4.2 MULTIPLE CHOICE SETTINGS VIA MODBUS ..................................................................................37
5 FACTORY DEFAULT SETTINGS 38
6 TECHNICAL SPECIFICATIONS 40
www.weg.net
1 GENERAL INFORMATION
1.1 DEVICE FEATURES
MMW03-M22CH is designed to measure:
Phase-neutral voltages; Phase-phase voltages; Phase current; Neutral current; Frequency; CosØ; Power factors; Active powers; Reactive powers; Apperant powers; THDV; THDI; 1-31 current and voltage harmonics.
Besides, MMW03-M22CH has numerous features such as:
Phase loss information and sequence error display; Determining and saving in the memory of maximum and minimum values of current, voltage, frequency,
cosØ, power factor, THDV, THDI, active, reactive and apparent;
Measuring current, active power, reactive power and apparent power values and saving in the memory; Setting alarm for current, voltage, frequency and power factor parameters; 2 tariff meters. These meters record Import Active, Export Active, Import Reactive, Export Reactive; Storing on hour counter (on hour), run hour counter (total energized time) and power interruption counter; RS485 communication via MODBUS RTU protocol; Digital inputs in order to start counter, 2nd tariff or run hour counter; Digital outputs which can be set to energy meters or counters as output parameters; 2 alarm relay outputs; Avoiding unauthorized control by a 4-digit-password.
MMW03-M22CH
Type of device enclosurePanel
Basic measurements (V, VLL, I, IN, F, Cos l, PF, P, Q, S, THD)l
1-31 Harmonics
Max-Min Value
Demand Values (I, P, Q, S)
On hour, Run Hour, Int
Energy Meters2 tariffs
Assigning alarm to the parameters
Alarm Relay2 Qty
RS485
Digital Input2 Qty
Digital Output2 Qty
Indicators and leds
Order no143 87019
Ta b el a 1.1: Product Features
l
l
l
l
l
l
l
6 | Energy Analyzer - MMW03-M22CH
www.weg.net
1.2 CORRECT USAGE AND CONDITIONS FOR SAFETY
Installation and wiring must be performed by authorized technicians in accordance with the instructions in
the user manual. Do not commission the device before proper wiring.
Make sure the device is de-energized before connecting to the mains. Short circuit the k-l terminals of the current transformer in another location before disconnecting the current
transformers. Failing to do so will cause dangerous high voltages in the secondary terminals of the current
transformers.
Use a dry cloth to clean the device. Do not use alcohol, thinner or any abrasive materials. Make sure all wiring is properly made before commissioning the device. Do not open the device. There are no serviceable parts by the user. Keep the device away from humidity, water, vibrations and dust. It is advisable to connect a circuit breaker or an automatic fuse between the current input of the device and
the mains (2 amps).
CAUTION!
The manufacturer does not assume any responsibility for any undesired consequences if the above measures are not
adhered to.
1.3 PANEL DEFINITIONS
Front Panel
7
6
5
4
3
2
1
89
MMW03
10
11
12
Figura 1.1: MMW03-M22CH Front Panel
1Current and Voltage situation :Indicate phase loss of currents and voltages.
2Sequence error icon:Indicate sequence error of voltages.
3Communication active icon:Indicate that RS485 communication is made.
4Relay icons:Indicate that relays are activated.
5Alarm icon:Indicate that there is alarm on the system.
6Pulse output icons:Indicate that pulse outputs are activated.
Energy Analyzer - MMW03-M22CH | 7
13
www.weg.net
7Energy counter icons:Indicate the type of the counter on the menu bar.
8Counter icon:Indicate the type of the counter on the menu bar.
9Tariff icons :Indicate that the counter of which tariff on the menu bar.
10Menu bar and counter units:Indicate menu names, energy counter and counters and settings.
11Submenu icons :Show that values of which submenu on the indicators.
12 Indicators and units: Indicate measurements, maximum, minimum and demand values and
their units.
13Keys : Use this key to switch between the menus and change the numerical
The menus are shown instantaneous measurements menu and their maximum, minimum, demand, average and
total value at the tables below. The menu pages change with up, down, right and left direction buttons.
1. 4 .1 Key Functions
The buttons placed front panel and their functions are explained at the table below.
At The Energy, Counters,
Harmonics, Settings
Menus
Short
Pressing
(t < 2sec)
Pass to the
one sub-
menu
Changes
the menu
page
Changes
the menu
page
Pass to the
one upper-
menu
Tabe la 1. 2: Key Functions
Long
Pressing
(t > 2sec)
Skips to
bottom
menu
N/A
N/A
Skip to the
last menu
from
Initialize the
Counter
Long
Pressing
(t < 2sec)
Changes
the active
step
Changes
the values
Changes
the value
Stops
changing
value and
confirms
the entering
value
Long
Pressing
(t > 2sec)
Activates
the value
changing
N/A
N/A
N/A
To change the settings
Short
Pressing
(t > 2sec)
Activates
the value
changing or
Changes
the active
step
Changes
the value
Changes
the value
Stops
changing
value and
confirms
the entering
value
Pressing
(t > 2sec)
Long
N/A
N/A
N/A
N/A
Right
button
Down
button
Up button
Left button
At the Measurements
Menus
Short
Pressing
(t < 2sec)
switching
between
menus
switching
between
menus
switching
between
menus
switching
between
menus
Long
Pressing
(t > 2sec)
Skips to
“ENERGY”
menu
N/A
N/A
Skips to
Starting
Page
8 | Energy Analyzer - MMW03-M22CH
www.weg.net
Instantaneous
Value
<Voltage(L-N)>V L- N
<Voltage(L-L)>VL- L
<Current>IMax. I
<I Neutr>
Neutral
Current (In)
<Cosq>
Cos Ø
<PF>
Power
Factor (PF)
INMax. INMin. IN
COS Ø
PF
Max.Min. Demand Avg/Total
COS Ø
Max.
V L- N
Max.
V L- L
Max.
Max.
PF
M i n. V L- N
M i n. V L- LA vg . VL- L
Min. IDemand ITotal I
Min.
COS Ø
Min. PFTotal PF
Avg.
V L- N
Avg max/
Total max
Max.
Avg.
V L- N
Max.
Av g. V L-L
Max
Total I
Max.
Total PF
Avg min/
Total min
Min. Avg.
Min. Avg.
Total I
Min. Total
V L- N
V L- L
Min.
PF
Demand
Demand I
Total
Total
<Power P>
Active
Power (P)
<Power Q>
Reactive
Power(Q)
<Power S>
Apperant
Power (S)
<Σ P-Q-S>
Tot a l Powe r
(Σ P-Q-S)
<Freq>
Frequency(F)
<THD V> THDV
<THD I> Anlık
PMax. PMin. P
Q
SMax. SMin. S
Σ P-Q-S
FMax. FMin. F
Maks.
Q
Max.
Σ
P-Q-S
Max.
THDV
Max.
THDI
Min.
Min. Q
Min.
Σ P-Q-S
THDV
Min.
THDI
Demand
P
Demand
Q
Demand S
Demand
Σ P-Q-S
Total P
Total Q
Total S
Max Total PMin. Total
Max.
Total Q
Max.
Total S
P
Min. Total
Q
Min. Total
S
Total
Demand
P
Total
Demand
Q
Total
Demand
S
Tabe la 1. 3: Menu Switch-1 (Instantaneous Measurement Menus and Sub Menu)
Energy Analyzer - MMW03-M22CH | 9
www.weg.net
ENERGY
(Energy counter
menu)
TARIFF 1
(Tari1 Menu)
IMPORT ACTIVE 1
(Tari-1 Import Active Energy)
EXPORT ACTIVE 1
(Tari-1 Export Active Energy)
IMPORT REACT 1
(Tari-1 Import Reactive Energy)
EXPORT REACT 1
(Tari-1 Export Reactive Energy)
IMPORT ACTIVE 2
(Tari-2 Import Active Energy)
EXPORT ACTIVE 2
(Tari-2 Export Active Energy)
COUNTER
(Counter Menu)
HARMONICS
(Harmonic Menu)
(MMW03-M22CH)
TARIFF 2
(Tari 2 Menu)
COUNTER 1 (Counter 1)
COUNTER 2 (Counter 2)
RUN HOUR (Run Hour Counter )
ON HOUR (On Hour Counter )
POWER INT. COUNTER
(Power Interrupt Counter)
V HARM
(Voltage Harmonics)
IMPORT REACT 2
(Tari-2 Import Reactive Energy)
EXPORT REACT 2
(Tari-2 Export Reactive Energy)
V HARM 1
V HARM 3
.
