weedingtech Foamstream M600 User Manual

Page 1
USER MANUAL
ENGLISH (EU) – 16/05/2018 – ISSUE 3
Page 2
Page 3
3
TABLE OF CONTENTS
1 SAFETY INFORMATION _______________ 4
1.1 OPERATOR ATTENTION ____________________________________ 4
1.2 CARBON MONOXIDE HAZARDS ______________________________ 4
1.3 ELECTRIC SHOCK HAZARDS ________________________________ 4
1.4 FIRE AND BURN HAZARDS _________________________________ 4
1.5 GENERATOR FUEL WARNING _______________________________ 4
2 INTRODUCTION ____________________ 5
3 IMPORTANT INFORMATION ___________ 5
4 PRODUCT DESCRIPTION _____________ 6
5 FOAMSTREAM® ___________________ 12
5.1 HOW FOAMSTREAM® KILLS WEEDS ______________________ 12
5.2 INDICATORS ____________________________________________ 12
5.3 CAUTION POISONOUS WEEDS ____________________________ 13 THE EFFECT OF THE SYSTEM ON PLANTS ____________________________ 13
6 PRE-START CHECKS ________________ 15
7 START PROCEDURE ________________ 16
8 SCREEN AND PLC NAVIGATION _______ 19
9 USING THE M600 __________________ 20
10 FOAMSTREAM® APPLICATION (KILLING WEEDS) ____________________________ 22
10.1 HOSE REEL ___________________________________________ 22
10.2 SPEED _______________________________________________ 22
10.3 USE OF THE LANCE _____________________________________ 22
10.4 TREATMENT OF THICK WEEDS ____________________________ 23
10.5 TREATMENT ___________________________________________ 23
10.6 CONFIRMATION OF TREATMENT ___________________________ 23
10.7 CORRECT POSTURE _____________________________________ 23
11 SHUT-DOWN PROCEDURE ___________ 24
12 BASIC FAULT FINDING ______________ 25
13 SERVICE CHECKS AND INTERVALS ____ 30
14 LOADING AND HANDLING ___________ 31
15 SCHEMATICS _____________________ 32
16 WARRANTY _______________________ 37
17 PRODUCT CERTIFICATION ___________ 39
Page 4
4
1 Safety Information
To ensure safety while operating the M600, please carefully read the following information.
1.1 Operator Attention
WARNING
Read and understand this user manual before operating
the M600.
The M600 should only be used by trained operators.
Proper PPE is to be worn at all times while operating the
M600 (see section 3).
Major repair work should only be carried out by
professionally trained service engineers.
1.2 Carbon Monoxide Hazards
WARNING
Boiler and generator exhaust contains poisonous carbon
monoxide gas.
Never run the M600 indoors, even if a door or window
is open. ONLY USE IN A WELL VENTILATED AREA.
Do not use the M600 in potentially explosive
atmospheres.
1.3 Electric Shock Hazards
WARNING
Do not operate the M600’s electrical components with
wet hands.
Do not expose the generator to rain, moisture, or snow.
Always ensure electric cables are in good condition.
1.4 Fire and Burn Hazards
WARNING
LPG and diesel are explosive and flammable. Always
ensure spark or fire source point away while refueling.
Do not refill diesel while machine is in use.
Clean up any overflowing fuel prior to turning on the
M600.
Never smoke while operating the M600.
Do not touch the working components in the M600 while
in use or immediately following use. Allow sufficient time to cool before servicing.
Shut off generator by closing LPG supply to prevent
unburned gas from remaining in the system.
1.5 Generator Fuel Warning
WARNING
NEVER USE PETROL IN THE M600. ONLY USE LPG TO FUEL THE GENERATOR.
If the generator is used outside the M600 as a backup generator and petrol is used, follow the instructions below prior to using the M600.
Remove all remaining petrol from generator and
clean all spills and allow to dry/evaporate before putting the generator back inside the M600.
Turn the fuel switch (item 7 in Figure 11) to the OFF
position.
Connect LPG cylinder and start as normal.
Page 5
5
2 Introduction
Thank you for purchasing the Foamstream M600!
IT IS IMPORTANT THAT ALL OPERATORS READ AND
UNDERSTAND THESE INSTRUCTIONS BEFORE USING
THE MACHINE
Having read these instructions, the operator will:
Understand how the M600 works
Identify key components in the M600
Know how to carry out pre-start and start-up
procedures
Observe safe operating practices
Be able to effectively operate the M600
Be able to shut down and clean the M600
Be able to perform basic maintenance and
troubleshooting tasks
PLEASE KEEP THESE INSTRUCTIONS IN A SAFE PLACE
FOR FUTURE REFERENCE
3 Important information
The following PPE (Personal Protective Equipment) are recommended when operating the M600:
Eye protection is required when handling
Foamstream® concentrate
Gloves are required as the lance assembly will get hot
Safety Footwear suitable for working in the areas
concerned is recommended
No specific protective clothing is required, although
use of overalls and a HI-Viz vest is suggested as best practice.
IT IS THE RESPONSIBILITY OF THE OPERATOR TO WEAR
APPROPRIATE PPE
Never operate the machine without checking that there are adequate supplies of clean diesel, clean water, and clean Foamstream® concentrate in the appropriate tanks.
