or lower the
CFW701 | 13
Installation and Connection
In order to meet UL requirements, use class J fuses at the inverter supply with a current not
higher than the values presented in Table B.1 on page 148, Table B.2 on page 149 and
Table B.3 on page 150 .
English
Optionally, slow blow fuses can be used at the input. They shall be sized for 1.2 x the rated
input current of the inverter. In this case, the installation is protected against short-circuit, but
not the inverter input rectifier. This may result in major damage to the inverter in the event of
an internal component failure.
3.2.3 Power Connections
PE R S T U V W PE
PE
Shielding
R
S
T
Power
supply
The switch-disconnector is not necessary if the inverter has the DS optional item (with
Disconnect
switch
Fuses
Figure 3.2: Power and grounding connections
PE W V U
switch-disconnector).
3.2.3.1 Input Connections
DANGER!
Provide a disconnect device for the input power supply of the inverter.
This device shall disconnect the input power supply for the inver ter when needed
(for instance, during servicing).
DANGER!
Montez un dispositif de coupure sur l'alimentation du variateur.
Ce composant déconnecte l'alimentation du variateur si cela est nécessaire
(ex. pendant l'entretien et la maintenance).
14 | CFW701
Installation and Connection
ATTENTION!
The power supply that feeds the inverter shall have a solid grounded neutral.
In case of IT networks, follow the instructions described below.
ATTENTION!
In order to be able to use the CFW701 with built-in C3 RFI filter (CFW701…
C3…) in IT networks (neutral conductor not grounded or grounded via a high
ohmic value resistor) or in corner-grounded delta systems, it is necessary to
remove some RFI filter components (capacitor for frame sizes A, B, C and
D and capacitor and the MOV for frame size E) connected to the ground by
removing the screws indicated in Figure A.6 on page 142 for inverter frame
sizes A, B, C and D and changing the position of the J1 jumper on the PRT1
board from (XE1) to “NC” (XIT), according to the Figure A.6 on page 142
for inverter frame size E.
AC power supply considerations
Suitable for use on a circuit capable of delivering not more than 100.000 A
Ampères at 240 V, 480 V or 600 V maximum, when protected by Class J fuses (for 240 V
symmetrical
rms
and 480 V models) or special purpose fuses (for 600 V).
In case the CFW701 is installed in power supplies with current capacity higher than 100.000 A
it is necessary to provide adequate protections circuits such as fuses or switches.
rms
3.2.3.2 Dynamic Braking (standard built-in for frame sizes A, B, C and D and
optional built-in for frame size E - CFW701...DB...)
Refer to Table B.1 on page 148, Table B.2 on page 149 and Table B.3 on page 150 for
the following dynamic braking specifications: maximum current, resistance, RMS current and
cable gauges.
The power rating of the dynamic braking resistor is a function of the deceleration time, the load
inertia and the resistant torque.
English
,
Dynamic braking installing procedure:
Install the braking resistor between the power terminals DC+ and BR.
Use twisted cable for the connection. Separate these cables from the signal and control
cables.
Size the cables according to the application, respecting the maximum and effective currents.
If the braking resistor is installed inside the inverter cabinet, consider its additional dissipated
energy when sizing the cabinet ventilation.
The thermal protection of the dynamic braking resistor must be provided externally using a
thermal relay in series with the resistor and/or a thermostat in contact with the resistor frame,
connected so as to switch the input power supply of the inverter, as shown in Figure 3.3 on
page 16.
CFW701 | 15
Installation and Connection
Set P0151 and P0185 to their maximum values (400 V or 800 V) when using dynamic braking.
English
The DC link voltage actuation level of the dynamic braking is set by parameter P0153 (Dynamic
Braking Level).
Power
supply
Control power
supply
3.2.3.3 Output Connections
CFW701
Contactor
R
S
T
BR
Thermal
relay
Thermostat
Figure 3.3: Connection of the braking resistor
DC+
Braking
resi stor
16 | CFW701
ATTENTION!
The inverter has an electronic motor overload protection that shall be adjusted
according to the driven motor. When several motors are connected to the
same inverter, install individual overload relays for each motor.
