weedingtech FoamStream M1200 User Manual

Page 1
USER MANUAL
ENGLISH (EU) – 01/03/2018 – ISSUE 2
Page 2
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
Page 3
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
3
TABLE OF CONTENTS
1. INTRODUCTION ____________________ 4
2. IMPORTANT INFORMATION ___________ 4
3. PRODUCT DESCRIPTION _____________ 5
4. FOAMSTREAM® ___________________ 11
4.1 HOW FOAMSTREAM® KILLS WEEDS ______________________ 11
4.2 INDICATORS ____________________________________________ 11
4.3 CAUTION – POISONOUS WEEDS ____________________________ 12
4.4 THE EFFECT OF THE SYSTEM ON PLANTS _____________________ 12
5. PRE-START CHECKS ________________ 14
6. START PROCEDURE ________________ 15
7. SCREEN AND PLC NAVIGATION _______ 18
8. USING THE M1200 _________________ 19
9. FOAMSTREAM® APPLICATION (KILLING
WEEDS) ____________________________ 21
9.1 HOSE REEL _____________________________________________ 21
9.2 SPEED _________________________________________________ 21
9.3 USE OF THE LANCE _______________________________________ 21
9.4 TREATMENT OF THICK WEEDS ______________________________ 22
9.5 TREATMENT _____________________________________________ 22
9.6 CONFIRMATION OF TREATMENT ____________________________ 22
9.7 CORRECT POSTURE_______________________________________ 22
10. SHUT-DOWN PROCEDURE _________ 23
11. BASIC FAULT FINDING ___________ 24
12. SERVICE CHECKS AND INTERVALS _ 29
13. LOADING AND HANDLING ________ 30
14. SCHEMATICS ___________________ 31
15. WARRANTY ____________________ 34
16. PRODUCT CERTIFICATION ________ 36
Page 4
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
4
1. Introduction
Thank you for purchasing the Weedingtech M1200!
IT IS IMPORTANT THAT ALL OPERATORS READ AND
UNDERSTAND THESE INSTRUCTIONS BEFORE USING
THE MACHINE
Having read these instructions, the operator will:
• Understand how the M1200 works
• Identify key components in the M1200
• Know how to carry out pre-start and start-up
procedures
• Observe safe operating practices
• Be able to effectively operate the M1200
• Be able to shut down and clean the M1200
• Be able to perform basic maintenance and
troubleshooting tasks
PLEASE KEEP THESE INSTRUCTIONS IN A SAFE PLACE
FOR FUTURE REFERENCE
2. Important information
The following PPE (Personal Protective Equipment) are recommended when operating the M1200:
• Eye protection is required when handling
Foamstream® concentrate
• Gloves are required as the lance assembly will get hot
• Safety Footwear suitable for working in the areas
concerned is recommended
• No specific protective clothing is required, although
use of overalls and a HI-Viz vest is suggested as best practice.
IT IS THE RESPONSIBILITY OF THE OPERATOR TO WEAR
APPROPRIATE PPE
Never operate the machine without checking that there are adequate supplies of clean diesel, clean water and clean Foamstream® concentrate in the appropriate tanks.
The M1200 produces VERY HOT water. This can cause serious burns and injury if used incorrectly.
Never point the lance at people or animals as this machine operates at high temperature and low pressure.
All personnel operating a M1200 machine must be deemed competent to do so and must be adequately trained. A copy of the training record is available on demand.
Always check the M1200 for any damage before use. Damaged cables, hoses or connections must be reported immediately, and the machine taken out of use until repairs have been completed.
Use only genuine Weedingtech spare parts and Foamstream® consumables. This will ensure the best performance of your machine and maintain the warranty of the unit.
The M1200 must never be modified, safety interlocks bypassed or settings adjusted (unless specified in these guidance notes) without Weedingtech’s written consent.
Ensure that the M1200 is placed in an area where there is adequate ventilation when in use.
Page 5
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
5
Ensure that the consumable liquid (foam concentrate) is not subject to temperatures below 5 degrees centigrade at any time.
Ensure that both the M1200 and its water tank are securely attached to the transport vehicle. It is the responsibility of the vehicle driver to ensure that any load is secure and that any payload restrictions are observed you can refer to section 13 for more information on transport.
NEVER OPERATE THE M1200 WITHOUT FOAMSTREAM®
CONCENTRATE
3. Product description
The M1200 weed control unit consists of:
• Foamstream®
• Water tank (780 litres)
• Hose reel (30 metres)
• Lance
The M1200 houses a diesel-powered boiler, a diesel­powered generator, a logic controller (PLC), a piston pump, a 52 litres diesel tank, and a 22 litres Foamstream® concentrate tank.
