4.2 MULTIPLE CHOICE SETTINGS VIA MODBUS ..................................................................................37
5 FACTORY DEFAULT SETTINGS 38
6 TECHNICAL SPECIFICATIONS 40
www.weg.net
1 GENERAL INFORMATION
1.1 DEVICE FEATURES
MMW03-M22CH is designed to measure:
Phase-neutral voltages; Phase-phase voltages; Phase current; Neutral current; Frequency; CosØ; Power factors; Active powers; Reactive powers; Apperant powers; THDV; THDI; 1-31 current and voltage harmonics.
Besides, MMW03-M22CH has numerous features such as:
Phase loss information and sequence error display; Determining and saving in the memory of maximum and minimum values of current, voltage, frequency,
cosØ, power factor, THDV, THDI, active, reactive and apparent;
Measuring current, active power, reactive power and apparent power values and saving in the memory; Setting alarm for current, voltage, frequency and power factor parameters; 2 tariff meters. These meters record Import Active, Export Active, Import Reactive, Export Reactive; Storing on hour counter (on hour), run hour counter (total energized time) and power interruption counter; RS485 communication via MODBUS RTU protocol; Digital inputs in order to start counter, 2nd tariff or run hour counter; Digital outputs which can be set to energy meters or counters as output parameters; 2 alarm relay outputs; Avoiding unauthorized control by a 4-digit-password.
MMW03-M22CH
Type of device enclosurePanel
Basic measurements (V, VLL, I, IN, F, Cos l, PF, P, Q, S, THD)l
1-31 Harmonics
Max-Min Value
Demand Values (I, P, Q, S)
On hour, Run Hour, Int
Energy Meters2 tariffs
Assigning alarm to the parameters
Alarm Relay2 Qty
RS485
Digital Input2 Qty
Digital Output2 Qty
Indicators and leds
Order no143 87019
Ta b el a 1.1: Product Features
l
l
l
l
l
l
l
6 | Energy Analyzer - MMW03-M22CH
www.weg.net
1.2 CORRECT USAGE AND CONDITIONS FOR SAFETY
Installation and wiring must be performed by authorized technicians in accordance with the instructions in
the user manual. Do not commission the device before proper wiring.
Make sure the device is de-energized before connecting to the mains. Short circuit the k-l terminals of the current transformer in another location before disconnecting the current
transformers. Failing to do so will cause dangerous high voltages in the secondary terminals of the current
transformers.
Use a dry cloth to clean the device. Do not use alcohol, thinner or any abrasive materials. Make sure all wiring is properly made before commissioning the device. Do not open the device. There are no serviceable parts by the user. Keep the device away from humidity, water, vibrations and dust. It is advisable to connect a circuit breaker or an automatic fuse between the current input of the device and
the mains (2 amps).
CAUTION!
The manufacturer does not assume any responsibility for any undesired consequences if the above measures are not
adhered to.
1.3 PANEL DEFINITIONS
Front Panel
7
6
5
4
3
2
1
89
MMW03
10
11
12
Figura 1.1: MMW03-M22CH Front Panel
1Current and Voltage situation :Indicate phase loss of currents and voltages.
2Sequence error icon:Indicate sequence error of voltages.
3Communication active icon:Indicate that RS485 communication is made.
4Relay icons:Indicate that relays are activated.
5Alarm icon:Indicate that there is alarm on the system.
6Pulse output icons:Indicate that pulse outputs are activated.
Energy Analyzer - MMW03-M22CH | 7
13
www.weg.net
7Energy counter icons:Indicate the type of the counter on the menu bar.
8Counter icon:Indicate the type of the counter on the menu bar.
9Tariff icons :Indicate that the counter of which tariff on the menu bar.
10Menu bar and counter units:Indicate menu names, energy counter and counters and settings.
11Submenu icons :Show that values of which submenu on the indicators.
12 Indicators and units: Indicate measurements, maximum, minimum and demand values and
their units.
13Keys : Use this key to switch between the menus and change the numerical
The menus are shown instantaneous measurements menu and their maximum, minimum, demand, average and
total value at the tables below. The menu pages change with up, down, right and left direction buttons.
1. 4 .1 Key Functions
The buttons placed front panel and their functions are explained at the table below.