The M600 produces VERY HOT water. This can cause serious burns and injury if used incorrectly.
Never point the lance at people or animals as this machine operates at high temperature and low pressure.
All personnel operating a M600 machine must be deemed competent to do so and must be adequately trained. A copy of the training record is available on demand.
Always check the M600 for any damage before use. Damaged cables, hoses or connections must be reported immediately, and the machine taken out of use until repairs have been completed.
Use only genuine Weedingtech spare parts and Foamstream® consumables. This will ensure the best performance of your machine and maintain the warranty of the unit.
The M600 must never be modified, safety interlocks bypassed, or settings adjusted (unless specified in these guidance notes) without Weedingtech’s written consent.
Ensure that the M600 is placed in an area where there is adequate ventilation when in use.
Page 6
6
Ensure that the consumable liquid (foam concentrate) is not subject to temperatures below 5 degrees centigrade at any time.
Ensure that both the M600 and its water tank are securely attached to the transport vehicle. It is the responsibility of the vehicle driver to ensure that any load is secure and that any payload restrictions are observed. You can refer to section 14 for more information on transport.
4 Product description
The M600 weed control unit consists of:
Foamstream®
Water tank (270 litres)
Hose reel (30 metres)
Lance
The M600 houses a diesel-powered boiler, an LPG-powered generator, a logic controller (PLC), a piston pump, a 35 litres diesel tank, and a 15 litres Foamstream® concentrate tank.
When the water reaches 95 degrees centigrade, a valve opens allowing water to flow from the lance (7 lpm @ 12 bar) and a venturi mixer opens to allow Foamstream® concentrate to be injected at a ratio of 99.5 parts water to
0.5 parts concentrate. Air is added to the water and Foamstream® mix as it exits the lance to create the foam.
Figure 1 - M600 (operator and vehicle not included)
When the machine is switched on and operational, water is pumped at 7 litres per minute and passes through the boiler to be heated up to a minimum of 95 degrees centigrade.
The M600 has been designed to require no manual input or adjustment. The PLC monitors the system pressure, temperature and flow rate to ensure optimum performance of the unit.
NEVER OPERATE THE M600 WITHOUT FOAMSTREAM®
CONCENTRATE
Page 7
7
A pressure relief valve and over-temperature sensor ensure that internal pressure and temperature will not exceed 35 bar or 120 degrees centigrade in the event of a system fault.
Operation of the M600 is via the user interface at the front of the unit (see section 7 for details).
Filters are fitted to the diesel, water and foam systems to ensure supplies are kept clean and free from debris. These needs to be checked daily (see section 6).
The top cover and front doors can be opened with a key to allow access to all internal components. The generator is on a slider and can be removed for improved access. The side panels can be easily opened by removing the three 1/4-turn screws on each side for maintenance purposes. Access to the electronics is via a door on the front of the M600 which can be opened by a key.
The standard water tank (270 litres) can be either wrap around the unit or be separate. There are two hydraulic connections (water supply, water return) and one electrical connection (water sensor).
An automatic hose reel is located inside the unit to allow the 30 metres hose to be stowed safely when the M600 is not in use. The hose comes off the right side of the reel and is connected to the lance via a threaded collar.
M600
HEIGHT (mm)
1200
WIDTH (mm)
1000 or 1260 (with tank)
DEPTH (mm)
800 or 1110 (with tank)
WEIGHT (kg)
240 EMPTY, 270 FULL
WATER
270 LITRES
FUEL
DIESEL – 35 LITRES
FOAMSTREAM
FOAMSTREAM – 15 LITRES
GENERATOR OIL
0.6 LITRES SAE 5W40
PUMP OIL
0.3 LITRES SAE 5W40
FLOW RATE
7 LITRES PER MINUTE
OPERATING PRESSURE
30 BAR ON HEAT UP, 12 BAR
TRIGGER OPEN
OPERATING TEMPERATURE
95 – 110 °C
PRESSURE RELIEF VALVE
35 BAR
OVER TEMPERATURE CUT-OUT
125 °C
GENERATOR
3.2 kVA – LPG POWERED
BOILER
48 kWh – DIESEL POWERED
Page 8
Figure 2 – Perspective view of the M600
Num.
Description
1
Control Panel
2
Generator
3
Water tank
4
Lance
5
Hose reel orifice
6
Water Filter
7
Forks entrance
8
Boiler exhaust flap
9
Warning light
10
Control panel access door
11
Generator access door
12
Top cover
13
Hydraulic pressure gauge
14
LPG cylinder
15
LPG regulator
Page 9
9
Figure 3 - Internal components of the M600 (panels removed)
Num.
Description
1
LPG generator
2
Diesel boiler (CAUTION HOT)
3
Water pump
4
Control box
5
Automatic hose reel
6
Hydraulic plate (hydraulic components not represented)
7
Diesel & Foamstream® filling points
Page 10
10
Figure 4 - View of the M600 hydraulic panel (some parts hidden
for clarity)
Num.