The motor overload protection available for the CFW701 is in accordance
with UL508C as per the following information:
- Trip current equal to 1.25 times the motor rated current (P0401) adjusted
in the oriented start-up menu.
- The maximum value of P0398 (Motor Service Factor) is 1.15.
- Parameters P0156, P0157 and P0158 (Overload Current at 100 %,
50 % and 5 % of the rated speed, respectively) are automatically adjusted
when the parameters P0401 (Motor Rated Current) and/or P0406 (Motor
Ventilation) are changed on the “Oriented Start-up” menu. If the parameters
P0156, P0157 and P0158 are set manually, the maximum allowed value
is 1.05 x P0401.
Installation and Connection
ATTENTION!
If a disconnect switch or a contactor is installed between the inverter and the
motor, never operate them with a spinning motor or with voltage at the inverter
output.
The characteristics of the cable used for the inverter and motor interconnection, as well as
the physical location are extremely important to avoid electromagnetic interference in other
equipment and to not affect the life cycle of motor windings and motor bearings controlled by
inverters.
Keep motor cables away from other cables (signal cables, sensor cables, control cables, etc.),
according to item 3.2.6 Cable Distances on page 22.
Connect a fourth cable between the motor ground and the inverter ground.
When using shielded cables for connecting the motor:
Follow the recommendations of IEC60034-25.
Use low impedance connection to high frequencies to connect the cable shield to ground.
Using parts supplied with the drive. See item below.
For inverter frame sizes A, B and C there is an accessory called “Shielding kit for power
cables PCSx-01” (see section 7.2 ACCESSORIES on page 37), which can be mounted at
the bottom of the cabinet – the Figure 3.4 on page 17 shows an example. The shielding
kit for power cables PCSx-01 goes along with inverters with optional internal C3 RFI filter
(CFW701...C3...). The grounding for the motor cable shield on inverter frame sizes D and E
is already provided in the standard inverter cabinet. This is also provided on the “Nema1
Kits (KN1x-01)” of the inverter frame sizes A, B and C.
For frame sizes B and C with degree of protection IP55, the accessory "PCSC-03 power
cable shield kit" is available, and for frame size D and E with degree of IP55 use the standard
accessories for shielding. The PCSC-03 shield kit comes with the inverter as optional item N12.
English
Figure 3.4: Motor cable shielding connection with PCSx-01 accessory
CFW701 | 17
Installation and Connection
3.2.4 Grounding Connections
English
DANGER!
The inverter shall be connected to a Protective Ground (PE). Use the minimum ground wiring gauge as indicated in the Table B.1 on page
148 , Table B.2 on page 149 and Table B.3 on page 150.
Connect the inverter grounding connections to a ground bus bar, to a single
ground point, or to a common grounding point (impedance ≤ 10 Ω).
The neutral conductor of the network shall be solidly grounded; however,
this conductor shall not be used to ground the inverter.
It is necessary to use a copper cable with 10 mm
2
minimum or 2 cables with
the same wire gauge as specified in Table B.1 on page 148, Table B.2 on
page 149 and Table B.3 on page 150 for connecting the inverter to the
ground protection to be in accordance with IEC61800-5-1 since the leakage
current is greater than 3.5 mA AC.
DANGER!
Le variateur doit être raccordé à une terre de protection (PE). Utilisez la section minimale de raccordement à la terre indiquée dans les Ta b l e
B.1 à la page 148, Table B.2 à la page 149 et Table B.3 à la page 150.
Connectez la masse du variateur à une barre collectrice de terre en un seul
point ou à un point commun de raccordement à la terre (impédance ≤ 10 Ω).
Le conducteur neutre doit être solidement raccordé à la terre; néanmoins,
ce conducteur ne doit pas s'utiliser pour raccorder le variateur à la terre.
Il est nécessaire d'utiliser un câble de section minimale 10 mm
2
ou 2 câbles
de section identique (voir les Table B.1 à la page 148, Table B.2 à la page
149 et Table B.3 à la page 150 pour raccorder le variateur à la terre
conformément à la norme IEC61800-5-1 du fait que le courant de fuite
alternatif est supérieur à 3.5 mA.