At The Energy, Counters,
Harmonics, Settings
Menus
Short
Pressing
(t < 2sec)
Pass to the
one sub-
menu
Changes
the menu
page
Changes
the menu
page
Pass to the
one upper-
menu
Tabe la 1. 2: Key Functions
Long
Pressing
(t > 2sec)
Skips to
bottom
menu
N/A
N/A
Skip to the
last menu
from
Initialize the
Counter
Long
Pressing
(t < 2sec)
Changes
the active
step
Changes
the values
Changes
the value
Stops
changing
value and
confirms
the entering
value
Long
Pressing
(t > 2sec)
Activates
the value
changing
N/A
N/A
N/A
To change the settings
Short
Pressing
(t > 2sec)
Activates
the value
changing or
Changes
the active
step
Changes
the value
Changes
the value
Stops
changing
value and
confirms
the entering
value
Pressing
(t > 2sec)
Long
N/A
N/A
N/A
N/A
Right
button
Down
button
Up button
Left button
At the Measurements
Menus
Short
Pressing
(t < 2sec)
switching
between
menus
switching
between
menus
switching
between
menus
switching
between
menus
Long
Pressing
(t > 2sec)
Skips to
“ENERGY”
menu
N/A
N/A
Skips to
Starting
Page
8 | Energy Analyzer - MMW03-M22CH
www.weg.net
Instantaneous
Value
<Voltage(L-N)>V L- N
<Voltage(L-L)>VL- L
<Current>IMax. I
<I Neutr>
Neutral
Current (In)
<Cosq>
Cos Ø
<PF>
Power
Factor (PF)
INMax. INMin. IN
COS Ø
PF
Max.Min. Demand Avg/Total
COS Ø
Max.
V L- N
Max.
V L- L
Max.
Max.
PF
M i n. V L- N
M i n. V L- LA vg . VL- L
Min. IDemand ITotal I
Min.
COS Ø
Min. PFTotal PF
Avg.
V L- N
Avg max/
Total max
Max.
Avg.
V L- N
Max.
Av g. V L-L
Max
Total I
Max.
Total PF
Avg min/
Total min
Min. Avg.
Min. Avg.
Total I
Min. Total
V L- N
V L- L
Min.
PF
Demand
Demand I
Total
Total
<Power P>
Active
Power (P)
<Power Q>
Reactive
Power(Q)
<Power S>
Apperant
Power (S)
<Σ P-Q-S>
Tot a l Powe r
(Σ P-Q-S)
<Freq>
Frequency(F)
<THD V> THDV
<THD I> Anlık
PMax. PMin. P
Q
SMax. SMin. S
Σ P-Q-S
FMax. FMin. F
Maks.
Q
Max.
Σ
P-Q-S
Max.
THDV
Max.
THDI
Min.
Min. Q
Min.
Σ P-Q-S
THDV
Min.
THDI
Demand
P
Demand
Q
Demand S
Demand
Σ P-Q-S
Total P
Total Q
Total S
Max Total PMin. Total
Max.
Total Q
Max.
Total S
P
Min. Total
Q
Min. Total
S
Total
Demand
P
Total
Demand
Q
Total
Demand
S
Tabe la 1. 3: Menu Switch-1 (Instantaneous Measurement Menus and Sub Menu)
Energy Analyzer - MMW03-M22CH | 9
www.weg.net
ENERGY
(Energy counter
menu)
TARIFF 1
(Tari1 Menu)
IMPORT ACTIVE 1
(Tari-1 Import Active Energy)
EXPORT ACTIVE 1
(Tari-1 Export Active Energy)
IMPORT REACT 1
(Tari-1 Import Reactive Energy)
EXPORT REACT 1
(Tari-1 Export Reactive Energy)
IMPORT ACTIVE 2
(Tari-2 Import Active Energy)
EXPORT ACTIVE 2
(Tari-2 Export Active Energy)
COUNTER
(Counter Menu)
HARMONICS
(Harmonic Menu)
(MMW03-M22CH)
TARIFF 2
(Tari 2 Menu)
COUNTER 1 (Counter 1)
COUNTER 2 (Counter 2)
RUN HOUR (Run Hour Counter )
ON HOUR (On Hour Counter )
POWER INT. COUNTER
(Power Interrupt Counter)
V HARM
(Voltage Harmonics)
IMPORT REACT 2
(Tari-2 Import Reactive Energy)
EXPORT REACT 2
(Tari-2 Export Reactive Energy)
V HARM 1
V HARM 3
.
.
V HARM 31
I HARM 1
SETTINGS
(Settings)
I HARM
(Current Harmonics)
BASIC, ALARMS, RELAYS …
SETTINGS
Tabe la 1.4: Menu Switch-2 (Energy, Counters, Harmonics and Setting Sub-menus)
I HARM 3
.
.
I HARM 31
Energy counters, counters, odd harmonics up to 31st and settings menus are placed at the table above. Menu
switching are made via up, down, right and left direction buttons as stated at the table.
NOTE:
Right button shall be pressed long in order to switch from Table 1-3 to Table 1-4, and.
10 | Energy Analyzer - MMW03-M22CH
www.weg.net
1.5 FOUR QUADRANT REPRESENTATION
The angle(Ø) between voltage and current provides us information about the direction of energy flow. A positive
sign for active/reactive power indicates that active/reactive power is consumed. And also a negative sign for active/
reactive power indicates that active/reactive power is generated.