Description
1
Lance solenoid valve
2
Lance pressure switch
3
Venturi
4
Return to tank flow switch
5
Pressure relief valve (PRV)
6
Diesel filter
7
Main flow switch
8
Diesel tank
9
Foam tank
10
Foam filter
11
Pressure gauge
Page 11
11
Figure 5 - Closed control box (left) open (right)
Figure 6 – Detail of the switches on the front panel
Num.
Description
1
Emergency stop
2
Main contact switch
3
Boiler reset button
4
Power light
5
PLC screen (touch screen)
Page 12
5 FOAMSTREAM®
5.1 How FOAMSTREAM® kills weeds
Foamstream® uses heat to kill weeds. Water is heated to near boiling point and then mixed with the Foamstream® concentrate to produce foam before being applied. The foam blanket ensures that the heat is held on the plant so that the weeds experience hot, killing temperatures for a few seconds. Figure 10 below explains and compares the process to hot water and steam.
5.2 Indicators
The lances can apply large volumes of water and foam and can be used to kill larger weeds. Foam cover, and hence heat retention on weeds, is easier to achieve on prostrate plants that are near the ground. Tall plants should be trodden down either by foot or by using the lance outlet, to aid foam cover and heat retention.
Figure 7 - Foamstream during treatment
Immediately after treatment, weeds will go dark green and limp. This indicates that the machine is operating properly. The weeds will die; this becomes more obvious within the next one to seven days (depending on species and weather). If weeds fail to go limp, temperatures may be too low or forward speed to high.
Figure 8 - Weed immediately after treatment with Foamstream
Figure 9 - Weed 24 hours after treatment with Foamstream
Page 13
13
If weeds go brown immediately after treatment, this could indicate that forward speed is too slow and excessive heat is being applied.
Figure 10 - Foamstream's triple action
Steam / Hot Water
Kills the leaves
Kills weeds
No effects on seeds
Sterilises seeds
Very weak effect on roots
Damages the root
In general, annual weeds are easier to kill than biennial or perennial ones. Weed species that originate from desert or semi-arid regions are more heat tolerant and will need a slightly prolonged treatment period compared to other species.
Biennial or perennial weeds usually have parts protected against heat (especially regenerative parts under the soil, the Rhizome). Foamstream is a contact application, it will kill foliage, but many perennial and biennial plants will regenerate. The number of repeat treatments required to completely kill weeds depends on the species and their size.
5.3 Caution – poisonous weeds
Some poisonous weeds, such as common ragweed (Senecio jacobaea) may still be attractive to animals after treatment with Foamstream. When treating any area where animals are likely to graze after treatment with Foamstream, check for the presence of such potentially toxic weeds and remove them or keep out of reach of animals that are at risk.
The effect of the system on plants
The M600 has been designed to operate in an urban environment and control weed growth on both hard surfaces and cultivated land. These weeds may be in, at, or around kerbs and channels, footpath edges, driveways, boundaries, obstacles etc.
Within these environments there are various plant species that need to be controlled. These species may vary in type and growth patterns depending on the specific geographic location.
The system, through its unique operation, delivers a plant kill based on thermal activity penetrating and breaking down the cell structure of the plant.
With varying plants in the target area, it is important for the operator have some knowledge of the weed types, sizes and
Page 14
14
ages that they are treating, as this impacts on the speed of operation to deliver an effective kill.
For maximum efficacy, it is important that all weeds in the target area are in contact with the hot foam. Either flatten tall weeds i.e. by treading or use of the lance or ensure that
the stems are ‘ring barked’ (completely surrounded by a
blanket of foam). The density of the plants and foliage is a very important aspect for the operator to be aware of, as this also impacts on the speed of operation. It should be noted:
As the height and/or density of the target plants
increases, the speed of operation will be slower.
In a situation where regular treatment of the area is
part of a maintenance programme the weeds will generally be easier to treat as regrowth should be reduced.
Regular treatment also allows increased speed of
operation, as the volume of target plants to kill will be minimised on each maintenance cycle.
Page 15
15
6 Pre-start checks
THESE CHECKS MUST BE COMPLETED BEFORE EACH
START OF THE M600. ANY FAULTS MUST BE RECTIFIED
BEFORE THE M600 IS SWITCHED ON.
6.1 Checklist The M600 is in good condition and securely attached
to the transport vehicle
The M600 water tank is securely attached to the
transport vehicle
The LPG cylinder is full, secured, and in good
condition
Water tank is full of clean water Water filter is clean and free from debris Air intakes are clear of debris The lance, hose reel and hose are securely connected
and free from damage
Lance wear pads are not excessively worn The water return pipe and water level sensor are
connected
Pipe/hose routes are clear of sharp edges and hot
surfaces
There are no signs of leaks from any pipe or
connection
Fuel tank is full of clean diesel fuel Boiler fuel filter is clean and free from debris The Foamstream® concentrate has not been subject
to temperatures below 5°C and frozen or separated
Foamstream® concentrate tank is full of clean
Foamstream® concentrate
Foamstream® filter is clean and free from debris Vent screw on Foamstream® tank filler cap is open Generator engine oil level is correct
Pump oil level is correct Generator and boiler exhaust are secure and clear of
debris and obstruction
Fuel switch on generator is in the OFF position when
using LPG
Generator is switched to normal mode Water feed valve is connected and in the ON (inline)
position
Air has been bled from water system The LPG cylinder valve is connected, open, and leak
free.