When the water reaches 95 degrees centigrade, a valve opens allowing water to flow from the lance (12 lpm @ 12 bar) and a venturi mixer opens to allow Foamstream® concentrate to be injected at a ratio of 99.5 parts water to
0.5 parts concentrate. Air is added to the water and Foamstream® mix as it exits the lance to create the foam.
Figure 1 - M1200 (operator not included)
When the machine is switched on and operational, water is pumped at 12 litres per minute and passes through the boiler to be heated up to a minimum of 95 degrees centigrade.
The M1200 has been designed to require no manual input or adjustment. The PLC monitors the system pressure, temperature and flow rate to ensure optimum performance of the unit.
A pressure relief valve and over-temperature sensor ensure that internal pressure and temperature will not exceed 35 bar or 120 degrees centigrade in the event of a system fault.
Operation of the M1200 is via the user interface at the front of the unit (see section 6 for details).
Page 6
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
6
Filters are fitted to the diesel, water and foam systems to ensure supplies are kept clean and free from debris. These needs to be checked daily (see section 5).
Access panels to the right and left-hand side of the M1200 can be opened with a key to allow access to filters, pipes and hydraulic components. These panels can be easily removed for maintenance purposes. Access to the electronics is via a door on the front of the M1200 which can be opened by a key.
The water tank (780 litres) can be either separate from the unit or attached to it by bolts on the frame. There are two hydraulic connections (water supply, water return), one electrical connection (water sensor) and 13 bolts when the tank is attached to the unit.
An automatic hose reel is located inside the unit to allow the 30 metres hose to be stowed safely when the M1200 is not in use. The hose comes off the top of the reel and is connected to the lance via a connector.
M1200
HEIGHT (mm)
1200
WIDTH (mm)
1206
DEPTH (mm)
1250 or 2120 (with tank)
WEIGHT (kg)
326 EMPTY, 400 FULL
WATER
780 LITRES
FUEL
DIESEL – 52 LITRES
FOAMSTREAM
FOAMSTREAM – 22 LITRES
GENERATOR OIL
1.2 LITRES SAE 5W40
PUMP OIL
0.3 LITRES SAE 5W40
FLOW RATE
12 LITRES PER MINUTE
OPERATING PRESSURE
30 BAR ON HEAT UP, 12 BAR
TRIGGER OPEN
OPERATING TEMPERATURE
95 – 110 °C
PRESSURE RELIEF VALVE
35 BAR
OVER TEMPERATURE CUT-OUT
125 °C
GENERATOR
4.5 kVA – DIESEL POWERED
BOILER
95 kWh – DIESEL POWERED
Page 7
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
Figure 2 – Perspective view of the M1200
Num.
Description
1
Control panel
2
Lance
3
Water tank
4
Exhaust hood
5
Hose reel orifice
6
Forks entry
7
Left cover panel
8
Right cover panel
9
Traffic lights
10
Hot air extraction fan
Page 8
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
8
Figure 3 - Left inside view of the M1200
Num.
Description
1
Diesel particulates filter (Optional extra)
2
Water pump
3
Diesel generator vent (CAUTION HOT)
4
Diesel generator (CAUTION HOT)
1 2
3
4
Page 9
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
9
Figure 4 - Right view of the inside of the M1200
um.
Description
1
Lance solenoid valve
2
Pressure gauge
3
Main flow switch
4
Return to tank flow switch
5
Pressure relief valve (PRV)
6
Lance pressure switch
7
Venturi
8
Foam filter
9
Foam tank
10
Diesel tank
11
Boiler diesel filter
12
Water filter
Page 10
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
10
Figure 5 - Closed control box (left) open (right)
Figure 6 – Detail of the switches on the front panel
Num.
Description
1
Emergency stop
2
Main contact switch
3
Boiler reset button
4
Power light
5
Diesel generator start key
6
PLC screen (touch screen)
Page 11
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
4. FOAMSTREAM®
4.1 How FOAMSTREAM® kills weeds
Foamstream® uses heat to kill weeds. Water is heated to near boiling point and then mixed with the Foamstream® concentrate to produce foam before being applied. The foam blanket ensures that the heat is held on the plant so that the weeds experience hot, killing temperatures for a few seconds. Figure 10 below explains and compares the process to hot water and steam.
4.2 Indicators
The lances can apply large volumes of water and foam and can be used to kill larger weeds. Foam cover, and hence heat retention on weeds, is easier to achieve on prostrate plants that are near the ground. Tall plants should be trodden down either by foot or by using the lance outlet, to aid foam cover and heat retention.
Figure 7 - Foamstream during treatment
Immediately after treatment, weeds will go dark green and limp. This indicates that the machine is operating properly. The weeds will die; this becomes more obvious within the next one to seven days (depending on species and weather). If weeds fail to go limp, temperatures may be too low or forward speed to high.