Reactive Power
QUADRANT-2
P
=> negative
Q
=> positive
CosØ
=> capacitive
PF
=> negative
Meters
Exp. Active &
Imp. Reactive
&
QUADRANT-3
P
=> negative
Q
=> negative & inductive
CosØ
=> inductive
PF
=> negative
capacitive
QUADRANT-1
P
S
Q
P
Q
CosØ
PF
Imp. Active &
Imp. Reactive
=> positive
=> positive
=> inductive
=> positive
Meters
&
inductive
Active Power
QUADRANT-4
P
=> positive
Q
=>
CosØ
PF
negative
=> capacitive
=> positive
&
capacitive
Meters
Exp. Active &
Exp. Reactive
Figura 1.2: Four Quadrant Representation
Meters
Imp. Active &
Exp. Reactive
NOTE:
If the signs of active and reactive power are examined, it can be defined the quadrant that MMW03-M22CH
measures.
In order to understand P and Q signs in MMW03-M22CH 110P and Ecras, instantaneous displays for P and Q
must be checked.
If active power display is seem constantly, it means active power(P) is positive. If it is blinked, it means active
power(P) is negative.
If reactive power(Q) display is seem constantly, it means reactive power(Q) is positive. If it is blinked, it means
reactive power(Q) is negative.
NOTE:
Signs of P and Q can be reached through modbus communication.
Assembly and related connections of the product, must be implemented by authorized persons in accordance with the
instructions of user manual.
DANGER!
The device must not be put into service if the operator is not sure that all connections are correctly accomplished.
2.2 MOUNTING
MMW03-M22CH is placed vertically into the gap located in the panel. After the product is placed into the panel,
fixing brackets should be installed on the product. After that it should be fixed to the panel wall with the screws.
DANGER!
Before wiring up voltage and current ends to MMW03-M22CH, you must be sure that the power is cut.
DANGER!
The product is connected to current transformer(s). Before disconnecting current transformer leads, be sure that they are
short circuited elsewhere or connected to a parallel load which has sufficiently low impedance. Otherwise dangerously high
voltages will be induced at the current transformer leads. Same phenomena also apply for putting into service.
2.3 CONNECTION DIAGRAMS
2. 3 .1 3P-4W and 3p-3W Connections
There are two ways for connections of voltage and current. With neutral (3P-4W), without neutral (3P-3W).
3P-4W (wth neutral) 3P-3W (wthout neutral)
12 | Energy Analyzer - MMW03-M22CH
Figura 2.1: Connection Diagram
CAUTION!
Fi g ure 1-1 1st item, displays current and voltage phase position are On/Off. If a current or voltage phase seems incomplete
and should be checked by the relevant links / connections reached the device.
Fi g ure 1-1 2nd item, if there is an error in the voltage phase during due to incorrect sequence; "Voltage phase sequence
error icon" will appear. If this icon appears; phase-sequence voltage should be checked.
2.3.2 Digital Output Connection Diagram
www.weg.net
DO (-)DO (+)
External DC Power
Supply must be connected.
(5-30VDC)
Figura 2.2: Digital Output Connection Diagram
2.4 DIMENSIONS MMW03-M22CH (MM)
+
-
65,0
Figura 2.3: Dimensions for MMW03-M22CH
Energy Analyzer - MMW03-M22CH | 13
www.weg.net
3 MENUS
3.1 INSTANTANEOUS MEASUREMENT MENUS
Voltage (L-N and L-L), current, neutral current, cosØ, power factor, active power, reactive power, apparent power,
THDV and THDI values are shown in instantaneous menu.
Menu are given the name of which is shown in Menu bar.
The values shown on the display is expressed in what phase or phases at the lower left corner of the display
numbers.
Phase Numbers are not displayed at Menus which display avarege, total and other properties of network. In this
case phases are displayed in 2. Level.
Next to each index value unit of respective rows are indicated. It also states that inductive or capacitive phases
are indicated next to the relevant indicators.
Table 1-3 for parameters displayed in the menus.
POWER Q
Figura 3.1: Instantaneous Measurement Menus (Reactive Power)
CAUTION!
When the product is mounted on a panel which consumes power, active power (P) must be positive. If active power is
negative, operator should cross connect k-l leads of the current transformer.
When the product is mounted on a panel which generates power, active power (P) must be negative. If active power is
positive, operator should cross connect k-l leads of the current transformer.
3.2 MAXIMUM, MINIMUM VE DEMAND MENUS
Minimum and maximum values are calculated and stored in the non-volatile memory for below parameters:
Voltage (phase-neutral, phase-phase); Neutral current; Frequency; CosØ; Power factor; THDV; THDI.
14 | Energy Analyzer - MMW03-M22CH
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.