CLOSE LPG CYLINDER VALVE WHEN MACHINE IS NOT IN
OPERATION
NEVER RUN THE GENERATOR WITH LPG WHILE
PETROL REMAINS IN THE GENERATOR’S PETROL
TANK
Page 16
16
7 Start procedure
Complete pre-start checks (see section 6) Press and hold priming button on regulator Start the generator by either:
Turning the key to position E and release to
position D when engine starts (see
Figure 11) or
Turn the key to position D and double press and
hold ON on the remote
Turn the isolator switch to position A (see Figure 11), the PLC screen should illuminate (see Figure
12)
Figure 11 - Details of the switches of the front panel
The reset indicator (blue light) lights up and FAULT will
appear on the top right hand corner of the PLC screen
Press the RESET button (blue button on the front panel,
see Figure 5), the FAULT indicator goes out and you should see the screen represented in Figure 12
Wait a few seconds before requesting air bleed: buttons
1 or 2 in Figure 12
If you have disconnected the water tank or are starting
for the first time of the day, please use “Air bleed
Total
If you just took a break or want to perform an additional
air bleed, please select “Air bleed Partial
When bleeding the machine, the trigger must be
pushed to allow water to flow out of the lance. Failure to
do so will cause the machine to display a fault message.
Once button 1 or 2 is pressed the bleed screen
represented in Figure 13 will appear.
Wait until the purge is completed. A new screen will
appear, represented in Figure 14.
Press START, the button turns green and the screen
represented on Figure 15 will appear.
The amber HEATER light will illuminate and the red
FAULT button should go out. This indicates that the
boiler has switched on and is heating the water
The green READY light will illuminate when the M600
has reached operating temperature and the system is ready for use (2 – 4 minutes).
AFTER A COLD NIGHT (BELOW 0 DEGREES CELSIUS),
LET THE GENERATOR RUN FOR 15 MINUTES TO WARM
UP THE MACHINE BEFORE STARTING THE PUMP OR
BLEEDING THE UNIT
Page 17
17
Figure 12 - Start-up screen of the PLC
Num.
Description
1
Press this button to purge the M600 for 30 seconds.
2
Press this button to purge the M600 for 10 seconds.
3
Indication message.
4
Air bleed status indicator.
5
Menu access
Figure 13 - Bleed screen of the PLC
Figure 14 - Start screen of the PLC
Num.
Description
1
Start button
2
Boiler water input temperature
3
Boiler water output temperature
4
Indication message
5
Menu access
1
2
3
4
5
1
2 3
4
5
Page 18
18
Figure 15 - Running screen of the PLC
Page 19
19
8 Screen and PLC navigation
When the M600 is ready to start, the screen below will appear (same as Figure 14)
To access the menu, click on the “Menu” button on the top
left-hand side of the screen. The screen in will appear.
Figure 16 - Menu screen
Num.
Description
1
Return to main page
2
Go to summary screen
3
Purge
4
Language and units selection
5
Fault summary panel
6
Maintenance mode
Users have no need to access pages 5 and 6. Page 6 is restricted by a password. The screens are summarized in the table below (in the same order as is Figure 16)
1
2 3
4
5
1 2
3
4 5
6
Page 20
20
9 Using the M600
The M600 control panel gives important feedback on the status of the M600:
Status
Red
Orange
Green
Ready
Fixed
Fixed
Stand-by
Fixed
Flashing
Boiler active
Fixed
Boiler fault
Fixed
Water tank too hot
Flashing
Level sensor low
Flashing
Boiler overtemp.
Fixed
Flashing
POWER LIGHT - WHITE
When the generator is on, this light should be illuminated. If the generator does not start, then the generator plug should be checked. If the generator breaker position is correct and the generator does not start the M600 should be checked by a competent service engineer.
AMBER HEATER LIGHT
If the amber light is illuminated the water is below 96 degrees centigrade and is being heated. If the amber light does not illuminate, and the red fault light stays on, there may be a system fault (see below)
GREEN READY LIGHT
When this light is illuminated the M600 is ready for use. If the green light is not illuminated the water may need heating (amber light will be on) or there is a system fault (red fault light will be on, see below).
FLASHING ORANGE LIGHT
If the amber light is flashing the water in the water tank is too hot. If water in the water tank exceeds 45°C the boiler will shut down. The water tank will need to be drained and refilled with cold water, or the level topped up with cold water.
BLUE RESET LIGHT
The blue reset light should switch off when the reset button is pressed during start up. If the light stays on there is an electrical fault which needs rectification. The M600 should be switched off until the fault has been corrected.
FLASHING BLUE RESET LIGHT
A flashing blue reset light indicates a boiler fault. The M600 must be switched off and checked by a competent service engineer.
RED FAULT LIGHT
The red fault light will illuminate at start up until the green button is pressed and the amber light illuminates. If the red light stays on, and the amber light fails to illuminate, the system may need to be bled to remove air (see section 7). If the red light fails to switch off after bleeding there is a system fault. The M600 should be switched off until the fault has been corrected by a competent service engineer.