Figure 8 - Weed immediately after treatment with Foamstream
Figure 9 - Weed 24 hours after treatment with Foamstream
Page 12
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
12
If weeds go brown immediately after treatment, this could indicate that forward speed is too slow and excessive heat is being applied.
Figure 10 - Foamstream's triple action
Steam / Hot Water
Kills the leaves
Kills weeds
No effects on seeds
Sterilises seeds
Very weak effect on roots
Damages the root
In general, annual weeds are easier to kill than biennial or perennial ones. Weed species that originate from desert or semi-arid regions are more heat tolerant and will need a slightly prolonged treatment period compared to other species.
Biennial or perennial weeds usually have parts protected against heat (especially regenerative parts under the soil, the Rhizome). Foamstream is a contact application, it will kill foliage but many perennial and biennial plants will regenerate. The number of repeat treatments required to completely kill weeds depends on the species and their size.
4.3 Caution – poisonous weeds
Some poisonous weeds, such as common ragweed (Senecio jacobaea) may still be attractive to animals after treatment with Foamstream. When treating any area where animals are likely to graze after treatment with Foamstream, check for the presence of such potentially toxic weeds and remove them or keep out of reach of animals that are at risk.
4.4 The effect of the system on plants
The M1200 has been designed to operate in an urban environment and control weed growth on both hard surfaces and cultivated land. These weeds may be in, at, or around kerbs and channels, footpath edges, driveways, boundaries, obstacles etc.
Within these environments there are various plant species that need to be controlled. These species may vary in type and growth patterns depending on the specific geographic location.
The system, through its unique operation, delivers a plant kill based on thermal activity penetrating and breaking down the cell structure of the plant.
With varying plants in the target area it is important for the operator have some knowledge of the weed types, sizes and
Page 13
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
13
ages that they are treating, as this impacts on the speed of operation to deliver an effective kill.
For maximum efficacy, it is important that all weeds in the target area are in contact with the hot foam. Either flatten tall weeds i.e. by treading or use of the lance or ensure that
the stems are ‘ring barked’ (completely surrounded by a
blanket of foam). The density of the plants and foliage is a very important aspect for the operator to be aware of, as this also impacts on the speed of operation. It should be noted:
• As the height and/or density of the target plants
increases, the speed of operation will be slower.
• In a situation where regular treatment of the area is
part of a maintenance programme the weeds will generally be easier to treat as regrowth should be reduced.
• Regular treatment also allows increased speed of
operation, as the volume of target plants to kill will be minimised on each maintenance cycle.
Page 14
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
14
5. Pre-start checks
THESE CHECKS MUST BE COMPLETED BEFORE EACH
START OF THE M1200. ANY FAULTS MUST BE RECTIFIED
BEFORE THE M1200 IS SWITCHED ON.
✓ The M1200 water tank is securely attached to the
transport vehicle
✓ The M1200 is in good condition and panels are
closed
✓ There are no signs of leaks from any pipe or
connection
✓ Pipe routes are clear of sharp edges and hot
surfaces
✓ Air intakes are clear of debris ✓ Generator and boiler exhaust are secure and clear of
debris and obstruction
✓ Water tank is full of clean water ✓ Water filter is clean and free from debris ✓ Water feed valve is connected and in the ‘on’ (inline)
position
✓ The water return pipe and water level sensor is
connected
✓ Air has been bled from water system (see section 7) ✓ Fuel tank is full of clean diesel fuel (derv or gasoil) ✓ Boiler fuel filter is clean and free from debris ✓ Foamstream® concentrate tank is full of
Foamstream® concentrate
✓ Foamstream® filter is clean and free from debris ✓ The consumable has not been subject to
temperatures below 5°C and frozen or separated
✓ Vent screw on Foamstream® tank filler cap is open ✓ Generator engine oil level is correct
✓ Pump oil level is correct ✓ The lance, hose reel and hose are securely
connected and free from damage
✓ Lance wear pads are not excessively worn
Page 15
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
15
6. Start procedure
✓ Complete pre-start checks (see section 5) ✓ Start the generator by turning the key in a clockwise
direction to position ‘B’, release to position ‘A’ when the engine starts (see Figure 11)
✓ Turn the isolator switch to position ‘B’ (see Figure 11), the
PLC screen should illuminate (see Figure 12)
Figure 11 - Details of the switches of the front panel
✓ The reset indicator (red light) lights up and ‘FAULT’ will
appear on the top right hand corner of the PLC screen
✓ Press the ‘RESET’ button (red button on the front panel,
see Figure 5), the ‘FAULT’ indicator goes out and you should see the screen represented in Figure 12
✓ Wait a few seconds before requesting air bleed: buttons
‘1’ or ‘2’ in Figure 12
If you have disconnected the water tank or are starting
for the first time of the day, please use “Air bleed full”
If you just took a break or want to perform an additional
air bleed, please select “Air bleed partial”
When bleeding the machine, the trigger must be
pushed to allow water to flow out of the lance. Failure to
do so will cause the machine to display a fault message.