.
V HARM 31
I HARM 1
SETTINGS
(Settings)
I HARM
(Current Harmonics)
BASIC, ALARMS, RELAYS …
SETTINGS
Tabe la 1.4: Menu Switch-2 (Energy, Counters, Harmonics and Setting Sub-menus)
I HARM 3
.
.
I HARM 31
Energy counters, counters, odd harmonics up to 31st and settings menus are placed at the table above. Menu
switching are made via up, down, right and left direction buttons as stated at the table.
NOTE:
Right button shall be pressed long in order to switch from Table 1-3 to Table 1-4, and.
10 | Energy Analyzer - MMW03-M22CH
www.weg.net
1.5 FOUR QUADRANT REPRESENTATION
The angle(Ø) between voltage and current provides us information about the direction of energy flow. A positive
sign for active/reactive power indicates that active/reactive power is consumed. And also a negative sign for active/
reactive power indicates that active/reactive power is generated.
Reactive Power
QUADRANT-2
P
=> negative
Q
=> positive
CosØ
=> capacitive
PF
=> negative
Meters
Exp. Active &
Imp. Reactive
&
QUADRANT-3
P
=> negative
Q
=> negative & inductive
CosØ
=> inductive
PF
=> negative
capacitive
QUADRANT-1
P
S
Q
P
Q
CosØ
PF
Imp. Active &
Imp. Reactive
=> positive
=> positive
=> inductive
=> positive
Meters
&
inductive
Active Power
QUADRANT-4
P
=> positive
Q
=>
CosØ
PF
negative
=> capacitive
=> positive
&
capacitive
Meters
Exp. Active &
Exp. Reactive
Figura 1.2: Four Quadrant Representation
Meters
Imp. Active &
Exp. Reactive
NOTE:
If the signs of active and reactive power are examined, it can be defined the quadrant that MMW03-M22CH
measures.
In order to understand P and Q signs in MMW03-M22CH 110P and Ecras, instantaneous displays for P and Q
must be checked.
If active power display is seem constantly, it means active power(P) is positive. If it is blinked, it means active
power(P) is negative.
If reactive power(Q) display is seem constantly, it means reactive power(Q) is positive. If it is blinked, it means
reactive power(Q) is negative.
NOTE:
Signs of P and Q can be reached through modbus communication.
Assembly and related connections of the product, must be implemented by authorized persons in accordance with the
instructions of user manual.
DANGER!
The device must not be put into service if the operator is not sure that all connections are correctly accomplished.
2.2 MOUNTING
MMW03-M22CH is placed vertically into the gap located in the panel. After the product is placed into the panel,
fixing brackets should be installed on the product. After that it should be fixed to the panel wall with the screws.
DANGER!
Before wiring up voltage and current ends to MMW03-M22CH, you must be sure that the power is cut.
DANGER!
The product is connected to current transformer(s). Before disconnecting current transformer leads, be sure that they are
short circuited elsewhere or connected to a parallel load which has sufficiently low impedance. Otherwise dangerously high
voltages will be induced at the current transformer leads. Same phenomena also apply for putting into service.
2.3 CONNECTION DIAGRAMS
2. 3 .1 3P-4W and 3p-3W Connections
There are two ways for connections of voltage and current. With neutral (3P-4W), without neutral (3P-3W).
3P-4W (wth neutral) 3P-3W (wthout neutral)
12 | Energy Analyzer - MMW03-M22CH
Figura 2.1: Connection Diagram
CAUTION!
Fi g ure 1-1 1st item, displays current and voltage phase position are On/Off. If a current or voltage phase seems incomplete
and should be checked by the relevant links / connections reached the device.
Fi g ure 1-1 2nd item, if there is an error in the voltage phase during due to incorrect sequence; "Voltage phase sequence
error icon" will appear. If this icon appears; phase-sequence voltage should be checked.
2.3.2 Digital Output Connection Diagram
www.weg.net
DO (-)DO (+)
External DC Power
Supply must be connected.
(5-30VDC)
Figura 2.2: Digital Output Connection Diagram
2.4 DIMENSIONS MMW03-M22CH (MM)
+
-
65,0
Figura 2.3: Dimensions for MMW03-M22CH
Energy Analyzer - MMW03-M22CH | 13
www.weg.net
3 MENUS
3.1 INSTANTANEOUS MEASUREMENT MENUS
Voltage (L-N and L-L), current, neutral current, cosØ, power factor, active power, reactive power, apparent power,
THDV and THDI values are shown in instantaneous menu.
Menu are given the name of which is shown in Menu bar.
The values shown on the display is expressed in what phase or phases at the lower left corner of the display
numbers.
Phase Numbers are not displayed at Menus which display avarege, total and other properties of network. In this
case phases are displayed in 2. Level.
Next to each index value unit of respective rows are indicated. It also states that inductive or capacitive phases
are indicated next to the relevant indicators.
Table 1-3 for parameters displayed in the menus.
POWER Q
Figura 3.1: Instantaneous Measurement Menus (Reactive Power)
CAUTION!
When the product is mounted on a panel which consumes power, active power (P) must be positive. If active power is
negative, operator should cross connect k-l leads of the current transformer.
When the product is mounted on a panel which generates power, active power (P) must be negative. If active power is
positive, operator should cross connect k-l leads of the current transformer.
3.2 MAXIMUM, MINIMUM VE DEMAND MENUS
Minimum and maximum values are calculated and stored in the non-volatile memory for below parameters:
Voltage (phase-neutral, phase-phase); Neutral current; Frequency; CosØ; Power factor; THDV; THDI.
14 | Energy Analyzer - MMW03-M22CH
www.weg.net
Besides maximum and minimum values, demand values are calculated and stored in the non-volatile memory
for below parameters:
Current; Active power; Reactive power; Apparent power.
Table 1-3 shows the menu movements.
NOTE:
The values held in memory can be deleted by selecting "CLEAR" menu in the "SETTINGS’’ menu. Reset and
return to the factory settings can be made with RS 485 communication.
POWER
Figura 3.2: Instantaneous Measurement Menus (Active Power)
3.3 ENERGY METERS MENU (ENERGY)
These tariffs are shown in “Enr” menu. Each tariff has import active, export active, import reactive and export
reactive meters.
Import Active Energy Meter (I.Ac). Export Active Energy Meter (E.Ac). Import Reactive Energy Meter (I.rE). Export Reactive Energy Meter (E.rE).
Energy Analyzer - MMW03-M22CH | 15
www.weg.net
The menu structure is shown below:
ENERGY
(Energy counter
menu)
TARIFF 1
(Tari 1 Menu)
IMPORT ACTIVE 1
(Tari-1 Import Active Energy)
EXPORT ACTIVE 1
(Tari-1 Export Active Energy)
IMPORT REACT 1
(Tari-1 Import Reactive Energy)
EXPORT REACT 1
(Tari-1 Export Reactive Energy)
IMPORT ACTIVE 2
(Tari-2 Import Active Energy)
EXPORT ACTIVE 2
(Tari-2 Export Active Energy)
TARIFF 2
(Tarife 2 Menu)
Ta b el a 3 .1: Energy Meters Menu
The following menu icons are active in “ENERGY” menu:
: This icon appears with Tariff 1 counters.
: This icon appears with Tariff 2 counters.
imp : This icon appears with import energy counters.
exp : This icon appears with export energy counters.
act : This icon appears with active energy counters.
rea : This icon appears with reactive energy counters.
IMPORT REACT 2
(Tari-2 Import Reactive Energy)
EXPORT REACT 2
(Tari-2 Export Reactive Energy)
CAUTION!
Counters are displayed in the format xx xxx xxx kWh / kVArh (See: Figure 3-3). All counters are reset at 99 999 999 kWh /
kVArh andthen start over from zero. It is possible to initialize the counters under the “ENERGY” menu.