Page 21
21
RED FAULT AND FLASHING AMBER LIGHT
An illuminated red fault light and flashing amber light indicates the boiler is too hot. The M600 should be switched off and checked by a competent service engineer.
GREEN AND AMBER WITH FLASHING RED FAULT LIGHT
A flashing red fault light with illuminated green and amber lights indicates one of the fluid levels is low (water, Foamstream® or diesel). The levels should be checked and filled up accordingly.
THE M600 SHOULD BE SWITCHED OFF AND CHECKED BY
A COMPETENT SERVICE ENGINEER IF IT DOES NOT
OPERATE AS EXPECTED, OR THE LIGHTS ILLUMINATE IN
A DIFFERENT WAY THAN EXPLAINED.
Page 22
22
10 Foamstream® application (killing
weeds)
To effectively control vegetation with the herbicide-free Foamstream® system, you must co-ordinate all the different elements that give a successful result. If one element is not functioning properly, the desired result will not be achieved.
For effective results the Foamstream® system requires the:
Correct volume
Correct temperature
Correct method
Correct quantity of foam agent
This section looks at the speed and method of application.
10.1 Hose reel
The M600 unit is fitted with an automatic hose reel which contains 30 m of hose as standard. The hose comes off the top of the reel and is connected to the lance by a swivelling connection covered by an insulating sleeve.
Only remove as much hose as is required.
Once finished, rewind the hose onto the reel neatly.
10.2 Speed
Operators will average approximately 2 - 4 kilometres per hour, when proficient at applying the Foamstream® with the M600. Foamstream® and the M600 are unaffected by weather, thus ensuring overall productivity each week is similar.
DO NOT HURRY!
If the operator moves too quickly over the vegetation, the required volume of hot water and foam may not have penetrated or been applied correctly. Total vegetation control will not have been achieved.
10.3 Use of the lance
To kill weeds effectively, the lance head must be no more than 25 mm above the ground at all times. If possible, keep the lance head in contact with the ground. While every element of the treatment is important, the most critical aspect is to ensure the lance head is not lifted from the targeted area.
Control of vegetation for up to 90 days will only be achieved if the temperature measured at the lance head does not fall below 96oC. If the lance head is more than 30mm above the ground, a less than acceptable result may be achieved due to the rapid temperature loss.
It is recommended the operator keeps the trigger open if possible. This maintains constant flow of hot water and foam and ensures that they are leaving the lance at the correct temperature.
If the trigger is released for more than 30 seconds, the operator will have to wait until the water and foam mixture is replaced, this normally takes up to 45 seconds. When moving the lance head from one treatment zone to another, turn off trigger and ensure the hot water and foam is not applied to sensitive plant areas.
Page 23
23
If there is a reduction in foam produced from the lance head, you will not achieve the desired kill. You can check this by lifting the lance and observing the water flow.
10.4 Treatment of thick weeds
The Foamstream system works by penetration of heat into plant cells. In cases of dense growth and dense swards of grass (especially species such as kikuyu) progress will be slower as a greater volume of liquid (thermal energy) is required to ensure a result.
The Foamstream system is designed to control vegetation up to 200 mm high in optimum conditions.
10.5 Treatment
The 'treatment zone' will be stated in the job specification. The operator must kill the total area of the plant in the treatment zone including any parts that hang over onto the sealed area.
10.6 Confirmation of treatment
With practice, operators will become familiar with determining whether weeds have been treated correctly.
Broad leaf weeds will go floppy and wilt (similar to boiled cabbage). In most cases these will go darker in colour.
Grasses: usually, grasses immediately lighten in colour and flatten to the ground. This can be difficult to observe when using hot foam.
Moss will go bright green.
In all cases, a distinctive smell (similar to cooking spinach) also assists to confirm a result.
VISUAL CONFIRMATION THAT THE TREATMENT HAS BEEN
SUCCESSFUL IS ESSENTIAL.
10.7 Correct posture
When using the equipment for several hours per day it is important that operators adopt the correct posture and technique.
Remember it is the heat that controls the vegetation.
When treating straight stretches of roads or parks, use just the trigger hand to guide the lance. This keeps your back upright and not twisted and you are not encouraged to push down with the other hand.
Only use the other hand when changing direction or raising the lance.
When walking, swap trigger hands every so often to rest the muscles.
Page 24
24
11 Shut-down procedure
Upon completion of work, or when taking a break, the unit must be shut down correctly:
Press the red stop button pictured on Figure 17. All
lights will extinguish apart from the power light (white) and the red fault light. The red fault light will remain on until the water temperature in the M600 drops to a safe level and the pump stops.
Wait until the red fault light switches off
Turn the isolator switch to B (Figure 11).
Turn the generator key switch to C (Figure 11) or
press OFF on the remote.
Close the LPG cylinder valve
AT THE END OF THE DAY OR BEFORE AN EXTENDED
BREAK SHUT OFF THE GENERATOR BY TURNING OFF
THE GAS (LPG) SUPPLY. USING THE KEY OR REMOTE
WILL NOT STOP THE SUPPLY OF GAS AND THIS MUST
BE DONE MANUALLY FOR SAFETY REASONS, TO STOP
UNBURNED GAS REMAINING IN THE SYSTEM.