3.2.5 Control Connections
The control connections (analog inputs/outputs and digital inputs/outputs), shall be performed
in connector XC1 of the CC701 control board. Functions and typical connections are presented
in Figure 3.5 on page 20.
18 | CFW701
Installation and Connection
NC
PTC
NC
NC
A - RS-485
B - RS-485
GND
AI3-
AI3+
AI2-
AI2+
DO3
RL2-C
RL2-NA
≥5 kΩ
AI1-
AI1+
REF+
(1) Refer to Figure 3.5 on page 20 for active low digital inputs connection.
REF-
rpm
AO1
amp
AO2
AGND (24 V)
AGND (24 V)
(a) Active high digital inputs
>300 Ω
RL1-C
Active high digital inputs
+24 V
DO4
DO5
>300 Ω
>300 Ω
RL1-NA
COM
+24 V
(1)
GND (24 V)
DI5
DI6
DI7
DI8
English
DI4
DI3
DI2
DI1
GND (24 V)
CFW701 | 19
Installation and Connection
English
Active low digital inputs
+24 V
DI5
DI6
GND (24 V)
DI7
DI8
+24 V
COM
GND (24 V)
DI1
DI2
DI3
DI4
(b) Active low digital inputs
Figure 3.5: (a) and (b) XC1 connection terminals
Refer to Figure A.3 on page 139 to find the control board, the XC1 connector (control
signals), the S1 DIP-switches (to select the type of signal of the analog inputs and outputs)
and S2 (RS-485 network termination) and slots 3 and 5 for accessories (see section 7.2
ACCESSORIES on page 37).
The CFW701 inverters are supplied with the digital inputs configured as active high and the
analog inputs and outputs configured for voltage signal 0...10 V.
NOTE!
To be able to use the analog input and/or output as current signals, it is
necessary to change the switch S1 and the related parameters as per Table
3.1 on page 21. In order to set the analog inputs to bipolar voltage signal
(-10…10 V), it is necessary to set P0233 and P0238 according to Table 3.1 on
page 21. Refer to the CFW701 programming manual for more information.
20 | CFW701
Installation and Connection
Table 3.1: Configuration of the switch for the analog input and output signals selection
Input/
Output
Signal
Voltage S1.2 = OFF
AI1
CurrentS1.2 = ON
Voltage S1.1 = OFF
AI2
CurrentS1.1 = ON
AI3Current
VoltageS1.3 = ON
AO1
CurrentS1.3 = OFF
VoltageS1.4 = ON
AO2
CurrentS1.4 = OFF
(*) Factory setting.
S1 Switch
Settings
Signal
Range
(*)
0…10 V
(*)
-10…10 V P0233 = 4
P0233 = 0 (direct reference) or 2 (reverse reference).
Parameter Settings
0...20 mA P0233 = 0 (direct reference) or 2 (reverse reference).
4...20 mA P0233 = 1 (direct reference) or 3 (reverse reference).
(*)
0…10 V
(*)
-10…10 V P0238 = 4
P0238 = 0 (direct reference) or 2 (reverse reference).
0...20 mA P0238 = 0 (direct reference) or 2 (reverse reference).
4...20 mA P0238 = 1 (direct reference) or 3 (reverse reference).
-0...20 mA P0243 = 0 (direct reference) or 2 (reverse reference).
-4...20 mA P0243 = 1 (direct reference) or 3 (reverse reference).
(*)
0...10 V
(*)
P0253 = 0 (direct reference) or 2 (reverse reference).
0...20 mA P0253 = 0 (direct reference) or 2 (reverse reference).
4...20 mA P0253 = 1 (direct reference) or 3 (reverse reference).
(*)
0...10 V
(*)
P0256 = 0 (direct reference) or 2 (reverse reference).
0...20 mA P0256 = 0 (direct reference) or 2 (reverse reference).
4...20 mA P0256 = 1 (direct reference) or 3 (reverse reference).