16 | Energy Analyzer - MMW03-M22CH
Figura 3.3: Tariff 1 Impor t Active Energy Menu
www.weg.net
CAUTION!
To activate 2.tarif counters, firstly digital counter input type should be selected as 2.tarif ("tr2") and it must take an active
position of the digital input. DI digital input becomes active when GND- ends are shorted. Otherwise 1.tarif is active.
Figura 3.4: Tariff 2 Export Reactive Energy Menu
3.3.1 Assigning Predefined Value for Energy Meters
In any meter menu, press and hold the right key for at least 2 seconds and the respective menu title starts blinking.
Using the right arrow key, move to the digit you want to change and enter the value using the up/down arrows. When
you are done entering the value, confirm using the left arrow key. Move on to the storage procedure to store the
changes you made. (See: 3.6.2 Save Procedure).
CAUTION!
If password protection is enabled, press and hold the right key for at least 2 sec to display the password authentication
page. Enter the password to proceed to the counter assignment.
3.4 COUNTERS MENU (COUNTERS)
There are counters under the “COUNTERS” menu below:
“COUNTER1”: When a digital input 1 is assigned to a counter, it counts the changes in the digital input. The
value is displayed in “COUNTER1” menu.
“COUNTER2”: When a digital input 2 is assigned to a counter, it counts the changes in the digital input. The
value is displayed in “COUNTER2” menu.
“ON HOUR” Counts and displays the total “on” time for the device in hours. “RUN HOUR”: If the digital input type was set to “run hour enable”, it counts the time elapsed during the
digital input is in active position. This counter requires signal from 3- phase voltage and 3-phase current
inputs to function without connecting to a digital input. The measured value is displayed in hours.
“POWER INTERRUPTION COUNTER”: Counts the power interruptions for the device.
“POWER INTERRUPTION COUNTER”: Counts the power interruptions for the device.
The menu structure is shown below:
Energy Analyzer - MMW03-M22CH | 17
www.weg.net
COUNTER 1 (Counter 1)
COUNTER 2 (Counter 2)
COUNTER
(Counter Menu)
Tab e l a 3 .2: Counters Menu Structure
RUN HOUR (Run Hour Countersı)
ON HOUR (On Hour Countersı)
POWER INT. COUNTER
(Power Interrupt Counter)
Counters showing the following icons on the “COUNTERS” menu is active:
cnt1 :This icon appears with “COUNTER1” counter;
cnt2 :This icon appears with “COUNTER2” counter;
run :This icon appears with “RUN HOUR” counter;
on :This icon appears with “ON HOUR” counter;
int :This icon appears with “POWER INTERRUPTION COUNTER” counter.
Figura 3.5: COUNTER2 Menu
CAUTION!
Counters are displayed as 8 digits. All counters are reset at 99 999 999 and then start over from zero.
Only “COUNTER1”, “COUNTER2” and “RUN HOUR” counters can be assigned values or reset.
Use the procedure for assigning default values to assign values to counters.
See: 3.3.1 Save Procedure.
When the energy meters are displayed instantaneously, last measured parameters (such as voltage, current, active power
values etc.) are continued to display under the energy meter value as well.
3.5 SETTINGS MENU (SETTINGS)
MMW03-M22CH setings are made in the SETTINGS menu. Table 3-3 shows the SETTINGS menu tree.
18 | Energy Analyzer - MMW03-M22CH
MenuSub Menu 1Sub Menu 2 Sub Menu 3 Sub Menu 4Description
Settings
Basic settings
CtrCurrent transformer rate
BASIC
UtrVoltage transformer rate
Connection type options
Conn
3P4W3P4W connection type
3P3W3P3W connection type
Alarm setup
Voltage (phase-neutral) alarm setup
HIVoltage (phase-neutral) alarm high limit
www.weg.net
SETTINGS
ALARMS
VLN ALM
VLL ALM
I ALM
IN ALM
LOVoltage (phase-neutral) alarm low limit
hYS tVoltage (phase-neutral) alarm hysteresis value
dl Y.tVoltage (phase-neutral) alarm delay time
Voltage (phase-phase) alarm setup
HIVoltage (phase-phase) alarm high limit
LOVoltage (phase-phase) alarm high low limit
hYS tVoltage (phase-phase) alarm hysteresis value
dl Y.tVoltage (phase-phase) alarm delay time
Current alarm setup
HICurrent alarm high limit
LOCurrent alarm low limit
hYS tCurrent alarm hysteresis value
dl Y.tCurrent alarm delay time
Neutral current alarm setup
HINeutral current alarm high limit
LONeutral current alarm low limit
hYS tNeutral current hysteresis value
COSQ
ALM
PF ALM
dl Y.tNeutral current alarm delay time
Cos φ alarm setup
HICos φ alarm high limit
LOCos φ alarm low limit
hYS tCos φ alarm hysteresis value
dl Y.tCos φ alarm delay time
Power factor alarm setup
HIPower factor alarm high limit
LOPower factor alarm low limit
hYS tPower factor alarm hysteresis value
dl Y.tPower factor alarm delay time
Energy Analyzer - MMW03-M22CH | 19
www.weg.net
MenuSub Menu 1Sub Menu 2 Sub Menu 3 Sub Menu 4Description
Frequency alarm setup
HIFrequency alarm high limit
SETTINGS
ALARMSFREQ ALM
rLY1
RE L AYS
rLY2
Demand setup
DEMAND
dEd.tDemand time setup
bAudBaud rate options
IdSlave ID setup
LOFrequency alarm low limit
hYS tFrequency alarm hysteresis value
dl Y.tFrequency alarm delay time
Relay output setup
Relay 1 setup
OFFRelay 1 OFF
LOWAssign relay 1 to level low alarms
HIGHAssign relay 1 to level high alarms
Relay 2 setup
OFFRelay 2 OFF
LOWAssign relay 2 to level low alarms
HIGHAssign relay 2 to level high alarms
RS485 setup
RS485
DI INPUT
PrYt
INPUT1
Parity check setup
NONEParity check off
EVENEven parity
ODDOdd parity
Digital input setup
Digital input 1 setup
Digital input 1 options
OFFOff
tYPE
dLYDigital input 1 detection delay time
EdgE
TAR I F F 2Enable tariff 2
COUNTEREnable counter
RUN HOUREnable Run Hour
Digital input 1 detection edge
RISINGDetection in rising edge
FALLINGDetection in falling edge (Only valid for counter)
BOTH EDGDetection in both edges (Only valid for counter)
20 | Energy Analyzer - MMW03-M22CH
MenuSub Menu 1Sub Menu 2 Sub Menu 3 Sub Menu 4Description
Digital input 2 setup
Digital input 2 options
OFFOff
www.weg.net
SETTINGS
DI INPUTINPUT2
PULSE
OUT1
tYPE
dLYDigital input 2 detection delay time
EdgE
OUT
TAR I F F 2Enable tariff 2
COUNTEREnable counter
RUN HOUREnable Run Hour
Digital input 2 detection edge
RISINGDetection in rising edge
FALLINGDetection in falling edge (Only valid for counter)
BOTH EDGDetection in both edges (Only valid for counter)
Pulse output setup
Pulse output 1 setup
Pulse output 1 parameter setup
OFFOff
IMP ACT1Assign to tariff 1 import active energy counter
EX P ACT1Assign to tariff 1 export active energy counter
IMP RE A1Assign to tariff 1 import reactive energy counter
EX P R E A1Assign to tariff 1 export reactive energy counter
IMP ACT2Assign to tariff 2 import active energy counter
EXP ACT2Assign to tariff 2 export active energy counter
PULSE
OUT1
OUT2
IMP REA2Assign to tariff 2 import reactive energy counter
EXP REA2Assign to tariff 2 export reactive energy counter
DIN1Assign to digital input 1 counter
OUT
DIN2Assign to digital input 2 counter
durAPulse duration of the pulse output 1
rAtStep range for pulse output 1
Pulse duration of the pulse output 2
Step range for pulse output 2
OFFOff
IMP ACT1Assign to tariff 1 import active energy counter
EX P ACT1Assign to tariff 1 export active energy counter
IMP RE A1Assign to tariff 1 import reactive energy counter
EX P R E A1Assign to tariff 1 export reactive energy counter
OUT
IMP ACT2Assign to tariff 2 import active energy counter
EXP ACT2Assign to tariff 2 export active energy counter
IMP REA2Assign to tariff 2 import reactive energy counter
EXP REA2Assign to tariff 2 export reactive energy counter
DIN1Assign to digital input 1 counter
DIN2Assign to digital input 2 counter
Energy Analyzer - MMW03-M22CH | 21
www.weg.net
MenuSub Menu 1Sub Menu 2 Sub Menu 3 Sub Menu 4Description
SETTINGS
PULSEOUT2
SECURITY
DI S P L AY
MENU
durAPulse duration of the pulse output 2
rAtStep range for pulse output 2
Password protection setup
ActEnable/disable password protection
NOpassword protection disable
YESpassword protection enable
Timeout for password protection. If you do press any
keys after entering the password or do not change
Pin.t
PinPassword value
ScrL
Sc r. PMenu display time
Strt
OFFMenu scroll disable
ONMenu scroll enable
VOLTAGELNHome page Voltage(L-N)
VOLTAGELLHome page Voltage(L-L)
any settings via MODBUS, password protection is re-
enabled after the time has elapsed.