The emergency stop shuts off the boiler and the pump in the event of an emergency. Example scenarios below but not limited to:
Water temperature exceeds 120 degrees centigrade
Steam emits from the lance
A significant leak occurs
The emergency stop button is not to be used in place of the red stop button (Figure 17). Doing so can damage the hydraulic system by holding hot water inside. The shutdown procedure includes flushing the system with
cooler water to bring down the internal temperature to safe storage levels prior to stopping the M600.
Once per week or after 40 hours use, whichever comes first, it is recommended to test the emergency stop to ensure it functions as intended.
IF THE EMERGENCY STOP HAS BEEN USED IN AN
EMERGENCY OR IF IN THE PERIODIC TEST IT DOES NOT
FUNCTION PROPERLY THE M600 SHOULD BE CHECKED
BY A COMPETENT SERVICE ENGINEER, AND ANY FAULTS
RECTIFIED BEFORE THE M600 IS SWITCHED BACK ON
AGAIN.
Figure 17 – Stop button showing on the PLC
Page 25
25
12 Basic fault finding
The PLC of the M600 is designed to help the user in case something goes wrong.
Figure 18 – Summary screen of the PLC
Num.
Description
1
Boiler incoming water temperature
2
Boiler outgoing water temperature
3
Foamstream tank level sensor
4
Water tank level sensor
5
Diesel level sensor
6
Boiler controller
7
Water pump
8
Venturi
9
Lance solenoid valve
10
Lance flow switch
11
Lance pressure switch
12
Boiler diesel pump
13
Return to tank flow switch
Green colour indicates that the sensor is seeing a signal and grey or red that it doesn’t. Red colour does not necessarily mean that there is an issue with the sensor. Normal sensor states during start-up/shut-down and normal operation are described in the table below.
Num.
Start-up
Running
1
Not applicable
2
Not applicable
3
Green
Green
4
Green
Green
5
Green
Green 6 Should be visible
7
Green
Green
8
Grey
Green
9
Grey
Green
10
Green
Green
11
Grey
Green
12
Green
Green
13
Green
Grey
When a fault occurs, a fault message will be displayed in the box no4 of Figure 14. Below are the faults that can appear in that screen and what they mean.
1
2
3
4
5
6
7
8
9
10
11
12
13
Page 26
26
Sentence
Colour
Explanation
Machine running
Green
Machine is running and producing foam
Clear fault
Red
Press the red button on front panel to clear the fault
Outlet temp. too
high
Red
The temperature at boiler outlet is too high. Clean the water filter and check for leaks. If the problem persists, please contact your WTL distributor
Inlet temp. too
high
Red
The temperature in the main water tank is too high (more than 45C) and the machine has stopped. Let the water cool down in the tank or top it up with cooler water.
Low level in
foam tank
Yellow
The fluid level is low, the machine will keep running 2 minutes and will then stop. Please top up.
Low level in
water tank
Yellow
Same as above
Low level in
diesel tank
Yellow
Same as above
Outlet pressure
too low
Red
The lance valve is open and the flow is ok but there is no signal from the pressure switch. Please control the pressure on the pressure gauge of the side panel. If the pressure is below 5 bars this means you have no lance or a large leak before the lance. If the pressure is above 5 bars you might have an issue with the pressure switch and need to change it
Boiler fault,
press "Reset"
Red
Press "Reset". If the boiler does not start, stop the machine and restart it. If the problem persists, please call a Weedingtech distributor.
Boiler could not
start
Red
20s after the start-up signal is given, the boiler is not started. Press "Reset" and try again. If the boiler does not start, stop the machine and restart it. Check on the summary screen that “stage
1” and “stage 2” are in
green, if not check that the plugs have not fallen out of the boiler. If that is not the case and the problem persists, please call a Weedingtech distributor.
Page 27
27
Boiler not ready
Red
The boiler fan is running but the boiler is not running as the ‘ready signal from controller was not received.
Push on the ‘reset’ button
for 5 seconds and try again. If the problem persists, please call your Weedingtech distributor.
Emergency stop
activated
Red
The emergency stop button is activated, release it and press "reset".
No flow at outlet
Red
The pump is running but no flow is detected. Please check the hydraulic panel for leaks. If no leaks are found, the flow switch might be faulty.
No flow at
bypass
Red
The pump is running and the water heating up but no flow is detected in the return to tank line. Please check the hydraulic panel for leaks. If no leaks are found, the flow switch might be faulty.
Press "Air bleed"
Green
Press "Air bleed"
Machine ready,
press "Start"
Green
Press "Start"
Boiler starting
up
Yellow
Nothing
Water & Boiler
pre-heating
Yellow
The boiler is warming up the water to reach 95° and will then open the lance
valve. You have nothing to do.