✓ Once button ‘1’ or ‘2’ is pressed the bleed screen
represented in Figure 13 will appear.
✓ Wait until the purge is completed. A new screen will
appear, represented in Figure 14.
✓ Press ‘START’, the button turns green and the screen
represented on Figure 15 will appear.
✓ The amber ‘HEATER’ light will illuminate and the red
‘FAULT’ button should go out. This indicates that the
boiler has switched on and is heating the water
✓ The green ‘READY’ light will illuminate when the M1200
has reached operating temperature and the system is ready for use (3 – 5 minutes).
AFTER A COLD NIGHT (BELOW 0 DEGREES CELSIUS),
LET THE GENERATOR RUN FOR 15 MINUTES TO WARM
UP THE MACHINE BEFORE STARTING THE PUMP OR
BLEEDING THE UNIT
Page 16
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
16
Figure 12 - Start-up screen of the PLC
Num.
Description
1
Press this button to purge the M1200 for 30 seconds.
2
Press this button to purge the M1200 for 10 seconds.
3
Indication message.
4
Air bleed status indicator.
5
Menu access
Figure 13 - Bleed screen of the PLC
Figure 14 - Start screen of the PLC
Num.
Description
1
Start button
2
Boiler water input temperature
3
Boiler water output temperature
4
Indication message
5
Menu access
1
2
3
4
5
1
2 3
4
5
Page 17
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
17
Figure 15 - Running screen of the PLC
Page 18
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
18
7. Screen and PLC navigation
When the M1200 is ready to start, the screen below will appear (same as Figure 14)
To access the menu, click on the “Menu” button on the top
right hand side of the screen. The screen in will appear.
Figure 16 - Menu screen
Num.
Description
1
Return to main page
2
Go to summary screen
3
Purge
4
Language selection
5
Fault summary panel
6
Maintenance mode
Users have no need to access pages ‘5’ and ‘6’. Page ‘6’ is
restricted by a password. The screens are summarized in the table below (in the same order as is Figure 16)
1
2 3
4
5
1 2
3
4 5
6
Page 19
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
19
8. Using the M1200
The generator manufacturer does not recommend to use the generator below 6 degrees Celsius and above 40 degrees Celsius of ambient temperatures.
The M1200 control panel gives important feedback on the status of the M1200:
Status
Red
Orange
Green
Ready
Fixed
Fixed
Stand-by
Fixed
Flashing
Boiler active
Fixed
Boiler fault
Fixed
Water tank too hot
Flashing
Level sensor low
Flashing
Boiler overtemp.
Fixed
Flashing
WHITE ‘POWER’ LIGHT
When the generator is on, this light should be illuminated. If the generator does not start, then the generator plug should be checked. If the generator breaker position is correct and the generator does not start the M1200 should be checked by a competent service engineer.
AMBER ‘HEATER’ LIGHT
If the amber light is illuminated the water is below 96 degrees centigrade and is being heated. If the amber light
does not illuminate, and the red fault light stays on, there may be a system fault (see below)
GREEN ‘READY’ LIGHT
When this light is illuminated the M1200 is ready for use. If the green light is not illuminated the water may need heating (amber light will be on) or there is a system fault (red fault light will be on, see below).
FLASHING ORANGE LIGHT
If the amber light is flashing the water in the water tank is too hot. If water in the water tank exceeds 45°C the boiler will shut down. The water tank will need to be drained and refilled with cold water, or the level topped up with cold water.
RED ‘RESET’ LIGHT
The red reset light should switch off when the reset button is pressed during start up. If the light stays on there is an electrical fault which needs rectification. The M1200 should be switched off until the fault has been corrected.
FLASHING RED ‘RESET’ LIGHT
A flashing red reset light indicates a boiler fault. The M1200 must be switched off and checked by a competent service engineer.
RED ‘FAULT’ LIGHT
The red fault light will illuminate at start up until the green button is pressed and the amber light illuminates. If the red light stays on, and the amber light fails to illuminate, the system may need to be bled to remove air (see section 7).
Page 20
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
20
If the red light fails to switch off after bleeding there is a system fault. The M1200 should be switched off until the fault has been corrected by a competent service engineer.
RED ‘FAULT’ AND FLASHING AMBER LIGHT
An illuminated red fault light and flashing amber light indicates the boiler is too hot. The M1200 should be switched off and checked by a competent service engineer.