Secreen setup
Menu setup
Menu scroll setup
Home page setup
DI S P L AY
MENUStrt
BACKLGHT
CURRENTHome page Current
I NEUTRHome page Neutral Current
COSQHome page CosQ
PFHome page Power Factor
POWER PHome page Active Power
POWER QHome page Reactive Power
POWER SHome page Apperant Power
φ P-Q-SHome page Total Power
FREQHome page Frequency
THD VHome page THDV
THD IHome page THDI
Display backlight setup
Display backlight options
oPt
durADisplay backlight always on time
TIME DEPDisplay backlight depending on the time
CONT ONDisplay backlight always on
CONT OFFDisplay backlight always off
22 | Energy Analyzer - MMW03-M22CH
MenuSub Menu 1Sub Menu 2 Sub Menu 3 Sub Menu 4Description
Clear Menu
CLr
OFFClear abort
ALLReset the device to factory settings
ENERGYClear the energy counters
COUNTERSClear the counters
CLEAR
SETTINGS
INFO
UErFirmware version information
MA X VALSClear the max. values
MIN VALSClear the min. values
DEMANDSClear the demand values
SETTINGSReset the setup to factory settings
ALARMS
KLEA 220P
POWYS
3121
Tab e l a 3 .3: SETTINGS Menu
Reset the alarm setup to factory settings
Information
www.weg.net
3.5.1 Basic Settings Menu (BASIC)
This is the menu item where you make the current transformer ratio, voltage transformer ratio and connection
type settings. Please see Table 3-3 for the menu tree and SECTION 5 for the menu tree and Section 5 for the
factory default settings.
Current transformer ratio (Ctr): The calculated currents are multiplied by the current transformer ratio (Ctr) to
be indicated on the displays and the modbus addresses.
Voltage transformer ratio (Utr): The calculated voltages are multiplied by the voltage transformer ratio (Utr) to be
indicated on the displays and the modbus addresses.
Connection (Conn): This menu is for the network connection settings.
If “3P4W” (3-phase, 4-wire connection type) was specified for the network connection setup, the initial menu is
“Voltage (Phase-Neutral)”. This menu is displayed first when the device is energized.
If “3P3W” (3-phase, 3-wire connection type) was specified for the network connection setup, the initial menu is
“Voltage (Phase-Phase)”. This menu is displayed first when the device is energized.
3.5.2 Alarm Settings Menu (ALARMS)
Use this menu item to set the alarm limits, hysteresis value and alarm delay time. Please see Table 3-3 for the
menu tree and SECTION 5 for the factory default settings.
CAUTION!
Outside the alarm limits:
- The values which are belong to adjusted alarm parameter, start flashing.
- When alarm delay time is expired, ( ) symbol is displayed in main scren.
- If relay outputs are assigned to any alarm and also if there is an alarm in the system, related relay symbols (
displayed in the main screen after alarm delay time.
Energy Analyzer - MMW03-M22CH | 23
) are
www.weg.net
Amplitude
High limit
Hysteresis %
Hysteresis %
Low limit
B
A
Figura 3.6: Alarm Example
C
Time
A low limit alarm occurs at point A. Alarm disappears at point B. A high limit alarm occurs at point C. Alarm disappears at point D.
3.5.3 Alarm Relay Settings Menu (RELAYS) (MMW03-M22CH)
Use this menu item to set the conditions of the alarm relays. You can set both alarm relays to the following positions:
OFF : Relay does not energize in an alarm condition; LO : Relay energizes when a low limit alarm occurs; HI : Relay energizes when a high limit alarm occurs.
Related relay is de-energized when the alarm condition ends. Please see Table 3-3 for the menu tree and SECTION
5 for the factory default settings.
3.5.4 Demand Period Setting Menu (DEMAND)
Use this menu item to setup the demand period. At the end of the specified period, demand values are calculated
in a periodic cycle.
Please see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
3.5.5 RS485 Settings Menu (RS485)
Use this menu item to set the baudrate, slave ID and parity control settings in RS485 communication. Please see
Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
Baudrate (bAud): Communication Signal speed is expressed with "baud" in terms of units. The baud rate can
be changed in the adjustment range.
Slave ID (Id): RS485 communication is working on the basis of one or more slave devices communicate with
one master. MMW03-M22CH, as a slave in the RS485 communication responds to queries made by the master.
If the device is slave match in this communication are set in the slave ID Menu.
Parity Check (PrtY): It is a control mechanism for data accuracy. It counts odds ‘’1’’ in Binary data. There are
"odd" and "even" parity control method. For communication, master and slave devices must be using the same
method. The desired method is selected from the menu or "NONE" option selected to make parity check feature
turned off.
3.5.6 3.5.6 Digital Input Settings Menu (DI INPUT)
Use this menu item to set the on/off position, type, delay time and detection edge for the digital input. Please see
Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
24 | Energy Analyzer - MMW03-M22CH
www.weg.net
CAUTION!
Digital input is based on dr y contact detection principle. Never apply signal to inputs. Otherwise there is risk of damaging
the device.
Digital input type (tYPE):
Option to enable tariff 2 (TARIFF 2): If you choose this option for the digital input type, tariff2 energy counters
will be enabled when the digital input is active (dry contact must be applied from related DIN+ and DIN-).
Option to enable the counter (COUNTER): If you choose this option for the digital input type, the counter will
count the changes in the position of the digital input depending on the chosen detection edge.
If you choose rising edge detection (RISING) for the detection edge, the counter will increase by 1 on each
activation of the dry contact that is connected to the digital input.
If you choose falling edge detection (FALLING) for the detection edge, the counter will increase by 1 on each
de-activation of the dry contact that is connected to the digital input.
If you choose both edges detection (BOTH EDGE) for the detection edge, the counter will increase by 1 on
each activation and de-activaton of the dry contact that is connected to the digital input.
Run Hour enable option (RUN HOUR): If you choose this option for the digital input type, the “run hour
counter” start counting when the digital input is active. (Dry contact must be applied from related DIN+ and
DIN-).
Detection delay time (dLY):
The input is enabled or disabled based on the detection delay time which is set to account for contact spikes or
noise in the digital input.
Detection edge (EdgE):
Use this menu item to choose the position where the digital input is detected active or passive. This menu is
available only for the digital input mode “counter”. Other options always use the rising edge detection.
3.5.7 Pulse Output Settings Menu (PULSE)
Use this menu item to specify the on/off position, output parameter, pulse duration and step range settings for
the pulse outputs. You can freely choose the settings for each pulse output independent of each other. Please
see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
The pulse output is activated with an increase in the predefined output parameter that is equal to each step range
and deactivates after the predefined time.
Output parameter setup (OUT):
Use this menu item to set the parameter dependency of the output. The respective output is closed when you
choose “OFF”.
Pulse duration setup (durA):
Use this menu item to specify the time the pulse is active.