Air bleeding in
progress
Green
Wait until the bleeding is complete
Pressure sensor
fault
Red
The pump is not running but the pressure sensor sends a signal. The pressure sensor is faulty and needs to be changed
Outlet flow
sensor fault
Red
The pump is not running but the flow sensor sends a signal. The flow switch needs to be changed
Inlet flow sensor
fault
Red
The pump is not running but the flow sensor sends a signal. The flow switch needs to be changed
Boiler controller
fault
Red
The boiler is not running but ready signal from controller is received. Please contact a Weedingtech distributor
Water pump
speed inverter
fault
Red
Fault signal from speed inverter. Please stop and start the machine. If the problem persists you will need to contact a Weedingtech distributor to open the electrical box and reset the inverter.
Release trigger
Yellow
Release the trigger.
Page 28
28
Manual bleeding
required
Red
You need to bleed the air from the unit manually by unscrewing the brass tap on top of the water filter to let air go out.
The table below explains what to do to solve an issue when the sentence above appears on the screen.
The table below lists other basic faults which can be diagnosed and rectified by a competent M600 operator. Please refer to the training documentation provided during training.
BEFORE BEGINNING ANY WORK ENSURE THE
WEEDINGTECH M600 HAS BEEN SWITCHED OFF, AND
THE ELECTRICAL SUPPLY FROM THE GENERATOR IS
DISCONNECTED. WARNING: WATER IN THE M600 MAY
BE HOT.
THE M600 SHOULD BE SWITCHED OFF AND CHECKED
BY A COMPETENT SERVICE ENGINEER IF THE
OPERATOR IS UNABLE TO DIAGNOSE AND RECTIFY A
FAULT USING THE TABLE BELOW, OR IF A FAULT
PERSISTS.
SYMPTOM
CAUSE
REMEDY
Generator will
not start (no
lights)
Battery is flat
Charge battery
No fuel in LPG
tank
Refill tank and bleed fuel system
Air in the fuel
pipe
Prime fuel using the in-line hand pump
The PLC will not
illuminate
Generator is not
started
Start generator
Main switch is
still on ‘OFF’
position
Turn main switch on ‘ON’ position
Boiler will not
fire up.
(pump runs, red
fault light on)
Air in water feed
line
Stop the machine and bleed water once again
Water filter
blocked
Clean and replace filter
Hot water in tank
Drain tank and refill with cold water
Boiler control box
safety switch
activated
Press reset button on boiler control box
Boiler switched
off at boiler
control box
Turn switch on boiler control box to ‘on’
Flow too low
Check water filter is clean
No water flows
from lance
Water
temperature too
low
Wait until water temperature reaches correct level
No water in the
water tank
Refill water tank
Intermittent Flow (amber
light on,
Water
temperature too
low
Wait until water temperature reaches correct level
Page 29
29
intermittent green light)
Steam coming
from lance
Temperature
control system
faulty
Switch off M600 and call competent service engineer
Red light
flashing
Water and/or
Foam and/or
Diesel level too
low
Check water and/or Foamstream® and/or diesel levels and refill as needed.
Blue reset light
on
Electrical fault
Press reset button on control panel
No foam coming
out of the lance
No foam in the
tank
Fill up tank with foam
Breathing screw
of the foam tank
too tight (air not getting through)
Loosen the breathing screw on top of the cap of the foam tank
Foam filters
clogged
Clean foam filters using hot water or replace them
Dosage plate
blocked
Clean dosage plate using warm water
Pressure too high
(more than 18
bars)
Untighten pressure relief valve to reach 12 to 15 bars operating pressure
Foam is too cold
and has
separated
Drain foam from tank, clean pipes, filter and dosage
plate holder, re­mix foam and refill tank.
Air coming in the
foam system
Check the foam pipe for air contamination. Then tighten the faulty connection
Page 30
30
13 Service checks and intervals
Figure 19 – 50 hours before maintenance
Figure 20 – Maintenance due
The PLC screen will let you know 50 hours before the first major maintenance of the unit, as depicted on Figure 19. Once the maintenance is due, Figure 20 will show.
BEFORE BEGINNING ANY WORK ENSURE THE
WEEDINGTECH M600 HAS BEEN SWITCHED OFF,
AND THE ELECTRICAL SUPPLY FROM THE
GENERATOR IS DISCONNECTED.
EVERY 50 HOURS (1 MONTH MAXIMUM)
Change generator oil
EVERY 250 HOURS (6 MONTHS MAXIMUM)
Check boiler flue gas for CO content,
adjust air flap setting if required
Check and de-scale coil (if necessary)
Change particulates filter cartridge (if applicable)
Clean generator air filter
Check and/or adjust generator spark plug
EVERY 500 HOURS (12 MONTHS MAXIMUM)
Change generator oil filter
Change generator air filter
Change fuel filter.
Check and clean boiler mixing device.
Replace electrodes and nozzles if necessary
Check and adjust boiler burner pressure regulator
setting
Check and clean boiler burner chamber
Check electrical control panel for moisture damage
Check and adjust boiler pump oil pressure and level
Change particulates filter cartridge (if applicable)
EVERY 750 HOURS (OR 18 MONTHS MAXIMUM)
Change pump oil and filter cartridge (if applicable)
Page 31
31
14 Loading and handling
Before lifting the M600 you should make sure that the water tank is not full of water.