GREEN AND AMBER WITH FLASHING RED ‘FAULT’ LIGHT
A flashing red fault light with illuminated green and amber lights indicates one of the fluid levels is low (water, Foamstream® or diesel). The levels should be checked and filled up accordingly.
THE M1200 SHOULD BE SWITCHED OFF AND CHECKED
BY A COMPETENT SERVICE ENGINEER IF IT DOES NOT
OPERATE AS EXPECTED, OR THE LIGHTS ILLUMINATE IN
A DIFFERENT WAY THAN EXPLAINED.
Page 21
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
21
9. FOAMSTREAM® application (killing
weeds)
To effectively control vegetation with the herbicide-free Foamstream® system, you must co-ordinate all the different elements that give a successful result. If one element is not functioning properly, the desired result will not be achieved.
For effective results the Foamstream® system requires the:
• Correct volume
• Correct temperature
• Correct method
• Correct quantity of foam agent
This section looks at the speed and method of application.
9.1 Hose reel
The M1200 unit is fitted with an automatic hose reel which contains 30 m of hose as standard. The hose comes off the top of the reel, and is connected to the lance by a swivelling connection covered by an insulating sleeve.
Only remove as much hose as is required.
Once finished, rewind the hose onto the reel neatly.
9.2 Speed
Operators will average approximately 2 - 4 kilometres per hour, when proficient at applying the Foamstream® with the M1200. Foamstream® and the M1200 are unaffected by weather, thus ensuring overall productivity each week is similar.
DO NOT HURRY!
If the operator moves too quickly over the vegetation, the required volume of hot water and foam may not have penetrated or been applied correctly. Total vegetation control will not have been achieved.
9.3 Use of the lance
To kill weeds effectively, the lance head must be no more than 25 mm above the ground at all times. If possible, keep the lance head in contact with the ground. While every element of the treatment is important, the most critical aspect is to ensure the lance head is not lifted from the targeted area.
Control of vegetation for up to 90 days will only be achieved if the temperature measured at the lance head does not fall below 96oC. If the lance head is more than 30mm above the ground, a less than acceptable result may be achieved due to the rapid temperature loss.
It is recommended the operator keeps the trigger open if possible. This maintains constant flow of hot water and foam and ensures that they are leaving the lance at the correct temperature.
If the trigger is released for more than 30 seconds, the operator will have to wait until the water and foam mixture is replaced, this normally takes up to 45 seconds. When moving the lance head from one treatment zone to another, turn off trigger and ensure the hot water and foam is not applied to sensitive plant areas.
Page 22
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
22
If there is a reduction in foam produced from the lance head, you will not achieve the desired kill. You can check this by lifting the lance and observing the water flow.
9.4 Treatment of thick weeds
The Foamstream system works by penetration of heat into plant cells. In cases of dense growth and dense swards of grass (especially species such as kikuyu) progress will be slower as a greater volume of liquid (thermal energy) is required to ensure a result.
The Foamstream system is designed to control vegetation up to 200 mm high in optimum conditions.
9.5 Treatment
The 'treatment zone' will be stated in the job specification. The operator must kill the total area of the plant in the treatment zone including any parts that hang over onto the sealed area.
9.6 Confirmation of treatment
With practice, operators will become familiar with determining whether weeds have been treated correctly.
Broad leaf weeds will go floppy and wilt (similar to boiled cabbage). In most cases these will go darker in colour.
Grasses: usually, grasses immediately lighten in colour and flatten to the ground. This can be difficult to observe when using hot foam.
Moss will go bright green.
In all cases, a distinctive smell (similar to cooking spinach) also assists to confirm a result.
VISUAL CONFIRMATION THAT THE TREATMENT HAS BEEN
SUCCESSFUL IS ESSENTIAL.
9.7 Correct posture
When using the equipment for several hours per day it is important that operators adopt the correct posture and technique.
Remember it is the heat that controls the vegetation.
When treating straight stretches of roads or parks, use just the trigger hand to guide the lance. This keeps your back upright and not twisted and you are not encouraged to push down with the other hand.
Only use the other hand when changing direction or raising the lance.
When walking, swap trigger hands every so often to rest the muscles.
Page 23
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
23
10. Shut-down procedure
Upon completion of work, or when taking a break, the unit must be shut down correctly:
• Press the red stop button pictured on Figure 17. All
lights will extinguish apart from the white ‘power’ light and the red fault light. The red fault light will remain on until the water temperature in the M1200 drops to a safe level and the pump stops.
• Wait until the red fault light switches off
• Turn the isolator switch to ‘A’.
• Turn the generator key switch to ‘A’.
DO NOT USE THE EMERGENCY STOP TO STOP THE
MACHINE OTHER THAN IN AN EMERGENCY.