Pulse step range (rAt):
Use this menu to specify the smallest possible increase for the input parameter that will
output a pulse.
3.5.8 Password Settings Menu (SECURITY)
Use this menu item to turn the password protection on/off, set a password activation time and change password
settings editing options. Please see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
4 digit password protects the product setup and counter menus against unauthorized access and modifications.
When activated, a password query screen is displayed if someone attempts to change the values. After a successful
login, the device will not ask for a password until the “password activation time” has elapsed. You can set this value in
the respective menu item. Please see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.
Energy Analyzer - MMW03-M22CH | 25
www.weg.net
CAUTION!
If you do not press any keys after entering the password or do not change the settings via MODBUS, password protection
is re-enabled after the password activation time has elapsed.
3.5.9 Display Setup (DISPLAY)
The settings about menu screen and backlight are made in this menu.
Menu Setup (MENU):
Menu scroll setting, display time and start page are made in this sub-menu:
Menu scroll setup (ScrL): Menu Navigation is given as a name to command which is moving menu screen to
next one at the end of display time. If "ON" is selected, menu navigation is activated after device start or 15
seconds after the last key is pressed.
Menu display period (Scr.P): Each menu appears in the screen during the period that is adjusted in “menu
display time”. The unit is second and it is effective when menu scroll mode is “on”. It is ineffective when
menu scroll mode is “off”.
Home page setup (Strt): When the device is first energized, first screen menu is called Menu opening page.
Any of this menu can be set from available instantaneous measurements Menu as Home page. Pre value
"VOLTAGELN" menu is designated as Home page.
Display Backlight Setup (BACKLGHT)
Is subhead which lets adjustment of display backlight options and duration of backlight.
l Display backlight options (oPt): This menu is adjustment of display backlight activation depending on the
time (TIME DEP), always on (CONT ON) or permanently closed (CONT OFF).
Time Dependent (TIME DEP): Backlight is turned on with device operates or with a pressing any key. Display
backlight will be turned off if there is no pressing any key after set time. It is preferred to have longer-lasting
power-saving and LED lighting.
Continuous ON (CONT ON): Display backlight stays on permanently. Continuous OFF (CONT OFF): Display backlight is permanently closed. Display Backlight On Time (durA): Menu is where screen backlight time period is set with unit of second.
Display Backlight On Time (durA): Menu is where screen backlight time period is set with unit of second.
3.5.10 Clear Menu (CLEAR)
Use this menu to delete the stored values in the memory and restore the factory settings. Please see Table 3-3
for the menu tree and SECTION 5 for the factory default settings.
The following options are available in the clear menu:
OF : Disables the clear process. ALL : Clears all values stored in the memory and restores them to the default factory settings. ENERGY : Resets all energy counters. COUNTERS : Resets all counters. MAX VALS : Clears the maximum values stored in the memory. MIN VALS : Clears the minimum values stored in the memory. DEMAND : Clears the demand values stored in the memory. SETTINGS : Restores all settings to the factory settings. ALARMS : Restores the alarm settings to the factory settings.
In order to prevent an accidental deletion, “NO” / “YES” prompt is displayed if you choose any option other than
“OFF” 3.6.3 Approval Prosedure:
To confirm the action:
Press the right key to blink the “NO” sign. Use the up/down keys to change the “NO” to “YES”. Then, press
the left key to confirm the action.
To discard the action:
Press the right key to blink the “NO” sign. Then, press the left key to confirm the “NO” option and exit the
menu without making any deletions.
26 | Energy Analyzer - MMW03-M22CH
www.weg.net
CAUTION!
The device restarts if you choose SETINGS, ALARM or All and confirm the action. It will not restart if you choose other
options. It will clear the values and returns back to the CLEAR menu.
3.6 SAVE, CHANGING VALUE AND APPROVAL PROCEDURE
3.6 .1 Changing Value/Setting
SETTINGS
BASIC
Menu titles in the menu "SETTINGS" are displayed in the menu bar. When the submenus are entered into, the
menu in which the change will occur is shown in the indicator in the first row and the value belonging the related
setting is shown in the menu bar and the change may be made here.
There are 2 different menus for changing the values:
Multiple choice menus: These menus contain predefined options. Press the right key to choose and blink
the first variable of the menu. Press the up/down keys to choose and blink the desired option. Then press
the left button to complete your choice.
Menus with numerical input values: In these menus, move through the digits to set the desired value. Press
the right key to choose and blink the first digit of the variable from the left. Use the right key to move through
the digits. Use the up/down keys to increase/decrease the value of the active digit. Set the desired values for
variables by setting the individual digit values and press the left key to complete your action.
CAUTION!
If any change is made on settings, a registration procedure which is questioning whether or not to record the change will be
active after return to "settings" menu. If the changes are saved, device restarts. See: 3.6.2 Save Prosedure.
3.6.2 Save Procedure
Press the left key until you see the “SAVE” display to confirm or discard the changes you made.
To confirm the changes:
Press the right key to blink the “NO” sign. Use the up/down keys to change the “NO” to “YES”. Then, press the left
key to store the changes.
YES
SAVE
To discard the changes:
Press the right key to blink the “NO” sign. Then exit the menu using the left key without saving your changes.
NO
SAVE
Energy Analyzer - MMW03-M22CH | 27
www.weg.net
3.6.3 Approval Procedure
Following query screen comes up to confirm the action or to reject. To confirm the changes:
YES
To discard the changes:
Press the right key to blink the “NO” sign. Then exit the menu using the left key without saving your changes.
NO
CAUTION!
In the Delete Menu SETTINGS ALL or ALARMS option shuts down the device after the approval of the selected transactions
will be reopened. Other options for the restart process is not performed. The device returns to the CLEAR menu and perform
the deletion.
28 | Energy Analyzer - MMW03-M22CH
www.weg.net
4 RS485 COMMUNICATION
4.1 READABLE AND WRITABLE DATA
The following functions are supported:
Function 03H: This function reads the readable addresses in the modbus table. Function 10H: This function writes to the writable addresses in the modbus table.
Specifications:
R / W : Can read and write the value in this address. RO : Can only read the value in this address. WO : Can only write to this address. float : 32 bit floating number.