NOTE!
Settings of the S2 switch:
S2.1 = ON and S2.2 = ON: RS-485 is ON. S2.1 = OFF and S2.2 = OFF: RS-485 is OFF.
The factory default for the S2.1 and S2.2 switches are OFF.
Other combinations of switch S2 are not allowed.
English
Follow instructions below for the proper installation of the control wiring:
2. Maximum tightening torque: 0.50 N.m (4.50 lbf.in).
3. Use shielded cables for the connections in XC1 and run the cables separated from the remaining
circuits (power, 110 V / 220 Vac control, etc.), according to item 3.2.6 Cable Distances on page
22. If control wiring must cross other cables (power cables for instance), make it cross
perpendicular to the wiring and provide a minimum separation of 5 cm (1.9 in) at the crossing
point.
Refer to item 3.2.6 Cable Distances on page 22, for the proper cable distances.
Isolate with tape
Inverter
side
Do not ground
(a) Cable shield connection
(b) Connection sample of the shield to
ground
Figure 3.6: (a) and (b) Shield connection
CFW701 | 21
Installation and Connection
4. Relays, contactors, solenoids or coils of electromechanical brakes installed close to the
inverter may eventually create interferences in the control circuitry. To eliminate this effect,
RC suppressors (with AC power supply) or free-wheel diodes (with DC power supply) shall
English
be connected in parallel to the coils of these devices.
3.2.6 Cable Distances
The power cables and control cables must be separated (relay output cables and other control
cables) according to Table 3.2 on page 22.
Table 3.2: Cable distances
Rated Output
Inverter Current
≤ 24 A
≥ 28 A
Cable Length(s)
≤ 100 m (330 ft)
> 100 m (330 ft)
≤ 30 m (100 ft)
> 30 m (100 ft)
Minimum Separation
Distance
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
3.3 INSTALLATION ACCORDING TO THE EUROPEAN DIRECTIVE OF
ELECTROMAGNETIC COMPATIBILITY
All inverters have internal C3 RFI filter to reduce electromagnetic interference. These inverters,
when properly installed, meet the requirements of “EMC Directive 2004/108/EC”.
The CFW701 inverter series was developed for professional applications, applying the harmonic
emission limits defined by standards EN 61000-3-2 and EN 61000-3-12. The inverters meet the
EN 61000-3-2 requirements without restrictions and EN 61000-3-12 when installed in networks
with a drop lower than 1%.
3.3.1 Conformal Installation
1. Inverters with built-in C3 RFI filter CFW701...C3...
2. Frame sizes A to D inverters with built-in C3 RFI filter capacitors grounding screws and frame
size E with J1 cable in the position (XE1). For more information see Figure A.6 on page
142 .
3. Shielded output cables (motor cables) and connect the shield at both ends (motor and
inverter) with a low impedance connection for high frequency. Use PCSx-01 kit supplied with
frame sizes A, B and C inverters. For frame sizes B and C with degree of protection IP55,
use the PCSC-03 shield kit. For frame sizes D and E inverters use the clamps supplied with
the product. Ensure good contact between the cable shield and the clamps. Refer to Figure
3.4 on page 17 and keep the proper separation from other cables according to item 3.2.6
Cable Distances on page 22. The maximum motor cable length and conduction and
radiated emission levels are presented at Table B.6 on page 163. Use an external RFI filter
at the input of the inverter if necessary to have a lower emission level and/or a longer motor
cable length. For more information (RFI filter commercial reference, motor cable length and
emission levels) refer to Table B.6 on page 163.
4. Shielded control cables and separate the remaining cables according to item 3.2.6 Cable
Distances on page 22.
5. Inverter grounding according to the instructions on item 3.2.4 Grounding Connections on
page 18.
22 | CFW701
6. Grounded power supply.
3.3.2 Emission and Immunity Levels
Table 3.3: Emission and immunity levels
EMC Phenomenon
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz).
Electromagnetic Radiation Disturbance
Refer to Table B.6 on page 163 for conducted and radiated emission levels accomplished
with and without external RFI filter. The reference model for the external filter is also presented.