The emergency stop should only be used in an ‘emergency’ for example:
• Water temperature exceeds 120 degrees centigrade
• Steam emits from the lance
• A significant leak occurs
IF THE EMERGENCY STOP HAS BEEN USED THE M1200
SHOULD BE CHECKED BY A COMPETENT SERVICE
ENGINEER, AND ANY FAULTS RECTIFIED BEFORE THE
M1200 IS SWITCHED BACK ON AGAIN.
Figure 17 – Stop button showing on the PLC
Page 24
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
24
11. Basic fault finding
The PLC of the M1200 is designed to help the user in case something goes wrong.
Figure 18 – Summary screen of the PLC
Num.
Description
1
Boiler incoming water temperature
2
Boiler outgoing water temperature
3
Foamstream tank level sensor
4
Water tank level sensor
5
Diesel level sensor
6
Boiler controller
7
Water pump
8
Venturi
9
Lance solenoid valve
10
Lance flow switch
11
Lance pressure switch
12
Boiler diesel pump
13
Return to tank flow switch
Green colour indicates that the sensor is seeing a signal and grey or red that it doesn’t. Red colour does not necessarily mean that there is an issue with the sensor. Normal sensor states during start-up/shut-down and normal operation are described in the table below.
Num.
Start-up
Running
1
Not applicable
2
Not applicable
3
Green
Green
4
Green
Green
5
Green
Green 6 Should be visible
7
Green
Green
8
Grey
Green
9
Grey
Green
10
Green
Green
11
Grey
Green
12
Green
Green
13
Green
Grey
When a fault occurs, a fault message will be displayed in the box no4 of Figure 14. Below are the faults that can appear in that screen and what they mean.
1
2
3
4
5
6
7
8
9
10
11
12
13
Page 25
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
25
Sentence
Colour
Explanation
Machine running
Green
Machine is running and producing foam
Clear fault
Red
Press the red button on front panel to clear the fault
Outlet temp. too high
Red
The temperature at boiler outlet is too high. Clean the water filter and check for leaks. If the problem persists, please contact your WTL distributor
Inlet temp. too high
Red
The temperature in the main water tank is too high (more than 45C) and the machine has stopped. Let the water cool down in the tank or top it up with cooler water.
Low level in foam tank
Yellow
The foam level is low, the machine will keep running 2 minutes and will then stop. Please top up.
Low level in water tank
Yellow
Same as above
Low level in diesel tank
Yellow
Same as above
Outlet pressure too low
Red
The lance valve is open and the flow is ok but there is no signal from the pressure switch. Please control the pressure on the pressure gauge of the side panel. If the pressure is below 5 bars this means you have no lance or a large leak before the lance. If the pressure is above 5 bars you might have an issue with the pressure switch and need to change it
Boiler fault, press "Reset"
Red
Press "Reset". If the boiler does not start, stop the machine and restart it. If the problem persists, please call a Weedingtech distributor.
Boiler could not start
Red
20s after the start-up signal is given, the boiler is not started. Press "Reset" and try again. If the boiler does not start, stop the machine and restart it. Check on the
summary screen that “stage 1” and “stage 2” are in
green, if not check that the plugs have not fallen out of the boiler. If that is not the case and the problem persists, please call a Weedingtech distributor.
Page 26
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
26
Boiler not ready
Red
The boiler fan is running but the boiler is not running as the ‘ready’ signal from controller was not received.
Push on the ‘reset’ button
for 5 seconds and try again. If the problem persists, please call your Weedingtech distributor.
Emergency stop activated
Red
The emergency stop button is activated, release it and press "reset".
No flow at outlet
Red
The pump is running but no flow is detected. Please check the hydraulic panel for leaks. If no leaks are found, the flow switch might be faulty.
No flow at bypass
Red
The pump is running and the water heating up but no flow is detected in the return to tank line. Please check the hydraulic panel for leaks. If no leaks are found, the flow switch might be faulty.
Press "Air bleed"
Green
Press "Air bleed"
Machine ready, press "Start"
Green
Press "Start"
Boiler starting up
Yellow
Nothing
Water & Boiler pre-heating
Yellow
The boiler is warming up the water to reach 95° and will then open the lance
valve. You have nothing to do.
Air bleeding in progress
Green
Wait until the bleeding is complete
Pressure sensor fault
Red
The pump is not running but the pressure sensor sends a signal. The pressure sensor is faulty and needs to be changed
Outlet flow sensor fault
Red
The pump is not running but the flow sensor sends a signal. The flowswitch needs to be changed
Inlet flow sensor fault
Red
The pump is not running but the flow sensor send a signal. The flowswitch needs to be changed
Boiler controller fault
Red
The boiler is not running but ready signal from controller is received. Please contact a Weedingtech distributor
Water pump speed inverter fault
Red
Fault signal from speed inverter. Please stop and start the machine. If the problem persists you will need to contact a Weedingtech distributor to open the electrical box and reset the inverter.