Related modbus table is given below:
Adress Parametre Type Read / WriteWrite Condition
Faz 1 Basic Measurements
0Phase 1 Voltage (L-N)floatRO
2Phase 1-2 Voltage (L-L)floatRO
4Phase 1 CurrentfloatRO
6
8Phase 1 Power FactorfloatRO
40Phase 3 Voltage (L-N)floatRO
42Phase 3-1 Voltage (L-L)floatRO
44Phase 3 CurrentfloatRO
46
48Phase 3 Power FactorfloatRO
50Phase 3 Active PowerfloatRO
52Phase 3 Reactive PowerfloatRO
54Phase 3 Apparent PowerfloatRO
56Phase 3 THDVfloatRO
58Phase 3 THDIfloatRO
60Average Voltage (L-N)floatRO
62Average Voltage (L-L)floatRO
64Total CurrentfloatRO
66System Power FactorfloatRO
68Total Active PowerfloatRO
70Total Reactive PowerfloatRO
72Total Apparent PowerfloatRO
74System FrequencyfloatRO
76Neutral CurrentfloatRO
Phase 1 Cosφ
Phase -2 Basic Measurements
Phase 2 Cosφ
Phase -3 Basic Measurements
Phase 3 Cosφ
Common Measurements (Phase-1, Phase-2, Phase-3)
floatRO
floatRO
floatRO
Energy Analyzer - MMW03-M22CH | 29
www.weg.net
Adress Parametre Type Read / WriteWrite Condition
Phase-1 Voltage Harmonic Measurements (MMW03-M22CH)
78Phase 1 Voltage Harmonics 1floatRO
80Phase 1 Voltage Harmonics 3floatRO
82Phase 1 Voltage Harmonics 5floatRO
84Phase 1 Voltage Harmonics 7floatRO
86Phase 1 Voltage Harmonics 9floatRO
88Phase 1 Voltage Harmonics 11floatRO
90Phase 1 Voltage Harmonics 13floatRO
92Phase 1 Voltage Harmonics 15floatRO
94Phase 1 Voltage Harmonics 17floatRO
96Phase 1 Voltage Harmonics 19floatRO
98Phase 1 Voltage Harmonics 21floatRO
100Phase 1 Voltage Harmonics 23floatRO
102Phase 1 Voltage Harmonics 25floatRO
104Phase 1 Voltage Harmonics 27floatRO
106Phase 1 Voltage Harmonics 29floatRO
108Phase 1 Voltage Harmonics 31floatRO
Phase-1 Current Harmonic Measurements (MMW03-M22CH)
110Phase 1 Current Harmonics 1floatRO
112Phase 1 Current Harmonics 3floatRO
114Phase 1 Current Harmonics 5floatRO
116Phase 1 Current Harmonics 7floatRO
118Phase 1 Current Harmonics 9floatRO
120Phase 1 Current Harmonics 11floatRO
122Phase 1 Current Harmonics 13floatRO
124Phase 1 Current Harmonics 15floatRO
126Phase 1 Current Harmonics 17floatRO
128Phase 1 Current Harmonics 19floatRO
130Phase 1 Current Harmonics 21floatRO
132Phase 1 Current Harmonics 23floatRO
134Phase 1 Current Harmonics 25floatRO
136Phase 1 Current Harmonics 27floatRO
138Phase 1 Current Harmonics 29floatRO
140Phase 1 Current Harmonics 31floatRO
Phase-2 Voltage Harmonic Measurements (MMW03-M22CH)
142Phase 2 Voltage Harmonics 1floatRO
144Phase 2 Voltage Harmonics 3floatRO
146Phase 2 Voltage Harmonics 5floatRO
148Phase 2 Voltage Harmonics 7floatRO
150Phase 2 Voltage Harmonics 9floatRO
152Phase 2 Voltage Harmonics 11floatRO
154Phase 2 Voltage Harmonics 13floatRO
156Phase 2 Voltage Harmonics 15floatRO
158Phase 2 Voltage Harmonics 17floatRO
160Phase 2 Voltage Harmonics 19floatRO
162Phase 2 Voltage Harmonics 21floatRO
164Phase 2 Voltage Harmonics 23floatRO
166Phase 2 Voltage Harmonics 25floatRO
168Phase 2 Voltage Harmonics 27floatRO
170Phase 2 Voltage Harmonics 29floatRO
172Phase 2 Voltage Harmonics 31floatRO
Phase-2 Current Harmonic Measurements (MMW03-M22CH)
174Phase 2 Current Harmonics 1floatRO
176Phase 2 Current Harmonics 3floatRO
178Phase 2 Current Harmonics 5floatRO
180Phase 2 Current Harmonics 7floatRO
182Phase 2 Current Harmonics 9floatRO
184Phase 2 Current Harmonics 11floatRO
186Phase 2 Current Harmonics 13floatRO
188Phase 2 Current Harmonics 15floatRO
190Phase 2 Current Harmonics 17floatRO
192Phase 2 Current Harmonics 19floatRO
30 | Energy Analyzer - MMW03-M22CH
www.weg.net
Adress Parametre Type Read / WriteWrite Condition
194Phase 2 Current Harmonics 21floatRO
196Phase 2 Current Harmonics 23floatRO
198Phase 2 Current Harmonics 25floatRO
200Phase 2 Current Harmonics 27floatRO
202Phase 2 Current Harmonics 29floatRO
204Phase 2 Current Harmonics 31floatRO
Phase-3 Voltage Harmonic Measurements (MMW03-M22CH)
206Phase 3 Voltage Harmonics 1floatRO
208Phase 3 Voltage Harmonics 3floatRO
210Phase 3 Voltage Harmonics 5floatRO
212Phase 3 Voltage Harmonics 7floatRO
214Phase 3 Voltage Harmonics 9floatRO
216Phase 3 Voltage Harmonics 11floatRO
218Phase 3 Voltage Harmonics 13floatRO
220Phase 3 Voltage Harmonics 15floatRO
222Phase 3 Voltage Harmonics 17floatRO
224Phase 3 Voltage Harmonics 19floatRO
226Phase 3 Voltage Harmonics 21floatRO
228Phase 3 Voltage Harmonics 23floatRO
230Phase 3 Voltage Harmonics 25floatRO
232Phase 3 Voltage Harmonics 27floatRO
234Phase 3 Voltage Harmonics 29floatRO
236Phase 3 Voltage Harmonics 31floatRO
Phase-2 Current Harmonic Measurements (MMW03-M22CH)
238Phase 3 Current Harmonics 1floatRO
240Phase 3 Current Harmonics 3floatRO
242Phase 3 Current Harmonics 5floatRO
244Phase 3 Current Harmonics 7floatRO
246Phase 3 Current Harmonics 9floatRO
248Phase 3 Current Harmonics 11floatRO
250Phase 3 Current Harmonics 13floatRO
252Phase 3 Current Harmonics 15floatRO
254Phase 3 Current Harmonics 17floatRO
256Phase 3 Current Harmonics 19floatRO
258Phase 3 Current Harmonics 21floatRO
260Phase 3 Current Harmonics 23floatRO
262Phase 3 Current Harmonics 25floatRO
264Phase 3 Current Harmonics 27floatRO
266Phase 3 Current Harmonics 29floatRO
268Phase 3 Current Harmonics 31floatRO
330Max. Average Voltage (L-N)floatRO
332Max. Average Voltage (L-L)floatRO
334Max. Total CurrentfloatRO
336Max. System Power FactorfloatRO
338Max. Total Active PowerfloatRO
340Max. Total Reactive PowerfloatRO
342Max. Total Apparent PowerfloatRO
344Max. System FrequencyfloatRO
346Max. Neutral CurrentfloatRO
348Phase 1 Min. Voltage (L-N)floatRO
350Phase 1-2 Min. Voltage (L-L)floatRO
352Phase 1 Min. CurrentfloatRO
354
356Phase 1 Min. Power FactorfloatRO
358Phase 1 Min. Active PowerfloatRO
360Phase 1 Min. Reactive PowerfloatRO
362Phase 1 Min. Apparent PowerfloatRO
364Phase 1 Min. THDVfloatRO
366Phase 1 Min. THDIfloatRO
368Phase 2 Min. Voltage (L-N)floatRO
370Phase 2-3 Min. Voltage (L-L)floatRO
372Phase 2 Min. CurrentfloatRO
374
376Phase 2 Min. Power FactorfloatRO
378Phase 2 Min. Active PowerfloatRO
380Phase 2 Min. Reactive PowerfloatRO
382Phase 2 Min. Apparent PowerfloatRO
384Phase 2 Min. THDVfloatRO
386Phase 2 Min. THDIfloatRO
388Phase 3 Min. Voltage (L-N)floatRO
390Phase 3-1 Min. Voltage (L-L)floatRO
392Phase 3 Min. CurrentfloatRO
394
396Phase 3 Min. Power FactorfloatRO
398Phase 3 Min. Active PowerfloatRO
400Phase 3 Min. Reactive PowerfloatRO
402Phase 3 Min. Apparent PowerfloatRO
404Phase 3 Min. THDVfloatRO
406Phase 3 Min. THDIfloatRO
408Min. Average Voltage (L-N)floatRO
410Min. Average Voltage (L-L)floatRO
412Min. Total CurrentfloatRO
414Min. System Power FactorfloatRO
416Min. Total Active PowerfloatRO
418Min. Total Reactive PowerfloatRO
420Min. Total Apparent PowerfloatRO
Phase 3 Max. Cosφ
Maximum Common Measurements (Phase-1, Phase-2, Phase-3)
Phase-1 Maximum Measurements
Phase 1 Min. Cosφ
Phase-2 Maximum Measurements
Phase 2 Min. Cosφ
Phase-3 Maximum Measurements
Phase 3 Min. Cosφ
Minimum Common Measurements (Phase-1, Phase-2, Phase-3)
floatRO
floatRO
floatRO
floatRO
32 | Energy Analyzer - MMW03-M22CH
www.weg.net
Adress Parametre Type Read / WriteWrite Condition
422Min. System FrequencyfloatRO
424Min. Neutral CurrentfloatRO
Alarm Flags (MMW03-M22CH)
426Alarm Flags32 bit integerROSee Table 4.2