THE M600 SHOULD NOT BE LIFTED WITH A FULL
TANK OF WATER
Before driving, the user should make sure that the unit and the water tank are appropriately strapped or bolted to the vehicle.
Figure 21 - Strapping of the M600 to the vehicle
Page 32
15 Schematics
Figure 22 - M600 P&ID
Page 33
33
WATER
FOAMSTREAM
FUEL
AC SUPPLY
DC SUPPLY
INSTRUMENT SIGNAL
AV
Actuated Valve
MV
Manual Valve
PI
Pressure Gauge
PS
Pressure Switch
FS
Flow Switch
PRV
Pressure Relief Valve
TC
Thermocouple
FLS
Flame Sensor
L
Level Switch
Page 34
34
Figure 23 – Foam and water schematics
WATER TANK
WATER FILTER
WATER PUMP VENTURI
FOAM TANK
FOAM FILTER 1
BOILER
PRESSURE
RELIEF VALVE
LANCE
Page 35
35
Figure 24 – Fuel schematics
DIESEL TANK BOILER DIESEL FILTER
LEVEL SENSOR
Page 36
M600 – User manual – English (EU) – 16/05/2018 - ISSUE 3
Figure 25 – Electrics schematics
KEY SWITCH
GENERATOR
ISOLATOR
CONTROL BOX
CONTROL
PANEL
BOILER
PUMP
LANCE VALVE
PRESSURE
SWITCH
TEMPERATURE
SENSOR INLET
TEMPERATURE
SENSOR OUTLET
LANCE FLOW
SWITCH
BYPASS FLOW
SWITCH
LEVEL SWITCH
FOAM
LEVEL SWITCH
WATER
LEVEL SWITCH
DIESEL
Page 37
16 Warranty
(a) The following is an inexhaustive summary of relevant aspects of the standard terms and conditions of Weeding
Technologies Ltd (“WTL”) and is subject to those terms and
conditions and to any special terms and conditions agreed between the parties. Where this summary and WTL’s standard terms and conditions conflict, those terms and conditions take precedence (and any special terms and
conditions take precedence both over WTL’s standard terms
and conditions and over this document). You are advised to read the full terms and conditions including so as to take note of further exclusions of liability.
(b) In no case (without express written agreement, and save as required by law) does WTL accept any liability towards any person other than the person (“you”) who originally made the purchase from WTL or in respect of any alleged defect not notified by you to WTL within 12 months from delivery.
You are notified that the standard warranty period given by the manufacturer is 12 months from delivery.
(c) You must inspect all goods thoroughly with 7 days of delivery. Subject to the rules set out in section 3 below, any claim must be notified to WTL within 7 days of delivery or (subject to clause (b) above) in the case of any defect which is not reasonably apparent on inspection then within seven days of the defect coming to your attention (or of the date when the defect reasonably should have been apparent to you, if earlier).
(d) Subject to section 3 below, WTL will have no liability if you do not comply with the above.
(e) WTL’s options, in cases where it is liable, include
repairing or replacing defective goods and allowing you credit for them. If WTL exercises such an option it has no further liability. In any event, the liability of WTL is limited to parts, freight and a limited amount of labour as set out in
WTL’s standard terms and conditions. Labour in excess of
such limits will be at your cost in any event.
(f) You must, if so requested in writing by WTL, at your risk promptly return any goods the subject of any claim and any packing materials securely packed and carriage paid to WTL for examination. (If the claim is substantiated, WTL will normally reimburse these costs)
(g) If any repairs, modifications, or adjustments are carried out upon goods other than by WTL or personnel that hold a valid training certificate or are an authorised sub-contractor then WTL will have no liability in respect of those goods.
(h) WTL does not accept any liability to you for any loss or damage of any nature except as expressly stated in the standard terms and conditions (or in such terms and conditions as may be specially agreed between you and WTL). This means among other things that WTL has no liability for consequential losses, property damage, penalties, liquidated, exemplary or aggravated damages, downtime, loss of goodwill, capital costs or any pure economic loss.
(i) Subject to section 3 below, WTL does not accept any liability for defects resulting from wear and tear, accident, improper use or use except in accordance with the
Page 38
38
instructions or advice of WTL or authorised dealer or neglect or from any instructions or materials provided by you. Please note that this means WTL cannot accept liability in the event of use of unauthorised foam concentrate or alteration in factory foam additive dosage settings. Please note that it is not to be inferred or implied from the fact that WTL may supply you with any technical means of altering the settings for the use of the goods that you have any contractual or other legal protection in the event that you do so - any alterations to the settings for the use of the Units if not made in accordance with WTL's or the manufacturer's express written instructions are made at your own risk.
Page 39
39
17 Product certification
M600 is CE certified. Certification is available upon request.
Sound Pressure Level: 69dB(A)
Guaranteed Sound Power Level: 77dB(A)
Measurement Uncertainty K: ±0.4dB(A)
Some specific versions of M600 are CSA and UL certified. Documents and specification are available upon request.
Weeding Technologies Ltd
Unit 2, Westpoint Trading Estate, Alliance Road,
London W3 0RA
EMAIL: info@weedingtech.com
Loading...