Release trigger
Yellow
Release the trigger.
Page 27
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
27
Manual bleeding required
Red
You need to bleed the air from the unit manually by unscrewing the blue tap on top of the water filter to let air go out.
The table below explains what to do to solve an issue when the sentence above appears on the screen.
The table below lists other basic faults which can be diagnosed and rectified by a competent M1200 operator. Please refer to the training documentation provided during training.
BEFORE BEGINNING ANY WORK ENSURE THE
WEEDINGTECH M1200 HAS BEEN SWITCHED OFF, AND
THE ELECTRICAL SUPPLY FROM THE GENERATOR IS
DISCONNECTED. WARNING: WATER IN THE M1200 MAY
BY HOT.
THE M1200 SHOULD BE SWITCHED OFF AND
CHECKED BY A COMPETENT SERVICE ENGINEER IF THE
OPERATOR IS UNABLE TO DIAGNOSE AND RECTIFY A
FAULT USING THE TABLE BELOW, OR IF A FAULT
PERSISTS.
SYMPTOM
CAUSE
REMEDY
Generator will not start (no lights)
Battery is flat
Charge battery
No fuel in tank
Refill tank and bleed fuel system
Air in the fuel pipe
Prime fuel using the in-line hand pump
The PLC will not illuminate
Generator is not started
Start generator
Main switch is
still on ‘OFF’
position
Turn main switch on ‘ON’ position
Boiler will not fire up. (pump runs, red fault light on)
Air in water feed line
Stop the machine and bleed water once again
Water filter blocked
Clean and replace filter
Hot water in tank
Drain tank and refill with cold water
Boiler control box safety switch activated
Press reset button on boiler control box
Boiler switched off at boiler control box
Turn switch on boiler control box to ‘on’
Flow too low
Check water filter is clean
No water flows from lance Water temperature too low
Wait until water temperature reaches correct level
No water in the water tank
Refill water tank
Intermittent Flow (amber light on, intermittent green light)
Water temperature too low
Wait until water temperature reaches correct level
Page 28
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
28
Steam coming from lance
Temperature control system faulty
Switch off M1200 and call competent service engineer
Red light flashing
Water and/or Foam and/or Diesel level too low
Check water and/or Foamstream® and/or diesel levels and re fill as needed.
Red reset light on
Electrical fault
Press reset button on control panel
No foam coming out of the lance
No foam in the tank
Fill up tank with foam
Breathing screw of the foam tank too tight (air not getting through)
Loosen the breathing screw on top of the cap of the foam tank
Foam filters clogged
Clean foam filters using hot water or replace them
Dosage plate blocked
Clean dosage plate using warm water
Pressure too high (more than 18 bars)
Untighten pressure relief valve to reach 12 to 15 bars operating pressure
Foam is too cold and has separated
Drain foam from tank, clean pipes, filter and dosage plate holder, re­mix foam and refill tank.
Air coming in the foam system
Check the foam pipe for air contamination. Then tighten the faulty connection
Page 29
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
29
12. Service checks and intervals
Figure 19 – 50 hours before maintenance
Figure 20 – Maintenance due
The PLC screen will let you know 50 hours before the first major maintenance of the unit, as depicted on Figure 19. Once the maintenance is due, Figure 20 will show.
BEFORE BEGINNING ANY WORK ENSURE THE
WEEDINGTECH M1200 HAS BEEN SWITCHED OFF,
AND THE ELECTRICAL SUPPLY FROM THE
GENERATOR IS DISCONNECTED.
EVERY 250 HOURS (6 MONTHS MAXIMUM)
• Change generator oil
• Check boiler flue gas for CO content,
adjust air flap setting if required
• Check and de-scale coil (if necessary)
• Change particulates filter cartridge (if applicable)
EVERY 500 HOURS (12 MONTHS MAXIMUM)
• Change generator oil filter
• Change generator air filter
• Check and adjust and clean generator injectors
• Check and adjust and clean generator valve and
rocker head clearance
• Change fuel filter.
• Check and clean boiler mixing device.
Replace electrodes and nozzles if necessary
• Check and adjust boiler burner pressure regulator
setting
• Check and clean boiler burner chamber
• Check electrical control panel for moisture damage
• Check and adjust boiler pump oil pressure and level
• Change particulates filter cartridge (if applicable)
EVERY 750 HOURS (OR 18 MONTHS MAXIMUM)
• Change pump oil and filter cartridge (if applicable)
Page 30
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
30
13. Loading and handling
Before lifting the M1200 you should make sure that the water tank is not full of water. This could result in a serious damage to the machine if the tank is attached to the frame.