Demand Measurements
428Phase 1 Current DemandfloatRO
430Phase 2 Current DemandfloatRO
432Phase 3 Current DemandfloatRO
434Total Current DemandfloatRO
436Phase 1 Active Power DemandfloatRO
438Phase 2 Active Power DemandfloatRO
440Phase 3 Active Power DemandfloatRO
442Total Active Power DemandfloatRO
444Phase 1 Reactive Power DemandfloatRO
446Phase 2 Reactive Power DemandfloatRO
448Phase 3 Reactive Power DemandfloatRO
450Total Reactive Power DemandfloatRO
452Phase 1 Apparent Power DemandfloatRO
454Phase 2 Apparent Power DemandfloatRO
456Phase 3 Apparent Power DemandfloatRO
458Total Apparent Power DemandfloatRO
Digital Input
460Digital Input 1 Counter32 bit integerR / WIf password protection is active, enter the
462Digital Input 2 Counter32 bit integerR / W
464Run Hour Counter32 bit integerR / W
466On Hour Counter32 bit integerRO
468Power Interruptions Counter32 bit integerRO
Energy Meters
Tariff 1 Total Energy Values (Phase1+Phase2+Phase3)
470Import Active Energy T1 (Tariff 1)32 bit integerR / W
472Export Active Energy T1 (Tariff 1)32 bit integerR / W
474Import Reactive Energy T1 (Tariff 1)32 bit integerR / W
476Export Reactive Energy T1 (Tariff 1)32 bit integerR / W
Tariff 2 Total Energy Values (Phase1+Phase2+Phase3)
478Import Active Energy T2 (Tariff 2)32 bit integerR / W
480Export Active Energy T2 (Tariff 2)32 bit integerR / W
482Import Reactive Energy T2 (Tariff 2)32 bit integerR / W
484Export Reactive Energy T2 (Tariff 2)32 bit integerR / W
Tariff 1 Phase1 Energy Values
486Import Active Energy T1-Phase1 (Tariff 1)32 bit integerR / W
488Export Active Energy T1-Phase1 (Tariff 1)32 bit integerR / W
490Import Reactive Energy T1-Phase1 (Tariff 1)32 bit integerR / W
492Export Reactive Energy T1-Phase1 (Tariff 1)32 bit integerR / W
Tariff 1 Phase 2 Energy Values
494Import Active Energy T1-Phase2 (Tariff 1)32 bit integerR / W
496Expor t Active Energy T1-Phase2 (Tariff 1)32 bit integerR / W
498Import Reactive Energy T1-Phase2 (Tariff 1)32 bit integerR / W
500Export Reactive Energy T1-Phase2 (Tariff 1)32 bit integerR / W
Tariff 1 Phase 3 Energy Values
502Import Active Energy T1-Phase3 (Tariff 1)32 bit integerR / W
504Export Active Energy T1-Phase3 (Tariff 1)32 bit integerR / W
506Import Reactive Energy T1-Phase3 (Tariff 1)32 bit integerR / W
508Export Reactive Energy T1-Phase3 (Tariff 1)32 bit integerR / W
Tariff 2 Phase 1 Energy Values
510Import Active Energy T2-Phase1 (Tariff 2)32 bit integerR / W
512Export Active Energy T2-Phase1 (Tariff 2)32 bit integerR / W
514Import Reactive Energy T2-Phase1 (Tariff 2)32 bit integerR / W
516Export Reactive Energy T2-Phase1 (Tariff 2)32 bit integerR / W
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
Energy Analyzer - MMW03-M22CH | 33
www.weg.net
Adress Parametre Type Read / WriteWrite Condition
Tariff 2 Phase 2 Energy Values
518Import Active Energy T2-Phase2 (Tariff 2)32 bit integerR / W
520Export Active Energy T2-Phase2 (Tariff 2)32 bit integerR / W
522Import Reactive Energy T2-Phase2 (Tariff 2)32 bit integerR / W
524Export Reactive Energy T2-Phase2 (Tariff 2)32 bit integerR / W
Tariff 2 Phase 3 Energy Values
526Import Active Energy T2-Phase3 (Tariff 2)32 bit integerR / W
528Export Active Energy T2-Phase3 (Tariff 2)32 bit integerR / W
530Import Reactive Energy T2-Phase3 (Tariff 2)32 bit integerR / W
532Export Reactive Energy T2-Phase3 (Tariff 2)32 bit integerR / W
Device Settings
534Current Transfer Rate (CTR)32 bit integerR / W
536Voltage Transfer Rate (VTR)floatR / W
538Connection Type32 bit integerR / W
540Relay 1 Function (MMW03-M22CH)32 bit integerR / W
542Relay 2 Function (MMW03-M22CH)32 bit integerR / W
544Demand Time32 bit integerR / W
546Password Enable32 bit integerR / W
548Password Activation Time32 bit integerR / W
550Password Value32 bit integerR / W
552Baud Rate32 bit integerR / W
554Slave ID32 bit integerR / W
556Parity Control32 bit integerR / W
558Digital Input 1 Type32 bit integerR / W
560Digital Input 1 Delay Time32 bit integerR / W
562Digital Input 1 Edge32 bit integerR / W
564Digital Input 2 Type32 bit integerR / W
566Digital Input 2 Delay Time32 bit integerR / W
568Digital Input 2 Edge32 bit integerR / W
570Pulse Output 1 Parameter32 bit integerR / W
572Pulse Output 1 Duration32 bit integerR / W
574Pulse Output 1 Rate32 bit integerR / W
576Pulse Output 2 Parameter32 bit integerR / W
578Pulse Output 2 Duration32 bit integerR / W
580Pulse Output 2 Rate32 bit integerR / W
582Menu Scroll On/Off32 bit integerR / W
584Menu Display Period32 bit integerR / W
586Home page Setup32 bit integerR / W
588Display backlight options32 bit integerR / W
590Display backlight on time32 bit integerR / W
Alarm Settings
592Voltage (L-N) Alarm High LimitfloatR / W
594Voltage (L-N) Alarm Low LimitfloatR / W
596Voltage (L-N) Alarm HysteresisfloatR / W
598Voltage (L-N) Alarm Delay Time32 bit integerR / W
600Voltage (L-L) Alarm High LimitfloatR / W
602Voltage (L-L) Alarm Low LimitfloatR / W
604Voltage (L-L) Alarm HysteresisfloatR / W
606Voltage (L-L) Alarm Delay Time32 bit integerR / W
608Current Alarm High LimitfloatR / W
610Current Alarm Low LimitfloatR / W
612Current Alarm HysteresisfloatR / W
614Current Alarm Delay Time32 bit integerR / W
616Neutral Current Alarm High LimitfloatR / W
618Neutral Current Alarm Low LimitfloatR / W
620Neutral Current Alarm HysteresisfloatR / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
Enter the password in the “Settings
Protection” field if password protection is
enabled.
Enter the password in the “Settings
Protection” field if password protection is
enabled.
34 | Energy Analyzer - MMW03-M22CH
www.weg.net
Adress Parametre Type Read / WriteWrite Condition
622Neutral Current Alarm Delay Time32 bit integerR / W
624
626
628
630
632Power Factor Alarm High LimitfloatR / W
634Power Factor Alarm Low LimitfloatR / W
636Power Factor Alarm HysteresisfloatR / W
638Power Factor Alarm Delay Time32 bit integerR / W
640Frequency Alarm High LimitfloatR / W
642Frequency Alarm Low LimitfloatR / W
644Frequency Alarm HysteresisfloatR / W
646Frequency Alarm Delay Time32 bit integerR / W
Device Model
648Device Firmware VersionfloatRO
650Device Model32 bit integerRO
Password/Pin activation
652Setting protection32 bit integerR / W
Reset Commands
1000Reset Energy Values32 bit integerWO
1002Reset Counter Values32 bit integerWO
100 4Reset Max. Values32 bit integerWO
100 6Reset Min. Values32 bit integerWO
100 8Reset Demand Values32 bit integerWO
1010Reset Settings32 bit integerWO
1012Reset Alarm Limits(MMW03-M22CH)32 bit integerWO
1014Reset the Device to Factory Settings32 bit integerWO
Save The Changes
2000Save Changes32 bit integerWO
Manual Output Relay Control
4000
4002
4004
Enable/Disable to Assigning Predefined Value for Energy Meters
5000Enable Counter Change32 bit integerWO
Cosφ Alarm High Limit
Cosφ Alarm Low Limit
Cosφ Alarm Hysteresis
Cosφ Alarm Delay Time
Enable Relay Control
Relay 1 Control
Relay 1 Control
Ta b el a 4 .1: Readable and Writable Data
floatR / W
floatR / W
floatR / W
32 bit integerR / W
32 bit integerWO
32 bit integerWO
32 bit integerWO
Enter the password in the “Settings
Protection” field if password protection is
enabled.