CFW701 | 23
Keypad (HMI) and Basic Programming
4 KEYPAD (HMI) AND BASIC PROGRAMMING
4.1 INTEGRAL KEYPAD - HMI-CFW701
English
The integral keypad can be used to operate and program (view / edit all parameters) of the
CFW701 inverter. There are two operation modes in the keypad: monitoring and programming.
The key functions and display indications of the keypad may change according to the operation
mode. The programming mode consists of three levels.
- When in monitoring mode: press
this key to increase the speed.
- When in programming mode, level
1: press this key to go back to the
previous group.
- When in programming mode, level
2: press this key to go to the next
parameter.
- When in programming mode, level
3: press this key to increase the
parameter value.
- When in programming mode, level
1: press this key to go back to the
monitoring mode.
- When in programming mode, level
2: press this key to go back to the
le ve l 1.
- When in programming mode, level
3: press this key to cancel the new
value (the value will not be saved)
and it will return to level 2 of the
programming mode.
- Press this key to define the motor
rotation.
This option is active when:
P0223 = 2 or 3 in LOC and/or
P0226 = 2 or 3 in REM.
- Press this key to change between
LOCAL and REMOTE mode.
This option is active when:
P0220 = 2 or 3.
- Press this key to accelerate the motor up to the speed set in P0122. The motor speed is maintained
while the key is pressed. When the key is released the motor decelerates up to its complete stop.
This function is active when all the following conditions are met:
1. Start/Stop = Stop.
2. General Enable = Active.
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.
(1) Available from the serial number 1023801859.
USB communication port
(1)
Figure 4.1: Operator keys
- When in monitoring mode: press this key
to decrease the speed.
- When in programming mode, level 1: press
this key to go to the next group.
- When in programming mode, level 2:
press this key to go back to the previous
parameter.
- When in programming mode, level 3: press
this key to decrease the parameter value.
- When in monitoring mode: press this key
to enter in the programming mode.
- When in programming mode, level 1: press
this key to select the desired parameter
group – it shows the parameters of the
selected group.
- When in programming mode, level 2: press
this key to show the parameter – it shows
the parameter value for its modification.
- When in programming mode, level 3: press
this key to save the new parameter value
– it returns to level 2 of the programming
mode.
- Press this key to accelerate the motor
according to the acceleration ramp time.
This option is active when:
P0224 = 0 in LOC and/or
P0227 = 0 in REM.
- Press this key to decelerate the motor
according to the deceleration ramp time.
This option is active when:
P0224 = 0 in LOC and/or
P0227 = 0 in REM.
24 | CFW701
NOTE!
It is necessary to set the password at P0000 for parameter modification;
otherwise the parameters contents can only be viewed.
The default password for P0000 is 5. It is possible to change the password at
P0200. Refer to the CFW701 programming manual.
Motor rotation
Local/Remote
(commands and
references source)
Keypad (HMI) and Basic Programming
Inverter status
Menu (parameters
group selection) –
only one parameter
group is shown at
each time.
Main display
Figure 4.2: Display sections
Parameter groups available at the Menu:
PARAM: all parameters.
READ: only the reading parameters.
MODIF: only the parameters changed compared to the factory default.
BASIC: basic application parameters.
MOTOR: parameters related to motor data control.
I/O: parameters related to the digital and analog inputs/outputs.
NET: parameters related to the communication protocol.
HMI: parameters for the keypad configuration.
Secondary display
English
Variable unit
(shows the value of
the main display)
HVAC: parameters related to HVAC application.
STARTUP: parameters for the oriented startup.
Inverter status:
LOC: local reference.
REM: remote reference.
: motor rotation according to the arrows.
CONF: configuration. It indicates that the inverter is in the Oriented Start-up routine or with
incompatible parameter programming. Refer section Incompatibility Between Parameters in
the programming manual of the CFW701.
SUB: DC link undervoltage.
RUN: inverter enabled and/or DC braking activated.
CFW701 | 25
Loading...
+ 155 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.