THE M1200 SHOULD NOT BE LIFTED WITH A FULL
TANK OF WATER
Before driving, the user should make sure that the unit and the water tank are appropriately strapped or bolted to the vehicle.
Figure 21 - Strapping of the M1200 to the vehicle
Page 31
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
14. Schematics
Figure 22 – Foam and water schematics
WATER TANK
WATER FILTER
WATER PUMP VENTURI
FOAM TANK
FOAM FILTER 1
FOAM FILTER 2
BOILER
PRESSURE
RELIEF VALVE
LANCE
Page 32
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
32
Figure 23 – Fuel schematics
DIESEL TANK
DIESEL FILTER
GENERATORHAND PUMP
LEVEL SENSOR
BOILER
Page 33
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
Figure 24 – Electrics schematics
KEY SWITCH
GENERATOR
ISOLATOR
CONTROL BOX
CONTROL
PANEL
BOILER
PUMP
LANCE VALVE
PRESSURE
SWITCH
TEMPERATURE
SENSOR INLET
TEMPERATURE
SENSOR OUTLET
LANCE FLOW
SWITCH
BYPASS FLOW
SWITCH
LEVEL SWITCH
FOAM
LEVEL SWITCH
WATER
LEVEL SWITCH
DIESEL
Page 34
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
15. Warranty
(a) The following is an inexhaustive summary of relevant aspects of the standard terms and conditions of Weeding
Technologies Ltd (“WTL”) and is subject to those terms and
conditions and to any special terms and conditions agreed
between the parties. Where this summary and WTL’s
standard terms and conditions conflict, those terms and conditions take precedence (and any special terms and
conditions take precedence both over WTL’s standard terms
and conditions and over this document). You are advised to read the full terms and conditions including so as to take note of further exclusions of liability.
(b) In no case (without express written agreement, and save as required by law) does WTL accept any liability towards any person other than the person (“you”) who originally made the purchase from WTL or in respect of any alleged defect not notified by you to WTL within 12 months from delivery.
You are notified that the standard warranty period given by the manufacturer is 12 months from delivery.
(c) You must inspect all goods thoroughly with 7 days of delivery. Subject to the rules set out in section 3 below, any claim must be notified to WTL within 7 days of delivery or (subject to clause (b) above) in the case of any defect which is not reasonably apparent on inspection then within seven days of the defect coming to your attention (or of the date when the defect reasonably should have been apparent to you, if earlier).
(d) Subject to section 3 below, WTL will have no liability if you do not comply with the above.
(e) WTL’s options, in cases where it is liable, include
repairing or replacing defective goods and allowing you credit for them. If WTL exercises such an option it has no further liability. In any event, the liability of WTL is limited to parts, freight and a limited amount of labour as set out in
WTL’s standard terms and conditions. Labour in excess of
such limits will be at your cost in any event.
(f) You must, if so requested in writing by WTL, at your risk promptly return any goods the subject of any claim and any packing materials securely packed and carriage paid to WTL for examination. (If the claim is substantiated, WTL will normally reimburse these costs)
(g) If any repairs, modifications, or adjustments are carried out upon goods other than by WTL or personnel that hold a valid training certificate or are an authorised sub-contractor then WTL will have no liability in respect of those goods.
(h) WTL does not accept any liability to you for any loss or damage of any nature except as expressly stated in the standard terms and conditions (or in such terms and conditions as may be specially agreed between you and WTL). This means among other things that WTL has no liability for consequential losses, property damage, penalties, liquidated, exemplary or aggravated damages, downtime, loss of goodwill, capital costs or any pure economic loss.
(i) Subject to section 3 below, WTL does not accept any liability for defects resulting from wear and tear, accident, improper use or use except in accordance with the
Page 35
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
35
instructions or advice of WTL or authorised dealer or neglect or from any instructions or materials provided by you. Please note that this means WTL cannot accept liability in the event of use of unauthorised foam concentrate or alteration in factory foam additive dosage settings. Please note that it is not to be inferred or implied from the fact that WTL may supply you with any technical means of altering the settings for the use of the goods that you have any contractual or other legal protection in the event that you do so - any alterations to the settings for the use of the Units if not made in accordance with WTL's or the manufacturer's express written instructions are made at your own risk.
Page 36
M1200 – User manual – English (EU) – 01/03/2018 - ISSUE 2
36
16. Product certification
M1200 is CE certified. Noise measurements and certification are available upon request.
Some specific versions of M1200 are CSA and UL certified. Documents and specification are available upon request.
Weeding Technologies Ltd
Unit 2, Westpoint Trading Estate, London W3 0RA
Loading...