Address for the device password. It displays
the enabled/disabled condition of the
password protection when reading using.
Enter the password in the “Settings
Protection” field if password protection is
enabled. Enter “1” into the respective address
to reset the values. Enter “0” before saving to
restore the values.
Enter the password in the "Settings
Protection" field if password protection is
enabled. Enter "1" to save the changes and
restart.
Enter the password in the "Settings
Protection" field if password protection is
enabled. Enter "1111" here to enable the relay
control. Enter "0" here to disable the relay
control.
Enter the password in the "Settings
Protection" field if password protection is
enabled. Then, enter "1111" for the "Enable
Relay Control" address. Enter "1" to activate,
"0" to de-activate the relay.
Enter the password in the "Settings
Protection" field if password protection is
enabled. Then, enter "1111" for the "Enable
Relay Control" address. Enter "1" to activate,
"0" to de-activate the relay.
Enter the password in the "Settings
Protection" field if password protection
is enabled. Enter "2222" here to enable
assigning the relay control. Enter "0" here to
disable the meter assignment.
Energy Analyzer - MMW03-M22CH | 35
www.weg.net
4.1.1 Status/Alarm Flags
“Alarm Flags” modbus address showing the alarm conditions and alarm conditions represented with bits are
given below.
458 Alarm Flags
31302928272625242322212019181716
Dl2
Status
1514131211109876543210
V2
OFF
bitDescription
31 : DI2 Status: Digitial input 2 signal condition (active or passive).
30 : DI1 Status: Digitial input 1 signal condition (active or passive).
29 : DI1 Status: Digitial input 1 signal condition (active or passive).
28 : Relay 1 Status: Relay 1 active/pasive status.
27 : DO2 Status: Digital Output 2 active/pasive status.
26 : DO1 Status: Digital Output 1 active/pasive status.
25-21 : Reserve.
20 : SEQ - Phase Order Alarm.
19 : I3 OFF - 3. No current in Line-3.
18 : I2 OFF - 2. No current in Line-2.
17 : I1 OFF - 1. No current in Line-1.
16 : V3 OFF - 3. No voltage in Line-3.
15 : V2 OFF - 2. No voltage Line-2.
14 : V1 OFF - 1. No voltage in Line-1.
13 : Freq Low - Low frequency alarm.
12 : Freq High - High frequency alarm.
11 : PF Low - Low power factor alarm.
10 : PF High - High power factor alarm.
9 : Cos φ Low - Low Cos φ alarm.
8 : Cos φ High - High Cos φ alarm.
7 : I(N) Low - Low neutral current alarm.
6 : I(N) High - High neutral current alarm.
5 : I Low - Low current alarm.
4 : I High - High current alarm.
3 : V(L-L) Low - Low phase-phase voltage alarm.
2 : V(L-L) High - High phase-phase voltage alarm.
1 : V(L-N) Low - Low phase-neutral voltage alarm.
0 : V(L-N) High - High phase-neutral voltage alarm.
Dl1
Status
V1
OFF
Relay 2
Status
Freq
Low
Relay 2
Status
Freq
High
DO2
Status
PF
Low
DO1
Status
PF
High
Reserve/OFFSEQ
Cosφ
High
I(Nötr)
Low
Cosφ
Low
Tab e l a 4 .2: Alarm Flags
I(Nötr)
High
I
Low
I
High
I3
OFF
V(L-L)
Low
I2
OFF
V(L-L)
High
I1
OFF
V( L- N )
Low
V3
OFF
V( L- N )
High
CAUTION!
If the device was not restarted after entering the password or the “password activation time” has not elapsed, this will read
“0” to indicate that password protection is disabled in the “Settings protection” address (modbus adr: 604). In this case,
you don’t need to re-enter the password.
Password activation time resets and restar ts each time a modbus write action is performed or a key is pressed.
36 | Energy Analyzer - MMW03-M22CH
www.weg.net
4.2 MULTIPLE CHOICE SETTINGS VIA MODBUS
Modbus addresses for the multiple choice settings, input values and their descriptions are given below.
AdressRegister nameWrite value
538Connection Type
540Relay 1 Function
542Relay 2 Function
546Password Enable
552Baud Rate
556Party Control
558
562
564
568
Digital Input 1
Type
Sayısal Giriş 1
Edge
Sayısal Giriş 1
Edge
Digital Input 2
Edge
03P4W
13P3W
0OFF
1LOW
2HIGH
0OFF
1LOW
2HIGH
0OFF
1ON
012 0 0 baud
12400 bau d
24800 baud
39600 baud
41920 0 ba ud
538400 baud
657600 baud
0NONE
1EVEN
2ODD
0OFF
1TARIFF 2
2COUNTER
3RUN HOUR
0RISING
1FALL ING
2BOTH EDG
0OFF
1TARIFF 2
2COUNTER
3RUN HOUR
0RISING
1FALL ING
2BOTH EDG
Description
name
AdressRegister nameWrite value
0OFF
1IMP ACT1
2EXP ACT1
3I M P R E A1
4EX P R E A1
5IMP ACT2
6EXP ACT2
7IMP REA2
8EXP REA2
9DIN1
10DIN2
0OFF
1IMP ACT1
2EXP ACT1
3I M P R E A1
4EX P R E A1
5IMP ACT2
6EXP ACT2
7IMP REA2
8EXP REA2
9DIN1
10DIN2
0OFF
1ON
0V OL TA G E ( L-N )
1VOLTAGE (L-L)
2CURRENT
3I NEUTR
4COSQ
5PF
6POWER P
7POWER Q
8POWER S
9φ P-Q-S
10FREQ
11THD V
12THD I
0TIME DEP
1CONT ON
2CONT OFF
570
576
582
586
588
Pulse Output 1
Parameter
Pulse Output 2
Parameter
Menu Scroll On/
Of
Home Page
Settings
Display
Backlights
Options
Description
name
Tab e l a 4 .3: Description List
Energy Analyzer - MMW03-M22CH | 37
www.weg.net
5 FACTORY DEFAULT SETTINGS
MenuSub Menu 1
CtrCurrent transformer ratio1-0.00 - 1.00
BASIC
ALARMS
ALARMS
RE L AYS
DEMANDdEd.sDemand time setup15dk1 - 60
RS485
DI INPUT
UtrVoltage transformer ratio1.0-0.00 - 1.00
ConnConnection type options3 P4W-0.00 - 1.00
VLN ALM
VLL ALM
I ALM
IN ALM
COSQ ALM
PF ALM
FREQ ALM
rLY1Relay 1 setupOFF-OFF/LOW/HIGH
rLY2Relay 2 setupOFF-OFF/LOW/HIGH
bAudBaud rate options38400Baud
IdSlave ID setup1-1 - 247
PrtYParity check setupNONE-NONE/EVEN/ODD
INPUT1
INPUT2
Sub
Menu 2
HI
LO
hYS t
dl Y.t
HI
LO
hYS t
dl Y.t
HICurrent alarm high limit0.0A1200/2400/4800/9600/19200/38
LOCurrent alarm low limit0.0A400/57600
hYS tCurrent alarm hysteresis value0.1A1 - 247
dl Y.tCurrent alarm delay value5snNONE/EVEN/ODD
HINeutral current alarm high limit0.0A
LONeutral current alarm low limit0.0A10 - 2000
hYS tNeutral current hysteresis value0.1ARISING/FALLING/BOTH EDG